Professional Documents
Culture Documents
Avionics ventilation
Figure 5. Simplified avionics cooling schematic
If a fault occurs with one of the fans, a FAULT light will illuminate on the
associated button (Figure 6, Avionics ventilation controls (1)). The
BLOWER FAULT light is also used to indicate a duct overheat. Selecting
OVRD puts the system in closed-circuit configuration and opens the air
conditioning inlet valve so that air conditioned air assists with the
cooling. If the BLOWER button is in OVRD, the blower fan is stopped. If
the EXTRACT button is in OVRD, the extract fan is controlled directly
from the pushbutton and both fans continue to run. {TODO: There
appears to be a conflict between the text and the diagram with regards
to the action of the skin exchange inlet bypass valve when EXTRACT is in
OVRD. The diagram essentially indicates air con as sole intake and no
exhaust!}
A smoke detector is situated immediately upstream of the extract fan. If
smoke is detected both FAULT lights come on. Selecting OVRD on both
buttons puts the system in smoke removal mode. This is similar to opencircuit except the intake air is provided by the air-conditioning rather
than from outside the aircraft and the blower fan is stopped.