Tank Vent Sizing & Selection Report


16-ene-2014

Venezuela
+58-212-9440966
rdiaz@controval.com
Quote Number:

No

Prpd. Chk. Appr.

Date

Revision

Client: PDVSA GAS


Location: ESTACION FLUJO CHIMIRE 6 (CHEF-6)

End-User Ref. No.:

Project: FACILIDADES DE PRODUCCION CHIMIRE


1

Project Ref. No.: DB410901


41

Valve ID

SIZING DATA
Non-Code

Tag No. PSV-3001A00 / PSV-3001B00

42

Design Code

Service Alivio de Tanque Produccin TK-01-A/B

43

Sizing Basis

PID No. DB410901-EF1D3-PP03005

44

Fluid State at Inlet

Gas / Vapor

Line No. TK-01-A/B

45

Relieving Case

Pressure & Vacuum Relief

5
6
7

Quantity
2

GENERAL
Weight Loaded Tank Vent - Vent to Atm.

Valve Type

46
47

System Conditions
Operating Pressure

48
49

MAWV

10

50

Atmospheric Pressure

51

Operating Temperature

12

Inlet

6"

13

Outlet

Vent

14

CONNECTIONS
FF
150#
To

Standard

52

Min. Design Temperature

ANSI B16.5

53

Max. Design Temperature

Drilling

Atm.

0 psig

14.696 psia

MATERIALS OF CONSTRUCTION
Body
Aluminum

54

16

Trim

Aluminum

56

Molecular Weight, M

17

Trim Coating

None

57

Compressibility, Z

0.99

18

Insert

Buna-N

58

Ratio of Sp. Heats, k (Cp / Cv)

1.127

19

Gaskets

Buna-N

59

Subsonic Flow Factor, Fs

20

O-ring

Buna-N

60

Pressure Set

0.25 psig

21

Screen

304 SST

61

Over Pressure

0.025 psig

22

Retainer

316 SST

62

Built-Up

0 psig

23

Pressure Range

Low Pressure Setting

63

Constant

0 psig

24

Vacuum Range

Low Pressure Setting

Variable Superimposed

0 psig

25

Spring

15

Pressure Relief Conditions


Fluid Name
Natural Gas (SG=0.6)

55

Back
64 Pressure
65

Total

26

66

Inlet Loss

27

67

Relieving Temperature

28

68

29

69

30

70

31

Valve Model No.

32

Brand

33
34

Required Flow

35

Max. Flow per Valve

36

Total Selected Flow

37

SIZING / SELECTION
2010B61BFFBS0202

71

API2000

MAWP

9
11

Sizing Std.

Blocked Discharge

Vacuum Relief Conditions


Fluid Name

41.429

0.134

0 psig
0 psig
130 F

Air

Molecular Weight, M

28.970

72

Compressibility, Z

1.000

Pressure Case
790.73 lb/hr

73

Ratio of Sp. Heats, k (Cp / Cv)

1.400

74

Subsonic Flow Factor, Fs

4681.933 lb/hr

75

Pressure Set

0.84 in wc g
0.084 in wc g

Varec

9363.866 lb/hr

76

Under Pressure

Vacuum Case
790.73 lb/hr

77

Relieving Temperature

Required Flow

39

Max. Flow per Valve

1123.328 lb/hr

79

Estimated Reaction Force

40

Total Selected Flow

2246.656 lb/hr

80

Estimated Noise Level (db)

130 F

78
58.2 at 100-ft

Tag Notes

38

0.048

Printed On: 25-mar-2014

Pentair PRVSIZE Software Version pr5_20131223.1

Page : 1

Pentair Valves & Controls and its parent, subsidiaries, and affiliates assume no liability in any way whatsoever for any direct or indirect loss or damage through the application of this software. See terms of license
agreement. Not for resale. All rights reserved. All trademarks, trade names and/or registered trademarks referred to in this program are the property of their respective owners. Copyright 2014 Pentair Valves & Controls.

CONTROVAL
Edif. 446A, Calle San Rafael c/

Pressure Relief Valve Calculation Report


16-ene-2014

Venezuela
+58-212-9440966
rdiaz@controval.com
Quote Number:

No

Prpd. Chk. Appr.

Date

Revision

Client: PDVSA GAS


Location: ESTACION FLUJO CHIMIRE 6 (CHEF-6)

End-User Ref. No.:

Project: FACILIDADES DE PRODUCCION CHIMIRE


1

Tag No. PSV-3001A00 / PSV-3001B00


Valve Model No. 2010B61BFFBS0202

4
5
6

VALVE ID

2
3

Project Ref. No.: DB410901

Flow

Qty. 2

CALCULATION SUMMARY

10

Required

790.73 lb/hr

11

4681.933 lb/hr

12

Max. Flow per Valve

CALCULATION NOTES

PRESSURE CONDITION
Variable Type

Variable Name

Fluid Properties

Molecular Weight

41.429

41.429

Ratio of Specific Heats

1.127

1.127

Compressibility

0.99

Process Cond.

Symbol

Required Mass Flow

Wreq

Set Pressure

Valve Data

Input Value

790.73 lb/hr

Equation Value

0.99
790.73 lb/hr

Pset

0.25 psig

0.25 psig

Over Pressure

Pover

0.025 psig

0.025 psig

Atmospheric Pressure

Patm

14.696 psia

Relieving Temperature

130 F

Distance from Valve (noise)

Maximum Flow Coefficient

Kmax

14.696 psia
589.670 R

100 ft

100 ft

0.89

0.89

Transition to Full Open

Tp

1.5

1.5

Shape Factor

0.34

0.34

Orifice Area

28.89 in

28.89 in

Calculate Inlet Relieving Pressure, Outlet Pressure, Absolute Pressure Ratio


P1 = Pset + Pover + Patm

P1

14.971 psia

P2 = Patm

P2

14.696 psia

PR = P2 / P1

PR

0.982

Fs

0.134

0.1

Calculate Sub-Critical Flow Factor


Fs = {[k / (k - 1)] * [PR^(2 / k) - PR^((k+1)/k)]}^0.5
Calculate Over Pressure Ratio
X = Pover / Pset
Calculate Discharge Coefficient

0.413

Kd

If X > Tp, then Kd = Kmax, else Kd = Kmax * {sin[(X / Tp) * ( / 2)]}^E


Calculate Mass Flow

4681.933 lb/hr

4681.933 lb/hr

W = 735 * Kd * A * P1 * Fs * [M / (T * Z)]^0.5
Calculate Required Orifice Area

Areq

4.879 in

4.879 in

Areq = A * Wreq / W
Calculate Noise Level at 100-ft (30-m)

L100

58.2 db

L100 = [87.75 * log( 1/PR ) + 14.09] + [10 * log(0.29354 * W * k * T / M)]

Printed On: 25-mar-2014

Pentair PRVSIZE Software Version pr5_20131223.1

Page : 2

Pentair Valves & Controls and its parent, subsidiaries, and affiliates assume no liability in any way whatsoever for any direct or indirect loss or damage through the application of this software. See terms of license
agreement. Not for resale. All rights reserved. All trademarks, trade names and/or registered trademarks referred to in this program are the property of their respective owners. Copyright 2014 Pentair Valves & Controls.

CONTROVAL
Edif. 446A, Calle San Rafael c/

Pressure Relief Valve Calculation Report


16-ene-2014

Venezuela
+58-212-9440966
rdiaz@controval.com
Quote Number:

No

Prpd. Chk. Appr.

Date

Revision

Client: PDVSA GAS


Location: ESTACION FLUJO CHIMIRE 6 (CHEF-6)

End-User Ref. No.:

Project: FACILIDADES DE PRODUCCION CHIMIRE


1

Tag No. PSV-3001A00 / PSV-3001B00


Valve Model No. 2010B61BFFBS0202

4
5
6

VALVE ID

2
3

Project Ref. No.: DB410901

Flow

Qty. 2

CALCULATION SUMMARY

10

Required

790.73 lb/hr

11

4681.933 lb/hr

12

Max. Flow per Valve

Calculate Noise Level at Distance, r

CALCULATION NOTES

Lp

58.2 db

Lp = L100 - 20 * log(r / 100)

Printed On: 25-mar-2014

Pentair PRVSIZE Software Version pr5_20131223.1

Page : 3

Pentair Valves & Controls and its parent, subsidiaries, and affiliates assume no liability in any way whatsoever for any direct or indirect loss or damage through the application of this software. See terms of license
agreement. Not for resale. All rights reserved. All trademarks, trade names and/or registered trademarks referred to in this program are the property of their respective owners. Copyright 2014 Pentair Valves & Controls.

CONTROVAL
Edif. 446A, Calle San Rafael c/

Pressure Relief Valve Calculation Report


16-ene-2014

Venezuela
+58-212-9440966
rdiaz@controval.com
Quote Number:

No

Prpd. Chk. Appr.

Date

Revision

Client: PDVSA GAS


Location: ESTACION FLUJO CHIMIRE 6 (CHEF-6)

End-User Ref. No.:

Project: FACILIDADES DE PRODUCCION CHIMIRE


1

Tag No. PSV-3001A00 / PSV-3001B00


Valve Model No. 2010B61BFFBS0202

4
5
6

VALVE ID

2
3

Project Ref. No.: DB410901

Flow

Qty. 2

CALCULATION SUMMARY

10

Required

790.73 lb/hr

11

1123.328 lb/hr

12

Max. Flow per Valve

CALCULATION NOTES

VACUUM CONDITION
Variable Type

Variable Name

Fluid Properties

Molecular Weight

28.970

28.970

Ratio of Specific Heats

1.400

1.400

Compressibility

1.000

Process Cond.

Symbol

Required Mass Flow

Wreq

Set Pressure

790.73 lb/hr

Vset

0.84 in wc g

Over Pressure

Vover

0.084 in wc g

Atmospheric Pressure

Patm

Relieving Temperature
Valve Data

Input Value

Maximum Flow Coefficient

14.696 psia
130 F

Equation Value

1.000
790.73 lb/hr
0.030 psig
0.003 psig
14.696 psia
589.670 R

Kmax

0.58

0.58

Transition to Full Open

Tp

1.75

1.75

Shape Factor

0.22

Orifice Area

28.89 in

0.22
28.89 in

Calculate Inlet Relieving Pressure, Outlet Pressure, Absolute Pressure Ratio


P1 = Patm

P1

14.696 psia

P2 = Patm - Vset - Vover

P2

14.663 psia

PR = P2 / P1

PR

0.998

Fs

0.048

0.1

Calculate Sub-Critical Flow Factor


Fs = {[k / (k - 1)] * [PR^(2 / k) - PR^((k+1)/k)]}^0.5
Calculate Over Pressure Ratio
X = Vover / Vset
Calculate Discharge Coefficient

0.341

Kd

If X > Tp, then Kd = Kmax, else Kd = Kmax * {sin[(X / Tp) * ( / 2)]}^E


Calculate Mass Flow

1123.328 lb/hr

1123.328 lb/hr

Areq

20.336 in

20.336 in

W = 735 * Kd * A * P1 * Fs * [M / (T * Z)]^0.5
Calculate Required Orifice Area
Areq = A * Wreq / W

Printed On: 25-mar-2014

Pentair PRVSIZE Software Version pr5_20131223.1

Page : 4

Pentair Valves & Controls and its parent, subsidiaries, and affiliates assume no liability in any way whatsoever for any direct or indirect loss or damage through the application of this software. See terms of license
agreement. Not for resale. All rights reserved. All trademarks, trade names and/or registered trademarks referred to in this program are the property of their respective owners. Copyright 2014 Pentair Valves & Controls.

CONTROVAL
Edif. 446A, Calle San Rafael c/

Pressure Relief Valve Dimensional Drawing


16-ene-2014

Venezuela
+58-212-9440966
rdiaz@controval.com
Quote Number:

No

Prpd. Chk. Appr.

Date

Revision

Client: PDVSA GAS


Location: ESTACION FLUJO CHIMIRE 6 (CHEF-6)

End-User Ref. No.:

Project: FACILIDADES DE PRODUCCION CHIMIRE


1

Project Ref. No.: DB410901


7

Valve ID

SELECTION SUMMARY

Tag No. PSV-3001A00 / PSV-3001B00

Valve Model No.

2010B61BFFBS0202

Service Alivio de Tanque Produccin TK-01-A/B

Brand

Varec

PID No. DB410901-EF1D3-PP03005

10

Line No. TK-01-A/B

2
3

11

Inlet

6"

Drilling

12

Outlet

Vent

FF

Standard

Atm.

To

ANSI B16.5

46.17 lb

20.94 kg

A=

24 in

609.60 mm

B=

17 in

431.80 mm

C=

13.19 in

335.03 mm

D=

15.5 in

393.70 mm

E=

F=

G=

H=

Tag Notes
Printed On: 25-mar-2014

150#

Wt.=

Dimension Notes

CONNECTIONS

Quantity

Pentair PRVSIZE Software Version pr5_20131223.1

Accessories not shown.


Weight and dimensions shown
are approximate.
Actual valve may vary from.
image.

Page : 5

Pentair Valves & Controls and its parent, subsidiaries, and affiliates assume no liability in any way whatsoever for any direct or indirect loss or damage through the application of this software. See terms of license
agreement. Not for resale. All rights reserved. All trademarks, trade names and/or registered trademarks referred to in this program are the property of their respective owners. Copyright 2014 Pentair Valves & Controls.

Pentair PRVSIZE Software


Brand:

Varec

Printed On: 25-mar-2014

Valve Type:

6" 2010B

Pentair PRVSIZE Software Version pr5_20131223.1

Page : 6

Pentair Valves & Controls and its parent, subsidiaries, and affiliates assume no liability in any way whatsoever for any direct or indirect loss or damage through the application of this software. See terms of license
agreement. Not for resale. All rights reserved. All trademarks, trade names and/or registered trademarks referred to in this program are the property of their respective owners. Copyright 2014 Pentair Valves & Controls.

Pentair PRVSIZE Software


Summary Report
Project Information
Company:
Location:

PDVSA GAS
ESTACION FLUJO CHIMIRE 6 (CHEF-6)

Project:
Project Ref. No.:

FACILIDADES DE PRODUCCION CHIMIRE


DB410901

Tag Information
Tag Number:
Revision:
Prepared By:

PSV-3001A00 / PSV-3001B00
Last Modified:
Checked By:

16/01/2014 01:12:50 p.m.


Approved By:

Specific Tank Data


Sized Using User Defined Flow
Pressure Fluid:
Natural Gas (SG=0.6)
Pressure Set Point:
0.25 psig
Allowed Over Pressure:
0.025 psig
Pressure Flow Rate:
790.73

Product in Tank:
Vacuum Fluid:
Vacuum Set Point:
Allowed Under Pressure:
Vacuum Flow Rate:

CRUDO
Air
0.84 in wc g
0.084 in wc g
790.73

Valve Sizing Information


Valve Type:
2010B, 6"
Part Number: 2010B61BFFBS0202
Max Pressure Flow Capacity:
4681.933 lb/hr

Quantity to Order:
1
Max Vacuum Flow Capacity:

1123.328 lb/hr

Selected Valve Description


Code
201
0
B
6
1
B
F
F
B
S
02
02

Category
Style1
Trim Coating
Style2
Size
Body Trim
Insert
Flange Drilling
Flange Face
Gaskets
Screen Retainer
Pressure Range
Vacuum Range

Printed On: 25-mar-2014

Description
Pressure & Vacuum Relief, Vented Pressure Outlet
Air Cushion Seating
Weight Loaded Modular
6"
Alum Body / Alum Trim
BUNA-N
ANSI 150# Drilling & Fractional Studs
FF Flange
BUNA-N Gasket / BUNA-N O-Ring
304 SST Screen / 316 SST Retainer
Low Pressure Setting
Low Vacuum Setting

Pentair PRVSIZE Software Version pr5_20131223.1

Page : 7

Pentair Valves & Controls and its parent, subsidiaries, and affiliates assume no liability in any way whatsoever for any direct or indirect loss or damage through the application of this software. See terms of license