Air System Sizing Summary for UMA-02 Ok

Project Name: NOGALES IMSS


Prepared by:

01/12/2014
05:36p.m.

Air System Information


Air System Name ....................................... UMA-02 Ok
Equipment Class ............................................ CW AHU
Air System Type ................................................ SZCAV

Number of zones ............................................................. 1


Floor Area ............................................................... 1593.0 ft
Location ................................................ Nogales, Mexico

Sizing Calculation Information


Calculation Months ..................................... Jan to Dec
Sizing Data .................................................. Calculated

Zone CFM Sizing ................. Sum of space airflow rates


Space CFM Sizing ............. Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load .......................................................... 17.2
Total coil load ........................................................ 206.7
Sensible coil load ................................................. 124.3
Coil CFM at Jul 1500 ............................................. 4035
Max block CFM ..................................................... 4035
Sum of peak zone CFM ........................................ 4035
Sensible heat ratio ............................................... 0.594
ft/Ton ..................................................................... 94.4
BTU/(hr-ft) ........................................................... 127.1
Water flow @ 10.0 F rise .................................... 40.52

Tons
MBH
MBH
CFM
CFM
CFM

gpm

Load occurs at ..................................................... Jul 1500


OA DB / WB ...................................................... 98.6 / 78.8
Entering DB / WB ............................................. 98.6 / 78.8
Leaving DB / WB .............................................. 67.0 / 65.3
Coil ADP ..................................................................... 63.5
Bypass Factor .......................................................... 0.100
Resulting RH ................................................................. 70
Design supply temp. ................................................... 58.0
Zone T-stat Check .................................................... 1 of 1
Max zone temperature deviation .................................. 0.0

F
F
F
F
%
F
OK
F

Central Heating Coil Sizing Data


Max coil load ........................................................ 123.7
Coil CFM at Des Htg ............................................. 4035
Max coil CFM ........................................................ 4035
Water flow @ 20.0 F drop ................................... 12.38

MBH
CFM
CFM
gpm

Load occurs at ..................................................... Des Htg


BTU/(hr-ft) ................................................................. 77.7
Ent. DB / Lvg DB .............................................. 38.0 / 70.5 F

Supply Fan Sizing Data


Actual max CFM .................................................... 4035 CFM
Standard CFM ....................................................... 3529 CFM
Actual max CFM/ft ................................................. 2.53 CFM/ft

Outdoor Ventilation Air Data

Fan motor BHP ........................................................... 0.00 BHP


Fan motor kW .............................................................. 0.00 kW
Fan static ..................................................................... 0.00 in wg
CFM/person ............................................................ 183.41 CFM/person

Design airflow CFM ............................................... 4035 CFM


CFM/ft ................................................................... 2.53 CFM/ft

Hourly Analysis Program v4.80

Page 1 of 4

Ventilation Sizing Summary for UMA-02 Ok


Project Name: NOGALES MARCO
Prepared by: IPD

01/04/2015
05:36p.m.

1. Summary
Ventilation Sizing Method ...................................... Sum of Space OA Airflows
Design Ventilation Airflow Rate ................................................................... 4035 CFM

2. Space Ventilation Analysis Table

Zone Name / Space Name


Zone 1
UMA-02 Quir Urgencias
Totals (incl. Space Multipliers)

Hourly Analysis Program v4.80

Mult.

Floor
Area
(ft)

Maximum
Occupants

1593.0

22.0

Maximum
Required
Supply Air Outdoor Air
(CFM) (CFM/person)
4035.0
4035.0

0.00

Required
Outdoor Air
(CFM/ft)
0.00

Required
Required
Outdoor Air Outdoor Air
(CFM) (% of supply)
4035.0

0.0

Uncorrected
Outdoor Air
(CFM)
4035.0
4035.0

Page 2 of 4

Air System Design Load Summary for UMA-02 Ok


Project Name: NOGALES MARCO
Prepared by: IPD

ZONE LOADS
Window & Skylight Solar Loads
Wall Transmission
Roof Transmission
Window Transmission
Skylight Transmission
Door Loads
Floor Transmission
Partitions
Ceiling
Overhead Lighting
Task Lighting
Electric Equipment
People
Infiltration
Miscellaneous
Safety Factor
>> Total Zone Loads
Zone Conditioning
Plenum Wall Load
Plenum Roof Load
Plenum Lighting Load
Return Fan Load
Ventilation Load
Supply Fan Load
Space Fan Coil Fans
Duct Heat Gain / Loss
>> Total System Loads
Central Cooling Coil
Central Heating Coil
>> Total Conditioning
Key:

Hourly Analysis Program v4.80

01/04/2015
05:36p.m.

DESIGN COOLING
DESIGN HEATING
COOLING DATA AT Jul 1500
HEATING DATA AT DES HTG
COOLING OA DB / WB 98.6 F / 78.8 F
HEATING OA DB / WB 38.0 F / 31.7 F
Sensible
Latent
Sensible
Latent
Details
(BTU/hr)
(BTU/hr)
Details
(BTU/hr)
(BTU/hr)
0 ft
0
0 ft
169 ft
301
169 ft
486
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
2390 W
8153
0
0
0W
0
0
0
5000 W
17060
0
0
22
5390
4510
0
0
0
0
0
0
0
0
0
0
0
0% / 0%
0
0
0%
0
0
30904
4510
486
0
31668
4510
926
0
0%
0
0
0
0%
0
0
0
0%
0
0
0
4035 CFM
0
4035 CFM
0
4035 CFM
88602
77694
4035 CFM
122777
0
4035 CFM
0
4035 CFM
0
0
0
0%
0
0%
0
124270
82204
123703
0
124270
82204
0
0
0
123703
124270
82204
123703
0
Positive values are clg loads
Positive values are htg loads
Negative values are htg loads
Negative values are clg loads

Page 3 of 4

Psychrometric Analysis for UMA-02 Ok


Project Name: NOGALES MARCO
Prepared by: IPD

01/04/2015
05:36p.m.

Location: Nogales, Mexico


Altitude: 3664.0 ft.
Data for: July DESIGN COOLING DAY, 1500
1
1. Outdoor Air
2. Central Cooling Coil Outlet
3. Supply Fan Outlet
4. Room Air

0.020
0.018
0.016

S p e c i f i c H u m i d i t y ( l b /l b )

23

0.014
0.012
0.010
0.008
0.006
0.004
0.002
0.000
30

Hourly Analysis Program v4.80

40

50

60
70
Temperature ( F )

80

90

100

Page 4 of 4