You are on page 1of 5

Full Hydraulic Calculations Computer Printout Page No 1

Submitted by Engr Anwar Ul Karim, MBA, PMP


MIEB No M/34416

Project:
Address:
Number:
Area ref:
Hazard:
Authority:
Systems
Source:
Printout:

Tel: Fax:

Evince Garments Ltd


Mirpur. Dhaka
BI-EGL-01
Most Unfavourable
ordinary
NFPA 13 : 2013 - Installation of Sprinkler
845.6 l/min @ 4.352 bar
5-September-14

Project Data and Design Parameters


Project name
Area reference
Address / location
Project number
Installation number(s)
Drawing number(s)
Issue no / date
Designers reference
Project Data File
Hazard classification
Design authority
Insurance company
Specified density of discharge
Assumed maximum area of operation
Number of operating sprinkler heads
Maximum area covered per head
Highest head / nozzle above source
Number of pipes in system
Pressure loss equation used
Fluid
Pipe Data Table
Maximum fluid velocity
Volume of pipework and fittings
Elbows are welded for
Comment
Checked by & Date

:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:

Evince Garments Ltd


Most Unfavourable
Mirpur. Dhaka
BI-EGL-01
Pendent
BI-EGL-v-1.0
05.09.2014
9th floor
D:\HYDRAU~1\BENGAL~1\BI-EGL~1.FHC
ordinary
NFPA 13 : 2013 - Installation of Sprinkler Systems
--5.00 mm/min (l/min/m2)
148.80 m2
16
9.30 m2
37.68 m
69
from 25 to 150 mm
Hazen-Williams
Water
STD_PIPE.PDT
3.11 m/s in pipe 167 168
1.42 m3
65
mm and above
---

Source duty = 845.6 l/min @ 4.352 bar at node no 100

FHC - Hydraulic Analysis Software - Ver: 1.8.0

Program FHC

Full Hydraulic Calculations Computer Printout Page No 2


Submitted by Engr Anwar Ul Karim, MBA, PMP
MIEB No M/34416

Tel: Fax:

Project:
Address:
Number:
Area ref:
Hazard:
Authority:
Systems
Source:
Printout:

Evince Garments Ltd


Mirpur. Dhaka
BI-EGL-01
Most Unfavourable
ordinary
NFPA 13 : 2013 - Installation of Sprinkler
845.6 l/min @ 4.352 bar
5-September-14

Operating Sprinkler Heads, Nozzles and Hydrants


Head|Node|
no | no |
31 149
32 150
33 151
34 152
35 154
36 155
37 157
38 158
39 160
40 161
41 163
42 164
43 165
44 166
45 168
46 169

Size | 'K' |F l o w|A


mm | factor| l/min |
15.0
80.00
58.0
15.0
80.00
56.2
15.0
80.00
49.4
15.0
80.00
47.4
15.0
80.00
53.5
15.0
80.00
51.4
15.0
80.00
53.5
15.0
80.00
51.4
15.0
80.00
53.5
15.0
80.00
51.4
15.0
80.00
58.0
15.0
80.00
56.1
15.0
80.00
49.3
15.0
80.00
47.3
15.0
80.00
55.8
15.0
80.00
53.6

r e a|Density mm/min|Pressure bar|Heights|Pipe


m2 |Req.d
Actual| Min
Actual|
m
| no
9.300
5.00
6.24
0.35
0.526 37.676
49
9.300
5.00
6.04
0.35
0.493 37.676
50
9.300
5.00
5.31
0.35
0.381 37.676
51
9.300
5.00
5.09
0.35
0.351 37.676
52
9.300
5.00
5.75
0.35
0.448 37.676
54
9.300
5.00
5.53
0.35
0.413 37.676
55
9.300
5.00
5.75
0.35
0.447 37.676
57
9.300
5.00
5.52
0.35
0.412 37.676
58
9.300
5.00
5.75
0.35
0.447 37.676
60
9.300
5.00
5.52
0.35
0.412 37.676
61
9.300
5.00
6.23
0.35
0.525 37.676
63
9.300
5.00
6.03
0.35
0.492 37.676
64
9.300
5.00
5.30
0.35
0.380 37.676
65
9.300
5.00
5.09
0.35
0.350 37.676
66
9.300
5.00
6.00
0.35
0.487 37.676
68
9.300
5.00
5.77
0.35
0.449 37.676
69

0 heads are under the required density / minimum pressures

FHC - Hydraulic Analysis Software - Ver: 1.8.0

Program FHC

Full Hydraulic Calculations Computer Printout Page No 3


Submitted by Engr Anwar Ul Karim, MBA, PMP
MIEB No M/34416

Tel: Fax:

Project:
Address:
Number:
Area ref:
Hazard:
Authority:
Systems
Source:
Printout:

Evince Garments Ltd


Mirpur. Dhaka
BI-EGL-01
Most Unfavourable
ordinary
NFPA 13 : 2013 - Installation of Sprinkler
845.6 l/min @ 4.352 bar
5-September-14

Hydraulically Significant Pipes in System


NUMBERS | P I P E | F L O W |DIMENSIONS|ANGLE| VALUES |HEIGHT M|PRESSURES BARS
Pipe|Start|Size
Type| L/min | Length VJ|Dir. | Eq.len | Start | Start
Frict
no | End |Bore
'C'| Vel m/s |EL T
VT|Slope| mbar/m |
End | End
Static
1 100 150mm
MW
845.6
0.600
Up
10.74
0.000
4.352 -0.005
101 155.32 120
0.7
0 0
MV 90.0
0.5
0.600
4.288 -0.059
2 101 150mm
MW
845.6
0.500
Up
3.67
0.600
4.288 -0.002
102 155.32 120
0.7
0 0
BV 90.0
0.5
1.100
4.238 -0.049
3 102 150mm
MW
845.6
2.000
90
7.70
1.100
4.238 -0.004
103 155.32 120
0.7
1 0
WE
0.0
0.5
1.100
4.234 +0.000
4 103 150mm
MW
845.6
36.576
Up
42.28
1.100
4.234 -0.020
104 155.32 120
0.7
1 0
WE 90.0
0.5
37.676
0.631 -3.583
5 104 150mm
MW
845.6
0.812
90
13.17
37.676
0.631 -0.006
105 155.32 120
0.7
1 0
ST
0.0
0.5
37.676
0.624 +0.000
6 105 150mm
MW
845.6
4.114
180
7.92
37.676
0.624 -0.004
106 155.32 120
0.7
1 0
GV
0.0
0.5
37.676
0.621 +0.000
7 106 150mm
MW
845.6
1.168
90
6.87
37.676
0.621 -0.003
107 155.32 120
0.7
1 0
WE
0.0
0.5
37.676
0.617 +0.000
10 107 150mm
MW
845.6
3.048
90
3.05
37.676
0.617 -0.001
110 155.32 120
0.7
0 0
0.0
0.5
37.676
0.616 +0.000
13 110 150mm
MW
845.6
0.558
90
0.56
37.676
0.616 -0.000
113 155.32 120
0.7
0 0
0.0
0.5
37.676
0.616 +0.000
16 113 150mm
MW
845.6
1.981
90
1.98
37.676
0.616 -0.001
116 155.32 120
0.7
0 0
0.0
0.5
37.676
0.615 +0.000
21 116 150mm
MW
845.6
1.041
90
1.04
37.676
0.615 -0.000
121 155.32 120
0.7
0 0
0.0
0.5
37.676
0.614 +0.000
24 121 150mm
MW
845.6
1.981
90
1.98
37.676
0.614 -0.001
124 155.32 120
0.7
0 0
0.0
0.5
37.676
0.613 +0.000
29 124 150mm
MW
845.6
1.041
90
1.04
37.676
0.613 -0.000
129 155.32 120
0.7
0 0
0.0
0.5
37.676
0.613 +0.000
32 129 150mm
MW
845.6
1.981
90
1.98
37.676
0.613 -0.001
132 155.32 120
0.7
0 0
0.0
0.5
37.676
0.612 +0.000
37 132 150mm
MW
845.6
1.041
90
1.04
37.676
0.612 -0.000
137 155.32 120
0.7
0 0
0.0
0.5
37.676
0.611 +0.000
40 137 150mm
MW
845.6
1.981
90
1.98
37.676
0.611 -0.001
140 155.32 120
0.7
0 0
0.0
0.5
37.676
0.610 +0.000
45 140 150mm
MW
845.6
1.041
90
1.04
37.676
0.610 -0.000
145 155.32 120
0.7
0 0
0.0
0.5
37.676
0.610 +0.000
48 145 150mm
MW
845.6
1.981
90
1.98
37.676
0.610 -0.001
148 155.32 120
0.7
0 0
0.0
0.5
37.676
0.609 +0.000
49 148
40mm
MW
210.9
1.092
0
3.81
37.676
0.609 -0.083
149
41.86 120
2.6
0 1
0.0
21.7
37.676
0.526 +0.000
Continued on the next page

FHC - Hydraulic Analysis Software - Ver: 1.8.0

Program FHC

Full Hydraulic Calculations Computer Printout Page No 4


Submitted by Engr Anwar Ul Karim, MBA, PMP
MIEB No M/34416

Tel: Fax:

Project:
Address:
Number:
Area ref:
Hazard:
Authority:
Systems
Source:
Printout:

Evince Garments Ltd


Mirpur. Dhaka
BI-EGL-01
Most Unfavourable
ordinary
NFPA 13 : 2013 - Installation of Sprinkler
845.6 l/min @ 4.352 bar
5-September-14

Hydraulically Significant Pipes in System


NUMBERS | P I P E | F L O W |DIMENSIONS|ANGLE| VALUES |HEIGHT M|PRESSURES BARS
Pipe|Start|Size
Type| L/min | Length VJ|Dir. | Eq.len | Start | Start
Frict
no | End |Bore
'C'| Vel m/s |EL T
VT|Slope| mbar/m |
End | End
Static
50 149
40mm
MW
152.9
2.743
0
2.74
37.676
0.526 -0.033
150
41.86 120
1.9
0 0
0.0
12.0
37.676
0.493 +0.000
51 150
25mm
MW
96.7
2.743
0
2.74
37.676
0.493 -0.113
151
27.31 120
2.8
0 0
0.0
41.1
37.676
0.381 +0.000
52 151
25mm
MW
47.4
2.743
0
2.74
37.676
0.381 -0.030
152
27.31 120
1.3
0 0
0.0
11.0
37.676
0.351 +0.000
53 148 150mm
MW
634.7
1.041
90
1.04
37.676
0.609 -0.000
153 155.32 120
0.6
0 0
0.0
0.3
37.676
0.609 +0.000
54 153
25mm
MW
104.9
1.651
180
3.37
37.676
0.609 -0.161
154
27.31 120
3.0
0 1
0.0
47.7
37.676
0.448 +0.000
55 154
25mm
MW
51.4
2.743
180
2.74
37.676
0.448 -0.035
155
27.31 120
1.5
0 0
0.0
12.7
37.676
0.413 +0.000
56 153 150mm
MW
529.8
2.800
90
2.80
37.676
0.609 -0.001
156 155.32 120
0.5
0 0
0.0
0.2
37.676
0.608 +0.000
57 156
25mm
MW
104.9
1.651
0
3.37
37.676
0.608 -0.161
157
27.31 120
3.0
0 1
0.0
47.7
37.676
0.447 +0.000
58 157
25mm
MW
51.4
2.743
0
2.74
37.676
0.447 -0.035
158
27.31 120
1.5
0 0
0.0
12.7
37.676
0.412 +0.000
59 156 150mm
MW
425.0
0.250
90
0.25
37.676
0.608 -0.000
159 155.32 120
0.4
0 0
0.0
0.1
37.676
0.608 +0.000
60 159
25mm
MW
104.8
1.651
180
3.37
37.676
0.608 -0.161
160
27.31 120
3.0
0 1
0.0
47.7
37.676
0.447 +0.000
61 160
25mm
MW
51.4
2.743
180
2.74
37.676
0.447 -0.035
161
27.31 120
1.5
0 0
0.0
12.7
37.676
0.412 +0.000
62 159 150mm
MW
320.1
2.800
90
2.80
37.676
0.608 -0.000
162 155.32 120
0.3
0 0
0.0
0.1
37.676
0.608 +0.000
63 162
40mm
MW
210.7
1.092
0
3.81
37.676
0.608 -0.083
163
41.86 120
2.6
0 1
0.0
21.7
37.676
0.525 +0.000
64 163
40mm
MW
152.7
2.743
0
2.74
37.676
0.525 -0.033
164
41.86 120
1.9
0 0
0.0
11.9
37.676
0.493 +0.000
65 164
25mm
MW
96.6
2.743
0
2.74
37.676
0.493 -0.112
165
27.31 120
2.7
0 0
0.0
41.0
37.676
0.380 +0.000
66 165
25mm
MW
47.3
2.743
0
2.74
37.676
0.380 -0.030
166
27.31 120
1.3
0 0
0.0
10.9
37.676
0.350 +0.000
67 162 150mm
MW
109.4
0.250
90
0.25
37.676
0.608 -0.000
167 155.32 120
0.1
0 0
0.0
0.0
37.676
0.608 +0.000
68 167
25mm
MW
109.4
1.651
180
2.34
37.676
0.608 -0.121
168
27.31 120
3.1
1 0
0.0
51.6
37.676
0.487 +0.000
Continued on the next page

FHC - Hydraulic Analysis Software - Ver: 1.8.0

Program FHC

Full Hydraulic Calculations Computer Printout Page No 5


Submitted by Engr Anwar Ul Karim, MBA, PMP
MIEB No M/34416

Tel: Fax:

Project:
Address:
Number:
Area ref:
Hazard:
Authority:
Systems
Source:
Printout:

Evince Garments Ltd


Mirpur. Dhaka
BI-EGL-01
Most Unfavourable
ordinary
NFPA 13 : 2013 - Installation of Sprinkler
845.6 l/min @ 4.352 bar
5-September-14

Hydraulically Significant Pipes in System


NUMBERS | P I P E | F L O W |DIMENSIONS|ANGLE| VALUES |HEIGHT M|PRESSURES BARS
Pipe|Start|Size
Type| L/min | Length VJ|Dir. | Eq.len | Start | Start
Frict
no | End |Bore
'C'| Vel m/s |EL T
VT|Slope| mbar/m |
End | End
Static
69 168
25mm
MW
53.6
2.743
180
2.74
37.676
0.487 -0.038
169
27.31 120
1.5
0 0
0.0
13.8
37.676
0.449 +0.000

FHC - Hydraulic Analysis Software - Ver: 1.8.0