***ALL ITEMS ARE REQUIRED AND ALL RESPONSES MUST BE FILLED UNLESS NOT APPLICABLE.***
Response
1)
Please provide Single-Line Diagram(s), Three-Line Diagram(s), and Protective Relay List &
Trip Schedule for the generation and interconnection facilities:
General SLD Comments and Questions
a.
260351419.xls
Transformer impedance(s).
ii.
The protective relaying and metering for the generators, transformers, buses, and all
other main substation equipment.
iii.
For the potential transformers, please indicate the type, quantity, ratio, and accuracy
rating.
iv.
For the current transformers, please indicate the type, quantity, ratio, and accuracy
rating, and thermal rating factor.
v.
Auxiliary power devices (e.g. capacitors, reactors, storage systems, etc.) and their
rating(s); additional inquiries may be made to obtain technical data for these devices.
vi.
For the interconnection / tie lines (overhead or underground) and the plant's
generation system, please provide the following, as applicable:
BIL rating.
vii.
viii.
All applicable notes pertaining to the design and operation of the facility.
b.
The Protective relay list & trip schedule should list the protected equipment; the relay
description, type, style number, quantity, ANSI Device No., and range; and the
breaker(s)/switching device(s) tripped, for both the generator protection and the
interconnection facilities protection.
c.
Please provide both a paper and an electronic version (e.g. dgn, dxf, or pdf) of the singleline diagram(s) and the protective relay list & trip schedule.
d.
Single-line diagrams should be provided for both the generation plant and the
interconnection substation.
Page 1 of 9
Updated 9/19/11
FOR PV GENERATION
PROJECT:
DATE:
Preliminary
Interconnection Requirement Study - Data Request
(Nonexclusive Preliminary List)
***ALL ITEMS ARE REQUIRED AND ALL RESPONSES MUST BE FILLED UNLESS NOT APPLICABLE.***
Response
2)
Please provide a plan map of the Non Utility Generation (NUG) facilities; please indicate the
interconnection point to the HECO system.
3)
For the power transformers including the generator step-up transformers, please provide:
4)
5)
6)
260351419.xls
a.
Transformer voltage and MVA ratings, and available taps. Attach copy of transformer test
report or data sheet
b.
c.
d.
Transformer winding connections and grounding used. If the transformer is not solidly
grounded, provide the impedance value for the grounding method.
e.
For the circuit breakers and fault-clearing switching devices, including the generator
breakers, please provide:
a.
b.
b.
a.
Data for the CTs used with the relaying including the manufacturer, type of CT, accuracy
class, and thermal rating factor.
b.
Data for the PTs used with the relaying including the manufacturer, type of PT, voltage
ratings, and quantity.
Page 2 of 9
Updated 9/19/11
FOR PV GENERATION
PROJECT:
DATE:
Preliminary
Interconnection Requirement Study - Data Request
(Nonexclusive Preliminary List)
***ALL ITEMS ARE REQUIRED AND ALL RESPONSES MUST BE FILLED UNLESS NOT APPLICABLE.***
Response
7)
Please provide protective relay settings for existing and proposed generators, including
but not limited to, reverse power, negative sequence, over and underfrequency, over and
under voltage, volts per hertz, etc.
8)
9)
10)
Please provide the following generation and load information for the NUG facilities:
a.
260351419.xls
b.
Expected KW and KVAR loads including, but not limited to, generators' auxiliary load
curve, process load(s) profile(s), etc.
Expected minimum and maximum MW and MVAR import from AND export to HECO.
c.
Page 3 of 9
Updated 9/19/11
FOR PV GENERATION
PROJECT:
DATE:
Preliminary
Interconnection Requirement Study - Data Request
(Nonexclusive Preliminary List)
***ALL ITEMS ARE REQUIRED AND ALL RESPONSES MUST BE FILLED UNLESS NOT APPLICABLE.***
Response
11)
In addition to the items mentioned above, please provide the following for PSS/E models:
a.
12)
Object files and IPLANS for user written models, and applicable library files. The
uncompiled source code for object files shall be provided to ensure compatability with
future versions of PSS/E. In lieu of the uncompiled object file source code, compiled object
file updates compatible with future PSS/E versions shall be provided as requested for the
life of the project.
In addition to PSS/E, other power system analysis tools are required to study events that
cannot accurately be modeled in PSS/E due to limitations of the program (e.g. sub-cycle
behavior). Data compatible with the following tools shall be provided:
a.
b.
NOTE: **Equivalent models other than PSSE may be required if the PSSE model cannot be converted properly.
260351419.xls
Page 4 of 9
Updated 6/15/11
Instructions:
Please fill in the data in the green blanks below
(Note: This does not include the internal isolation transformer, if used)
[1]
[2]
[3]
kVA
NOTE: These parameters should reflect the inverter response for all types of
faults at any point on the electrical system to which the inverter is connected.
This includes faults at the inverter output terminals, and also on the 138 kV
transmission system. If the stated parameters do not cover this range, please
state the adjustments needed to these parameters to accurately represent the
inverter response across this range.
These parameters will be used to model the inverter in the Aspen Oneliner
program as shown in the sample dialog box below:
Updated 6/15/11
Updated 6/15/11
Instructions:
Please fill in the data in the green blanks below
[1]
[2]
Per Unit
Degrees
Amps
NOTE: These parameters should reflect the inverter response for all types of
faults at any point on the electrical system to which the inverter is connected.
This includes faults at the inverter output terminals, and also on the 138 kV
transmission system. If the stated parameters do not cover this range, please
state the adjustments needed to these parameters to accurately represent the
inverter response across this range.
These parameters will be used to model the inverter in the Aspen Oneliner
program as shown in the sample dialog box below:
Updated 6/15/11
Instructions:
Please fill in the data in the green blanks below
(Note: This is not required if an internal isolation transformer is not used)
[1]
[2]
Winding Configuration
Inverter Side =
Customer Side =
[2]
kVA
Delta/Wye
Delta/Wye
Positive Sequence =
Zero Sequence =
[3]
These parameters will be used to model the inverter in the Aspen Oneliner
program as shown in the sample dialog box below:
Updated 6/15/11