Minicontactors
Type CI 5-
Technical brochure
Technical brochure
Mini Contactors CI 5-
IC.PD.C10.F1.02-520B3254
Technical brochure
Minicontactor type CI 5-
Contents
Page
Minicontactor CI 5Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Ordering. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Auxiliary contact blocks CI 5- . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Accessories for minicotators CI 5- . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Thermal overload relay TI 9C-5
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Ordering. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Construction standards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Rated life . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Approvals and standards. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Electrical life curves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
Tripping graph. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
Contact symbols and control relays terminal markings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Main circuit. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Power loss . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Short circuit coordination . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Control circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
UL specications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Dimensions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
IC.PD.C10.F1.02-520B3254
Technical brochure
Mini Contactors CI 5-
Introduction
Ordering
AC-3 load
Ue
Ue
230-240 V 400-690 V
kW
kW
1.5
1.5
3.0
3.0
3.0
3.0
3.0
1
)
)
)
4
)
2
3
2.2
2.2
4.0
4.0
4.0
5.5
5.5
104)
104)
14
14
14
14
14
14
14
4.9
4.9
8.5
8.5
8.5
11.5
11.5
Ithe3)
(AC-1)
Encl.
A
Main
contacts
number
A
64)
64)
11
11
11
11
11
11
11
3
3
3
3
4
3
3
Built-in
auxiliary
contacts
Number/
Function
Code no.1)
Type
4 NO
2 NO, 2 NC
1 NO
1 NC
1 NO
1 NC
1 NO
1 NC
037H3500
037H3501
037H3502
037H3503
037H3504
037H3505
037H3506
037H3507
037H3508
CI 5-2 40E4)
CI 5-2 22Z4)
CI 5-5 10
CI 5-5 01
CI 5-9 10
CI 5-9 01
CI 5-9 M40
CI 5-12 10
CI 5-12 01
Coil voltage/frequency or Sux no. (see table below) must be added to the Danfoss code no.
The thermal current value lth gives the maximum load at 40C, which corresponds to installing the contactor in air (open).
The thermal current value lthe gives the maximum load at 60C, corresponding installing the contactor inside an enclosure.
Control relay , rating according to AC-12 category
Sux no.
13
23
32
33
37
Sux no.
*12 V dc
24 V dc
1)
IC.PD.C10.F1.02-520B3254
01
02
Technical brochure
Minicontactor type CI 5-
Auxiliary contact
CBN
Ie
(AC - 15)
A
2
2
2
2
2
Ith *)
(AC - 1)
A
10
10
10
10
10
Ithe *)
(AC - 1)
A
6
6
6
6
6
Ue
Code no.
Type
V
500
500
500
500
500
037H3511
037H3513
037H3514
037H3515
037H3512
CBN 40
CBN 02
CBN 11
CBN 22
CBN 04
*) Ith and Ithe are dened and specied under Technical data
CBN mirror contact block ensures reliable monitoring of the status of the CI 5 contactor according to IEC 60947-4-1.
Comments
Code no.
Mech. interlock
Diode element
037H3510
037H3518
037H3519
037H3516*
037H3521
037H3520
Mechanical interlock
RC element
RC element
RCN
Clip-on timer
Clip-on timer
ETN-ON
Snap-in Card
037H3517*
IC.PD.C10.F1.02-520B3254
Technical brochure
Mini Contactors CI 5-
Thermal overload relay TI 9C-5 is used with minicontactor CI 5 for protection of squirrel cage
motors where compactness is required. The relay
have single phase protection, i.e. accelerated
release if phase drop-out occurs.
This is particularly important for motors with delta
connected windings.
Other features of TI 9C-5 :
stop/ reset button
manual/automatic reset
test button
double scale for direct start or Y/D start
galvanically isolated signal contact
Introduction
Ordering
Range
Max. fuse 1)
Motor
starter
Y/Dstarter
0.13 - 0.20
0.19 - 0.29
0.27 - 0.42
0.4 - 0.62
0.6 - 0.92
0.85 - 1.3
1.2 - 1.9
1.8 - 2.8
2.7 - 4.2
4.0 - 6.2
6.0 - 9.2
gl, gL, gG
BS 88, type T
type 1
A
type 2
A
type 1
A
type 2
A
3.2 - 4.8
4.7 - 7.3
6.9 - 10.7
10 - 16
25
25
25
25
25
25
25
25
25
35
50
2
2
4
4
6
6
16
20
20
32
32
32
32
32
32
32
32
32
40
50
2
2
4
6
6
10
10
20
25
25
1
1
1
1
3
3
6
15
15
15
35
Code no.
Type
047H3130
047H3131
047H3132
047H3133
047H3134
047H3135
047H3136
047H3137
047H3138
047H3139
047H3140
TI 9C-5
1)
2)
In accordance with HRC form II, TI 9C and TI 12C is suitable for operation in Canada and the USA.
HRC2)
Form
II
IC.PD.C10.F1.02-520B3254
Example:
Full load current: 9A
- With direct start the suitable motor starter
range is 6.0 9.2A, i.e. thermal overload relay
047H3134
- With Y/D start, the suitable motor starter
range is 6.9 10.7, i.e. thermal overload relay
047H3139
Technical brochure
Minicontactor type CI 5-
Construction standards
CI 5- General data
Rated impulse voltage
withstand
Uimp
[kV]
6
CI 5-5, -9,-12
CI 5-5, -9, -12 and CBN
Ambient temperature
Ambient temperature
Type
Operation
25C ... +60C
CI 5-
Storage/Transport
55C ... +80C
Type
CI 51)
2)
Shock2)
5g, 30ms
Environment
Type
Temperature
compensated
Ambient
temperature
Vibration
-5 ... +40 C
2 g at 200 Hz
TI 9C-5
Shock
perpendicular to
contact system
9 g for 7.5 ms
Max.
operations
per hour
30
Mounting direction
Rated life
Type
Mechanical life
Electrical life
AC-3 load
Operations
CI 5-2
CI 5-5
CI 5-9
CI 5-12
15 x 106
15 x 106
0.7 x 106
UL approvals :
CI 5- :
TI 9C-5 :
cULus
cULus
CE
IC.PD.C10.F1.02-520B3254
Electrical life
AC-15 load
Operations
0.7 x 106
600
Technical brochure
Mini Contactors CI 5-
IC.PD.C10.F1.02-520B3254
Technical brochure
Minicontactor type CI 5-
Tripping graph
TI 9C-5
3-phase overload
1)
Measure overload current
2)
Find the overload factor (x) by dividing the measured
value by the set value of the thermal overload relay
(motor full load current).
3)
Find (x) on the horizontal axis and follow a line vertically
up until it intersects the upper curve.
4)
From the intersection point, follow a horizontal line to
the left and read o on the vertical axis the time that
will elapse before the thermal overload relay cuts out
the motor.
Explanation of graphs
Mean value curves
Upper curve: 3-phase tripping and asymmetric load
tripping at min. setting.
Lower curve: Asymmetric load tripping at max. setting.
When tripping from the operationally warm condition,
the tripping times are approx. 30% of the values shown.
These values apply at an ambient temperature = 20C.
measured current
3-phase tripping: x = rated
motor current
Asymmetric load tripping: x =
measured current
max. scale value on
overload relay
IC.PD.C10.F1.02-520B3254
Mini Contactors CI 5-
Auxiliary contacts
Technical brochure
Contactors
Contactor
CI 5-5 10, CI 5-9 10, CI 5-12 10
Contactors
CI 5-9 M40
10
IC.PD.C10.F1.02-520B3254
Contactor
CI 5-5 01, CI 5-9 01, CI 5-12 01
Technical brochure
Minicontactor type CI 5-
Main circuit
Single
core
Type
Connection method
2
1)
2)
with
terminal sleeve
without
terminal sleeve
Recommended
Tightening
torque
[mm ]/ [AWG]
[mm ]
[mm ]
[Nm] / [lb-in]
1)
CI 5-
1-4 / 18-12
0.75-2.5
1.2 /10.6
TI 9C-5
0.75 - 4
0.75 - 4
1-4
0.8 - 2
Type
CI 5-5
CI 5-9
CI 5-12
230-240 V
400-415 V
500 V
690 V
6.3
4.9
3.9
2.8
kW
1.5
2.2
2.2
2.2
11.3
8.5
6.8
4.9
kW
11.3
11.5
9.2
6.7
kW
5.5
5.5
5.5
Type
CI 5-5
CI 5-9
CI 5-12
230-240 V
400-415 V
2.3
500 V
1.9
kW
0.37
0.75
0.75
3.2
3.9
3.6
kW
0.75
1.5
1.5
3.9
3.6
3.2
kW
0.75
1.5
1.5
Star-delta starting
Rated loads at 50 Hz
Type
CI 5-5
CI 5-9
CI 5-12
230-240 V
400-415 V
500 V
690 V
11.3
8.5
6.8
4.9
kW
20
15.5
12.4
8.9
kW
5.5
7.5
7.5
7.5
Type
CI 5-5
CI 5-9
CI 5-12
230 V
240 V
400-415 V
500 V
600 V
20
20
20
20
20
kW
8.3
14
17
24
Type
CI 5-5
CI 5-9
CI 5-12
230 V
240 V
400 V
415 V
500 V
690 V
16
16
16
16
16
16
kW
6.4
6.7
11
12
14
19
24...240 V
230...500 V
230...690 V
24...240 V
230...500 V
230...690 V
10
10
10
IC.PD.C10.F1.02-520B3254
11
Technical brochure
Mini Contactors CI 5-
Type
24 V/ 48 V/ 120 V
230 V/ 240 V
400 V
480 V/ 500 V
600 V/ 690 V
1.2
0.6
CI 5-2
Type
CI 5-5
CI 5-9
CI 5-12
230-240 V
400 V/ 415 V
500 V
2.9
2.4
1.8
600 V
-
kV A
1.2
1.7
1.7
5.4
4.1
3.2
kV A
2.8
2.8
5.4
5.4
3.2
kV A
3.4
3.4
AC-7a
AC-7b
AC-8a
230 V
400 V
230 V
400 V
400 V
CI 5-5
20
20
11
500 V
10
CI 5-9
20
20
11
11
18
15
CI 5-12
20
20
11
11
18
15
Switching lighting
Incandescent lamps
Max. operating current at 230/240 V
[A]
Type
CI 5-5
CI 5-9
CI 5-12
open
closed
10 kA
20 kA
18
14.5
750
400
12
24 V
48/ 60 V
110 V
220 V
440V
24 V
48/ 60 V
110 V
220 V
440 V
CI 5-5
0.8
0.15
0.6
0.1
CI 5-9
1.2
0.2
0.1
CI 5-12
1.2
0.2
0.1
IC.PD.C10.F1.02-520B3254
Technical brochure
Minicontactor type CI 5-
24 V
48/60 V
110 V
220 V
440 V
1-pole
2-pole
3-pole
1-pole
2-pole
3-pole
1-pole
2-pole
3-pole
1-pole
2-pole
3-pole
1-pole
2-pole
3-pole
CI 5-5
4/1
0.6
0.2
0.8
0.08
0.2
0.4
CI 5-9
CI 5-12
6/1.5
0.3
1.2
0.1
0.3
0.6
Continuous current
Type
CI 5-2
Power loss
24 V AC
2.3
400 V/ 440 V
0.15
600 V
0.1
CI 5-2
6.5
2.6 1)
CI 5-5
2.2
0.3
CI 5-9
CI 5-12
2.2
0.9
1)
Type
TI 9C-5
48 V AC
1
Type
CI 5-5
CI 5-9
CI 5-12
IC.PD.C10.F1.02-520B3254
Average power
Min. setting
Max. setting
Typically 2.15 W
Typically 4.87 W
Type 1
50 kA
Available
Fault current
35
Type 2
16
35
20
35
20
13
Technical brochure
Mini Contactors CI 5-
Control circuit
Connections, auxiliary contacts
Type/ Application
[mm2] / [AWG]
Recommended
Tightening
torque
[Nm] / [lb-in]
Single core
Connection method
Multi core
CI 5- built in
1...4 / 18...12
0.75...2.5
1.2 / 10.6
CBN for CI 5-
1...4 / 18...12
0.75...2.5
1.2 / 10.6
TI 9C-5
0.75-2.5
0.75-1.5
0.75...1.5
0.78-1
Comments
AC-15
AC-12
24 V - 120 V
240 V
400 V
480 V
500 V
600 V
690 V
40C
60C
CI 5-
Built into
contact
1.8
1.5
1.4
1.2
10
CBN
For contact
CI 5-
1.2
0.6
0.6
10
Comments
DC-12
12 V
48 V
110 V 125 V
DC-13
220 V 250 V
400 V 440 V
12 V
DC-14
48 V
110 V 125 V
220 V 250 V
400 V 440 V
12 V
48 V
110 V 125 V
220 V 250 V
400 V 440 V
CI 5-
Built
into
contact
0.6
0.2
0.08
2.5
0.4
0.12
0.05
2.8
1.2
0.55
0.27
0.15
CBN
For
contact
CI 5-
2.3
0.55
0.27
0.15
Coil consumption
Inrush power
Type
CI 51)
2)
AC
Holding power
DC
VA
35
32
AC
W
31)
2.62)
VA
1.8
31)
Pull-in voltage
Drop-out voltage
DC
AC
DC
AC
(0.85...1.1) US
(0.8...1.1) US
(0.2...0.75) US
(0.1...0.75) US
2.62)
DC
cold
warm
Break time
AC
DC
AC
AC+RC module
DC
DC+integrated diode
ms
ms
ms
ms
ms
ms
ms
15...40
18...40
15...33
15...28
6...12
8...12
35...50
Comments
overvoltage factor
n = Umax/Un
1 - 2.5
TI 9C-5
14
Load
Max. fuse
AC-15
DC-13
, gL, gG
Bs 88 type T
500 V
2A
200 VA
250 V
2A
20 W
4A
6A
IC.PD.C10.F1.02-520B3254
DC+external diode
Technical brochure
Minicontactor type CI 5-
General
purpose
current
(enclosed)
3-phase
115 V
230 V
200 V
230 V
460 V
575 V
[A]
[A]
[HP]
[A]
[HP]
[A]
[HP]
[A]
[HP]
[A]
[HP]
[A]
[HP]
CI 5-5
12
9.8
0.5
6.9
1.5
1.5
4.8
3.9
CI 5-9
15
9.8
0.5
10
1.5
7.8
6.8
7.6
6.1
CI 5-12
18
13.8
0.75
12
11
9.6
11
7.5
7.5
Type
200 V
230 V
460 V
CI 5-5
2.5
2.5
575 V
5
CI 5-9
3.3
3.3
8.5
8.5
CI 5-12
12
12
Comments
CI 5-2
AC
DC
max. 600
B600
max. 600
Q600
CI 5, 9, 12
max. 600
A600
max. 600
Q600
CBN
For contact CI 5-
max. 600
B600
max. 600
Q600
IC.PD.C10.F1.02-520B3254
15
Technical brochure
Minicontactor type CI 5-
Dimensions
Contactor CI 5-
IC.PD.C10.F1.02-520B3254
16