Models V3409, V3410
40.16
Standard Spray
Horizontal Sidewall
and Recessed Horizontal Sidewall
Technical Specifications:
Models: V3409, V3410
Style: Horizontal Sidewall
Nominal Orifice Size: 17/ 32"/14 mm
K Factor: 8.0 Imp./11.5 S.I.1
Nominal Thread Size: 3/4"/20 mm NPT
Max. Working Pressure: 175 psi/1200 kPa
Horizontal Sidewall
(V3409 and V3410)
Approvals/Listings:
For K-Factor when pressure is measured in Bar, multiply S.I. units by 10.0.
Product Description:
These Model V34, standard spray horizontal sidewall
sprinklers are designed to produce large discharge
capacity in a crescent-shaped pattern for installation
along or under a beam or ceiling. It is cast with a
hex-shaped wrench boss to allow easy tightening from
many angles, reducing assembly effort. This sprinkler
is available in various temperature ratings (see chart on
page 3) and finishes to meet many design requirements.
Coverage
For coverage area and sprinkler placement, refer to
NFPA 13 or applicable standard.
Exaggerated
for clarity
Exaggerated
for clarity
Job/Owner
Engineer
System No.
Spec Section
Location
Paragraph
Contractor
Approved
Submitted By
Date
Date
Material Specifications:
Horizontal Deflector: Bronze per UNS C22000
Installation Wrench:
Recessed: V34
Finishes:
Plain Brass
Chrome plated
Seal:
White painted3
Teflon2
tape
Custom painted3
victaulic.com
APPROVALS/LISTINGS
V3409
17/32
14
8.0
11.5
Standard
V3409
17/32
14
8.0
11.5
Standard
V3410
17/32
14
8.0
11.5
Quick
V3410
17/32
14
8.0
11.5
Quick
Horizontal Sidewall
Recessed HSW
Up to 3/4" Adjustment
Horizontal Sidewall
Recessed HSW
Up to 3/4" Adjustment
F/C
cULus
135F/57C
155F/68C
175F/79C
200F/93C
286F/141C
360F/182C
135F/57C
175F/79C
200F/93C
135F/57C
155F/68C
175F/79C
200F/93C
286F/141C
135F/57C
175F/79C
200F/93C
NYC/MEA # 62-99-E
135F/57C
155F/68C
175F/79C
200F/93C
286F/141C
360F/182C
135F/57C
175F/79C
200F/93C
135F/57C
155F/68C
175F/79C
200F/93C
286F/141C
135F/57C
175F/79C
200F/93C
CSFM # 7690-0531:112
135F/57C
155F/68C
175F/79C
200F/93C
286F/141C
360F/182C
135F/57C
175F/79C
200F/93C
135F/57C
155F/68C
175F/79C
200F/93C
286F/141C
135F/57C
175F/79C
200F/93C
5 For
victaulic.com
1516"
33 mm
916"/
14 mm
516"/
8 mm
1516"
24 mm
238"
60 mm
158"
41 mm
58"/16 mm
Finished Ceiling
4 12"/102 305 mm
Per NFPA
2"/51 mm
Min. Hole
Finished Surface
victaulic.com
Finished Ceiling
4 12"/102 305 mm
Per NFPA
238"/60 mm
Max. Hole
2"/51 mm
Min. Hole
21516"
75 mm
Finished Surface
Typical Wall
Typical Wall
MAXIMUM EXTENSION
3 /4"
138"
35 mm
MAXIMUM RECESS
238"/60 mm
Max. Hole
2,4 m
10'
3,0 m
8'
2,4 m
6'
1,8 m
6'
1,8 m
Distribution Patterns:
4'
1,2 m
6'
Models
V3410
1,8 V3409,
m
4'
m
K8.0 Standard Horizontal Sidewall and Recessed Horizontal 1,2
Sidewall
Distribution Patterns Trajectory
4'
1,2 m
2'
0,6 m
10'
3.0m
2'
0,6 m
8'
2.4m
4'
1.2m
2'
0,6 m
4' 7 psi
1,248
mkPa
6'
1,8 m
6'
1,8 m
8'
2,4 m
14'
4,3 m
4'
1,2 m
6'
1,8 m
8'
2,4 m
14'
4,3 m
30 psi
207 kPa
10'
3,0 m
2'
0.6m
4'
1.2m
6'
1.8m
8'
2.4m
10'
3.0m
12'
3.7m
15 psi
103 kPa
14'
4.3m
16'
4.9m
18'
5.5m
20'
6.1m
10'
3,0 m
10'
26'
7.9m
28'
8.5m
8'
2,4 m
30 psi 8'
2,4kPa
m
207
6'
1,8 m
0'
8'
2,4 m
4' 7 psi
1,248
m kPa
2'
0,6 m
30 psi
207 kPa
7 psi
48 kPa
2'
0,6 m
15 psi
103 kPa
7 psi
48 kPa
2'
0.6m
6'
1.8m
2'
0,6 m
8'
10'
12'
14' 6' 16'
18'
2.4m 3.0m 3.7m 4.3m
1,8 m 4.9m 5.5m
20'
22'
6.1m 6.7m
24'
26'
7.3m 4'
7.9m
4'
1.2m
8'
2.4m
10'
3.0m
2'
0,6 m
7 psi
48 kPa
12'
3.7m
2'
0,6 m
2'
0,6 m
2'
0,6 m
6'
1.8m
28'
8.5m
1,2 m
4'
1,2 m
2'
0.6m
4'
1,2 m
4' 7 psi
1,248
mkPa
15 psi
103 kPa
6'
1,8 m
2'
0,6 m
8'
2,4 m
4' 7 psi
1,248
m kPa
6'
1,8 m
2'
0,6 m
8'
2,4 m
14'
4,3 m
4'
1,2 m
6'
1,8 m
30 psi
207 kPa
14'
4.3m
16'
4.9m
18'
5.5m
7 psi
48 kPa
NOTES:
15 psi
103 kPa
30 psi
207 kPa
victaulic.com
8'
2,4 m
14'
4,3 m
Available Wrenches:
Maximum
Victaulic
Nominal
Ambient
Part
Temperature Temperature
Identification
Rating
Allowed
Glass
Bulb
Color
Ordinary
135F/57C
100F/38C
Orange
Ordinary
155F/68C
100F/38C
Red
Intermediate
175F/79C
150F/65C
Yellow
Intermediate
200F/93C
150F/65C
Green
High
286F/141C 225F7/107C
Extra High 6
360F/182C
300F/149C
Mauve
Open
No Bulb
V34
Recessed
V34
Open End
No escutcheon
With escutcheon
Blue
WARNING
Always read and understand installation, care, and maintenance instructions, supplied with each box of sprinklers, before proceeding with installation of any sprinklers.
Always wear safety glasses and foot protection.
Depressurize and drain the piping system before attempting to install, remove, or adjust any Victaulic piping
products.
Installation rules, especially those governing obstruction, must be strictly followed.
Painting, plating, or any re-coating of sprinklers (other than that supplied by Victaulic) is not allowed.
Failure to follow these instructions could result in serious personal injury and/or property damage.
The owner is responsible for maintaining the fire protection system and devices in proper operating condition. For
minimum maintenance and inspection requirements, refer to the current National Fire Protection Association pamphlet that describes care and maintenance of sprinkler systems. In addition, the authority having jurisdiction may
have additional maintenance, testing, and inspection requirements that must be followed.
If you need additional copies of this publication, or if you have any questions about the safe installation of this
product, contact Victaulic World Headquarters: P.O. Box 31, Easton, Pennsylvania 18044-0031 USA, Telephone:
001-610-559-3300.
Installation
Reference should always be made to the I-40 Victaulic FireLock Automatic Sprinklers
Installation and Maintenance Sheet for the product you are installing. This installation sheet
is included with each shipment of Victaulic products for complete installation and assembly
data, and is available in PDF format on our website at victaulic.com.
Note
This product shall be manufactured by Victaulic or to Victaulic specifications. All products
to be installed in accordance with current Victaulic installation/assembly instructions.
Victaulic reserves the right to change product specifications, designs and standard
equipment without notice and without incurring obligations.
Warranty
Refer to the Warranty section of the current Price List or contact Victaulic for details.
Trademarks
Victaulic and FireLock are registered trademarks of Victaulic Company.
victaulic.com