You are on page 1of 4

Annex-1

Project Lift Pump Along With Associated Accessories And Pipework For Installation In Waste Water Collection Catch Pits
Title
Design Calculation for Oil Skimmer Capacity for Tuiladungri catch pit
Date
20/02/2012
Rev
00
300
Maximum Inlet flow of waste water(m3/hr)
Minimum inlet flow of waste water (m3/hr)
150
300
Maximum amount of heavy oil and grease to be skimmed for designed inflow (mg/L)
300000
Maximum amount of heavy oil and grease to be skimmed for designed inflow (mg/m3))
Maximum mass flow rate for oil and grease to be skimmed at minimum waste water flow (mg/hr)
45000000
45
Maximum mass flow rate for oil and grease to be skimmed at minimum waste water flow (Kg/hr)
Maximum mass flow rate for oil and grease to be skimmed at maximum waste water flow (mg/hr)
90000000
90
Maximum mass flow rate for oil and grease to be skimmed at maximum waste water flow (Kg/hr)
Density of oil and grease (Kg/lit)
0.88
102.2727272727
Capacity for oil skimmer for maximum waste water flow(L/hr)
Therefore Capacity for oil skimmer for maximum waste water flow(L/hr)
110
51.1363636364
Capacity for oil skimmer for minimum waste water flow(L/hr)
Therefore Capacity for oil skimmer for minimum waste water flow(L/hr)
50
50
to 110
Hence, Capacity of Oil Skimmer to be installed(lph)

Annex-1
Project Lift Pump Along With Associated Accessories And Pipework For Installation In Waste Water Collection Catch Pits
Title
Design Calculation for Oil Skimmer Capacity for Gharabasa catch pit
Date
20/02/2012
Rev
00
400
Maximum Inlet flow of waste water(m3/hr)
Minimum inlet flow of waste water (m3/hr)
300
300
Maximum amount of heavy oil and grease to be skimmed for designed inflow (mg/L)
300000
Maximum amount of heavy oil and grease to be skimmed for designed inflow (mg/m3))
Maximum mass flow rate for oil and grease to be skimmed at minimum waste water flow (mg/hr)
90000000
90
Maximum mass flow rate for oil and grease to be skimmed at minimum waste water flow (Kg/hr)
Maximum mass flow rate for oil and grease to be skimmed at maximum waste water flow (mg/hr)
120000000
120
Maximum mass flow rate for oil and grease to be skimmed at maximum waste water flow (Kg/hr)
Density of oil and grease (Kg/lit)
0.88
136.3636363636
Capacity for oil skimmer for maximum waste water flow(L/hr)
Therefore Capacity for oil skimmer for maximum waste water flow(L/hr)
140
102.2727272727
Capacity for oil skimmer for minimum waste water flow(L/hr)
Therefore Capacity for oil skimmer for minimum waste water flow(L/hr)
100
100 to 140
Hence, Capacity of Oil Skimmer to be installed(lph)

Annex-1
Project Lift Pump Along With Associated Accessories And Pipework For Installation In Waste Water Collection Catch
Title
Design Calculation for Oil Skimmer Capacity for Jugsalai catch pit 1
Date
20/02/2012
Rev
00
200
Maximum Inlet flow of waste water(m3/hr)
150
Minimum inlet flow of waste water (m3/hr)
300
Maximum amount of heavy oil and grease to be skimmed for designed inflow (mg/L)
300000
Maximum amount of heavy oil and grease to be skimmed for designed inflow (mg/m3))
45000000
Maximum mass flow rate for oil and grease to be skimmed at minimum waste water flow (mg/hr)
45
Maximum mass flow rate for oil and grease to be skimmed at minimum waste water flow (Kg/hr)
Maximum mass flow rate for oil and grease to be skimmed at maximum waste water flow (mg/hr)
60000000
Maximum mass flow rate for oil and grease to be skimmed at maximum waste water flow (Kg/hr)
60
Density of oil and grease (Kg/lit)
0.88
Capacity for oil skimmer for maximum waste water flow(L/hr)
68.1818181818
Therefore Capacity for oil skimmer for maximum waste water flow(L/hr)
70
Capacity for oil skimmer for minimum waste water flow(L/hr)
51.1363636364
Therefore Capacity for oil skimmer for minimum waste water flow(L/hr)
50
Hence, Capacity of Oil Skimmer to be installed(lph)
50
to
70

Annex-1
Project Lift Pump Along With Associated Accessories And Pipework For Installation In Waste Water Collection Catch Pits
Title
Design Calculation for Oil Skimmer Capacity for Jugsalai catch pit 2
Date
20/02/2012
Rev
00
300
Maximum Inlet flow of waste water(m3/hr)
Minimum inlet flow of waste water (m3/hr)
200
300
Maximum amount of heavy oil and grease to be skimmed for designed inflow (mg/L)
300000
Maximum amount of heavy oil and grease to be skimmed for designed inflow (mg/m3))
Maximum mass flow rate for oil and grease to be skimmed at minimum waste water flow (mg/hr)
60000000
60
Maximum mass flow rate for oil and grease to be skimmed at minimum waste water flow (Kg/hr)
Maximum mass flow rate for oil and grease to be skimmed at maximum waste water flow (mg/hr)
90000000
90
Maximum mass flow rate for oil and grease to be skimmed at maximum waste water flow (Kg/hr)
Density of oil and grease (Kg/lit)
0.88
102.2727272727
Capacity for oil skimmer for maximum waste water flow(L/hr)
Therefore Capacity for oil skimmer for maximum waste water flow(L/hr)
110
68.1818181818
Capacity for oil skimmer for minimum waste water flow(L/hr)
Therefore Capacity for oil skimmer for minimum waste water flow(L/hr)
60
60
to 110
Hence, Capacity of Oil Skimmer to be installed(lph)

You might also like