You are on page 1of 7

JEPE 278

Electrical Power and Energy Systems 21 (1999) 183189

Dynamics of diesel and wind turbine generators on an isolated power


system
D. Das a,*, S.K. Aditya a, D.P. Kothari b
a

Electrical Eng. Dept., Indian Institute of Technology, Kharagpur721302, India


Centre for Energy Studies, Indian Institute of Technology, New Delhi110016, India

Abstract
The paper presents dynamic system analysis of an isolated electric power system consisting of a diesel generator and a wind turbine
generator. The 150 kW wind turbine generator is operated in parallel with a diesel generator to serve an average load of 350 kW. Time
domain solutions are used to study the performance of the power system. Optimum values of gain settings of the Proportional-Integral
controller (P-I) are obtained by using the integral squared error (ISE) technique. A simple variable structure control (VSC) logic is also
proposed for improvement of the dynamic performance of the system. 1998 Elsevier Science Ltd. All rights reserved.
Keywords: Wind and diesel power system; Stability; Optimization

1. Introduction
A constantly increasing power demand has to be met
through an adequately planned electrical power generation
programme. Electrical energy is environmentally the most
benign form of energy, with production routed through
conventional fossil fuel burning or through nuclear energy
and wherever possible through hydro resources. All of these
in addition to other disadvantages give rise to environmental
issues of a varied nature. Therefore it is necessary to
consider the problems of electrical energy generation and
environment jointly so that the increasing need of electricity
for industrialization will be met with minimal environmental degradation. One of the solutions is to utilize wind
energy in favourable sites which are remote from centralised
energy supply systems. Since wind power varies randomly
there must be a stand-by power source to meet load demand.
The diesel and wind system is one of the hybrid systems
utilizing more than one energy source. A wind and diesel
system is very reliable because the diesel acts as a cushion to
take care of variation in wind speed, and would always
provide power equal to load minus the wind power.
Scott et al. [1] have investigated the dynamic interaction
to quantify any increased disturbance to the Block Island
Power Company (BIPCO), on Block Island (which operates
an isolated electric power system consisting of diesel and
wind turbine generators resulting from connection of the
MOD-OA wind turbine generator). In this study, the
* Corresponding author; e-mail: ddas@ee.iitkgp.ernet.in.

dynamic simulation of the wind turbine generator operated


in parallel with a diesel generator on an isolated power
system is carried out. Optimum values for the gain settings
of the Proportional-Integral (P-I) controller have been
obtained using the Integral Squared Error (ISE) technique.
A simple Variable Structure Control (VSC) logic is also
proposed for the improvement of system dynamic performance.

2. Description of diesel and wind systems


The model considered in this study consists of the following sub-systems [1,3,4]:
Wind dynamics model;
Diesel dynamics model;
Blade pitch control of wind turbine;
Generator dynamics model.
The wind model is one feature that is unique to the wind
turbine generator and is not required for the diesel generator
system in the stability programme. Anderson et al. [2] have
presented one model that can properly simulate the effect of
wind behaviour, including gusting, rapid (ramp) changes
and background noise. The basic conditions for start up
and synchronization are that the wind speed is to be within
an acceptable range and there must be a phase match
between the generator and system voltages [1].
The diesel dynamics is associated with diesel power and
the nature of the dynamic behaviour in this model is

0142-0615/99/$ - see front matter 1998 Elsevier Science Ltd. All rights reserved.
PII: S0142-061 5(98)00033-7

184

D. Das et al. / Electrical Power and Energy Systems 21 (1999) 183189

Fig. 1. Conceptual model of diesel and wind turbine generator system.

dominated by the diesel speed governor controller. A total


power set point is selected in which it can manually adjusted
from zero to maximum value. The purpose of the adjustable
power set point is to allow system utility personnel to lower
the power setting below the maximum settings of the wind
generator to prevent controlling diesel from dropping to less
than 50% of the rated power. Operation of a diesel engine
for extended periods at two power levels could result in
possible engine damage.
Pitch control has the potential for producing the highest
level of interaction because of the presence of both diesel
and wind turbine control loops. The pitch control system
consists of a power measurement transducer, a manual
power set point control, a proportional plus integral feedback function, and a hydraulic actuator which varies the
pitch of the blades. Turbine blade pitch control has a significant impact on the dynamic behaviour of the system. This
type of control only exists in horizontal axis machines.

Variable pitch turbines operate efficiently over a wider


range of wind speeds than fixed pitch machines. However,
cost and complexity are higher.
The generator dynamics model consists of a synchronous
generator driven by a diesel engine through a flywheel and
connected in parallel with an induction generator driven by
a wind turbine. The diesel generator will act as a dummy
grid for the wind generator which is connected in parallel.
Variations of electrical power due to changes in wind speed
should be as small as possible; this is obtained by using the
induction generator as a wind turbine drive train. Unlike
synchronous generators, induction generators are high
compliance couplings between the machine and the electrical system. This is true for induction generators with slip of
at least 12% at rated power. The controlled variables are
turbine speed and shaft torque. Control acts on the turbine
blade pitch angle (pitch control). Since the torque speed
characteristic of the induction generator is nearly linear in

Fig. 2. Functional block diagram for wind and diesel systems with pitch control.

D. Das et al. / Electrical Power and Energy Systems 21 (1999) 183189

185

Fig. 3. Kp vs J for several values of KI.

the operating region, torque changes are reflected as speed


changes. Therefore, it is possible to provide a single speed
controller to control speed as well as torque.

A linear model is formulated for the wind and diesel


turbine generator system for the purpose of identifying
and quantifying the underdamped oscillation. This objective
is met by retaining the pertinent controller dynamics for
both the diesel unit governors and wind turbine generator
pitch controller/actuator. The conceptual model that results
is shown in Fig. 1. The fluid coupling shown in Fig. 1
transfers speed difference into power. The actual function
is nonlinear (Square law) but for the model it is linearized,
resulting in a constant for the particular power set point
selected. Fig. 2 shows the functional block diagram that is
obtained.
The transfer function of the hydraulic pitch actuator is
given as:
1

But Tk is very small compared to Tp2 and hence Tk is


neglected from the mathematical model. Therefore Eq. (1)
can be written as
Kp2 1 STp1
DHS

1 STp2 1 S
U1 S

DPf S
K 1 S
d
Dvref S Dv2 S
S1 ST1

As vref is the reference speed setting (a constant) for the


diesel generator, therefore Dvref 0.0. Substituting Dvref
0.0 in Eq. (3), we get

3. Mathematical model of the system

Kp2 1 STp1
DHS

2
U1 S
Tk S STp2 11 S

given as:

The transfer function Eq. (2) of the hydraulic pitch actuator is split into two blocks (Fig. 2) and DH1 is a dummy
variable.
The transfer function of the diesel governor (Fig. 2) is

DPf S
K 1 S
d
Dv2 S
S1 ST1

The transfer function of the diesel governor Eq. (4) is split


into two blocks and DPf1 is a dummy variable.
Appearing in a block (Fig. 2) labelled data fit pitch
response is a simple lag which is required to match the
phase/gain characteristic of the model. Other state variables
are marked in Fig. 2. The system is a linear continuous-time
dynamic system and can be represented by a set of linear
differential equations of the form:
X_ AX BU GP

where X, U and P are state, control and disturbance vectors


and A, B and G are constant matrices associated with them
respectively. For this system (Fig. 2), X, U and P are
given as
X 0 DH1 DH DD Dv1 Dv2 DPf 1 DPf

U U1

P 0 DPv DPload

where, 0 stands for transpose. A, B and G are given in


Appendix 1. Data for this system are given in
Appendix 2.

186

D. Das et al. / Electrical Power and Energy Systems 21 (1999) 183189

is given as
U1 Kp DPmax DPvtg KI

Zt
0

DPmax DPvtg dt 9

For the study system, Pmax 150 kW is constant, therefore DPmax 0.0. Substituting DPmax 0.0 in Eq. (9)
we obtain
U1 Kp DPvtg KI

Zt
0

DPvtg dt

10

An attempt is made to obtain the optimum values of P-I


gain settings (Kp and KI) using the integral squared error
(ISE) technique for a 1% step increase of load.
A performance index
Fig. 4. Plot of Kv vs J.

J
4. Optimization of the Proportional-Integral (P-I)
controller gain settings using the ISE technique
Many utilities prefer to use the P-I controller for
better system dynamic response and in the present
study, the P-I controller is used. The P-I control law

Zt
0

DPvtg 2 dt

11

is minimized to obtain the optimum values for P-I gain


settings. Note that DPvtg is also a function of Dv1 and Dv2
(Fig. 2).
Fig. 3 shows the plot of J vs Kp for several values of
KI, where Kp and KI are proportional and integral gains

Fig. 5. Frequency responses with conventional and variable structure controllers.

D. Das et al. / Electrical Power and Energy Systems 21 (1999) 183189

187

Fig. 6. Power responses with conventional and variable structure controllers.

respectively. From Fig. 3, it is seen that Kp 10:0 and KI


4:0 are more or less optimum values of P-I gain settings.
5. Variable structure control (VSC) logic
In this study, an attempt is also made to improve the
system dynamic performance by using a simple variable
structure control (VSC) logic which is based on proportional
(P) and proportional-integral (P-I) control concept. If the
control law applied at the first stage of the transient (as
long as error is sufficiently large) is chosen as
U1 Kv DPvtg if DPvtg 1

12

where 1 0 is some constant, but when the error is small


the control law is
Zt
13
U1 Kp DPvtg KI DPvtg dt if DPvtg 1
0

where DPvtg 1 for t t1 , then if the parameters Kv, Kp, KI


and 1 are suitably selected, one can ensure a high-quality
transient response, distinguished by good dynamic and
steady-state characteristics. Indeed taking the magnitude
of Kv as being sufficiently large, one can make sure that
the speed of the system is high; thus, the error DPvtg, in

response to a step input rapidly enters the region


DPvtg 1. At the instant t1 , when the error has fallen to
1, the structure of the controller is changed by switching to a
P-I control, which eliminates the steady error remaining in
the system.
An attempt is made to obtain optimum values of Kv by
using the ISE technique. The same performance index J Eq.
(11) is chosen to obtain the optimum values of Kv. Throughout this optimization process, values of Kp and KI are fixed at
10.0 and 4.0, respectively. Fig. 4 shows the plot of J vs Kv
for 1 0.0004. It is worth mentioning here that several
values of 1 are tried out. However, 1 0.0004 gives the
lowest value of J. From Fig. 4, it is seen that the optimum
value of Kv is 10.0. However, any positive value of Kv
does not minimize the performance index J Eq. (11) and
perhaps this is due to excessive control action.

6. Dynamic responses
Figs. 5 and 6 show the dynamic responses for a 1% step
increase of load with the P-I controller and variable structure controller (VSC). It is seen that the activation of pitch
control with the conventional P-I controller results in an
underdamped response. Although this is a stable response,
the low damping allows the oscillation to continue for a

188

D. Das et al. / Electrical Power and Energy Systems 21 (1999) 183189

deviations and settling time compared to that of the conventional fixed structure P-I controller.
It can also be concluded that wind turbine generation,
even when providing a large proportion of the power
required by an isolated utility can be a practical option
resulting in system disturbances no greater than those
found in a conventional diesel system.

longer time before damping out. It is seen that with the use
of VSC, damping is greatly improved. Peak wind generator
frequency deviation (Fig. 5(a)) and peak diesel power deviation (Fig. 6(a)) are much less compared to the conventional
P-I controller. From Fig. 6(b), it is also seen that with the use
of VSC, the wind power deviation (DPvtg) is slow and
monotonic and hence is preferred. From Figs 5 and 6, it is
also seen that with the use of VSC, settling time is much less
compared to that of the conventional P-I controller. Therefore, it can be concluded that the variable structure controller improves the system damping compared to the fixed
structure P-I controller.
2

Appendix 1
A, B and G matrices of the system (Fig. 2) are given
below:

1
Tp2

6
6
6
!
6
6
6 Kp2 Kp2 Tp1
6
Tp2
6
6
6
6
0
6
6
6
A6
0
6
6
6
6
6
6
0
6
6
6
6
0
6
6
4
0
2

1
Tp2

6
6
6
6
6 Kp2 Tp1
6
6 T
6
p2
6
6
0
6
B6
6
6
0
6
6
6
0
6
6
6
6
0
4
0
7. Conclusions
A linear mathematical model of the wind and diesel turbine
generators operating on an isolated electric power system has
been formulated for the purpose of identifying and quantifying
the underdamped oscillation. The simulation incorporates
wind turbine pitch control and diesel governor. Optimum
values for the gain parameters of the conventional proportional-integral (P-I) controller and variable structure controller
(VSC) have been obtained using the integral squared error
(ISE) technique. Analysis reveals that the variable structure
controller gives better dynamic performance in terms of peak

3
7
7
7
7
7
7
7
7
7
7
7
7;
7
7
7
7
7
7
7
7
7
5

Kp3

Kpc
2Hv

Kfc
2Hv

Kfc
2Hv

Kfc
2Hd

Kfc

Kd

Kd
T1

1
T1

6
6 0
6
6
6 0
6
6
6 1
6
6
G 6 2Hv
6
6
6
6 0
6
6
6
6 0
4
0

3
0 7
7
7
7
7
0 7
7
7
7
7
0 7
7
7
7
0 7
7
7
7
7
7
1 7
7
7
7
0 7
7
7
1 5
T1

7
0 7
7
7
0 7
7
7
7
0 7
7
7
7
7
1 7
7
2Hd 7
7
7
0 7
5
0

Note that B is a 7 1 matrix because there is only one


control input.

Appendix 2
Area capacity; PR 350 kW;
Hv inertia constant on machine base
3:5 s for wind system;
Hd inertia constant on machine base
8:5 s for diesel system;

D. Das et al. / Electrical Power and Energy Systems 21 (1999) 183189

189

Kfc 16:2 pu kW=Hz Kd 16:5 pu kW=Hz;

References

Kp2 1:25

Tp2 0:041 s;

Kp3 1:40

Tp1 0:60 s;

DPload 0:01 pu kW

Kpc 0:80;

T1 0:025 s

Tk 0:0009 s:

[1] Scott GW, Wilrekar VF, Shaltens RK. Wind turbine generator interaction with diesel generators on an isolated power system. IEEE Trans
Power Apparatus Syst 1984;PAS 103(5):933937.
[2] Anderson PM, Bose A. Stability simulation of wind turbine systems.
IEEE Trans Power Apparatus Syst 1983;PAS 102(12):37913795.
[3] Hinrichsen EN. Controls for variable pitch wind turbine generators.
IEEE Trans Power Apparatus Syst 1984;PAS 103(4):886892.
[4] Hinrichsen EN, Nolan PJ. Dynamics and stability of wind turbine
generators. IEEE Trans Power Apparatus Syst 1982;PAS
101(8):26402648.

You might also like