JULY 2013
EPC CONTRACTOR
ENGINEERING CONSULTANT
DALIANEAST-CCE20006-DBR-XXX-800 /
REV 00
26.07.13
00
C.Sudarmathi
P.Manivannan
S.Manivel
Document No.
Issue
Date
Rev
No.
Prepared By
Reviewed By
Approved By
DALIANEAST-CCE-20006DBR-XXX-800 / REV 00
Page 2 of 27
1.00.00.
INTRODUCTION
2.00.00.
Location
Altitude
(Dry)
Minimum: 9C
Maximum: 48C
40%
4.7 m/s
DALIANEAST-CCE-20006DBR-XXX-800 / REV 00
Page 3 of 27
3.00.00.
368.34 mm
Seismic zone
Zone III
guidelines
of
the
following
will
also
be
observed
in
3.01.00.
CBIP Recommendations.
IEC.
IEEE.
Transformer
: IS 2026
Circuit Breaker
: IEC - 56 / IS 13118
LT Switchgear
: IS 4237 / IS 4047
LT Cables
Current Transformer
: IS 2705
Potential Transformer
: IS 3156
Earthing
: IS 3043
Lightning Protection
: IS 2309
Motors
: IS 325 / IS 4029
: IS15652-2006
DALIANEAST-CCE-20006DBR-XXX-800 / REV 00
Page 4 of 27
4.00.00.
DESIGN CONSIDERATIONS
The Electrical system will be designed based on the requirements for the
safe, reliable performance, easy operation and maintenance of all
equipments covered in this report and the associated electrical system.
4.01.00.
Proposed Capacity
23.5 MW
1 x 23.5 MW
System Frequency
50 Hz 5%
Generation voltage
11kV
DC System Voltage
110V
50 deg C
Design life
At least 30 years
Environment
Tropical,dusty,chemical,laden,
atmosphere
VFD selection
after
derating
at
4.01.01.
System
Fault Level
Duration
11 KV System
40KA
1 seconds
415 V System
50KA
1 seconds
110 V DC System
10 KA
1 seconds
DALIANEAST-CCE-20006DBR-XXX-800 / REV 00
Page 5 of 27
4.01.02.
System Neutral
S.No.
Service
Voltage
Phase
01.
Generation
11 KV
AC, 3Ph
11 KV
AC, 3Ph
02.
HV
Distribution
Earthing
Low Resistance
Non Effectively
Earthed
Solidly earth at
04.
LV Panels
415V
AC, 3Ph
transformer star
point
05.
LV Motors
415V
AC, 3Ph
Earthed
230V
AC,1Ph&N
Earthed
AC, 1Ph&N
Earthed
Lighting /
Space
06.
heater
Circuits
4.01.03.
The
07.
UPS
230V
08.
DC System
110V DC
system
details
at
DC (2 Wires) Unearthed
various
utilization
equipment
Sl.
Service
No.
01.
02.
03.
Voltage
Control Voltage
(HT Panel)
Aux. Voltage
110V DC
Remarks
Protection, Breaker control
and indication
230 V UPS
Metering
Control Voltage
110V DC /
(PCC)
AC
and indication
(HT Panel)
DALIANEAST-CCE-20006DBR-XXX-800 / REV 00
Page 6 of 27
04.
05.
06.
07.
Aux. Voltage
(PCC)
Control Voltage
(MCC)
110 V AC
230V AC
Metering
Breaker control and its
indication
Aux. Voltage
110V AC (2
(MCC)
Wire)
indication
Aux.Voltage
240 V
(MCC)
AC (2 Wire)
etc.
5.00.00.
System Configuration
5.01.00.
5.02.00.
Once the STG is started, the incomer breaker of the generator feeder
connecting to the 11 kV switchgear at CPP can be closed i.e. the generator
will be synchronized with the start-up supply source. When the STG is in
service it will feed its own auxiliary loads and excess power will be
evacuated through evacuation breaker.
DALIANEAST-CCE-20006DBR-XXX-800 / REV 00
Page 7 of 27
6.00.00.
Equipment Design
6.01.00.
Generator:
The generator will be 2 poles, 50Hz, star connected, 3 phase type and it is
designed for continuous operation at its rated output of 25 MW at 0.8pf.
The cooling system will be closed air circuit water cooled (CACW) type.
6.02.00.
AVR panel:
The excitation system shall be with Microprocessor based Digital AVR with
2 nos auto channel and 2 nos manual channel. The digital Auto excitation
regulator will be fed through excitation transformer.
6.03.00.
LASCPT PANEL
Surge Capacitor
: 12kV, 0.25F
Lightening arrestor
: 12kV, 10kA
DALIANEAST-CCE-20006DBR-XXX-800 / REV 00
Page 8 of 27
Sl.No
PTs
CORE 1
CORE 2
CORE 3
CL 3P, 100VA
CL 3P , 100VA
(For GPR-2)
(For Generator
CL 3P , 100VA
CL 3P , 100VA
(For GPR-1)
CL 0.2, 100VA
1
PT 1
PT 2
Panel)
3
6.04.00.
PT 3
CL 0.2, 100VA
CL 3P , 100VA
CL 3P , 100VA
(Spare PT)
(Spare)
(Spare)
(Spare)
NGR Panel :
Resistance
Vacuum contactor
: 12kV, 400A
DALIANEAST-CCE-20006DBR-XXX-800 / REV 00
Page 9 of 27
CTs
RATIO
CORE 1
CORE 2
CORE 3
CL : 0. 2, 10VA
CT-1
100 / 1A
(Generator
CL:5P20,10VA
CL:5P20,10VA
Metering Cum
(GPR-1)
( For GPR-2)
Syn Panel)
CL : 0. 2, 30VA , CL : PS , KPV
CT - 2
2500 / 1A
Imag 15 (For
AVR Metering)
2)
CL : 0. 2, 30VA ,
CT - 3
2500 / 1A
Imag 15
(Spare)
CL : PS , KPV
250 (For GPR-1)
CL : PS , KPV
CL : 0. 2, 30VA , 250 (For
CT - 4
2500 / 1A
Imag 15
Generator
(Spare)
Metering cum
Syn Panel)
6.05.00.
DALIANEAST-CCE-20006DBR-XXX-800 / REV 00
Page 10 of 27
6.05.01.
DALIANEAST-CCE-20006DBR-XXX-800 / REV 00
Page 11 of 27
6.06.00.
and
Auto/Manual
Generator
selector
incomer
switch
breaker
in
will be
Generator
provided
Control,
through
metering
&
6.07.00.
11 KV, 3 Phase 3200 Amps, Segregated Phase Bus dud (SPBD) shall be
provided for generator Phase terminal to LASCPT Panel and Generator
Neutral terminal lo NGR panel. Maximum allowable temperature rise on
bus duct shall be 40 deg C and enclosure shall be 25 deg C. The degree of
protection for enclosure shall be IP55.
DALIANEAST-CCE-20006DBR-XXX-800 / REV 00
Page 12 of 27
6.08.00.
6.08.01.
6.08.02.
Type
Service
Indoor
Rated voltage
11kV
rated current
3200A
Copper
Degree of protection
VCB
O-0.3sec-CO-3min-CO
Closing mechanism at CB
FEEDER DETAILS
Bus PT 1 NO
The protections envisaged for different feeders are listed below. Main
protective relays will be Numerical fixed type. However auxiliary relays will
be electromechanical type only.
A) 11 KV Incomer feeders:
DALIANEAST-CCE-20006DBR-XXX-800 / REV 00
Page 13 of 27
DC Fail relay(27D)
DC Fail relay(27 D)
DC Fail relay(27 D)
D) Bus PT feeder
DC Fail relay(27 D)
DALIANEAST-CCE-20006DBR-XXX-800 / REV 00
Page 14 of 27
6.08.03.
Metering:
6.09.00.
LV Transformers:
6.09.01.
LV Auxiliary Transformers
Auxiliary Transformers are Oil impressed type, 2.5 MVA rated ,2 x 100%
capacity, 11/ 0.433kV, ONAN cooled, Dyn11 vector group, 8.25 %
impedance, 99.5% efficiency at 50% load, 99.0% efficiency at 100% load,
outdoor type. This transformer will be provided with off load tap switch
having +5 to -5 % taps in steps of 2.5% on HV side. The LV side neutral
of this transformer will be solidly grounded.
The following assumptions as per normal power plant practice had been
made in sizing the transformer
Load factor
Coincidence factor = 0.05 for motorized valves, 0.5 for AC & heater
unit, 1 for continuous load
General:
The flux density considered is 1.67 T for the core and yoke at the rated
MVA, voltage & frequency. The transformer & all its accessories including
CTs shall be designed to withstand without any injury the thermal &
mechanical effects caused due to short circuit fault. Transformers shall
withstand, without injurious heating, the combined voltage & frequency
fluctuations.
DALIANEAST-CCE-20006DBR-XXX-800 / REV 00
Page 15 of 27
Double float type buchholz relay having alarm and trip contacts
Dial type (150 mm) oil temperature indicator with alarm and trip
contacts.
Jacking pads.
6.09.02.
Earthing Terminals
Lifting Lugs
Radiators
Lighting Transformers:
6.10.00.
NSPBD:
415 V, 3 Phase + Neutral 4000 Amps TPN Sand witch type Non
Segregated Phase Bus duct (NSPBD) shall be considered for connecting
DALIANEAST-CCE-20006DBR-XXX-800 / REV 00
Page 16 of 27
6.11.00.
6.11.01.
LTPCC:
Type
Fixed type
Service
Indoor
Current Rating
4000 A
Protection
IP4X
Busbar material
Aluminium
0.8A/mm2
Incomers
Closing/tripping of ACB
110 V DC / AC
a) LTPCC Incomers:
DALIANEAST-CCE-20006DBR-XXX-800 / REV 00
Page 17 of 27
Metering:
Energy meter shall be provided in the all incoming and outgoing feeders of
PCC. Analog type ammeter and voltmeter with selector switch shall be
provided on the incoming feeders. For Bus PT feeders voltmeter with
selector switch will be provided
6.11.02.
MCC
MCC shall be double front as per the contract. MCC shall have uniform
height placed side by side.
Type
Service
Indoor
Current Rating
as per requirement
Enclosure
IP 52
Rated voltage
415V
0.8A/mm2
Aluminum
Incomers
Two
TG MCC
WTP MCC
APFC MCC
Emergency MCC
DALIANEAST-CCE-20006DBR-XXX-800 / REV 00
Page 18 of 27
6.12.00.
415V Motors
Local Push Button Station (LPBS) shall be provided for all the motors and
MOV's (for VFD LPBS shall have RPM meter and raise lower push buttons).
For motors 3.7 kW and above ,LPBS shall be equipped with Ammeter.
For above 22kW motors ammeters shall be provided. For above 30kW
motors Space heaters shall be provided. For 75kW and above motors
bearing & winding temperature monitoring shall be provided.
7.00.00.
DC system
One no 800AH 1X100% (2V X 55), 110 Volts , 2 wire ungrounded system ,
four (4) hours back up Vented type Plante Lead acid Battery of adequate
capacity with their Float cum Boost charger shall be considered for DC
loads with associated FRP battery racks etc..
110 V DC power supply is the most reliable source of power supply for
control, protection, interlock and annunciation requirements of the power
station.
DALIANEAST-CCE-20006DBR-XXX-800 / REV 00
Page 19 of 27
Float charger:
Continuous DC load + trickle charging current of battery +15 % margin.
Boost charger
Boost charging current of battery+ continuous DC load.
Battery Charger
7.00.01.
Service - Indoor
Degree of protection - IP 42
DC Distribution Board
Service - Indoor
Degree of protection - IP 42
DALIANEAST-CCE-20006DBR-XXX-800 / REV 00
Page 20 of 27
8.00.00.
2 Nos x 500 WAR , 113 STEPS (50 KVAR OF -10 Nos ) capacitor units shall
be hermetically sealed type, with two bushings and shall be designed to
carry a minimum of 1 .5 times the rated current at 110% of rated voltage
and 1.35 times rated reactive power, continuously. The capacitors should
be of non PCB type, suitable for operation in tropical areas
9.00.00.
Cabling System:
9.01.00.
Cables:
9.01.01.
HT Power cable
operating
temperature
under
normal
condition
for
XLPE
DALIANEAST-CCE-20006DBR-XXX-800 / REV 00
Page 21 of 27
9.01.02.
LT Power cable
LT power cable used for 415V AC, 230VAC, 110V AC & 110 V DC system
will be 1.1kV (E) grade, stranded aluminum conductor with FRLS, XLPE
insulated, not extruded PVC inner sheath, G.S. Flat/round wire with
armoured, extruded PVC (ST-2) outer sheath conforming to IS 7098 partI. Maximum operating temperature under normal condition for XLPE
insulation cables will be 90C. Cables less than 10 sq.mm shall be of
copper conductor. DC Power cables for EOP will be UNINYVIN CABLE &
Cable for UPS will be Copper armour cable. Separate earthing cable shall
be laid from each VFD to respective Motor.
9.01.03.
Control cable
Control cables will be 1100V (E) grade, multi-core with stranded 1.5 mm
and copper conductor with FRLS, PVC insulated, extruded PVC inner
sheath, G.S. flat / round wire armoured and extruded sheath of PVC (ST1) with numbering of all cores, conforming to IS 1554 part-I/IS 5831.
9.02.00.
Cable Tagging
Cable tagging shall be at both end & at every 20 meter considered for all
cable. Anodised type tagging plate will be provided.
9.03.00.
Cable Trays
DALIANEAST-CCE-20006DBR-XXX-800 / REV 00
Page 22 of 27
Separate cable tray for HT Power, LT Power, Control Cable, Instt. Analog
Input/output cable each, Instt. Digital Input/output cables each &
Compensating Cable shall be considered.
10.00.00.
llumination System:
10.01.00.
Basic Concept
The system provides lighting and service power at 240V, single phase 50
Hz to receptacles and single phase feeders in plant areas. The plant
illumination system
DC lighting.
10.02.00.
DALIANEAST-CCE-20006DBR-XXX-800 / REV 00
Page 23 of 27
10.03.00.
Emergency DC Lighting
Critical DC lighting will be provided with bulk head lamps at Cable Cellar
MCC room, CCR, TG house, stair cases, steam drums on all boilers & Start
up vents. This DC lighting will remain OFF normally and will be switched
ON automatically when main AC supply fails. The power supply for lighting
will be fed from 110V DCDB. FL DC lamp with integral battery shall be
provided for Boiler area MCC room.
10.04.00.
1 Phase & 3 Phase power receptacles will be provided for alternative floors
of Boiler area, each floor ACC areas and at least 3 Nos in TG building, MCC
room, cable cellar area. 3 Phase Welding Sockets will be provided at each
stage of boiler, TG Floor & as required in ACC area etc. 24 Volt AC power
receptacles with transformers and proper distribution at all location of
boilers, ACC floors will be provided.
10.05.00.
Area Description
Cable gallery,
Transformer Area
Compressor room,
Battery charger room,
P&V room & Storeroom
MCC Switchgear room
Battery rooms
Control Rooms & Office
rooms
Type of Fixture
Type of Luminaries
2x28 W Fluorescent
Lamp
2x36 W Fluorescent
Lamp
Corrosion Proof
TG Building Operating
floor
TG Building Staircases
Turbine houses
DALIANEAST-CCE-20006DBR-XXX-800 / REV 00
2x36 W Fluorescent
Lamp
2x28 W Fluorescent
Lamp
1 X 80W HPMV
1x400 W MH Lamp
2x36 W Fluorescent
Lamp
Page 24 of 27
11.00.00.
11.01.00.
Plant Earthing:
1x70 W MH Lamp
1 X 36 W Fluorescent
Lamp
1 x 150 W MH Lamp
1X 100W GLS
2x28 W Fluorescent
Lamp
DALIANEAST-CCE-20006DBR-XXX-800 / REV 00
Page 25 of 27
11.01.01.
Equipment Earthing:
Flat from the main earthing grid to local network and electrical equipment
will be GI flats of suitable size, except for smaller items, which will be
connected using steel wire. However, for portable equipment, if one of the
conductors of the connecting cable/plug socket is earthed, no other earth
connection is required.
An earthing conductor will be installed along the entire length of top most
power cable trays. The tray earth will be connected at various locations to
the station earth grid. The offsite areas will be connected through the
earth flats running along the cable trays. Earth continuity will be provided
for all cable trays & conduits. The following aspects will be addressed
during design, of the equipment earthing system to be adopted.
Trays: 50 mm x 6 mm GI Flat.
DALIANEAST-CCE-20006DBR-XXX-800 / REV 00
Page 26 of 27
11.02.00.
Lightning Protection:
is
required
except
adequate
grounding
connections.
Air
The zone of protection will depend on each structure height, overall shape,
and physical location in relation to other structures.
DALIANEAST-CCE-20006DBR-XXX-800 / REV 00