GENERAL NOTES

1.

Orientation

(a) Buildings should be oriented preferably N-S so as to allow maximum light and
ventilation inside. Keeping in view the wind direction and Vassthu if desired by the
users.
(b) Care should be taken to avoid direct glare of sunlight as far as possible.
(c) Light should preferably come from the NORTH in school bldg, workshops,
laboratories or any building requiring more intensity of light.
(d) For storage accn / hangers polycarbonate sheets should be used for natural
light..
(e) The layout/siting should be in conformity of the approved Zonal plan/master plan.

2.

Plinth Level

(a) Plinth of the buildings should be decided in relation with the adjoining roads,
preferably higher than the road level so as to avoid siting of the bldgs in a low lying
area. As general principle the plinth height will be kept 45 cm from av GL.
(b) The cutting and filling of the ground should be judiciously decided, keeping
economy in view possibility of stepping of buildings to be fully explored in a places
where ground is sloping.

3.

Chajjas/Sun Shades

(a)
Sun breakers/louvers should be provided especially on the western side of
reduce heat and specifically at places where air conditioning is required.
(b) Sunken windows may be provided wherever feasible
(c) Chajjas should be sloping downwards and should extend by 100mm (minimum)
on both sides of the windows

ZONAL SPECIFICATIONS

CE (AF) WAC PALAM

(d)
At the junctions of chajjas and walls covering shall be provided in cm (1:3) with
admixture of WPC.
(e)

Slope of 1 in 30 shall be provided on upper sides of chajjas to avoid seepage

(f)
Upper sides of chajjas shall be finished smooth in cm 1:3 with admixture of
WPC. This operation shall be done during plastering stage.
(g) Width of Chajjas should be 550/500/ 450mm for the Ground Floor, First Floor,
Second Floor etc respectively beginning from ground floor to avoid dripping from
Chajjas of higher storeys.
4.

Porch/Portico

(a) Proper care should be taken while designing Porch/Portico. The minimum size
should be 3.6m x 5m according to the size of the building and free movement of
vehicles.

5.

Roof

Roof will be non accessible & without parapet unless specifically catered for in BOO
or due to technical reqmt. The roof will be laid on slope as under
(i) Span upto 4.0 m
- 1:40
(ii) Span more than 4.0 m
- 1:60

6.

Groove in Plaster

Groove in plaster will be provided at the junction of bk work & RCC beam/ column.

7.

Form works

Form work shall be of steel plates. Steel scaffolding will be used. No wooden
scaffolding of timber/ ballies will be used.

5.

General Features

(a) Rain water pipes should be avoided in front and if provided be concealed as far
as possible. Rain water pipes will not be concealed in walls/ columns. They will be
concealed in separate casing of bk/RCC
(b) PCC drains wherever provided in front of the buildings should be covered to give
a neat appearance.

ZONAL SPECIFICATIONS

-2-

CE (AF) WAC PALAM

(c) Long monotonous facades should be avoided, but if provided, should be broken
by off sets and different surface finishes.
(d) Entrance Halls, Lobbies, Foyers should be planned to enhance the grandeur of
the buildings like HQ bldgs, Offrs Mess & other impt bldgs as decided at board stage.
(e)
Buildings should be planned to incorporate the latest architectural features
including flower boxes/local materials/local Architecture to provide a distinct identity.
(f) Roof should be laid in slope .Roof projections should be 600mm all around. If no
windows are provided on either side , 300mm roof projection will be given. Roof with
parapet can be planned if reqd for architecture features.
(g) Staircase should always be planned in the clock wise direction. Width of the stair
case & location will be based on NBC.
(h) Window cills wherever provided/feasible should be finished with Kota stone/PCC
(j) Powder coated/colour GI pipe/Aluminium railing to be provided wherever feasible
(k) Ventilation and lighting in Kitchens/toilets should be planned in such a way so
that foul smell/odours to escape easily and this can be done by providing
window/ventilators at the proper place and of proper size.
(l) Shaft should be of adequate size for a man to work comfortably in case of repairs
and cutouts to be provided in the facades to provide good air and circulation and
ventilation
(m)
Heights/locations of fitting and fixtures in kitchen/toilets to be provided
judiciously to facilitate easy movement.

ZONAL SPECIFICATIONS

-3-

CE (AF) WAC PALAM

6.

Colour Scheme

(a) Colour schemes provided for internal/external walls should be pleasing and
samples must be put on the walls before doing the finishes. Ext colour scheme will be
followed as per stn colour scheme.
(b) Colours likely to fade in short duration should be avoided.
(c) Colours preferably should be matched in contrast to give pleasing appearance,
Pale yellow and Brick Red/Terracotta combination to be avoided.
(d) For impt buildings, the external finish may be one of the following:(i) Grit Finish
(ii) Dholpur stone/Red Stone
(iiii) Acrylic finish

7.

Single living Accn

(a) Partition in cubicals to be of Gyp board/ calcium silicate.


(b) Stailess steel wash hand basin to be provided.

8.

Stair case Railing

No PVC hand rail will be provided in adm accn/ Offrs Mess/ Offrs living .

ZONAL SPECIFICATIONS

-4-

CE (AF) WAC PALAM

ZONAL DATA
1.

Geographical Situation
(a)
(b)
(c)
(d)

2.

Plains and semi-deserts.


220M above MSL.
Latitude
Longitude

28 to 31
73 to 77

20cm
60cm
50cm
100cm

12.6 cm
23.3 cm
25cm

Rain fall
(a)

Average yearly
(i)
(ii)
(iii)
(iv)

(b)

Bikaner Area
Chandigarh Area
Palam Area
Ambala Area

Max rainfall recorded in last 15 years (in 24 hrs)


(i)
(ii)
(iii)

Bikaner
Palam
Chandigarh

(c)

Incidence of hail storm/max


velocity.

Not very common 160 Km/hour

(c)

Max size of hail experienced


in the area.

2.5 cm.

ZONAL SPECIFICATIONS

-5-

CE (AF) WAC PALAM

3.

Weather conditions

4.

Temperature
(a)
(b)

5.

6.

Extreme (Hot and cold)

42-50o C
1-6 o C

Maximum temperature in the year


Minimum temperature in the year

Duration of seasons ( in a year)

From

To

(a)
(b)
(c )

Summer season
Winter season
Rainy season

Apr
Oct
Jul

Jun
Mar
Sep

(a)

Duration of prevailing wind

Jan to Mar
Apr to Jun
Jul to Sep
Oct to Dec

(b)

Normal velocity of wind

Wind

(i)
(ii)
(iii)

Bikaner
Ambala/Chandigarh
Palam

30 to 50 Km per hour
30 to 35 Km per hour
10 to 20 Km per hour

(c )

Maximum velocity of wind

160 Km per hour

(d)

Max velocity of storm in 15 years

160 Km per hour

ZONAL SPECIFICATIONS

SE to NW
W to E
SE to NW
N to S

-6-

CE (AF) WAC PALAM

(e)
7.

Nature of storm with rains/without rains/with snow.

With and without rains

Seismic Zone
(a)
(b)

Bikaner/Nal/Suratgarh
All other Stns

8.

Snow fall ( for snow bound areas only)

9.

Water Table below GI


(a)

Bikaner
Chandigarh
Palam

8 to 120 Meter
15 to 18 Meter
7 to 30 Meter

During Rainy Season


(i)
(ii)
(ii)

Bikaner
Chandigarh
Palam

10.

Water Quality

11.

Soil
(a)

Not applicable

During Dry Season


(i)
(ii)
(iii)

(b)

III
IV

4 to 120 Meter
13 to 16 Meter
4 to 25 Meter
Potable except for Nal and Bikaner where it is saline.

Type of soils/rocks met within excavation.


(i)

Bikaner

ZONAL SPECIFICATIONS

Sandy/Silty/Clayey

-7-

CE (AF) WAC PALAM

(ii)
(iii)
(iv)

12.

Chandigarh
Palam
Ambala Area

Sandy/Clayey
Gravel/Rocks/Clayey
Silty Sand

(b)

Soil used for filling in foundation/floors.

Ordinary soil.

(c )

Soil used for filling in formation of Roads/berms.

Ordinary soil.

(d)

Behavior of soil with rise in moisture content.

Becomes soft and plastic.

(e)

Maximum dry density achieved at OMC.

1680 to 2100 Kg/Cum

(f)

Bearing capacity of soil in dry and saturated condition.6 to 15 Ton/Sq metre

(g)

Angle of repose of soil.

25 to 30 deg.

(h)

Soil used in Mud Phuska for water proofing treatment.

Clayey soil.

(j)

Soil strata upto depth of 10 metre below ground

Sandy/Clayey/gravel/Rocks

Materials locally available


(a)

Brunt clay Bricks

Crushing strength of bricks Minimum 100


Kg/Sq.cm for all places except Bikaner and Nal for
Bikaner and Nal minimum crushing strength of 35 Kg/Sq
cm.

(b)

Fly Ash bricks

Crushing strength of bricks Minimum 100


Kg/Sq.cm

ZONAL SPECIFICATIONS

-8-

CE (AF) WAC PALAM

Distance from thermal power house:(a)


Palam
(b)
Chandi Nagar
(c )
Gurgaon/ Rajokri/Dhansa (d)
Ambala
(e)
Patiala
(f)
Halwara
(g)
Barnala
(h)
Sarwawa
(j)
Chandigarh/ Kasuli
(k)
Adampur
(l)
Amritsar
(m)
Sirsa
(n)
Suratgarh
(o)
Bikaner/Nal
(p)
Bisiana
13.

<100 Km
<100 Km
<100 Km
>100 Km
>100 Km
>100 Km
>100 Km
>100 Km
<100 Km
>100 Km
>100 Km
>100 Km
<100 km
>100 km
<100 km

Degree of insect infestation


(a)

White ants/termite

(b)

Mosquitoes

-do-

(c)

Flies

-do-

ZONAL SPECIFICATIONS

Mild to high

-9-

CE (AF) WAC PALAM

Building Work
Sl
No
1
1

Item of work

Specification

Stns

Remarks

Pre-construction anti termite treatment will be


provided to foundation trenches, column pits,
filling under floor, junction of walls & floor and soil
along external perimeter for building as per
clause 3.26 perimeter of building. of SSR 2004
and IS 6313 Part I to II. In case of pile
foundations, anti termite treatment shall be
carried out to back fill and under floors, perimeter
of building.

All Stns

Anti termite
treatment

Post anti termite treatment will be provided to


building where ever reqd as per SSR 2004 and
IS 6313 Part III.
Chemical for ATT will be Chloropryophose or
Lindane ( EC 20)

(a) Treatment will be got done from


specialist agency .The agency should
be the member of the Pest Control
Association of India.
(b) In following accn anti termite
treatment will not be carried out
(i) A & B vehicles garages, repair
bays, apron/ hard standing, ramps,
Insp pits etc.
(ii) Incinerator Sentry boxes/ Dhobi
Ghat Open shed where no timber is
used.
(iii) RCC reservoirs/ OHT
c) The chemical used for Anti termite
treatment should be got tested from
National Test House Alipore Calcutta or
any other approved test house/
laboratories.
(d) For detailed instructions on
antitermite treatment E-in-Cs Branch TI
No
6-10/1973
&
subsequent
amendments be referred.

ZONAL SPECIFICATIONS

- 10 -

CE (AF) WAC PALAM

1
2.

Foundation
(i) Sub Base

Lean cement concrete 1:4:8 type D2 using


crushed/ broken stone aggregate .

(ii) Masonry in
foundation upto
plinth level

Stone masonry
RR stone masonry in 1: 6 brought to course at
every 60cm and as specified in SSR.

All
stations

Soil testing will be done for individual


site . Foundation will designed be as per
the the recommendation given in the
report.

Bk masonry
Bk work in CM (1:6) using bricks of class 75
compressive strength of 75 Kg/Sqm.

All
stations

Inside of the bk surface in contact with


the soil will be plastered in CM 1:4 &
given
two coats industrial type of
bitumen 85/25 @ 1.2 Kg/SM at following
Stns.
Ambala, Patiala, Halwara, Barnala.,
Adampur & Amritsar.

(iii) Column
Footing/Raft
foundation

RCC M-25( design mix) 20 mm crushed stone


aggregate.

(iv)Pile Foundation

RCC M-30 (design mix) using 20mm graded


crushed stone aggregate .

All
stations

(a) Pile fdn will be provided in areas with


high water table or low lying areas with
low bearing capacity.
(b) Initial load test as per IS-2911 on
piles shall be carried out to ascertain the
load carrying capacity of pile.

(c) Plinth
Beam/Band

RCC M-25 design mix using 20m graded


aggregate

All
stations

No DPC will be provided where plinth


beam /band in provided. PB/ Floor band
will be provided at floor level

ZONAL SPECIFICATIONS

- 11 -

All
stations

CE (AF) WAC PALAM

1.

3.

Damp proof
Course

4.

Plinth Protection

5.

Super Structure
(a) Brick Masonry

(b) RCC work

ZONAL SPECIFICATIONS

40mm thick PCC (1:2:4) with 12.5mm stone


aggregate using integral water proofing
compound as per manufacturers instructions
over. A coat of polymer modified bitumen @
1.5kg/sqm shall be applied over PCC.

All
stations

Polyethylene sheet 100 micron th will be provided Ambala,


over DPC
ASR,
Adampur,
Halwara,
Patiala,
Barnala
50 mm thick 750 mm wide PCC M15 ( Nominal All
Mix) over 100 mm thick PCC 1:4:8 type E2 using stations
40mm stone aggregate .

Fire Clay bks


Bk work in CM (1:6) using bricks of class for 75
(compressive strength of 75Kg/Sqm)
Fly Ash Bks:- Fly Ash Bricks in cement mortar
1:6. The bricks shall be uniform in shape and
regular corners of class 75.(compressive strength
of 75Kg/Sqm)
All RCC wk for structural members such as
roof/floor slab, lintels, Chajjas, beams, columns.
staircase, balcony etc shall be Grade M-25
design mix using 20 mm graded crushed stoned
aggregate .

- 12 -

5
(a) DPC shall be provided over full
width of all internal and external walls
except dwarf walls and partition walls
resting on the floor sub base.
(b)
DPC shall be provided in all
openings as per clause 5.42.1 of SSR
96 and shall be sunken at opening to
allow flooring.
(c) A moisture groove equal to thickness
of DPC will be provided at DPC level in
ext plaster
Plinth protection will be laid in a outward
slope of 1 in 12 and in alternate bays
not more than 2.5 m length. Joints
between two panels 12 mm wide will be
filled up with mix of 85/25 bitumen &
sand.

All
stations

All
stations

Fly ash bks will be conforming to IS


& to be used as per the location of the
stn with respect to the thermal power
station
Chajjas will be casted to a slope of 1:30
with rounded coving in 200mm plastered
in 1:4 using water proofing compound .

CE (AF) WAC PALAM

6.

(c) OHT

RCC M-30 (design mix) using 20mm graded


crushed stone

All
stations

(d) Service tank

RCC M-25 (design mix) using 20 mm graded


crushed stone

All
stations

(e) Partition Walls. Half brick walls in cement mortar 1:4 with 75 mm
th RCC M-15 band with 2 no 8 mm CTD bar at
every 4 th course for wall height of 1200 mm &
above.

All
stations

(f) Bk Isolated
Pillars/columns

BB wk in CM 1:4

All
stations

(g) Window cills

40 mm th PCC M15 ( Nominal Mix) with 20 mm


stone aggregate with a proj as per Arch drgs

All
stations

(h) Compound wall

Height up to 1.2M : 1 brick in CM 1:6


Height 1.2M
: as per actual design

All
stations

(j)Steel/structure

As per design requirements.

All
stations

Seismic Provisions Seismic provisions will be provided as IS 1893

ZONAL SPECIFICATIONS

- 13 -

Bks will be of class 75 with compressive


strength min 75 Kg/ Sq m as specified in
Appx A
- doTop of the window cills will be finished
with polished Kota stone.

All
stations

CE (AF) WAC PALAM

1
7.

2
Roof
(a) Flat Roof.

(b) Pent roof

RCC M-25 design mix using 20mm graded


crushed stone aggregate. RCC slab shall be laid All
flat /or to a slope of 1:40 and will be finished even stations
and fair using wooden float at the time of casting
without using extra cement/mortar.

(i) RCC M-25 design mix using


20 mm graded aggregate crushed aggregate.

(i) Roof projection shall be min 600 mm


with down ward fascia of 300 mm .
(ii) A layer of polythene sheet 150
micron thick shall be laid on finished flat
surface of shuttering before laying RCC
for roof slabs

All
stations

(ii) Corrugated/semi corrugated AC sheet of 6mm


thickness/CGI sheet/ Precoated MS sheets with
purling on trusses of steel/tubular/gable walls
( c) Reinforcement
for RCC

(i) MS round Gde I of IS 432 (Part I) 1986..

All
stations

Steel will be purchased from maim


producer or secondary producer as per
policy.

All
stations

(i) Before taking up roof treatment, RCC


roof slab shall be tested by ponding with
25mm height of water for 72 hours.

\(ii) High Yield Strength Deformed bars : IS


1786 1979.
(iii) TMT bar
8.

Water proofing
treatment
(i) Roof Slab

ZONAL SPECIFICATIONS

Water proofing treatment will be carried out as


under.
3

- 14 -

CE (AF) WAC PALAM

(a) Mud Phuska

(a) Apply primer conforming to IS: 3384-1965 @


0.50 kg/SM to the prepared surface, till the
surface is properly impregnated and the solvent
oil in primer shall be allowed to evaporate
completely.
(b) Apply hot bitumen straight run grade 30/40
(Grade S-35) conforming to IS: 73-1961 @ 0.70
kg/SM.

To be
provided
as per
reqmt

(ii) If no leakage/seepage noticed then


only further treatment to the roof will be
carried out. If seepage / leakage is
observed same will rectified by presser
grouting using polymers & cement ,\.
After the grouting , the roof will be
further tested for water tightness by
ponding the roof for 72 hrs.

(c) Polyethylene film 150 micron (heavy duty)


conforming to IS: 2508-1977, laid with over laps
bonded with cold cut back bitumen adhesive,
overlaps being not less than 150 mm. The film
shall be natural or black in colour.
(d) Apply semi-hot straight run bitumen grade
30/40 (Grade S-35) conforming to IS 73-1961 @
0.70 kg/SM over the Kraft paper and pasted on
the Polyethylene film.
(e) Blinding material, such as sand in dry
condition, @ 0.5 to 1 kg/SM shall be dusted over
the bitumen indicated in (e) above.
(g) Mud Phuska treatment min 50 mm and av th
so as to achieve desired slope . Mud Phuska to
be covered with 40mm thick brick tiles toping
grouted in CM 1:3 & pointed with CM 1:3 using
crude oil @5 % weight of cement as per SSR per

ZONAL SPECIFICATIONS

- 15 -

CE (AF) WAC PALAM

specified in Clause 11.26 on page 11.10 of SS


1991 Part I.
(h) Minimum 10 days curing of roof surface by
keeping surface wet, using gunny bags, or any
other method approved by GE
(b)APP Polymeric
Membrane

All Stns
(i) The surface will be painted with one coat of
primer conforming to IS 3488 @ 0.3 Kg/SM

(i) All Building


except garages of (ii) A layer of APP based polymeric membrane 3
all types
mm thick (min) and weighing not less than 3.0
kg/SM reinforced with polyester non woven mat
160GSM th. The membrane will be laid by torch
application. Side overlap of 75 mm & end
overlaps of 100 mm will be provided . The joints /
overlaps will be sealed with torch application. For
parapet the membrane will be taken upto 30 cm
& then inserted inside the parapet in a groove.
(iii) PCC padding in 1:2:4 type B0 av 50 mm th
will be laid to achieve a slope of 1:40 in case of
flat roof. The uniform thickness of 50 mm will be
provided in case roof is laid on slope.
(iv) 40 mm th bk tile to be laid in CM 1:6 & jointed
in CM 1:3 using crude oil @ 5 % of weight of
cement. over PCC padding.

ZONAL SPECIFICATIONS

- 16 -

CE (AF) WAC PALAM

(v) Covered fillet in PCC 1:2:4 type BO of radius


75 mm to be provided at junction of roof &
parapet.
(ii) Garages of all 15mm thick cement plaster 1:4 with WPC to be
types
laid over the RCC roof slab when the concrete is
green.
Terrace
(a) 10 mm thick cement plaster 1:4 with WPC to
be laid over the RCC roof slab when the concrete
is green.
(b) Polyethylene film 150 micron (heavy duty)
conforming to IS: 2508-1977, laid with over laps
bonded with cold cut back bitumen adhesive,
overlaps being not less than 150 mm. The film
shall be natural or black in colo
(c) Apply a uniform coat of blown graded
bitumen 85/25 at 1.20 kg/sqm conforming to IS
702 over a coat of primer at 0.70 kg/sqm over
cement plaster.
( c) 20-22 mm mm thick hydraulically pressed
factory made ISI marked cement/ Terrazo tiles
200x200mm or 230 x 230mm in size, over 20mm
thick screed in cement mortar 1:4 jointed and
pointed in CM 1:3, .

ZONAL SPECIFICATIONS

- 17 -

CE (AF) WAC PALAM

9.

Sunken Slab

Providing and laying water proofing treatment to All Stns


sunken portion of WCs, bathroom etc by applying
cement slurry mixed with Acrylic based polymer
modified cementitious composite compound
coating of make as approved in Technical
Instruction 5/2003 :-

5
RCC sunken slab shall be laid in slope
of 1:20 mixed with water proofing
compound and shall be tested for water
tightness by ponding of water for 72 hrs.

(i) 15mm thick plaster 1:4 cement sand mortar


with integral water proofing compound both on
floor and wall. The surface shall then be cured
and allowed to dry.
(ii) First layer of slurry of cement @ 0.488 kg/sqm
mixed with Acrylic based polymer modified
cementitious composite compound @ 0.253
kg/sqm. This layer will be allowed to air cure for
4 Hrs
(iii) Second layer of slurry of cement @ 0.242
kg/sqm mixed with Acrylic based polymer
modified cementitious composite compound @
0.126 kg/sqm. This layer will be allowed to air
cure for 4 hours followed with water curing for 48
hours.
(iv) The sunken portion shall be filled with lean
concrete 1:5:10 using bk aggregate.

ZONAL SPECIFICATIONS

- 18 -

CE (AF) WAC PALAM

1
10.

2
Flooring
(a) PCC Floor
(i) Domestic &
OTM

(i) Ground floor :- 40mm thick PCC M20 grade


( Nominal Mix) finished fair using extra cement
over 100 mm thick PCC 1:5 :10 sub base type E2
over rammed earth. Top layer shall be laid in
panels using 4mm thick and 38mm wide glass
dividing strips.

All
stations

(ii) First floor and above (floor over RCC slab)


40 mm thick PCC 1:2:4 type B-1 finished fair
using extra cement laid over floor slab. PCC to
be laid in panels using 4mm thick 38mm wide
glass dividing strips.
(ii) Garages
(a) Car/Scooter/
Cycles/ Motor
Cycle

75 mm thick PCC M20 grade( Nominal Mix)laid


in alternate panels over sub base of 100mm thick
PCC 1:5:10 type E-2.over rammed earth

(b) B Vehiclesone ton/ Three


Tonne/ Four Tonne

100 mm thick PCC M20 grade( Nominal Mix) laid


in alternate panels over 100 mm thick PCC
1:5:10 over rammed earth.

All
stations

(a) Expansion/construction/dummy
joints shall be provided as per design
considerations.
(b) Where ever higher water table is
encountered 150 mm hardcore below
sub base will be provided.

(c) Type C Veh


150 mm thick PCC M20 grade( Nominal Mix) laid
in alternate panels over 100 mm thick PCC
1:5:10 over rammed earth over 150 mm th hard
core.

ZONAL SPECIFICATIONS

- 19 -

CE (AF) WAC PALAM

(d ) Garages of
tracked vehicles.

Stone sets (granite/trap/basalt/ quartzite) 150 mm


thick laid and jointed in CM (1:3) over 20 mm
thick cement screed in CM (1:3) on 100 mm M 20
concrete (Nominal Mix) over 75 mm thick
compacted WBM on 150 mm thick boulder
soling.

(e) Storage accn

75 mm th PCC M20 ( Nominal Mix)with floor


hardner over 100 mm th PCC 1:5:10 Type E2
over rammed earth.

All
stations

(f) Hy duty
Industrial Flooring

20mm thick hardonite or other wear proof topping


over 30mm thick granolithic concrete over
150mm thick PCC 1:2:4 over 100 mm thick PCC
sub base1:4: 8 type D2 . or as per actual design.

All
stations

(b) Ceramic Tile


Flooring

(i) Ground Floor


Non skid ceramic tiles of 7 mm th laid over 15mm
thick screed in CM 1:4 over 25 mm thick PCC
M20 grade (Nominal Mix) over 100 mm th PCC
1:5:10 type E2
(ii) First floor and above
Non skid ceramic tiles of 7 mm th laid over
15mm thick screed in CM 1:4 over 20 mm thick
PCC M 20 grade ( Nominal Mix) using 12.50 mm
graded stone aggregates

ZONAL SPECIFICATIONS

- 20 -

The specification is for general type of


accn. In case of specific reqmt the floor
to be designed as per actual load reqmt.

be as under:All
stations

(i) Toilet/WC/Bath
(ii) Other places

- Grade III
- Grade IV

CE (AF) WAC PALAM

2
(c ) Vitrified Tile

(i) Ground Floor


Vitrified tile 10 -12 mm thick laid with 15mm thick
screed in CM 1:4 over 25 mm thick PCC M20
grade (Nominal Mix) on sub base of 100 mm
thick PCC 1: 5:10 type E2 .

5
At impt accn like MES IB, guest rooms,
& area as recommended by BOO
vitrified ceramic tile 10 mm th of size
60x60 cm or more will be provided

(ii) First Floor & above


Vitrified tile 10 mm thick laid with 15mm thick
screed in CM 1:4 over 20 mm thick
PCC M20 grade ( Nominal Mix) over
floor slab.
(d) Kota Stone
Flooring

(e) Marble
Flooring/ granite
flooring

ZONAL SPECIFICATIONS

(i) Ground Floor


All
18-20 mm thick mirror polished kota stone
stations
flooring set with neat cement slurry mixed with
colour to match the colour of stone, over 30mm
PCC M-20 (Nominal Mix) B1 over 100 mm thick
PCC 1:5:10 type E2.
(ii) First Floor & above
18-20 mm thick mirror polished kota stone
flooring set with neat cement slurry mixed with
colour to match the colour of stone, over 20 mm
PCC M20 grade ( Nominal Mix)

(i) Kota stone will be provided at


Entrance hall, passage, corridor,
verandah where heavy wear and tear
is likely to be there.
(ii) Pattern of Kota/ marble will be
provided in entrance hall Adm block /
Technical accn , Offrs Mess. , SNCOs
Mess etc.

(i) Ground Floor


20mm thick white marble stone flooring set with
neat cement slurry mixed with colour to match
the colour of stone, over 30mm PCC M20 grade (
Nominal Mix) over 100 mm thick PCC 1:5:10
type E2.

- 21 -

CE (AF) WAC PALAM

(ii) First Floor & above


18-20 mm thick mirror polished marble stone
flooring set with neat cement slurry mixed with
colour to match the colour of stone, over 20mm
PCC M20 grade ( Nominal Mix).
(f) Terrazzo
Flooring

(i) 20-22 mm thick factory made terrazzo tiles in All


white cement laid over 15 mm cement screed in stations
CM 1:4 set with neat white cement slurry mixed
with colour to match the colour of tile over 30mm
PCC M20 grade ( Nominal Mix) over 100 mm
thick PCC 1:5:10 type E2
(ii) First Floor & above
20-22 mm thick terrazzo tiles in white cement laid
over 15 mm cement screed in CM 1:4 set with
neat white cement slurry mixed with colour to
match the colour of tile over 20 mm PCC M20
grade ( Nominal Mix)

(g) Acid
Resistance
Flooring

20 mm thick acid Resistant tiles conforming to IS4457 laid over two coats of acid primer, screed
and mortar.

All
stations

(h) PVC Flooring.

2 mm th PVC floor laid over PCC floor with


adhesive.

All
stations

ZONAL SPECIFICATIONS

- 22 -

Tiles shall be provided keeping in view


the type/concentration of Acid and
quality of discharge as per
manufacturers instrns.

CE (AF) WAC PALAM

11.

(j) Floor for


mechanical
laundries

30mm thick granolithic concrete finished with


sodium silicate treatment as per SSR over 100
mm thick PCC 1:2:4 over 150mm thick hard
core.

All
stations

(k) Wk shop
Flooring

15 mm thick wear proof topping over 100 mm


PCC M20 ( Nominal Mix) laid in alternate bays
over 150 mm PCC 1:5:10 type E2 sub-base. Or
as per actual design.

All
stations

(l) Hospital flooring

As per user reqmt for diff locations in hospitals.

All
stations

Plaster/ Pointing
(a) Internal
Plaster

Plaster shall be finished fair and even without


using extra cement.
(i) Bk surface.
12 mm thick in CM 1:6 in one coat.
(ii) Stone masonry
15 mm thick in CM 1:6 in one coat

All
stations

(iii) All RCC surface not contiguous with bk wk


incl soffits of slab.
5mm thick in CM 1:4
Skirting/Dado : 15 mm thick CM 1:4

ZONAL SPECIFICATIONS

- 23 -

CE (AF) WAC PALAM

(iv) RCC Shelves and Projections


5mm thick plaster in CM 1:3
finished smooth.
(b) External
Plaster.

(i) Bk masonry
15mm thick in cement mortar in CM 1:4 mixed
with approved water proofing compound as per
manufacturers instns.

All
stations.

(ii) Stone masonry


20mm thick in two layers consisting of first layer
10mm thick in CM 1:4 and top layer 10 mm thick
in CM 1:6 mixed with water proofing compound
as per manufacturers instrns
(d) Bearing Plaster

20 mm thick in cm (1:4) over full width of bearing


with two layers of bitumen impregnated paper
conforming to IS-5134-1977.

All
stations

(e) Pointing

(i) Bk masonry
Keyed pointing in CM 1:3 .

All
stations.

Stone masonry
Pointing as per architectural requirement in CM
1:3.
12.

Skirting

ZONAL SPECIFICATIONS

150 mm high Skirting will be provided matching


with floor.

- 24 -

All
stations

CE (AF) WAC PALAM

1
13.

14.

2
Dado

Joinery
(i) Door Frame

Ceramic glazed Tile.


White/colored 7/5mm thick 300x200 mm size tile All
over 10mm thick screed in CM 1:3.
stations

Pressed Steel
Prefabricated pressed steel door
frames made out of 1.25 thick steel sheet as
per IS/4351 made to shape and filled with PCC
1:3:6 type C-0 in the core.

(ii) Door Shutter

Al doors will be provided at the entrance


of Adm block, MI room,Offrs Mess,
JCOs Mess etc or any specific places if
covered in BPs/AA.

ZONAL SPECIFICATIONS

All
stations

(i) Panel shutters


Factory made shutter 35 mm thick made as per
IS 1003 (1987) from second class HW treated as
per IS-1141. Panels shall be of 12 mm thick
BWP grade BWR ply wood .

- 25 -

To be provided in kitchen bath and


toilets of officers qtrs laboratories, hosp,
nitches over sinks/WHBs in sanitary
annexes, all toilets of OTM accn, Dining
Hall etc.

All
stations

Aluminum
Aluminum frame made from std box sec.
Timber.
Ist/IInd class hard wood

Teak wood shall be specified if surface


is to be polished.

All
stations .

CE (AF) WAC PALAM

(iii) Fly proof shutters


32/35 mm thick factory made fly proof door as
per IS 1003 (1987) from second class HW
treated as per IS-1141.
(ii) Flush door shutters
35 mm thick factory made flush door shutters
shall be solid core type with block board core &
shall conform to IS-2202 (Part-I) 1983. Plywood
face panels will be non-decorative (Commercial)
type or decorated type depending upon reqmt.
Shutters shall be internally lipped.

All
stations

Only Flush doors will be provided in all


accn to have better finish & quality.
Flush doors will be obtained from
reputed manufactures .

OR
Flush shutters as per IS:2202/made out of MDF
as per IS 12406 and IS 14587 .
(iii) PVC door - PVC doors will be of Solid foam
PVC doors of Rajshree Indore / Accura polytech
Ahmedabad with PVC door frame
(c) Window

(i)Box type Steel Windows factory fabricated /


Pre coated galvanized steel will be provided as
per drg .

To be provided in Bath/WC/ Toilets in all


accn

All
Stations

(i) No Z section windows will be


provided in original worksin any stns .
(ii) Thickness of anodizing over

ZONAL SPECIFICATIONS

- 26 -

CE (AF) WAC PALAM

(ii)Aluminum anodized/ power coated windows


will be provided in case of specific requirement
& if included in AA

aluminium will be 15 micron. Sections of


the aluminium window will be from
Indal/Hindalco/ Jindal.

(iii) UPVC windows can be provided as per arch


reqmt.

(iii) UPVC windows can also be


provided in technical accn/ single living /
Messes.

(d) Steel doors

Steel doors with angle iron frame with 1.0 mm


thick PBI sheet covering.

(e) Ward Robe


and cup board.

Cub Board & Ward Robe


(i) Frame
Second class hard wood locally available
(Hollock / Sal).

All Stns

For Stores, Kots,tradesman shop,


shopping complex etc.

All
Stations

(ii) Shutter
Flush door one side 25 mm thick made of
prelaminated particle bd conforming to IS12823. Gde I typeI. Core of the prelaminated
particle bd shall be wood based solid core flat
pressed three layered type I exterior grade with
phenol formaldehyde synthetic resin adhesive
BWP as per IS 3087.
(iii) Shelves
19 mm thick prelaminated particle board. One
side decorative.

ZONAL SPECIFICATIONS

- 27 -

CE (AF) WAC PALAM

2
(iii) Meat safe &
other items of
kitchen.

(aa) Frame. 2nd class hard wood


(ab) Shutters. 18 mm thick one side pre
laminated particleboard phenol formaldehyde
bonded exterior grade.

All stns

5
(i) Built in furniture shall be provided as
indicated and authorised in E-in-C
typical drawings.
(ii) In SM Barracks built in furniture i.e.
writing table & bookshelf shall be
provided as authorized vide GOI MOD
letter
No
65582/Q3/63)
policy-1)
1464/Do-II/D (Wks) dt 17 Oct 96.

15.

(iv) Kitchen sink/


Draining Board.

Stainless steel sink with or without draining board

All
stations

(v) Pelmet Box.

12 mm thick one side pre laminated particleboard


phenol formaldehyde bonded exterior grade
/MDF board 12 mm th with twak wood lipping 6
mm th for officers accn.

All
stations.

Decorative drapery rod will be provided


in Offrs Mess, SNCOs Mess & other
places .

i) 3/4/5 mm thick plain frosted/pin headed sheet


glass as per reqmt

All
stations

Frosted/figured glass shall be provided


in all windows/ ventilators of WC, bath
and toilets.

Glazing

ii) 5.5mm thick wired/sheet glass for window


panes/north light glazing in factories, workshop
and at other places where shock absorbing is
reqd.
iii) 5.5 mm heat absorbing coloured glass of
(calorex brand) of reqd thickness for AC rooms
(iv) Float glass for large glazing area.

ZONAL SPECIFICATIONS

- 28 -

CE (AF) WAC PALAM

(v) Double glass for sound proofing & heat


insulation

16

Mosquito proofing

SS wire mesh of wire dia 0.56 mm and


apertures of 1.16 mm.

17.

Guard Bars/Grills

(i) Window MS flat/square/round bars


embedded in PCC or fixed to steel/wooden
frames.
(ii) Ventilators Guard bars or wire netting fixed
to steel/wooden frames.

18

Iron Mongery

Butt Hinges Steel/Wrought iron fitting , pressed


steel but hinges(medium grade) for all buildings.

All
stations.
All
stations.

All
stations

Godrej type automatic locking


arrangement and safety chain should be
provided in main entrance door of all
md accn.

Door fittings Aluminum anodized fitting with


cadmium-coated screws.
Ball and catch . this will be of brass heavy duty
type.
19

Surface Finishes
(a) Internal

ZONAL SPECIFICATIONS

(a) OTM Accn


Walls surfaces.
(i) 2 coats of OBD over one coat wall care putty
except kitchen, store, toilets

- 29 -

All
stations

Hosp, Messes & other important


building shall be provided with plastic
emulsion paint as per authorisation.

CE (AF) WAC PALAM

Ceiling
Three coats of white wash as specified.
(b)Married Accn
Wall surfaces
(i) Offrs
2 coats of OBD over a coat of wall care putty on
walls
Ceiling
Three coats of white wash as specified

All
stations

All rooms except toilet & kitchen where


three coats of white wash will be
provided.

All
stations

(i) Purling and similar items etc, should


have two coats of wood preservatives
like creosote oil.

(ii)Other Md Accn
Two coats of colour wash over a coat of white
wash
Ceiling
Three coats of white wash as specified in all
accn.
Wood work
Two coats (under & finishing) of synthetic enamel
paint over a coat of primer.

(ii) Two coats of tar to wooden surfaces


in contact with or buried in concrete
earth/BB /stone masonry/Plaster.
Steel work including grills & quard bars.

All
stations

2 Coats of synthetic enamel paint over a coat of


red oxide primer

ZONAL SPECIFICATIONS

- 30 -

CE (AF) WAC PALAM

Cupboard & wardrobes


Two coats synthetic enamel paint on internal
plastered surface over a coat of primer
(b) External finish

Plastered/Pointed surfaces
(i) Two coats of cement base paints over a coat
of primer

All
stations
All
stations

Superior finish like grit wash, weather


proof paint will be provided if included in
AA

(ii) Two coats of colour wash over a coat of white


wash.

ZONAL SPECIFICATIONS

- 31 -

CE (AF) WAC PALAM

Internal Water Supply


1

General

All plumbing work including Kitchen/Toilets/WCs to be


carried out will be concealed

All Stns

Storage Tank

For Officers
Storage tank for each Md Qtr shall be 1000 ltrs cap
and for servant Qtrs shall be of 500 ltrs.

All Stns

(i) The inlet to service tanks for Md accn


will be 25 mm dia.
(ii) Water connection to WHB, WCs and
bath shall be from service tank. For
geyser separate water connection from
service tank to be given.

For JCOs/Hav/OR
Storage tank for each Qr shall be 750 ltrs per Qr.

(iii) PVC rotational moulded tank upto


1000 lit cap & RCC tank beyond 1000-lit
cap will be provided.
3

Kitchen

For Officers
Kitchen Sink tap shall be fed from the service tank
and the kitchen fresh water tap to be fed from direct
water riser.

All Stns

For JCOs/Hav/OR
Kitchen shall be fed from the direct rise and from the
service tank.

ZONAL SPECIFICATIONS

- 32 -

CE (AF) WAC PALAM

Water Meter

Pipe and
Fittings

Size of water meter for Officers and other paying


consumers shall be 25 mm dia.
All pipes for internal water supply shall be of mild
steel galvanized tubes (pipes) of medium grade as
per IS : 1239 (Part-I).

All Stns
All Stns

Fitting of GI Pipes shall be mild steel galvanised or


malleable cast iron pipe fitting galvanised as per IS1239 (Part-II) and IS-1879 (Part I to X).
6

Bib taps & stop


valves

Bib taps and stop valves shall be PTMT (ISI marked)


for JCO/OR Md accn & OTM accn except officers
mess , single officers qtrs, adm block, MI room.

Fancy type bib


tapes/
stop
cocks

Cast copper alloy nickel chromium plated fancy type


All Stns
fittings for Officers toilets, adm block, JCOS mess, MI
rooms & in other important bldgs, bib taps and stop
valves shall be of fancy type of cast copper alloy
nickel chromium plated conforming to IS 8931 and
as per clause 18.15 of SSR 1991 (Part-I).

Self closing

Self closing taps shall be of JAYCO or equivalent taps All Stns


pattern conforming to IS : 1711 and clauses 18.17 of
SSR 1991 (Part I)

ZONAL SPECIFICATIONS

- 33 -

All Stns

These will be provided only on specific


requirement.

CE (AF) WAC PALAM

10

Piller taps/
single
hole basin
mixer

(i) Pillar taps shall be with capstan head nickel


chromium plated conforming to IS : 1795 and clause
18.16 of SSR (Part I) 1991 except in officers toilets
and important bldgs, where pillar taps shall be fancy
type, conforming to IS 8934 and clause 18.16.1 of
SSR 1991 Part I.

All Stns

Single hole basin mixer will be


provided in offrs accn on WHB.

Shower rows will be provided with 45


cm chromium plated pipe.

(ii) In MH, SSQ and MI rooms pillar taps fancy type


with elbow handle shall be provided .
11

Shower Roses

Shower roses shall be of chromium plated brass ,


heavy pattern, suitable for 15 mm bore inlet.

All Stns

12

Non return
valves

Non return valves shall be, of high pressure, cast


copper alloy, suitable for 15 mm bore pipe except for
officers accn and important bldgs, where these shall
be cast copper alloy, chromium plated.

All Stns

Ball valve for


over head
tank.

These shall be of high pressure type with polythene


float, brass rod all as per IS : 1703 and clause 18.19
of SSR-1991 (Part-I)

All Stns

ZONAL SPECIFICATIONS

- 34 -

CE (AF) WAC PALAM

SANITARY FITTINGS/SEWAGE
1.

Flushing Cistern

PVC low level Flushing Cistern 10 /12.5 liters


capacity for n WC & 5 lit cap auto flushing cistern
for urinals.

All Stns

WC

EWC

All Stns

5
Color savitary fittings matching with
tile can be provided recommended
by BOO

White glazed pedestal pattern WC (for officers md


accn & offrs toilets in OTM accn) as per IS 2556
(part II) with black/ white plastic seat cover, low
down PVC flushing cistern 10/12.5 litres capacity
with accessories as mentioned
IWC
550 mm Orissa pattern IWC with low level PVC
flushing cistern 10/12.5 lit cap with all fittings in all
other accns
3

WHB

Oval type vitreous china WHB with 19 mm th


granite counter with 32 mm bore GI waste pipe / CP
bottle trap will be provided.

All Stns

Soil/ waste pipe

Centrifugal cast C.I. pipes marked with ISI 3989

All Stns

ZONAL SPECIFICATIONS

- 35 -

(i) All joints in soil & waste water


pipes shall be outside for easy
detection of leakage and repairs.
(ii) Lead joints for CI pipe under
floor, wall and concealed locations.

CE (AF) WAC PALAM

Rain Water pipe

PVC 100/150 mm bore pipe

All Stns

SGSW pipe

SGWG pipe Gde A

All Stns

Service Tank

HDPE/ RCC Service tanks conforming to relevant


IS shall be provided.

All Stns

5
All rainwater pipes will be encased I
RCC/ Bk work separetely
(i) HDPE tank upto 1000 liters cap.
Beyond 1000 liter RCC tank will be
used
(ii)HDPE rotational moulded tanks
Service tanks conforming to
relevant IS & IS marked will be
used.

Stack system

Single stack where sewage is carried and


discharged in river or treatment plant and double
stack where night soil is discharged to specific
tanks.

9.

PCC corbelling
over Nahani
Trap

PCC corbelling in the same specifications as of floor All Stns


shall be provided all around the raised Nahani trap
from floor.

ZONAL SPECIFICATIONS

- 36 -

All Stns

Nahani trap with long bodynwill be


used to avoid joint under the floor.

CE (AF) WAC PALAM

ROADS/ PATH
Ser
No
1

Item

Specification

Station

Remarks

(a) Soling

(i)150 mm (spread thickness) with broken


boulders or quarried stone interstices
filled, surface formed and rolled and
consolidated to required gradient and
camber.

All other stns

Type of aggregate will be as per


availability in the local area.

(b)WBM

150 mm th (compacted thickness) WBM in two


layers with coarse aggregate of grading 2 (63 to
40 mm size) for first layer & of grading 3 (50 to
20 mm size) for second layer spread, rolled and
consolidated to reqd gradient and camber .

All stns

Thickness of soling and WBM


may be increased
depending on
soil/conditions and traffic
load.

(c) Bituminous
premix carpet

Premix carpet 2.5 cm th consolidated thickness


with 0.34 cum of stone chippings mixed
with 23.9 Kg binder including sand seal
coat. The grading of the aggregate will
be as under:Sieve size
% age passing the
sieve
12.5 mm
100
10.0 mm
70-100
4.75 mm
20-40
2.36 mm
05-20
75 micron
0-04

All stns

Bituminous carpet will be laid


using paver & hot mixed plant

ZONAL SPECIFICATIONS

- 37 -

CE (AF) WAC PALAM

(d) Asphaltic
Concrete
Ser
No

Item

Bituminous semi dense asphaltic conc 25 mm /


30mm consolidated with 5.5% binder
content(80/100 straight run bitumen)
Specification

Station

(d) Edging

Bk/Stone Edging

All stns

(e) Kerb Stone

PCC M25 grade

All Stns

(f) Foot Path/ Hard


standing

PCC Path

Remarks

.
(i) PCC M 20( Nominal Mix) 75/ 100 mm thick
laid over 100 mm th stone hard core. Top of the
concrete will be chequered finish.

All stns

(ii) Interlocking Pavers 50 mm th M 35 grade


over 100 mm th PCC 1:5:10 type E2
(iii) PCC chequered tile 20-22 mm th of size
250x250 mm laid over 20 mm th screed 1:4
over PCC 1:4:8 type D2.
(iv) Designers tile like Ultra of different sizes as
per reqmt laid over 20 mm th screed 1:4 over
PCC 1:4:8 type D2.

ZONAL SPECIFICATIONS

- 38 -

CE (AF) WAC PALAM

External Water Supply


1

Pipes

Pipes of sizes above 80 mm bore shall be ductile


iron as per IS-8329 for pipes and IS-9523 for fittings
and upto 80 mm of galvanized iron medium quality
GI pipes as per IS-1239 Part I.

All Stns

C.I Fittings

These shall be as per IS-1538 (Part to XXIII).

-do-

D.I Fittings

These shall be as per IS- 9523.

-do-

Sluice valve

Sluice valves shall be as per IS-780

-do-

Laying/Jointing of pipes

Pipes shall be laid and jointed as specified in SSR


and IS-3114.

-do-

Water supply system

The system shall conform to IS-2065 and manual on


water supply and treatment of Min of Wks and
Housing.

-do-

7.

Pressure testing

Hydraulic pressure testing shall be carried as per


SSR Part I clause 18.48.7 and 18.50.4/manual of
water and treatment of Min of Wks & Housing.

-do-

ZONAL SPECIFICATIONS

- 39 -

CE (AF) WAC PALAM

Internal Electric Supply


Ser
No
.

Item
Wiring

Specification
(a) All wiring will be concealed in PVC conduit.

Station

Remarks

All stns

(b) Power wiring shall be kept separate & distinct


from light wiring i.e. cables for power and
light/fan/5A sockets outlets shall be drawn in
separate conduits
(c) All conductor will be of copper.The minimum
sizes of aluminum conductor cables shall be as
under :(i) Lighting and fan circuit
cables
(ii) Power circuit cables
(iii) Sub main cables

- 1.5 sq mm
- 2.50sq mm
- 4 sq mm/6 Sq mm

However higher sizes of cable shall be determined


as per actual load.
(d) Each lighting/fan sub circuit shall have not more
than eight points of lights/fans/5A socket outlets.
Load on each sub-circuit shall be limited to 800 W.
Each power sub-circuit shall not have more than two
outlets.

ZONAL SPECIFICATIONS

- 40 -

CE (AF) WAC PALAM

(f) Flame proof electrical wiring shall be provided in


Magazine bldg/Explosive stores along with flame
proof fittings and control switches.
(g) Multi stranded aluminum conductor cables should
be provided.
(h) Terminal boxes shall be of pressed steel of
1.6mm thick and shall be sunk in wall and be
covered with bakelite sheet 3 mm thick. These shall
be earthed.
(k) For wiring explosive bldgs, solid drawn rigid steel
electric resistant welded (ERW) conduit shall be
provided.
(j) For conduit wiring, ISI marked PVC conduit of
19mm shall be used . MS conduit should only be
used where there is extreme climatic variation i.e (+)
55 to (-) 4C and where there is likely hood of
damage to PVC conduit while laying in R.C.C
members
(l) In case of batten wiring where vertical run of
batten is to be provided upto one meter from FFL,
concealed conduit wiring shall be used instead of
batten wiring.
(m) In case of surface wiring the portion covering in
ceiling should be concealed in conduit. The conduit
shall be laid along with the casting of roof.

ZONAL SPECIFICATIONS

- 41 -

CE (AF) WAC PALAM

Switches

Piano type switches (ISI marked) shall be used.

Multi Purpose Socket


outlets

Earthing

5 Amp plug socket shall be 2 pin and 3 pin type. 15


All stns
Amps plug socket shall be 3 pin 5 Amps and 3 pin 15
Amps type. All socket out lets shall be fixed at
height of 1.2 m from floor level.
Earthing shall comply with IS-3043 and as per
All stns
clause 19.137 to 19.146 and as shown in electrical
plate of SSR Part I 1991.

Isolators, MCBs and DBs

Meter Boxes/Switch
Boxes

7.

Miscellaneous

Isolators and MCBs shall be of suitable rating to


match the circuit requirement. Distribution boards
shall be factory made.
MS sheet type meter boxes/switch boxes shall be
used. No wooden component shall be provided in
these boxes.

All stns

All stns
All stns

(a) Wiring clips shall be of aluminum, screws & tacks


shall be of alloy aluminum or cadmium plated iron.
(b) Height of socket outlet, switches, fan regulators,
call bells push button shall be 120 cm above FFL.
However when equipment kept on floor is to be fed
supply, socket outlet for these may be at height 23
cm above FFL, as required in non-domestic accn.
(c ) Height of light fittings shall be 215 cm from
finished floor level
(d) Height of fan shall be 260 cm above finished floor
level, its location shall be decided keeping in view
layout of furniture & asthetics

ZONAL SPECIFICATIONS

- 42 -

CE (AF) WAC PALAM

3
(e) It shall be ensured that switch for one of the light
points in bed room of md officers accn shall be next
to the bed.
(f) 10 Amps MCB SPNL with enclosure on II nd class
HW board 20 x 20 x 4 cm will be provided in main
toilet for Geysers.

All stns

(g) For fixing battens, fittings, boards etc in


electrification work wooden gutties shall not be used.
Only rawl plug/PVC expendable sleeves shall be
used.
(h) 40 mm dia GI Pipe light grade will be laid below
FFL in stair case and along wall for the main switch
board all concealed.
8

Exhaust Fan

Geysers

ZONAL SPECIFICATIONS

(a) 230 mm sweep for kitchen of Md officers accn.


(b) Suitable size for each cook house and other
authorised locations.
Geysers shall be of standard make ISI marked
vertical type and installed with the following :(a) Plug and socket
(b) Vent pipe
(c) Fusible plug
(d) Pressure reducing valve in case of multi storyed
bldgs.
(e) Safety valve
(f) Proper earth connection
(g) Separate inlet pipe line from tank to geysers

- 43 -

All stns
All stns

CE (AF) WAC PALAM

1.

2.

3.

4.

10

Telephone connection

Socket with concealed conduit upto the external wall


of bldg at following locations :(a) Md Officers Accn
(b) Civilian type IV & V accn
(c )Officers/Tech bldgs
(d) Institution bldg.

All stns

11

Door Call Bell

Shall be of standard make and provided for :-

All stns

5.

(a) Civilian type I to V Accn


(b) Md officers Accn
12

Antenna

13

Light Fitting

Antenna Bracket is to be provided with hole and


PVC Conduit in in external wall of the building for
following accn.
(a) Md accn for all rank
(b) Civilian type I to V
The following lifht fittings shall be used for the
locations as shown against each:-

All stns

All stns

(a) 1x40W Box type FTL fitting


(i) Md officers incldg Civ offrs quarters in Kitchens,
Drawing room and dinning rooms.
(ii) OTM accm
(b) 1x40W Patti type FTL fitting
Md Offrs Qtrs in rooms except mentioned at (a) (i)
above, Md JCO/OR accn / Civ accn Type I to III in all
rooms and kitchen, servant qtrs and garages of offrs
qtrs , basements etc

ZONAL SPECIFICATIONS

- 44 -

CE (AF) WAC PALAM

14

CFL Fittings.

In each rooms of md accn, toilets/bath/WC, stair cases/hall,


All stns
in each rooms of servant qtrs, garages , lobbies etc

15

Service connection

Underground service connections with PVC


armoured LT heavy duty aluminum cable of 1100
volts grade of suitable size shall be provided for all
Md accn, Messes, Adm/Tech accn and all important
buildings. Overhead service connection with weather
proof cable of suitable size shall be provided for
storage accn, hutted accn, garages & buildings of
temporary specification.

All stns

16

Service connection

Underground service connections with PVC


armoured LT heavy duty aluminum cable of 1100
volts grade of suitable size shall be provided for all
Md accn, Messes, Adm/Tech accn and all important
buildings. Overhead service connection with weather
proof cable of suitable size shall be provided for
storage accn, hutted accn, garages & buildings of
temporary specification.

All stns

17

Testing

On completion of installation the testing shall be


carried out as per clause 19.146 of SSR Part I.

All stns

ZONAL SPECIFICATIONS

- 45 -

CE (AF) WAC PALAM

17

Obstruction Light

18.

Lighting Protection

Obstruction light will be provided on high rise


All stns
structures for air craft warning wherever considered
essential.
Lightning protection shall be provided in magazines All stns
and explosive stores, bulk petrol installations, signal
and computer installations, air craft hangers, ATC
building, missile accommodation and other important
buildings and tall structures as per provisions of
Indian Standard specifications.

ZONAL SPECIFICATIONS

- 46 -

CE (AF) WAC PALAM

EXTERNAL ELECTRIFICATION
Ser
No

Item

General

Steel Tublar poles


swaged type
Pre-stressed concrete
poles

ZONAL SPECIFICATIONS

Specification

Stations

(a) All materials, fittings and equipments used in


All stns
electrical requirement work shall comply with the
requirements of relevant Indian Standard specification.
The makes shall be standardized/approved by this HQ
from time to time.
(b) In all major electrical installations, such as main
receiving and distribution sub stations, industrial
establishments, transmission and distribution lines and
cable networks, safety procedures, instruction for
working on low, medium and high voltage lines and
apparatus and safety practices listed out in IS 5216
shall be followed to the extent applicable.
(c ) The system/Installation shall conform to S-732 and
shall be as per IS 5216 shall be followed to the extent
applicable.
(d) All electrical equipments provided shall satisfy the
requirement laid down in IS : 1646; Code of practice
for fire safety bldgs (General) electrical installation and
IS 3034, Code of Practice for fire safety of industrial
buildings, electrical generating and distribution
stations, to the extent applicable.
These shall conform to IS-2713
All stns
These shall comply with the requirement of IS 1678

- 47 -

Remarks
The switch boards shall be
provided with two separate
earthing wherever 3 phase
supply being provided.

These will be used as reqd


basis

All stns

CE (AF) WAC PALAM

1
4

2
Over head lines

3
(a) Conductor used shall be ACSR and shall confirm
to IS-398 (Part I)

All stns

(b) Joints on OH conductor at tapping points and


jumper points shall be sealed with epoxy sealing
compound.
(c ) Heat shrink or cold shrink cable joint/boxes for HT
XLPE cables shall be used in place of CI cable and
boxes both or indoor and cut door joints.
(d) All non-galvanised steel structure shall be painted
with anti corrosive paint & further with 2 coat of
synthetic enamel paint or aluminum paint.
(e) Lightning arresters shall be provided at terminating
ends on HT and LT overhead lines at all two/four pole
structure mounted with HT air break switches & should
be of distibution class expulsion type 5 KA discharge
current.
5

Cables

ZONAL SPECIFICATIONS

HT cable shall be XLPE. LT cables shall be PVC/


XLPE insulated. Both shall be armoured and as per
IS with aluminum conductors.

- 48 -

All stns

CE (AF) WAC PALAM

Transformers

(a) Unless otherwise specified, transformers upto 250


KVA shall be aluminum winding and above 250 KVA of
copper winding.

All stns

(b) Out door transformers shall be upto 250 KVA


capacity. For higher capacities indoor transformers
shall be provided except 33/11 KV transformers. Out
door transformers upto 100 KVA capacity shall n be
pole mounted. For areas where wind velocity is high,
these out door transformers shall be installed on a
PCC platform on ground with protective fencing.
(c ) Transformer must have its neutral brought out for
earthing
(d)Transformer must be earthed by two independent
earthing with GI strips for body and by another two
independent earths with GI strips for neutral.

Switch Gears

(e) Transformers shall be installed as described in IS10028 (Part II).


(a) Isolating arrangement will be made for both HT and All stns
LT systems. The LT isolation being effective for
neutral as well. Oil or vacuum circuit breaker (VCB)
should be provided for HT system for capacity 400
KVA and above.
(b) A pad lock must be provided for locking the
operating handle of gang operated air break switches.

ZONAL SPECIFICATIONS

- 49 -

CE (AF) WAC PALAM

(c ) Switch fuses shall be provided for all LT main


controls upto 400 Amps. Beyond this it should be
ACBs/ OCBs.
(d) MCBs, RCCBs or MCCBs shall be provided for
control of out going circuits.
(e) All metal switch gears and boards shall be factory
made and shall be painted prior to ercetion with one
coat of anticorrosive primer and after erection with two
coats of approved enamel or alluminium paints .
(f) MCCB upto 800 Amps load (LT system) shall be
used.
(g) ACB/OCB above 800 Amps, load (LT system) shall
be used
(h) VCB for 33 KV & 11KV system shall be used
8

Distribution pillar boxes


(WP)

These shall conform to IS-5039 and SSR.

All stns

Anti-climbing devices /
danger notice
board.

These shall be provided as per IE rules on all HT


poles. 3 phase LT control system shall be provided
with danger boards only.

All stns

ZONAL SPECIFICATIONS

- 50 -

CE (AF) WAC PALAM

10

Testing / commissioning

All electrical installations shall be systematically tested


as per IE rules / relevant IS/SSR and records
maintained. Pre-commissioning tests shall be carried
out by Electrical Inspector.

All stns

11

GOD

It should be mounted on 12 insulators( 4 insulators on


each phase) & min 200 A at 11 KV.

All stns

ZONAL SPECIFICATIONS

- 51 -

CE (AF) WAC PALAM

Miscellaneous Works
Ser
No
1

Item of work
Fire Fighting works

Specifications

Stations

Fire fighting works in this zone mainly pertains to amn


related works, ie Mags & ESHs , Hangers & some other
technical buildings as per user reqmt. The fire fighting
schemes are to decided as per the recommendation of
Fire Advisor of MOD.

All

Remarks

In other buildings, Fire fighting works shall be planned all


as per IS : 1648 1961.
2.

Rain Water
Harvesting

Ground water has been the mainstay for meeting water


supply requirements. However, growing demand for
agriculture, industries and urban areas has resulted in
substantial decline in ground water levels. Therefore,
there is an urgent need to augment this resource through
rain water harvesting measures to utilize the surplus
monsoon run-off which otherwise goes waste.

All

The scheme is to be drawn


up in consultation with
Central Ground Water Board
at the time of detailed
planning.

In all works, rain water harvesting is to be included in the


BPs and AEs in terms of GOI, MOD letter No 35105/79/
POL (Works-Proc)/1818/DO-II/D(Works-I) dated 01 Oct
2002.
3.

Solar Energy

ZONAL SPECIFICATIONS

As per policy issued E-in-Cs Br letter No 62688/SENGY/


THR/ Misc/E4(UI) dt 09 Aug 2002 Solar lighting & water
heaters are to be included in BPs/AEs. As regards lighting

- 52 -

All

CE (AF) WAC PALAM

few lights in remote areas or imp bldgs from security point


of view may be provided as decided by the planner.
4.

Arboriculture

ZONAL SPECIFICATIONS

Arboriculture works are to be planned and executed in


terms of policy letter issued by GOI, MOD letter No
3(4)/97/DO-II/D(Works) dt 22 Oct 2002. The salient points
are given as under : (i)
To be sanctioned by CFA in areas where some
construction activity is in progress where some
accn has come up.
(ii)

Slection of trees and plants These would be


selected after detailed examinations of local
flora, in liaison with local state horticulture and
forest departments.

(iii)

Coordination with bldg work One of the main


reason for damage to young plants is lack of
coordination with construction pgme. As such
properly designed tree guards should be
erected around newly planted trees.

(iv)

Water supply Requirement of raw water


supply to nourish saplings and hedges be kept
in view while drawing water supply scheme.
Alternatively, as far as possible supply of
unfiltered water should be arranged for watering
of trees, hedges, etc..

- 53 -

All

These works will be done in


consultation with local
Horticulture and/or ForestDeptt.

CE (AF) WAC PALAM

Executing Agency The arboriculture works sanctioned as


a part of the project will be executed through MES in
consultation with local Horticulture or Forest Department.
5.

Furniture
Timber

Timber shall be Ist class seasoned hard wood(teak) for all


wooden furniture articles or as shown on standard drgs.

(i) Ply wood

Plywood shall be of BWP grade and ISI marked thickness


of ply wood shall be 3.5 mm, 6mm, and 12 mm as
required. Ply may be one side commercial and other side
teak face or both side commercial, as shown on drgs.

For maintenance works also


only ISI marked BWP quality
plywood and Particle Board
shall be by used.

(ii) Particle Board

Particle Board shall be of BWP grade and ISI marked. It


would be prelaminated as shown on drgs.

Prelamination where
specified shall have
balancing lamination on
other side of the board.

(iii) Pipe for charpoys

GI pipe 32 mm bore medium grade, ISI marked shall be


used for frame of chapoys and elbow shall be 32 mm dia, 3
ways, medium grade.
Best quality of cane from virgin plastic, white/cream colour
shall be used. Sizes shall be 1.5mm, 2 mm and 4 mm and
thickness of cane shall be 0.4 mm. Cane shall be woven in
Godrej; pattern.

(iv) Cane Plastic

(v) Nylon Newar

ZONAL SPECIFICATIONS

Best quality of nylon newar of size 50 to 55 mm wide light


colours/patterns shall be used and woven closelt. Weight
shall not be less than 1.5 to 1.7 kg per charpoys. Each
charpoy shall be woven in one colour. Weight should not
be less than 1 Kg for 60 RM length of Newar.

- 54 -

Cane plastic furniture should


not be left/stored in the sun.

Nylon newar furniture should


not be left/store in the Sun.

CE (AF) WAC PALAM

(vi) Cotton Newar

Best quality of cotton tread shall be used in newar of size


50.55 mm wide, closely woven. Weight should not be less
than 1 Kg for 34 RM length of Newar.

(vii)Sofa set Cushion

Foam shall be 75 to 100 thick with 32 to 36 density of


foam, ISI marked. Foam shall be covered with tapestry
cloth/Raxine, as required.

(ix) Tapestry cloth

Tapestry cloth shall be of good quality. Colour and quality


shall be as approved by the Accepting Officer.

(x) MS tube

MS tubes used in Tables/Chairs shall be ISI marked, 24/25


mm square and 1.6 mm thick.

ZONAL SPECIFICATIONS

- 55 -

CE (AF) WAC PALAM

Appx A
Common Burnt Clay Bricks
Common burnt clay building bricks (here after termed as bricks) shall conform to the requirements laid down in IS 1077-1986. Bricks
shall have minimum compressive strength 100 Kg/CM2 (Class designation 100).
The brick shall have smooth rectangular faces with sharp corner & slight round edges, and shall be well burnt, uniform in colour,
free from cracks, flaws, nodules of lime and emit clear ringing sound when struck.
Sampling and tests. Samples of bricks shall be subjected to the following tests.
Dimensional tolerance.
Water absorption.
Efflorescence.
Compressive strength.
Sampling .for carrying out the above tests, the samples of shall be done as per IS: 5454 at random according to the size of lot a
given in Table 1 below. The sample thus taken shall be stored in a dry place until tests are made.
Samples shall be taken as per details given below:Sampling from a stack.The brick stack, the stack shall be divided in to a number of real or imaginary sections and the required
number of real and imaginary sections and the required number of bricks drawn from each section. Sampling from trucks shall be
as per IS: 5454.Scale of sampling and criteria for conformity for visual and dimensional characteristics: -

ZONAL SPECIFICATIONS

- 56 -

CE (AF) WAC PALAM

For characteristics specified for individual bricks


No. of bricks in a lot
No. of bricks to be selected

Permissible no. of defective in the


sample

20
32
50

1
2
3

2001-10000
10000-35000
35001-50000

No. of bricks to be
selected for
dimensional
characteristics 20
bricks
40
60
80

b) Visual characteristics. The number of bricks to be selected from a lot and shall be in accordance of col. 1 & 2 of Table for
visual characteristics in all cases and dimensional characteristics if specified for individual bricks. All the bricks selected above
in accordance with col. 1 & 2 of Table shall be examined for visual characteristics as specified in col 2. If the number of defective
bricks found in the sample is less than or equal to the corresponding number as specified in col. 3 of table , the lot shall be
considered as satisfying the requirements of visual characteristics, otherwise the lot shall be deemed as not having met the
visual requirements.
c) Dimensional characteristics. The number of bricks to be selected for inspecting the dimensions and tolerance shall be in
accordance with col. 1 & 4 of Table 1. These bricks will be divided into groups of 20 bricks thus formed will be tested as per IS:
1077 for all the dimensions and tolerance as given below
i)

Type of bricks

Non modular bricks

ii)

Nominal size

230X114X75mm

iii)

Actual size

230X111X70 mm

iv)

Dimensional for group of 20 bricks


Length 442 to 478 cm (460 18 cm)
Width

213 to 231 cm (222 9 cm)

Height 134 to 146 cm (140 6 cm)

ZONAL SPECIFICATIONS

- 57 -

CE (AF) WAC PALAM

(d) A lot shall be considered having found meeting the requirements of dimensions and tolerance if none of groups of bricks
inspected fails to meet the specified requirements.
(e) Scale of sampling and criteria for physical characteristics shall be as per IS: 5454.
(f) The Lot, which has been found satisfactory in respect of visual and dimensional requirements, shall be next tested for
physical characteristics like compressive strength, water absorption, and efflorescence.
(g) `The physical requirements of the bricks shall be tested as per IS: 3498 (Part I to IV)
(h) The bricks shall have physical characteristics as specified here under:Water absorption

20% Max

Compressive strength

75 Kg/CM2

Efflorescence
show a

Nil to Slight sign of efflorescence i.e. 0-10% of surface area of the brick should
thin deposit of salt

(j) A lot shall be considered having satisfied the requirements of physical characteristics if the condition stipulated here in are all
satisfied
(k) The average compressive strength shall satisfy the requirements specified in Para 5(b).
(l) The compressive strength of any individual brick tested in sample shall not fall below the minimum average compressive
strength specified for the corresponding class of brick by more than 20 %
(m) Average water absorption shall be as specified in Para 5(a)
The Number of bricks failing to satisfy the requirements of the efflorescence specified in Para 5(c) should not be more than the
permissible in IS: 5454

ZONAL SPECIFICATIONS

- 58 -

CE (AF) WAC PALAM

Appx B
RCC WORKS
The minimum grade of concrete for RCC work shall be as follows depending on type of construction and importance of
structure: (a) All RCC work will be in M25 (Design Mix) for moderate exposure
(b) Water retaining structures (like Overhead tank, Under
Ground sump),

M30 (Design Mix)

Note:- Special and very important structure minimum grade of concrete for RCC will be decided separately
2. The contractor shall carryout the mix design and the mix so designed shall be got approved from GE . The parameters and
other stipulations are laid down as under:Design Mix
Grade of concrete

M25/M30 as applicable

Type of cement

Ordinary Portland Cement 43/53 Grade

Maximum nominal size of aggregate

20 mm for all sections more than 75 mm thick


10 mm for section 75mm

(d)

Minimum cement content

As IS 456

(e)

Maximum water cement ratio

0. 45 for M30 and 0.50 for M25

(f)

Workability

25-75mm.

Mild/Moderate.

(g) Exposure conditions

ZONAL SPECIFICATIONS

- 59 -

CE (AF) WAC PALAM

(j) Max temperature of concrete at the time of placing of concrete 40C.


(k) Type of aggregate. Coarse aggregates will be crushed stone graded aggregate conforming to IS 383 & fine aggregates
conforming to IS 383 and Grading Zone I, II and III.
(l) Degree of control

Very good ( Ref table 40 of SP 23 1982)

(m) Water: as per clause 5.4 of IS456-2000


(n) Maximum chloride content should be 0.6% as kg/cum of chloride ion (Maximum acid soluble chloride content)
(o) Maximum cement content

As per IS456

3. The batching of concrete shall be as per clause 10.2 of IS 456: 2000. Volumetric batching shall not be allowed.
4. The concrete shall be mixed in mechanical mixture in accordance to clause 10.3 of IS 456: 2000.
5.The formwork shall be as per clause 11 of IS 456:2000.
6.Assembly of reinforcement shall be as per clause 12 of IS 456: 2000
7. Nominal cover to Reinforcement: Nominal cover is the design depth of concrete cover
as given in table below:-

to all steel reinforcements, including links

Exposur
e@

Nominal cover
in mm not less
than

Slab

Walls

Beams

Columns

Mild
Moderat

20mm
30mm

20mm
30mm

20mm
30mm

20mm
30mm

40mm
40mm

ZONAL SPECIFICATIONS

- 60 -

CE (AF) WAC PALAM

e
In case of columns of minimum dimension of 200 mm or under, whose reinforcing bars do not exceed 12mm; a nominal
cover may be of 25 mm
@ Exposure conditions as per table 3 of IS 456-2000
For further details clause 26.4 0f IS 456-2000 be referred
8. Transporting, placing compaction and curing of concrete shall be as per clause 13 of IS 456: 2000.
9. During hot and cold weather the concreting should be done as per the procedure set out in IS 7861 part II and part I.
10.Sampling and strength of designed concrete mix shall be as per clause 15 of IS 456: 2000.
11.The concrete may be accepted, as per clause 16 of IS 456: 2000.
12. Inspection of concrete structure shall be as per clause 17 of IS 456: 2000.
13.The following documentation shall be maintained at site: Test reports and manufacturers certificate for material
Concrete mix design details
Pour cards for site organization and clearance for concrete placement.
Record of site inspection of workmanship, and field test.
Non conformance reports, change orders,
Quality control charts and
Statistical analysis.
14. Irrespective what ever mentioned in SSR regarding RCC works, all RCC work shall be executed as per IS 45- 2000.

ZONAL SPECIFICATIONS

- 61 -

CE (AF) WAC PALAM

Appx C
WATER PROOFING TREATMENT TO RCC ROOF & SUNKEN FLOOR
1

Water proofing treatment shall be provided with APP modified water proofing membrane 3 mm th (weighting not less
than 3.0 Kg/Sm) on prepared surface as per manufacturer instruction and under strict supervision of manufacturers
technical representative. The treatment over roof slab and sunken floor will be carried out as under :-

2.

Material
APP Polymeric water proofing membrane shall consist of a Center core of 160GSM Non Woven Polyester mat
protected on both sides with a high quality polymeric asphaltic mix. The polymeric asphaltic mix will be protected on
both sides with thermo fusible HMHDPE film. The material shall have the following characteristic/properties:-

3.

Technical specifications
Reinforcement (Center core)
Heat resistance 1000C for 1 hour
Cold resistance at (-) 5 0C
Tensile strength
Lengthwise
Cross wise
Elongation
Length wise
Cross wise

4.

160GSM Non Woven Polyester mat


Does not drip
Does not break/ crack
-

700 N/5 cm
450 N/5 cm

- > 40%
- > 45%

Application
(i)

Apply 10 mm thick plaster in CM 1:4 mixed with WPC when concrete is green as per manufactures instructions.

(ii) The surface of roof, parapet and gutters, drain mouths, etc. over which waterproofing treatment is to be applied

ZONAL SPECIFICATIONS

- 62 -

CE (AF) WAC PALAM

shall be cleaned of all foreign matter such as, fungus, moss, dust etc by wire brushing and dusting. For cast iron drain
out lets a grove shall be cut around to tuck in the treatment. Concrete angle-fillets shall be provided at junctions
between roofs and vertical faces of walls (parapet and other walls), around obstacles such as pipes, chimneystacks,
etc. and other similar situation to ease up about corners.
(iii) Apply Primer conforming to IS: 3384-1965 @ 0.3 Kg/SM to be applied on prepared surface, till the surface is
properly impregnated .
(iv) After the primer has dried the membrane will be laid by torching to the surface .
(v)

Topping of polymeric membrane


(i) Roof slab -- Brick tiles 40 mm thick bedding layer of CM 1:4 and jointed & pointed in CM 1:4 . Linseed oil @
5% by weight of cement shall be mixed in cement mortar for screed and pointing to the brick tiles laid over 50 mm
thick PCC padding type Bo . After laying the curing shall be cured with water ponding.

(vi) Laying of polymeric water proofing membrane and bonded completely to the substrate & the overlaps are then
scaled/fused by flame as per manufacture instructions.
5.

Laying procedure are as under :(a) The membrane shall normally be laid in length at right angles to direction of the run-off gradient, commencing at
the lowest level and working up to the crest. The membrane shall be first cut to required lengths, brushed clean of
dusting material and laid out flat on the roof. Each length of membrane prepared for laying shall be laid in position and
rolled up for a distance of half of its length. The hot binding material shall be laid on to the roof across the full width of
the rolled membrane as the later is steadily rolled out and pressed. The excess bonding squeezed out at the ends
shall be removed as laying proceeds.
(b) When the first half of the membrane has been bonded to the roof, the other half shall be rolled up and then unrolled
on to the hot bonding material in the same way as per Para (v) a above.

ZONAL SPECIFICATIONS

- 63 -

CE (AF) WAC PALAM

(c) The minimum overlaps of 100 mm shall be allowed at the ends and sides of strips polymeric membrane. All
overlaps shall be firmly bonded by heating and fusing the layer of asphalt and melting the protective plastic film, but
taking care not to over heat this, as too much heat can harm the central polyethylene core, which is essential for water
proofing function.
6.

Overlap fusing methodology


(i) Keep the overlap open with the help of trowel and the direct the flame uniformly inside and towards both
membranes. Working the flame in opposite direction to the advance of the applicator.
(ii) When the asphalt starts to flow, the applicator should press both membranes with his foot; on the opposite side to
the hand holding the torch until a thin string of fluid asphalt appears, indicating correct fusing and bonding. During this
phase, the trowel should be worked with a back and forth, lengthwise motion, to homogenize the bonded area.
(iii) Apply a layer of blown grade bitumen (conforming to IS : 702) 85/25@ 1.2 Kg/Sqm.
(iv) Binding material, such as sand in dry condition @ 0.5 to 1.0 Kg/Sqm shall be dusted over the bitumen.

7.

Treatment around rain water pipe/rain water pipe.


The rain water pipe outlets (here after referred as drains) can be horizontal or vertical depending on whether they are
situated in the floor or in the parapet walls. In either case, the treatment is the same, although the difficulty of
application may vary. The correct execution of a drain should include the following steps.
(a)

Cut a strip of polymeric membrane 25 cm in width and length equal to the perimeter of the drain, adding 10 cm for
the overlapping. Flame bonds the part of the strip to be inserted into the drain. i.e. approx. 15 cm.

(b)

Cut the protruding end of the drain strip vertically upwards, with the aid of a heated trowel, into as may slits as are
necessary to then be able to press it downwards and flame bond it to the surrounding roof deck. Then, with the
help of the trowel and torch, go over the exterior of the drain to obtain an even spread of the asphalt and fill in all
the pores.

ZONAL SPECIFICATIONS

- 64 -

CE (AF) WAC PALAM

8.

(c)

Cut a square piece of polymer membrane about 15 cm larger than the diameter of the drain. Flame bonds this
square over the drain opening, as centered as possible.

(d)

Then, using the heated trowel cut the part that covers the opening of the drain in to the shape of a star with 8
peaks. Fold the peaks outwards and heat them one by one with the torch and then insert them into the drain.
Pressing them down with your fingers to ensure perfect adherence.

(e)

The last step is to go over the inside of the drain, leveling of the surface. The drains shall be at least 15 mm lower
than the substrata, so that the extra thickness caused by the various layers of the polymeric membrane do not
cause unnecessary ponding of water.

Water proofing treatment to Parapets.


In vertical finished with polymeric membrane shall be cut in suitable length and width and should be adhered to the
parapets and taking up and over the top of the parapet wall in case of RCC parapet. The lower portion of membrane
shall be taken over wall/RCC slab joint and taken up to a length 150 mm horizontally and bonded effectively with
polymeric membrane as explained above. The membrane shall be protected with 15 mm thick cement mortar 1:4
plaster and PCC coping at top of the parapet.

9.

Testing
Frequency of test At least one test consist of three sample specimen at random from each lot. The Polymeric
membrane shall be got tested from the test house as mentioned here under:(a)Chemical & Meetallurgical services
T.S No. 63, SIDCO Industrial Estate
Ekkaduthangal,
Chennai 600097
Fax No. 44 2312944

ZONAL SPECIFICATIONS

- 65 -

CE (AF) WAC PALAM

(b) CENTRAL INSTITUTE OF PLASTIC


ENGINEERING & TECHNOLOGY
(Ministry of Chemical and Fertilizers,Govt. of India)
Gundy, Chennai 600032
Fax No. 91 44 2344673
(c ) National Test House Alipore
10.

Calcutta

Execution of work
The work will be got executed through authorized applicator of the manufacture under strict supervision of Engineer-inCharge.

11.

Guarantee
Guarantee for 10 years will be given by the contractor and submitted to the GE.

ZONAL SPECIFICATIONS

- 66 -

CE (AF) WAC PALAM

Recommended Finishes
S.No.
01.

Type of Bldg
Offrs Mess

ZONAL SPECIFICATIONS

Flooring
-Foyer Marble with
borders.
-Main staircase
Marble.
-Corridors and other
staircase
Kota stone with
marble bounders.
-Ante room/
Dining/Bar.
Marble/Vitrified with
borders.
-Other rooms
Ceramic
tiles.400x400mm
-Terraces (if
any)
Kota stone
-Kitchen
complex
Kota stone with
granite tops on
working shelfs.
-Toilets
Non skid ceramic
tiles.
-Guest rooms
Vitrified tiles.

Base
Wall
care
putty on
plastered
walls.

Walls
Int
Plastic
emulsion
paint
In ante
room,
dining bar,
pvt dining
guest
rooms
foyer.
Toilets
Glazed
tiles with
borders.

Windows
Ext
(a)
Dholpur
cladding.
(b) Grit
finish.
(c)
Weather
proof
paints.

Appdx D
Doors

Remarks

(a)Rolled
form pre
coated
windows.

(a) Teak paneled


doors with etched
glass at main
entrance door.

(a) False ceiling to


be provided in
Antiroom, dining,
Bar, Pvt Dining.

(b) Alu
(powder
coated or
anodized).

For other rooms.


(b) Flush doors
with decorative
finish (Polished).

(b) All internal roads


be made of
PCC/interlocking
pavers.
(c) Railing to stair
case be of stainless
steel/MS pipes.
(d) For
parking/paved area
Interlocking
pavers.
(e) Light fitting
combination of
decorative
fillings/CFL.
(f) Semi stall urinals,
oval type WHB with
granite counter to
be provided.
(g) Censor based
flushing cistern for
Urinals.

- 67 -

CE (AF) WAC PALAM

S.No.

Type of Bldg

Flooring
Base

02

Single Accn for


Offrs

Rooms
Vitrified Tiles
600x600 mm
Corridor/ Stair
Hall/Stair Case
Kota Stone with
marble border

03.

Mess for
JCOs/OR

Entrance hall
Marble/Kota stone
Corridors & staircase
Kota with borders of
marble.
Club room/Dining
Ceramic tiles
400x400.
Kitchen complex
Kota stone with
granite top on shelf.
Toilets.
Non skid ceramic
tiles.
Pvt dining/Cards/ Bar
Non skid ceramic
tiles 400x400 mm
Terrace Kota

ZONAL SPECIFICATIONS

Walls
Int

Wall
OBD
care
White
putty on
wash in
plastered
kitchen
halls
and
toilets.
Toilet
Glazed
ceramic tile
of size
200x300 .
Wall
OBD
care
White
putty on
wash in
plastered
kitchen
halls
and
toilets.
Toilet
Glazed
ceramic tile
of size
200x300
upto lintel
level.

- 68 -

Windows

Doors

Remarks

Ext

Cement
base
paint

Rolled form
precoated
steel
windows

Flush doors
Sold panel PVC
doors
Durosam Fly proof
doors

Cement
based
paint

Rolled
form
precoated
steel
windows.

Entrance door,
Ante Room.
Anodized/powder
coated alu section
with 8mm th glass.
Others
Flushed doors
with decorative
viewer (Polished)

(h) All drain in front


and around to be
covered.
Ext doors with
Mortice Locks

1. Paved area to be
provided with
interlocking paver.
2. Urinal-Semi stall
with censor based
flushing cistern.
3. WHB with
granite counter.

CE (AF) WAC PALAM

S.No.

Type of Bldg

Flooring

04.

Living in accn
for
SNCOs/Airmen

Rooms
Kota Stone.
Toilet
Non skid ceramic tile.
Stair case
Kota stone
Verandah
Kota with marble

05.

OTM BLDG
(a) HQ Bldg
(b) Office Bldg
(c) Tech Bldg
and similar type
of accn.

Entrance
Marble with borders.
Main staircase
Marble with borders.
Head of the Org
Secretariat
Vitrified tiles
Other Offrs
Ceramic tile 400x400
Corridors and side
staircase
Kota with marble
border.
Terrance
Kota stone
Toilets.
Non skid ceramic
tiles with borders.

Walls
Base
Int
Wall
OBD in
care
rooms.
putty
White
wash in
toilets.
Toilets
Glazed
ceramic tile
upto lintel
level.
Wall
OBD
care
Toilet
putty on
Ceramic
plastered tile upto
walls.
lintel level.
White
wash.

Ext
-do-

Windows

Box Type
Windows

Doors

Remarks

1. PVC door in
bath rooms.
2. Panelled door
in living.

1. WHB to be
provided with
granite counter.
2. Full size mirror
to be provided in Air
Men Accn.

Grit
finish/
Weather
proof
paint

Pre coated
rolled from
steel
windows /
Box Type
Windows

Entrance
Anodized
(a) Alum.

(a) False ceiling to


be provided in air
conditioned area.

(b) Flush doors


with decorative
ply.

(b) Wherever bldg is


centrally airconditioned false
ceiling will also be
provided in the
corridors.
(c) Hard ware for
the doors of
important areas to
be of S/S./Brass.
(d) All hardstanding
parking area to be
provided with
interlocking pavers.
(e) Interlocking tiles

ZONAL SPECIFICATIONS

- 69 -

CE (AF) WAC PALAM

S.No.

Type of
Bldg

Flooring
Base

Walls
Int

Windows

Doors

in porch.
Remarks

Ext
(f) Railing of MS
iron/stainless steel
pipes depending upon
importance of bldg.
(g) PVC door in bath
rooms.
(h) WHB oval type with
granite counter.
(j) Urinal semi stall with
censor based flushing
cistern.
(k) Full size mirror over
WHB.
(l) Wall mountable WC
in the toilet of head of
the office.
(m) All drains to be
covered in front of the
office.

06.

FWC/MI
Room/SMC

Entrance
Marble
Stair case
Kota stone
Verandah/Corridor
Kota stone
MOs
Ceramic tile

ZONAL SPECIFICATIONS

Wall
care
putty on
plastered
walls.

OBD
Toilet
Ceramic
tile upto
lintel level.
White
wash.

- 70 -

Cement
Based
paint

Pre coated
rolled from
steel
windows

Alum.

CE (AF) WAC PALAM

LIST OF PRODUCTS/ITEMS
AppxE
S No

Items & Makes/ Manufactures

Ply wood
(i)
Kitply
(ii)
Mysore Chip board
(iii)
Century plywood
(iv)
Green ply
(v)
Durian

Plain/Prelaminated Particle Board


(i)
(ii)
(iii)
(iv)
(v)

S No
5.

Panelled/Glazed/ Gauge Door Shutters


(i)
M/S Goel Brothers Raipur
(ii)
M/S Ram Fabricater Pvt. Ltd.
223, Industrial Area,Panchkula
(iii)
M/S Sohal Industries, 182,
Industrial Area, Patiala
(iv)
M/S Chandigarh Timber
Product, Mubarakpur, Patiala
(v)
M/S Choiti Industries, Kanpur.
(vi)
M/S Supreme doors & Allied
Products Jajmau Kanpur
(vii)
M/S Pioneer Timber Product,
Chandigarh
(viii)
M/S NND wood Industrieis,
Sriganganagar
(ix)
M/S Jain wood Industries,
Sonepat.
(x)
M/S Shree Khrishna Associates
Panchkula
(xi)
M/S Shakti Industries Barnala

6.

Flush Door Shutters,


(i)
M/S Swastik
(ii)
M/S Mysore Chip Board Archid
(iii)
M/S Century Ply.
(iv)
M/S Duro Ply
(v)
M/S Green ply Industries.

Kitply
Bhutan board
Nepal board
Mysore chipboard
Novapan

MDF Board
(a)
NUWUD
(b)
Duratuff

Laminated sheets
(i)
Mysore chip board.
(ii)
Formica
(iii)
Sunmica
(iv)
Backlyte Hylum,
(v)
Greenlam
(vi)
Merino

ZONAL SPECIFICATIONS

- 71 -

Items & Makes/ Manufactures

CE (AF) WAC PALAM

S No
7.

8.

Items & Makes/ Manufactures

S No

PVC Doors
(a) Solid PVC Panels
(i)
Rajshri Plastiwood,
(ii)
Sintex Industries
(iii)
Accura Polytech Ahmedabad
(iv)
Quite Extrusions
Steel Windows/Pressed steel Door frame
(i)
M/S Sen-Harvic, Vora Building 1st
floor, 50 Nakhoda Street Bombay
(ii)
M/S Man Industries, Jaipur.
(iii ) M/S Mahata Engg & Construction,
Bikaner
(iv)
M/S Surbhi Metal (India), Pvt. Ltd,
Jodhpur
(vi)
M/S Asvini & Sons Ghaziabad.
(vii) M/S Multiwyn Industrial Corpn,
Calcutta.
(viii) M/S AGEW Steel Manufactures(Pvt),
Ahmedabad
(viii) M/S G.S. Udyog, Panki Industrial Area
Kanpur
(ix)
M/S Ram Fabricators Pvt. Ltd.
Panchkula.
(x)
M/S Shree Khrishna Associates
Panchkula
(xi)
Trishul Industries Meerut
(xii)
Chandni Industries ,Morta Meerut
Road Ghaziabad.

ZONAL SPECIFICATIONS

Items & Makes/ Manufactures

9.

UPVC Windows
(i)
Poly Windows, Pune.
(ii)
Finefta ( DCM Sri Ram)
(iii)
Accura Polytech Ahmedabad
(iv)
Quite Extrusions

10.

AL Sections
(i) Hidalco
(ii) Indal
(iii) Ajit India
(iv) Jindal

11.

AL Sheets
(i) Hindalco
(ii) Indal
(iii)Ajit India
(iv) Jindal

12

CGI / PGI Sheets


(i) Bhushan Steel
(ii) SAIL
(iii) TATA
(iv) Jindal

- 72 -

CE (AF) WAC PALAM

S No

Items & Makes/ Manufactures

13

S No

AC Sheets
(i)
(ii)
(i)
(ii)

16.

M/S Ramco ACC Sheets


SWASTICK
M/S Evrest Bldg products Ltd
Jata Sankar Bosa Marg
Mulund (West) Bombay-400080
M/S UP Asbestos
Charminar

Terrazzo tiles
(i)
(ii)
(iii)
(iv)

17
14.

Items & Makes/ Manufactures

PCC tiles( Plain/Chequreed)

Ceramic tiles
(i)
(i) Kajaria
(ii) Spartex
(iii) Johnson
(iv) Somani
(v) NITCO
(vi) Orient
(vii) Bell

15

M/S Mehatab tiles


8, Rani shopping Centre,
Bhanwar, Indore-452001
NITCO
Bharat Tiles.
Hindustan Tiles Alwar

(ii)
(iii)
18

PVC Roll/Tiles
(i) Marblex Tiles
(ii) Krishna Vinyl
(iii) Polyfin
(iv) Armstrong

ZONAL SPECIFICATIONS

19.

- 73 -

M/S Mehatab tiles


8, Rani shopping Centre,
Bhanwar, Indore-452001
NITCO
Bharat Tiles.

Porcelains Vitrified tiles


(i) Murndeshwar Ceramic Ltd.(Naveen
Diamond tile)
(ii) Johnson- Marbonite
(iii) Bell Granato
(iv) Euro (v) Asian (vi) Orient (vi) Kajaria
(vii) Somany
Cement based Paints
(i) Snowcem plus
(ii) Duracem
(iii)
Super Accroem (iv) Nerocem

CE (AF) WAC PALAM

S No
20.

Items & Makes/ Manufactures

S No

Acrylic Washable Dist/OBD


(i) Goodlass Nerolc (Super Acrylic)
(ii) Shalimar paints (No 1 Premium
Acrylic(Distemper)
(iii) Asian paints (Tractor Acrylic distemper
(iv) Berger paints (Bison Super)
(v) ICI India (Maxilite Acrylic distemper)

21

24.

22

PVC water storage tanks


(i) Sintex
(ii) Rotex
(iii) Polywell
(iv) JS Polyplast

26.

PVC Rain water pipes


(i) Jain pipes
(ii) Finolex
(iii) Supreme
(iv) Kisan
(v) Prince

Plastic/Acrylic Emulsion Paint


(i) Goodless Nerolc (All Escapes)
(ii) Shalimar paints (Hussain collection)
(iii) Jenson & Nicholson (Special Effect)
(iv) Asian paints (royal)
(v) Berger Paints (Luxol Silk Splender)
(vi) ICI India (Dulux Velvet touch)

23

27.

Exterior Emulsion
(i)
Apex Ultima
(ii)
Berger weather coat

ZONAL SPECIFICATIONS

(iii) Nerolac Impression Excel


(iv) Dulux weather shield ultra clean
(v) Allrounder- Snowcem Paints
Wall care putty
(i) Birla white
(ii) JK White
(iii Sara ( Ferrous)

25.
Synthetic Enamel Paint
(i) ICI Paint (Dulux Gloss)
(ii) Asian Paint (Apcolite)
(iii) Godlass Nerolac paints (Nerolac)
(iv) Jenson & Nicholson paints Ltd (Brolac)
(v) Berger paints (luxol Hi Glass)

Nerolac
Items & Makes/ Manufactures

- 74 -

CI Soil, waste vent pipe Centrifugally


caste
(i)
NECO
(ii)
Hepco
(iii)
Kapilansh
(iv)
Anand Founders & Engineers
Batala

CE (AF) WAC PALAM

S No
28.

29

Items & Makes/ Manufactures


SGSW Pipes
(i)
Perfect Jabalpur
(ii)
Devraj Ind Gaziabad

S No
33

(i)
(ii)
(iii)
(v)
(vi)

MS Pipes & fittings


(i)
BST
(ii)
TATA
(iii)
TIRUPATI
(iv)
Jindal

30

GI Pipes & fittings


(i)
Jindal
(ii)
TATA
(iii)
Prakash Surya

31

CI Valves & fittings


(i)
M/S BIR
(ii)
M/S Upadhyay

32

Sanitary fittings
( IWC/EWC/ urinals/WHB)
(i)
Neycer Kermag (standard)
(ii)
Hindustan sanitary Were (Hindware 1st
quality)
(iii)
Parryware (Super fine)
(iv)
Cera ( 1st quality)

ZONAL SPECIFICATIONS

Items & Makes/ Manufactures


PVC flushing cistern

- 75 -

M/S Johnson Poddar


Commander Champion
Parry ware-slimline
Hindware
Speed flow- Anupam Ind

34

Mirror/Glass
(i)
Saint Globin
(ii)
Modi Float
(iii)
Triveni Float Glass
(iv)
Hindustan Pilkington Glass Works

35

Bath room fittings


(Taps/Valves/Shower rose)
(i)
Gem
(v)
Soma
(vi)
Dripless
(vii) ARK
(viii) Zim Aqua
(vii) Jaguar (viii) Mark

36

Kitchen Sink( ISI Marked)


(i)
Diamond
(ii)
Nirali
(iii)
Neel Kanth
(iv)
Jayna
(v)
Blue Star Anupam Industries
(vi)
Allex- Impex Steels ( India)

CE (AF) WAC PALAM

S No
37.

38

Items & Makes/ Manufactures


EWC seat cover
(i) Commander Champion
(ii) Parryware
(iii)Hindware
(iv)SpeedFlow Anupam Ind

40

41

Items & Makes/ Manufactures

42.

Chemicals for Anti-termite treatment.


(i)
DE-NOCIL BOMBAY
(ii)
Pest Control of India
(iii)
Montari Industries Chandigarh

43

Construction Chemicals

Utensil Stand
(i)
(ii)
(iii)
(v)

39

S No

Diamond
Nirali
Neel Kanth (iv) Blue Star- Anupam Ind
Kobra

(i) Chokesy Chemicals


(ii) Fairmate
(iii) Pidilite
(iv) MC Bauchemic
(v) CICO
(vi) Fosroc (vii) Huntsman

Al Mongery
(i) Mepro
(ii) Argent New Delhi
(iii) Classic New Delhi
(iv) M/S Mowjee
(v) Nu Lite, New Delhi

44

(i)
(ii)
(iii)
(iv)
(v)

Hydraulic door closers


(i)
Everest
(ii)
Universal
(iii)
Godrej
(iv)
AMAR
Floor door Springs
(i)
Everest
(ii)
Godrej (iii)
AMAR

ZONAL SPECIFICATIONS

Integral water proofing compound

45

- 76 -

Water seal from Acrompaints


Impermo from Snowcem
Accoproof from ACC
Fair Plast IP from Fairmate.
CICO No.1

Float valve
(i) Leader
(ii) Bombay metal & alloy Co.

CE (AF) WAC PALAM

S No
46.

Items & Makes/ Manufactures

S No

False ceiling

50.

(i) Gypboard
(ii) Armstrong
(iii) Hilux
(iv) Aerolite
47

Glass Mosaic tile


(i)
(ii)
(iii)

Coral
Bisaza
Opio

Items & Makes/ Manufactures


APP Waterproofing Membranes
(i)
Multiplas M/S Texas
(ii)
Hyperplas by IWL, India,
Chennai
(iii)
Tikkitar
(iv)
STP Limited
(iv)
Shivam Tar Products.
(vi)
Pidilite
(vii) Polyplus TM M/S Percept
Engineers Pvt Ltd
(viii) M K Petroproducts
(ix)
Hydro Flame

51.
Stainless Steel WC/ WHB( ISI Marked)

48

Paving/Wall Tile/Designer Tile


(i)
(ii)
(iii)
(iv)
(v)

(i) NITCO
(ii) Unilite
(iii) Ultra
49

Tile Adhesive

Diamond
Nirali
Neel Kanth
Jayna
Blue Star Anupam Industries

52.
PCC Interlocking tiles

(i)
(ii)
(iii)

Ferrous Crete
Bal Endura
Pidilite

ZONAL SPECIFICATIONS

(i)
M/S Mehatab tiles
(ii)
NITCO
Tiles.
(iv)
Coral Industries.

- 77 -

CE (AF) WAC PALAM

(v)
S No
50

Items & Makes/ Manufactures


Transformer 66 KV Step down/Step up
(i)
(ii)
(iii)
(iv)

51

S No

54.

GOD (Gang operated Device/Isolator, 11


KV and above.
(i) PACTIL
(ii) JAIPURIA
(iii) Alston
(iv) Cromption

ALSTOM
BHEL
KIRLOSKAR
CROMPTON GREAVES
55

Transformer 11 KV step down/step up 400


KVA above and including 400 KVA
(i)
(ii)
(iii)
(iv)

53

Bharat Bijlle,
SIEMENS
CROMPTION GREAVES

Transformer 33 KV Step down/step up


(i)
(ix)
(x)
(xi)

52

Items & Makes/ Manufactures


(vi)
(vii)
(viii)

ALSTOM
BHEL
KIRLOSKAR
CROMPTON GREAVES

A-ONE Tiles

(i) BHEL
(ii) ABB
(iii) SCHNEIDER
(iv) SIEMENS
(v) CROMPTON GREAVES
(vi) ALSTOM

ALSTOM
BHEL
KIRLOSKAR
CROMPTON GREAVES

Transformer 11 KV step down/step up upto


400 KVA
(i)
(ii)

56

KIRLOSKAR
INDIAN TRANSFORMER &
ELECTRICAL GURGAON,

ZONAL SPECIFICATIONS

HT Switch Gear 33 KV, VCB, HT switch


Gear/66KV.VCB

- 78 -

HT Switch Gear 11 KV, VCB


(i) BHEL
(ii) ABB
(iii) SCHNEIDER
(iv)SIEMENS

CE (AF) WAC PALAM

(iii)
S No
57.

58

RAJASTHAN TRANSFORMER LTD

Items & Makes/ Manufactures

(v)CROMPTON GREAVES
S No

HT Switch gear protection relay


Electromechanical/Numerical
(i)
BHEL
(ii)
ABB
(iii)
SCHNEIDER

61.

HT Ring Main unit,SF6/VCB,11 KV

62.

Package/unified Sub Station

63.

CT & PT 11 KV
(i)
(ii)
(iii)

64.

- 79 -

AE
ENGLISH ELECGTRIC
CROMPTON

CT & PT,33KV/66KV
(i)
(ii)
(iii)

HT Cable, XLPE
(i)
CABLE CORPORATION OF INDIA
(iv)
UNIVERSAL
(v)
ASIAN CABLES (PRG)
(vi)
INDUSTRIAL CABLES LTD

ZONAL SPECIFICATIONS

HT Voltage stabilizer
KIRLOSKAR
CROMPTION
ANDREW YVLE, APLAB

ABB
SCHNEIDER
SIEMENS
BHEL
KIRLOSKAR
CROMPTON
60

HT Cable Joints Cold Shrinkable


BIRLA 3M
DENSON
RAY CHEM

ABB
SCHNEIDER
SIEMENS
CROMPTION
ALSTOM
59

Items & Makes/ Manufactures

AE
ENGLISH ELECTRIC
CROMPTON

CE (AF) WAC PALAM

(v)
S No
65.

66.

POLY CAB

Items & Makes/ Manufactures

S No

HT Cable Joints Heat Shrinkable

69.

(i) RAYCHEM
(ii) DENSON
(iii) REPL
HT/LT Steel tubular swaged pole

HT/LT PCC Poles


(i)
(ii)
(iii)
(iv)
(v)

68.

LT Air Circuit Breaker upto 2000 Amps


(i) CROMPTON
(ii) L & T
(iii) SCHNEIDER
(iv) SPACEAGE
(v) LEGRAND

71.

LT OCB upto 2000 Amps


(i)
(ii)
(iii)
(iv)
(v)

72.

OBLUM
ALSTOM LEMCOS CO
CROMPON
SCHNEIDER

ZONAL SPECIFICATIONS

- 80 -

BHEL
JAYSHREE

70.

HINDUSTAN PREFAB
CEMENT FABRIC CHANDIGARH
PRECTO CHANDIGARH
M/S CONCRETE UYDOG, JHANSI
M/S MOHAN

Lightning Arrestor
(i)
(ii)
(iii)
(iv)

Disc Insulator, Pin Insulator 11KV/66KV


(i)
(ii)

(i) ADVANCE STEEL TUBES


(ii) NATIONAL TUBING CO
(iii) VIKRAM INDUSTRIES MOHALI
(iv) BCW KANPUR
(v) UNITED ENGINEERS KANPUR
67.

Items & Makes/ Manufactures

C & S GEWISS
HH ELCON
CROMPTON
L&T
ANDREW YULE

MCCB
(i)
L&T
(ii)
SCHNEIDER
(iii)
SIEMENS
(iv)
HAVELLS
(v)
LEGRAND

CE (AF) WAC PALAM

S No

Items & Makes/ Manufactures


(v)
(vi)
(vii)

73.

S No

GE POWER
STANDARD
HPL

76.

LT Panel
(i) L & T
(ii) NATINAL ENGINEERING WORKS
(iii)POWER SYSTEM & CONTROLS
(iv) SUPERTECH
(v) ADVANCE
(vi) MILESTONE
(vii)MADHU ELECTRICALS
(viii)S & S PANNEL,
(ix) SHALABH
77.

74.

Voltmeter/Ammeter/Frequency
meter/meters/PF meter.

MCB
(i)
(ii)
(iii)
(iv)
(v)
(vi)
(vii)
(viii)
(ix)

INDO ASIAN
HVELLS
LEGRAND
SCHNEIDER
SIEMENS
HEGGER (L&T)
STANDARD
HP
DATAR

Street Light Timers


(i)
(ii)
(iii)
(iv)
(v)

AE
MECO
SECURE
SCHNEIDER
75.

Items & Makes/ Manufactures

L&T
LEGRAND
HARPAL
INDO ASIAN THEBEN
HAVELLS

Push Button
(i)
(ii)

L&T
RAAS

ZONAL SPECIFICATIONS

- 81 -

CE (AF) WAC PALAM

(iii)

CONCORD

S No

Items & Makes/ Manufactures

S No

78

Selector Switch

81.

(i)
(ii)
(iii)
(iv)
(v)

L&T
RAAS
CONCORD
KAYCEE
SIEMENS

Items & Makes/ Manufactures


LT Cables, 1100 Volts, XLPE
(i)
(ii)
(iii)
(iv)
(v)
(vi)
(vii)
(viii)
(ix)

79.

Indicating Lamps
(i)
(ii)
(iii)
(iv)
(v)

80.

82.

L&T
RAAS
CONCORD
VAISHNO
SIEMENS

ZONAL SPECIFICATIONS

Voltage stabilizer above 5KVA


(i)
(ii)
(iii)
(iv)
(v)
(vi)
(vii)
(viii)
(ix)
(x)

Main Switch/ Change over Switch


(i) AVELLS
(ii) CONTROL & SWITCHGEAR
(iii) L & T
(iv) INDO ASIAN
(v) STANDARD
(vi) HPL

- 82 -

INDUSTRIAL CABLE (INDIA) LTD


RAJPURA (PATIALA)
PLAZA
NICCO
UNIVERSAL
CABLE CORPORATION OF
INDIA
FORT GLOSTER
ASIAN CABLES (RPG)
HAVELLS

APLAB
VNER-7
SINETRAC
VOLINA
ITE GURGOAN
VINITEC
AE
ELECTROTEKNICA
UNILINE
ANDREWYULE

CE (AF) WAC PALAM

(vii)SCHENIDER
S No
83.

Items & Makes/ Manufactures

S No

DG Sets

85.

KWH Meter
(i)
HAVELLS
(ii)
BENTEX
(iii)
CADEL
(iv)
SECURE
(v)
HPL
(vi)
ALSTOM
(vii) SCHNEIDER

86.

Voltage stablisers upto 5 KVA

ENGINE
(i)
(ii)
(iii)
(iv)
(v)
(vi)

CUMMINS
KIRLOSKAR
CROMPTON
ASHOK LEYLAND
RUSTON
GREAVES COTTON

ALTERNATOR
KIRLOSKAR ELECTRIC
ALSTOM
STAMFORD
JYOTHI

84.

Thimbals/Studs/Lugs

87.

DOWELLS
AXIS
INDIANA
ASIAN

ZONAL SPECIFICATIONS

- 83 -

Items & Makes/ Manufactures

(i)
APLAB
(ii)
VENER-7
(iii)
SINERTRAC
(iv)
VOLINA
(v)
ITE GURGOAN
(vi)
VINITEC
(vii) ELECTROTEKNICA
(viii) LABOTEK
CTS (LT)
(i)
C&S
(ii)
ALSTOM
(iii)
KAPPA
(iv)
INDO TECH
(v)
AE
(vi)
MELTEK
(vii)
ENGLISH ELECTRIC

CE (AF) WAC PALAM

S No
88.

Items & Makes/ Manufactures


ELCB/ RCCB
(i)
(ii)
(iii)
(iv)
(v)
(vi)
(vii)
(viii)

89.

LEGRAND
GE POWER
HAVELLS
INDO KOPP
STANDARD
HPL
DATAR
PLAZA

92.

93.

ALSTOM
EPCOS
DUCATI
L&T
CROMPTON
DATAR
GEPC

ZONAL SPECIFICATIONS

- 84 -

LEGRAND
INDO KOPP
BALS ELECTRONIC

PT Switch/Sockets
(i)
(ii)
(iii)
(iv)
(v)
(vi)

KALINGA
BAJAB
PARTEEK
PLAZA

FINOLEX
NICCO
PLAZA
HAVELLS
SULAABH

Thermo Plastic sockets


(i)
(ii)
(iii)

94.

TIRUPATI
POLYPACK

Copper wires 650/1100 Volts


(i)
(ii)
(iii)
(iv)
(v)

PVC Conduit pipe


(iii)
(iv)
(v)
(vi)

Items & Makes/ Manufactures


(i)
(ii)

Capacitor Banks (LT)


(i)
(ii)
(iii)
(iv)
(v)
(vi)
(vii)

91.

S No

ANCHOR
LEGRAND
PLAZA
HAVELLS
SSK
CONA

CE (AF) WAC PALAM

(vii)
S No
95

Items & Makes/ Manufactures

S No

PVC Rigid pipe (Heavy Duty)


(i)
(ii)
(iii)
(iv)
(v)

96

FINOLEX

98

FINOLEX
PRINCE
TRIPUTI
DUTRON
SUPREME

Modular switches/sockets
(i)
(ii)
(iii)
(iv)
(v)
(vi)

LEGRAND
CRABTREE
ANCHOR
SSK
CONA
SIEMENS

MCB DB (SP/TP)
99
(i)
(ii)
(iii)
(iv)
(v)
(vi)
(vii)
(viii)

97

Items & Makes/ Manufactures

INDO ASIAN
LEGRAND
ALSTOM
PLAZA
HEGGER (L&T)
STANDARD
HPL
GEPC

9i) ANCHOR
LEGRAND
CRABTREE
SSK
CONA

Fittings & Accessories HPSV


(70/150/250/400)
(i)
(ii)
(iii)
(iv)
(v)

100

Box type tube light fitting


(i)
(ii)
(iii)
(iv)
(v)
(vi)

PHILIPS
CROPTON
BAJAJ
KESELC SCHREDER
GE LIGHTING

ZONAL SPECIFICATIONS

Ceiling Rose

- 85 -

PHILIPS
CROPTON
BAJAJ
KESELC SCHREDER
GE LIGHTING
WIPRO

CE (AF) WAC PALAM

(vi)
S No
101

Items & Makes/ Manufactures


HPMV (80/125/250/400)
(i)
(ii)
(iii)
(iv)
(v)
(vi)

102.

S No
104.

105.

OSRAM
PHILIPS
CROMPTON
BAJAJ
WIPRO INDO ASIAN
ECOLITE
HAVELLS

ZONAL SPECIFICATIONS

Box type decorative

ANCHOR
LEGRAND
CONA

Wall mounted fan/Air circulator


(i)
(ii)

- 86 -

OSRAM
PHILIPS
CROMPTON
BAJAJ
WIPRO
GE LIGHTING

Electric Call Bell


(i)
(ii)
(iii)

107.

PHILIPS
CROPTON
BAJAJ
KESELC SCHREDER
WIPRO
ASIAN

CFL Fittings
(i)
(ii)
(iii)
(iv)
(v)
(vi)

106.

ASIAN

Items & Makes/ Manufactures

(i)
(ii)
(iii)
(iv)
(v)
(vi)

PHILIPS
CROPTON
BAJAJ
KESELC SCHREDER
GE LIGHTING
WIPRO

CFL Lamps
(i)
(ii)
(iii)
(iv)
(v)
(vi)
(vii)

(vii)

PHILIPS
CROPTON
BAJAJ
KESELC SCHREDER
GE LIGHTING
WIPRO

Metal Halide Street light fitting


(i)
(ii)
(iii)
(iv)
(v)
(vii)

103

WIPRO

ALSTOM
CROMPTON

CE (AF) WAC PALAM

(iii)
S No

109

110

111.

Items & Makes/ Manufactures


(iii)
(iv)
(v)
UPS
(i)
(ii)
(iii)
(iv)

BAJAJ
POLAR
ALMONARD

S No
113.

Exhaust Fans
(i)
GEC
(ii)
CROMPOTN CHNAITAN
(iii)
BAJAJ
(iv)
POLAR

Items & Makes/ Manufactures


Energy efficient Tube light
(i)
(ii)
(iii)
(iv)
(v)
(vi)

APLAB
LABOTEK
INVENSYS
114.

KHAITAN

ASIAN
OSRAM
CROMPTON
PHILIPS
BAJAJ
WIPRO

Flame Proof fittings and fixture


(i)
(ii)
(iii)
(iv)

SUDHIR
BALIGA
FLEXRO
SHYAAM

SK Fittings
115.
(i)
(ii)
(iii)
(iv)
(v)

VIKAS
PRAKASH
DAYAL
EVERSHINE
WIPRO

CI Pipes
(i)
(ii)
(iii)
(iv)

112.
ERW Pipes
(i)
(ii)
(iii)

WATER SUPPLY

ELECTRO-STEEL
NECO
KESHORAM
KOLKATA

JINDAL
BST
TATA

ZONAL SPECIFICATIONS

- 87 -

CE (AF) WAC PALAM

(iv) TIRUPATI
S No
116.

Items & Makes/ Manufactures


Sluice valve
(i)
(ii)
(iii)

117.

S No
120.

KIRLOSKAR
LEADER
KARTAR

KSB
BS
SU
CROMPTON GREAVES

Non Return Valve


(i)
(ii)
(iii)

KIRLOSKAR
LEADER
KARTAR

KIRLOSKAR
CROMPTON
JYOTHI
BECON

122.

KIRLOSKAR
CROMPTON
BECON
JYOTHI

ZONAL SPECIFICATIONS

Motor starter
(i)
(ii)
(iii)
(iv)

Centrifugal Pumps
(i)
(ii)
(iii)
(iv)

Submersible cable
HAVELLS
KALINGA
PLAZA
FINOLEX

Pump Sets Mono Block


(i)
(ii)
(iii)
(iv)

119.

Submersible Pump
(i)
(ii)
(iii)
(iv)

121.

118.

Items & Makes/ Manufactures

123.

VT Pump
(i)
(ii)
(iii)

- 88 -

L&T
BCH
HAVELLS
TELEMECHANIQUE AND
CONTROL

KIRLOSKAR
JOHNSON
JYOTHI

CE (AF) WAC PALAM

S No

Items & Makes/ Manufactures

S No
127

124

(i)
(ii)
(iii)
(iv)
(v)

AKASH
PHOTRON
PUMPUTER

Single phase preventor/ phase sequence


corrector
(i)
(ii)
(iii)
(iv)
(v)

126

Chloronome plant

Water level indicator


(i)
(ii)
(iii)

125

Items & Makes/ Manufactures

128

AKASH
MINILILEC
TELEMECHANIC
L&T
HAVELLS

SIEMENS
ALSTOM
KIRLOSKAR
BHARAT BIJLE
NGEF

ZONAL SPECIFICATIONS

130

SU-KAM

Battery
(i)
(ii)
(iii)
(iv)
(v)

Electric Motor
(i)
(ii)
(iii)
(iv)
(v)

Battery Charger
(i)

129

CHILOTECH
JESCO
ADVANCE-2000
RAMCO
CAPITAL

EXIDE
AMRON
NICCO
STANDARD
FURKUWA

Compressor
(i) KIRLOSAKR
(ii) ACCEL
(iii) TECHUMSH
(iv) ELGI

- 89 -

CE (AF) WAC PALAM

S No
131

Items & Makes/ Manufactures


Motor Starter
(i)
(ii)
(iii)
(iv)

132

134

135

136

L&T
BCH
TELEMECHANIQUE & CONTROL
SIEMENS
137

VOLTAS
CARRIER
BLUE STAR

Air filter

Cooling Tower
(i) PAHARPUR
(ii) DELTA
(iii) MIHIR
(iv) COOL DROP

Condenser
(i) VOLTAS
(ii) BLUE STAR
(iii)CARRIER

138

Expansion valve
(i) DANFOSS
(ii) SPORLON
(iii) ALCO
(iv) INDFOSS

Non Chemical type water softening plant


(i) SCALE GUARD
(ii) AQUAMAG
(iii)DELTA

139

Thermostat
(i) RANCO
(ii) DANFOSS
(iii) HONEY WELL
(iv)INDFOSS

Humidistat
(i) DANFOSS
(ii) HONEY WELL

ZONAL SPECIFICATIONS

Items & Makes/ Manufactures

(i) TENACITY
(ii) PUROLATOR
(iii) AIR TECH

Cooling coil/ AHU


(i)
(ii)
(iii)
(iv)

133

S No

- 90 -

CE (AF) WAC PALAM

(iii) INDFOSS
S No
140.

Items & Makes/ Manufactures

S No

HP/LP cut off

145

(i) DANFOSS
(ii) RANCO
(iii) INDFOSS
141

Thermometers

146

Butterfly valve
147

Package type AC
(i) BLUE STAR
(ii) VOLTAS
(iii) CARRIER

Rubber mat
(i) JYOTH
(ii) DUNLOP

144

Split type AC /Window type


(i) BLUE STAR
(ii) LG
(iii) CARRIER
(iv) VOLTAS
(v) SRIRAM (USHA)
(vi) HITACHI

(i) AUDCO
(ii) CASTLE
(ii) SCOPE
(iv) ADVANCE
143

Shut off valve


(i) DANFOSS
(ii) INDFOSS
(iii) CASTAL

(i) RENUTROL
(ii) H.GURU
(iii) SCINTIFIC
142

Items & Makes/ Manufactures

148

Chilling package unit


(i) VOLTAS
(ii) BLUE STAR
(iii) CARRIER

Hot water generator


(i) THERMEX
(ii) RAPID CONTROL

ZONAL SPECIFICATIONS

- 91 -

CE (AF) WAC PALAM

(iii)ZENITH

ZONAL SPECIFICATIONS

- 92 -

CE (AF) WAC PALAM