Test Report
What the designer needs to know
By Luke M. Snell
/ December 2010
41
42
December 2010
/ Concrete international
ACI 318-08, Section 5.6.3.3, gives two criteria for accepting the strength of the concrete:
The average of any three consecutive strength tests
equals or exceeds fc; and
No individual strength test falls below fc by more than
500 psi when fc is 5000 psi or less or by more than 10%
of fc when fc is greater than 5000 psi.
If the test result fails to meet either of these criteria,
youll need to take appropriate measures for the concrete
represented by the failed test(s) and for any concrete yet
to be placed on the job. Details of how to apply these
procedures are given in ACIs Concrete Knowledge
Center.4 But what measures are appropriate?
/ December 2010
43
44
December 2010
/ Concrete international
References
1. Whiting, D., Strength and Durability of Residential Concrete
Containing Fly Ash, Research and Development Bulletin RD099,
Portland Cement Association, Skokie, IL, 1989, 42 pp.
2. ACI Committee 318, Building Code Requirements for
Structural Concrete (ACI 318-08) and Commentary, American
Concrete Institute, Farmington Hills, MI, 2008, 473 pp.
3. ACI Committee 311, ACI Manual of Concrete Inspection
(SP-2(07)), American Concrete Institute, Farmington Hills, MI, 2007,
pp. 16-17.
4. Snell, L.M., Acceptance of Concrete Test Results, ACI
Committee E702 Example Problems, Concrete Knowledge Center
Designing Concrete Structures, accessed at www.concrete.org/
Technical/CKC/Designing_Concrete_Structures.htm, accessed
Oct. 1, 2010.
Note: Additional information on the ASTM standards discussed
in this article can be found at www.astm.org.
Selected for reader interest by the editors.