1. IEEE 1547, Standard for interconnecting Distributed Resources


with Electric Power Systems

Other references:
UK: Electricity Standard G83/1, for embedded generators up to 16
Amps per phase

2. Switzerland: STI 219.0201d, Parallelbetrieb von EEA mit dem


Niederspannungsnetz

UK: Electricity Standard G59/1/NI: for embedded generators less


than 5 MW and 20 kV

3. Austria: Paralllelbetrieb von Erzeugungsanlagen mit


Verteilernetzen

Canada: Various work ongoing


4. Sri Lanka: CEB Guide for Grid Interconnection of Embedded
Generators, December 2000

Ireland: Grid Code Connection Conditions (CC), CER/0104/01, 2001


Australia: AS 4509.1-1999, .2-2002, .3-1999, Stand-alone power
systems
1

Grid Interconnection

Grid Interconnection

IEEE standard

IEEE standard

27 pages
The actual technical part
covers only 10 pages

Terminology: Distributed Resource, Point of


Common Coupling

Micro-grid aspect is implicitely covered (Area


EPS) but not suitable for Nepali needs: The DR
shall not energize the Area EPS when the Area
EPS is de-energized.

Specified for 60 Hz

Grid Interconnection

Grid Interconnection

Switzerland

20 pages

Local grid is covered but only


as local 400V loads

Typical connection diagrams


are useful for showing area of
application. Applicable to 400V
only.

Swiss rules

1. Synchronous
generator without
isolated operation
(400 V)

Grid Interconnection

Grid Interconnection

Swiss rules

Swiss rules

2. Asynchronous
generator
(without isolated
operation)

3. Synchronous
generator
with isolated
operation

400V connection

400V

Grid Interconnection

Grid Interconnection

Swiss rules: Protection and tolerances

Setting of voltage relay:


Setting of frequency relay:

Austrian rules

UN +/- 10%
fN +/- 1%

31 pages

Frequency relay is optional if a vector shift relay is provided.

Slightly more global approach than


Swiss guideline

Synchronizing conditions: At least


UN +/- 10%
fN +/- 0.5 Hz
+/- 10
Cos Phi shall be between 0.9 capacitive and 0.8 inductive (exact
value may be fixed by the utility)

Defines system services:


- Power factor correction
- Voltage stabilization
- Frequency control

Remote command signals must not be disturbed (provide filters)

No detailed rules for protection;


these have to be fixed individually

Utility staff must permanently have access to an isolator switch


9

Grid Interconnection

10

Grid Interconnection

How the standards compare

The Nepali Model

Area of application

Remarks

Unique requirements not compatible with Western environment!

IEEE

<10MVA

Focusses on MW-size
Isolated start-up is
prohibited

There is the opportunity to let embedded generators contribute to


several major goals:

Switzerland

All kinds of plants but LV


only

Australia

Basically focussed on
inverter-based solar PV
Small systems = 10 kW

Rural income generation, community-based projects


Cost reduction of national grid extension
Increase of national grid stability

Not relevant for Nepali


micro-hydro context
Designed for use by
approx. 15 power retail
companies
Often identical sell&buy
rates
11

12

Grid Interconnection

Grid Interconnection

The Nepali Model

The Nepali Model

The Nepali model is based on a long-term vision: The Dynamic Power Grid

The Dynamic Power Grid: Flexible topology and free flow of


energy. An information network is used to manage the power
network. Substations are generally equipped with synchrocheck
reclosers
Island

Island

Reduced network load

13

Grid Interconnection

14

Grid Interconnection

The Nepali Model

The Nepali Model

Islands can participate in the grid or not; innovative technical


solutions are to be developed.

Islands can participate in the grid or not; innovative technical


solutions are to be developed.

- New versatile distribution system designs for instance, overlapping


national grid with island grid for more flexibility

- New versatile distribution system designs for instance, overlapping


national grid with island grid for more flexibility

- Communication technology or other intelligent ways to exchange


grid information

- Communication technology or other intelligent ways to exchange


grid information

15

16

You might also like