Product Manual

602 B - 99/12 B
Date: December 1999
Supersedes: 602 B - 99/12 B

Water cooled water chillers


WHZ 024.2047.2
cooling capacity from 85 to 164 kW
50 Hz - refrigerant: HFC 407 C

McQuay water cooled water chiller


General characteristics

McQuay Int'l introduces their newest water cooled water


chiller type WHZ equipped with Scroll compressors and
electronic control system. McQuay have once again succeeded in developing a high quality product with extraordinary
performance which is able to satisfy HVAC application, industrial refrigeration an icestore application. For more than
60 years, McQuay have designed and built successful line
of products.The latest technology is included in the new
WHZ chiller range equipped with Scroll compressor and unsurpassed advanced features. All units are equipped with
electronic control device control which optimises the unit
operation also improving the interface with devices for remote monitoring.

Compressors: unit model WHZ 024.2 is equipped with two


single compressors, unit model WHZ 032.2047.2 install
two tandem scroll hermetic compressors. Electric motors
are DOL starting type.

Low operating costs

Evaporator

The McQuay WHZ chillers use the most reliable and efficient components in the industry. Scroll compressors offer
an operating economy that at partial load conditions is uncomparable with the most aggressive competitors. The unloading system with multiple capacity steps reduce allows
the electrical consumption to the plant requirement. The use
of a single evaporator provided with multiple refrigerant circuits improves the unit performance at partial load operation.

The evaporator is a direct expansion shell-and-tube type


constructed with a carbon steel shell and seamless high efficiency copper tubes. It is equipped with a baffled shell side
to ensure the appropriate water flowing outside the tubes
obtaining the maximum heat exchange with the lowest pressure drop. Externally the shell is protected by 10 mm thickness closed-cell insulation material. Evaporator water
connections of victaulic type are equipped with a water
nozzle to be welded on the plant piping system.

Low installation costs

Condensers

All units are completely factory assembled. A rigid steel base with lifting points permits quick unit rigging. Power and
control panel mounted on the shorter side of the unit determines a more optimized location of unit inside the chillers
room, allowing easy maintenance and control. WHZ unit are
fully wired and supplied with a single power connection. Extensive quality control operation tests assure trouble-free installation and start-up.

Condensers are shell and cleanable, through-tube type. The


unit has independent condensers, one per circuit. Each
condenser has a carbon steel and seamless, integrally finned high efficiency copper tubes, roll expanded into heavy
carbon steel tube sheets. Water heads are removable and
include vent and drain plugs. Condensers come complete
with liquid shut-off valve, spring loaded relief valve.

Full factory testing

Each refrigerant circuit is completely independent and complete with all control and regulation devices such as: filter
driers, liquid sight glass and thermostatic expansion valves.

Pressure vessels tests are performed on all units then evacuated and charged with refrigerant HFC 407C. All safety
and operating controls are properly checked and calibrated
at the factory. A complete performance test simulates the given conditions. A second series of tests may also be performed at customer's presence. Before shipment, each unit is
re-checked for pressure and refrigerant charge control.

Code requirements
WHR units can be manufactured and certified in accordance
with following code requirements: ISPESL, TV and SA.
Code requirement must be specified when order is placed.

Structure
The chiller is equipped with brackets directly installed on
heat exchangers. The evaporator and the suction piping are
appropriately insulated to prevent condensation.

Scroll Compressors

Refrigerant circuits

Power and starting panel


Inside the electrical panel is installed a programmable
electronic control, including temperature sensors, keypad to
set and control data protected by a password. All devices
are factory installed and wired. The unit controls are
designed to allow the reading and the updating of data both
locally and remotely.

Reliability
The use of scroll compressors together with the most
advanced and efficient control system assures reliable
functioning. Each refrigerant circuit comes complete with
multiple safety devices which prevent compressor damage.

Serviceability
All multiple compressor units use independent refrigerant
circuits. They permit shut-down, routine maintenance and
service of one of the circuit while the others maintain the
system operation.

Programmable electronic control device


The control device is installed as standard on all water
cooled chiller series WHZ. It visualises all operating values
and setpoint recorded allowing setting and modifying the
regulation parameters at a later stage. An infrared remote
control and a serial output board are available as option for
a supervisor connection.

602 B - 99/12 B - pag. 2/8

Versions available
Water chiller model WHZ are available in three versions:
WHZ ST Standard version equipped with water cooled
condensers
WHZ LR Special execution without the water cooled
condensers. The units suitable for remote condenser
operation are equipped with liquid receivers, one per circuit
and with copper tube connection.
WHZ ME Special execution as the previous version but
also without the liquid receivers to be arranged on the
installation.

Accessories and options


01 - 100% total heat recovery (R) produced with tube
bundle placed in a single shell with the water condensers.
Heat exchangers heads are provided with 2 connections for
entering/leaving heat recovery water and 2 separate
connections for condensing water.
11 - Compressor thermal relays. Safety device against
compressor motor overloading.
42 - Flow switch. For field installation on evaporator and
condensers pipes to prevent freeze up under low temperature conditions. It must be wired to the power panel terminals by the customer.
84 - Rubber antivibration isolators. They are available for
field installation to reduce vibrations transmission through
the unit base.
86 - Sound proof jacket on compressors. Made of insulated material to reduce the sound noise level of the compressors (-3 dBA).

Table 1 Operating limits


Max. evap. entering water temperature (without glycol)

HFC 407C
24

Max. evap. leaving water temperature (without glycol)


C
Min. evap. leaving water temperature (with glycol)
C
Max. cond. leaving water temperature
C
Min. cond. leaving water temperature
C
Note: Table 1 are referred to 2 passes evaporator and condenser.

16
-8
50
30

Table 2 Evaporator fouling factors


Fouling factors

Cooling capacity

Power input

COP

m2C/kW

Correction factor

Correction factor

Correction factor

0,044
0,088
0,132

1
0,986
0,972

1
0,992
0,984

1
0,994
0,987

Table 3 Condenser fouling factors


Fouling factors

Cooling capacity

Power input

COP

m2C/kW

Correction factor

Correction factor

Correction factor

0,044

0,088
0,132

0,99
0,981

1,018
1,036

0,973
0,945

Table 4 Ethylene glycol correction factors


Air ambient temperature C
% of ethylene glycol by weight

-3
10

-8
20

-14
30

-22
40

-33
50

Cooling capacity correction factor


Power input correction factor
COP correction factor

0,991
0,996
0,995

0,9852
0,992
0,99

0,972
0,986
0,985

0,961
0,976
0,982

0,946
0,966
0,979

Flow rate correction factor


Water pressure drop correction factor

1,013
1,07

1,04
1,129

1,074
1,181

1,121
1,263

1,178
1,308

Table 5 Brine application correction factors


Glycol/water leaving temperature C
Min. % of ethylene glycol
Cooling capacity correction factor
Power input correction factor

-2

-4

-6

-8

10
0,84
1,016

20
0,782
1,018

20
0,726
1,019

30
0,673
1,020

30
0,623
1,022

30
0,575
1,024

COP correction factor


0,826
0,768
0,712
0,659
0,609
0,561
Correction factors on Table 5 must be applied to the nominal performance data to have the adjusted value (+7C leaving evap. water temp.)

602 B - 99/12 B - pag. 3/8

Physical data WHZ 024.2047.2 (HFC 407 C)


WHZ Unit size
Cooling capacity (1)
Power input (1)
No. of compressor
Compressor model
No. of reduction steps
No. of refrigerant circuit
No. of evaporator
Max water pressure
No. of condenser/no. of passes
Max water pressure
Unit length (2 passes)
Unit width
Unit height
Shipping weight
Note: (1)

kW
kW

bar
bar
mm
mm
mm
kg

024.2

032.2

041.2

047.2

84,6
21,6
2
Scroll
2
2
1
16
2/2
16
1700
600
1575
550

109,0
27,6
2 tandem
Scroll
4
2
1
16
2/2
16
2500
600
1575
860

142,4
36,6
2 tandem
Scroll
4
2
1
16
2/2
16
2500
600
1575
860

164,1
43,0
2 tandem
Scroll
4
2
1
16
2/2
16
2500
600
1575
860

Nominal cooling capacity are based on: 12/7 C entering/leaving evaporator water temperature; 30/35C entering/leaving
condenser water temperature.

Sound pressure level (Standard version)


Sound pressure level at 1 m from the unit in free field (rif. 2 x 10 -5)

WHZ
unit size

63 Hz

125 Hz

250 Hz

500 Hz

1000 Hz

2000 Hz

4000 Hz

8000 Hz

dBA

024.2

63,0

55,5

63,5

75,0

72,5

69,5

68,0

58,5

77,0

032.2

64,0

56,5

64,5

76,0

73,5

70,5

69,0

59,5

78,0

041.2

64,0

56,5

64,5

76,0

73,5

70,5

69,0

59,5

78,0

047.2

64,0

56,5

64,5

76,0

73,5

70,5

69,0

59,5

78,0

Note: Average sound pressure level rated in accordance to ISO 3744, free field conditions.

Sound pressure level (with sound proof jacket)


Sound pressure level at 1 m from the unit in free field (rif. 2 x 10 -5)

WHZ
unit size

63 Hz

125 Hz

250 Hz

500 Hz

1000 Hz

2000 Hz

4000 Hz

8000 Hz

dBA

024.2

62,5

55,0

62,0

74,0

68,5

64,5

62,5

53,0

74,0

032.2

63,5

56,0

63,0

75,0

69,5

65,5

63,5

54,0

75,0

041.2

63,5

56,0

63,0

75,0

69,5

65,5

63,5

54,0

75,0

047.2

63,5

56,0

63,0

75,0

69,5

65,5

63,5

54,0

75,0

Note: Average sound pressure level rated in accordance to ISO 3744, free field conditions.

Electrical data (power supply 400-3-50)


WHZ Unit size
FLA compressor 1
FLA compressor.2
FLA unit
LRA compressors
Inrush unit current

A
A
A
A
A

Notes: Unbalance between phase 3%


Allowable voltage tolerance 10%.

602 B - 99/12 B - pag. 4/8

024.2

032.2

041.2

047.2

35
35
70
175
210

50
50
100
120
195

70
70
140
175
280

70
70
140
175
280

WHZ
Unit size

WHZ
024.2

WHZ
032.2

WHZ
041.2

WHZ
047.2

Evap.leaving
watertemp.-C

Standard ratings WHZ 024.2047.2 (HFC 407C)

4
5
6
7
8
9
10
11
12
13
14
15
16
4
5
6
7
8
9
10
11
12
13
14
15
16
4
5
6
7
8
9
10
11
12
13
14
15
16
4
5
6
7
8
9
10
11
12
13
14
15
16

ENTERING CONDENSER WATER TEMPERATURE - C


25

30

35

40

45

Cooling
capacity
kW

Power
input
kW

Cooling
capacity
kW

Power
input
kW

Cooling
capacity
kW

Power
input
kW

Cooling
capacity
kW

Power
input
kW

Cooling
capacity
kW

Power
input
kW

80,8
83,3
85,8
88,4
91,0
93,6
96,3
99,0
101,7
104,5
107,3
110,2
113,0
104,0
107,2
110,4
113,7
117,1
120,5
123,9
127,4
131,0
134,5
138,2
141,8
145,5
135,6
139,8
144,0
148,4
152,7
157,2
161,7
166,3
170,9
175,6
180,4
185,2
190,0
156,7
161,5
166,3
171,3
176,3
181,3
186,5
191,7
196,9
202,3
207,7
213,1
218,6

19,1
19,2
19,3
19,4
19,6
19,7
19,8
19,9
20,1
20,2
20,3
20,5
20,6
24,4
24,5
24,6
24,8
24,9
25,0
25,1
25,3
25,4
25,5
25,7
25,8
25,9
32,5
32,7
32,9
33,1
33,3
33,5
33,7
33,9
34,1
34,3
34,5
34,7
34,9
37,9
38,2
38,4
38,6
38,9
39,1
39,4
39,6
39,9
40,2
40,4
40,7
41,0

77,3
79,7
82,1
84,6
87,1
89,7
92,3
94,9
97,5
100,2
102,9
105,7
108,4
99,6
102,7
105,8
109,0
112,3
115,6
118,9
122,3
125,7
129,2
132,7
136,2
139,8
130,0
134,1
138,2
142,4
146,7
151,0
155,3
159,8
164,3
168,8
173,4
178,1
182,8
150,0
154,7
159,4
164,1
169,0
173,9
178,8
183,9
188,9
194,1
199,3
204,6
209,9

21,2
21,3
21,5
21,6
21,8
21,9
22,0
22,2
22,3
22,5
22,6
22,8
22,9
27,2
27,4
27,5
27,6
27,8
27,9
28,1
28,2
28,4
28,5
28,7
28,8
29,0
36,0
36,2
36,5
36,7
36,9
37,1
37,3
37,5
37,8
38,0
38,2
38,4
38,7
42,2
42,5
42,8
43,0
43,3
43,6
43,8
44,1
44,4
44,7
45,0
45,3
45,6

73,5
75,8
78,2
80,5
83,0
85,4
87,9
90,4
92,9
95,5
98,1
100,8
103,4
94,7
97,7
100,7
103,8
107,0
110,1
113,4
116,6
119,9
123,3
126,6
130,1
133,5
124,0
127,9
131,9
135,9
140,0
144,2
148,4
152,7
157,0
161,4
165,8
170,3
174,8
142,8
147,2
151,7
156,3
161,0
165,7
170,5
175,3
180,2
185,2
190,2
195,2
200,4

23,6
23,8
23,9
24,1
24,2
24,4
24,6
24,7
24,9
25,0
25,2
25,4
25,5
30,5
30,7
30,8
31,0
31,1
31,3
31,5
31,6
31,8
31,9
32,1
32,3
32,4
40,0
40,2
40,4
40,7
40,9
41,1
41,4
41,6
41,8
42,1
42,3
42,6
42,8
47,1
47,4
47,7
48,0
48,3
48,6
48,9
49,2
49,5
49,8
50,1
50,4
50,7

69,4
71,6
73,8
76,1
78,4
80,7
83,1
85,5
88,0
90,4
92,9
95,4
98,0
89,3
92,2
95,1
98,1
101,1
104,1
107,2
110,3
113,5
116,7
120,0
123,2
126,6
117,4
121,2
125,0
128,9
132,8
136,8
140,8
144,9
149,0
153,2
157,5
161,8
166,2
134,8
139,1
143,4
147,8
152,3
156,8
161,3
166,0
170,7
175,4
180,2
185,1
190,0

26,4
26,5
26,7
26,9
27,0
27,2
27,4
27,5
27,7
27,9
28,1
28,3
28,4
34,3
34,5
34,7
34,8
35,0
35,2
35,3
35,5
35,7
35,9
36,1
36,2
36,4
44,4
44,6
44,9
45,1
45,4
45,6
45,9
46,1
46,4
46,6
46,9
47,2
47,4
52,6
52,9
53,2
53,5
53,8
54,1
54,5
54,8
55,2
55,5
55,8
56,2
56,5

64,9
67,0
69,1
71,3
73,5
75,7
77,9
80,2
82,5
84,9
87,3
89,7
92,1
83,3
86,1
88,9
91,7
94,6
97,5
100,4
103,4
106,5
109,5
112,6
115,8
118,9
110,2
113,8
117,5
121,1
124,9
128,7
132,5
136,5
140,4
144,4
148,5
152,6
156,8
126,2
130,3
134,4
138,5
142,8
147,1
151,4
155,8
160,3
164,8
169,4
174,0
178,7

29,5
29,6
29,8
30,0
30,2
30,3
30,5
30,7
30,9
31,1
31,3
31,5
31,7
38,7
38,9
39,0
39,2
39,4
39,6
39,8
40,0
40,2
40,3
40,5
40,7
40,9
49,3
49,5
49,8
50,1
50,3
50,6
50,9
51,1
51,4
51,7
52,0
52,2
52,5
58,7
59,0
59,4
59,7
60,1
60,4
60,8
61,1
61,5
61,9
62,2
62,6
63,0

Notes: Ratings based on evaporator and condenser fouling factor of 0.044 (m2C/kW) and evaporator and condenser
temperature drop of 5C.

602 B - 99/12 B - pag. 5/8

Water pressure drop

evaporator
WHZ 047.2
WHZ 041.2
WHZ 032.2
WHZ 024.2

100
90
80
70
60

Pressure drop (kPa)

50
40

30

20

10
1

8 9 10

Water flow rate (L/s)

Water pressure drop

condenser
2 passes
WHZ 047.2
WHZ 041.2
WHZ 032.2
WHZ 024.2

60
50

Pressure drop (kPa)

40

30

20

10
2

Water flow rate (L/s)

602 B - 99/12 B - pag. 6/8

10

12 14 16 18 20

Dimensions WHZ 024.2

WHZ
Unit size
024.2
032.2
041.2
047.2

A
1700
2500
2500
2500

Dimensions (mm)
B
600
600
600
600

C
1575
1575
1575
1575

Dimensions WHZ 032.2047.2

602 B - 99/12 B - pag. 7/8

We reserve the right to make changes in design and construction at any time without notice, thus the cover picture is not binding.