You are on page 1of 14

http://eweb.chemeng.ed.ac.

uk/courses/con
trol/restricted/course/fourth/course/mo
dule3-1.html
Module 3.1: Control of Distillation
Columns
Introduction
The aim of this module is to introduce the control of distillation columns. We will start by
analysing the degrees of freedom to establish how many and which control parameters it
is possible to control and/or manipulate. Then we move on to discuss different ways to
control the two most important parameters: composition at the top of the column and the
pressure of the column. Finally there are a number of examples showing different control
structures.

Degrees of Freedom Analysis


We will use the method developed by Professor Ponton in his Paper
Degrees of Freedom Analysis in Process Control, Chemical Engineering Science, 1994,
Volume 49, No. 13, pp 2089 - 2095
to determine the number of control degrees of freedom in a distillation column. There are
two equivalent procedures based on the equation C.D.F. = Total No. of Streams - No. of Phases Present + 1
All we have to do is count all the streams in the process. Separately count the total
number of extra phases i.e. add up all occurrences of phases greater than one in all units.
The number of control degrees of freedom is the difference between these two numbers.
Figure 1 below shows this method.

Figure 1 - Degrees of Freedom Analysis of Distillation Column

Total Streams = 8
Extra Phases = -3
Degrees of Freedom = 5

So the number of degrees of freedom is 5. However, a typical control strategy for such a
process would use only 4 of these - feedrate, column pressure, top and bottom
composition. This is because the column and condenser are normally maintained at the
same pressure.
However, a valve could be placed in the line between. This would actually be undesirable
as reducing the condenser pressure will decrease the temperature driving force available
from the cooling medium.

Controlling Pressure in Distillation


In a distillation column it is usually necessary to regulate the pressure in some way.
Below there are five different methods described for doing this.
Vent to Atmosphere
Cooling Water

Flooded Condenser - 1
Flooded Condenser - 2
Partial Condenser

One thing to note is that in none of them is a valve simply placed on the vapour line. This
would lead to the use of a large expensive control valve. Instead the pressure is controlled
indirectly involving the use of the condenser and/or reflux drum.

Vent to Atmosphere
Figure 2 below shows the easiest way to control the pressure in a column operating at
atmospheric pressure.

Figure 2 - Vent to Atmosphere


In this case the cooling water flow stays constant and the reflux drum is vented to
atmosphere. Thus the reflux drum and hence the top of the column are at atmospheric
pressure. The advantage of this scheme is that it requires one less control valve. The
disadvantage is that the tops have to be subcooled so that a minimal amount of vapour is
lost through the vent. Hence more energy is required from the reboiler when the reflux is
added to the top of the column.

Cooling Water
Figure 3 shows the most common method for controlling the pressure - adjustment of the
cooling water flow.

Figure 3 - Cooling Water


In this case if the cooling water flow is increased then more vapour is condensed and the
vapour pressure is reduced (and vice versa).

Flooded Condenser - 1
Figure 4 shows the classic flooded condenser approach.

Figure 4 - Flooded Condenser - 1

Again in this setup, as with the first example, there is no valve on the cooling water.
Instead the valve is in the liquid line between the condenser and reflux drum.
If this valve is closed then the condensed vapour i.e. liquid will build up and flood the
condenser. This has the effect of reducing the heat exchange area, thus reducing the
amount of vapour being condensed and hence increasing the pressure.
The valve can then be opened, the liquid level will fall, increasing the heat exchange area
and hence decreasing the pressure.

Flooded Condenser - 2
Figure 5 shows an alternative arrangement for a flooded condenser.

Figure 5 - Flooded Condenser 2


The first thing to notice about this setup is that the reflux drum and condenser are at the
same level. The second important point is that the vapour line, on which there is the
control valve, is very small in comparison with the overhead line. If the valve is opened
there is a small escape of gas into the reflux drum. This pushes the liquid level down in
the drum and up in the condenser, flooding it and reducing the heat exchange area as in
the last example.
Therefore to increase the pressure the valve is opened and to decrease the pressure the
valve is closed.

Partial Condenser
The final example is the control of a partial condenser.

Figure 6 - Partial Condenser


The above scheme is used if the overhead product is required as a vapour.

Controlling Tops Composition in Distillation


As well as pressure, the other parameter most likely to be controlled is the composition of
the tops product. The reason is that the final product will most probably come from the
top of the column and it is important to know its composition. Again, as with pressure,
there are many different ways of controlling the tops composition. Three methods are
described below.
Reflux Rate
Reflux Ratio
Distillate Rate

Reflux Rate
In this first example the reflux rate is adjusted to control the composition of the tops
product.

Figure 7 - Reflux Rate


As the amount of reflux is changed so the temperature profile in the column changes and
hence the composition.

Reflux Ratio
The second example uses the reflux ratio as the control parameter.

Figure 8 - Reflux Ratio


When designing a distillation column it is usually the reflux ratio that is determined. This
can be kept constant throughout operation by using two flow indicators and a ratio
controller.

Distillate Rate
The third example is for high purity tops. It uses the distillate flowrate to control the
distillate composition.

Figure 9 - Distillate Rate


It can be shown that for a high purity column i.e. one with a large reflux, that the
composition of the distillate is sensitive to the distillate flow but insensitive to the reflux
rate. Therefore for a high purity column the control scheme outlined above is used. It
should be noted that tight control on the level in the reflux drum is required using the
reflux rate.

Distillation Column Control Examples


The following examples describe alternative control strategies of fairly standard form.
Pressure, Overheads Rate and Composition
Pressure, Bottoms Rate and Composition
Pressure, Bottoms Rate and Overhead Composition, With Partial Condenser
Pressure, Overhead Rate and Bottoms Composition
Pressure, Bottoms Rate, Overhead Rate and Composition
In all cases actual composition controllers are shown. These could of course be replaced
by inferential measurement from temperature, with or without cascade of a slower
analyser. Unless otherwise stated, it has been assumed that the feed rate to the system is
not available as a manipulated variable.

Pressure, Overheads Rate and Composition


This is a fairly standard configuration for a single product column, i.e. when the bottoms
streams is a byproduct, recycle or goes to further processing.

Although the overheads composition is regulated by adjusting the steam rate at the base
of the column, the response of the column to heat input changes is quite rapid, and so this
strategy is acceptable.
Pressure control on condenser cooling water is shown; of course any other pressure
control scheme would be acceptable.

Figure 10 - Overheads Rate and Composition

Pressure, Bottoms Rate and Composition


This is the analogous situation to the previous case, in the rather less usual circumstances
where a main product is withdrawn from the bottom of the column.
This does not work well, since either the bottom level, as here, or composition, has to be
regulated by adjusting the reflux rate. In either case the loop involves a long delay due to
the hydraulic lags on each tray.
It is probably marginally better to regulate composition by steam rate since this is a more
important quantity than level, although the two loops could be interchanged with the
steam adjusting the level, which is quite a good scheme, and the reflux manipulating the

bottoms composition, which is very poor. Fotunately this is an unusual requirement, as


main products normally come from the top of columns for other reasons.
A standard flooded condenser pressure control system is shown.

Figure 11 - Bottoms Rate and Composition

Pressure, Bottoms Rate and Overhead Composition,


With Partial Condenser
This is not a particularly common strategy, but the arrangements for a column with partial
condenser are typical. The pressure in such a system is almost always manipulated by a
valve on the vapour product line. There is no reflux drum, and reflux rate is often set
implicitly by adjusting the cooling load on the condenser.

Figure 12 - Bottoms Rate and Overhead Composition, With Partial Condenser

Pressure, Overhead Rate and Bottoms Composition


This scheme should work satidfactorily as all adjustments are made at the same end of
the column as the related measurements. The pressure control scheme is the so-called hot
gas bypass. Note that the layout of condenser and reflux drum shown is critical to the
operation of this method, which is actually a variation on the flooded condenser
approach. The bypass is a very small pipe which bleeds vapour into the reflux drum
where it does not immediately condense. The pressure in the system rises as the bypass
valve is opened.

Figure 13 - Overhead Rate and Bottoms Composition

Pressure, Bottoms Rate, Overhead Rate and


Composition
Since three regulated quantities are specified, the feed to the unit must be available as an
adjustment. Apart from this, the arrangements are similar to those of the first example.
Level control on the column base is not very satisfactory due to the lags between the feed
and the bottom of the column, but any other arrangement would be worse.

Figure 14 - Bottoms Rate, Overhead Rate and Composition

You might also like