Professional Documents
Culture Documents
K.Stump,Sr. Member
Siemens E&A
Atlanta, GA, USA
KEYWORDS
SVC, thyristor controlled reactor (TCR), thyristor switched capacitor (TSC), reactive power compensation,
voltage control, filter design
NEW MEXICO
\---*.y
I
ABSTRACT
This paper describes the steps for the design of the
Static VAR Compensator (SVC) Eddy County. The
specified system requirements on operating range, loss
evaluation and harmonic performance led to an SVC
configuration which contains one TSC branch, one TCR
branch for continuous reactive power control and two
double tuned filter branches. The system voltage of the
SVC secondary bus was optimized to 8.5 kV based on thyristor equipment capabilities. The paper shows the voltage
and current stresses of the thyristor valves taking into
account system faults for the TCR branch and misfiring
effects on the TSC branch. The approach for filter design
considering the harmonic performance requirements and
i
:
s
e
*
resulting component
ratings
are shown.
The Eddy
County
SVC commenced commercial operation in April 1992.
Roswell
Lubbock
Denver City
To EPE
Maddox
4 - - - - -
TEXAS
A Catisbad
Legend:
- - - - - - 345 kV
230 kV
INTRODUCTION
115 kV
System studies conducted by Southwestern Public Service indicated the need for reactive compensation between
-50 MVAr (inductive) and + 100 MVAr (capacitive). A Static
VAR Compensator system covering this range has been
designed and installed at the 230 kV Eddy County substation located in the southwest corner of the SPS system.
Figure 1 shows the SPS system in the area of Eddy County. Significant features of the Eddy County substation are
that it contains a back to back HVDC converter (rated 200
MW) to transfer power between the SPS system and
western New Mexico, it has a 345 kV connection to a
major generating station at Tolk, and it has a 230 kV connection to generators in the Cunningham / Maddox area.
The purpose of this SVC is to provide voltage support for
the system and allow most efficient use of the generators
in the system.
This paper presents the SVC designed for the Eddy
County substation and highlights the main SVC design considerations and procedures. The SVC secondary voltage is
optimized to take full advantage of the thyristors as proven
by type tests for the selected thyristor design. The circuit
configuration and SVC physical layout are presented. Filter
design considerations and techniques are discussed.
HVDC Back-to-BackStation
NETWORK REQUIREMENTS
System characteristics:
Normal voltage
Max. cont. voltage
Min. cont. voltage
Max. phase voltage unbalance
Transient overvoltage
Normal base frequency
Normal frequency deviation
Min. cont. frequency
Max. cont. frequency
Short circuit power range
230 kV (1 .O pu)
242 kV (1.05 pu)
219 kV (0.95 pu)
2 Yo
345 kV (1.5 pu)
60 Hz
20.02 Hz
59.5 Hz
60.5 Hz
1.1 ... 2.0 GVA
1.O%
1.5%
Design points
Rated inductive power
Rated capacitive power
-50 MVAr
1OOMVAr
1.O pu voltage
1.O pu voltage
Operating range
Continuous cap. operation 0.85 to 1.1 pu voltage
0.9 to 1.1 pu voltage
Continuous ind. operation
Full inductive operation at voltages above 1.1 pu
758
230 kV, 60 Hz
design point
design point
Continuous
VAoperation
4
TSC
DF1
DF2
TCR
1.o
0.5
0.5
brim
Capacitive
Operation
in PU+
A ~~leurCaf:ivofi
LTSC =
C T ~ C=
=
LI
=
L2
C1
=
Cp
=
L3
4
=
=
C3
=
C4
=
R
=
LTCR =
0.58 mH
765 pF
0.81 mH
73pH
10000 pF
368pF
0.20 mH
50pH
1753 pH
441 pH
7.5 Q
7.5 mH
SVC DESIGN
Fig. 3: Single line diagram and data
of the SVC Eddy County
Basic configuration
Figure 3 shows a single line diagram of the SVC configuration selected to meet requirements outlined in the
previous section. SVC capacitive requirements are met by
a 76 MVAr TSC branch and a 24 MVAr filter. The filter is
chosen to shunt away harmonic currents produced by the
TCR so that the harmonic distortion limits of the system
are satisfied. The TCR branch is rated for approximately 74
MVAr to compensate the filter and absorb the required 50
MVAr from the system. The MVAr figures are referred to
the 230 kV bus and include the effect of the 12% SVC
transformer.
The TSC branch includes two surge arresters. An arrester labeled CC in Figure 3 is connected across the capacitor to limit voltage in case the thyristor misfires at the
worst possible time. A second surge arrester labeled SR in
Flgure 3 connected across the TSC valve and reactor
protects the thyristor against overvoltages. Neither of these
arresters operate during normal SVC operation. They
protec! the TSC branch from faults and misfiring transients.
Figure 4 shows the SVC operating diagram. There is an
overlap range of approximately 10 degrees where the TSC
may be either off or on depending upon past history. This
overlap is controlled by a hysteresis type effect and avoids
control instability at the TSC switching time even for the
case of large system frequency deviations as specified.
I
I
I
I
I
I
I
TSC+TCR+FC
I
I
I I
I 1
I 1
I
100
50
TCR+FC
1
I
I
I
50
Oprim in MVAr
Capacitive
Range
Inductive
Range
'
759
Operatinq losses
The SVC losses are evaluated according to the following
formula.
LOSS-Cost = $Cl x A + $C2 x B + $C3 x C
A, B, C
$Cl, $C2, $C3
The TCR reactors consists of two coils per phase installed in a double stack arrangement. Reactors for the
TSC are installed side by side. The filter arrangement
consists of two double tuned filters (DF). The first is tuned
to the 3rd and 5th harmonics and the second is tuned to
the 7th and ll.5th harmonics. The second DF includes a
resistance to achieve a high pass characteristic for the
higher harmonics.
Filter branches are tuned very accurately to keep the
harmonic distortion to a minimum and within specified
limits. Filter reactors have been designed with taps to
enable the inductance to be adjusted. This allows initial
mistuning due to reactor and capacitor manufacturing
tolerances to be compensated. Filter reactors are installed
in a triple stack arrangement. Hence, it is very important to
consider the influence of mutual coupling between coils to
achieve proper tuning. More information about the filter
design procedure is given in the Filter Design section.
Losses
1/F100
Ind.
k
Filters
Physical Layout
760
DesiQncalculations for the thyristor valves
49.7kV.
- 25 kV1
- 10 kA
,Water
- 22.5 kA
15.8 kV
T
20kVL
-- 10
kA capacitor voltage
-24.4kV
+\
capacitor current,
Side View
i30.1 kV
22.5 kA
Thyristor electronics
tubes
-29.0kV'
20 kV
10 kAr
valve voltage
25 kV
40 kV
4k q
-valve current AB
n rq
wv
valve voltage AB
nubber c a p a c i t
Water Cooled ,
snubber r e s i s t
9.35 kA
valve voltage CA
761
- range of generation
- range of load
- various steps of HVDC compensation
- system configuration (lines out).
equiv.
Fig. 11: Test results of the TCR valve type test
(DC trapped current)
Filter desiqn
Filter design is one of the most important steps in the
SVC design process. The first step in proper filter design
must ensure that the specified distortion limits are not
exceeded. The second step in filter design is to ensure
I v TCR
762
assumed. Afterwards a two double tuned filter arrangement
had to be selected, but the total fundamental power for the
filter branch was not changed.
The worst resonance condition between the network
impedance boundary and the harmonic filters was
assumed for the calculation of the individual harmonic
voltage distortion. Harmonic voltage distortion was also
computed with the network circuit open. The total harmonic
distortion (THD) was computed with the two highest
individual harmonic distortion values from the worst case
network resonance conditions and the remaining harmonic
distortions determined with the network open circuited.
This yields to the worst possible THD results.
Harnnonic performance is based on:
Nominal system voltage
Maximum initial mistuning due to tolerances
Detuning according temperature range
Assuming m a . magnitudes of TCR harmonic current
independant on firing angle
Negative sequence voltage content which gives rise
to generation of triple harmonics outside the delta
Firing angle unsymmetry which results in generation
of even harmonics
Loss of capacitor units of up to alarm level
Operating ranges of the TCR
Rating calculations for the filter components are done
seperately from the performance calculations. They are
based on similar conditions as above with the addition that
the following conditions are imposed:
- SVC energization
- Three phase system fault and voltage recovery.
CONCLUSION
A Static Var Compensator meeting the, -50 MVAr to
REFERENCES
G.Thumm, H.Tyll, A Closer Look at Thyristors in
SVC applications, Siemens Energy and Automation,
Vol. 1 pp. 12-17, 1989
B. Endres, G. Thiele, I. Bonfanti, G. Testi, Design
and Operational Testing on Thyristor Modules for the
SVC Kemps Creek, IEEE Transaction on Power
Delivery, Vol. 5, No 3, July 1990, pp. 1321-1328
W.Baver. K. H. Kruaer. D. Povh. B. Kulicke. Studies
for HVDC and SVC Using the NETOMAC Digital
Program System, IEEE I CSEE Joint conference on
High Voltane Transmission Systems in China, 1987,
Paper 873C-32
H. Tyll, K. Leowald, F. Labrenz, D. Mader, Special
Features of the Control Svstem of the Brushv Hill
SVC , Canadian Electrical Association, Power Sistem
Planning and Operation Section, Spring meeting,
Toronto 1989
kV
Fig. 14: Voltage and current stresses of the components
in the parallel circuit of DF 3 / 5
763
BIOGRAFIES
William H. ( Bill ) Elliott was born in Bird
City, KS on June 1, 1942. He received a
bachelor of sience degree in electrical
engineering
from
Kansas
State
University, Manhattan, Kansas in 1965.
He joined Southwestern Public Service,
Amarillo, TX in 1965. Mr. Elliotts
activities have been in the field of
system and transmission operation,
system
engineering and planning.
-~
Currently he is working as Principal
Engineer in Electrical Operations. Mr. Elliott is member of
the Institute of Electrical & Electronic Engineers (IEEE), the
Texas Society of Professional Engineers ( TSPE ) and the
National Society of Professional Engineers ( NSPE ).
Klaus Habur was born in Furth, Bavaria,
Federal Republic of Germany on April 8,
1952. He received his education at the
Ohm-PolytechnikumiNurnbergand at the
DAG-TechnikumMlurzburg. He joined
Siemens AG 1980 as a design engineer
for electrochemical plants. Previous to
this work, he was with a consulting
engineers company. In 1985 he joined
the Reactive Power Compensation Sales
Department and worked as a project
engineer and project manager for various SVC projects.
Gabriele Huesmann was born in
Munster, Westfalia, Federal Republic of
Germany on March 18, 1963. She joined
Siemens in 1982 and received an
education as engineers assistant. After
two years work in the Transportation
Systems department, she joined the
network planning department. Since
1986 she is active in the field of
programming, SVC design and harmonic
system analysis.
Keith B. Stump was born in Richmond,
Indiana, on February 12, 1941. He
received a bachelor of Science de ree
in electrical engineering from 8hio
University in 1963, and a Master of
Science degree in electrical engineering
from Purdue University in 1965. He was
employed by Allis-Chalmers Corp. in
Milwaukee, WI, from 1965 through 1977.
He then transferred to Siemens-Allis,
Inc. in 1978 which became Siemens
Energy &Automation, Inc., Atlanta, GA. Mr. Stump is
currently working in the Power Systems Technology
department in the area of system simulation and analysis.
Mr. Stump is a member of the IEEE Power Engineering
Society and vice chairman of the IEEE Surge Protective
Devices Committee.