Version:1.0.1
Date: Oct. 2010

AboutThisManual
ThismanualisaguidetoinstallationandconnectionoftheC3100/200/400access
controloperatorpanel.Forhowtousethesoftwareoftheproduct,seeZKAccess4.0
UserManual.

InstructionsforInstallationandUseoftheC3100/200/400ControlPanel

Contents
1ImportantSecurityInstructions.......................................................................1
1.1Important SecurityInstructions.................................................................1
1.2InstallationCautions.................................................................................2
2Introduction......................................................................................................5
2.1SystemFunctionParameters.....................................................................5
2.2ProductTechnicalParameters ...................................................................5
2.3ControlOperatorPanelIndicators.............................................................6
3ConnectionandInstallation..............................................................................8
3.1CaseInstallation.......................................................................................8
3.2InstallationofAccessControlOperatorPanelWires..................................9
3.3ControlOperatorPanelSystemInstallation .............................................10
3.4ControlOperatorPanelConnectionTerminals.........................................12
3.5ConnectionwithDoorSensors,ExitSwitches,andAuxiliaryInputDevices
...................................................................................................................16
3.6ConnectionwithWiegandReaders..........................................................18
3.7RelayOutputConnection........................................................................20
3.8AccessControlOperatorPanelSystemPowerSupplyStructure...............25
4AccessControlOperatorPanelSystemNetworking ......................................27
4.1AccessControlNetworkingWiresandWiring.........................................27
4.2TCP/IPNetworkCommunication............................................................29
4.3RS485NetworkCommunication ............................................................29

InstructionsforInstallationandUseoftheC3100/200/400ControlPanel

4.4 DIP Switch Setting (485 Address Setting, Factory Setting, and Terminal
ResistanceSetting).......................................................................................31

II

InstructionsforInstallationandUseoftheC3100/200/400ControlPanel

1ImportantSecurityInstructions
1.1ImportantSecurityInstructions
1.

Read,followandkeepinstructions:Beforeoperatingtheequipment,readand
follow strictly all security and operation instructions. Please keep the
instructionsingoodconditionforfuturereference.

2.

Accessories:Pleaseusetheaccessoriesrecommendedbythemanufactureror
deliveredwiththeproduct.Anyotherrelatedproductisnotrecommendedas
the majoralarming or monitoringsystem. The majoralarming ormonitoring
system should comply with the local applicable fireprevention and security
standards.

3.

Installationcautions:Donotplacethisequipmentonanyunstabletable,tripod
mount, support or base,lestthe equipmentshouldfall and get damaged, and
more undesirably cause severe personal injuries.Therefore, it is important to
installtheequipmentasinstructedbythemanufacturer.

4.

Allperipheraldevicesmustbegrounded.

5.

No external connection wirescan be exposed. All connectionsand idle wire


endsmustbewrappedwithinsulatingtapestopreventaccidentalcontactwith
exposedwiresfromdamagingtheequipment.

6.

Repair:Donotattemptunauthorizedrepairoftheequipment.Disassemblyor
detachment is likely to cause shock or other risks. All repair jobs should be
donebyqualifiedrepairpersonnel.

7.

Damagesinneedofrepair:Inanyofthefollowingcases,firstdisconnectthe
AC/DC power supply from the equipment and notify qualified repair
personnel forrepairs:

Thepowercordorconnectorisdamaged.

Thereisentryofliquidoranyotherforeignobjectintotheequipment.

Theequipmentiswettedorexposedtobadweather(rain,snow,etc.).
1

InstructionsforInstallationandUseoftheC3100/200/400ControlPanel

If the equipment cannot work normally even though operated as


instructed,pleasebesuretoadjustonlythecontrolcomponentsspecified
in the operation instructions. Incorrect adjustment of other control
components may cause damage to the equipment, and add to
troubleshootingworkloadofthequalifiedtechnicians.

8.

Theequipmentfallsdownoritsperformancechangesobviously.

Replacing components: If it is necessary to replace a component, the repair


personnelmustuseonlythesubstitutesspecifiedbythemanufacturer.

9.

Security inspection: After the equipmentis repaired,therepair personnelare


supposed to conduct security inspection to ensure the equipment can work
normally.

10. Power supply: Operate the equipment with only the type of power supply
indicatedonthelabel.Contacttheoperatorforanyuncertaintyaboutthetype
ofpowersupply.

1.2InstallationCautions
1.

Allwiresmustrunthroughcasingpipes,forexamplePVCorgalvanizedpipes,to
prevent failure causedby rodent damage.Although a control panel is designed
with good antistatic, lightningproof, and leakageproof functions, ensure its
chassis and the AC ground wire are connected properly and the AC ground
wireisgroundedphysically.
2

InstructionsforInstallationandUseoftheC3100/200/400ControlPanel

2.

It is recommended not to plug/unplug connection terminals frequently when


the system is energized. Be sure to unplug the connection terminals before
startinganyrelevantweldingjob.

3.

Do notdetach orreplace any control panel chip withoutpermission, because


unprofessionaloperationmaycausedamagetothecontrolpanel.

4.

It is recommended not to connect any other auxiliary devices without


permission. All nonroutine operations must be communicated to our
engineersinadvance.

5.

A control panel should not share one power socket with any other
largecurrentdevice.

6.

Itispreferabletoinstallcardreadersandbuttonsatheightsof1.41.5m above
the ground, but the heights are subject to proper adjustment according to
customersusualpractice.

7.

It is advised to install control panels at places easy of maintenance, like a


weakelectricwell.

8.

It is strongly recommended thattheexposed part of any connection terminal


shouldnotbelongerthan4mm,andspecializedclampingtoolsmaybeused
to avoid shortcircuit or communication failure resulting from accidental
contactwithexcessiveexposedwires.

9.

To save access control event records, read data periodically from control
panels.

10. Get prepared countermeasures according to application scenarios for


unexpectedpowerfailure,like selectingpowersupplywithUPS.
11. The connection between a card reader and a control panel should not be
longerthan100m.
12. The connection between a PC and a control panel should be shorter than
1200mforRS485communications.Alengthwithin600m isrecommendedto
makecommunicationsmorestable.
3

InstructionsforInstallationandUseoftheC3100/200/400ControlPanel

13. To protect the access control system against the selfinduced electromotive
force generated by an electronic lock at the instant of switching off/on, it is
necessaryto connectadiodeinparallel (pleaseusetheFR107deliveredwith
thesystem) withtheelectronic locktoreleasetheselfinduced electromotive
forceduringonsiteconnectionforapplicationoftheaccesscontrolsystem.
14. It is recommended that an electronic lock and a control panel should use
respectivepowersupplies.
15. It isrecommendedto usethe power supply delivered withthe system asthe
controlpanelpowersupply.
16. Inaplacewithstrongmagneticinterference,galvanizedsteelpipesorshielded
cables arerecommended, andpropergroundingisrequired.

InstructionsforInstallationandUseoftheC3100/200/400ControlPanel

2Introduction
Theaccesscontrolmanagementsystemisanewmodernizedsecuritymanagement
system,whichisaneffectivemeasureforsecurityandprotectionmanagement.Itis
mainlyusedtomanageentrancesandexitsofimportantplaces, suchas banks,hotels,
equipmentrooms,offices,smartcommunities,andfactories.

2.1SystemFunctionParameters
Highspeed32bit400MHzCPU,32MRAM,and256MFlash.
EmbeddedLINUXoperatingsystem.
Onedoor/twodoortwowayaccessorfourdooronewayaccess.
Amaximumof30,000cardholdersand100,000offlineeventrecords.
SupportofmultipleWiegandcardformatsandapasswordkeypad,compatible
withvarioustypesofcards.
Use of dual communication technologies: the Ethernet plus the RS485
industrialbus,forreliablecommunications.
Withawatchdog(hardware)builtin thecontrolpaneltopreventcrash.
Overcurrent, overvoltage, and inversevoltage protection for input of power
supplyto the controlpanel.
Overcurrentprotectionforthepowersupplytocardreaders.
Instantovervoltageprotectionforallinput/outputports.
Instantovervoltageprotectionforcommunicationports.

2.2ProductTechnicalParameters
Workingpowersupply:ratedvoltage12V(20%)DCratedcurrent0.5A.
Workingenvironment:temperature0C55Chumidity10%80%.

InstructionsforInstallationandUseoftheC3100/200/400ControlPanel

Outputload:workingvoltageAC30V,ratedcurrent8ADC36V,rated
current5A.
Ctype electronic lock relay output terminal: 10A contact current, 12V DC,
withLEDstatusindications.
Outputterminaloftheauxiliaryrelay:2Acontactcurrent,30VDC,withLED
statusindications.
Withdetachableconnectionterminalsmadeofalloysteelnonmagneticflange
materials.
OutlinedimensionsofthecontrolPCB:160mm(length)106mm(width)for
C3100/200218mm(length)106mm(width)forC3400.
MountingholedimensionsofthecontrolPCB:147.32mm(length)91.44mm
(width)forC3100/200203.2mm(length)106mm(width)forC3400.
External boxdimensions:345mm275mm70mm.

2.3ControlOperatorPanelIndicators
WhentheC3100/200/400ispoweredon,normallythePOWERindicator(red)islit
constantly,theRUNindicator(green)flashes(indicatingthesystemisnormal),and
otherindicatorsarealloff.
Exceptthecasesasfollows:
1.

LINK indicator (green): indicates proper TCP/IP connection if it is lit


constantly

2.

ACTindicator(yellow):indicatestransmissionofTCP/IPdataifitflashes

3.

TXindicator(yellow):indicatessendingof485dataifitflashes

4.

RXindicator(green):indicatesreceivingof485dataifitflashes

5.

Lock indicator (green): indicates unlocking if it is lit constantly (if the


auxiliary output indicator is lit in green constantly, it indicates the auxiliary
deviceisenabled)

6.

CARDindicator(yellow):indicatesinputofWiegandsignalifitislit.
6

InstructionsforInstallationandUseoftheC3100/200/400ControlPanel

SeetheC4indicatorsinthefollowingfigure:

Figure21IndicatorsintheC3400

InstructionsforInstallationandUseoftheC3100/200/400ControlPanel

3ConnectionandInstallation
3.1CaseInstallation

InstructionsforInstallationandUseoftheC3100/200/400ControlPanel

3.2InstallationofAccessControlOperatorPanel
Wires

Figure31 AccessControl OperatorPanelWireInstallationDiagram

Notes:
1.

Before connection, make sure the power supply is disconnected, because


connectionwithpowerconnectedwillcauseseveredamagetotheequipment.

2.

The access control wires must be separated according to heavy and light
current the control panel wires, electronic lock wires, and exit button wires
mustrunthroughtheir respectivecasingpipes.

InstructionsforInstallationandUseoftheC3100/200/400ControlPanel

3.3ControlOperator PanelSystemInstallation
Printer
Cardissuer

Hub

TCP/IPEthernet

Managementhost

C3400 controloperatorpanel

Internal
button

Cardreader 1

Internal
button

Internal
button

Cardreader2

Door1

Internal
button

Cardreader 4

Cardreader3

Door2

Door3

Door4

Controllingonewayentry/exitoffourdoors

Door1

Door2

Controllingtwowayentry/exitoftwodoors

Figure32 SchematicDiagramofC3400SystemInstallation

10

InstructionsforInstallationandUseoftheC3100/200/400ControlPanel

Note: The diagram above takes the C3400 for example. By contrast, only
onedoor twoway access is applicable to the C3100 system only twodoor
onewayortwodoortwoway accessisapplicabletotheC3200system.
The access control management system consists of two parts: management
workstation (PC) and control operator panel. They communicate via TCP/IP and
RS485 networks. On a 485 bus, each management workstation can be connected
with up to 63 C3 control operator panels (preferably fewer than 32). The
communication wires should be kept away from highvoltage wires as far as
possible,andshouldbe neitherroutedinparallelwithnorbundledwithpowerwires.
A management workstationisactually a PC connectedto the network. By running
the access control management software installed in the PC, access control
management personnel can remotely perform various management functions, like
adding/deleting a user, viewing event records, opening/closing doors, and
monitoringstatusofeachdoorinrealtime.

11

InstructionsforInstallationandUseoftheC3100/200/400ControlPanel

3.4ControlOperator PanelConnectionTerminals
C3100terminalconnectiondiagram

12

InstructionsforInstallationandUseoftheC3100/200/400ControlPanel

C3200terminalconnectiondiagram

13

InstructionsforInstallationandUseoftheC3100/200/400ControlPanel

C3400terminalconnectiondiagram

14

InstructionsforInstallationandUseoftheC3100/200/400ControlPanel

Descriptionsoftheterminals:
1.

The auxiliary input may be connected to infrared body detectors, fire


alarms,smokedetectors,etc.

2.

The auxiliary output may be connected to alarms, cameras, door bells,


etc.

3.

Alltheterminalsmentionedabovearesetthroughrelevantaccesscontrol
software.Pleaseseetherespectivesoftwareinstructionsfordetails.

PortsontheC3control operator panel:

No.

FunctionalPort

Wiegand card reader


interface

C3100

C3200

(OneDoor

(TwoDoor

TwoWay)

TwoWay)

C3400
(FourDoor
OneWay/TwoD
oorTwoWay)

Exitbutton

Controllockrelay

Doorsensor

Extensioninput

Extensionoutput

7
8
9

RS485

&

PC

communication
RS485

extension

communication
TCP/IP

15

InstructionsforInstallationandUseoftheC3100/200/400ControlPanel

3.5ConnectionwithDoorSensors,ExitSwitches,and
AuxiliaryInputDevices
Doorsensor
Adoorsensorisusedtosensetheopen/closedstatusofadoor.Withadoorsensor
switch,anaccesscontrolpanelcandetectillegalopeningofadoor,andwilltrigger
an output of alarm. Moreover, if a door is not closed within a specified period of
time after it is opened, the door control panel will also prompt an alarm. It is
recommendedtoselecttwocorewireswitha gauge over0.22mm2. Adoorsensormaybe
omittedifitisunnecessarytomonitoronlinetheopen/closedstatusofadoor,giveoutan
alarm whenthedoorisnot closed for alongtime orthereisillegal access, and usethe
interlockfunction.
Exitswitch
Anexitswitchisaswitchinstalledindoorstoopenadoor.Whenitisswitchedon,
thedoorwillbeopened.Anexitbuttonisfixedataheightofabout1.4mabovethe
ground.Ensureitislocatedintherightpositionwithoutslant,anditsconnectionis
correct andsecure.(Cut off theexposed end of any unused wireand wrap it with
insulating tape.) Note to guard against electromagnetic interference (such as light
switches and computers). Itisrecommendedto usetwocorewireswith agaugeover
0.3mm2astheconnectionwirebetweenanexitswitchandacontrolpanel.
Auxiliaryinput
C3100 provides no auxiliary input interface C3200 provides two, and C3400
providesfour,whichareconnectedtoinfraredbodydetectors,smokedetectors,gas
detectors,windowmagneticalarms,wirelessexitswitches,etc.Auxiliaryinputsare
set through relevant access control software. For details, please see ZKAccess4.0
UserManual.

16

InstructionsforInstallationandUseoftheC3100/200/400ControlPanel

Figure33ConnectionsbetweenC3400andDoorSensors,ExitSwitches,and
AuxiliaryInputDevices

17

InstructionsforInstallationandUseoftheC3100/200/400ControlPanel

Note: The diagram above takes C3400 for example. By contrast, C3100
provides no auxiliary input interface C3200 provides two, and C3400
providesfour.

3.6ConnectionwithWiegandReaders
C3100 can connecttwo Wiegand readersinthe onedoor twoway mode. C3200
provides four readers, which can be connected in the twodoor twoway mode.
C3400providesfourreaders,whichcanbeconnectedinthetwodoortwowayor
fourdooronewaymode.
The Wiegand interfaces provided by the C3 series can be connected to different
typesofreaders.IfyourcardreaderdoesnotusethevoltageofDC12V,anexternal
powersupplyisneeded. Areadershouldbeinstalledataheightofabout1.4mabove
thegroundandatadistanceof3050mmawayfromadoorframe.

18

InstructionsforInstallationandUseoftheC3100/200/400ControlPanel

Figure34ConnectionbetweenC3400andReaders
19

InstructionsforInstallationandUseoftheC3100/200/400ControlPanel

3.7RelayOutputConnection
C3100hastworelays(oneusedasacontrollockbydefault,andtheotherusedas
an auxiliary output) C3200 has four relays (two used as controllocks bydefault,
andtheothertwousedasauxiliaryoutputs)C3400haseightrelays(fourusedas
controllocksbydefault,andtheotherfourusedasauxiliaryoutputs).
The relays for auxiliary outputs may be connectedto monitors, alarms, door bells,
etc.Auxiliary outputs are setthroughrelevantaccess controlsoftware. For details,
pleasesee ZKAccess4.0UserManual.
Alockrelaycanbeconnectedinthedryandwetmodes,whileanauxiliaryoutput
relay cannot. The following illustrates relay output connection with anexample of
doorconnection.
1.

An access control operator panel provides multiple electronic lock outputs.


The COM and NO terminals are applicable to the locks that are unlocked
whenpowerisconnectedandlockedwhenpowerisdisconnected. TheCOM
and NC terminals are applicable to the locks that are locked when power is
connectedandunlockedwhenpowerisdisconnected.

2.

Bysettingthejumperterminalbesidethelockrelay,youcanselectthedevice
powersupplyorlockpowersupplyforthelock(thatis,thewetmodeordry
mode).Werecommendtousethewetmodeforyourconvienceofconnection.
Dry mode jumpersetting:short 12 and 34, andthedevice power supply
willbeusedfortherelayoutput.

Wetmodejumpersetting:short23and45,andthelockpowersupplywillbe
usedfortherelayoutput.

Note:Thefactorydefaultjumpingissetasdrymode.
20

InstructionsforInstallationandUseoftheC3100/200/400ControlPanel

3.

To protect the access control system against the selfinduced electromotive


force generated by an electronic lock at the instant of switching off/on, it is
necessaryto connectadiodeinparallel (pleaseusetheFR107deliveredwith
thesystem) withtheelectronic locktoreleasetheselfinduced electromotive
forceduringonsiteconnectionforapplicationoftheaccesscontrolsystem.

1. WetmodeExternalpowersupplyforNOLock

2. WetmodeExternalpowersupplyforNCLock

21

InstructionsforInstallationandUseoftheC3100/200/400ControlPanel

3. DrymodeExternalpowersupplyforNOLock

4. DrymodeExternalpowersupplyforNCLock
22

InstructionsforInstallationandUseoftheC3100/200/400ControlPanel

5. DrymodeThesystemcontroltheNormallyOpenlockusetheswitchvalue.

6. DrymodeThesystemcontroltheNormally Close lockusetheswitchvalue.

23

InstructionsforInstallationandUseoftheC3100/200/400ControlPanel

24

InstructionsforInstallationandUseoftheC3100/200/400ControlPanel

220V AC

3.8AccessControlOperator PanelSystemPower
SupplyStructure

25

InstructionsforInstallationandUseoftheC3100/200/400ControlPanel

An access control operator panel is powered by +12V DC. Generally, to reduce


power interference between control panels, each control operator panel should be
poweredseparately.Whenhighreliabilityisrequired,controlpanelsandelectronic
locksshouldbepoweredrespectively.
Topreventpowerfailureofacontroloperatorpanelfrommakingthewholesystem
unabletoworknormally,theaccesscontrolmanagementsystemisusuallyrequired
to have one UPS at least, and access control locks are powered externally to
guarantee the access control management system can still work normally during
powerfailure.

26

InstructionsforInstallationandUseoftheC3100/200/400ControlPanel

4AccessControlOperatorPanelSystem
Networking
4.1AccessControlNetworkingWiresandWiring
1.

RS485 communication wires are made of internationally accepted shielded


twistedpairs,which proveeffectivetopreventandshieldinterference.

2.

Thepowersupplyis12VDCconvertedfrom220V.

3.

The Wiegand readers use 6core communication shielded wires (RVVP


60.5mm) (usually there are 6core, 8core, and 10core types available for
users to select according to the ports) to reduce interference during
transmission.

4.

Asanelectroniclockhasabigcurrent,itgeneratesstronginterferencesignal
during anaction.Toreducetheeffectofanelectroniclockduring anactionon
otherelements,4core wires(RVV 40.75mm2, two for a powersupply and
twoforadoorsensor)arerecommended.

5.

Other control cables (like exit switches) are all made of 2core wires (RVV
20.5mm2).

6.

Notesforwiring:

Signal wires (like network cables and RS485 wires) can neither run in
parallel with nor share one casing pipe with largepower electric wires
(like electronic lock wires and power cables). If parallel wiring is
unavoidableforenvironmentalreasons,thedistancemustbeover50cm.

Try to avoid use of any conductor with a connector during distribution.


When a connector is indispensable, it must be crimped or welded. No
mechanicalforcecanbeappliedtothejointorbranchofconductors.

Inabuilding,distributionlinesmustbeinstalledhorizontallyorvertically.
Theyshouldbeprotectedincasingpipes(likeplasticorironwaterpipes,
to be selected according to the technical requirements of indoor
27

InstructionsforInstallationandUseoftheC3100/200/400ControlPanel

distribution). Metal hoses are applicable to ceiling wiring, but must be


secureandgoodlooking.

Shielding measures and shielding connection: If the electromagnetic


interferenceinthewringenvironmentisfoundstronginthesurveybefore
construction, it is necessary to consider shielding protection for data
cables when designing a construction scheme. Overall shielding
protectionisrequiredifthereisalargeradioactiveinterferencesourceor
wiring has to be parallel with a largecurrent power supply on the
construction site. Generally, shielding measures include: keeping a
maximumdistancefromanyinterferencesource,andusingmetalwiring
troughs or galvanized metal water pipesto ensure reliable grounding of
theconnectionbetweentheshieldinglayersofdatacablesandthemetal
troughs or pipes. Note that a shielding enclosure can have a shielding
effectonlywhenitisgroundedreliably.

Groundwireconnectionmethod:Reliablelargediametergroundwiresin
compliance with applicable national standards are needed on thewiring
site, and should be connected in a tree form to avoid DC loop. These
ground wires must be kept faraway from lightning fields. No lightning
conductor can serve as a ground wire, and ensure there is no lightning
current through any ground wire when there is lightning. Metal wiring
troughs and pipes must be connected continuously and reliably, and
linked to ground wires through largediameter wires. The impedance of
thissectionofwirecannotexceed2ohm.Theshieldinglayeralsomustbe
connectedreliably,andgroundedatoneendtoguaranteeuniformcurrent
direction. The ground wire of the shielding layer must be connected
throughalargediameter(notsmallerthan2.5mm2)wire.

28

InstructionsforInstallationandUseoftheC3100/200/400ControlPanel

4.2TCP/IPNetworkCommunication
TheEthernet10/100BaseTCrossoverCable,atypeofcrossovernetworkcable,is
mainly used for cascade hubs and switches, or used to connect two Ethernet
endpointsdirectly(withoutahub).Both10BaseTand100BaseTaresupported.

Printer

Managementhost
Cardissuer

Hub
TCP/IPEthernet

C3 controlpanel

C3 controlpanel

C3 controlpanel

Figure41 TCP/IPCommunicationSystemNetworking

4.3RS485NetworkCommunication
1.

RS485communicationwiresaremadeofinternationallyacceptedRVSPwires
(shielded twisted pairs), which prove effective to prevent and shield
interference. RS485 communication wires should be connected by means of
bus cascade instead of in astar form, to achievea better shielding effect by
reducingsignalreflectionduringcommunications.

29

InstructionsforInstallationandUseoftheC3100/200/400ControlPanel

2.

A single485bus can be connected with 63 access control operator panels at


most,but preferably shouldbeconnectedwithlessthan32.

3.

To eliminate signal attenuation in communication cables and suppress


interference, if the bus is longer than 300 meters, one 120ohm resistance is
usuallyinsertedbetweenthefirstandlastaccesscontroloperatorpanelsonthe
RS485bus.

4.

Forthisaccesscontroloperatorpanel,puttingplace8oftheDIPswitchtothe
ON position is equivalent to parallel connection of one 120ohm resistance
betweenthe485+and485 lines.

Asshowninthefigurebelow,putplace8oftheDIPswitchesofthefirstandlast

controloperatorpanelstothe ON position.

Figure42RS485CommunicationSystemNetworking
30

InstructionsforInstallationandUseoftheC3100/200/400ControlPanel

4.4DIPSwitchSetting(485AddressSetting,Factory
Setting,andTerminalResistanceSetting)
485addresssetting
Places 16 of the DIP switch are reserved to set device number for RS485
communication. The code is binary, and the lower places are in the front.
Whentheswitchissettothe ONposition,itindicates1(on)whentheswitch
issetdownwards,itindicates0(off).
Forexample,tosetadevicenumber39=1+2+4+32,whichcorrespondstothe
binarycode111001,putplaces1,2,3,and6totheONposition,asillustrated
below.

485addresssettingtable:
SwitchSetting

PlaceAddress
1

AddressNo.

01

ON

02

3
4

16

32

64

OFF OFF

OFF

OFF

OFF

OFF

ON

OFF

OFF

OFF

OFF

03

ON

ON

OFF

OFF

OFF

OFF

04

OFF

OFF ON

OFF

OFF

OFF

05

ON

OFF ON

OFF

OFF

OFF

06

OFF

ON

ON

OFF

OFF

OFF

07

ON

ON

ON

OFF

OFF

OFF

08

OFF

OFF OFF

ON

OFF

OFF

09

ON

OFF OFF

ON

OFF

OFF

10

OFF

ON

OFF

ON

OFF

OFF

11

ON

ON

OFF

ON

OFF

OFF

12

OFF

OFF ON

ON

OFF

OFF

31

InstructionsforInstallationandUseoftheC3100/200/400ControlPanel

SwitchSetting

PlaceAddress
1

13

ON

OFF ON

ON

OFF

OFF

14

OFF

ON

ON

ON

OFF

OFF

15

ON

ON

ON

ON

OFF

OFF

16

OFF

OFF OFF

OFF

ON

OFF

17

ON

OFF OFF

OFF

ON

OFF

18

OFF

ON

OFF

OFF

ON

OFF

19

ON

ON

OFF

OFF

ON

OFF

20

OFF

OFF ON

OFF

ON

OFF

21

ON

OFF ON

OFF

ON

OFF

22

OFF

ON

ON

OFF

ON

OFF

23

ON

ON

ON

OFF

ON

OFF

24

OFF

OFF OFF

ON

ON

OFF

25

ON

OFF OFF

ON

ON

OFF

26

OFF

ON

OFF

ON

ON

OFF

27

ON

ON

OFF

ON

ON

OFF

28

OFF

OFF ON

ON

ON

OFF

29

ON

OFF ON

ON

ON

OFF

30

OFF

ON

ON

ON

ON

OFF

31

ON

ON

ON

ON

ON

OFF

32

OFF

OFF OFF

OFF

OFF

ON

33

ON

OFF OFF

OFF

OFF

ON

34

OFF

ON

OFF

OFF

OFF

ON

35

ON

ON

OFF

OFF

OFF

ON

36

OFF

OFF ON

OFF

OFF

ON

37

ON

OFF ON

OFF

OFF

ON

38

OFF

ON

ON

OFF

OFF

ON

39

ON

ON

ON

OFF

OFF

ON

32

InstructionsforInstallationandUseoftheC3100/200/400ControlPanel

SwitchSetting

PlaceAddress
1

40

OFF

OFF OFF

ON

OFF

ON

41

ON

OFF OFF

ON

OFF

ON

42

OFF

ON

OFF

ON

OFF

ON

43

ON

ON

OFF

ON

OFF

ON

44

OFF

OFF ON

ON

OFF

ON

45

ON

OFF ON

ON

OFF

ON

46

OFF

ON

ON

ON

OFF

ON

47

ON

ON

ON

ON

OFF

ON

48

OFF

OFF OFF

OFF

ON

ON

49

ON

OFF OFF

OFF

ON

ON

50

OFF

ON

OFF

OFF

ON

ON

51

ON

ON

OFF

OFF

ON

ON

52

OFF

OFF ON

OFF

ON

ON

53

ON

OFF ON

OFF

ON

ON

54

OFF

ON

ON

OFF

ON

ON

55

ON

ON

ON

OFF

ON

ON

56

OFF

OFF OFF

ON

ON

ON

57

ON

OFF OFF

ON

ON

ON

58

OFF

ON

OFF

ON

ON

ON

59

ON

ON

OFF

ON

ON

ON

60

OFF

OFF ON

ON

ON

ON

61

ON

OFF ON

ON

ON

ON

62

OFF

ON

ON

ON

ON

ON

63

ON

ON

ON

ON

ON

ON

Restoringfactory setting
Thesilkscreened7(place7)oftheDIPswitchistheswitchforrestorationof
system settings.The placeissettoOFF by default. When place7is moved
33

InstructionsforInstallationandUseoftheC3100/200/400ControlPanel

upwardsanddownwardsforthreetimeswithin10secondsandfinallyreturned
to the OFF position, the factory settings will be restored after the access
controloperatorpanelisrestarted.
Terminalresistancesetting
Place 8 is forsettingthe RS485 terminationresistance. Puttingthe switch to
theONpositionisequivalenttoparallelconnectionofa120ohmtermination
resistancebetween485+and485.

485terminal
resistance
Restore
factorysetting

34