Hitec Power Protection

Diesel Rotary UPS systems

www.hitec-ups.com
Diesel UPS systems

Ride through systems

Hitec Power Protection


What we do

The problems

The solution

The result

1. Spikes
2. Frequency Variations
3. Voltage Sags
4. Outages
5. Harmonic Distortions
6. Transients

7. Continuous Quality Power

Major components
Diesel engine

Generator

Choke
coil

Switchgear

Dicon

Induction
coupling

Freewheel
clutch
Control panel

Free inner rotor principle

AC machine

Induction coupling

Freewheel clutch

Diesel engine

Four basic principles (1)




Simple, sure and reliable


Rotary UPS/CPS concept invented and patented by Hitec
Power Protection in 1969
Rotary UPS/CPS = static UPS + standby generator
Fewer components than static UPS
Smaller footprint than static UPS
Easy installation & operation
Long lifespan (>25 years)

Line-interactive system
Rotary UPS/CPS run in parallel with utility power
Life-guarding mission critical processes
No power conversion

Four basic principles (2)




Active filter (choke coil + generator)

Compensation utility voltage deviations


Filtering of utility borne harmonic voltages
Filtering of load borne harmonic currents
Power factor improvement (>0.98)

Environmental friendly system

Most energy efficient UPS/CPS system


Use of stored kinetic energy
No batteries required, no chemical waste
No conditioned battery room required, saving space and energy
for ventilation and cooling
Lowest Total Cost of Ownership (TCO)

Diesel Rotary UPS system


Specifications










Diesel, UPS and energy storage combined


Lowest TCO, 25+ years productive lifetime
No power conversion
High end-to-end efficiency (>96%)
High output values
Single unit rating  Up to 2,5 MVA
Parallel configuration rating  Up to 40 MVA
Output voltage
LV  380 .. 480 V, 50/60 Hz
MV  Up to 24 kV, 50/60 HZ
Voltage deviation +/- 1%
Frequency deviation +/- 1%
Options (e.g. remote monitoring, containerized designs,
vibration monitoring, .)

All in one

Standby Diesel

Hitec DRUPS

Static UPS
PFC
Standby Batteries

Air Conditioning
UPS Inverters

Spark-proof Lighting

Busduct & Cabling


Fire Protection
& Security

Lowest TCO
Total losses <3%
100%

Hitec Rotary UPS

Benefits Hitec Power Protection systems:


- Energy efficiency (no power conversion)
>96%
- Reliability (fewer elements)
- Space efficiency (zero footprint)
- Lowest maintenance
- Environmental friendly (no batteries)
- Lifespan system (>25 years)

Static UPS System

Total losses >8%

100%

Fire Protection
& Security

Air Conditioning

UPS Inverters

PFC

Standby Batteries

<92%

Busduct & Cabling

Spark-proof Lighting

It is in the windings
Outer Rotor
 2 pole AC windings
 2 pole DC windings
50 Hz
1500 RPM

60Hz
1800 RPM

Inner Rotor
 Stored Energy
50 Hz
1500
3000 +
4500 RPM

60Hz
1800
3600 +
5400 RPM

System operation

Dependent system load


Speed (rpm)

3n

Time

Utility mode

Speed (rpm)

3n

Time
Q3

Reactor and generator function as


active filter. The induction
coupling stores kinetic energy.

Q1

Q2

Change-over to diesel mode

Speed (rpm)

3n

Time
Q3

Power problem - Q1 opens, energy


from the inner rotor goes via the
generator to the load. The diesel
engine starts up and takes over
the power supply.

Q2

Q1

Diesel mode

Speed (rpm)

3n

Time
Q3

The outer rotor of the induction


coupling is re-energized. The
speed of the diesel engine is
digitally controlled ensuring a
constant output

Q1

Q2

Back to utility mode

Speed (rpm)

3n

Time
Q3

Utility power is back and after it


has stabilized the UPS/CPS
synchronizes and closes Q1. The
diesel engine ramps down and
the free-wheel clutch disengages.

Q2

Q1

Recording mains failure


Dynamic UPS at 100% load
Moment of
mains failure
Mains
Voltage

Mains
voltage

Diesel engine RPM


1500 rpm

Output
voltage

Free wheel clutch


engaging

50.5 Hz

50 Hz Line

50 Hz
49.5 Hz
1 sec.

Diesel
start

Output
frequency [Hz]

Technical features D-UPS










Uses stored kinetic energy 50/60 Hz technology


Integrated power factor correction
Effective filter for spikes & harmonic distortion
High non-linear load capacity
High peak current capability (typical 15 In)
Very efficient with low operational costs
Easily paralleled MV applications up to 40 MVA

Hitec D-UPS configurations

Unit configurations

System configurations

Single output

Parallel redundant

Dual output

Master slave

Medium Voltage

Cross link
Isolated redundant
Distributed redundant

Thank you for your interest

For more information please visit our website

www.hitec-ups.com
Ride through systems

Diesel UPS systems