Programmable Logic Controller

MasterLogic-200

Honeywell's next generation PLCs


Powerful, compact, versatile, open network

Programmable Logic Controller

MasterLogic-200
Powerful & Versatile processors
Scalable & Modular
Compact pocket-size modules
Range of I/O modules-digital (source/sink, transistor/relay), analog(voltage/current)
Special modules-high speed counter, position control, motion control
Open network-Profibus-DP, DeviceNet, Fast Ethernet, MODBUS
Dedicated Peer-to-Peer networking of PLCs
Remote I/O

Contents
Overview

CPU module
Input/Output module
Sample circuit diagram for Digital I/O modules

12

Network configuration
FEnet/FDEnet system
Snet system
Rnet system
Dnet system
Pnet system
Communication example
SMART I/O

28

General introduction
Analog input module
Analog output module
High speed counter module
Positioning module
Motion control module

50

SoftMaster-200 programming
SoftMaster-PD programming
SoftMaster-APM Software Package

71

Product list
Dimensions

86

20
23

Overview
CPU &
System configuration

30
32
34
36

Network

38
40
48

52
54
56

Special

60
62

83

Software

85

87

Product

MasterLogic-200
Honeywell's next generation
Programmable Logic Controller

MasterLogic-200
Overview

Overview
4

Overview

Programmable Logic Controller

MasterLogic-200
Honeywell's next generation Programmable Logic Controllers
providing real power, performance and versatility with compact
size, high speed scanning of I/O channels and execution of program instructions, open network via Ethernet, ProfibusTM-DP,
DeviceNetTM, remote I/O and engineer-friendly programming &
diagnostic software tools.

MasterLogic-200
Honeywell's next generation
Programmable Logic Controller

Overview

MasterLogic-200 is a workhorse in an industrial logic control application. Its


speed and power are truly state of the art, apart from being compact in size.
Scan times are as low as 10-15 milliseconds (typical, estimated) even a large
scale and program intensive application e.g. 3500 I/Os and 50Ksteps of program
Overview

instructions.

Remote I/O
Base I/O
Powerful & versatile processors - High speed i.e. (28ns/step, flash memory, hot-swapping)

32,000

Compact size - rack room & cabinet size space / costs saver
Open network protocols - Profibus DP, DeviceNet, MODBUS

Total I/O point

Open communication - Ethernet, Fiber-optic (100MBPS), serial RS232/RS422


Peer-to-Peer communications - Dedicated Ethernet 100 MBPS

2MLKCPUS

2MLKCPUH

0.084

0.028

Wide range I/O modules - Over 50 types: digital/analog, HSC, position control
Remote I/O - Base type & Block type Remote I/O modules
Integration with Experion PKS - Diagnostics & SCADA via MLDP special protocol
Self-Diagnostics - Network diagnostics, system logs, Auto scan, monitoring system
Engineer friendly software - Ease of configuration & trouble-shooting

16,000

8,192

6,142

4,096
3,072
2,048
1,024
512

Various Other Manufacturers

256
0.5

0.2

0.1

Processing speed (s/step)

Overview

Size Innovation. . .

Compact

saves cabinet & floor space considerably


The smallest size
The module size is as small as 27x98x90
mm (pocket size). This helps achieving cost
and floor space efficiency in todays world
where floor space is a premium & costly
resource.
Item

Power Supply

CPU

Size (WxHxD)

55x98x90

27x98x90

4-slot Base

6-slot Base

8-slot Base

12-slot Base

210x98x107

264x98x107

318x98x107

426x98x107

*all dimensions are in millimetres (mm)


MasterLogic-200
Honeywell's next generation
Programmable Logic Controller

Overview

Speed Innovation. . .

Speed & Power

Overview

High speed scan (e.g. estimated 10ms ~ 15ms for typical large PLC
applications, say, 3500 I/Os and program size of 50KSteps).

High Speed Processing


A powerful, state of the art processor in the
CPU makes it intrinsically powerful. All program
instructions are executed at a high speed of
0.028s/step thus enabling even complex
instructions to be processed very fast.
High-Speed dedicated I/O controller
The powerful processor as above (28s/step)
is well-supported by a dedicated I/O bus
controller to achieves overall fast scan cycles.
This dedicated I/O controller supplements the
main processor in I/O refresh and achieves high
speed scan (e.g. estimated 10ms ~ 15ms for
typical large PLC applications, say, 3500 I/Os
and program size of 50KSteps).

Main Base

Expansion Base

20Mbyte / sec

5Mbyte / sec

Network Innovation. . .

Open Standards
Experion PKS
Overview

System Integration with Open Network


The open communication standards have continuously
evolved and so is MasterLogic PLCs interface capability
with them.
In addition to MODBUS (Ethernet and serial),
MasterLogic-200 supports several open protocols in
control industry standards e.g. DeviceNet, ProfibusTMDP etc.

Item
Transmission speed

Fast Ethernet
FEnet

FDEnet

Snet

Profibus-DP

DeviceNet

100 / 10Mbps
300 ~ 115,200bps
Max. 12Mbps
Max. 500Kbps
Max 500m
100m (Node to Node, UTP/ STP)
Max. 1.2Km
Transmission distance
Max 500m
(422 / 485)
2Km (Node to Node, Fiber Optic)
Max. number of station
64 (HS link)
32
126 (32 / Seg)
64
HS link

MLDP Protocol

Open Protocol
(MODBUS)
(MODBUS)
Service
P2P

SoftMaster-200 I/F

E-Mail

Configuration Software
SoftMaster-PD
SoftMaster-PD & SyCon
Number of installation
24 ( HS link Service: 12, P2P Service: 8)

MECHATROLINK-II
10Mbps
Max 50m
16 (# of axis)

No limit

MasterLogic-200
Honeywell's next generation
Programmable Logic Controller

Overview

Engineering & Programming Innovation. . .

Versatile

Versatile

Overview
Modular
Interrupt driven
programs
Program and
modularization
and Task
operation
MasterLogic-200 allows the engineer to modularize
the entire program into several easily manageable
components. Also, several interrupt driven programs
are supported e.g. timer or process condition driven
interrupts. The table summarizes the max # of
programs that are supported.

Program type
Scan program Scan
Initialization task
Time driven task

Description
Executed in every scan
Executed only one time when power turns on
Executed with a constant time interval specified
in parameter setting

Task program Internal interrupt Executed by internal interrupt condition


External interrupt
Executed by external interrupt condition
task

#Qty
256-task
1
32
32
32

Special Register
MasterLogic-200 expands device memory and support advanced programming environment with
Index register (Z), File register (U), and Analog register (U).

File register

Analog register

As a non-volatile memory type,


data are secured even in times
of power blackout or CPU reset.

Unlike old methods, no analog commands


are required. The data after A/D
conversion can be directly accessed by
assigning an I/O address i.e. base, slot
and memory buffer.

Index register

Example of Analog Register

Base No.
Slot No.

<Old Method>

Index registers (Z) come handy to


engineers when array based access of
various devices (dynamic addressing)
is required. A device address can be
dynamically offset with an index register
value.

Memory buffer

<SoftMaster-200>

Analog Operation without Programming


Special module setup and operation is achieved just by parameter setting without any additional program.

X
Set up analog module

10

Set up high-speed
counter module

Software Innovation. . .

Engineer-Friendly
Overview

Integrated Programming & Engineering


SoftMaster-200 software package provides integrated engineering environment from basic
programming to different special module setting as well as diagnosis. This package consists of
SoftMaster-200 (PLC programming), SoftMaster-PD (Communication programming) and
SoftMaster-APM software package (Positioning programming).

SoftMaster-200
Engineer-friendly software (multiple PLCs monitored in a single window/project)
Easy project documentation - programs, variable assignments, comments, etc
Import/Export - configuration file can be imported or exported
Two levels of remote connections
Online Editing & Debugging Facility
A special wizard for hot swapping of modules
Various trouble-shooting and diagnostic features

SoftMaster-PD
Slot assignment & configuration of all communication modules (Ethernet,
Serial, ProfibusTM-DP, DeviceNetTM ,etc)
Peer-to-Peer networking configuration
Data Transfer (transmission & receive) definitions
Various network diagnostic features (e.g. protocol analysis)

SoftMaster-APM
Positioning module parameter setting
Data Editing in EXCEL
Various Monitoring & Diagnosis
Tracking Function

Engineer-Friendly
11

+
+

+
+

+
+

+
+

+
+

+
+

CPU

CPU & System Configuration


MasterLogic-200 has two models of CPU, one standard model
for general application and a premium model for high speed and
large scale application.
It offers over 50 types of I/O modules so that you can choose
and optimize your system configuration according to the needs
discrete, analog, pulse, position control, etc.
Special modules are available to enable connectivity to open
networks such as DeviceNet, Profibus-DP, MODBUS-TCP,
MODBUS serial protocol standards.

12

+
+

+
+

CPU

Premium CPU for high-speed and large scale application

2MLK-CPUH
Program capacity: 64K steps
I/O points: 6,144 (using 64-channel I/O module)
I/O device point: 32,000 (Remote I/O)
Processing speed: 28ns/step
96 slots

Standard CPU for general application

2MLK-CPUS
Program capacity: 32K steps
I/O points: 3,072 (using 64-channel I/O module)
I/O device point: 32,000 (Remote I/O)
Processing speed: 84ns/step
48 slots

MasterLogic-200
Honeywell's next generation
Programmable Logic Controller

13

MasterLogic-200

System configuration
CPU module
XGT-CPUS
MODE
RUN
STOP
ERROR
BAT
COM

Type
USB cable
or

Battery

CPU module

RS-232C

SoftMaster-200

Item

Type

Description

USB cable
RS-232C cable

USB-301A
KIC-050A

USB downloading cable


RS-232C downloading cable

XGT-PAFA

XGT-CPUS
MODE
RUN
STOP
ERROR
BAT
COM

POWER

CPU
Power module
(2MLP-)

Main Base (2MLB-MA)

Expansion cable
(2MLC-E)

Type
2MLC-E041
2MLC-E061
2MLC-E121
Expansion
2MLC-E301
cable
2MLC-E501
2MLC-E102
2MLC-E152
Expansion end 2MLT-TERA

Description
Expansion cable 0.4m
Expansion cable 0.6m
Expansion cable 1.2m
Expansion cable 3.0m
Expansion cable 5.0m
Expansion cable 10m
Expansion cable 15m
Expansion base end connector

XGI-D22A

3
8

2
14

XGQ-RY2A

3
8

2
14

XGQ-TR2A

3
8

2
14

XGQ-RY8A

3
8

2
14

XGQ-TR8A

3
8

2
14

XGQ-RY4A

3
8

2
14

XGQ-TR4A

3
8

2
14

Power module

Output

2MLP-ACF1

DC5V / 3A, DC24V / 0.6A

2MLP-ACF2
2MLP-AC23
2MLP-DC42

DC5V / 6A
DC5V / 8A
DC5V / 6A

Item

16 points
32 points
64 points
Input module
(2MLI-)
Item
8 points
16 points
32 points
64 points

Expansion base (2MLB-EA)

Input

8 points

Output module
(2MLQ-)

XGI-A22A

Flexi Voltage
110/220V AC
AC 220V
DC 24V

Item

I/O point
6,144 (Using 64-ch)
3,072 (Using 64-ch)

2MLK-CPUH
2MLK-CPUS

Input module
AC220V
2MLI-A21A
-

AC110V
2MLI-A12A
-

Output module
Triac

Relay

2MLQ-SS2A
-

2MLQ-RY1A
2MLQ-RY2A
2MLQ-RY2B
-

DC24V
2MLI-D21A
2MLI-D22A
2MLI-D22B
2MLI-D24A
2MLI-D24B
2MLI-D28A
2MLI-D28B

Transistor
2MLQ-TR2A
2MLQ-TR2B
2MLQ-TR4A
2MLQ-TR4B
2MLQ-TR8A
2MLQ-TR8B

Special module
2MLF-AV8A
Voltage input type, 8ch
2MLF-AC8A
Current input type, 8ch
2MLF-DV4A
Voltage output type, 4ch
2MLF-DC4A
Current output type, 4ch
D/A
conversion 2MLF-DV8A *
Voltage output type, 8ch
2MLF-DC8A *
Current output type, 8ch
Pulse (OC) input type, 2ch
High-speed 2MLF-HO2A
counter
2MLF-HD2A
Pulse (LD) input type, 2ch
2MLF-PO3A
Pulse (OC) output type, 3axes
2MLF-PO2A
Pulse (OC) output type, 2axes
2MLF-PO1A
Pulse (OC) output type, 1axis
Positioning
2MLF-PD3A
Pulse (LD) output type, 3axes
2MLF-PD2A
Pulse (LD) output type, 2axes
2MLF-PD1A
Pulse (LD) output type, 1axis
A/D
conversion

Item

Main base

Expansion base

4 Slot
6 Slot
8 Slot
12 Slot

2MLB-M04A
2MLB-M06A
2MLB-M08A
2MLB-M12A

2MLB-E04A
2MLB-E06A
2MLB-E08A
2MLB-E12A

SoftMaster-200 Cable (RS-232C)


Cnet (9Pin, Male)

PC (9Pin, Female)
Special module
(2MLF-)

Motion
control

2MLF-M16M

Motion dedicated net (M-II) type, 16axes

Temperature
control

2MLF-TC4S *
2MLF-RD4A *

Temperature (TC) input, 4ch, Insulation


Temperature (RTD) input, 4ch
* Due to release

* OC: Open Collector


LD: Line Driver

Communication module

Communication
module
(2MLL-)

14

2MLL-CH2A
Snet
2MLL-C22A
2MLL-C42A
2MLL-EFMF
FEnet
(Open Ethernet) 2MLL-EFMT
2MLL-EDSF
FDEnet
2MLL-EDST
(Dedicated
2MLL-EDMF
Ethernet)
2MLL-EDMT
2MLL-RMEA
Rnet
2MLL-DMEA
Dnet
2MLL-PMEA
Pnet

RS-232C/RS-422
RS-232C, 2ch
RS-422, 2ch
Optical, Master, SC type
Electric, Master, RJ-45
Optical, Slave, SC type
Electric, Slave, RJ-45
Optical, Master, SC type
Electric, Master, RJ-45
Rnet, Master, TP
DeviceNet, Master, ODVA Standard
Profibus-DP, Master, DP Standard

3
8
14

Specifications
Standard

Description
0 ~ 55 oC
-25 ~ +70 oC
5 ~ 95%RH (Non-condensing)
5 ~ 95%RH (Non-condensing)

Item
Ambient temperature
Storage temperature
Ambient humidity
Storage humidity
Frequency
10 f > 57Hz
57 f 150Hz

Vibration resistance

Frequency
10 f > 57Hz
57 f 150Hz

Occasional vibration
Acceleration
9.8m/s2 {1G}
Continuous vibration

Pulse width
0.075mm
-

Acceleration
4.9m/s2 {0.5G}

Pulse width
0.035mm
-

10 times
each
direction
(X, Y and Z)

IEC 61131-2

Half-sine, 3 times each direction per each axis

Noise resistance
Operating Ambience
Altitude
Pollution degree
Cooling

1,500Vp-p
Square wave impulse noise
4KV
Electrostatic discharge
27~500MHz, 10V/m
Radiated electromagnetic field noise
Voltage, 2KV power module, 1KV Digital/Analog I/O Comm. I/F
Fast transient/ Burst noise
Free from corrosive gases and excessive dust
Up to 2,000m
Less than or equal to 2
Air-cooling

Honeywell Standard
IEC 61131-2. IEC 1000-1-2
IEC 61131-2. IEC 1000-1-3
IEC 61131-2. IEC 1000-1-4

* Pollution degree 2 is non-conductive pollution. However, occasional conductivity caused by condensation can be expected.

Item

Description
2MLK-CPUS

Remarks

2MLK-CPUH

Operation method

Cyclic execution of stored program, Time-driven interrupt, Process-driven interrupt

I/O control method

Indirect mode (Refresh method), Direct by program command

Program language

Ladder diagram, Instruction list

Number of
instructions
Processing
speed

Basic
Application
Sequence instruction (s)
Application instruction (s)
Floating instruction (s)

Program capacity
I/O points (available to install)
P
M
K
L
F

T
Data area

File register

Program type

C
S
D
U
Z
N
R
Flash Area
Total program
Initialization
Time-driven
External
Internal

Operation mode
Self-diagnosis
Programming port
Data retention at power failure
Max. expansion stage
Current consumption (mA)
Weight (kg)

42
600
0.084s/step
0.252s/step
: 1.442s (S), 2.87s (D)
x: 1.948s (S), 4.186s (D)
: 1.974s (S), 4.2s (D)
32K Steps
768 (16-point I/O)
1536 (32-point I/O)
3072 (32-point I/O)

0.028s/step
0.084s/step
: 0.602s (S), 1.078s (D)
x: 1.106s (S), 2.394s (D)
: 1.134s (S), 2.66s (D)
64K Steps
1536 (16-point I/O)
3072 (64-point I/O)
6144 (64-point I/O)

S: Single
D: Double

P00000 ~ P2047F (32,768 points)


M00000 ~ M2047F (32,768 points)
K00000 ~ K2047F (32,768 points )
L00000 ~ L11263F (180,224 points )
F00000 ~ F2047F (32,768 points )
100ms: T0000 - T0999
10ms: T1000 - T1499
1ms: T1500 - T1999
0.1ms: T2000 - T2047
C0000 ~ C2047
S00.00 ~ S127.99
D0000 ~ D32,767
D0000 ~ D19,999
U0.0 ~ U7F.31
U0.0 ~ U3F.31
128points
N00000 ~ N21,503

I/O relay
Auxiliary relay
Special relay
Link relay
Keep relay
Timer
(Adjustable)

RAM: 2 blocks
Flash: 2M byte, 32 blocks
256
1 (_INT)
32
32
32
RUN, STOP, DEBUG
Execution, Delay, Memory error, I/O error, Battery error, Power error
RS-232C (1CH), USB (1CH)
Latch setting in Basic Parameters
4 (Main + Expansion), up to 15m
8 (Main + Expansion), up to 15m
940
960
0.12
0.12
RAM: 1 block

Counter
Step controller
Register
Analog resister
Index register
Network register
File register1 block: R0 ~ R32767
Control by file register

MODBUS slave

MasterLogic-200
Honeywell's next generation
Programmable Logic Controller

15

CPU

Peak acceleration : 147m/s2 {15G}


Duration: 11ms

Shock resistance

IEC 61131-2

MasterLogic-200
0 1 2 3 4 5

Main system composition

Item

2MLK-CPUS
3 stages

2MLK-CPUH
7 stages

48 modules

96 modules

Max. I/O count(using 64 channel modules)

3,072

6,144

Max. expansion distance

15m

15m

Max. # expansion bases


Max. # modules/slots

CPU

Fixed I/O address


assignment

In fixed assignment, 64 I/O addresses are assigned to each slot regardless of module type installed
in the slot.
16 slots are assigned to each base regardless of base size (4, 6, 8 or 12).
The starting address for base 0 is P0000.

example of fixed I/O address for 12 slots.


Slot number:

Power

MasterLogic-200 supports
two types of I/O address
assignment; fixed and
variable

P80
~
P11F

P120
~
P15F

P160
~
P19F

P200
~
P23F

P240
~
P27F

P280
~
P31F

P320
~
P35F

9 10 11

CPU

P0
~
P3F

P40
~
P7F

P360
~
P39F

P400
~
P43F

P440
~
P47F

In variable assignment, I/O addresses are assigned automatically to each slot according to the
installed module type.

Also, each communication module slot is assigned 16 I/O addresses.


The starting address for base 0 is P0000
Variable I/O address
assignment

Slot number:

9 10 11

P110
~
P12F

P130
~
P16F

P170
~
P18F

P190
~
P19F

P200
~
P21F

32 points

16 points

32 points

32 points

64 points

P90
~
P10F

6
32 points

P80
~
P8F

5
32 points

P40
~
P7F

4
16 points

P20
~
P3F

3
64 points

P10
~
P1F

2
32 points

P00
~
P0F

1
16 points

The default setting is fixed


I/O address assignment i.e.
64 points for each slot

CPU

16 points

Power

P0220
~
P23F

Expansion system composition


This drawing demonstrates the following:
how the main base and expansion bases are connected using the
expansion cable.
expansion base address setting via dip switch
Fixed I/O address assignment is followed in this example. However,
the address can be adjusted in SoftMaster-200 programming
software.
The last expansion base should be terminated with a terminator
(2MLT-TERA)

Main base
(Base number: 0)

Slot number:

Power CPU

P0000 P0040 P0080 P0120 P0160 P0200 P0240


~
~
~
~
~
~
~
P003F P007F P011F P015F P019F P023F P027F

7
P0280
~
P031F

Expansion cable
Slot number:

Power

Switch for setting


base number: 1

Expansion base
Base Number:2

Slot number:

Power

Slot number:
Expansion base
Base Number:7
Terminator

16

Power

P0640 P0680 P0720 P0760 P0800 P0840 P0880


~
~
~
~
~
~
~
P067F P071F P075F P079F P083F P087F P091F

P1280 P1320 P1360 P1400 P1440 P1480 P1520


~
~
~
~
~
~
~
P131F P135F P139F P143F P147F P151F P155F

0
P4480
~
P003F

P4520 P4560 P4600 P4640 P4680 P4720


~
~
~
~
~
~
P007F P011F P015F P019F P023F P475F

7
P0920
~
P095F

7
P1560
~
P159F

7
P4760
~
P479F

MasterLogic-200 CPU Key functions


Modularizing scan programs:
MasterLogic-200 CPU enables modularizing the overall PLC programming into a max of 256
normal scan programs (components) which are executed once every scan cycle.
Interrupt programs:
In addition to normal scan programs, MasterLogic-200 CPU has a powerful range of handling
interrupt programs as follows:
Type

Timer Interrupts

External Interrupts

Internal Interrupts

# Interrupt
programs

32

32

32

Execution
condition

Once when the time interval


elapses (max.
4,294,967, 295 msec)

Once when digital input


condition (on/off)
becomes true

Once when internal


device (memory)
condition becomes true

Detection
time

Max. 0.2ms

Max. 1ms

Max. scan time

Execution
priority

2~7 level setting


(2 level is highest in priority)

same

same

0~31 (no duplication)

32~63 (no duplication)

64~95 (no duplication)

Spec

Task no.

Latch areas (data retention):


MasterLogic-200 has two latch areas a) Latch 1 and Latch 2. They are non-volatile data
retention memory areas. Various devices and address range can be configured as latch areas.
Data in those two latch areas are saved for easy restarting of PLC upon mode change or
power reset.
Latch 1 area can be cleared only by
Overall Reset: Reset dip switch (3 seconds or longer) or Overall reset command (SoftMaster200)
Clear PLC command (SoftMaster-200: latch 1 selection) in stop mode
Data Clear dip switch: instantly on/off in stop mode, which clears all the device except latch
2 area.
Latch 2 area cannot be cleared by above two actions. It can be cleared only by
Data Clear dip switch: 3 seconds or longer (in stop mode), which clears all the device.
Clear PLC command (SoftMaster-200: latch 2 selection) in stop mode which clears latch 1
area too.
Force I/O:
The I/O refresh memory can be forced manually to any specific value for maintenance and
trouble-shooting purposes. Both input and output (bit data) image area can be forced to a
value.
Real Time Clock (RTC):
MasterLogic-200 CPU has a built-in clock (RTC) which runs on battery even in case of power
failure. The PLC event history recorded by CPU stores the time stamp of the events.

MasterLogic-200
Honeywell's next generation
Programmable Logic Controller

17

Direct I/O operation:


In normal operation, the I/O refresh takes place once every scan i.e. input refresh at the
beginning of scan and output refresh at the end of every scan. However for any time critical
application, IORF command can be used in the program to directly read/write from/to the I/O
module during program execution.

CPU

Operation History:
MasterLogic-200 CPU stores four types of event history for monitoring, diagnostics and
trouble-shooting purposes. The events are details are stored in CPU until they are reviewed
and deleted from SoftMaster-200 software.

Event Type

Condition

Size

Details

Error History

Any error

2048 events
max

Timestamp, Error code,


description

Mode Change
History

RUN/STOP

1024 events
max

Timestamp, mode etc

Power shutdown
History

ON/OFF

1024 events
max

Timestamp, power status


etc

System History

Key System
message

2048 events
max

Timestamp, Error code,


description

Skip I/O:
For any maintenance purpose, an entire I/O base including all its slots or any selective slot
(module) can be set for I/O skip through the software. The CPU ignores that I/O base or the
particular slots in it during operation.

Hot swapping:
MasterLogic-200 allows the engineer to change the module online during operation in two
ways.
By Module Change Wizard function in SoftMaster-200software.
By using M.XCHG dip switch in the CPU
Communication modules (Profibus and DeviceNet) have to be setup & configured separately
on a standby system before they can be changed online.
Online Editing:
The program can be modified online during CPU run mode by following a simple procedure

18

Remote I/O
MasterLogic-200 supports two types of remote I/O functionality, depending upon the application
a) block type remote I/O (fixed I/O)
b) base type remote I/O (flexible I/O or special module)
0

Block type remote I/O system


Profibus-DP/DeviceNet/Rnet/MODBUS
master
FEDnet master
Main base

CPU

For simple remote I/O applications, Smart


I/O modules make it easy to implement.
Smart I/O modules are standalone DIN rail
mounted block I/Os supporting connected
to MasterLogic-200 both on Honeywell
proprietary (RNET) and also open protocols
Profibus-DP, DeviceNet, MODBUS etc.
As they support open protocols, these
Smart I/O modules can be connected to
any other manufacturers PLCs or other
controllers e.g. they serve as RTUs
Various types of digital I/O and analog I/O
modules are available in Smart I/O blocks.

Main base
2MLPACF1

2MLKCPUH

2MLL....

Smart I/O

Please see Smart I/O section for more


0details.
1 2 3 4 5 6 7

Smart I/O

Smart I/O

9 10 11

Base type remote I/O system (under development)


0Base
1 type
2 3remote
4 5 I/O6 serves
7
a more flexible
remote I/O just like any other main base,
except it is located remote and connected
via Ethernet. Any type of I/O or other special
modules can be installed in any slot of the
remote I/O base. Also, hot-swapping of I/O
module is supported as in main base.
0 1 2 3 4 5 6 7

FDEnet master

2MLPACF1

2MLKCPUH

Main base

2MLLEDMT

Remote base (Same as main base)

The remote I/O functionality is achieved


with the help of FDEnet (dedicated Ethernet)
master and slave configuration as shown in
the drawing.

FDEnet slave

2MLLEDST

2MLPACF1

Data are transferred bi-directionally between


remote I/O base and main CPU via high
0 speed
1 2 link3 (HSL)
4 5parameter
6 7 settings
Fixed I/O address assignment is always
used (64 points, 4 word per slot)
Available range of I/O address assignment is
32,768 points (P0000 ~ P2047F)

MasterLogic-200
Honeywell's next generation
Programmable Logic Controller

19
0

9 10 11

Digital I/O Modules

Features
24VDC input modules (Sink/source or source only type)
AC input modules (110V or 220V AC)
Relay, Triac, transistor ouput modules (sink or source type)
8, 16, 32, 64 points I/O module
Photo-coupler isolation
LED for module & input status
Easy maintenance: Terminal block type, one-touch installation of module

CPU
Input module specifications
DC input

Input type
2MLI-D21A

Type
Input point

2MLI-D22A

2MLI-D22B

2MLI-D24B

16

2MLI-D28A

32

Rated input voltage

DC24V

Rated input current

4mA

2MLI-D28B

Off -> On

AC100~120V

AC100~240V

8mA

17mA

5mA or more
1mA or less

16/COM

2mA or less

15mA or less

1ms/3ms/10ms/20ms/100ms (set by CPU parameter) Initial value: 3ms


8/COM

10mA ormore

AC30V or more / AC60V or more /

1ms/3ms/10ms/20ms/100ms (set by CPU parameter) Initial value: 3ms

On -> Off

Common (COM)

2MLI-A21A

16

AC80V or more / AC130V or more /

DC11V or less / 1.7mA or less

OFF voltage/current

2MLI-A12A

64

19V or more / 3mA or more

ON voltage/current

Response

AC input

2MLI-D24A

25mA or less

32/COM

16/COM

8/COM

Photocoupler Isolation

Insulation method
Current consumption (mA)

20

30

50

60

30

20

Weight (kg)

0.1

0.12

0.1

0.15

0.13

0.13

Output module specifications


Relay

Input type

Rated load voltage

Response time

16

Output point
Rated output
current

Transistor

Triac

2MLQ-RY1A 2MLQ-RY2A 2MLQ-RY2B 2MLQ-TR2A 2MLQ-TR2B 2MLQ-TR4A 2MLQ-TR4B 2MLQ-TR8A 2MLQ-TR8B 2MLQ-SS2A

Type

32

16

DC12/24V, AC110/220V
1 point

Common

2A
2A

8A

0.1A

4A

2A

10ms or less

1ms or less

On -> Off

12ms or less

1ms or less

1/COM

16/COM

Insulation method
Current consumption (mA)

260

Weight (kg)

0.13

Surge killer
External power supply

16/COM

Relay

0.19
Varistor

4A
1ms or less
0.5cycle
+1ms or less
16/COM

32/COM

70

130

230

0.11

0.1

0.15

300
0.2

Zener diode

Varistor

Voltage: DC 12/24 (10%) (ripple voltage within 4Vp-p)

Current: 10mA (at DC 24V) (Max. all points ON)

20

0.6A

Photocoupler Isolation
500

0.17

16
AC110/220V

0.5A

Off -> On

Common (COM)

64

DC12/24V

Wiring diagram for input modules


2MLI-D21A

2MLI-D22A

2MLI-D22B

2MLI-D24A

CPU

2MLI-D24B

2MLI-A12A

2MLI-D28A

2MLI-D28B

2MLI-A21A

MasterLogic-200
Honeywell's next generation
Programmable Logic Controller

21

Digital I/O modules

Wiring diagram for output modules


2MLQ-RY2A/B

2MLQ-TR4A

2MLQ-TR4B

2MLQ-TR2A

2MLQ-TR2B

CPU

2MLQ-RY1A

2MLQ-TR8B

22

2MLQ-TR8A

2MLQ-SS2A

Sample Circuit diagram for Digital I/O modules

Digital Output Wiring Examples

2MLQ-RY2A
16-point Relay Output

2MLQ-TR2A
16-point Transistor Output Module
(sink type)

2MLQ-RY2B
16-point Relay Output Module
(with surge absorber)
2MLQ-TR2B
16-point Transistor Output Module
(source type)

2MLQ-SS2A
16-point Triac Output Module

MasterLogic-200
Honeywell's next generation
Programmable Logic Controller

23

Sample Circuit diagram for Digital I/O modules

Digital Input Wiring Examples

2MLI-D21A
8-point DC24V Input Module
(Source/Sink Type)

2MLI-D22B
16-point DC24V Input Module
(Source Type)

2MLI-A12A
16-point AC110V Input

2MLI-A21A
8-point AC220V Input Module

24

Digital I/O modules

Some useful tips for selecting the right digital I/O module:
As wiring & function varies with module type, please select the right

The following graph presents the maximum relay lifespan of relay


output module.

module according to the input device.

Use an interrupt module when a high-speed response is required for


fast changing input. However, please note only one interrupt module
can be installed per CPU.

If switching frequency is high or inductive switching load is used,


the lifespan of relay output module will be reduced. Therefore, it is
recommended to use transistor output module or triac output module.

When driving an inductive load with output module, set the maximum

CPU

No. of
switching 100
(x 10,000)

50

switching ON & OFF frequency to 1 second.

When using counter or timer with DC/DC converter, surge currents

30
20

may cause a break down. Therefore, please either connect a resistor/


inductor to the load or use the module whose max. load current is high.

10

AC 125V Resistive load


DC 30V Resistive load
AC 250V Resistive load

Fuse of output module is not replaceable to prevent a damage of


external wiring when output module has a short-circuit.

The number of simultaneous ON points varies depending on input


voltage, ambient temperature. Refer to the specification of the input
module.

0.5

2 3

10

100
Switching current

Resistor

Compressed terminal attaching sleeve cannot be mounted to


MasterLogic-200 terminal block. The following picture shows
appropriate compressed terminals for terminal block.

Load current

6.0mm
or less

Output
modul

Inductor

Load current

6.0mm
or less

Output
modul

Use 0.3~0.75mm2 twisted pair, below 2.8mm thickness cable for


connecting to terminal block.

Be careful when choosing and using the cable since the permissible
current differs according to the insulation thickness.

Joint torque of fixed screw and terminal block screw of the module
needs to be within the range in the following table.
Joint

Joint torque range

I/O module terminal block screw (M3)

42~58 N cm

I/O module terminal block fixed screw (M3)

68~89 N cm

Thermal protector is built in transistor module to protect PLC from


overload and overheating.

MasterLogic-200
Honeywell's next generation
Programmable Logic Controller

25

+
+

+
+

Network

Network
The open communication standards have
continuously evolved and so is MasterLogic-200
interface capability with the outside world.
In addition to MODBUS (TCP-IP Ethernet and
Serial), MasterLogic-200 supports several
open control industry standards protocol e.g.
DeviceNet, Profibus-DP etc.

26

+
+

+
+

+
+

+
+

+
+

+
+

+
+

FEnet / FDEnet (Fast Ethernet)

10/100Mbps support, industrial-use high speed Ethernet


10/100Base-TX, 100Base-FX (Fiber-optic)
Open Ethernet (FEnet) and Honeywell dedicated Ethernet (FDEnet)
High reliability and performance with 32-bit processor
Various connection to MMI S/W (Experion PKS, MODBUS/TCP)

Network

Snet
RS-232C/485/422 communication
Long-distance communication via modem connection
Various connection to MMI S/W
(MasterLogic-200, Modbus RTU (slave), Modbus ASCII)
User-defined communication support
Convenient P2P master (MasterLogic-200, MODBUS master)

Rnet

MasterLogic-200

Honeywell proprietary protocol for communication with Smart I/O module


High speed communication: 1Mbps
Long communication distance: Max. 750m
Network management using AUTO SCAN (Slave module information)

Dnet (DeviceNet)

Connectable to other PLCs and control device


Compliance to ODVA standard
Flexible communication speed setting: 125, 250, 500Kbps
Multi-drop and T branch connection
Long communication distance: Max. 500m
Convenient parameter setting through SyCon/HS link parameter

Pnet (Profibus-DP )
Low cost network appropriate to field level
Proper to communicate among a master device and distributed
slave I/O devices
Fast slave communication omitting application layer
Long communication distance: Max. 1200m
Convenient parameter setting through SyCon/HS link parameter

MasterLogic-200
Honeywell's next generation
Programmable Logic Controller

27

Network / General introduction


Features

Item

Fast Ethernet
FEnet

Transmission speed

Snet

Profibus-DP

DeviceNet

300 ~ 115,200bps

Max 12Mbps

Max 500m
(422 / 485)
32

(MODBUS)

FDEnet

100 / 10Mbps

100m (Node to Node, UTP/ STP)


Transmission distance
2Km (Node to Node, Fiber Optic)
Max. number of station
64 (HS link)
HS link

MLDP Protocol

Open Protocol
(MODBUS)
Service
P2P

SoftMaster-200 I/F

E-Mail

Configuration Software
SoftMaster-PD
Number of installation

Rnet

MECHATROLINK-II

Max 500Kbps

1Mbps

10Mbps

Max 1.2Km

Max 500m

Max 750m

Max 50m

32 / Seg

64

32 / Seg

16 (# of axis)

SoftMaster-PD & SyCon


24 ( HS link Service: 12, P2P Service: 8)

SoftMaster-PD

No limit

Network
Experion PKS

FEnet, FDEnet
IFOS

2MLT-PAFA

2MLT-CPUS

2MLI-A22A

2MLI-D22A

2MLQ-RY2A

2MLQ-TR2A

2MLQ-RY2A

2MLQ-TR8A

2MLT-PAFA

MasterLogic-200
FDEnet

MasterLogic-100R

MasterLogic-100R

Ethernet

28

2MLT-CPUS

2MLI-A22A

2MLI-D22A

2MLQ-RY2A

2MLQ-TR2A

2MLQ-RY2A

2MLQ-TR8A

2MLT-PAFA

2MLT-CPUS

2MLI-A22A

2MLI-D22A

2MLQ-RY2A

2MLQ-TR2A

2MLQ-RY2A

2MLQ-TR8A

MasterLogic-200
FEnet (dedicated Ethernet)

No. of network module available


Item

2MLK-CPUH

2MLK-CPUS

Total network module

24

24

High Speed link module

12

12

P2P service

Network

WEB

IFOS
MasterLogic-200

Wireless LAN
2MLT-PAFA

2MLT-CPUS

2MLI-A22A

2MLI-D22A

2MLQ-RY2A

2MLQ-TR2A

2MLQ-RY2A

2MLQ-TR8A

MasterLogic-100R
Dedicated Ethernet (FDEnet)
2MLT-PAFA

2MLT-CPUS

2MLI-A22A

2MLI-D22A

2MLQ-RY2A

2MLQ-TR2A

2MLQ-RY2A

2MLQ-TR8A

2MLT-PAFA

MasterLogic-200

2MLT-CPUS

2MLI-A22A

2MLI-D22A

2MLQ-RY2A

2MLQ-TR2A

2MLQ-RY2A

2MLQ-TR8A

MasterLogic-200
MECHATROLINK

Rnet (Honeywell proprietary)

Smart I/O

Profibus-DP

Smart I/O
Master Panel
Snet

DeviceNet

Smart I/O
Other PLC

Other INV

MasterLogic-200
Honeywell's next generation
Programmable Logic Controller

29

FEnet / FDEnet system (Fast Ethernet)


2MLT-PAFA

2MLT-CPUS

2MLI-A22A

2MLI-D22A

2MLQ-RY2A

2MLQ-TR2A

2MLQ-RY2A

2MLQ-TR8A

2MLI-D22A

2MLI-A22A

2MLT-CPUS

2MLT-PAFA

2MLQ-RY2A

2MLQ-TR2A

2MLQ-RY2A

2MLQ-TR8A

Features
10/100Mbps support, industrial-use high speed Ethernet (IEEE802.3)
Two models available: 10/100Base-TX (RJ45-Cat5), 100Base-FX
2MLT-PAFA

2MLT-CPUS

2MLI-A22A

2MLI-D22A

2MLQ-RY2A

2MLQ-TR2A

2MLQ-RY2A

2MLQ-TR8A

2MLT-CPUS

2MLT-PAFA

2MLI-D22A

2MLI-A22A

2MLQ-RY2A

2MLQ-TR2A

2MLQ-RY2A

2MLQ-TR8A

(Fibre-Optic)

Open Ethernet (FEnet) for integration with Experion PKS or other


SCADA/HMI via MasterLogic Dedicated Protocol (MLDP) or standard
MODBUS TCP slave protocol.
Dedicated Ethernet (FDEnet) for peer-to-peer communications between
MasterLogic-200 PLCs
High reliability and performance with 32-bit processor
Remote programming (upload/download), monitoring and control by
SoftMaster-200 software via Ethernet
E-mail transmission support
Providing network status information to Auto-scan and Ping utility
software
Easy network configuration and diagnosis / monitoring by SoftMasterPD software
User defined protocol (TCP/UDP) for integration with other device
manufacturers (P2P service)
Providing information on services - High Speed Link (HSL), P2P,
MasterLogic dedicated protocol (MLDP), media condition
2MLT-PAFA

2MLT-CPUS

2MLI-A22A

2MLI-D22A

2MLQ-RY2A

2MLQ-TR2A

2MLQ-RY2A

2MLQ-TR8A

2MLT-CPUS

2MLT-PAFA

2MLI-A22A

2MLI-D22A

2MLQ-RY2A

2MLQ-TR2A

2MLQ-RY2A

2MLQ-TR8A

Network

Experion PKS
Other SCADA/HMI
Bridge or
Router

FEnet
2MLK-CPUH/S
2MLL-EFMT
2MLL-EFMF

2MLK-CPUH/S
2MLL-EFMT
2MLL-EFMF
2MLT-PAFA

2MLT-CPUS

2MLI-A22A

2MLI-D22A

2MLQ-RY2A

2MLQ-TR2A

2MLQ-RY2A

2MLQ-TR8A

2MLT-PAFA

2MLT-CPUS

2MLI-A22A

2MLI-D22A

2MLL-EDMT
2MLL-EDMF

2MLQ-RY2A

2MLQ-TR2A

2MLQ-RY2A

MasterLogic-100R
G3L-EUFB

G3L-EUTB
G3L-EU5B

Other PLC

2MLQ-TR8A

2MLL-EDMT
2MLL-EDMF

Ethernet I/F

FDEnet
Public
network
Internet

2MLT-PAFA

2MLT-CPUS

2MLI-A22A

2MLI-D22A

2MLQ-RY2A

2MLQ-TR2A

2MLQ-RY2A

2MLQ-TR8A

2MLL-EDST
2MLL-EDSF

2MLT-CPUS

2MLI-A22A

2MLI-D22A

2MLQ-RY2A

2MLQ-TR2A

2MLQ-RY2A

2MLQ-TR8A

2MLK-CPUH/S
2MLL-EDMT
2MLL-EDMF

(Remote I/O)

Bridge or
Router

2MLT-PAFA

FEnet
2MLK-CPUH/S
2MLL-EFMT
2MLL-EFMF
2MLT-PAFA

2MLT-CPUS

2MLI-A22A

2MLI-D22A

2MLQ-RY2A

2MLQ-TR2A

2MLQ-RY2A

2MLQ-TR8A

2MLK-CPUH/S
2MLL-EFMT
2MLL-EFMF
2MLT-PAFA

2MLT-CPUS

2MLI-A22A

2MLI-D22A

2MLQ-RY2A

2MLQ-TR2A

2MLQ-RY2A

MasterLogic-100R

G3L-EUFB
G3L-EUTB
G3L-EU5B

Other PLC

2MLQ-TR8A

Ethernet I/F

30

Specifications
FEnet

Item
Communication specification

2MLL-EFMT
10/100BASE-TX

2MLL-EFMF
100BASE-FX, Fiber Optic

Protocol

TCP/IP, UDP/IP
With MasterLogic PLCs

Service

High-speed link, P2P service


P2P service

With other devices


Application

MLDP (MasterLogic Dedicated protocol) service, SoftMaster-200 service, E-Mail service, MODBUS-TCP
200 words/block (Max. 128 blocks)

HS link sending/receiving data

16 channels

No. of channel connectable to upper stage


General use

Communication with Experion PKs & Other SCADA/HMI and external devices, high speed communication among MasterLogic PLCs

Media

x62.5/125um, Multi-mode, SC connector

UTP/STP Category 5

Current consumption (mA)

410

630

Weight (kg)

0.11

0.11

Item
Communication specification

2MLL-EDMT

2MLL-EDMF

10/100BASE-TX

100BASE-FX, Fiber Optic


Dedicated protocol

Protocol

High Speed link, P2P service

With MasterLogic PLCs


Service

Network

FDEnet

With other devices

SoftMaster-200 service

Application

200 words /block

Sending/receiving data

64 stations

No. of connection stations


General use
Media

High-speed link communication among MasterLogic PLCs


UTP/STP Category 5

x62.5/125um, multi-mode, SC connector

Current consumption (mA)

410

630

Weight (kg)

0.11

0.11

MasterLogic-200
Honeywell's next generation
Programmable Logic Controller

31

Network / Snet system

Features
RS-232C, RS-422 & RS-485 serial communication protocols supported
Three models available, each has 2 ports with varying port types: both RS232C ports or both RS-422/485 ports or one each.

Both MODBUS master (P2P) & MODBUS slave protocol supported


(configurable, RTU / ASCII)

Adjustable baud rate (300~115,200bps) and other communication settings


Supports both full and half duplex
Multi-drop configuration supported up to 32 units
Long-distance communication via modem & telephone connection
Diagnostics using SoftMaster-PD software (I/O, link & service status),
monitoring send/receive frame packets

Easy replacement of communication modules


Program upload/download by SoftMaster-200 programming software (RS-

Network

232C)

Configurable MODBUS settings

Communication via RS-232C/422 devices


2MLT-PAFA

2MLT-CPUS

2MLI-A22A

2MLI-D22A

2MLQ-RY2A

2MLQ-TR2A

2MLQ-RY2A

2MLQ-TR8A

2MLK-CPUH/S
2MLL-C22A
2MLL-C42A
2MLL-CH2A

RS-232C/485
2MLT-PAFA

2MLT-CPUS

2MLI-A22A

2MLI-D22A

2MLQ-RY2A

2MLQ-TR2A

2MLQ-RY2A

2MLQ-TR8A

1: N and N: M connection (Honeywell and other)


Other PLC

2MLT-PAFA

2MLT-CPUS

2MLI-A22A

2MLI-D22A

RS-232C interface
Long distance available

2MLQ-RY2A

2MLQ-TR2A

2MLQ-RY2A

2MLQ-TR8A

2MLT-CPUS

2MLT-PAFA

2MLI-A22A

2MLI-D22A

2MLQ-RY2A

2MLQ-TR2A

2MLQ-RY2A

2MLQ-TR8A

RS-232C interface

2MLK-CPUH/S
2MLL-C22A
2MLL-CH2A
2MLT-PAFA

2MLT-CPUS

2MLI-A22A

2MLI-D22A

2MLQ-RY2A

2MLQ-TR2A

2MLQ-RY2A

2MLQ-TR8A

2MLK-CPUH/S
2MLL-C42A
2MLL-CH2A

32
2MLT-PAFA

2MLT-CPUS

2MLI-A22A

2MLI-D22A

2MLT-PAFA

2MLT-CPUS

2MLQ-TR2A

2MLQ-RY2A

2MLQ-TR8A

RS-232C interface

2MLK-CPUH/S
2MLL-C22A
2MLL-CH2A
2MLI-A22A

RS-422/485

2MLQ-RY2A

Other PLC

2MLI-D22A

2MLQ-RY2A

2MLQ-TR2A

2MLQ-RY2A

2MLQ-TR8A

MasterLogic-100R

Specifications
Specifications

Item
Interface

2MLL-C22A

2MLL-C42A

2MLL-CH2A

RS-232C, 2 channels

RS-422, 2 channels

RS-232C/RS-422, 1 channel each

Remote communication with external devices via modem connection. Available for only RS-232C port.

Modem connection
Dedicated

1: 1 or 1: N communication using MLDP (MasterLogic dedicated protocol) with Experion or other SCADA

Communication
mode

SoftMaster-200

Operation
mode

Server (Slave)

Program upload/download and remote control


User-defined protocol with SoftMaster-PD software for interface with other PLCs

P2P

MODBUS RTU/ASCII master communication


Remote connection using MasterLogic Dedicated Protocol (MLDP) or MODBUS server

Master

MODBUS RTU/ASCII master, user-defined protocol

Start Bit
2MLT-PAFA

2MLT-CPUS

2MLI-A22A

2MLI-D22A

2MLQ-RY2A

2MLQ-TR2A

2MLQ-RY2A

2MLQ-TR8A

Data Bit

7 or 8
1 or 2

Stop Bit

Data type

Even/Odd/None

Parity

Network

Basic parameter setting with SoftMaster-PD

Setting
Synchronization

Asynchronous

Transmission speed (bps)

Selectable among 300/600/1,200/2,400/4,800/9,600/19,200/38,400/57,600/115,200 bps

Station number setting

Up to 32 stations from 0 to 31 with SoftMaster-PD

Transmission distance

RS-232C: Max. 15m (Extendible by using modem), RS-422/485: Max. 500m

Modem communication

Available

Not available

Network configuration

Available via RS-232C

RS-232C 1: 1, RS-422 1: 1, 1: N, N: M

Diagnosis function

Available through LED and SoftMaster-PD diagnosis service, loop back

Current consumption (mA)

310

300

310

Weight (kg)

0.12

0.12

0.12

2MLT-PAFA

2MLT-CPUS

2MLI-A22A

2MLI-D22A

2MLQ-RY2A

2MLQ-TR2A

2MLQ-RY2A

2MLQ-TR8A

2MLT-PAFA

2MLT-CPUS

2MLI-A22A

2MLI-D22A

2MLQ-RY2A

2MLQ-TR2A

2MLQ-RY2A

2MLQ-TR8A

MODBUS
SMART I/O
RS-232C interface
Long distance available
MSL-D22A/D24A

2MLK-CPUH/S
2MLL-C22A
2MLL-CH2A
2MLT-PAFA

2MLT-CPUS

2MLI-A22A

2MLI-D22A

2MLQ-RY2A

2MLQ-TR2A

2MLQ-RY2A

Inverter

MasterLogic-100

MSL-TR2A/TR4A

Other PLC

2MLQ-TR8A

MSL-RY2A
2MLK-CPUH/S
2MLL-C42A
2MLL-CH2A

MSL-DT4A

RS-422/485 interface (Modbus)

Snet cable connection


Cnet (9Pin, Male)
Cnet (9Pin, Male)

Cnet (9Pin, Male)


Cnet (9Pin, Male)

Cnet (9Pin, Male)


Cnet (9Pin, Male)

PC (9Pin, Female)
PC (9Pin, Female)

MasterLogic-200
Honeywell's next generation
Programmable Logic Controller

33

Network / Rnet system

Features

Honeywell proprietary for communication with Smart I/O modules


High speed communication: 1Mbps
Long communication distance: Max. 750m per segment
Distance increased by using repeaters (max 6, support up to 5.25km)
Network management using AUTO SCAN (Slave module information)
Multi-drop network to Smart I/O modules (MRL series
Communication diagnosis and status monitoring from SoftMaster-PD

Network
System configuration
2MLT-PAFA

2MLT-CPUS

2MLI-A22A

2MLI-D22A

2MLQ-RY2A

2MLQ-TR2A

2MLQ-RY2A

2MLQ-TR8A

2MLT-PAFA

2MLT-CPUS

2MLI-A22A

2MLI-D22A

2MLQ-RY2A

2MLQ-TR2A

2MLQ-RY2A

2MLQ-TR8A

2MLK-CPUH/S
2MLL-RMEA

Repeater
MOL-FREB
MOL-FREC

Electric/optical
MOL-FOEA

SMART I/O Rnet


MRL-D22A

MRL-TR2A
MRL-TR4A
PMU Series
PMO-730R
PMO-530R
PMO-330R

MRL-RY2A

MRL-DT4A

34

Specifications
Item

Specifications (2MLL-RMEA)
1Mbps

Transmission speed

Manchester Biphase-L

Encoding

Max. 750m

Transmission distance (Per segment)

Max 750m *(6 repeaters +1) = 5.25km

Transmission distance (When using repeaters)

Twisted pair shield cable

Transmission cable
Max. size of protocol

256 bytes

Medium access method

Circulated Token Passing

Frame error check

CRC 16 check

Installation position

Main base or expansion base

Current consumption (mA)

410

Weight (kg)

0.12

Network

SMART I/O
Reduction of wiring costs and hassles
Easy to install and implement
Real-time monitoring & control of distributed
I/O

Various digital I/O module types available


(16/32 points)

Serves as an RTU

Repeater specifications
Item

Specifications
M0L-FREB: AC110V ~ AC220V, M0L-FREC: DC 24V

Type
Communication speed

1Mbps

Transmission method

Twisted pair shield cable

Transmission distance

Max. 750m per repeater


Max. 6 repeaters

Max. number of installation between stations

5.25km (when 6 repeaters are installed)

Max. distance between stations

Error data transmission

Faulty data reception

CRC 16 check

Frame error check

Network cable and peripheral devices


Item
Twisted pair electric cable
Terminator resistor

Specifications

Remarks

LIREV-AMESB, 2 X 1 mm, 18AWG


110, 1/2Watt

MasterLogic-200
Honeywell's next generation
Programmable Logic Controller

35

Network / Dnet system

Features

Network
36

Open communication with all DeviceNet devices (actuators, sensors, drives, switches, valves etc)
Compliance to ODVA standard
Flexible communication speed setting: 125, 250, 500Kbps
Flexibility in network configuration: Multi-drop and T branch connection
Max. 63 slave modules controlled by one master module
Long communication distance: Max. 500m
Easy configuration through SyCon/Softmaster-PD software
Diagnostics & status monitoring of slave modules in the network using Auto-Scan (SoftMaster-PD)
Communication setup using High Speed link parameter

Specifications
Item

Specifications (2MLL-DMEA)
Master

Module type
Trans. speed

Max. network length

Max. drop cable

Length of all drop cable

Transmission

500kbps

100m

6m

39m

distance and speed

250kbps

250m

6m

78m

125kbps

500m

6m

156m

Max. number of

64 stations (Master 1 + Slave 63)

connection stations
Max. number of node

Max. 64 MAC ID/Identifier, Max. 2048 I/O points

Communication method

2MLT-PAFA

2MLT-CPUS

2MLI-A22A

2MLI-D22A

2MLQ-RY2A

Diagnosis function

2MLQ-TR2A

2MLQ-RY2A

2MLQ-TR8A

Strobe, Poll, COS, Cyclic

Duplicated station check Abnormal station detection/CRC error check/Scan List/Operation display (LED)

Cable

Dnet dedicated cable: 5 (Signal: 2, power: 2, shield: 1)


SyCon

Configuration port

RS-232C Configuration Port

Current consumption (mA)

440

Weight (kg)

0.11

Network

Configuration tool

System configuration

2MLT-PAFA

2MLT-CPUS

2MLI-A22A

2MLI-D22A

2MLQ-RY2A

2MLQ-TR2A

2MLQ-RY2A

2MLQ-TR8A

SyCon, SoftMaster-PD
2MLK-CPUH/S
2MLL-DMEA
(Master)

A.B, OMRON,
FUJI

DeviceNet
Driver

SMART I/O Dnet


MDL-D22A/C
MDL-D22A/C

A.B

OMRON

MDL-TR2A/A1/B/C/C1
MDL-TR4A/A1/B/C/C1

MDL-RY2A/C
Other inverter
(DeviceNet driver)

Other DeviceNetTM I/O devices


MDL-DT4A/A1/B/C/C1

MasterLogic-200
Honeywell's next generation
Programmable Logic Controller

37

Network / Pnet system

Features
Open communication with Profibus-DP devices (transducers, drives, starters etc)
Compliance to DP standard
Transmission speed: 9.6Kbps ~ 12Mbps
Long communication distance: Max. 1200m
One master module can communicate with several distributed slave I/O devices
Max. 126 slave stations available (32 stations per segment)
Low cost network to field
Easy configuration through SyCon/SoftMaster-PD software & HS link parameter
Available to use 7K I/O data of master station
Diagnostics & status monitoring of slave modules in the network using Auto-Scan (SoftMaster-PD)
Supports multi-master

Network
38

Specifications
Item

Specifications (2MLL-PMEA)

Module type

Master

Network type

Profibus-DP

Standard

EN50170/DIN19245

Interface

RS-485 (Electric)

Media access

Token Passing & Poll

Topology

Bus

Modulation

NRZ

Cable

Shield Twisted Pair Cable


1,000m

9.6K~187Kbps

Transmission distance

400m

and speed

200m

1.5Mbps

100m

3M~12Mbps

500Kbps

Max. number of slave per network

126

Max. number of slave per segment

32

Network

Max. I/O data

Input: 3584Byte, Output: 3584Byte

Max. number of communication points

7Kbytes

Communication parameter setting

SoftMaster-PD, SyCon

Configuration Tool

SyCon

Configuration Port

RS-232C Configuration Port

Current consumption (mA)

550

Weight (kg)

0.11

System configuration with other products

2MLT-PAFA

2MLT-CPUS

2MLI-A22A

2MLI-D22A

2MLQ-RY2A

2MLQ-TR2A

2MLQ-RY8A

2MLQ-TR8A

SyCon,
SoftMaster-PD
2MLK-CPUH/S
2MLL-PMEA

A.B, Siemens

Profibus
Device Driver

SMART I/O Pnet


MPL-D22A/C

A.B

Siemens

MPL-TR2A/A1/B/C/C1

MPL-RY2A/C
Other inverter

Other Profibus I/O devices


MPL-DT4A/A1/B/C/C1

MasterLogic-200
Honeywell's next generation
Programmable Logic Controller

39

Network / Communication example (Snet)

Serial
Communication
between PLCs

This example demonstrates implementing serial communication between MasterLogic-200 PLCs usingzz modules. In this
example, PLC1 is the master (Client) and other PLCs are slaves (Server). The master PLC is configured using communication
basic parameter and P2P settings. And slave PLC is configured using basic parameter and driver setting.

Data memory

Objective
PLC1 continuously reads current value of PLC2s address C0000
(upcounter) and transfers it to address M0200 of PLC1.
2MLL-C22A
2MLL-C42A
2MLL-CH2A

RS-232C/422/485
115,200bps
2MLT-PAFA

2MLT-CPUS

2MLI-A22A

2MLI-D22A

2MLQ-RY2A

2MLQ-TR2A

2MLQ-RY8A

2MLQ-TR8A

2MLQ-RY4A

2MLQ-TR4A

2MLT-PAFA

2MLT-CPUS

2MLI-A22A

2MLI-D22A

2MLQ-RY2A

2MLQ-TR2A

2MLQ-RY8A

2MLQ-TR8A

2MLQ-RY4A

PLC station

PLC memory

PLC 1

M0100

PLC 2

C0000

2MLQ-TR4A

Setting Item
1. SoftMaster-PD parameter setting,
2. SoftMaster-200 programming
1. SoftMaster-PD parameter setting,
2. SoftMaster-200 programming

PLC2 (Slave)

PLC1 (Master)

SoftMaster-PD setting
Network

PLC 1 setting (Master)

Communication basic parameter setting


Setting up station number, communication
speed, etc. And setting up the operation
mode as P2P (PTP)

Enable Link
Enabling P2P (PTP) for communication
start

P2P (PTP) channel setting


Setting up channel 01 as
[MLDP client]

Parameter writing
Downloading parameters to PLC after
online connection

P2P setting
Setting up P2P block (READ)

Communication data setting


Setting up Read area, Save area, etc.

PLC 2 setting (Slave)

Communication parameter setting


Setting up station number and channel 01
mode as 1 and MLDP server

SoftMaster-200 programming
PLC station 2 setting
Make up-counter program using
CTU command

PLC station 1 setting


Check out the counter value of
M0100 is transmitted.

40

Parameter writing
Downloading parameters to PLC after
online connection

* For basic parameter setting and SyCon setting/change, reset the module (Online reset).

Serial
communication
with Experion PKS
/ Other HMI

This example demonstrates implementing serial communication between MasterLogic-200 PLC and Experion PKS SCADA.
In this example, PLC is the slave (Server) and Experion PKS SCADA is the Master (Client). The slave PLC is configured using
communication basic parameter and driver setting.

Objective

Data memory
Providing On/Off command from Experion PKS SCADA to control
address M0001 in PLC.

PLC memory

Setting item
1. SoftMaster-PD parameter setting

M00001

2. SoftMaster-200 programming

Experion PKS
Using SCADA
Point

2MLL-C22A
2MLL-C42A
2MLL-CH2A

RS-232C / 422 / 485


115, 200kps
2MLT-PAFA

2MLT-CPUS

2MLI-A22A

2MLI-D22A

2MLQ-RY2A

2MLQ-TR2A

2MLQ-RY8A

2MLQ-TR8A

2MLQ-RY4A

2MLQ-TR4A

Network

SoftMaster-PD setting

Basic communication parameter setting


Setting up station number, communication
speed, etc And setting up the operation
mode as MLDP server or MOBUS RTU/
ACSII

Parameter writing
Downloading parameters to PLC after
online connection

Experion PKS SCADA Setting


Setting up communication setting (speed, data,
stop, parity, etc) same as MasterLogic-200

* For basic parameter setting and SyCon setting/change, reset the module (Online reset).

SoftMaster-200 programming
Create program that
P00010 is on right
after M00001
is on.

MasterLogic-200
Honeywell's next generation
Programmable Logic Controller

41

Network / Communication example (FEnet)

Fast Ethernet
communication
with Experion
PKS /Other HMI

This example demonstrates implementing Fast Ethernet communication between MasterLogic-200 & Experion PKs SCADA/
other HMI using FENet module. HS link services are used. Setup involves just a few simple configuration steps i.e. basic
parameter, HS link item settings etc.

Objective

Data memory
Read the up-counter value C0000 of PLC1 and monitor it from
Experion PKS SCADA/Other HMI Software.

PLC memory

Setting item

Other HMI

1. SoftMaster-PD parameter setting


C0000

Using analog tag


2. SoftMaster-200 programming

PC IP: 100.100.100.1

Fast Ethernet (100Mbps)


2MLL-EFMT
2MLT-PAFA

2MLT-CPUS

2MLI-A22A

2MLI-D22A

2MLQ-RY2A

2MLQ-TR2A

Network

PLC1 IP: 100.100.100.2

2MLL-EFMT
2MLT-PAFA

2MLT-CPUS

2MLI-A22A

2MLI-D22A

2MLQ-RY2A

2MLQ-TR2A

PLC2 IP: 100.100.100.3

2MLL-EFMT
2MLT-PAFA

2MLT-CPUS

2MLI-A22A

2MLI-D22A

2MLQ-RY2A

2MLQ-TR2A

2MLL-EFMT
2MLT-PAFA

PLC3 IP: 100.100.100.4

2MLT-CPUS

2MLI-A22A

2MLI-D22A

2MLQ-RY2A

2MLQ-TR2A

PLC4 IP: 100.100.100.5

SoftMaster-PD setting
PLC 1 setting (Master)

Basic communication parameter setting


Specifying IP address and Subnet mask of
PLC as above. Also choose MLDP server or
MOBUS TCP server as the driver

Ping Test
Starting diagnosis after inputting IP
address of PLC

System Diagnosis
Selecting Ping Test

Parameter writing
Downloading parameters to PLC after
online connection

Communication test
Check online and system diagnosis.

* For basic parameter setting and SyCon setting/change, reset the module (Online reset).

SoftMaster-200 programming
Make the up-counter program
using CTU command.
Check out if the counter
value of CTU value is transmitted.
Observe
the value in
Experion PKS/
Other HMI

42

Fast Ethernet
communication
between PLCs

This example demonstrates implementing Fast Ethernet communication between MasterLogic-200


PLCs using FENet module. HS link services are used. Setup involves just a few simple configuration
steps i.e. basic parameter, HS link item settings etc.
Note: This example shows the use of FENet module. However, FDENet (Fast dedicated Ethernet)
module is recommended for dedicated peer-to-peer communications between MasterLogic-200
PLCs. Setup of FDEnet is also very similar to FENet module i.e. basic parameter, HS link item
settings etc.

Data memory

Objective
Read present value C0000 of PLC1
and transmit it to M0000 of PLC2.

PLC station

Fast Ethernet (100Mbps)


2MLL-EFMT
2MLT-PAFA

2MLT-CPUS

2MLI-A22A

2MLI-D22A

2MLQ-RY2A

2MLQ-TR2A

2MLT-PAFA

2MLT-CPUS

2MLI-A22A

2MLI-D22A

2MLQ-RY2A

2MLQ-TR2A

PLC2 IP: 100.100.100.3


2

2MLL-EFMT
2MLT-PAFA

2MLT-CPUS

2MLI-A22A

2MLI-D22A

2MLQ-RY2A

2MLQ-TR2A

PLC3 IP: 100.100.100.4


3

PLC 1

C0000

PLC 2

M0100

Setting Item
1. SoftMaster-PD parameter setting,
2. SoftMaster-200 programming
1. SoftMaster-PD parameter setting,
2. SoftMaster-200 programming

2MLL-EFMT
2MLT-PAFA

2MLT-CPUS

2MLI-A22A

2MLI-D22A

2MLQ-RY2A

2MLQ-TR2A

PLC4 IP: 100.100.100.5


4

Network

PLC1 IP: 100.100.100.2


High Speed link station
number 1

2MLL-EFMT

PLC memory

SoftMaster-PD setting
PLC station 1
setting
Parameter writing
Downloading parameters to PLC
after online connection

Basic communication parameter setting


Specifying HS link station, IP address and
Subnet mask of PLC as above

Communication data setting


Setting up communication data in HS link
item as above

Enable Link
Enabling link for communication
start

PLC station 2
setting

Parameter writing
Downloading parameters to PLC
after online connection

Basic communication parameter setting


Specifying HS link station, IP address and
Subnet mask of PLC as above

Communication data setting


Setting up communication data in HS link
item as above

Enable Link
Enabling link for communication
start

* For basic parameter setting and SyCon setting/change, reset the module (Online reset).

SoftMaster-200 programming
PLC1 setting
Make the up-counter
program using CTU
command

PLC2 setting
Check out if the counter
value of M0100 is
transmitted.
MasterLogic-200
Honeywell's next generation
Programmable Logic Controller

43

Network / Communication example (Rnet)


For simple remote I/O applications, Smart I/O modules make easy implementation. They are standalone DIN rail mounted
block I/Os supporting communication with MasterLogic-200 both on Honeywell proprietary (Rnet) and also open protocols
Profibus-DP, DeviceNet, MODBUS etc.

Block-type
remote I/O
configuration
with
MasterLogic200 PLCs

In this example, only Rnet protocol is discussed where 2MLL-RMEA is the Rnet master module in MasterLogic-200 and other
Rnet Smart I/O modules are slaves. Setup is again simple involving just a few configuration steps i.e. basic communication
parameters and high speed link setting.

Objective

2MLL-RMEA

PLC controls of monitors


each smart I/O module
(16 channel)

2MLT-PAFA

2MLT-CPUS

2MLI-A22A

2MLI-D22A

2MLQ-RY2A

2MLQ-TR2A

2MLQ-RY8A

2MLQ-TR8A

2MLQ-RY4A

2MLQ-TR4A

PLC (Master)
Rnet 1Mbps, 750m
MRL-D22A

MRL-D22A

MRL-D22A

MRL-TR22A

MRL-TR22A

Smart I/O
#1 (Input)

#2 (Input)

#3 (Input)

#4 (Output)

#5 (Output)

Data memory
Network

Smart I/O #
1

Smart I/O address

PLC address

P0000

P0010 (P00100~P0010F)

Setting item

P0000

P0011 (P00110~P0011F)

P0000

P0012 (P00120~P0012F)

P0000

P0013 (P00130~P0013F)

P0000

P0014 (P00140~P0014F)

1. SoftMaster-PD parameter setting,


2. SoftMaster-200 programming

SoftMaster-PD setting
Communication data setting
Setting up type name, station
number, address of each stations
Smart I/O in HS link item as
following example.

HS link registration completed

Parameter writing
Downloading parameters to PLC
after online connection

* For basic parameter setting and SyCon setting/change, reset the module (Online reset).

SoftMaster-200 programming
Write a program using I/O
address of Smart I/O.

44

Enable Link
Enabling link for communication
start

Network / Communication example (ProfibusTM-DP)


Communication
with ProfibusDP standard
devices
(transducers,
drives, starters
etc)

This example demonstrates how easy is implementing Profibus-DP open communication to DP standard compliant devices
using 2MLL-PMEA master module.
In this case, 2MLL-PMEA is the Pnet (Profibus-DP) master and the other devices are slaves. Setup is simple involving
Sycon software and basic parameter and high speed link settings.

Configuration

2MLL-PMEA

PLC controls & monitors


each ProfibusTM-DP device
on the Pnet network.

2MLT-PAFA

2MLT-CPUS

2MLI-A22A

2MLI-D22A

2MLQ-RY2A

2MLQ-TR2A

2MLQ-RY8A

2MLQ-TR8A

2MLQ-RY4A

2MLQ-TR4A

PLC (Master)
Profibus-DP 12Mbps
MPL-D22A

#15 (Input)

MPL-TR2A

#20 (Output)
Profibus Smart I/O Modules

MPL-TR2A

#21 (Output)
Inverter

Other
Profibus
devices

Smart I/O #

Smart I/O address

PLC address

Setting item

15

P0000

P0010 (P00100~P0010F)

20

P0000

P0011 (P00110~P0011F)

21

P0000

P0012 (P00120~P0012F)

1. SyCon setting
2. SoftMaster-PD parameter setting,
3. SoftMaster-200 programming

Network

Data memory

SoftMaster-PD setting

SyCon setting
For detailed setting instruction, refer to
page 43 (SyCon setting)

HS link setting
Uploading SyCon and setting up each
Smart I/O station as following example

Parameter writing
Downloading parameters to PLC after
online connection

Enable Link
Enabling link for communication
start

* For basic parameter setting and SyCon setting/change, reset the module (Online reset).

SoftMaster-200 programming
Write a program using I/O
address of Smart I/O Pnet

MasterLogic-200
Honeywell's next generation
Programmable Logic Controller

45

Network / Communication example (DeviceNetTM)

Communication
with DeviceNet
standard devices
(switches, valves,
sensors etc)

This example demonstrates how easy implementing DeviceNet communication to ODVA standards compliant devices is by using
2MLL-DMEA master module.
In this case, 2MLL-DMEA is the Dnet (Profibus-DP) master and the other devices are slaves. Setup is simple involving Sycon
software and basic parameter and high speed link settings.

Configuration
PLC controls & monitors
each DeviceNetTM device
in the Dnet network.

2MLL-DMEA
2MLT-PAFA

2MLT-CPUS

2MLI-A22A

2MLI-D22A

2MLQ-RY2A

2MLQ-TR2A

2MLQ-RY8A

2MLQ-TR8A

2MLQ-RY4A

2MLQ-TR4A

PLC (Master)
DeviceNet 500kbps
MDL-D22A

#19 (Input)

MDL-TR2A

#20 (Output)
DeviceNet Smart I/O Modules

MDL-TR2A

#21 (Output)
Inverter

Network

Data memory
Smart I/O #

Smart I/O address

PLC address

Setting item

19

P0000

P0010 (P00100~P0010F)

20

P0000

P0011 (P00110~P0011F)

21

P0001

P0012 (P00120~P0012F)

1. SyCon setting
2. SoftMaster-PD parameter setting,
3. SoftMaster-200 programming

SoftMaster-PD setting

SyCon setting
For detailed setting instruction, refer to
page 43 (SyCon setting)

HS link setting
Uploading SyCon and setting up each
Smart I/O station as following example

Parameter writing
Downloading parameters to PLC after online
connection

Enable Link
Enabling link for communication
start

* For basic parameter setting and SyCon setting/change, reset the module (Online reset).

SoftMaster-200 programming
Write a program
using Smart I/O
address of
Smart I/O Dnet
module.

46

Other
DeviceNetTM
devices

Network / Communication (SyCon)

SyCon is the dedicated software that helps a user set up the communication environment for
Profibus-DP and DeviceNet more easily and conveniently.

Example of application

New file
Select fieldbus that is used.

Basic communication parameter setting


Select [Master] in Insert menu.

Master module setting


Select [COM-C-DNM] for DeviceNet
Select [COM-C-DPM] for Profibus-DP

Network

Bus parameter setting


Setting up communication speed of
master module

Master module setting


After clicking the port button, check
the right check-box.

Automatic network scan of connected Smart I/O and other Profibus-DP or DeviceNet devices
Perform automatic network scan after station number
setting and wiring with remote device such as Smart I/O.
At this time, all remote devices should be in normal connection (Power-On, etc).
After network scan is completed, press [Automatic Configuration] button and [OK] button.

Network checking
Check normal network (remote) condition.

Parameter download

Disconnect
Disconnect the port in Device
Assignment

MasterLogic-200
Honeywell's next generation
Programmable Logic Controller

47

Smart I/O modules

Features
Wiring reduction and real time control of distributed I/O
Supporting Rnet, DeviceNet, Profibus-DP, Modbus (RS-422/485)
Various I/O (DC/TR/Relay) modules with the unit of 16/32 points

Specifications
Input

Item
No. of point
Rated input (Load voltage)

Output

DC (Sink/Source)

Transistor (Sink)

16

16

32
DC 24V

Input current (Load current)

32
DC 24V

16

16

16

DC 24V/AC 110V/220V

DC 24V

DC 24V
0.1A/2A, 0.5A/3A

Network

2A/5A

7mA

Response

Off -> On

3ms or less

3ms or less

3ms or less

3ms or less

3ms or less

time

On -> Off

3ms or less

3ms or less

3ms or less

3ms or less

3ms or less

16 points/COM

16 points/COM

16 points/COM

Common

7mA

Mixed module
DC (Sink/Source) Transistor (Sink)

Relay

0.1A/2A, 0.5A/3A

16 points/COM

Current consumption

Network

200mA

300mA

280mA

380mA

350mA
MRL-DT4A

Rnet

MRL-D22A

MRL-D24A

MRL-TR2A

MRL-TR4A

MRL-RY2A

Profibus-DP

MPL-D22A

MPL-D24A

MPL-TR2A MPL-TR4A

MPL-RY2A

MPL-DT4A

DeviceNet

MDL-D22A MDL-D24A

MDL-TR2A MDL-TR4A

MDL-RY2A

MDL-DT4A

Modbus

MSL-D22A

MSL-TR2A

MSL-RY2A

MSL-DT4A

MSL-D24A

Note1) Specification stated in the table is specification of type A.


Refer to MasterLogic-200 user s manual.
A, C

16 points/COM

550mA

MSL-TR4A

A Sink, Rated current: 0.1A, terminal fixed type


A1 Sink, Rated current: 0.5A, terminal fixed type

A, A1, B, C, C1

B Source, Rated current: 0.5A, terminal fixed type


C Source, Rated current: 0.5A, terminal separated type
C1 Sink, Rated current: 0.5A terminal separated type

Communication specifications
Item
Protocol
Transmission speed
Transmission distance
Topology

Profibus-DP

DeviceNet

Modbus

Honeywell dedicated protocol

Profibus-DP
(RS-485/EN50170)

DeviceNet (CAN)

Modbus (RS-422/485)

Rnet (Honeywell Dedicated & network for Smart I/O)

1Mbps

9.6kbps ~ 12Mbps

125/250/500Kbps

2.4Kbps ~ 38.4Kbps

750m/segment

100m ~ 1.2km

500/250/125m (Thin cable: 100m)

500m

Bus Token

Bus

Trunk & Drop

Bus

Transmission

Pass & Broadcast

No. of stations
Link capacity

Token Pass &

CSMA/NBA

Master/Slave (Poll)

Master/Slave (Poll)

(Poll, Cyclic, COS, Bit Strobe)

32/segment (Input: 32, Output: 32)

32/segment, 99/network

64

32

2,048points/Master
(64 stations x 32 points)

7KB/master

2,048 points/master

64 points/station

Note1) Smart I/O supports Poll type currently; in future, cos, cyclic and strobe will be supported

Dimensions

16points

* MxL-RY2 (16-point relay output) module follows the dimension of 32-point module.
* The length of C type Smart I/O is 47.5mm

48

32points

Unit: mm

2MLT-PAFA
2MLT-PAFA

Smart I/O Rnet system

2MLT-CPUS
2MLT-CPUS

2MLI-A22A
2MLI-A22A

2MLI-D22A
2MLI-D22A

2MLQ-RY2A
2MLQ-RY2A

2MLQ-TR2A
2MLQ-TR2A

2MLT-PAFA

2MLT-CPUS

2MLI-A22A

2MLI-D22A

2MLQ-RY2A

2MLQ-TR2A

2MLT-PAFA

2MLT-CPUS

2MLI-A22A

2MLI-D22A

2MLQ-RY2A

2MLQ-TR2A

2MLT-PAFA
2MLT-PAFA

2MLT-CPUS
2MLT-CPUS

2MLI-A22A
2MLI-A22A

2MLI-D22A
2MLI-D22A

2MLQ-RY2A
2MLQ-RY2A

2MLQ-TR2A
2MLQ-TR2A

2MLL-RMEA
MRL-D24A
MRL-DT4A
MRL-RY2A
MRL-TR4A

Max. 32 stations
(including master)
/segment

MSL-D22A
MSL-TR2A

MSL-D24A
MSL-DT4A
MSL-RY2A
MSL-TR4A

Max. 32 stations
(including master)

MPL-D22A
MPL-TR2A

MPL-D24A
MPL-DT4A
MPL-RY2A
MPL-TR4A

Max. 64 stations
(including master)
/segment

MDL-D24A
MDL-DT4A
MDL-RY2A
MDL-TR4A

Max. 64 stations
(including master)

MRL-D22A
MRL-TR2A

Note1)

Smart I/O MODBUS system


2MLT-PAFA

2MLT-CPUS

2MLI-A22A

2MLI-D22A

2MLQ-RY2A

2MLQ-TR2A

2MLT-PAFA

2MLT-CPUS

2MLI-A22A

2MLI-D22A

2MLQ-RY2A

2MLQ-TR2A

Smart I/O Profibus-DP system


2MLT-PAFA
2MLT-PAFA

2MLT-CPUS
2MLT-CPUS

2MLI-A22A
2MLI-A22A

2MLI-D22A
2MLI-D22A

2MLQ-RY2A
2MLQ-RY2A

2MLQ-TR2A
2MLQ-TR2A

2MLL-PMEA

2MLT-PAFA

Smart I/O DeviceNet system


2MLT-PAFA

2MLT-PAFA
2MLT-PAFA

2MLT-CPUS

2MLI-A22A

2MLI-D22A

2MLQ-RY2A

2MLQ-TR2A

2MLT-CPUS

2MLI-A22A

2MLI-D22A

2MLQ-RY2A

2MLQ-TR2A

2MLT-CPUS
2MLT-CPUS

2MLI-A22A
2MLI-A22A

2MLI-D22A
2MLI-D22A

2MLQ-RY2A
2MLQ-RY2A

Note1)

2MLQ-TR2A
2MLQ-TR2A

2MLL-DMEA
MDL-D22A
MDL-TR2A

Note1) Segment: Communication section that does not use repeater or second master.
2MLT-PAFA

2MLT-CPUS

2MLI-A22A

2MLI-D22A

2MLQ-RY2A

2MLQ-TR2A

2MLT-PAFA

2MLT-CPUS

2MLI-A22A

2MLI-D22A

2MLQ-RY2A

2MLQ-TR2A

MasterLogic-200
Honeywell's next generation
Programmable Logic Controller

49

Network

2MLL-C42A

Special

Special
MasterLogic-200 offers several special modules such
as analog I/O, high speed counter (pulse input), and
positioning modules that serves diverse industrial needs.
So, if your PLC application demands process control (e.g.
temperature, pressure, flow etc) or an incremental encoder
input or advanced position control (e.g. servo motor),
MasterLogic-200 offers the best fit special module to your
needs.

50

MasterLogic-200 Special module


High speed processing e.g. A/D conversion e.g. 50s/channel

Setup via Programming network

Setup via software tool

Engineer friendly easy setup via software tool & avoid configuration via
programming method as before
SoftMaster-200 offers useful monitoring & diagnostic tools
Easy maintenance: Wizards to change special modules online without

Example of programming

turning off or holding CPU (hot-swapping).

Monitoring of special module

Analog input module


Spec.
2MLF-AV8A 8 channels, voltage input
2MLF-AC8A 8 channels, current input

2MLT-PAFA

2MLT-CPUS

2MLT-CPUS

Special

Normal

2MLT-PAFA

Analog output module


Normal

Spec.
2MLF-DV4A 4 channels, voltage input
2MLF-DC4A 4 channels, current input

Temperature input module


(under development)
Normal
Isolation

Spec.
4 channels,
2MLF-TC4S
thermocouple (isolation)
2MLF-RD4A 4 channels, RTD

High-speed counter module


Spec.
2MLF-HO2A 2channels, DC input
High-speed
2channels,
counter
2MLF-HD2A
differential input

Positioning module
Spec.

2MLF-PO3A

2MLF-HO2A

2MLF-PO3A

2MLF-HO2A

2MLT-PAFA

2MLT-PAFA

2MLT-CPUS

2MLT-CPUS

1/2/3 axis,
open collector
1/2/3 axis,
2MLF-PD3 (2/1)A
line driver
2MLF-PO3 (2/1)A

Normal

Motion control module


Motion

Spec.
For motion control,
2MLF-M16M
16 axes
MasterLogic-200
Honeywell's next generation
Programmable Logic Controller

51

Special module / Analog input module

Features
High speed A/D conversion & processing i.e. 50s/channel
High resolution (16 bit)
Easy configuration via SoftMaster-200 software and avoiding programming
Digital value after A/D conversion in 4 data formats

Specifications
Item

2MLF-AV8A (Voltage input type)

2MLF-AC8A (Current input type)

No. of input channel

8 channels
DC 1~5V, 0~5V

Analog input

DC 4~20mA

DC 0~10V, -10~10V

DC 0~20mA

Analog Input range configurable for each channel via software


Analog input

1~5V

0~5V

0~10V

Unsigned value
Voltage

Digital

Signed value

value

Precise value

-8,000~8,000
1,000~5,000

0~5,000

Percentile value

Digital value

0~10,000

-10,000~10,000

0~10,000

Analog input

4~20mA

0~20mA

Special

Unsigned value
Current

-10~10V

0~16,000

Digital

Signed value

value

Precise value

0~16,000
-8,000~8,000
4,000~20,000

0~20,000

Percentile value

0~10,000

Digital value format configurable for each channel via software


1/16,000
Resolution

Accuracy

1~5V

0.250mV

0~5V

0.3125mV

0~10V

0.625mV

10V

1.250mV

Max. absolute output


Insulation method

30mA

Photo-coupler isolation between input terminal and power supply (No isolation between channels)
18 points terminal
Fixed type: 64 points

assigned

Variable type: 16 points

Current consumption
Weight (kg)

DC 5V: 420mA

DC 5V: 420mA

0.14

Configuration

0.14

A/D conversion characteristics


+
-

Transducer
PreAmp

Digital value

Voltage, Current, Temperature,


flow, Pressure, etc.

-10V

52

1.25A

50s/channel

#I/O address

2MLF-AC8A

0~20mA

15V

Connection terminal

1.0A

0.2% or less (Ambient temperature 25C), 0.3% or less (Range of operation temperature)

Conversion speed

2MLF-AV8A

4~20mA

Digital value

16,000

16,000

8,000

8,000

10V

Voltage input

0 4mA

12mA

20mA

Current input

Special module / Analog input module (Example)

This is a simple example to wire a voltage or current to the analog

System configuration
2MLT-PAFA

2MLT-CPUS

Wiring
2MLI-D22A

2MLI-A22A

2MLQ-RY2A

2MLQ-TR2A

2MLQ-RY8A

2MLQ-TR8A

2MLQ-RY4A

2MLQ-TR4A

Voltage type
sensor

Current type
sensor

AD module (Slot 2)
Sensor

2MLF-AV8A

2MLF-AC8A

Parameter setting
In the parameter setting box,
select slot and analog module
that you want to use.
(This example shows to
select '0' channel of voltage
input type.)

Special

Press the <Details> button at lower end of parameter setting box after
selecting the module.

Programming
Create a program for A/D conversion (0~10V to
0~16000).

Special devices for programming


Refer to user's manual for more details.
U02.0.0: Error
U02.11.0: Requesting error-clear
U02.02: Memory of channel A/D value
Uxy.aa.bb
x: Base number
y: Slot number
aa,bb: Refer to users manual.

MasterLogic-200
Honeywell's next generation
Programmable Logic Controller

53

Special module / Analog output module

Features
High speed D/A conversion & processing i.e. 250s/channel
High resolution (16 bit)
Easy configuration via SoftMaster-200 software and avoiding programming
Digital value for D/A conversion in 4 data formats
Analog Output range & digital value format configurable for each channel via
software.

LED status displays for RUN / ERROR conditions (blinking rate changes with
error category)

Each channel can be individually enabled / disabled. This helps in maintenance


and in improving overall processing speed by disabling all un-used channels.

Specifications
2MLF-DV4A (Voltage output type)

Item

2MLF-DC4A (Current output type)


4 channels

No. of output channel


Analog output range

DC 1~5V, 0~5V

DC 4~20mA DC 4~20mA

DC 0~10V, -10~10V

DC 0~20mA

Analog output range configurable for each channel via software


Voltage type
Analog
output

1~5V

0~5V

Digital value

Digital range

1,000~5,000

Precise value

0~5,000

0~10,000

-10,000~10,000

0~10,000

Current type

4~20mA

0~20mA

Special

0~16,000

Unsigned value
Digital value

-10~10V

-8,000~8,000

Signed value
Percentile value

Analog
output

0~10V
0~16,000

Unsigned value

-8,000~8,000

Signed value
4,000~20,000

Precise value

0~20,000
0~10,000

Percentile value

Digital value format configurable for each channel via software


1/16,000 (Per each input range)
Max. resolution

1~5V

0.250mV

0~5V

0.3125mV

0~10V

0.625mV

10V

1.250mV

Accuracy

4~20mA

1.0A

0~20mA

1.25A

0.2% or less (Ambient temperature 25C), 0.3% or less (Range of operation temperature)

Conversion speed

250s/channel

Max. absolute output


Insulation method

15V

24mA

Photo-coupler isolation between input terminal and power supply (No isolation between channels):

Connection terminal

18 point terminal

#I/O address

Fixed type: assign 64 points

assigned

Variable type: assign 16 points

Current

Internal

DC 5V: 300mA

consumption

External

DC24V: 400mA

0.15

Weight (kg)

Output wiring

I/O conversion characteristics


Voltage output

2MLF-DV4A
2MLF-DC4A

C
H
0

C
H
0

Controller
(Heater, Valve, etc.)

Power conversion
C
H
0

C
H
0

4~20mA
1

0~220V

Current output

10V

20mA

0V

12mA

-10V

4mA
0

8,000

16,000
Digitalvalue

54

8,000

16,000
Digital value

Special module / Analog output module (Example)

This is a simple example to wire a voltage or current load to the analog output module, setup D/A conversion parameters such as output range,
digital value type etc in Software-200 software and a sample ladder logic program to send the output. For more details, refer to users manual.

Wiring

System configuration
2MLT-PAFA

2MLT-CPUS

2MLI-A22A

2MLI-D22A

2MLQ-RY2A

2MLQ-TR2A

2MLQ-RY8A

2MLQ-TR8A

2MLQ-RY4A

2MLQ-TR4A

Voltage
manipulation
type load
DA module (Slot 2)
Device

24V

2MLF-DV4A

Current
manipulation
type load

24V

2MLF-DC4A

Parameter setting
In the parameter setting
box, select slot and analog
module that you want to use.
(This example shows to
select 0 channel of voltage
output type.)

Special

Press the <Details> button at lower end of parameter setting box after
selecting the module.

Programming
Create a program for D/A conversion (0~16000
to 0~10V).

Special devices for programming


Refer to user's manual for more details.
U02.02.0: Admitting Channel 0 output
U02.03: Output data of channel 0
Uxy.aa.bb
x: Base number
y: Slot number
aa,bb: Refer to user's manual.

MasterLogic-200
Honeywell's next generation
Programmable Logic Controller

55

Special module / High-speed counter module (Pulse-Input)

Features
Two models available: Voltage Input (Open collector) and Differential Input (Line Drive) each

with two channels.


Incremental encoder available
Supporting various pulse input voltages (5V, 12V, 24V)
Various multiplication factors for 1-phase and 2-phase pulse input
7 comparison operators for preset function. Two built-in transistor outputs for each channel.
6 additional functions e.g. Count Clear, Count Latch, Input Frequency, Revolutions per Hour etc.
Preset or Gate function either by program or external input
Function to prevent from counting external signal
Supporting HTL-level incremental encoder in the line-drive input type
Configuration and monitoring using Softmaster-200
LED status displays for input, output and module READY condition.

Specifications
Specification

Item

2MLF-HO2A

2MLF-HD2A

Signal

No. of
command

A Phase, B Phase

Input type

Voltage input (Open Collector)

Signal level

DC 5/12/24V

Input voltage

24V DC
(17.0V ~ 26.4V)

12V DC
(9.8V ~ 13.2V)

5V DC
(4.5V ~ 5.5V)

Input current

7~11mA

7~11mA

7~11mA

Min. On guaranteed voltage

17.0V

9.8V

Max. Off guaranteed voltage

4.5V

3.0V

Line Driver

RS-422 Line Drive


HTL Level Line Drive

4.5V
1.7V

Set by program (Count only in 'Enable')

Counter Enable
200Kpps

Special

Max. counting speed

500Kpps (HTL input: 250Kpps)

No. of channels

2 channels

Counting range

Signed 32 Bit (-2,147,483,647 ~ 2,147,483,647)

Counting type

Linear count

(Program setting)

(Generating Carry/Borrow when exceeding counting range, Max/Min value)


1 Phase input

Input mode

2 Phase input

(Program setting)

CW/CCW input
Voltage

Signal type
Up/Down
counter setting

Multiplication

1-phase input

Program or B-phase

2-phase input
CW/CCW

Phase difference
A-phase input: Up count

1/2 multiplication (Programming)

2-phase input

1/2/4 multiplication (Programming)

Signal
Control input

1 multiplication
Preset signal, Signal to admit additional signal (Setting by terminal block or programming)

Signal level

DC 5V/12V/24V input type (Selecting terminal)

Signal type

Voltage

No. of output point


External output

Operating
status display (LED)

Addition functions
(Program setting)

Type

2 points/channel: Terminal output available


Single comparison (>,>=,=,=<,<) or section comparison

Output type

Open Collector (Sink)

Input signal

A-phase, B-phase, Preset signal, Signal to admit additional signal

Output signal

OUT1, OUT2

Operation status

Module Ready, Pulse input status of A, B phase


Count clear, Count latch
Pulse frequency count (Each input channel)
Section count (Set time value:1~60000ms)
Measuring counting number per a unit time (Set time value:1~60000ms)
Preventing from counting (Setting by internal/external input during counting)
40-pin connector

Terminal block
Current consumption
Weight (kg)

B-phase input: Down count

1-phase input
CW/CCW

56

Differential input (Line Drive)


RS-422 Line Drive/HTL LEVEL Line Drive

270

330
0.09

A12V A24V
A_C

A5V

B12V B24V
CH0

B_C

B5V

P12V P24V
P_C

P5V

G12V G24V
G_C

G5V

A12V A24V
A_C

A5V

B12V B24V
CH1

B_C

B5V

P12V P24V
P_C

P5V

G12V G24V
G_C

G5V

CH0 OUT1 OUT0


CH1 OUT1 OUT0

Terminal block configuration


2MLF-HO2A
Pin layout

24V

24V

24G

24G

2MLF-HD2A
DC24V
+

Pin number

Pin layout

Signal name

Pin number

Signal name

CH1

A phase DC12V input

17

AI-

AI- Input (LINE DRIVE TTL LEVEL Input)

A phase DC24V input

18

AI+

AI+ Input (LINE DRIVE TTL LEVEL Input)

A_C

A phase COM

AII-

AII- Input (LINE DRIVE HTL LEVEL Input)

A5V

A phase DC5V input

AI+

19

20

AI-

AII-

AII+

20

AII+

AII+ Input (LINE DRIVE HTL LEVEL Input)

21

B12V

B phase DC12V input

BI-

BI+

21

BI-

BI- Input (LINE DRIVE TTL LEVEL Input)

22

B24V

B phase DC24V input

BII-

BII+

22

BI+

BI+ Input (LINE DRIVE TTL LEVEL Input)

23

B_C

B phase COM terminal

23

BII-

BII- Input (LINE DRIVE HTL LEVEL Input)

24

B5V

B phase DC5V input

24

BII+

BII+ Input (LINE DRIVE HTL LEVEL Input)

25

P12V

Preset DC12V input

P12V Preset DC12V input

A5V

26

P24V

Preset DC24V input

AI+

25

10

AI-

AII-

AII+

10

26

P24V Preset DC24V input

B12V B24V

11

27

P_C

Preset COM terminal

BI-

BI+

11

27

P_C

Preset COM terminal

12

28

P5V

Preset DC5V input

BII-

BII+

12

28

P5V

Preset DC5V input

13

29

G12V

Gate DC12V input

P_C

13

29

G12V Gate DC12V input

14

30

G24V

Gate DC24V input

G12V G24V

14

30

G24V Gate DC24V input

15

31

G_C

Gate COM terminal

15

31

G_C

Gate COM terminal

CH1 OUT1 OUT0

16

32

G5V

Gate DC5V input

CH1 OUT1 OUT0

16

32

G5V

Gate DC5V input

24V

24V

33

35

OUT1 Comparison output OUT1

24V

24V

33

OUT1 Comparison output OUT1

24G

24G

34

36

OUT0 Comparison output OUT0

24G

24G

35

34

36

OUT0 Comparison output OUT0

37

38

24V

External power supply

37

38

24V

External power supply

39

40

24G

DC24V

39

40

24G

DC24V

CH1

17

A12V

18

A24V

19

A5V

B12V B24V
B_C

A12V A24V
A_C

CH0

B5V

P12V P24V
P_C

P5V

G12V G24V
G_C

G5V

A12V A24V
A_C

CH1

B_C

B5V

P12V P24V
P_C

P5V

G12V G24V
G_C

G5V

CH0 OUT1 OUT0

DC24V

CH0

P12V P24V
P_C

P5V

G12V G24V
G_C

CH1

G5V

P12V P24V

G_C

P5V
G5V

CH0 OUT1 OUT0

DC24V

Special

CHO

CHO

AIAI+
Configuration
AII-

CH0

AII+

BI-

BI+

BII-

BII+

P12V P24V
P_C

P5V

G12V G24V
G_C

CH1

G5V

CPU

AI-

AI+

AII-

AII+

BI-

BI+

BII-

BII+

P12V P24V
P_C

P5V

G12V G24V
G_C

G5V

Setting preset value


Setting set value
Writing operation status

HO2A/
HD2A
CH0

Counter admission, Reset,


Output admission
Reading operation status
Reading counting value

A Phase input

Encoder

B Phase input
Preset input
Gate input
Output 1 (Comparison signal)

CH1

Motor

Inverter

Output 2 (Comparison signal)


PLC analog
output

CH0 OUT1 OUT0


CH1 OUT1 OUT0
24V

24V

24G

24G

DC24V

MasterLogic-200
Honeywell's next generation
Programmable Logic Controller

57

Special module / High-speed counter module

System configuration

Wiring
2MLF-HD2A

2MLI-A22A

2MLT-PAFA

2MLI-D22A

2MLF-HD2A

ENCODER

2MLQ-TR2A

ENCODER
2 Phase 1 multiplication
(A, B Phase)

2MLF-HD2A Slot 2
Counter output (OUT0)

DC 24V

DC 5V

* This is wiring diagram of line driver. For


open collector or other control, refer to
user's manual.

Control configuration
Light a lamp of output when preset value reaches 1000 of pulse input counted by encoder.
Current value of pulse is saved in D100~D101 and is monitored.

Module test (On Line)


Module test function of MasterLogic-200 enables to monitor operation status of high-speed counter module and to test-run.

Special
Select [Monitor] -> [Special Module
Monitoring] in menu and highlight
high-speed counter.

After pressing the button for


[Start Monitoring],
press the button [FLAG monitor].

Change [Counter Enable]


status to ON.

Check current counting value in 'Monitor


Special Module' screen box.

58

Parameter setting
In I/O parameter setting box, select slot and high-speed
counter (HSC) module that you want to configure.
(This example selects 2MLF-HD2A (line driver) type module)
Press the <Details> button at the button of parameter setting
box after selecting the module.

Input 1000 as Max. and Min. comparison output.

Programming
After creating a program like in the example here, please download it to PLC and check operation status.
Special devices for programming
Refer to user's manual for more details.
U02.23.1: Count preset
U02.23.4: Consistent output admission

Uxy.aa.bb
x: Base number
y: Slot number
aa,bb: Refer to user's manual

Special

U02.23.0: Count operation admission

U02.23.5: Output external terminal admission


U02.23.6: OUT0 consistent signal reset
U02.00.6: Contact for checking external output (Practically effective output is outputted
through OUT0 terminal)
U02.02~U02.03: Counter present value

After downloading, monitor operation status.

For monitoring the preset value, follow the example here.

MasterLogic-200
Honeywell's next generation
Programmable Logic Controller

59

Special module / Positioning module [APM]

Features
UHighly reliable position control with ASIC-embedded processor
UEnhanced control with fast control processing speed
UHigh-speed motor control (Max. pulse output: 1Mbps)
UArc/linear interpolation, separate/synchronous operation
UTrapezoidal & S-curve acceleration/deceleration
UEasy and quick control through external input (JOG operation included)
UEncoder input support
UHigh-speed processing of command (4ms)
UEasy to set positioning parameters (Windows)
UMonitoring/Tracking/Simulation
UAvailable to edit operation parameter data in EXCEL
USelf-diagnosis
UReal-time information and solution for each error

Specifications
Specifications

Item

2MLF-PO1A, 2MLF-PD1A
1

Number of axes
Interpolation
Control method

2-axis linear interpolation, 2-axis arc interpolation

2/3-axis linear interpolation, 2-axis arc interpolation

Special

Pulse, MM, inch, degree

Positioning data

Each axis has 400 data range (Operation step number 1~400). It is available to set with software package or programming.

Software package

Available (Connected with RS-232C Port of CPU module)

Data backup

Flash memory (No battery)

Positioning method
Position
address
range

Absolute / relative method

mm

-214748364.8 ~ 214748364.7 (m)

Inch

-21474.83648 ~ 21474.83647

degree

-21474.83648 ~ 21474.83647

pulse

-2147483648 ~ 2147483647

Type
Position
speed
range

2MLF-PO A: Open collector, 2MLF-PD A: Line Driver


mm

0.01 ~ 20000000.00 (mm/min)

Inch

0.001 ~ 2000000.000 (Inch/min)

degree

0.001 ~ 2000000.000 (degree/min)

pulse

2MLF-PO A: 1~200,000 (pulse/sec), 2MLF-PD A: 1~1,000,000 (pulse/sec)

Accel/Decal pattern

Trapezoidal & S-curve acceleration/deceleration

Accel/Decel time

1 ~ 65,535ms

Max. output pulse

2MLF-PO A: 200kpps / 2MLF-PD A: 1Mpps

Max. distance

2MLF-PO A: 2m / 2MLF-PD A: 10m

Max. encoder input

200Kbps

Error display

LED

Operation display

LED

Connection connector

40 Pin connector

Size of cable

AWG #24

Occupied points of I/O


Current consumption (mA)

32 points
2MLF-PO1A: 380

2MLF-PO2A: 390

2MLF-PO3A: 400

2MLF-PD1A: 570

2MLF-PD2A: 660

2MLF-PD3A: 750

0.12

0.13

0.14

Weight (kg)
2MLF-PO O: Open Collector type, : Number of axis
2MLF-PD D: Line Drive type, : Number of axis

60

2MLF-PO3A, 2MLF-PD3A

Position control, speed control, speed/position control, position/speed control

Setting unit

Positioning

2MLF-PO2A, 2MLF-PD2A

Terminal block configuration


Pin layout

Pin number
For

21

41

61

FP+

Pulse output (Differential +)

->

22

42

62

FP-

Pulse output (Differential -)

->

23

43

63

RP+

Pulse sign (Differential +)

->

24

44

64

RP-

Pulse sign (Differential -)

->

25

45

65

OV+ *

High limit

<-

26

46

66

OV- *

Low limit

<-

27

47

67

STOP

External stop signal

<-

28

48

68

DOG

Approximate origin

<-

29

49

69

VTP

Speed/Position switching signal

30

50

70

ECMD

2/3 axes

Start

<-

command

Skip

<-

signal

JOG+ (Forward)

JOG reverse operation

<-

51

71

JOG-

32

52

72

COM

33

53

73

DRVIN *

Drive unit ready signal

<-

34

54

74

DRVIN COM

Drive unit ready signal common

<->

35

55

75

HOME +24V

Zero signal (+24V)

<-

36

56

76

NC

Not used

37

57

77

HOME +5V

Zero signal (+5V)

<-

38

58

78

HOME COM

Zero signal (+24V, +5V) Common

<->

39

59

79

24V

24V Power supply (Not used in case of line drive output)

40

60

80

P COM

External 24V GND (Not used in case of line drive output)

MPG A+

Manual pulse generator/Encoder A+ Input

<-

MPG A-

Manual pulse generator/Encoder A- Input

<-

MPG B+

Manual pulse generator/Encoder B+ Input

<-

MPG B-

Manual pulse generator/Encoder B- Input

<-

NC

Not used

<-

NC

Not used

<-

CON

External simultaneous start

<-

EMG *

Emergency stop

<-

NC

Not used

10

COM

(CON, EMG) Common

NC

Not used

11~20

Condition

<-

External

31

1 axis

C
o
m
m
o
n

APM - Ext. device

Common
(OV+, OV-, STOP, DOG, VTP, ECMD, JOG-)

Special

A
x
i
s

Signal direction

Signal name

<<->

<->

MasterLogic-200
Honeywell's next generation
Programmable Logic Controller

61

Special module / Positioning module [APM]

Connection with MR-J2/J2S-A


2MLF-PD1/2/3A (Line Driver)
Power
3phase 200VAC

Electronic
brake

OFF of Servo ON signal


Cutoff by alarm signal
Within 10m

Detector

2MLF-PD1/2/3A

High limit
Low limit
External stop
Approx. origin
VTP switching

External EMG

External Comm.
Jog reverse

Monitor output
Max. 10mA

Servo ON
Reset
Proportinal control
Torqe limit
Normal limit
Reverse limit

MPG
External
simultaneous start
Emergency stop

2m less

Failure Zero
speed detection
During torque
limit

Special

Analog torque limit


+10V/Max. current
2m less

2MLF-PO1/2/3A (Open Collector)


Power
3phase 200VAC

OFF of Servo ON signal


Cutoff by alarm signal
Within 2m

Electronic
brake

Detector

2MLF-PO1/2/3A

High limit
Low limit
External stop
Approx. origin

Monitor output

VTP switching

External EMG

External Comm.

Servo ON

Jog reverse

Reset

Max. 100mA

Proportinal control
Torqe limit
Normal limit
Reverse limit

MPG
External
simultaneous start
Emergency stop

Failure Zero
speed detection
During torque limit

Analog torque limit


+10V/Max. current
2m less

62

2m less

Connection with FDA-3000 AC Servo driver


2MLF-PO1/2/3A (Open Collector)

Max. 2m
2MLF-PO1/2/3A

High limit
Low limit
External stop
Approx. origin
VTP switching
External Comm.
Jog reverse

MPG

External
simultaneous start
Emergency stop

Special

MasterLogic-200
Honeywell's next generation
Programmable Logic Controller

63

Special module / Positioning module

Connection with FDA-5000 AC Servo driver


2MLF-PO1/2/3A (Open Collector)

Max. 2m
2MLF-PO1/2/3A

High limit
Low limit
External stop
Approx. origin
VTP switching
External Comm.
Jog reverse

MPG

External
simultaneous start
Emergency stop

Special
2MLF-PD1/2/3A (Line Driver)

Max. 10m
2MLF-PD1/2/3A

High limit
Low limit
External stop
Approx. origin
VTP switching
External Comm.
Jog reverse

MPG

External
simultaneous start
Emergency stop

64

Special module / Positioning module (Example)

This is a simple example to control 1-axis servo motor.

System configuration

Positioning system consists of control part, power part, and machinery part.
Control unit: Install APM module on base and complete parameter setting and programming.
Power unit: Power unit generates momentum, and it consists of servo-driver + servo-motor and step-driver + step-motor.
Machinery unit: Machinery unit is to transport objects, and it can be ball screw, timing belt and rack gear.

2MLT-PAFA

2MLT-CPUS

2MLI-A22A

2MLI-D22A

2MLQ-RY2A

2MLQ-TR2A

2MLQ-RY8A

2MLQ-TR8A

2MLQ-RY4A

2MLQ-TR4A

Control unit

Power unit

Machinery unit

System design
Special

APM: Determine type and quantity considering the number of control axis and operation function.
Driver: Select driver with identical output type of APM.
(In case output type of APM is line driver, driver should support a pulse train input type of line driver.)

Motor: Select capacity considering operation characteristics of load.


Mechanical: Design precise mechanical system to minimize error.

Connection to drivers
The following picture is wiring pulse train signal between driver and APM for pulse train signal.
Terminal besides pulse train signal is used additionally according to user-purpose, system characteristics.
For wiring of optional terminal of Servo (Step) driver, refer to users manual.

Line driver

Open collector

MasterLogic-200
Honeywell's next generation
Programmable Logic Controller

65

Special module / Positioning module (Example)

Parameter, data setting and transmission


Set system characteristic, target location, operation speed, and operation type using
APM software package.

Transmit operation parameter and data to APM.

Setting parameter of system characteristic

APM software package


Target location, speed, operation type, operation data

Special

Initial system inspection


Perform a trial-run using APM software package, and check external wiring, operation data setting, and status of
machinery part. It is recommended to do trial-run before programming.

If a program is saved in CPU and operation mode is RUN, a unexpected fault can occur due to disagreement
between operation condition of operation control program and operation result of APM S/W package.

Operate APM without positioning programming

66

Programming
Create a program using dedicated command for APM control.
ex) Origin point return-ORG, Independent operation-IST

Special

Program monitoring
Monitor the output condition following input condition and inspect the operation status of
APM and correct programming error.

MasterLogic-200
Honeywell's next generation
Programmable Logic Controller

67

Special module / Motion control module

Features
Motion control module adopting Mechatrolink-II
Prompt and precise motion control via high-speed network (Mechatrolink-II)
(Transmission speed: 10Mbps, Transmission period: 1ms/1.5ms/2ms)

Enhanced performance of motion synchronization


Perfect synchronization of Max. 16 axes
High-speed synchronous motion control by synchronizing execution period of application with
transmission period of network

Efficient system
Wiring reduction with motion control system via network
Enhanced stability and efficiency of system through absolute-coordinate operation
Multi-function engineering tool - M16M software package
Providing various functions from system design to maintenance
Automatic setting of communication & servo parameter by 'Self Configuration'

Specifications
Item
Control axis

9axes/1 port (M II-1ms)

Control
performance

2MLF-M16M
Motion: 6 axes/1ms, MOV: 16 axes/2ms

Data transmission time

15axes/1 port (M II-1.5ms)


16axes /1 port (M ii-2ms)
15axes/1 port (M II-17byte-1ms)

Max. number of control axis

Special

Max. transmission distance


Count range

capacity

1.0~32.0ms (Unit: 0.5ms)


RAM
FLASH
User memory

Data trace
Program
language

50m
Signed 32 Bit (-2,147,483,648 ~ 2,147,483,647)

Scan time setting


Memory

16axes

32MB (SDRAM)/512kB (SRAM)


8MB (Firm 2MB/User 6MB)
6MB
128kW (32Kw x 4Gr)
No. of program: 256

Motion language

No. of command: about 70


No. of simultaneous execution: 16

Memory backup

FLASH

Engineering port

RS-232C x 1

Self-configuration

System configuration
MECHATROLINK-II
Max. number of station: 16
Transmission period: 1ms/1.5ms/2ms
Features: Simple and easy system
setup using 'Self-Configuration'
S/W: M16M software package

68

Special module / M16M software package

Features
Providing 'Self-Configuration'
Reduced system setting time thanks to automatic recognition of network motion
system and automatic setting of comm. & servo parameter

Providing various screens (6 types of Manager, E-CAM tool)


Supporting dedicated language and ladder language for motion control
Easy programming and maintenance

Programming
Program for data exchange with M16M using motion instruction of Softmaster-200
Programming and editing ladder and motion program using M16M software package

Sharing data memory


between MasterLogic-200
CPU and motion module
(2MLF-M16M)

Special

Motion language
Easy and convenient
programming and editing
using structured Text-type
language.

Drivers & Motors for MECHATROLINK-II


Motor

Option

SGDH

Driver

-II series (Servo motor)

JUSP-NS115

Remarks

-III series

Servo motor

SGDS

Linear series

Linear motor

Direct-drive series

Direct drive motor

Installing option module in servo module

MasterLogic-200
Honeywell's next generation
Programmable Logic Controller

69

Software
SoftMaster-200 software provides integrated PLC engineering
environment all in one window such as programming, configuration
/ setup, debugging, monitoring, trouble-shooting, documentation and
maintenance etc.

Software

SoftMaster
-200
Main programming
software

SoftMaster SoftMaster
-APM
-PD
Network Manager

70

Position Module

Key Features of SoftMaster-200


Integrated PLC engineering environment:
SoftMaster-200 provides the engineer with an integrated PLC engineering environment
all in one window such as ladder programming, configuration / setup of CPU or other
special/communication modules, debugging, monitoring, trouble-shooting, documentation
and maintenance etc.
SoftMaster-200 is Microsoft Windows 2000, XP based software with standard and very
user-friendly GUI features:
Drag and drop
Short-cut keys & toolbar icons
Microsoft Excel-like cell input
Auto-fill, export/import
Unlimited Undo and Redo options
Context sensitive menu enabling/disabling
Customizable views, colors, fonts
Find, Replace

Software

Project Management:
SoftMaster-200 helps managing multiple PLCs through a single window. One project
file (.xgp) can encompass multiple PLCs of the site. Also this file will serve as a central
storage of all details related to each PLC
Scan programs & interrupt programs,
I/O module configuration & special module settings
Communication module settings
Variable names, comments, descriptions
Compare projects to nd out
even minor differences in each
Flash memory / data retention settings
category
Other PLC settings
There is no limit on #PLCs that can be included in one project file.
Project files can be compared automatically as in picture above.
Export / Import entire PLC data into/from a single file (.plc) or selectively on each
category (variable/comments -.cmt, programs -.prg, basic PLC configuration -.bsp, I/O
module settings -.iop etc.
Flexible documentation: Print the entire project documentation at the click of a button
e.g. customizable cover page, header/footer, variable/comments, normal scan programs,
task interrupt programs, basic PLC configuration, I/O module configuration etc for all
PLCs in the project.

MasterLogic-200
Honeywell's next generation
Programmable Logic Controller

71

Online functions:
Connection to PLC: SoftMaster-200 supports 4 methods of connection:
RS232C using RS232C port of computer and built-in RS232C port of CPU
(direct) or Snet module in the PLC.
USB using USB port of computer and the built-in USB port of CPU
Ethernet using Ethernet port of computer and Ethernet port of FEnet module
Modem via RS232C and telephone connections (as in first option).

Two levels of Remote Connection: This facility helps when your computer is not directly
connected to a PLC e.g. but through another PLC which is connected to the programming
computer.

PLC
RS232C/USB
Computer

PLC1A

PLC1B

PLC1C

PLC2A

PLC2B

PLC2C

Remote Level 1: Snet / FEnet / FDEnet

Remote Level 2: Snet / FEnet / FDEnet

Software

The CPU mode RUN/STOP/DEBUG can be switched remotely from the program. In
DEBUG mode, multiple breakpoints can be set in the program and run step by step for
critical trouble-shooting. Breakpoints also can be automatic based on a device condition.
READ / WRITE with the online PLC can be done selectively. For example, if there was
a change done only in specific area e.g. variable names or a program or I/O module
parameter, just that portion can be selectively downloaded to PLC.
Compare with PLC: The project opened in computer can be compared with the project in
online PLC for an automatic report on similarities and differences.
Configuring the use of flash memory whether the program can be backed up to flash
memory after every download or online editing
Online editing of ladder program while it is being executed.

72

Maintenance & Troubleshooting :


Force I/O: The I/O refresh memory can be forced manually to any specific value for
maintenance, trouble-shooting or simulation purposes. Both input and output (bit or word
data) image area can be forced to a value.
Skip I/O: For any maintenance purpose, an entire I/O base including all its slots or any
selective slot (module) can be set for I/O skip through the software. The CPU ignores
that I/O base or the particular slots during its operation.

Force I/O

Module exchange wizard: A software wizard guides the engineer through the steps
involved in exchanging a module safely during CPU run mode. Errors detected, if any
are displayed to the user.
In addition to the wizard, the engineer can also exchange the module (hot-swapping) by
setting the M-XCHG dip switch in CPU to ON.

Skip I/O

User-defined Event Recording (SOE): Any bit data device (digital I/O, memory flags
etc) can be configured for event recording when the device condition turns on (rising) or
off (falling) or any change of state. SoftMaster-200 allows an event list to be configured
and managed with add/edit and delete functions. Each event can be prioritized into three
categories: a) alarm message b) warning message c) information
The events can be recorded at millisecond resolution. The CPU also maintains the event
history in its memory.

Module exchange wizard

This functionality enables the engineer to program the PLC for Sequential Event
Recording (SER) or Sequence of Events (SOE) functionality.
Program verification (logic & syntax errors, duplicate coil checks, cross-references etc)

User-defined event

Monitoring:
Ladder monitor for online status of program execution. Force I/O setting can also be
done from here directly.

Variable Monitoring Related devices (I/O addresses and other data memory) of any
category (e.g. P, M, F, D, R) in any data type (e.g. BIT, WORD, DWORD, REAL) can
be grouped and monitored together in a single window for context sensitive troubleshooting.

Ladder Monitor

Software

System Monitoring This tool empowers the PLC support engineer to connect to
any PLC and monitor the overall system status in a single window i.e. Base, slot and
I/O module configuration, device status of I/O channels etc. Each I/O base can be
individually traversed back and forth for monitoring.

System Monitor

These variables are not restricted to one PLC but can be spread across multiple PLCs.
Variable Monitor

Special Module Monitoring Special modules such as Analog Input/Output modules,


High Speed Counter (HSC) modules are monitored through this tool.
Trend Monitoring Various analog and digital devices (data type such as BIT, WORD,
DWORD, REAL etc) from I/O and other memory devices can be trended together on
a single window for context sensitive trouble-shooting. Sampling speed, X and Y-axis
range (time and data value) also can be adjusted to the needs.

Special Module Monitor

Trace Device data (all I/O and other data memory areas) can be sampled & traced
automatically for a specific duration when some other device condition becomes true.
Trend Monitor
MasterLogic-200
Honeywell's next generation
Programmable Logic Controller

73

PLC Event History:


MasterLogic-200 CPU stores four types of event history for monitoring, diagnostics
and trouble-shooting purposes. The events are details are stored in CPU until they are
reviewed and deleted from SoftMaster-200 software.

Event Type

Condition

Size

Details

Error History

Any error

2048 events max

Timestamp, Error code, description

Mode change history

RUN/STOP

1024 events max

Timestamp, mode etc

Power shutdown history

ON/OFF

1024 events max

Timestamp, power status etc

System history

Key system messages

2048 events max

Timestamp, Error code, description

Easy ladder program navigation & editing:


SoftMaster-200 has numerous ways to assist the engineer in navigation through the
programs.
Variable name and a comment/description for each device address
Find and Replace via variable name, device address, comment
GOTO commands, Bookmarks
Breakpoints in online debug mode
Toolbar icons
Customizable rung length (column size)

Software

System Requirements:
Item

Windows 2000, XP (Limited use in Windows 98, ME)

CPU

IBM compatible PC with Min. 200MHz Pentium processor

Memory
HDD
Serial port

74

System requirement

O/S

Min. 128M
100 MB (Free memory space)
Communication port for program transmission (RS-232C, USB)

Printer

Compatible with Windows 98 or later

Mouse

Compatible with Windows 98 or later

Program download
Connection setting
Check a setting for connection
between MasterLogic-200 and
Softmaster-200
MasterLogic-200 supports USB
and RS-232C
Set up communication port and download
speed
* using 'USB TO RS-232C' converter,
115,200bps connection may be unavailable
depending on characteristics of converter. In
this case, change the communication speed
to 38,400bps.

RS-232C setting

USB connection setting

Data type
Data

Bit Data
Integer Data

Word Data

Real Data

Double-Word Data

32-bit Real

(Fraction, exponent, signbit)

Character Data

64-bit Long Real


Nibble/Byte Data
String, ASCII code
construction

Software

Nibble: 4-bit unit data


Byte: 8-bit unit data

Softmaster-200 programming
Index register Z
Index registers (Z) comes
handy to engineers
for array based access
of various devices
(dynamic addressing) is
required. Index register
dynamically offsets the
device address. The sum
of index register value
and directly specified
device number is real
device

MOV D100[Z1] D10[Z3]


P0020

Z1

Z3

b1
D100

D103

b2
D10

D15

D103

1234

D15

1234

Available Device
Bit Device: P, M, L, K, F, T, C, SD
Word Device: U, D, R, ZR, N, present value of T and present value of C
Ex) MOV T1[Z1] D10 : If Z1 is 5, present value of T(1+5)=T6 is transmitted to D10.
Ex) LOAD D10[Z1].5 : If Z1 is 5, LOAD(10+5).5 => LOAD D15.5 is set.
MasterLogic-200
Honeywell's next generation
Programmable Logic Controller

75

Device Type
Device

Size

32768 points

M
L

Bit Contact

Word Data

Name

P00000 ~ P2047F

P0000 ~ P2047

I/O Relay

32768 points

M00000 ~ M2047F

M0000 ~ M2047

Assistant Relay

180224 points

L00000 ~ L11263F

L0000 ~ L11263

Link Relay

21K words

N/A

N00000 ~ N21503

Comm. data register

32768 points

K00000 ~ K2047F

K0000 ~ K2047

Keep Relay

32768 points

F00000 ~ F2047F

F0000 ~ F2047

Special Relay

2048 points

T0000 ~ T2047

T0000 ~ T2047

Timer

2048 points

C0000 ~ C2047

C0000 ~ C2047

Counter

3072 words

U00.00.0 ~ U7F.31.F

U00.00 ~ U7F.31

Special Module Counter

128 words

N/A

Z0 ~ Z127

Index Register

128 groups

S00.00 ~ S127.99

N/A

Step Control Relay

32K words

D00000.0 ~ D32767.F

D00000 ~ D32767

Data Register

*1)

R (Internal RAM)

32K words

R00000.0 ~ R32767.F

R00000 ~ R32767

File Register

ZR (Internal RAM) *3)

32K words

N/A

ZR00000 ~ ZR65535

File Register

R (Extended)

1M words

N/A

Available as much as extension size

File Register

ZR (Extended)

1M words

N/A

Available as much as extension size

File Register

Note)

*2)

1) When communication module is not used in the PLC, N device addresses can be used as internal data area.
2) When internal RAM is more than 32Kwords, the valid address range for R device is only R00000.0~R32767.F (bit data) and R00000~R32767(word type)
3) When internal RAM is more than 32Kwords, the valid address range for ZR device is ZR00000.0~ZR32767.F (bit data) and R00000~R65535(word type)

Special module register U


Register for reading data from
special modules e.g. analog
input, analog output, HSC
(pulse) input etc.

b15

b0

U00.00
Slot number: 0
U00.31
U01.00

Ex) U93.12.x (x: Bit location, Hexadecimal display)

Slot number: 1

Available to read/write internal memory value of special module

U01.31

without using PUT (P), GET (P), PUTS (P), GETS (P)

Basic display in U area

U7F.00

Software

U7F.31

Assigning 32 words per slot in U area


Bit type display available

Slot number: 127

Ex) Uxy.z
x: Base number (0~7)
y: Slot number (0~F)
z: Word number of special module internal memory

File register R, ZR
RO
Block 0

R: Block unit access


ZR: Entire file register access

Block 1

Internal RAM (non-volatile memory): 32K words


FLASH: 1M words

ZR65535

76

R3276
RO

ZRO

R3276

Program Instructions
This section tabulates
several hundreds of program
instructions supported by
MasterLogic-200. The cover
page explains the symbols &
notations used.

Item

Name

Symbol

Remark

No. of
step

16 Bits
transfer

32 Bits

Item: Instruction classification

Name: Instruction names to be used in program.


Display rules: Instructions shall be basically displayed in word unit. According to data size,
operation characteristics, real number data process, text process, the rules are as follows;

Based on Data Size & Type


D: Double Word related instruction.
R: Real Number related instruction.
L: Long Real Number related instruction.
However, LMOV is 64 Bits transfer instruction.
$: String related instruction.
G: Group calculation.
4: Nibble related instruction, used only at the back of instruction.
8: Byte related instruction, used only at the back of instruction.
3: Instruction that process 3 operands, used only at the back of instruction.

Based on Operation Characteristics


P: Instruction that is executed for 1 scan when input signal is changed OFF => ON
3

Symbol: displays symbols used in program, showing the number of used operands and
the type of Source or Destination. Operand display rules are as follows;
S: Source, with data value not changed after calculated.

Program Instruction

D: Destination, with data value changeable after calculated.


N, n: The number to process.
St, En: Start and End, used only in BSFT & WSFT.
Sb: Source in case Bit position is specified, mostly used in Nibble/Byte instruction.
Db: Destination in case Bit position is specified.
Z: Control word, which means previously specified format as based on each instruction.
4

Remark: any relevant comment.

No. of step: (Program memory) by the instruction consumed

MasterLogic-200
Honeywell's next generation
Programmable Logic Controller

77

Program Instructions

Basic Instruction

Applied instruction

Name

Item

Symbol

D/P

AND

Long Real Number LMOV

LMOV

S D

AND NOT

4 bits

MOV4

MOV4

Sb Db

OR

8 bits

MOV8

MOV8

Sb Db

OR NOT

1's complement

CMOV

CMOV

S D

D/P

16 bits group

GMOV

GMOV

S D N

Multiple

FMOV

FMOV

S D N

BMOV

BMOV

S D N

GBMOV

S D Z N

Data Transfer

S D

LOADP

LOADN

ANDP

Specified bit

ANDN

Specified bit group GBMOV

ORP

String

$MOV

$MOV

S D

ORN

BCD

BCD

BCD

S D

D/P

A B

BIN

BIN

BIN

S D

D/P

Group

GBCD

GBCD

S D N

BCD, BIN

GBIN

GBIN

S D N

16 bits

12R

12L

S D

integer-to-real

12L

D2L

S D

32 bits

D2R

R2D

S D

integer-to-real

D2L

L2D

S D

R2I

R2I

S D

R2D

R2D

S D

L2I

L2I

S D

L2D

L2D

S D

CMP

CMP

S1 S2

D/P
P

A
B

OR LOAD
MPUSH
MLOAD
MPO

1
[ ]

[ ]

[ ]

NOT

MCS

MCS

MCSCLR

MCSCLR

Real-interger
Long Real-interger

OUT

OUT NOT

Unsigned

OUTP

[ p ]

comparison

OUTN

[ N ]

with special flag

SET

[ S ]

4/8 bits

CMP4

CMP4

S1 S2

RST

[ R ]

comparison

CMP8

CMP8

S1 S2

Table comparison

TCMP

TCMP

S1 S2 D

D/P

FF
Step control

No. of step Remark

RMOV

MPOP

Output

S D

RMOV

MLOAD

Master control

MOV

Real Number

MPUSH

Reverse

Symbol

MOV

LOAD LOAD

Combination

Name

1 word

LOAD NOT

Data Conversion

Contact

Item

No. of step Remark


1

LOAD

FF

D
sxx.xx

SES S
OUT S

[ S ]

GEQ

GEQ

S1 S2 D N

sxx.xx

GGT

GGT

S1 S2 D N

END

END

Group

GLT

GLT

S1 S2 D N

No-Process

NOP

No ladder

comparison

GGE

GGE

S1 S2 D N

TON

TON

T t

GLE

GLE

S1 S2 D N

TOFF

TOFF

T t

GNE

GNE

S1 S2 D N

TMR

TMR

T t

TMON

TMON

T t

TRTG

TRTFG

T t

CTD

CTD

C c

CTU

CTU

C c

CTR

CTR

C c
C U D c

Timer

Counter

CTUD

CTUD

LOAD=

S1 S2

LOAD>

>

S1 S2

LOAD<

<

S1 S2

LOAD>=

>=

S1 S2

LOAD<=

<=

S1 S2

LOAD< >

<>

S1 S2

AND=

S1 S2

AND>

>

S1 S2

AND<

<

S1 S2

AND>=

>=

S1 S2

AND<=

<=

S1 S2

AND< >

<>

S1 S2

Note) D: Double word related commands


It is located at the first of command.
Ex) [DMOV D100 D200]

D101
D201

Data Comparison

Program Instrucions

End

D100

16 bits data
comparison
(LOAD)

16 bit data
comparison
(AND)

D200

P: It indicates the commands executed one time when input signal is change from OFF to ON.
It is located at the last of command.
Ex) [DMOVP D100 D200]

16 bit data
comparison
(OR)

78

OR=

S1 S2

OR>

>

S1 S2

OR<

<

S1 S2

OR>=

>=

S1 S2

Applied instruction
Name

32 bits data
comparison
(LOAD)

32 bits data
comparison
(AND)

Data comparison

32 bits data
comparison
(OR)

Real number
comparison
(LOAD)

Real number
comparison
(AND)

Long real
number
comparison
(LOAD)

Long real
number
comparison
(AND)

S1 S2

No. of step Remark


2

Item

Name

Symbol

ORL=

L=

S1 S2

No. of step Remark


2

<>

S1 S2

Long real

ORL>

L>

S1 S2

LOADD=

D=

S1 S2

number

ORL<

L<

S1 S2

LOADD>

D>

S1 S2

comparison

ORL>=

L>=

S1 S2

LOADD<

D<

S1 S2

(OR)

ORL<=

L<=

S1 S2

LOADD>=

D>=

S1 S2

ORL< >

L< >

S1 S2

LOADD<=

D<=

S1 S2

LOAD$=

$=

S1 S2

LOADD< >

D< >

S1 S2

LOAD$>

$>

S1 S2

ANDD=

D=

S1 S2

LOAD$<

$<

S1 S2

ANDD>

D>

S1 S2

LOAD$>=

$>=

S1 S2

ANDD<

D<

S1 S2

LOAD$<=

$<=

S1 S2

ANDD>=

D>=

S1 S2

LOAD$< >

$< >

S1 S2

ANDD<=

D<=

S1 S2

AND$=

$=

S1 S2

ANDD< >

D< >

S1 S2

AND$>

$>

S1 S2

ORD=

D=

S1 S2

AND$<

$<

S1 S2

ORD>

D>

S1 S2

AND$>=

$>=

S1 S2

ORD<

D<

S1 S2

AND$<=

$<=

S1 S2

ORD>=

D>=

S1 S2

AND$< >

$< >

S1 S2

ORD<=

D<=

S1 S2

OR$=

G=

S1 S2

ORD< >

D< >

S1 S2

OR$>

G>

S1 S2

OR$<

G<

S1 S2

OR$>=

G>=

S1 S2

OR$<=

G<=

S1 S2

OR$< >

G< >

S1 S2

LOADR=

R=

S1 S2

LOADR>

R>

S1 S2

LOADR<

R<

S1 S2

LOADR>=

R>=

S1 S2

LOADR<=

R<=

S1 S2

LOADR< >

R< >

S1 S2

String
comparison
(LOAD)

String
comparison
(AND)

String
comparison
(OR)

LOADG=

G=

S1 S2 N

16 bits

LOADG>

G>

S1 S2 N

data group

LOADG<

G<

S1 S2 N

comparison

LOADG>=

G>=

S1 S2 N

(LOAD)

LOADG<=

G<=

S1 S2 N

ANDR=

R=

S1 S2

ANDR>

R>

S1 S2

ANDR<

R<

S1 S2

ANDR>=

R>=

S1 S2

LOADG< >

G< >

S1 S2 N

ANDR<=

R<=

S1 S2

ANDG=

G=

S1 S2 N

ANDR< >

R< >

S1 S2

16 bits

ANDG>

G>

S1 S2 N

ORR=

R=

S1 S2

data group

ANDG<

G<

S1 S2 N

ORR>

R>

S1 S2

comparison

ANDG>=

G>=

S1 S2 N

ORR<

R<

S1 S2

(AND)

ANDG<=

G<=

S1 S2 N

ORR>=

R>=

S1 S2

ANDG< >

G< >

S1 S2 N

ORR<=

R<=

S1 S2

ORG=

3=

S1 S2 N

ORR< >

R< >

S1 S2

16 bits

ORG>

3>

S1 S2 N

LOADL=

L=

S1 S2

data group

ORG<

3<

S1 S2 N

LOADL>

L>

S1 S2

comparison

ORG>=

3>=

S1 S2 N

(OR)

ORG<=

3<=

S1 S2 N

ORG< >

3< >

S1 S2 N

LOAD3=

3=

S1 S2 S3

Three 16 bits

LOAD3>

3>

S1 S2 S3

data group

LOAD3<

3<

S1 S2 S3

comparison

LOAD3>=

3>=

S1 S2 S3

(LOAD)

LOAD3<=

3<=

S1 S2 S3

LOAD3<>

3< >

S1 S2 S3

AND3=

3=

S1 S2 S3

AND3>

3>

S1 S2 S3

LOADL<

L<

S1 S2

LOADL>=

L>=

LOADL<=

L<=

S1 S2

LOADL< >

L< >

S1 S2

ANDL=

L=

S1 S2

ANDL>

L>

S1 S2

ANDL<

L<

S1 S2

ANDL>=

L>=

S1 S2

ANDL<=

L<=

S1 S2

ANDL< >

L< >

S1 S2

S1 S2

Three 16 bits
data group
comparison
(AND)

Program Instrucions

Real number
comparison
(OR)

Symbol
<=

Data comparison

Item

OR<=
16 bits data
comparison (OR) OR< >

MasterLogic-200
Honeywell's next generation
Programmable Logic Controller

79

Program Instructions

Applied instruction

Data increase/decrease

Program Instrucions

Location

S1 S2 S3

AND3<=

3<=

S1 S2 S3

AND3< >

3< >

S1 S2 S3

OR3=

3=

S1 S2 S3

OR3>

3>

S1 S2 S3

OR3<

3<

S1 S2 S3

OR3>=

3>=

S1 S2 S3

OR3<=

3<=

S1 S2 S3

OR3< >

3< >

S1 S2 S3

LOADD3=

D3=

S1 S2 S3

LOADD3>

D3>

S1 S2 S3

LOADD3<

D3<

S1 S2 S3

S1 S2 S3

3<=

S1 S2 S3

LOADD3< >

3< >

S1 S2 S3

ANDD3=

D3=

S1 S2 S3

ANDD3>

D3>

S1 S2 S3

ANDD3<

D3<

S1 S2 S3

ANDD3>=

3>=

S1 S2 S3

ANDD3<=

3<=

S1 S2 S3

ANDD3< >

3< >

S1 S2 S3

ORD3=

D3=

S1 S2 S3

ORD3>

D3>

S1 S2 S3

ORD3<

D3<

S1 S2 S3

ORD3>=

D3>=

S1 S2 S3

ORD3<=

D3<=

S1 S2 S3

ORD3< >

D3< >

S1 S2 S3

INC

INC

D/P

DEC

DEC

D/P

INC4

INC4

Db

INC8

INC8

Db

DEC4

DEC4

Db

DEC8

DEC8

Db

Data increase/
decrease
(Unsigned)
Left rotation

INCU

INCU

D/P

DECU

DECU

D/P

ROL

ROL

D n

D/P

4/8 bits left

ROL4

ROL4

Db n

rotation

ROL8

ROL8

Db n

Right rotation

ROR

ROR

D n

D/P

4/8 bits right

ROR4

ROR4

Db n

rotation

ROR8

ROR8

Db n

4/8 bits data


increase/
decrease
(Signed)

Left rotation
(Including carry)
4/8 bits left
rotation
(Including carry)
Right rotation
(Including carry)
4/8 bits right
rotation
(Including carry)
Bit shift

RCL
RCL4

RCL
RCL4

D n
Db n

2
3

Integer calculation

3>=

Data increase/
decrease
(signed)

Item

Shift

3>=

LOADD3<=

Three 32 bits
data group
comparison
(OR)

Shift

AND3>=

LOADD3>=

Three 32 bits
data group
comparison
(AND)

80

Exchange

Three 32 bits
data group
comparison
(LOAD)

No. of step Remark

S1 S2 S3

P
P

RCL8

RCL8

Db n

RCR

RCR

D n

RCR4

RCR4

Db n

RCR8

RCR8

Db n

BSFT

BSFT

St Ed

Group calculation String Real number calculation

Data comparison

Three 16 bits
data group
comparison
(OR)

Symbol
3<

BCD calculation

Three 16 bits
data group
comparison
(AND)

Name
AND3<

Logical calculation

Item

Name

Bit shift to left


4 Bits shift to left
8 Bits shift to left
Bit shift to right
4 Bit shift to right
8 Bit shift to right
Word shift
Word shift to left
Word shift to right
Bit movement
Data exchange
Group data exchange
Byte swap
Group byte swap
Integer
addition(signed)
Integer
substraction(signed)
Integer
multiplication(signed)
Integer
division(signed)
Integer
addition(unsigned)
Integer substraction
(unsigned)
Integer multiplication
(unsigned)
Integer division
(unsigned)
Real number
addition
Real number
substraction
Real number
multilplcation
Real number
division

BSFL
BSFL4
BSFL8
BSFR
BSFR4
BSFR8
WSFT
WSFL
WSFR
SR
XCHG
GXCHG
SWAP
GSWAP

String addition
Group addition

Group substraction

Symbol
BSFL

D n

BSFL4

Db n

BSFL8

Db n

No. of step Remark

D N

2
3
3
2
3
3
2
3
3
2
2
4
2
2

ADD

ADD

S1 S2 D

SUB

SUB

S1 S2 D

D/P

MUL

MUL

S1 S2 D

D/P

DIV

DIV

S1 S2 D

D/P

ADDU

ADDU

S1 S2 D

D/P

SUBU

SUBU

S1 S2 D

D/P

MULU

MULU

S1 S2 D

D/P

DIVU

DIVU

S1 S2 D

D/P

RADD
LADD
RSUB
LSUB
RMUL
LMUL
RDIV
LDIV

RADD

S1 S2 D

LADD

S1 S2 D

RSUB

S1 S2 D

LSUB

S1 S2 D

RMUL

S1 S2 D

LMUL

S1 S2 D

RDIV

S1 S2 D

LDIV

S1 S2 D

4
4
4
4
4
4
4
4

P
P
P
P
P
P
P
P

$ADD

$ADD

S1 S2 D

GADD

S1 S2 D N

GSUB

S1 S2 D N

GADD

GSUB

BSFR

D n

BSFR4

Db n

BSFR8

Db n

WSFT

Et Ed

WSFL

D1 D2 N

WSFR

D1 D2 N

SR

Db I D N

XCHG

D1 D2

GXCHG

D1 D2 N

SWAP
GXCHG

D/P
P
P
P

BCD addition

ADDB

ADDB

S1 S2 D

D/P

BCD substraction

SUBB

SUBB

S1 S2 D

D/P

BCD multiplication

MULB

MULB

S1 S2 D

D/P

BCD division

DIVB

DIVB

S1 S2 D

D/P

Logical AND
Logical OR
Exclusive OR
Exclusive AND

WAND
WOR
WXOR
WXNR

WAND

S1 S2 D

WOR

S1 S2 D

WXOR

S1 S2 D

WXNR

S1 S2 D

4
4
4
4

D/P
D/P
D/P
D/P

GWAND

GWAND

S1 S2 D N

GWOR

GWOR

S1 S2 D N

GWXOR

GWXOR

S1 S2 D N

Group logical
calculation

Applied instruction

Display

Data processing

ESTOP

TFLK

D1 S1 S2 D2

Fault indication

FALS

FALS

Scan clock

DUTY

DUTY

WDT initialization

WDT

WDT

Output control

OUTOFF

OUTOFF

Operation stop

STOP

STOP

I/O refresh

IORF

Bit check

BSUM

Encoding

ENCO

Decoding
Data disconnection
Data union

n
D n1 n2

2
4
P

S D n

S D

D/P

ENCO

S D n

DECO

DECO

S D n

DIS

DIS

S D n

UNI

UNI

S D n

Data search

SCH

SCH

S1 S2 D N

D/P

Max. value search

MAX

MAX

S D n

D/P

Min. value search

MIN

MIN

S D n

D/P

Sum

SUM

SUM

S D n

D/P

Average

AVE

AVE

S D n

D/P

MUX

MUX

MUX

S1 S2 D N

D/P

Data detection

DETECT

DETECT

S1 S2 D N

Ramp signal output

RAMP

RAMP

n1 n2 D1 n3 D2

Data sorting

SORT

SORT

s n1 n2 D1 D2

Data writing

FIWR

FIWR

S D

First-input, first-read

BSUM

FIFRD

FIFRD

S D

First-input, later-read FILRD

FILRD

S D

Data inserting

FIINS

FIINS

S D n

Data pulling

FIDEL

FIDEL

S D n

Word/ Byte

WTOB

WTOB

S D n

conversion

BTOW

BTOW

S D n

7 segment display

SEG

SEG

S D Z

Message display

MSG

MSG

S D Z

Conversion to
decimal ASCII code

BINDA

BINDA

S D

2/3

D/P

BINHA

BINHA

S D

2/3

D/P

Conversion to
hexadecimal ASCII

String length

ESTOP

IORF

Item

No. of step Remark

S1 S2 D N

String processing

System

Emergency stop

Symbol
GWXNR

Special function

Name

Data control

Item

Group logical calculation GWXNR


Time clock
TFLK

ASCII conversion
Decimal ASCII-to-

BCDDA

S D

2/3

D/P

DABIN

DABIN

S D

2/3

D/P

Hexadecimal
ASCII-to-BIN

HABIN

HABIN

S D

2/3

D/P

DABCD

DABCD

S D

2/3

D/P

Decimal ASCII-toBCD conversion


BIN 16/32-to-String
conversion
String-to-BIN
16/32 conversion
Real-to-String
conversion
Long real-to-String
conversion
String-to-Real
conversion

STR

STR

S1 S2 D

D/P

VAL

VAL

S D1 D2

D/P

RSTR

RSTR

S1 S2 D

LSTR

LSTR

S1 S2 D

STRR

STRR

S D

Branch

conversion

Interrupt Error Carry LOOP

String processing

BIN conversion

BCDDA

Symbol

No. of step Remark

S D cw

2
2/3
4

P
P
P

S D N

RIGHT

S D N

LEFT

LEFT

S D N

MID

MID

S1 S2 D

REPLACE

REPLACE S1 D S2

FIND

FIND

S1 S2 D N

RBCD

RBCD

S1 S2 D

LBCD

LBCD

S1 S2 D

BCDR

BCDR

S1 S2 D

BCDL

BCDL

S1 S2 D

CMTRD
LEN
SIN
COS
TAN
ASIN*
ACOS*
ATAN*
RAD
DEG
SQRT

CMTRD

S D

LEN

S D

SIN
COS

S D
S D

TAN

S D

ASIN
ACOS
ATAN

S D
S D
S D

RAD

S D

DEG
SQRT

S D
S D

2
2
2
2
2
2
2
2
2
2
2

P
D/P
P
P
P
P
P
P
P
P
P

S D

STRL
LEN

S D
S D

ASC

HEX

HEX

RIGHT

EXP*

EXP

EXPT*

EXPT

LOG*

LOG

S D

LN*

LN

S D

Limit control

LIMIT

LIMIT

S1 S2 S3 D

Band control

BAND

BAND

S1 S2 S3 D

D/P

Zone control

ZONE

ZONE

S1 S2 S3 D

D/P

DATERD

DATERD

D/P

DATEWR

DATEWR

ADDCLK

ADDCLK

S1 S2 D

SUBCLK

SUBCLK

S1 S2 D

SECOND
HOUR
JMP

S D
S D
LABEL

BREAK
STC
CLC

2
2
1
5
1
1
1
2
1
1
1
1

P
P
P

Carry flag set


Carry flag reset

SECOND
HOUR
JMP
LABEL
CALL
SBRT
RET
FOR
NEXT
BREAK
STC
CLC

Error flag clear

CLE

CLE

Interrupt setting
for all channels
Interrupt setting
for each channel

EI
DI
EIN
DIN

EI
DI
EIN
DIN

1
1
2
2

Date/Time data
read
Date/Time data
write
Time data addition
Time data
substraction
Time data format
conversion
Branching
instruction
Subroutine call
function
Loop instruction

LABEL
CALL
SBRT

S1 S2 D

()
LABEL
LABEL
RET
FOR
NEXT

N
N

MasterLogic-200
Honeywell's next generation
Programmable Logic Controller

81

Program Instrucions

BCD-to-Decimal

RTC

code

ASCII conversion
Hexadecimal
conversion
String extraction
from right
String extraction
from left
String random
extraction
String random
replacement
String search
Real-to-BCD
conversion
Long real-to-BCD
conversion
BCD-to-Real
conversion
BCD-to-Long real
conversion
Read comment
String length
SIN
COS
TAN
SIN-1
COS-1
TAN-1
RAD conversion
Degree conversion
Square root
Natural
exponential
Exponential
Common
Logarithm
Natural Logarithm

Name
STRL
LEN
ASC

Program Instructions

Applied instruction

Sign inversion

Item

Name

No. of step Remark


2
D/P

Symbol

2s complement

NEG

NEG

Real number data

RNEG

RNEG

sign inversion

LNEG

LNEG

Absolute value
inversion
Block change
Transmission of
flash word data

File related

Special module control instruction

ABS

ABS

D/P

RSET

RSET

EMOV

EMOV

S1 S2 D

Transmission of
flash double

EDMOV

EDMOV

S1 S2 D

Block reading

EBREAD

Block writing

EBWRITE

Block comparison EBCMP

PUT

sl S1 S2 N

P2P writing

P2PWR

P2PWR

N1 N2 N3 $

Return to origin point

ORG

ORG

sl ax

sl ax

Fixed origin point setting FLT

Name

DST

Indirect start

IST

IST

sl ax n

Linear interpolation

LIN

LIN

sl ax n1 n2

Circular arc interpolation CIN

CIN

sl ax n1 n2

SST

SST

sl ax n1 n2 n3 n4

VTP

VTP

sl ax

PTV

PTV

sl ax

sl ax

Simultaneous start

Position-to-speed

transformation

sl ax n1 n2 n3 n4 n5

SKP

SKP

Position synchronization SSP

SSP

sl ax n1 n2 n3

Speed synchronization

SSS

SSS

sl ax n1 n2 n3

Position override

VTP

VTP

sl ax n

Speed Override

SOR

SOR

sl ax n

PSO

PSO

sl ax n

Skip operation

No. of step Remark

DST

Symbol

FLT

Direct start

EBWRITE S1 S2 D

PID control instruction

Built-in PID

PUT

transformation

S1 S2 D1 D2

No. of step Remark

Internal memory writing

EBCMP

Symbol
sl S D N

S1 S2 D

EBREAD

Name
GET

Speed-to-position

word data

Item

Item

Internal memory reading GET

Position specified speed

Run

PIDRUN

PIDRUN

override

Pause

PIDPAUSE

PIDPAUSE

Continuous operation

NMV

NMV

sl ax n

Inching

INC

INCH

sl ax n

RTP

RTP

sl ax

SNS

SNS

sl ax n

SRS

SRS

sl ax n

Parameter change PIDPRMT


Stop

PIDSTOP

PIDPRMT

S N

PIDSTOP

Return to previous
position of manual
operation
Start-step no. change
Repeated step
no. change

MOF

MOF

sl ax

Present position change PRS

PRS

sl ax n

Zone enable

ZOE

ZOE

sl ax

Zone disable

ZOD

ZOD

sl ax

Encoder preset

EPRS

EPRS

sl ax n

Teaching

TEA

TEA

sl ax n1 n2 n3 n4

Teaching array

TEAA

TEAA

sl ax n1 n2 n3 n4

Emergency stop

EMG

EMG

sl ax

Error reset

CLR

CLR

sl ax n

Error history reset

ECLR

ECLR

sl ax

Point operation

PST

PST

sl ax n

Basic parameter setting

TBP

TBP

sl ax n1 n2

TEP

TEP

sl ax n1 n2

THP

THP

sl ax n1 n2

TMP

TMP

sl ax n1 n2

TSP

TSP

sl ax n

TCP

TCP

sl ax n1 n2

Decelerated stop

STP

STP

sl ax n

Parameter/data saving

WRT

WRT

sl ax n

TWR

TWR

sl ax n1 n2

PWR

PWR

sl ax n1 n2

SRD

SRD

sl ax n

M code Off

Program Instrucions

Extension parameter
setting
Return to origin
parameter setting
Manual operation
parameter setting
Input signal parameter
setting
Common parameter
setting

Multi teaching data


saving
Point operation step
saving
Present status reading

82

SoftMaster-PD [Network setup & diagnostics]

Features
Manages all communication modules (FEnet, FDEnet, Snet, Rnet, Pnet,
Dnet )

Easy setup of network configuration and associated communication


parameters (IP address, serial port etc)

Configuration of HSL (high speed link) service (send data, receive data,
packet size etc)

Configuration of P2P (point to point) service (channel, block settings etc)


Extended monitoring and diagnostics of network & communication modules
Fast interface with CPU by efficient network management
Unification of instruction system
Simple and easy connection using MLDP (MasterLogic dedicated protocol)
and other driver (MODBUS)

Various built-in Diagnosis functions (Link, Auto-Scan, Frame, etc.)


Item

FAST ETHERNET

COMPUTERLINK
Snet

High-Speed
link

Max. 64 stations
(Max. transmission
block=64x200 words)

N/A

Dedicated ETHERNET

Max. 64 stations
(Max. transmission
block=64x200 words)

Softmaster-200

1,2-stage connection

1,2-stage connection

1,2-stage connection

Dedicated
service
P2P service

MasterLogic-200
MODBUS

MasterLogic-200
MODBUS

Self-diagnosis

Error-check

Error-check

Error-check

Configuration
tool

SoftMaster-PD

SoftMaster-PD

Media

10/100BASE-TX
100BASE-FX
IEEE 802.3

900-115.2Kbps
RS-232T2
RS-232T1+RS

RNET

60 words per block

1 stage connection

DNET

PNET

Max. 64 stations
Supports POLL, COS,
CYCLIC, STROBE

Max. 128 stations


Token Passing & Poll
High-speed flag

1,2-stage connection

1,2-stage connection

Error-check

Error-check

Error-check

SoftMaster-PD

SoftMaster-PD

SoftMaster-PD/SyCon

SoftMaster-PD/SyCon

10/100BASE-TX
100BASE-FX
Toke Bus & CSMA/CD
mixed type

1Mbps

125/250/500Kbps
CSMA/NBA
Trunk/Drop line
Power signal line in

9.6k~12Mbps
RS-485 (Electric)

Max. 64 parameters
expendable

Software

MasterLogic-200
Honeywell's next generation
Programmable Logic Controller

83

SoftMaster-PD [Network setup & diagnostics]

Various network diagnosis and monitoring


Auto Scan: Searching and displaying each node connected to network
Link Monitor: Monitoring status of high-speed link communication of each station
Frame Monitor: Collecting and displaying sending/receiving frame in real time

Item
Auto Scan
Link Monitor
Frame Monitor

FEnet

FDEnet

Fast Ethernet

Dedicated Ethernet

Snet

Pnet

Dnet

Network Auto Scan

Ping

Fast Ethernet

Software

Snet
Pnet

Link

84

Loop Back

Frame

SoftMaster-APM [Positioning module] Software

Features
Windows-based easy operation
Supporting all types of MasterLogic-200 APM module
Improved parameter editing (Copy, Paste, Initialization, etc.)
Various monitoring (Operation type of each axis, etc.)
Profile trace and operation monitoring
Profile graph and simulation of circular arc interpolation
Available to edit operation parameter in EXCEL

Operation Data
Define operation method, target location, operation speed of each axis.

Monitoring (On-line)
Checking basic operation characteristics about each axis and monitoring
operation condition.

Software

Profile Trace (On-line)


Monitoring operation speed of each axis with graph type and saving result
as image file.

Profile simulation (Off-line)


Monitoring operation speed of each axis with graph type and saving result
as image file.

Operation parameter
Setting basic operation characteristics and limit value.

Circular arc interpolation simulation (Off-line)

MasterLogic-200
Honeywell's next generation
Programmable Logic Controller

85

Product list

Special Module

Basic Module
CPU

Power
Supply
(50/60Hz)

Main Base

Expansion Base

Input

Output

AD
conversion

2MLF-AV8A

V input, 8 ch, DC +1~5V, 0~+5V, 0~+10V, -10~+10V

2MLF-AC8A

I input, 8 ch, DC 4~20mA, 0-20mA

DA
conversion

2MLF-DV4A

V output, 4 ch, DC +1~+5V, 0~+5V, 0~+10V, -10~+10V

2MLF-DC4A

I output, 4 ch, DC 4~20mA, 0-20mA

High-speed
counter

2MLF-HO2A

Pulse (OC) input, 2 channels

2MLF-HD2A

Pulse (LD) input, 2 channels

2MLF-PO3A

Pulse (OC) output, 3 axes

6 slots

2MLF-PO2A

Pulse (OC) output, 2 axes

2MLB-M08A

8 slots

2MLF-PO1A

Pulse (OC) output, 1 axis

2MLB-M12A

12 slots

2MLF-PD3A

Pulse (LD) output, 3 axes

2MLB-E04A

4 slots

2MLF-PD2A

Pulse (LD) output, 2 axes

2MLB-E06A

6 slots

2MLF-PD1A

Pulse (LD) output, 1 axis

2MLB-E08A

8 slots

2MLB-E12A

12 slots

2MLI-A12A

16 points AC 110V Input

2MLI-A21A

8 points AC 220V Input

2MLI-D21A

8 points DC24V Input (Sink/Source type)

2MLI-D22A

16 points DC24V Input (Sink/Source type)

2MLI-D22B

16 points DC24V Input (Source type)

2MLI-D24A

32 points DC24V (Sink/Source type)

2MLI-D24B

32 points DC24V (Source type)

2MLI-D28A

64 points DC24V (Sink/Source type)

2MLI-D28B

64 points DC24V (Source type)

2MLQ-RY1A

8 points Relay Output, 2A, 1 Point/Com

2MLQ-RY2A

16 points Relay Output, 2A

2MLQ-RY2B

16 points Relay Output, 2A, BuiVaristor, CR absorber

2MLQ-SS2A

16 points Triac Output,1A

2MLQ-TR2A

16 points TR Output, 0.5A, (Sink Type)

2MLQ-TR2B

16 points TR Output, 0.5A, (Source Type)

2MLQ-TR4A

32 points TR Output, 0.1A (Sink Type)

2MLQ-TR4B

32 points TR Output, 0.1A (Source Type)

2MLQ-TR8A

64 points TR Output, 0.1A (Sink Type)

2MLQ-TR8B

64 points TR Output, 0.1A (Source Type)

2MLK-CPUH Max. I/O 6,144 points, P/G capacity : 64Kstep,28ns/step


2MLK-CPUS

Max. I/O 3,072 points, P/G capacity : 32Kstep, 84ns/step

2MLP-ACF1

Flexi Voltage Input: 100V,220V AC Output DC5V 3A, DC24V 0.6A

2MLP-ACF2

Flexi Voltage Input: 100V/220V AC Output Voltage / DC5V 6A

2MLP-AC23

AC Power Input: 220V AC Output DC5V, 8.A

2MLP-DC42

DC Powert Input 24VDC Output: DC5V, 6A

2MLB-M04A

4 slots

2MLB-M06A

Product

Communication Module
Snet

2MLL-CH2A

RS-232C, RS-422 (1 ch Each)

2MLL-C22A

RS-232C, 2ch

2MLL-C42A

RS-422, 2ch

FEnet (Fast Ethernet) 2MLL-EFMF


(SCADA Integration) 2MLL-EFMT
FDEnet (Dedicated 2MLL-EDMF
Ethernet)
2MLL-EDMT
Peer to peer
Rnet
2MLL-RMEA
Dnet
Pnet
DUMMY

86

Master, 100/100Mbps, SC Type (Fiber Optics)


Master, 100/100Mbps, RJ-45, CATS (Electric)
Master, 100/100Mbps, SC Type (Fiber Optics)
Master, 100/100Mbps, RJ-45, CATS (Electric)
Rnet, Master, 1Mbps, RJ-45 (Honeywell Proprietary)

2MLL-DMEA DeviceNet, Master, 500Kbps, ODVA standard


2MLL-PMEA Profibus, Master, 12Mbps, DP standard
2MLT-DMMA DUMMY Module

Positioning

Others
Item

Expansion
Cable

Type name

Content

2MLC-E041

Length: 0.4m

2MLC-E061

Length: 0.6m

2MLC-E121

Length: 1.2m

2MLC-E301

Length: 3.0m

2MLC-E501

Length: 5.0m

2MLC-E102

Length: 10m

2MLC-E152

Length: 15m

Cable Terminator 2MLT-TERA

Extension cable Terminating Resistor

USB Cable

USB-301A

USB Program download cable

RS232C

KIC-050A

RS232C Program download cable

Programming Tool SoftMaster-200

Software Package, Windows 2000, XP

Dimensions

Dimensions
Base

Power module

CPU and I/O module

Base Dimensions (W)


Item

2MLB-M04A/E04A

2MLB-M06A/E06A

2MLB-M08A/E08A

2MLB-M12A/E12A

190

244

298

406

210

264

318

426

Product

MasterLogic-200
Honeywell's next generation
Programmable Logic Controller

87

Australia

Japan

Singapore

Honeywell Ltd.

Honeywell Inc.

Honeywell Pte Ltd.

Phone: (61) 2-9353-4500

Phone: (81) 3-5440-1395

Phone: (65) 6355-2828

Fax: (61) 2-9353-7677

Fax: (81) 3-5440-1368

Fax: (65) 6445-3033

China

South Korea

Thailand

Honeywell (Tianjin) Ltd. - Beijing

Honeywell Co., Ltd.

Honeywell Systems Ltd.

Phone: (86-10) 8458-3290

Phone: (82) 2-799-6114

Phone: (662) 693-3099

Fax: (86-10) 8458-3102

Fax: (82) 2-792-9015

Fax: (662) 693-3085

Honeywell (Tianjin) Ltd. - Shanghai

Malaysia

Taiwan

Phone: (86-21) 6237-0237

Honeywell Engineering Sdn Bhd.

Honeywell Taiwan Ltd.

Fax: (86-21) 6237-3102

Phone: (603) 7958-4988

Phone: (886) 2-2245-1000

Fax: (603) 7958-8922

Fax: (886) 2-2245-3241

Indonesia

New Zealand

For Countries (SE Asia) Listed below,

PT Honeywell Indonesia

Honeywell Ltd.

call Honeywell Singapore Ofce

Phone: (62) 21-535-8833

Phone: (64-9) 623-5050

Pakistan, Cambodia, Laos, Mynmar, Vietnam and East Timor

Fax: (62) 21-5367-1008

Fax: (64-9) 623-5060