Technical Datasheet

1 VXI 145-4
Main Accessories :
THERMAL DESIGN DATA
Requested capacity (overall/unitary)(@ 100% RPM)..................................... 993 / 993 kW
Max. capacity (overall/unitary)(@ 100% RPM)............................................... 993 / 993 kW
Fluid type................................................................................................................ 35% EG
Freezing point.............................................................................................................-20 C
Requested fluid flow (overall/unitary)..............................................................37.5 / 37.5 l/s
Max. fluid flow (overall/unitary)....................................................................... 37.5 / 37.5 l/s
Entering wet bulb temp.............................................................................................22.0 C
Entering dry bulb temp............................................................................................. 32.0 C
Process fluid inlet temperature.................................................................................35.0 C
Process fluid outlet temperature...............................................................................28.0 C
Operating mode............................................................................................................. Wet
PHYSICAL DATA (including accessories) - UNITARY
Overall length........................................................................................................ 5965 mm
Standard unit.................................................................................................... 5385 mm
Pump 1............................................................................................................... 580 mm
Overall width..........................................................................................................2397 mm
Standard unit.................................................................................................... 2397 mm
Overall height........................................................................................................ 4483 mm
Standard unit.................................................................................................... 4483 mm
Shipping / operating weight........................................................................ 9260 / 14160 kg
Standard unit......................................................................................... 9260 / 14160 kg
Heaviest section...................................................................................................... 6690 kg
Material option................................................................. BALTIBOND HYBRID COATING
Overflow diameter........................................................................................ (1x) ND 80 mm
Make up diameter........................................................................................ (1x) ND 50 mm
Drain diameter..............................................................................................(1x) ND 50 mm
Number of coils per unit......................................................................................................2
Exact unit dimensions and weights may be influenced by accessories/option
combinations.
EVAPORATIVE COIL DATA - UNITARY
Evaporative coil type..........................................................................................Bare / HDG
Customer:
Project:Project 1
Office:
User:mabo

Evaporative coil arrangement..................................................................... Wet coil - 1pass


Evaporative coil inlet connections.....................................................................(2x) ND 100
Evaporative coil outlet connections...................................................................(2x) ND 100
Evaporative coil volume......................................................................................(2x) 995.0 l
Evaporative coil surface.................................................................................. (2x) 185.0 m
Evaporative coil dry weight............................................................................(2x) 2595.0 kg
ELECTRICAL DATA - UNITARY
Fan motor
General
Fan motor BHP (Net mechanical output power at motor shaft) ........... (1 x) 33.0 kW
Fan motor oversized for
Total ESP....................................................................................................... 0 Pa
Accessories total external static pressure.................................................0 Pa
Customer external static pressure............................................................ 0 Pa
Dry operation allowed....................................................................................... No
Fan motor voltage............................................................................................. 400 V
Frequency......................................................................................................... 50 Hz
Protection class...................................................................................................IP55
Mounting................................................................................................................ B3
Single speed
Fan motor power................................................................................... (1 x) 37.0 kW
Fan full load current (Nominal Voltage).................................... (1 x) 66.6 A ( 400 V )
Fan synchrone speed................................................................................ 1500 RPM
Framesize.............................................................................................................225
Spray pump motor power...................................................................................(1x) 4.0 kW
Spray pump motor voltage.......................................................................................... 400 V
Frequency................................................................................................................... 50 Hz
Spray pump full load current.......................................................................... (8.6 A ) 400 V
Spray pump synchrone speed.............................................................................1500 RPM
Protection class
Mounting
Framesize.......................................................................................................................132
* Note: For indicative cable sizing the "Fan Full Load Current" and the corresponding
"Nominal Voltage" have to be used.
AERODYNAMICAL DATA - UNITARY
Air flow (100% RPM/100% RPM)................................................................ 36.6 / 36.6 m/s

BALTIMORE AIRCOIL
S2Q V3.4.3

BAC ref.:CCCT 1
2014-09-18
P 1/4
quoteNr:

Technical Datasheet
Number of fans................................................................................................................... 3
Fan type.............................................................................................................. Centrifugal
Approximate Fan speed........................................................................................ 463 RPM
HYDRAULICAL DATA - UNITARY
Total pressure drop(@37.5 / 37.5)............................................................... 71.0 / 71.0 kPa
Standard unit........................................................................................... 71.0 / 71.0 kPa
Spray water flow................................................................................................ (1x) 38.5 l/s
Maximum evaporation................................................................................ 0.451 / 0.451 l/s
Bleed (cycles of concentration 2.5).............................................................0.301 / 0.301 l/s
Make-Up (cycles of concentration 2.5)....................................................... 0.751 / 0.751 l/s
Pan volume operating.................................................................................................1106 l
Pan volume overflow.................................................................................................. 2609 l
Pressure range mechanical make-up valve....................................................... 1 to 4,5 bar
Acoustical data (Standard unit no attenuation)
100 % RPM (@ 15.0m).......................................................................................... 58 dB(A)
Sound Power Level............................................................................................. 96.0 dB(A)
All acoustical data as sound pressure levels at quietest side of unit at indicated distance

ACCESSORIES - Winterisation package UNITARY


Pan heater package 2*4 kW (provides freeze protection to -18C ambient)
1 stage thermostat
Protection class...................................................................................................IP54
Temperature range.................................................................................... -20..50 C
Contacts...................................................................................................NO and NC
Rating (@250VAC)............................................................................................. 10 A
Pan heater 4 kW
Rating (@400VAC).......................................................................................... 5.78 A
Power................................................................................................................. 4 kW
Low level cut out switch with integral stilling chamber
Contacts......................................................................................................NO or NC
Voltage......................................................................................................... 240 VAC
Rating (@240VAC)............................................................................................... 1 A
Index of protection..............................................................................................IP 65
note

ACCESSORIES - Motor accessories UNITARY


PTC (only) (for fan motor)

Customer:
Project:Project 1
Office:
User:mabo

BALTIMORE AIRCOIL
S2Q V3.4.3

BAC ref.:CCCT 1
2014-09-18
P 2/4
quoteNr:

Sound Rating
Sound Rating

Input Options

Hz

Fan End(dB)

Back(dB)

End1(dB)

End2(dB)

63
125
250
500
1000
2000
4000
8000
dB(A)

66.0
66.0
65.0
63.0
61.0
58.0
56.0
49.0
66.0

60.0
62.0
56.0
56.0
53.0
49.0
40.0
40.0
58.0

65.0
62.0
58.0
60.0
55.0
50.0
47.0
40.0
61.0

65.0
62.0
58.0
60.0
55.0
50.0
47.0
40.0
61.0

Discharge
(dB)
62.0
65.0
64.0
63.0
62.0
59.0
55.0
52.0
67.0

Model
Sound Attenuation
Additional ESP (Pa)
Fan Motor Size (kW)
Approximate Fan Speed
Distance (m)

VXI 145-4
no attenuation
0
1 x 37.0 kW
100.0 %
15.0

Total Sound Power Level


Octave Band (Hz)
63
125
250
500
1000
2000
4000
8000
dB(A)

Total Sound Power Level


96.0
96.0
94.0
93.0
91.0
87.0
84.0
79.0
96.0

Octave band and A-weighted Sound Pressure Levels (SPL) in dB RE 0.0002 Microbar.
Note: Sound data are free field data valid for unit installation without elevation, not taking into account any reflections. Octave band values are shown for indicative purposes only.

Customer:
Project:Project 1
Office:
User:mabo

BALTIMORE AIRCOIL
S2Q V3.4.3

BAC ref.:CCCT 1
2014-09-18
P 3/4
quoteNr:

The new generation Baltibond hybrid coating


Save up to 33% water and chemicals

Ice Thermal Storage Products


TSU-C/D

TSU-M

325 - 5060 kWh

647 - 2676 kWh

3 good reasons to opt


for the new generation
Baltibond hybrid coating

For easier Maintenance


or lower Energy Consumption

For reduced
Sound Levels

Internal Ladder and Platform

VX Sound Attenuation

5,00

4,00

3,00

33%
typical
saving

2,00

1,00

1. Save money

Accessories
For increased Safety
and Hygiene

Relative water
consumption

Ice thermal storage products are used to build and


store cooling in the form of ice during periods of
reduced cooling demand. This way the mechanical
refrigeration system needs not to be sized on
peak load but on average conditions. Hence a
smaller refrigeration system with much lower power
requirements and a smaller refrigerant charge can
be selected. Ice thermal storage products can either
be of the internal or external melt type. For
internal melt only glycol solutions can be used as
secondary refrigerant. External melt ice storage
products can use either direct refrigerant feed or
glycol solutions.

Increase the service life of your evaporative


cooling
Reduce water consumption with higher cycles
of concentration
Reduce chemical consumption with higher cycles
of concentration
Experience an economical alternative to SST 304

0,00
1

Galvanized
New generation
Steel
Baltibond hybrid coating

5
Cycles of
concentration

The effect of cycles of concentration


on water and chemical consumption

2. Increase safety

The smooth surface finish


reduces the development of biofilm
facilitates internal cleaning

Filtration System

3. Respect the environment

VL Sound
Attenuation

Removable Fill

Combined
Inlet
Shields

Motor
removal
davit

Reduce chemical and water rejection


Reduce water consumption with higher cycles of concentration

S3000E and S1500E Sound Attenuation

Your BAC Representative :


External ladder and platform

Automatic
Blow-down

Baltiguard Drive System

LOW ENVIRONMENTAL
IMPACT PRODUCTS

Whisper
Quiet fans
Critical
spare parts kit

S 310 v14 EN

For more information :

www.BaltimoreAircoil.eu
info@BaltimoreAircoil.eu

Open Cooling Towers


The performance of BAC open cooling towers is
Eurovent certified.
Open cooling towers are a proven and
cost-effective method of cooling condenser water
loops and industrial processes. In operation, the
condenser water (or process water) flows directly
over the heat transfer surface of the open
cooling tower. As air is introduced into the tower,
a fraction of this water is evaporated, cooling
the remaining water. Open cooling towers provide
evaporative cooling for many types of systems,
and the specific application will largely determine
which BAC cooling tower is best suited for a
project. There are two main configurations of
factory assembled open cooling towers: crossflow
and counterflow. In crossflow cooling towers, the
water flows vertically down the wet deck as the
air flows horizontally across it. In counterflow
cooling towers, the water flows vertically down
the wet deck as the air flows vertically up it.

Crossflow

Open cooling
towers

S1500E
S3000E
PTE
VTL-E
VT 0/1

Counter
flow

Closed circuit cooling towers

FXVE
FXV-D
PFE
VFL
VXI
HXI
HFL
DFC
Spartium Series
Trillium Series

Refrigerant Condensers

CXVE
CXV-D
PCE
VCL
VXC

HXC
Trillium Series

Combined
flow

16 - 285 l/s

BAC participates in the ECC programme for cooling


towers. Check ongoing validity of certificate:
www.eurovent-certification.com or
www.certiflash.com

8 - 215 l/s

PTE
12 - 170 l/s

7 - 455 l/s

3 - 130 l/s

PFE

Axial
fan

Centrifugal
fan

Addition of product accessories can improve standard product features e.g. sound attenuation, plume abatement, maintenance,
operational safety, corrosion protection. Contact your BAC representative for more information.

Low
sound

Energy
efficiency

Easy
maintenance

Operational
safety

155 - 1790 kW

In an evaporative condenser, refrigerant vapour


is condensed in a coil, which is continually
wetted on the outside by a recirculating
water system. Air is circulated over the coil,
causing a small portion of the recirculating
water to evaporate. The evaporation removes
heat from the vapour in the coil, causing it
to condense. Evaporative condensers provide
lower condensing temperatures and compressor
kilowatts savings up to 30% when compared
with air cooled systems. BAC manufactures two
types of evaporative condensers: combined flow
and counterflow. Combined flow evaporative
condensers have both a heat exchange coil and
wet deck surface for heat transfer; they utilize
parallel flow of air and spray water over the
coil, and crossflow of air and spray water flow
through the wet deck surface.

VXI

VFL

19 - 2615 kW

70 - 575 kW

Evaporative Condensers

Water
saving

FXV-D

1425 - 2290 kW

FXVE

Combined flow closed circuit cooling towers have


both a heat exchange coil and wet deck surface
for heat transfer; they utilize parallel flow of air
and spray water over the coil, and crossflow of
air and spray water flow through the wet deck
surface.

Indoor
installation

Water Saving Products

235 - 1365 kW

BAC manufactures two types of closed circuit


cooling towers: combined flow and counterflow.

VT 0/1

VTL-E

Closed Circuit Cooling Towers


Closed circuit cooling towers keep
the process fluid clean and contaminant free in
a closed loop. This creates two separate fluid
circuits: an external circuit, in which spray water
circulates over the coil and mixes with the
outside air, and an internal circuit, in which the
process fluid to be cooled circulates inside the
coil. During operation, heat is transferred from
the warm fluid in the coil to the spray water, and
then to the atmosphere as a portion of the water
evaporates.

S1500E

S3000E

Best

CXV-D

CLOSED CIRCUIT COOLING TOWERS


Water saving and hybrid products (HXI, HFL) are of the closed circuit type
where the heat load to be rejected is transferred from the process fluid to
be cooled to the ambient air through a heat exchange coil. The coil serves
to isolate the process fluid from the outside air, keeping it clean and
contamination free in a closed loop. The hybrid wet/dry products cool the
liquid to be cooled by efficiently combining dry sensible air cooling with
evaporative cooling. These products include two or more distinctive heat
transfer surfaces or sections combined into one product optimising the use
of the ambient dry and wet bulb temperature.
DRY COOLERS
Dry fluid coolers (DFC) cool the liquid in a
closed circuit by means of sensible heat
transfer from the high-density finned
coil block to the air at ambient dry bulb
temperature.
The SpartiumCooler and TrilliumSeries
coolers are dry coolers equipped with an
adiabatic pre-cooler section. Before the air
is drawn through the high density finned
coil however, it is pre-cooled adiabatically
as it passes through an evaporative pad
where water is evaporated in the air.

HXI

HFL

130 - 1275 kW

170 - 1870 kW

DFCH

SP

120 - 800 kW

DFCV-AD

340 - 1560 kW

220 - 1620 kW

DFCV

220 - 1500 kW

Water Saving Condensers

2750 - 4025 kW

PCE
540 - 2710 kW

The HXC hybrid condenser offers significant water


savings versus traditional water-cooled and
evaporative condensers. Thanks to the standard
design features the HXC satisfies additional
environmental concerns by minimising also
energy consumption, refrigerant charge and
plume.

CXVE
440 - 2765 kW

VCL
180 - 1380 kW

VXC
60 - 6920 kW

The TrilliumSeries condensers are dry condensers


equipped with an adiabatic pre-cooler section.
Before the air is drawn through the high density
finned coil however, it is pre-cooled adiabatically
as it passes through an evaporative pad where
water is evaporated in the air.

Heat Transfer Products

HXC
545 - 1895 kW

DCV-AD
340 - 1030 kW

The new generation Baltibond hybrid coating


Save up to 33% water and chemicals

Ice Thermal Storage Products


TSU-C/D

TSU-M

325 - 5060 kWh

647 - 2676 kWh

3 good reasons to opt


for the new generation
Baltibond hybrid coating

For easier Maintenance


or lower Energy Consumption

For reduced
Sound Levels

Internal Ladder and Platform

VX Sound Attenuation

5,00

4,00

3,00

33%
typical
saving

1. Save money

Accessories
For increased Safety
and Hygiene

Relative water
consumption

Ice thermal storage products are used to build and


store cooling in the form of ice during periods of
reduced cooling demand. This way the mechanical
refrigeration system needs not to be sized on
peak load but on average conditions. Hence a
smaller refrigeration system with much lower power
requirements and a smaller refrigerant charge can
be selected. Ice thermal storage products can either
be of the internal or external melt type. For
internal melt only glycol solutions can be used as
secondary refrigerant. External melt ice storage
products can use either direct refrigerant feed or
glycol solutions.

Increase the service life of your evaporative


cooling
Reduce water consumption with higher cycles
of concentration
Reduce chemical consumption with higher cycles
of concentration
Experience an economical alternative to SST 304

2,00

1,00

0,00

Galvanized
New generation
Steel
Baltibond hybrid coating

5
Cycles of
concentration

The effect of cycles of concentration


on water and chemical consumption

2. Increase safety

The smooth surface finish


reduces the development of biofilm
facilitates internal cleaning

Filtration System

3. Respect the environment

VL Sound
Attenuation

Removable Fill

Combined
Inlet
Shields

Motor
removal
davit

Reduce chemical and water rejection


Reduce water consumption with higher cycles of concentration

S3000E and S1500E Sound Attenuation

Your BAC Representative :


External ladder and platform

Automatic
Blow-down

Baltiguard Drive System

LOW ENVIRONMENTAL
IMPACT PRODUCTS

Whisper
Quiet fans
Critical
spare parts kit

S 310 v14 EN

For more information :

www.BaltimoreAircoil.eu
info@BaltimoreAircoil.eu

The new generation Baltibond hybrid coating


Save up to 33% water and chemicals

Ice Thermal Storage Products


TSU-C/D

TSU-M

325 - 5060 kWh

647 - 2676 kWh

3 good reasons to opt


for the new generation
Baltibond hybrid coating

For easier Maintenance


or lower Energy Consumption

For reduced
Sound Levels

Internal Ladder and Platform

VX Sound Attenuation

5,00

4,00

3,00

33%
typical
saving

1. Save money

Accessories
For increased Safety
and Hygiene

Relative water
consumption

Ice thermal storage products are used to build and


store cooling in the form of ice during periods of
reduced cooling demand. This way the mechanical
refrigeration system needs not to be sized on
peak load but on average conditions. Hence a
smaller refrigeration system with much lower power
requirements and a smaller refrigerant charge can
be selected. Ice thermal storage products can either
be of the internal or external melt type. For
internal melt only glycol solutions can be used as
secondary refrigerant. External melt ice storage
products can use either direct refrigerant feed or
glycol solutions.

Increase the service life of your evaporative


cooling
Reduce water consumption with higher cycles
of concentration
Reduce chemical consumption with higher cycles
of concentration
Experience an economical alternative to SST 304

2,00

1,00

0,00

Galvanized
New generation
Steel
Baltibond hybrid coating

5
Cycles of
concentration

The effect of cycles of concentration


on water and chemical consumption

2. Increase safety

The smooth surface finish


reduces the development of biofilm
facilitates internal cleaning

Filtration System

3. Respect the environment

VL Sound
Attenuation

Removable Fill

Combined
Inlet
Shields

Motor
removal
davit

Reduce chemical and water rejection


Reduce water consumption with higher cycles of concentration

S3000E and S1500E Sound Attenuation

Your BAC Representative :


External ladder and platform

Automatic
Blow-down

Baltiguard Drive System

LOW ENVIRONMENTAL
IMPACT PRODUCTS

Whisper
Quiet fans
Critical
spare parts kit

S 310 v14 EN

For more information :

www.BaltimoreAircoil.eu
info@BaltimoreAircoil.eu

VXI
Closed circuit cooling towers
Construction details
1. Material options
Heavy-gauge hot-dip galvanized steel is used for external unit steel
panels and structural elements featuring Baltiplus Corrosion
Protection.
The unique Baltibond hybrid coating is an optional extra. A hybrid
polymer coating for longer service life, applied pre-assembly to all hotdip galvanized steel components of the unit.
Optional stainless steel panels and structural elements of type 304
or 316 for extreme applications.
Or the economical alternative: a water-contact stainless steel cold
water basin. Its key components and the basin itself are stainless
steel. The rest is protected with the Baltibond hybrid coating.

2. Heat transfer media


Our heat transfer media is a cooling coil. In comprehensive lab
thermal performance tests, it showed proved thermal cooler
performance and offers you unrivalled system efficiency.
The coil is constructed of continuous length of prime surface steel, hotdip galvanized after fabrication. Designed for maximum 10 bar
operating pressure according to PED.
Try our optional extended surface coils with selected rows, finned
at 3 to 5 fins per inch and hot-dip galvanized after fabrication, for dry
operation during winter time.
Optional stainless steel coils are in type 304L or 316L.

This file has been generated from the BAC website on: 22-08-2014
For more up to date information, visit: https://www.baltimoreaircoil.eu/products/VXI-construction-details

3. Air movement system


With motor-driven centrifugal fan and a V-belt drive. You can easily
remove the entire motor base for proper belt tensioning to ensure
constantly correct belt alignment. Together with the heavy duty fan
shaft bearings this guarantees optimal operational efficiency. Singleand multi speed motors available.
Centrifugal fan(s) are forward-curved and nearly noiseless.
Overcome external static pressure! Use sound attenuators and duct
work etc. for air intake/discharge with no loss of thermal performance!
Our drift eliminators come in UV-resistant plastic, which will not rot,
decay or decompose and their performance is tested and certified by
Eurovent. They are assembled in easily handled and removable
sections, for optimal internal access.
Steel eliminators, protected with the unique Baltibond hybrid coating,
for optimal corrosion protection, are also available for specific
applications.

4. Water distribution system


These consist of:
A header and spray branches with wide non-clog plastic
nozzles, secured by rubber grommets. You can easily remove, clean
and flush both nozzles and spray branches.
A cold water basin with:
- strainers which are easy to lift out and the anti-vortexing device also
helps stop trapped air
- mechanical make up
- circular access door
Close coupled, bronze fitted centrifugal spray pump with totally
enclosed fan cooled (TEFC) motor. Bleed line with metering valve
installed from pump discharge to overflow.

Like to know more about the VXI construction details? Contact your
local BAC representative.

This file has been generated from the BAC website on: 22-08-2014
For more up to date information, visit: https://www.baltimoreaircoil.eu/products/VXI-construction-details
Powered by TCPDF (www.tcpdf.org)

VXI
Closed circuit cooling towers

Key benefits

VXI characteristics
Counter flow, centrifugal fan, forced draft

Reliable
Quiet
Compact

Capacity range
up to 2615 kW

Maximum entering fluid temperature


82C

Typical applications
Small to medium HVAC and industrial applications
Tight enclosures and installations requiring a single air inlet
Indoor installations
Sound critical installations
High temperature industrial application
Dry operation in winter time

This file has been generated from the BAC website on: 07-07-2014
For more up to date information, visit: http://www.baltimoreaircoil.eu/products/VXI

Reliable operation guaranteed


Since 1978, thousands globally installed, proving the VXI coolers reliability
Fans, motor and drive system (V-belt) are located in the dry air , preventing moisture and condensation.
No external moving parts, helping it withstand the toughest weather.
Various corrosion-resistant materials, including the unique Baltibond hybrid coating for guaranteed long
service life.
Optional extended surface coil with steel fins for dry operation

Ideal for a quiet operation


VXI closed circuit cooling towers include quiet internal centrifugal fans for minimal surrounding noise.
Single-side air inlet, and a quieter tower rear for more noise-sensitive areas.
Cut operation noise still further with factory-designed and tested sound attenuators.

More compact
Compact design for confined spaces,
Single-side air inlet lets you install next to solid walls,
Units housable indoors thanks to centrifugal fans allowing intake or discharge ductwork.

Reduced shipping, rigging and installation costs


VXI units are factory-assembled. We ship larger models in 2 sections to reduce the size and weight of the
heaviest section for easy on-site assembly with smaller cranes
Single fan side requiring fewer motor starters to install and wire.
VXI offers high capacity and minimal operating weight. Save on steel supports, both underneath the
equipment and in the building itself for rooftop installations.
VXI-C models can be container-shipped (in 10 containers). Fan enclosures shippable loose in the
tower bottom section for easy on-site assembly.

Interested in the VXI cooling tower for cooling your process fluid? Contact your local BAC
representative.

Downloads
M - VX (ES)
R - VX (EN)

This file has been generated from the BAC website on: 07-07-2014
For more up to date information, visit: http://www.baltimoreaircoil.eu/products/VXI
Powered by TCPDF (www.tcpdf.org)

VXI
Closed circuit cooling towers
Principle of operation

Warm process fluid (1) enters through a heat exchange coil (2) and
gets water sprayed on by the spray system (3) at the top of the cooling
tower. At the same time the centrifugal fan (4), located at the bottom of
the unit, blows ambient air upwards (5) through the tower. During
operation, heat is transferred from the internal circuit coil to the water,
and then to the atmosphere as a portion of the water that evaporates.
The cooled down fluid then exits the unit (6). The tower sump (7) or
basin collects the remaining water. The spray water pump
(8) recirculates the water up to the water spray system. The warm
saturated air (9) leaves the tower through the drift eliminators (10) ,
which remove water droplets from the air.

You want to use the VXI cooling tower to cool your process fluid?
Contact your local BAC representative for more information.

This file has been generated from the BAC website on: 07-07-2014
For more up to date information, visit: http://www.baltimoreaircoil.eu/products/VXI-principle-of-operation
Powered by TCPDF (www.tcpdf.org)