Professional Documents
Culture Documents
SUMMARY
The Distributed Generation (DG) Intertie Protection, also known as DG Fault interconnection
protection, merits particular attention when connecting DGs in distribution networks. Its main purpose
is to disconnect the DG as soon as possible upon the inception of an area-EPS fault. The relatively
large fault currents that may be contributed by the synchronous DGs, even under the sole influence of
its flux dynamics, constitute the objective of this investigation. These contributions may expose nearby distribution system fuses to danger and compromise host-feeder fuse-saving schemes. On the other
hand, detection of faults whose signature is low-magnitude fault currents is not trivial despite their
reduced shock impact on the system infrastructure. Low magnitude fault currents, typically caused by
elevated arc/ground fault resistances at rather remote fault locations near feeder extremities, present a
difficult to meet protection requirement and can be quite challenging to both area-EPS and DG Fault
Interconnection protection. This article describes a methodology for training and setting Intelligent
Relays that fulfills the fundamental DG Intertie protection requirements by detecting all types of shunt
fault types occurring anywhere within the geographical span of the distribution feeder the DG is
connected at. The fault types investigated in this article are Three Phase (LLL), Single Line to Ground
(SLG), Line to line (LL) and Line to line to ground (LLG) shunt faults with and without arc/ground
resistances, on solidly grounded distribution feeders. An equally fundamental requirement the
intelligent relay must, by design, meet is that it avoids DG nuisance trips under non-faulted system
conditions. The performance of the Intelligent Relays, based on indices quantified per the abovementioned considerations is compared against the performance of several variants of over-current
relays.
KEYWORDS
Synchronous Distributed Generation, DG Fault Interconnection Protection, Intertie Protection, Shunt
Faults, Intelligent Relay, Arcing impedance, Ground Impedance, Multivariate Analysis, Data Mining,
Dependability, Security, Data Mining, Decision Trees, Arc Resistance
Si = {[ X i1 ]T , [ X i2 ]T , [ X i3 ]T ,......[ X iN ]T }
x1 = I A
x2 = I B
x3 = I C
Phase-A
Sym-RMS Current
Phase-B
Sym-RMS Current
Phase-C
Sym-RMS Current
x4 = I1
x5 = I 2
x6 = I 0
I0 > 3.74
YES
NO
I1 > 126.43
I2 > 27.80
NO
YES
NO
LL Fault
NO
YES
LLL Fault
I2 > 11.90
No Fault
SLG Fault
SLG Fault
LL Fault
YES
NO
No Fault
YES
LLG Fault
I1 > 100.72
NO
YES
NO
I2 > 21.54
I2 > 24.20
I1 > 110.12
NO
YES
YES
LLG Fault
Figure 1 Multi-class Decision Tree for the various shunt fault types.
It is seen that the resultant DT, pretty much in compliance with current practice: a) has selected
sequence currents as the intelligent relay protection handles, b) has used zero sequence currents to
discriminate between ground and phase faults. The Dependability index (DI), of this DT was
determined to be .93 meaning that 93% of the faults within the testing set were recognized as such.
Similarly, its security index, SI, was determined to be 100%, meaning that no non-fault events were
misclassified classified as fault events. The testing set consisted of 23 non-fault events and 34 fault
events of all types, each with fault impedances assuming the discrete values of .001 (practically solid
faults), 2, 3, 8 and 15 . The fact that the Decision Tree classified any fault event as a fault and
tripped the intelligent relay was, by design, sufficient. The misclassified fault events were further
scrutinized and found to be electrically remote form the DG while involving high arc/ground
resistances. The classifier lack of sufficient detection sensitivity and its complex and rather nonintuitive structure, was the motivation to explore the below explained alternative approach.
In this second approach, dedicated two-class DTs were constructed aiming at detecting shunt faults
exclusively on a per type basis. The training events are provided in the Table II. All the events were
simulated at 100% system loading. The faults were introduced at 14 different locations in the feeder,
provided in the Appendix.
Non-faults
31 events
LLL (ABC)
28 events
LL (BC)
28 events
LLG (BCG)
28 events
TRAINING EVENTS
Normal steady state operation
Connection or disconnection of one or group loads
Circuit breakers inadvertent opening operation
LLL faults with Rarc = 0 and 3
DTs were determined for each shunt fault type using non-fault and fault system events. The DTs were
trained, again, for current sequence variables. For example, the LLL DT was constructed using LLL
fault events and non-fault events, per Table II. The resultant DTs are shown in Figure 2.
I1 > 174.83
I2 > 21.20
YES
NO
NO FAULT
NO
NO FAULT
LLL
I2 > 34.34
YES
YES
NO
NO FAULT
LLG
I0 > 3.10
YES
NO
NO FAULT
LL
SLG
Figure 2 Dedicated Two-class Decision trees for all considered shunt fault types
It is readily seen that these DTs are much simpler with LLL, LL, LLG and SLG faults directly
identified by virtue of positive, negative and zero sequence currents exclusively. LLL faults are
symmetrical and the DT uses only positive sequence to detect these faults. LL and LLG faults are
unbalanced and are strongly characterized by negative sequence currents. Lastly, SLG faults DT are
identified by zero sequence currents, their value depending on system neutral grounding/ground
impedances.
A further improvement is, however, possible by producing DTs that feature faulted phase recognition
as well, for recording purposes. Figure 3 depicts these faulted-phase Augmented Decision Trees
(ADTs). They are, clearly, not applicable to LLL faults. The training set used to produce these trees
comprises the events shown in Table II augmented with LL, LLG, and SLG faults simulated on all
different possible phase combinations at 100% system loading. The phase faults had arc resistance of 0
and 2 and ground faults had ground resistance of 0 and 20 . Any differences in thresholds with
respect to the ones of Figure 2 are due to slightly different fault resistances.
I2 > 37.14
NO
I2 > 25.31
YES
NO FAULT
NO
NO FAULT
Ia > 118.2
NO
YES
LL-BC
LL-AC
YES
LLG-BC
YES
NO FAULT
Ia > 181.13
YES
NO
LLG_AB
YES
LLG_AC
YES
SLG-A
Ib > 111.3
Ic > 164.6
NO
LL-AB
YES
NO
Ia > 157.78
NO
Ib > 118.7
NO
I0 > 3.48
NO
SLG-C
YES
SLG-B
Figure 3 Faulted Phase Detection Augmented Decision Trees for LL, LLG, SLG faults
4. PROTECTIVE DEVICE SETTINGS AND PERFORMANCE
The normal phase full load current at the PCC, i.e. at the high voltage side of the DG interconnection
transformer is approximately 80 A (74.74A). The phase over-current relay tripping threshold was
taken to be 1.5 times full-load current, i.e. 120A, the Ground over-current relay pick up threshold was
taken to be 0.75 times the full load current, i.e. 60A and the voltage restraint relay settings were
calculated as = 1.5 / where Ip is the pickup current, Is is the steady state current, Va is the
actual voltage and Vs is the nominal voltage.
The intelligent relay model implementation can be seen in the Figure 4. It has four decision trees for
each fault type. This model detects whether there is a fault or not and sends trip signal if one of the
four decision trees conditions are met.
I1
> 174.83 A
I2
LLL
LL
> 34.35 A
TRIP
I2
>>21.20
2.7 kVA
LLG
I0
> 3.10 A
SLG
Non-faults
69 events
TESTING EVENTS
Normal steady state operation
Connection or disconnection of one or group loads
Circuit breakers inadvertent opening operation
LLL faults with Rarc ranging from 0 to 3
LLL (ABC)
243 events
- LL faults with Rarcranging from 0 and 3
LL (AB,BC,AC)
270 events
- LLG faults with Rarc = 0 to 3 with Rg = 0
LLG (ABG,BCG,ACG)
225 events
- SLG faults with Rg from 0 to 30
SLG (AG,BG,CG)
270 events
Table III: Testing data for determining performance of DTs and conventional protection
Table IV illustrates the performance indices of DTs shown in Figure 2, along with the performance of
the other considered protective devices for all types of faults (whenever applicable). Given the
structure of the intelligent relay, these performance indices reflect the intelligent relay performance as
well. It is seen that in terms of dependability, the intelligent relay performs as well as the other devices
in detecting LLL, LL, and LLG faults, but slightly better for SLG faults. In terms of security the
intelligent relay is capable of correctly identifying the non-fault event of inadvertent CB1 breaker
opening that increases the DG phase current to 150A (its DT trip threshold being 174A) something the
other devices cannot do (interpreting it as a system fault due to the 120 A phase threshold), a fact that
reduces their security indices. The same holds true LL and LLG faults.
Shunt
Fault
Type
LLL
LLG
LL
LG
Intelligent Relay
Relay Indices, %
Phase-O/Current
Relay Indices, %
Voltage Restraint
Relay Indices, %
DI
DI
DI
SI
SI
SI
Ground-Over
Current
Relay Indices, %
DI
SI
100 100
100
97
100
97
N.A.
N.A.
100 100
100
97
100
97
92
100
100 100
100
97
100
97
N.A.
N.A.
100 97
86
97
92
97
88
100
Table IV. Performance indices of protective devices for DTs shown in Figure 2
Figure 5 illustrates the performance indices of all devices for wide varying ground resistance SLG
faults. In terms of the results portrayed in Figure 6, it is seen that the Intelligent Relay retains a
dependability advantage for high-ground resistance faults. No reduction in the tripping performance
indices was observed when testing the Augmented Decision Trees of Figure 3, with the sole exception
of having a single SLG fault event on phase C interpreted as a phase B fault.
5. CONCLUSIONS
A methodology based on multivariate analysis and data mining methods was developed to set
Intelligent Relays for DG Intertie protection. The methodology was based on using sequence and
phase DG fault current contributions as protection handles. It proved capable of credibly capturing the
characteristics of the shunt fault inception phenomenon using a training process that involved standard
trim faults. The methodology provides a readily interpretable relay tripping logic, based on first-cycle
symmetrical RMS sequence fault currents resembling the tripping logic of currently used protective
devices. The capability of the intelligent relay to correctly trip for faults on other system phases has
also been demonstrated. The intelligent relay can also be trained to identify the system phase involved
in the various types of faults. The performance of the intelligent relay was found to be at par with the
remaining considered protective devices with a definite advantage for high-ground resistance faults.
7
Transformer 1
15 MVA
114.3 kV/24.94 kV
R = 0.2888 %
X = 7.464% B1
B2
CB-1
DL-01
B4
B3
B5
B9
B8
B7
DL-08
DL-06
DL-04
DL-03
DL-02
DL-09
B11
B10
CB-2
DL-15
DL-10
B12
DL-16
B13
DL-17
GY
L-02
L-03
L-05
L-04
L-09
L-10
DL-11
DL-07
DL-13
L-06
L-07
DL-12
L-01
DL-05
120 kV
SC Level =1000 MVA
X/R ratio = 10
A 5 MVA 4.16 kV synchronous generator supplies 30% of the system load in addition to auxiliary
load of 250 kW. The DG operates in power factor control mode and maintains 0.95 lagging power
factor at the PCC. It is connected to the distribution system through a 12 MVA, 25 kV/4.16 kV /Yg
transformer.
B6
L-12
L-15
L-16
L-17
L-13
L-11
DL-14
GY
C1
1.2 MVAR
L-08
Transformer 2
12 MVA
24.94 kV/4.16 kV
R = 0.8956 %
X = 8.956 %
B14
L-14
250 kW
Generator 1
5000 kVA/4.16 kV
Xd =3.12 pu
Xd = 0.592 pu
Xd = 0.354 pu