Professional Documents
Culture Documents
Page 15
The standard is likely to define the following parameters for output, energy consumption and energy
efficiency (COP):
Standard rating conditions: defines the water inlet temperature for water cooled condensers
and air inlet temperature for air cooled condensers as well as the water temperature leaving
the evaporator (Condition A).
Part load rating conditions: defines the water inlet temperature for water cooled condensers
and air inlet temperature for air cooled condensers at load output conditions of 75%, 50% and
25% of the rated output of the system (Conditions B, C and D respectively).
The draft standard specifies test setup for energy and capacity determination.
ARI550/590
Eurovent
29.4C (85F)
30C
Liquid
cooled
operation condition
0.054 L/s/kW
5K temp drop
35C (95F)
35C
6.7C (44F)
7C
0.043 L/s/kW
5K temp drop
Liquid
cooled
operation condition
condenser
condenser
Page 16
The ARI standard defines an Integrated Part Load Value (IPLV) which is defined as a weighted
average of the 4 test points COP values at Conditions A to D as follows:
IPLV = 0.01A + 0.42B + 0.45C + 0.12D
Where Condition A, B, C and D are COP at load outputs of 100%, 75%, 50% and 25% respectively.
Under ARI, part load conditions are as follows:
Condition A: 29.4C (85F) inlet temperature for water cooled condensers and 35C (95F) for
air cooled condensers, 100% rated output.
Condition B: 23.9C (75F)inlet temperature for water cooled condensers and 26.7C (80F) for
air cooled condensers, 75% rated output.
Condition C: 18.3C (65F) inlet temperature for water cooled condensers and 18.3C (65F) for
air cooled condensers, 50% rated output.
Condition D: 18.3C (65F) inlet temperature for water cooled condensers and 12.8C (55F)
for air cooled condensers, 25% rated output.
Page 17
COP at rated output is the primary comparative efficiency value for chillers. The Integrated Part Load
Value (IPLV), which weights data for all 4 test conditions, is also widely used as a comparative
efficiency value.
The IPLV is a pre-defined weighting of the efficiency of 4 load conditions to give and integrated
average annual efficiency. The weightings used in the standard IPLV formula may not suit all
applications and regions. However, it is widely used as an international benchmark for performance.
The separate reporting of COP at Conditions A to D would allow the standardised test outputs to be
weighted in a way that was more relevant to local conditions (if required) without the need for any
retesting.
COP at rated output and the IPLV are generally used together to define minimum energy
performance standards (MEPS) where applicable.
Performance Issues
The measurement of chiller energy efficiency is a relatively straight forward determination of output
energy over input energy. There only significant performance issue during operation is the fouling of
the evaporator and where applicable the condenser (where this is water cooled). The main standards
have allowances to estimate the performance degradation due to fowling during operation. These
range from standard fixed allowances to simulation approaches based on parameters such as
capacity, surface area of the heat exchanger and operating range of the liquids.
Recommended directions
Two major rating systems for chillers are in existence. While slightly different conditions are specified
in the North American and European systems, the practical differences in the measured efficiency
results will be small in most cases. Fortunately, this means that there is already a good level of global
harmonisation in the testing and reporting of chiller energy efficiency.
Part of the issue is that there is no international test procedure at this stage. However, work on an ISO
standard has been approved and it is hoped that this will draw on existing approaches in North
America and Europe to form the basis of a uniform global approach to testing and rating of chillers.
This should be supported as the basis for providing a basis for the global convergence of testing
approaches for chillers.
Page 18