Short Circuit and Protective

Device Coordination Study


for
XYZ Corp.
New York, NY
Date:

Prepared by:

SDM METRO
220 Maple Ave
Rockville Centre, NY 11570
Tel: 516-536-2600

Prepared for

Tabs
1

Short Circuit and Coordination Study Overview

One Line Drawing(s)


Input Data Report

Fault Analysis Summary Report - Normal

Fault Analysis Summary Report - Emergency

Protective Device Evaluation Report

Time Current Curves - Normal

Time Current Curves - Emergency

Component Setting Report(s)

Short Circuit and Protective Device Coordination Study Overview


XYZ Corp., New York, NY

Table of Contents
I.

INTRODUCTION

II.

SHORT CIRCUIT STUDY GENERAL INFORMATION

III.

SHORT CIRCUIT STUDY METHODOLOGY

IV.

COORDINATION STUDY GENERAL INFORMATION

V.

COORDINATION STUDY METHODOLOGY

VI.

SHORT CIRCUIT STUDY DATA

VII.

PROTECTIVE DEVICE EVALUATION DATA

VIII.

COORDINATION STUDY DATA

IX.

BASIC DATA AND ENGINEERING ASSUMPTIONS

Page 1

Short Circuit and Protective Device Coordination Study Overview


XYZ Corp., New York, NY

I.

Page 2

INTRODUCTION

This overview will function as a guide for the Short Circuit and Protective Device
Coordination Study for XYZ Corp. The aforementioned study was performed
using the relevant characteristics of the power distribution system at the subject
facility as well as the specific characteristics of the protective devices and other
components of the system.
II.

SHORT CIRCUIT STUDY GENERAL INFORMATION

The primary reason for performing a Short Circuit Study on a power system is to
calculate the available short circuit (fault) current at each bus location to facilitate
the selection of protective device interrupting ratings. A protective device must be
able to interrupt the available short circuit (fault) current (at its location in the
power system) therefore the protective device must have an interrupting rating
equal to or greater than that available short circuit (fault) current. The three
phase symmetrical RMS fault current (balanced fault) is typically considered to
be the maximum available fault current and hence is usually used as the basis
for the selection of protective device interrupting ratings.
The other major reason for performing a Short Circuit Study on a power system
is to calculate the available three phase symmetrical RMS fault current at each
bus location to be used as part of a Protective Device Coordination Study.
III.

SHORT CIRCUIT STUDY METHODOLOGY

The Short Circuit Study was performed using a computer-based software


program: Power Tools for Windows (PTW) by SKM System Analysis, DAPPER
Comprehensive Fault Analysis Module.
The systematic Short Circuit Study methodology begins by developing a system
one-line drawing (within the software program) that defines the electrical
characteristics of the power system. Each of the power system components
(utility sources, induction motors, transformers, cables, protective devices, etc.) is
modeled accordingly. When the study is run the software program places an
assumed three phase fault at each bus location in the system and the available
short circuit (fault) current is calculated for each bus location. The results of the
computer generated study are described below (VI. SHORT CIRCUIT STUDY
DATA).
IV.

COORDINATION STUDY GENERAL INFORMATION

The major reason for performing a Protective Device Coordination Study on a


power system is to determine if the protective devices in that system provide a
system of selective coordination. Coordination is defined as properly localizing a
fault condition to restrict outages to the equipment affected, accomplished by the
choice of selective fault-protective devices.

Short Circuit and Protective Device Coordination Study Overview


XYZ Corp., New York, NY

V.

Page 3

COORDINATION STUDY METHODOLOGY

The Protective Device Coordination Study was performed using a computerbased software program: Power Tools for Windows (PTW) by SKM System
Analysis, CAPTOR Protective Device Coordination Module. The systematic
Protective Device Coordination Study methodology begins by utilizing the system
one-line diagram (developed within PTW for the Short Circuit Study) that defines
the electrical characteristics of the power system. Time vs. current coordination
drawings that display the time-current curve(s) of one or more of the protective
devices to be analyzed are then created. Each of the protective devices is
individually modeled based on its specific time-current characteristics and the
available three phase symmetrical RMS fault current. The results of the computer
generated study are described below (VIII. COORDINATION STUDY DATA).
VI.

SHORT CIRCUIT STUDY DATA

The data generated by the Power Tools for Windows (PTW) DAPPER
Comprehensive Fault Analysis software program consists of the following:
One Line Drawing (Tab 2)
Input Data Report (Tab 2)
Fault Analysis Summary Report - Normal (Tab 3)
Fault Analysis Summary Report - Emergency (Tab 4)
The One Line Drawing shows each of the relevant power system components
(utility sources, induction motors, transformers, cables, protective devices, etc.)
and their interconnections.
The Input Data Report summarizes the bus-to-bus interconnections and data
used in performing the Short Circuit Study. The identification of buses was taken
from the project documents. Each bus represents one of the following: a utility
contribution point, a service end box, a switchboard a panelboard bus, or a motor
connection point.
The Fault Analysis Summary Report - Normal provides the three phase
symmetrical RMS fault current for each major point (bus) in the power system
under normal conditions (when the system is being fed by power from the
utility).
The Fault Analysis Summary Report - Emergency provides the three phase
symmetrical RMS fault current for each major point (bus) in the power system
under emergency conditions (when the system is being fed by power from the
emergency generator).
VII.

PROTECTIVE DEVICE EVALUATION

This evaluation consists of a comparison of the interrupting rating of each of the


protective devices to the available short circuit (fault) current (at its location in the
power system) under normal conditions and emergency conditions. The
results of this evaluation are presented in the Protective Device Evaluation
Report (Tab 5).

Short Circuit and Protective Device Coordination Study Overview


XYZ Corp., New York, NY

VIII.

Page 4

COORDINATION STUDY DATA

The data generated by the Power Tools for Windows (PTW) CAPTOR Protective
Device Coordination Module consists of the following:
Time Current Curves - Normal (Tab 6)
Time Current Curves - Emergency (Tab 7)
Component Setting Reports (Tab 8)
The Time Current Curves - Normal provide protective device coordination data
for the power system under normal conditions (when the system is being fed by
power from the utility) while the Time Current Curves - Emergency provide
protective device coordination data for the power system under emergency
conditions (when the system is being fed by power from the emergency
generator).
The software is programmed to plot the curves such that the right-most point
plotted for any of the individual device curves is at the calculated three phase
symmetrical RMS fault current at the bus that feeds the device.
Regarding fuse-to-fuse coordination, the most accurate and complete way to
ensure coordination is to use the manufacturers (BUSSMANN) Selectivity Ratio
Guide (line-side to load-side). For switchboard MSB, the ratio between the main
fuse (FU-MSB-MAIN), a KRP-C-4000, and the largest feeder fuse (FU-EMDP),
an FRN-R-600, exceeds the 4:1 minimum ratio required between these types of
fuses. Therefore, since all of the feeder fuses are FRN-R type of fuses, it can be
stated that there is selective coordination between the main fuse (FU-PP-RMAIN) and all of the feeder fuses. For panel PP-R, the ratio between the main
fuse (FU-PP-R-MAIN), an FRN-R-400, and the largest feeder fuse (FU-PP-K), an
FRN-R-100, exceeds the 2:1 minimum ratio required between these types of
fuses. Therefore, since all of the feeder fuses are BUSSMANN FRN-R type of
fuses, it can be stated that there is selective coordination between the main fuse
(FU-PP-R-MAIN) and all of the feeder fuses
IX.

BASIC DATA AND ENGINEERING ASSUMPTIONS

Basic data for the studies, including the system configuration and specific details
for the system components were obtained from the following sources:
Con Edison (utility available short circuit contribution)
Project Plans
Equipment Submittals
Emergency Generator Supplier
The following engineering assumptions were made:
In order to facilitate the modeling of the cable taps for the fire pump (CBLFPDISC) and for the fire alarm (CBL-FADISC) the impedance named MAIN
LUGS had to be created (modeled as a 4000 amp bus, 0.1 feet in length).
Where there are multiple branch protective devices of the same frame type
fed from the same bus, we have only presented a time current curve for the
largest branch protective device as this presents the worst case
coordination situation.
Induction motors are connected to the system and running.

Mar 22, 2005


INPUT DATA REPORT
Project: XYZ Corp., New York, NY
-----------------------------------------------------------------------------ALL INFORMATION PRESENTED IS FOR REVIEW, APPROVAL
INTERPRETATION AND APPLICATION BY A REGISTERED ENGINEER ONLY
SKM DISCLAIMS ANY RESPONSIBILITY AND LIABILITY RESULTING
FROM THE USE AND INTERPRETATION OF THIS SOFTWARE.
-----------------------------------------------------------------------------SKM POWER*TOOLS FOR WINDOWS
INPUT DATA REPORT
COPYRIGHT SKM SYSTEMS ANALYSIS, INC. 1995-2003
-----------------------------------------------------------------------------ALL PU VALUES ARE EXPRESSED ON A 100 MVA BASE.

Mar 22, 2005

Page 2

FEEDER INPUT DATA


===============================================================================================================
CABLE
FEEDER FROM
FEEDER TO
QTY VOLTS
LENGTH
FEEDER
NAME
NAME
NAME
/PH L-L
SIZE
TYPE
===============================================================================================================
CBL-ADALFT
BUS-EMDP
NODE-MTR-ADALF
1
208 400.0 FEET
12
Copper
Duct Material:
Magnetic
Insulation Type:
Insulation Class:
THHN
+/- Impedance:
1.87 + J 0.0910 Ohms/1000 ft
1728.92 + J
84.13 PU
Z0
Impedance:
5.89 + J 0.2241 Ohms/1000 ft
5448.78 + J 207.19 PU
CBL-AHU-1

CBL-AHU-2

CBL-AHU-3

CBL-AHU-4

CBL-AHU-5

CBL-ATS1-E

CBL-ATS1-N

CBL-ATS2-E

BUS-MSB
NODE-AHU-1
2
208 150.0
Duct Material:
Magnetic
Insulation Type:
+/- Impedance: 0.0640 + J 0.0497 Ohms/1000 ft
Z0
Impedance: 0.2017 + J 0.1224 Ohms/1000 ft

FEET

BUS-MSB
NODE-AHU-2
1
208 150.0
Duct Material:
Magnetic
Insulation Type:
+/- Impedance: 0.0552 + J 0.0495 Ohms/1000 ft
Z0
Impedance: 0.1739 + J 0.1219 Ohms/1000 ft

FEET

BUS-MSB
NODE-AHU-3
1
208 150.0
Duct Material:
Magnetic
Insulation Type:
+/- Impedance: 0.0552 + J 0.0495 Ohms/1000 ft
Z0
Impedance: 0.1739 + J 0.1219 Ohms/1000 ft

FEET

BUS-MSB
NODE-AHU-4
2
208 150.0
Duct Material:
Magnetic
Insulation Type:
+/- Impedance: 0.0640 + J 0.0497 Ohms/1000 ft
Z0
Impedance: 0.2017 + J 0.1224 Ohms/1000 ft

FEET

BUS-MSB
NODE-AHU-5
1
208 150.0
Duct Material:
Magnetic
Insulation Type:
+/- Impedance: 0.0552 + J 0.0495 Ohms/1000 ft
Z0
Impedance: 0.1739 + J 0.1219 Ohms/1000 ft

FEET

BUS-GEN
NODE-ATS1-E
2
208
60.0
Duct Material:
Magnetic
Insulation Type:
+/- Impedance: 0.0378 + J 0.0491 Ohms/1000 ft
Z0
Impedance: 0.1191 + J 0.1209 Ohms/1000 ft

FEET

BUS-MSB
NODE-ATS-1-N
2
208
30.0
Duct Material:
Magnetic
Insulation Type:
+/- Impedance: 0.0378 + J 0.0491 Ohms/1000 ft
Z0
Impedance: 0.1191 + J 0.1209 Ohms/1000 ft

FEET

BUS-FADISC-E
NODE-ATS2-E
1
208
55.0
Duct Material:
Magnetic
Insulation Type:
+/- Impedance:
1.18 + J 0.0854 Ohms/1000 ft
Z0
Impedance:
3.72 + J 0.2103 Ohms/1000 ft

FEET

4/0

Copper
Insulation Class:
11.09 + J
8.62 PU
34.97 + J
21.22 PU
Copper
Insulation Class:
19.14 + J
17.16 PU
60.29 + J
42.26 PU

THHN

250

Copper
Insulation Class:
19.14 + J
17.16 PU
60.29 + J
42.26 PU

THHN

250

Copper
Insulation Class:
11.09 + J
8.62 PU
34.97 + J
21.22 PU

THHN

4/0

Copper
Insulation Class:
19.14 + J
17.16 PU
60.29 + J
42.26 PU

THHN

250

Copper
Insulation Class:
2.62 + J
3.40 PU
8.26 + J
8.38 PU

THHN

350

Copper
Insulation Class:
1.31 + J
1.70 PU
4.13 + J
4.19 PU

THHN

350

Copper
Insulation Class:
150.01 + J
10.86 PU
472.76 + J
26.73 PU

THHN

10

THHN

Mar 22, 2005

Page 3

FEEDER INPUT DATA


===============================================================================================================
CABLE
FEEDER FROM
FEEDER TO
QTY VOLTS
LENGTH
FEEDER
NAME
NAME
NAME
/PH L-L
SIZE
TYPE
===============================================================================================================
CBL-ATS2-N
NODE-FADISC
NODE-ATS2-N
2
208
15.0 FEET
10
Copper
Duct Material:
Magnetic
Insulation Type:
Insulation Class:
THHN
+/- Impedance:
1.18 + J 0.0854 Ohms/1000 ft
20.46 + J
1.48 PU
Z0
Impedance:
3.72 + J 0.2103 Ohms/1000 ft
64.47 + J
3.65 PU
CBL-ATS3-E

CBL-ATS3-N

CBL-ELEV

CBL-ELP-1

CBL-EMDP

CBL-FACP

CBL-FADISC

CBL-FADISC-E

BUS-GEN
NODE-ATS3-E
1
208 100.0
Duct Material:
Magnetic
Insulation Type:
+/- Impedance: 0.2020 + J 0.0585 Ohms/1000 ft
Z0
Impedance: 0.6366 + J 0.1440 Ohms/1000 ft

FEET

NODE-FPDISC
NODE-ATS3-N
1
208
26.0
Duct Material:
Magnetic
Insulation Type:
+/- Impedance: 0.2020 + J 0.0585 Ohms/1000 ft
Z0
Impedance: 0.6366 + J 0.1440 Ohms/1000 ft

FEET

BUS-EMDP
NODE-MTR-ELEV
1
208
30.0
Duct Material:
Magnetic
Insulation Type:
+/- Impedance: 0.2020 + J 0.0585 Ohms/1000 ft
Z0
Impedance: 0.6366 + J 0.1440 Ohms/1000 ft

FEET

NODE-XF-45K-S
BUS-ELP-1
1
480
8.0
Duct Material:
Magnetic
Insulation Type:
+/- Impedance: 0.3210 + J 0.0632 Ohms/1000 ft
Z0
Impedance:
1.01 + J 0.1556 Ohms/1000 ft

FEET

NODE-ATS1-O
BUS-EMDP
2
208
8.0
Duct Material:
Magnetic
Insulation Type:
+/- Impedance: 0.0378 + J 0.0491 Ohms/1000 ft
Z0
Impedance: 0.1191 + J 0.1209 Ohms/1000 ft

FEET

NODE-ATS2-O
BUS-FACP
1
208
80.0
Duct Material:
Magnetic
Insulation Type:
+/- Impedance:
1.18 + J 0.0854 Ohms/1000 ft
Z0
Impedance:
3.72 + J 0.2103 Ohms/1000 ft

FEET

NODE-MAIN LUGS NODE-FADISC


1
208
25.0
Duct Material:
Magnetic
Insulation Type:
+/- Impedance:
1.18 + J 0.0854 Ohms/1000 ft
Z0
Impedance:
3.72 + J 0.2103 Ohms/1000 ft

FEET

BUS-GEN
NODE-FADISC-E
1
208
12.0
Duct Material:
Magnetic
Insulation Type:
+/- Impedance:
1.18 + J 0.0854 Ohms/1000 ft
Z0
Impedance:
3.72 + J 0.2103 Ohms/1000 ft

FEET

Copper
Insulation Class:
46.69 + J
13.52 PU
147.14 + J
33.28 PU
Copper
Insulation Class:
12.14 + J
3.52 PU
38.26 + J
8.65 PU

THHN

Copper
Insulation Class:
14.01 + J
4.06 PU
44.14 + J
9.99 PU

THHN

Copper
Insulation Class:
1.11 + J 0.2194 PU
3.51 + J 0.5403 PU

THHN

Copper
Insulation Class:
0.3495 + J 0.4540 PU
1.10 + J
1.12 PU

THHN

350

Copper
Insulation Class:
218.20 + J
15.79 PU
687.65 + J
38.89 PU

THHN

10

Copper
Insulation Class:
68.19 + J
4.93 PU
214.89 + J
12.15 PU

THHN

10

Copper
Insulation Class:
32.73 + J
2.37 PU
103.15 + J
5.83 PU

THHN

10

THHN

Mar 22, 2005

Page 4

FEEDER INPUT DATA


===============================================================================================================
CABLE
FEEDER FROM
FEEDER TO
QTY VOLTS
LENGTH
FEEDER
NAME
NAME
NAME
/PH L-L
SIZE
TYPE
===============================================================================================================
CBL-FP
NODE-ATS3-O
NODE-FP
1
208
5.0 FEET
2
Copper
Duct Material:
Magnetic
Insulation Type:
Insulation Class:
THHN
+/- Impedance: 0.2020 + J 0.0585 Ohms/1000 ft
2.33 + J 0.6761 PU
Z0
Impedance: 0.6366 + J 0.1440 Ohms/1000 ft
7.36 + J
1.66 PU
CBL-FPDISC

CBL-JP

CBL-LP

CBL-LP-1

CBL-LP-2

CBL-PP-1

CBL-PP-R

CBL-RP

NODE-MAIN LUGS NODE-FPDISC


1
208
30.0
Duct Material:
Magnetic
Insulation Type:
+/- Impedance: 0.2020 + J 0.0585 Ohms/1000 ft
Z0
Impedance: 0.6366 + J 0.1440 Ohms/1000 ft

FEET

NODE-FP
NODE-JP
1
208
8.0
Duct Material:
Magnetic
Insulation Type:
+/- Impedance:
1.18 + J 0.0854 Ohms/1000 ft
Z0
Impedance:
3.72 + J 0.2103 Ohms/1000 ft

FEET

BUS-MSB
NODE-XF-150K-P
2
208
16.0
Duct Material:
Magnetic
Insulation Type:
+/- Impedance: 0.0552 + J 0.0495 Ohms/1000 ft
Z0
Impedance: 0.1739 + J 0.1219 Ohms/1000 ft

FEET

NODE-XF-150K-S BUS-LP-1
1
480
15.0
Duct Material:
Magnetic
Insulation Type:
+/- Impedance: 0.0640 + J 0.0497 Ohms/1000 ft
Z0
Impedance: 0.2017 + J 0.1224 Ohms/1000 ft

FEET

BUS-LP-1
BUS-LP-2
1
480
30.0
Duct Material:
Magnetic
Insulation Type:
+/- Impedance: 0.2020 + J 0.0585 Ohms/1000 ft
Z0
Impedance: 0.6366 + J 0.1440 Ohms/1000 ft

FEET

BUS-MSB
BUS-PP-1
2
208
36.0
Duct Material:
Magnetic
Insulation Type:
+/- Impedance: 0.0640 + J 0.0497 Ohms/1000 ft
Z0
Impedance: 0.2017 + J 0.1224 Ohms/1000 ft

FEET

BUS-MSB
BUS-PP-R
2
208
25.0
Duct Material:
Magnetic
Insulation Type:
+/- Impedance: 0.0640 + J 0.0497 Ohms/1000 ft
Z0
Impedance: 0.2017 + J 0.1224 Ohms/1000 ft

FEET

BUS-MSB
NODE-RP-2
2
208
26.0
Duct Material:
Magnetic
Insulation Type:
+/- Impedance: 0.0640 + J 0.0497 Ohms/1000 ft
Z0
Impedance: 0.2017 + J 0.1224 Ohms/1000 ft

FEET

Copper
Insulation Class:
14.01 + J
4.06 PU
44.14 + J
9.99 PU
Copper
Insulation Class:
21.82 + J
1.58 PU
68.76 + J
3.89 PU

THHN

10

Copper
Insulation Class:
1.02 + J 0.9153 PU
3.22 + J
2.25 PU

THHN

250

Copper
Insulation Class:
0.4167 + J 0.3236 PU
1.31 + J 0.7969 PU

THHN

4/0

Copper
Insulation Class:
2.63 + J 0.7617 PU
8.29 + J
1.88 PU

THHN

Copper
Insulation Class:
2.66 + J
2.07 PU
8.39 + J
5.09 PU

THHN

4/0

Copper
Insulation Class:
1.85 + J
1.44 PU
5.83 + J
3.54 PU

THHN

4/0

Copper
Insulation Class:
1.92 + J
1.49 PU
6.06 + J
3.68 PU

THHN

4/0

THHN

Mar 22, 2005

Page 5

FEEDER INPUT DATA


===============================================================================================================
CABLE
FEEDER FROM
FEEDER TO
QTY VOLTS
LENGTH
FEEDER
NAME
NAME
NAME
/PH L-L
SIZE
TYPE
===============================================================================================================
CBL-RP-2
NODE-RP-2
BUS-RP-2
2
208
34.0 FEET
4/0
Copper
Duct Material:
Magnetic
Insulation Type:
Insulation Class:
THHN
+/- Impedance: 0.0640 + J 0.0497 Ohms/1000 ft
2.51 + J
1.95 PU
Z0
Impedance: 0.2017 + J 0.1224 Ohms/1000 ft
7.93 + J
4.81 PU
CBL-RP-SL

CBL-SE

CBL-SEF-1

CBL-SEF-2

CBL-XF-45KVA

MAIN LUGS

NODE-RP-2
BUS-RP-SL
2
208
20.0
Duct Material:
Magnetic
Insulation Type:
+/- Impedance: 0.0640 + J 0.0497 Ohms/1000 ft
Z0
Impedance: 0.2017 + J 0.1224 Ohms/1000 ft

FEET

BUS-PROP. LINE NODE-MAIN LUGS 10


208 320.0
Duct Material:
Magnetic
Insulation Type:
+/- Impedance: 0.0294 + J 0.0466 Ohms/1000 ft
Z0
Impedance: 0.0926 + J 0.1147 Ohms/1000 ft

FEET

BUS-EMDP
NODE-MTR-SEF-1
1
208 250.0
Duct Material:
Magnetic
Insulation Type:
+/- Impedance:
1.18 + J 0.0854 Ohms/1000 ft
Z0
Impedance:
3.72 + J 0.2103 Ohms/1000 ft

FEET

BUS-EMDP
NODE-MTR-SEF-2
1
208
70.0
Duct Material:
Magnetic
Insulation Type:
+/- Impedance:
1.18 + J 0.0854 Ohms/1000 ft
Z0
Impedance:
3.72 + J 0.2103 Ohms/1000 ft

FEET

BUS-EMDP
NODE-XF-45K-P
1
208
11.0
Duct Material:
Magnetic
Insulation Type:
+/- Impedance: 0.1280 + J 0.0540 Ohms/1000 ft
Z0
Impedance: 0.4034 + J 0.1329 Ohms/1000 ft

FEET

NODE-MAIN LUGS BUS-MSB


1
208 0.100
Duct Material:
Bus
Insulation Type:
+/- Impedance: 0.0039 + J 0.0013 Ohms/1000 ft
Z0
Impedance: 0.0232 + J 0.0070 Ohms/1000 ft

FEET

4/0

Copper
Insulation Class:
1.48 + J
1.15 PU
4.66 + J
2.83 PU
Copper
Insulation Class:
2.17 + J
3.45 PU
6.85 + J
8.48 PU

THHN

500

Copper
Insulation Class:
681.86 + J
49.35 PU
2148.90 + J 121.52 PU

THHN

10

Copper
Insulation Class:
190.92 + J
13.82 PU
601.69 + J
34.03 PU

THHN

10

Copper
Insulation Class:
3.25 + J
1.37 PU
10.26 + J
3.38 PU

THHN

1/0

4000
Aluminum
****
Insulation Class:
0.00090 + J 0.00030 PU
0.0054 + J 0.0016 PU

THHN

Mar 22, 2005

Page 6

TRANSFORMER INPUT DATA


=============================================================================================
TRANSFORMER
PRIMARY RECORD
VOLTS
* SECONDARY RECORD
VOLTS
FULL-LOAD
NOMINAL
NAME
NO NAME
L-L
NO NAME
L-L
KVA
KVA
=============================================================================================
XF-150KVA
NODE-XF-150K-P D
208.00
NODE-XF-150K-S YG
480.00 150.00
150.00
Pos. Seq. Z%:
1.94 + J
4.07 12.93 + j 27.13 PU
Zero Seq. Z%:
1.94 + J
4.07 12.93 + j 27.13 PU
Taps Pri. 0.000 % Sec. 0.000 % Phase Shift (Pri. Leading Sec.): 30.00 Deg.
XF-45KVA

NODE-XF-45K-P D
208.00
NODE-XF-45K-S YG
480.00
45.00
Pos. Seq. Z%:
2.73 + J
1.97 60.67 + j 43.78 PU
Zero Seq. Z%:
2.73 + J
1.97 60.67 + j 43.78 PU
Taps Pri. 0.000 % Sec. 0.000 % Phase Shift (Pri. Leading Sec.):

45.00

30.00 Deg.

Mar 22, 2005

Page 7

GENERATION CONTRIBUTION DATA


=====================================================================================
BUS
CONTRIBUTION
VOLTAGE
NAME
NAME
L-L
MVA
X"d
X/R
=====================================================================================
BUS-PROP. LINE UTIL-0001
208.00
43.05
Three Phase
Contribution:
119500. AMPS
3.33
Single Line to Ground Contribution:
0.1000 AMPS
1.0000
Pos Sequence Impedance (100 MVA Base) 0.6675 + J
2.22 PU
Zero Sequence Impedance (100 MVA Base) 5888195. + J 5888192. PU

BUS-GEN

GEN-1
208.00 0.250
0.0900
14.70
Pos Sequence Impedance (100 MVA Base)
2.45 + J
Neg Sequence Impedance (100 MVA Base)
5.17 + J
Zero Sequence Impedance (100 MVA Base)
1.36 + J

36.00 PU
76.00 PU
20.00 PU

Mar 22, 2005

Page 8

MOTOR CONTRIBUTION DATA


=====================================================================================
BUS
CONTRIBUTION
VOLTAGE
BASE
Motor
NAME
NAME
L-L
kVA
X"d
X/R Number
=====================================================================================
BUS-MTR-SEF-2 MTR-SEF-2
208
8.74
0.167
2.94 1.00
Pos Sequence Impedance (100 MVA Base) 650.53 + j 1910.28 PU
NODE-AHU-1

MTRI-AHU-1
208 116.56
0.17
10.0
Pos Sequence Impedance (100 MVA Base)
14.58 + j

1.00
145.84 PU

NODE-AHU-2

MTRI-AHU-2
208
69.94
0.17
10.0
Pos Sequence Impedance (100 MVA Base)
24.31 + j

1.00
243.07 PU

NODE-AHU-3

MTRI-AHU-3
208
69.94
0.17
10.0
Pos Sequence Impedance (100 MVA Base)
24.31 + j

1.00
243.07 PU

NODE-AHU-4

MTRI-AHU-4
208 116.56
0.17
10.0
Pos Sequence Impedance (100 MVA Base)
14.58 + j

1.00
145.84 PU

NODE-AHU-5

MTRI-AHU-5
208
69.94
0.17
10.0
Pos Sequence Impedance (100 MVA Base)
24.31 + j

1.00
243.07 PU

NODE-FP

MTR-FP
Pos

208
23.31
0.167
2.94
Sequence Impedance (100 MVA Base) 243.95 + j

1.00
716.35 PU

NODE-JP

MTR-JP
Pos

208
3.50
0.167
2.94 1.00
Sequence Impedance (100 MVA Base) 1626.32 + j 4775.69 PU

NODE-MTR-ADALF MTR-ADALFT
208
3.50
0.167
2.94 1.00
Pos Sequence Impedance (100 MVA Base) 1626.32 + j 4775.69 PU
NODE-MTR-ELEV

MTR-ELEV
208
17.48
0.167
2.94
Pos Sequence Impedance (100 MVA Base) 325.26 + j

1.00
955.14 PU

NODE-MTR-SEF-1 MTR-SEF-1
208
8.74
0.167
2.94 1.00
Pos Sequence Impedance (100 MVA Base) 650.53 + j 1910.28 PU

Mar 22, 2005

FAULT ANALYSIS SUMMARY REPORT NORMAL


Project: XYZ Corp., New York, NY
-----------------------------------------------------------------------------ALL INFORMATION PRESENTED IS FOR REVIEW, APPROVAL
INTERPRETATION AND APPLICATION BY A REGISTERED ENGINEER ONLY
SKM DISCLAIMS ANY RESPONSIBILITY AND LIABILITY RESULTING
FROM THE USE AND INTERPRETATION OF THIS SOFTWARE.
-----------------------------------------------------------------------------SKM POWER*TOOLS FOR WINDOWS
SHORT CIRCUIT ANALYSIS REPORT
COPYRIGHT SKM SYSTEMS ANALYSIS, INC. 1995-2003
------------------------------------------------------------------------------

Mar 22, 2005

Page 2

***************** F A U L T
A N A L Y S I S
S U M M A R Y ***************
------------------------------------------------------------------------------------------------------------------------------------------------------------BUS NAME
VOLTAGE
AVAILABLE FAULT CURRENT
L-L
3 PHASE
X/R LINE/GRND
X/R
BUS-ELP-1
BUS-EMDP
BUS-FACP
BUS-GEN
BUS-LP-1
BUS-LP-2
BUS-MSB
BUS-PP-1
BUS-PP-R
BUS-PROP. LINE
BUS-RP-2
BUS-RP-SL
NODE-AHU-1
NODE-AHU-2
NODE-AHU-3
NODE-AHU-4
NODE-AHU-5
NODE-ATS-1-N
NODE-ATS1-E
NODE-ATS1-O
NODE-ATS2-E
NODE-ATS2-N
NODE-ATS2-O
NODE-ATS3-E
NODE-ATS3-N
NODE-ATS3-O
NODE-FADISC
NODE-FADISC-E
NODE-FP
NODE-FPDISC
NODE-JP
NODE-MAIN LUGS
NODE-MTR-ADALF
NODE-MTR-ELEV
NODE-MTR-SEF-1
NODE-MTR-SEF-2
NODE-RP-2
NODE-XF-150K-P
NODE-XF-150K-S
NODE-XF-45K-P
NODE-XF-45K-S

480.
208.
208.
208.
480.
480.
208.
208.
208.
208.
208.
208.
208.
208.
208.
208.
208.
208.
208.
208.
208.
208.
208.
208.
208.
208.
208.
208.
208.
208.
208.
208.
208.
208.
208.
208.
208.
208.
480.
208.
480.

1389.6
34588.6
894.6
0.0
3231.2
3073.8
51165.0
32455.0
36644.4
126408.1
25893.0
29369.4
15971.7
9910.6
9910.6
15971.7
9910.6
37122.8
0.0
37122.8
0.0
3030.8
3030.8
0.0
9230.1
9230.1
3903.4
0.0
8583.5
15235.2
5221.7
51169.8
187.5
13379.5
475.3
1480.1
36222.1
41413.1
3273.0
25206.6
1406.2

0.8
1.8
0.1
0.0
2.0
1.8
2.2
1.4
1.6
3.4
1.3
1.3
1.2
1.2
1.2
1.2
1.2
1.9
0.0
1.9
0.0
0.1
0.1
0.0
0.5
0.5
0.1
0.0
0.5
0.6
0.3
2.2
0.3
0.6
0.4
0.2
1.5
1.8
2.0
1.2
0.8

1437.34
0.11
0.11

0.7
1.0
1.0

3410.56
3126.79
0.11
0.11
0.11
0.11
0.11
0.11
0.11
0.11
0.11
0.11
0.11
0.11

2.0
1.6
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0

0.11

1.0

0.11
0.11

1.0
1.0

0.11
0.11
0.11

1.0
1.0
1.0

0.11
0.11
0.11
0.11
0.11
0.11
0.11
0.11
0.11
0.11
3484.51
0.11
1467.66

1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
2.1
1.0
0.8

*********************** FAULT ANALYSIS REPORT COMPLETED ***********************

Mar 22, 2005

FAULT ANALYSIS SUMMARY REPORT EMERGENCY


Project: XYZ Corp., New York, NY
-----------------------------------------------------------------------------ALL INFORMATION PRESENTED IS FOR REVIEW, APPROVAL
INTERPRETATION AND APPLICATION BY A REGISTERED ENGINEER ONLY
SKM DISCLAIMS ANY RESPONSIBILITY AND LIABILITY RESULTING
FROM THE USE AND INTERPRETATION OF THIS SOFTWARE.
-----------------------------------------------------------------------------SKM POWER*TOOLS FOR WINDOWS
SHORT CIRCUIT ANALYSIS REPORT
COPYRIGHT SKM SYSTEMS ANALYSIS, INC. 1995-2003
------------------------------------------------------------------------------

Mar 22, 2005

Page 2

***************** F A U L T
A N A L Y S I S
S U M M A R Y ***************
------------------------------------------------------------------------------------------------------------------------------------------------------------BUS NAME
VOLTAGE
AVAILABLE FAULT CURRENT
L-L
3 PHASE
X/R LINE/GRND
X/R
BUS-ELP-1
BUS-EMDP
BUS-FACP
BUS-GEN
BUS-LP-1
BUS-LP-2
BUS-MSB
BUS-PP-1
BUS-PP-R
BUS-PROP. LINE
BUS-RP-2
BUS-RP-SL
NODE-AHU-1
NODE-AHU-2
NODE-AHU-3
NODE-AHU-4
NODE-AHU-5
NODE-ATS-1-N
NODE-ATS1-E
NODE-ATS1-O
NODE-ATS2-E
NODE-ATS2-N
NODE-ATS2-O
NODE-ATS3-E
NODE-ATS3-N
NODE-ATS3-O
NODE-FADISC
NODE-FADISC-E
NODE-FP
NODE-FPDISC
NODE-JP
NODE-MAIN LUGS
NODE-MTR-ADALF
NODE-MTR-ELEV
NODE-MTR-SEF-1
NODE-MTR-SEF-2
NODE-RP-2
NODE-XF-150K-P
NODE-XF-150K-S
NODE-XF-45K-P
NODE-XF-45K-S

480.
208.
208.
208.
480.
480.
208.
208.
208.
208.
208.
208.
208.
208.
208.
208.
208.
208.
208.
208.
208.
208.
208.
208.
208.
208.
208.
208.
208.
208.
208.
208.
208.
208.
208.
208.
208.
208.
480.
208.
480.

1118.0
7744.9
678.8
8604.4
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
7837.9
7837.9
1448.8
0.0
1448.8
4424.6
0.0
4424.6
0.0
5559.4
4298.0
0.0
3383.3
0.0
187.9
6388.0
476.8
1445.5
0.0
0.0
0.0
7330.2
1127.4

1.1
5.7
0.2
9.4
3.3
2.9
6.0
4.5
4.9
4.9
3.9
4.3
4.1
2.9
2.9
4.1
2.9
5.2
6.0
6.0
0.2
0.5
0.2
1.0
1.5
1.0
0.6
1.0
1.0
2.2
0.7
6.0
0.4
2.0
0.4
0.3
4.9
5.3
3.3
3.9
1.1

1146.06
6366.96
397.92
7361.44

1.1
4.6
0.1
8.5

6472.28
6472.28
858.56

4.8
4.8
0.2

858.56
2853.90

0.2
0.7

2853.90

0.7

3793.70
2752.91

0.7
0.7

2071.12

0.5

99.97
4773.81
253.28
833.40

0.2
1.5
0.2
0.2

5899.51
1162.90

3.0
1.1

*********************** FAULT ANALYSIS REPORT COMPLETED ***********************

Page 1 of 1

Protective Device Evaluation Report


Project: XYZ Corp., New York, NY
Bus
BUS-ELP-1
BUS-ELP-1
BUS-EMDP
BUS-EMDP
BUS-EMDP
BUS-EMDP
BUS-EMDP
BUS-GEN
BUS-GEN
BUS-LP-1
BUS-LP-1
BUS-LP-1
BUS-LP-2
BUS-LP-2
BUS-MSB
BUS-MSB
BUS-MSB
BUS-MSB
BUS-MSB
BUS-MSB
BUS-MSB
BUS-MSB
BUS-MSB
BUS-MSB
BUS-PP-1
BUS-PP-1
BUS-PP-R
BUS-PP-R
BUS-PP-R
BUS-RP-2
BUS-RP-2
BUS-RP-SL
BUS-RP-SL
NODE-FADISC
NODE-FADISC-E
NODE-FPDISC
NODE-MAIN LUGS

Device Name
CB-ELP-1-20A
CB-ELP-1-MAIN
CB-ADALFT
CB-ELEV
CB-SEF-1
CB-SEF-2
CB-XF-45KVA
CB-EMDP-E
CB-FP-E
CB-LP-1-20A
CB-LP-2
CB-LP-1-MAIN
CB-LP-2-20A
CB-LP-2-MAIN
FU-AHU-1
FU-AHU-2
FU-AHU-3
FU-AHU-4
FU-AHU-5
FU-EMDP
FU-PP-1
FU-PP-R
FU-RP
FU-LP
CB-PP-1-100A
CB-PP-1-MAIN
FU-PP-A
FU-PP-K
FU-PP-R-MAIN
CB-RP-2-20A
CB-RP-2
CB-RP-SL-20A
CB-RP-SL-MAIN
FU-FADISC
FU-FADISC-E
FU-FPDISC
FU-MSB-MAIN

Mfr.
SIEMENS
SIEMENS
SIEMENS
SIEMENS
SIEMENS
SIEMENS
SIEMENS
MERLIN GERIN
MERLIN GERIN
SQUARE D
SQUARE D
SQUARE D
SQUARE D
SQUARE D
BUSSMANN
BUSSMANN
BUSSMANN
BUSSMANN
BUSSMANN
BUSSMANN
BUSSMANN
BUSSMANN
BUSSMANN
BUSSMANN
SIEMENS
SIEMENS
BUSSMANN
BUSSMANN
BUSSMANN
SIEMENS
SIEMENS
SQUARE D
SQUARE D
BUSSMANN
BUSSMANN
BUSSMANN
BUSSMANN

Type
BQD
BQD
BL, 2 & 3-Pole
BL, 2 & 3-Pole
BL, 2 & 3-Pole
BL, 2 & 3-Pole
QJ2
Compact NSJ N/H, STR 23SP
Compact NSJ N/H, STR 23SP
ED
ED
KA
ED
KA
FRN-R, Class RK5
FRN-R, Class RK5
FRN-R, Class RK5
FRN-R, Class RK5
FRN-R, Class RK5
FRN-R, Class RK5
FRN-R, Class RK5
FRN-R, Class RK5
FRN-R, Class RK5
JHC, Class J
BL, 2 & 3-Pole
JXD2-A Sentron
FRN-R, Class RK5
FRN-R, Class RK5
FRN-R, Class RK5
BL, 2 & 3-Pole
QJ2
ED
KC
FRN-R, Class RK5
FRN-R, Class RK5
FRN-R, Class RK5
KRP-C, Class L

Bus
Voltage
480
480
208
208
208
208
208
208
208
480
480
480
480
480
208
208
208
208
208
208
208
208
208
208
208
208
208
208
208
208
208
208
208
208
208
208
208

Frame
Voltage
480
480
240
240
240
240
240
240
240
480
480
480
480
480
250
250
250
250
250
250
250
250
250
600
240
240
250
250
250
240
240
240
240
250
250
250
600

Device
Int kA
14
14
10
10
10
10
10
65
65
18
18
25
18
25
200
200
200
200
200
200
200
200
200
200
10
65
200
200
200
10
10
18
100
200
200
200
300

Fault Current
(normal)
1389.6
1389.6
34588.6
34588.6
34588.6
34588.6
34588.6
0.0
0.0
3231.2
3231.2
3231.2
3073.8
3073.8
51165.0
51165.0
51165.0
51165.0
51165.0
51165.0
51165.0
51165.0
51165.0
51165.0
32455.0
32455.0
36644.4
36644.4
36644.4
25893.0
25893.0
29369.4
29369.4
3903.4
0.0
15235.2
51169.8

Fault Current
(emergency)
1118.0
1118.0
7744.9
7744.9
7744.9
7744.9
7744.9
8604.4
8604.4
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
5559.4
0.0
0.0

Status
OK
OK
See Note 1
See Note 1
See Note 1
See Note 1
See Note 1
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
See Note 1
OK
OK
OK
OK
See Note 1
See Note 1
See Note 1
OK
OK
OK
OK
OK

Note 1: The interrupting rating of the circuit breaker is not adequate for the fault current (normal). A "series rating" (between the circuit breaker and the upstream fuse) that
exceeds the fault current (normal) or a breaker with an interrupting rating that exceeds the fault current (normal) should be considered.

Sample Curves

Sample Curves

Mar 22, 2005


Component Setting Report
Project: XYZ Corp., New York, NY
----------------------------------------------------------------------ALL INFORMATION PRESENTED IS FOR REVIEW, APPROVAL, INTERPRETATION,
AND APPLICATION BY A REGISTERED ENGINEER ONLY.
SKM DISCLAIMS ANY RESPONSIBILITY AND LIABILITY RESULTING
FROM THE USE AND INTERPRETATION OF THIS SOFTWARE.
----------------------------------------------------------------------CAPTOR (Computer Aided Plotting for Time Overcurrent Reporting)
COPYRIGHT SKM SYSTEMS ANALYSIS, INC. 1983 - 2003
-----------------------------------------------------------------------------------------

Mar 22, 2005

Page 2

----------------------------------------------------------------------------------------Device Name:
CB-ELP-1-20A
TCC Name:
TCC-ELP-1(20A).tcc
Bus Name:
BUS-ELP-1
Bus Voltage:
480.0V
Function Name:
Phase
Manufacturer:
SIEMENS
Description:
15-100A
Sub Type:
BQD
AIC Rating:
14kA
Fault Duty:
1389.6A
Frame:
BQD 480V 20A
Curve Multiplier: 1.00000
Trip:
20A
Setting: 1) Fixed
----------------------------------------------------------------------------------------Device Name:
CB-ELP-1-MAIN
TCC Name:
TCC-ELP-1(20A).tcc
Bus Name:
BUS-ELP-1
Bus Voltage:
480.0V
Function Name:
Phase
Manufacturer:
SIEMENS
Description:
15-100A
Sub Type:
BQD
AIC Rating:
14kA
Fault Duty:
1389.6A
Frame:
BQD 480V 70A
Curve Multiplier: 1.00000
Trip:
70A
Setting: 1) Fixed
----------------------------------------------------------------------------------------Device Name:
CB-ADALFT
TCC Name:
Bus Name:
BUS-EMDP
Bus Voltage:
208.0V
Function Name:
Phase
Manufacturer:
SIEMENS
Description:
15-125A
Sub Type:
BL, 2 & 3-Pole
AIC Rating:
10kA
Fault Duty:
34588.6A
Frame:
BL 240V 35A
Curve Multiplier: 1.00000
Trip:
15A
Setting: 1) Thermal Curve (Fixed
2) INST
Fixed
(525A)
----------------------------------------------------------------------------------------Device Name:
CB-ELEV
TCC Name:
TCC-EMDP(CB-ELEV).tcc
Bus Name:
BUS-EMDP
Bus Voltage:
208.0V
Function Name:
Phase
Manufacturer:
SIEMENS
Description:
15-125A
Sub Type:
BL, 2 & 3-Pole
AIC Rating:
10kA
Fault Duty:
34588.6A
Frame:
BL 240V 90A
Curve Multiplier: 1.00000
Trip:
80A
Setting: 1) Thermal Curve (Fixed
2) INST
Fixed
(850A)
----------------------------------------------------------------------------------------Device Name:
CB-SEF-1
TCC Name:
Bus Name:
BUS-EMDP
Bus Voltage:
208.0V
Function Name:
Phase
Manufacturer:
SIEMENS
Description:
15-125A
Sub Type:
BL, 2 & 3-Pole
AIC Rating:
10kA
Fault Duty:
34588.6A
Frame:
BL 240V 35A
Curve Multiplier: 1.00000
Trip:
30A
Setting: 1) Thermal Curve (Fixed
2) INST
Fixed
(525A)

Mar 22, 2005

Page 3

----------------------------------------------------------------------------------------Device Name:
CB-SEF-2
TCC Name:
Bus Name:
BUS-EMDP
Bus Voltage:
208.0V
Function Name:
Phase
Manufacturer:
SIEMENS
Description:
15-125A
Sub Type:
BL, 2 & 3-Pole
AIC Rating:
10kA
Fault Duty:
34588.6A
Frame:
BL 240V 35A
Curve Multiplier: 1.00000
Trip:
30A
Setting: 1) Thermal Curve (Fixed
2) INST
Fixed
(525A)
----------------------------------------------------------------------------------------Device Name:
CB-XF-45KVA
TCC Name:
TCC-ELP-1(20A).tcc
Bus Name:
BUS-EMDP
Bus Voltage:
208.0V
Function Name:
Phase
Manufacturer:
SIEMENS
Description:
60-225A
Sub Type:
QJ2
AIC Rating:
10kA ShortTime:10
Fault Duty:
34588.6A
Frame:
QJ2 240V 150A
Curve Multiplier: 1.00000
Trip:
150A
Setting: 1) Thermal Curve (Fixed
2) INST
Fixed
(1750A)
----------------------------------------------------------------------------------------Device Name:
CB-EMDP-E
TCC Name:
TCC-EMDP-E.tcc
Bus Name:
BUS-GEN
Bus Voltage:
208.0V
Function Name:
Phase
Manufacturer:
MERLIN GERIN
Description:
LSI, 150-600A
Sub Type:
Compact NSJ N/H, STR 23SP
AIC Rating:
65kA
Fault Duty:
200000.0A
Frame:
NSJ600N 240V 600A
Curve Multiplier: 1.00000
Sensor:
600A
Plug:
Setting: 1) LTPU (lo x Ir x S)
1 (480A)
0.8
2) LTD (Fixed)
Fixed
3) STPU (2-9 x LTPU)
9
(4320A)
4) STD (Fixed)
Fixed
5) INST (Fixed)
Fixed
(5400A)
Function Name:
Ground
Manufacturer:
MERLIN GERIN
Description:
GF, 150-600A
Sub Type:
Compact NSJ N/H, STR 53UP
AIC Rating:
100kA
Fault Duty:
200000.0A
Frame:
NSJ400H 240V 400A
Curve Multiplier: 1.00000
Sensor:
150A
Plug:
Setting: 1) GFPU (0.2-1.0 x S)
1
(150A)
2) GFD (0.1-0.4)
0.4
I^2 t Out
----------------------------------------------------------------------------------------Device Name:
CB-FP-E
TCC Name:
TCC-FP-E.tcc
Bus Name:
BUS-GEN
Bus Voltage:
208.0V
Function Name:
Phase
Manufacturer:
MERLIN GERIN
Description:
LSI, 150-600A
Sub Type:
Compact NSJ N/H, STR 23SP
AIC Rating:
65kA
Fault Duty:
200000.0A
Frame:
NSJ400N 240V 400A
Curve Multiplier: 1.00000
Sensor:
150A
Plug:
Setting: 1) LTPU (lo x Ir x S)
1 (150A)
1
2) LTD (Fixed)
Fixed
3) STPU (2-9 x LTPU)
9
(1350A)
4) STD (Fixed)
Fixed
5) INST (Fixed)
Fixed
(1350A)

Mar 22, 2005

Page 4

----------------------------------------------------------------------------------------Device Name:
CB-LP-1-20A
TCC Name:
TCC-LP-1(20A).tcc
Bus Name:
BUS-LP-1
Bus Voltage:
480.0V
Function Name:
Phase
Manufacturer:
SQUARE D
Description:
15-125A
Sub Type:
ED
AIC Rating:
18kA
Fault Duty:
3231.2A
Frame:
ED 480V 20A
Curve Multiplier: 1.00000
Trip:
20A
Setting: 1) Fixed
----------------------------------------------------------------------------------------Device Name:
CB-LP-1-MAIN
TCC Name:
TCC-LP-1(20A).tcc
Bus Name:
BUS-LP-1
Bus Voltage:
480.0V
Function Name:
Phase
Manufacturer:
SQUARE D
Description:
70-250A
Sub Type:
KA
AIC Rating:
25kA
Fault Duty:
3231.2A
Frame:
KA 480V 250A
Curve Multiplier: 1.00000
Trip:
225A
Setting: 1) Thermal Curve (Fixed
2) INST (5-10 x Trip)
9.99
(2247.8A)
----------------------------------------------------------------------------------------Device Name:
CB-LP-2
TCC Name:
TCC-LP-2(20A).tcc
Bus Name:
BUS-LP-1
Bus Voltage:
480.0V
Function Name:
Phase
Manufacturer:
SQUARE D
Description:
15-125A
Sub Type:
ED
AIC Rating:
18kA
Fault Duty:
3231.2A
Frame:
ED 480V 100A
Curve Multiplier: 1.00000
Trip:
100A
Setting: 1) Fixed
----------------------------------------------------------------------------------------Device Name:
CB-LP-2-20A
TCC Name:
TCC-LP-2(20A).tcc
Bus Name:
BUS-LP-2
Bus Voltage:
480.0V
Function Name:
Phase
Manufacturer:
SQUARE D
Description:
15-125A
Sub Type:
ED
AIC Rating:
18kA
Fault Duty:
3073.8A
Frame:
ED 480V 20A
Curve Multiplier: 1.00000
Trip:
20A
Setting: 1) Fixed
----------------------------------------------------------------------------------------Device Name:
CB-LP-2-MAIN
TCC Name:
TCC-LP-2(20A).tcc
Bus Name:
BUS-LP-2
Bus Voltage:
480.0V
Function Name:
Phase
Manufacturer:
SQUARE D
Description:
70-250A
Sub Type:
KA
AIC Rating:
25kA
Fault Duty:
3073.8A
Frame:
KA 480V 100A
Curve Multiplier: 1.00000
Trip:
100A
Setting: 1) Thermal Curve (Fixed
2) INST (5-10 x Trip)
10.0
(1000A)
----------------------------------------------------------------------------------------Device Name:
FU-AHU-1
TCC Name:
TCC-AHU-1.tcc
Bus Name:
BUS-MSB
Bus Voltage:
208.0V
Function Name:
Phase
Manufacturer:
BUSSMANN
Description:
FRN-R RK5
Sub Type:
15-600A
AIC Rating:
200kA
Fault Duty:
51165.0A
Cartridge:
FRN-R 250V 400A
Curve Multiplier: 1.00000
Size:
400A

Mar 22, 2005

Page 5

----------------------------------------------------------------------------------------Device Name:
FU-AHU-2
TCC Name:
TCC-AHU-2.tcc
Bus Name:
BUS-MSB
Bus Voltage:
208.0V
Function Name:
Phase
Manufacturer:
BUSSMANN
Description:
FRN-R RK5
Sub Type:
15-600A
AIC Rating:
200kA
Fault Duty:
51165.0A
Cartridge:
FRN-R 250V 400A
Curve Multiplier: 1.00000
Size:
250A
----------------------------------------------------------------------------------------Device Name:
FU-AHU-3
TCC Name:
Bus Name:
BUS-MSB
Bus Voltage:
208.0V
Function Name:
Phase
Manufacturer:
BUSSMANN
Description:
FRN-R RK5
Sub Type:
15-600A
AIC Rating:
200kA
Fault Duty:
51165.0A
Cartridge:
FRN-R 250V 400A
Curve Multiplier: 1.00000
Size:
250A
----------------------------------------------------------------------------------------Device Name:
FU-AHU-4
TCC Name:
Bus Name:
BUS-MSB
Bus Voltage:
208.0V
Function Name:
Phase
Manufacturer:
BUSSMANN
Description:
FRN-R RK5
Sub Type:
15-600A
AIC Rating:
200kA
Fault Duty:
51165.0A
Cartridge:
FRN-R 250V 400A
Curve Multiplier: 1.00000
Size:
400A
----------------------------------------------------------------------------------------Device Name:
FU-AHU-5
TCC Name:
Bus Name:
BUS-MSB
Bus Voltage:
208.0V
Function Name:
Phase
Manufacturer:
BUSSMANN
Description:
FRN-R RK5
Sub Type:
15-600A
AIC Rating:
200kA
Fault Duty:
51165.0A
Cartridge:
FRN-R 250V 400A
Curve Multiplier: 1.00000
Size:
250A
----------------------------------------------------------------------------------------Device Name:
FU-EMDP
TCC Name:
TCC-EMDP(CB-ELEV).tcc
Bus Name:
BUS-MSB
Bus Voltage:
208.0V
Function Name:
Phase
Manufacturer:
BUSSMANN
Description:
FRN-R RK5
Sub Type:
15-600A
AIC Rating:
200kA
Fault Duty:
51165.0A
Cartridge:
FRN-R 250V 600A
Curve Multiplier: 1.00000
Size:
600A
----------------------------------------------------------------------------------------Device Name:
FU-LP
TCC Name:
TCC-LP-1(20A).tcc
Bus Name:
BUS-MSB
Bus Voltage:
208.0V
Function Name:
Phase
Manufacturer:
BUSSMANN
Description:
JHC
600V
Sub Type:
1-600A
J
AIC Rating:
200kA
Fault Duty:
51165.0A
Cartridge:
JHC 600V 600A
Curve Multiplier: 1.00000
Size:
500A
----------------------------------------------------------------------------------------Device Name:
FU-PP-1
TCC Name:
TCC-PP-1(100A).tcc
Bus Name:
BUS-MSB
Bus Voltage:
208.0V
Function Name:
Phase
Manufacturer:
BUSSMANN
Description:
FRN-R RK5
Sub Type:
15-600A
AIC Rating:
200kA
Fault Duty:
51165.0A
Cartridge:
FRN-R 250V 400A
Curve Multiplier: 1.00000
Size:
400A

Mar 22, 2005

Page 6

----------------------------------------------------------------------------------------Device Name:
FU-PP-R
TCC Name:
Bus Name:
BUS-MSB
Bus Voltage:
208.0V
Function Name:
Phase
Manufacturer:
BUSSMANN
Description:
FRN-R RK5
Sub Type:
15-600A
AIC Rating:
200kA
Fault Duty:
51165.0A
Cartridge:
FRN-R 250V 400A
Curve Multiplier: 1.00000
Size:
400A
----------------------------------------------------------------------------------------Device Name:
FU-RP
TCC Name:
TCC-RP-SL(20A).tcc
Bus Name:
BUS-MSB
Bus Voltage:
208.0V
Function Name:
Phase
Manufacturer:
BUSSMANN
Description:
FRN-R RK5
Sub Type:
15-600A
AIC Rating:
200kA
Fault Duty:
51165.0A
Cartridge:
FRN-R 250V 400A
Curve Multiplier: 1.00000
Size:
400A
----------------------------------------------------------------------------------------Device Name:
CB-PP-1-100A
TCC Name:
TCC-PP-1(100A).tcc
Bus Name:
BUS-PP-1
Bus Voltage:
208.0V
Function Name:
Phase
Manufacturer:
SIEMENS
Description:
15-125A
Sub Type:
BL, 2 & 3-Pole
AIC Rating:
10kA
Fault Duty:
32455.0A
Frame:
BL 240V 100A
Curve Multiplier: 1.00000
Trip:
100A
Setting: 1) Thermal Curve (Fixed
2) INST
Fixed
(750A)
----------------------------------------------------------------------------------------Device Name:
CB-PP-1-MAIN
TCC Name:
TCC-PP-1(100A).tcc
Bus Name:
BUS-PP-1
Bus Voltage:
208.0V
Function Name:
Phase
Manufacturer:
SIEMENS
Description:
200-400A
Sub Type:
JXD2-A Sentron
AIC Rating:
65kA
Fault Duty:
32455.0A
Frame:
JXD2-A 240V 400A
Curve Multiplier: 1.00000
Trip:
400A
Setting: 1) Thermal Curve (Fixed
2) INST (LO-HI)
HI
(4000A)
----------------------------------------------------------------------------------------Device Name:
FU-PP-A
TCC Name:
Bus Name:
BUS-PP-R
Bus Voltage:
208.0V
Function Name:
Phase
Manufacturer:
BUSSMANN
Description:
FRN-R RK5
Sub Type:
15-600A
AIC Rating:
200kA
Fault Duty:
36644.4A
Cartridge:
FRN-R 250V 100A
Curve Multiplier: 1.00000
Size:
80A
----------------------------------------------------------------------------------------Device Name:
FU-PP-K
TCC Name:
Bus Name:
BUS-PP-R
Bus Voltage:
208.0V
Function Name:
Phase
Manufacturer:
BUSSMANN
Description:
FRN-R RK5
Sub Type:
15-600A
AIC Rating:
200kA
Fault Duty:
36644.4A
Cartridge:
FRN-R 250V 100A
Curve Multiplier: 1.00000
Size:
100A

Mar 22, 2005

Page 7

----------------------------------------------------------------------------------------Device Name:
FU-PP-R-MAIN
TCC Name:
Bus Name:
BUS-PP-R
Bus Voltage:
208.0V
Function Name:
Phase
Manufacturer:
BUSSMANN
Description:
FRN-R RK5
Sub Type:
15-600A
AIC Rating:
200kA
Fault Duty:
36644.4A
Cartridge:
FRN-R 250V 400A
Curve Multiplier: 1.00000
Size:
400A
----------------------------------------------------------------------------------------Device Name:
CB-RP-2
TCC Name:
TCC-RP-2(20A).tcc
Bus Name:
BUS-RP-2
Bus Voltage:
208.0V
Function Name:
Phase
Manufacturer:
SIEMENS
Description:
60-225A
Sub Type:
QJ2
AIC Rating:
10kA ShortTime:10
Fault Duty:
25893.0A
Frame:
QJ2 240V 225A
Curve Multiplier: 1.00000
Trip:
200A
Setting: 1) Thermal Curve (Fixed
2) INST
Fixed
(2650A)
----------------------------------------------------------------------------------------Device Name:
CB-RP-2-20A
TCC Name:
TCC-RP-2(20A).tcc
Bus Name:
BUS-RP-2
Bus Voltage:
208.0V
Function Name:
Phase
Manufacturer:
SIEMENS
Description:
15-125A
Sub Type:
BL, 2 & 3-Pole
AIC Rating:
10kA
Fault Duty:
25893.0A
Frame:
BL 240V 20A
Curve Multiplier: 1.00000
Trip:
20A
Setting: 1) Thermal Curve (Fixed
2) INST
Fixed
(575A)
----------------------------------------------------------------------------------------Device Name:
CB-RP-SL-20A
TCC Name:
TCC-RP-SL(20A).tcc
Bus Name:
BUS-RP-SL
Bus Voltage:
208.0V
Function Name:
Phase
Manufacturer:
SQUARE D
Description:
15-125A
Sub Type:
ED
AIC Rating:
254kA
Fault Duty:
29369.4A
Frame:
ED 240V 20A
Curve Multiplier: 1.00000
Trip:
20A
Setting: 1) Fixed
----------------------------------------------------------------------------------------Device Name:
CB-RP-SL-MAIN
TCC Name:
TCC-RP-SL(20A).tcc
Bus Name:
BUS-RP-SL
Bus Voltage:
208.0V
Function Name:
Phase
Manufacturer:
SQUARE D
Description:
110-250A
Sub Type:
KC
AIC Rating:
100kA
Fault Duty:
29369.4A
Frame:
KC 240V 225A
Curve Multiplier: 1.00000
Trip:
225A
Setting: 1) Thermal Curve (Fixed
2) INST (5-10 x Trip)
5.0
(1125A)
----------------------------------------------------------------------------------------Device Name:
FU-FADISC
TCC Name:
Bus Name:
NODE-FADISC
Bus Voltage:
208.0V
Function Name:
Phase
Manufacturer:
BUSSMANN
Description:
FRN-R RK5
Sub Type:
15-600A
AIC Rating:
200kA
Fault Duty:
3903.4A
Cartridge:
FRN-R 250V 30A
Curve Multiplier: 1.00000
Size:
30A

Mar 22, 2005

Page 8

----------------------------------------------------------------------------------------Device Name:
FU-FADISC-E
TCC Name:
Bus Name:
NODE-FADISC-E
Bus Voltage:
208.0V
Function Name:
Phase
Manufacturer:
BUSSMANN
Description:
FRN-R RK5
Sub Type:
15-600A
AIC Rating:
200kA
Fault Duty:
200000.0A
Cartridge:
FRN-R 250V 30A
Curve Multiplier: 1.00000
Size:
30A
----------------------------------------------------------------------------------------Device Name:
FU-FPDISC
TCC Name:
Bus Name:
NODE-FPDISC
Bus Voltage:
208.0V
Function Name:
Phase
Manufacturer:
BUSSMANN
Description:
FRN-R RK5
Sub Type:
15-600A
AIC Rating:
200kA
Fault Duty:
15235.2A
Cartridge:
FRN-R 250V 600A
Curve Multiplier: 1.00000
Size:
450A
----------------------------------------------------------------------------------------Device Name:
FU-MSB-MAIN
TCC Name:
TCC-EMDP(CB-ELEV).tcc
Bus Name:
NODE-MAIN LUGS
Bus Voltage:
208.0V
Function Name:
Phase
Manufacturer:
BUSSMANN
Description:
KRP-C 600V
Sub Type:
601-4000A
AIC Rating:
200kA
Fault Duty:
51169.8A
Cartridge:
KRP-C 600V 4000A
Curve Multiplier: 1.00000
Size:
4000A
----------------------------------------------------------------------------------------Device Name:
GFR-MAIN
TCC Name:
TCC-GFR.tcc
Bus Name:
NODE-MAIN LUGS
Bus Voltage:
208.0V
Function Name:
Ground
Manufacturer:
FEDERAL PIONEER
Description:
MGFR Relay
Sub Type:
MGFR
AIC Rating:
0kA
Fault Duty:
51169.8A
Frame:
MGFR-SE-ZB 600V 1200A
Curve Multiplier: 1.00000
Sensor:
Plug:
Setting: 1) Pick-up
1200
(1200A)
2) TIME
1
I^2 t In