SUNLIGHT Model AMF 5220 Automatic Mains Failure & Instrumentation System Operators Manual
SUNLIGHT Model AMF 5220 Automatic Mains Failure & Instrumentation System Operators Manual
TABLE OF CONTENTS
Section
Page
INTRODUCTION...............................................................................................5
OPERATION .....................................................................................................6
3.1
3.2
3.3
PROTECTIONS ..............................................................................................10
4.1
4.2
4.3
4.4
4.5
4.6
DESCRIPTION OF CONTROLS.....................................................................16
5.1
TYPICAL LCD DISPLAY SCREENS ................................................................................ 17
5.2
LCD DISPLAY AREAS...................................................................................................... 18
5.3
VIEWING THE INSTRUMENTS ........................................................................................ 19
5.3.1
CANBUS MESSAGES................................................................................................ 20
5.4
VIEWING THE EVENT LOG ............................................................................................. 21
5.5
INDICATORS..................................................................................................................... 22
5.6
CONTROLS....................................................................................................................... 22
PANEL CUT-OUT.............................................................................................................. 27
COOLING .......................................................................................................................... 27
UNIT DIMENSIONS........................................................................................................... 27
FRONT PANEL LAYOUT.................................................................................................. 28
REAR PANEL LAYOUT .................................................................................................... 28
SUNLIGHT Model AMF 5220 Automatic Mains Failure & Instrumentation System Operators Manual
8.2.9
PURCHASING ADDITIONAL CONNECTOR PLUGS FROM SUNLIGHT................. 35
8.3
ELECTRICAL CONNECTIONS TO J1939 ENABLED CONTROLLERS......................... 36
8.3.1
CUMMINS ISB / ISBE................................................................................................. 36
8.3.2
JOHN DEERE............................................................................................................. 37
8.3.3
PERKINS 2800 SERIES ............................................................................................. 38
8.3.4
SCANIA S6 ................................................................................................................. 39
8.3.5
VOLVO TAD12 ........................................................................................................... 40
COMMISSIONING.......................................................................................... 42
9.1.1
PRE-COMMISSIONING ............................................................................................. 42
10
11
12
13
APPENDIX .................................................................................................. 48
SUNLIGHT Model AMF 5220 Automatic Mains Failure & Instrumentation System Operators Manual
1 INTRODUCTION
The AMF 5220 automatic mains failure module has been designed to allow the OEM to meet most of the industrys
complex specifications. It has been primarily designed to monitor the mains (utility) supply, starting the generator
automatically should it fall out of limits. Transfer of the load is automatic upon a mains supply failure. If required the
generator and can be started and stopped manually, and if required, the user can transfer the load to the generator
either manually (via external push-buttons) or automatically. The user also has the facility to view all the system
operating parameters via the LCD display.
The AMF 5220 module monitors the mains (utility) supply indicating the status of the mains on the modules integral
LCD id splay. Additionally the module monitors the engine, indicating the operational status and fault conditions,
automatically shutting down the engine and giving a true first up fault condition of an engine failure by a flashing
common alarm LCD indicator. The exact failure mode is indicated by combined hidden til lit LEDs and the LCD
display on the front panel.
The powerful microprocessor contained within the module allows for a range of complex features to be incorporated
as standard:
Graphical Icon based LCD display (excluding the need for translations and languages).
Voltage, Current and Power monitoring.
Engine parameter monitoring.
Fully configurable inputs for use as alarms or a range of different functions.
Extensive range output functions using built in relay outputs or relay expansion available.
Selective operational sequences, timers and alarm trips can be altered by the customer via a PC using the 5200
series configuration software and P810 interface. Additionally, a subset of this information can be adjusted from the
modules front panel configuration editor.
The module is housed in a robust plastic case for front panel mounting. Connections to the module are via locking
plug and sockets.
CAUTION!
WARNING!
SUNLIGHT Model AMF 5220 Automatic Mains Failure & Instrumentation System Operators Manual
3 OPERATION
The following description details the sequences followed by a module containing the standard factory configuration.
Always refer to your configuration source for the exact sequences and timers observed by any particular module in
the field.
FIG 1
3.1
icon. When in panel lock, changing module modes will not be possible. Viewing the instruments
Should the mains (utility) supply fall outside the configurable limits for
longer than the period of the mains transient delay timer, the mains
(utility) failure indicator will illuminate and the mains (utility) available
GREEN indicator LED extinguishes. Additionally, while in AUTO mode,
the remote start input (if configured) is monitored. If active, the
Remote Start Active indicator (if configured) illuminates.
Overvoltage
Undervoltage
Overfrequency
Underfrequency
SUNLIGHT Model AMF 5220 Automatic Mains Failure & Instrumentation System Operators Manual
Whether the start sequence is initiated by mains (utility failure) or by remote start input, the follow sequence is
followed :
To allow for short term mains supply transient conditions or false remote start signals, the Start Delay timer is
initiated. After this delay, if the pre-heat output option is selected then the pre-heat timer is initiated, and the
corresponding auxiliary output (if configured) will energise.
NOTE:- If the mains supply returns within limits, ( or the Remote Start signal is removed if the
start sequence was initiated by remote start) during the Start Delay timer, the unit will return to a
stand-by state.
After the above delays the Fuel Solenoid is energised, then one second later, the Starter Motor is engaged.
The engine is cranked for a pre-set time period. If the engine fails to fire during this cranking attempt then the starter
motor is disengaged for the pre-set rest period. Should this sequence continue beyond the set number of attempts,
the start sequence will be terminated and
Fail to Start
symbol.
When the engine fires, the starter motor is disengaged and locked out at a pre-set frequency from the Alternator
output. Alternatively a Magnetic Pickup mounted on the flywheel housing can be used for speed detection (This is
selected by PC using the 5200 series configuration software). Rising oil pressure can also be used to disconnect
the starter motor, however it cannot be used for underspeed or overspeed detection.
After the starter motor has disengaged, the Safety On timer is activated, allowing Oil Pressure, High Engine
Temperature, Under-speed, Charge Fail and any delayed Auxiliary fault inputs to stabilise without triggering the
fault.
Once the engine is running, the Warm Up timer, if selected is initiated, allowing the engine to stabilise before
accepting the load.
If an auxiliary output has been selected to give a load transfer signal, this would then activate.
NOTE:-A load transfer will not be initiated until the Oil Pressure has risen. Thus preventing
excessive wear on the engine.
On the return of the mains supply, (or removal of the Remote Start signal if the set was started by remote signal) ,
the Stop delay timer is initiated, once it has timed out, the load Transfer signal is de-energised, removing the load.
The Cooling timer is then initiated, allowing the engine a cooling down period off load before shutting down. Once
the Cooling timer expires the Fuel Solenoid is de-energised, bringing the generator to a stop.
Should the mains supply fall outside limits again (or the Remote Start signal be re-activated) during the cooling
down period, the set will return on load.
SUNLIGHT Model AMF 5220 Automatic Mains Failure & Instrumentation System Operators Manual
3.2
MANUAL OPERATION
NOTE:- If a digital input configured to panel lock is active, the LCD will display the
in panel lock, changing module modes will not be possible. Viewing the instruments
affected by panel lock.
icon. When
is NOT
(indicated by an LED indicator beside the button), pressing the START (I) button will initiate the start sequence.
NOTE:- There is no Start Delay in this mode of operation.
If the pre-heat output option is selected this timer is then initiated, and the auxiliary output selected is energised.
After the above delay the Fuel Solenoid is energised, then the Starter Motor is engaged.
The engine is cranked for a pre-set time period. If the engine fails to fire during this cranking attempt then the starter
motor is disengaged for the pre-set rest period. Should this sequence continue beyond the set number of attempts,
the start sequence will be terminated and Fail to Start
shutdown
indicator.
When the engine fires, the starter motor is disengaged and locked out at a pre-set frequency from the Alternator
output. Alternatively a Magnetic Pickup mounted on the flywheel housing can be used for speed detection (This is
selected by PC using the 5200 series configuration software). Rising oil pressure can also be used to disconnect
the starter motor, however it cannot be used for underspeed or overspeed detection.
After the starter motor has disengaged, the Safety On timer is activated, allowing Oil Pressure, High Engine
Temperature, Under-speed, Charge Fail and any delayed Auxiliary fault inputs to stabilise without triggering the
fault.
Once the engine is running, the Warm Up timer, if selected, is initiated, allowing the engine to stabilise before it can
be loaded.
The generator will run off load, unless the mains supply fails or a Remote Start on load signal is applied. If Close
generator has been selected as a control source, the appropriate auxiliary output will then activate.
The generator will continue to run On load regardless of the state of the mains supply or remote start input until the
Auto mode is selected.
If Auto mode is selected, and the mains supply is healthy with the remote start on load signal not active, then the
Remote Stop Delay Timer begins, after which, the load is disconnected. The generator will then run off load
allowing the engine a cooling down period.
Selecting STOP (O) de-energises the FUEL SOLENOID, bringing the generator to a stop.
SUNLIGHT Model AMF 5220 Automatic Mains Failure & Instrumentation System Operators Manual
3.3
TEST OPERATION
NOTE:- If a digital input configured to panel lock is active, the LCD will display the
in panel lock, changing module modes will not be possible. Viewing the instruments
affected by panel lock.
icon. When
is NOT
by an LED indicator beside the button), pressing the START (I) button will initiate the start sequence.
NOTE:- There is no Start Delay in this mode of operation.
If the pre-heat output option is selected this timer is then initiated, and the auxiliary output selected is energised.
After the above delay the Fuel Solenoid is energised, then the Starter Motor is engaged.
The engine is cranked for a pre-set time period. If the engine fails to fire during this cranking attempt then the starter
motor is disengaged for the pre-set rest period. Should this sequence continue beyond the set number of attempts,
the start sequence will be terminated and Fail to Start
shutdown
indicator.
When the engine fires, the starter motor is disengaged and locked out at a pre-set frequency from the Alternator
output. Alternatively a Magnetic Pickup mounted on the flywheel housing can be used for speed detection (This is
selected by PC using the 5200 series configuration software). Rising oil pressure can also be used to disconnect
the starter motor, however it cannot be used for underspeed or overspeed detection.
After the starter motor has disengaged, the Safety On timer is activated, allowing Oil Pressure, High Engine
Temperature, Under-speed, Charge Fail and any delayed Auxiliary fault inputs to stabilise without triggering the
fault.
Once the engine is running, the Warm Up timer, if selected, is initiated, allowing the engine to stabilise before it can
be loaded.
The generator will continue to run On load regardless of the state of the mains supply or remote start input until the
Auto mode is selected.
If Auto mode is selected, and the mains supply is healthy with the remote start on load signal not active, then the
Remote Stop Delay Timer begins, after which, the load is disconnected. The generator will then run off load
allowing the engine a cooling down period.
Selecting STOP (O) removes the Close Generator output (if configured) and de-energises the FUEL SOLENOID,
bringing the generator to a stop.
SUNLIGHT Model AMF 5220 Automatic Mains Failure & Instrumentation System Operators Manual
4 PROTECTIONS
The module will indicate that an alarm has occurred in several ways;
The LCD display will indicate a common alarm either :
(warning),
(shutdown) or
(electrical trip)
If appropriate, the LCD display or LED indicators will display the
appropriate alarm icon i.e. for battery charging failure :
NOTE:- Alarm icons in the LED display area are hid until lit. This means that the display area
appears totally clear, and free from clutter. The advantage of this is that when an alarm does occur,
the respective LED icon will illuminate on the otherwise blank fascia. This makes alarm identification
much clearer.
In the event of a warning alarm the LCD will display the appropriate icon. If a shutdown then occurs the module will
display the appropriate icon. The original warning alarm icon will remain displayed.
Example:-
Followed by.
Underspeed and Shutdown alarm Icons are displayed flashing. The original warning will remain displayed as long at
the triggering conditions remain. Any subsequent warnings or shutdowns that occur will be displayed steady,
therefore only the first-up shutdown will appear flashing.
10
SUNLIGHT Model AMF 5220 Automatic Mains Failure & Instrumentation System Operators Manual
4.1
WARNINGS
Warnings are non-critical alarm conditions and do not affect the operation of the generator system, they serve to
draw the operators attention to an undesirable condition.
In the event of a warning alarm the LCD will display:-
BATTERY CHARGE FAILURE, if the module does not detect a voltage from the warning light terminal on the
auxiliary charge alternator the
icon will illuminate.
BATTERY LOW VOLTAGE, if the module detects that the plant DC supply has fallen below the low volts setting
level, the module will display:-
V
The Battery Low Voltage alarm is delayed by the Low DC Volts Delay timer.
BATTERY HIGH VOLTAGE, if the module detects that the plant DC supply has risen above the high volts setting
level, the module will display:-
V
The Battery High Voltage alarm is delayed by the High DC Volts Delay timer.
FAIL TO STOP, If the module detects the engine is still running when the Fail to stop timer expires, then the
module will display:-
NOTE:- Fail to Stop could indicate a faulty oil pressure sender - If engine is at rest check oil
sender wiring and configuration.
AUXILIARY INPUTS, if an auxiliary input has been configured as a warning the appropriate LCD segment will be
displayed:-
!
LOW FUEL LEVEL. If the fuel level detected by the fuel level sender falls below the low fuel level setting, a warning
will occur.
The
4.2
ANALOGUE PRE-ALARMS
The following alarms are termed pre-alarms as they pre warn the operator of a potentially more serious alarm
condition. For instance, if the engine temperature rises past the pre alarm level, a warning condition will occur to
notify the operator. If the temperature falls below this level, then the alarm ceases, and the set will continue to run
as normal. However if the temperature continues to rise until the coolant temperature trip point is reached, the
warning is escalated and a high coolant temperature shutdown is initiated.
During a pre-alarm condition, the warning symbol
icon:
LOW OIL PRESSURE, if the module detects that the engine oil pressure has fallen below the low oil pressure prealarm setting level after the Safety On timer has expired, a warning will occur.
The
icon will illuminate.
SUNLIGHT Model AMF 5220 Automatic Mains Failure & Instrumentation System Operators Manual
HIGH ENGINE TEMPERATURE if the module detects that the engine coolant temperature has exceeded the high
engine temperature pre-alarm setting level after the Safety On timer has expired, a warning will occur.
The
OVERSPEED, if the engine speed exceeds the pre-alarm trip a warning is initiated.
The
icon will illuminate.
Overspeed is not delayed, it is an immediate warning.
UNDERSPEED, if the engine speed falls below the pre-set pre-alarm after the Safety On timer has expired, a
warning is initiated.
The
GENERATOR HIGH FREQUENCY if the module detects a generator output frequency in excess of
the pre-set pre-alarm, a warning is initiated.
The
icon will illuminate.
Generator High Frequency is not delayed, it is an immediate warning.
GENERATOR LOW FREQUENCY, if the module detects a generator output frequency below the
pre-set pre-alarm after the Safety On timer has expired, a warning is initiated.
The
GENERATOR HIGH VOLTAGE if the module detects a generator output voltage in excess of the pre-set trip a
shutdown is initiated.
The V icon will illuminate.
High voltage is not delayed, it is an immediate shutdown.
GENERATOR LOW VOLTAGE if the module detects a generator output voltage below the below the pre-set prealarm after the Safety On timer has expired, a warning is initiated.
The
CAN ECU ERROR If the module is configured for J1939 operation and receives an error message from
the engine control unit, Can ECU fail is shown on the modules display and a warning alarm is generated.
Usually, an associated alarm code is also displayed, detailing the exact alarm detected. For details on
these code meanings, refer to the ECU instructions provided by the engine manufacturer.
4.3
GENERATOR HIGH CURRENT, if the module detects a generator output current in excess of the pre-set trip a
warning is initiated.
The
icon will illuminate.
If this high current condition continues for an excess period of time, then the alarm is escalated to a shutdown
condition. For further details of the high current alarm, please see High Current Shutdown Alarm.
12
SUNLIGHT Model AMF 5220 Automatic Mains Failure & Instrumentation System Operators Manual
4.4
SHUTDOWNS
Shutdowns are latching and stop the Generator. The alarm must be cleared, and the fault removed to reset the
module.
In the event of a shutdown alarm the LCD will display:(flashing).
The appropriate icon will also be displayed flashing
NOTE:- The alarm condition must be rectified before a reset will take place. If the alarm
condition remains it will not be possible to reset the unit (The exception to this is the Low Oil
Pressure alarm and similar delayed alarms, as the oil pressure will be low with the engine at rest).
Any subsequent warnings or shutdowns that occur will be displayed steady, therefore only the firstup shutdown will appear flashing.
FAIL TO START, if the engine does not fire after the pre-set number of attempts has been made a shutdown will be
initiated.
The
icon will illuminate.
EMERGENCY STOP, removal of the +ve DC Supply from the Emergency Stop input initiates the following
sequence, firstly it will initiate a controlled shutdown of the Generator and prevent any attempt to restart the
Generator until the Emergency Stop push-button has been reset. Secondly it removes the +ve DC supply from both
the Fuel Solenoid and Starter Solenoid.
The
LOW OIL PRESSURE, if the module detects that the engine oil pressure has fallen below the low oil pressure trip
setting level after the Safety On timer has expired, a shutdown will occur.
icon will illuminate.
The
HIGH ENGINE TEMPERATURE if the module detects that the engine coolant temperature has exceeded the high
engine temperature trip setting level after the Safety On timer has expired, a shutdown will occur.
The
OVERSPEED, if the engine speed exceeds the pre-set trip a shutdown is initiated.
The
icon will illuminate.
Overspeed is not delayed, it is an immediate shutdown.
NOTE:-During the start-up sequence the overspeed trip logic can be configured to allow an extra
trip level margin. This is used to prevent nuisance tripping on start-up - Refer to the 5200 series
configuration software manual under heading Overspeed Overshoot for details.
UNDERSPEED, if the engine speed falls below the pre-set trip after the Safety On timer has expired, a shutdown is
initiated.
The
SUNLIGHT Model AMF 5220 Automatic Mains Failure & Instrumentation System Operators Manual
GENERATOR HIGH FREQUENCY if the module detects a generator output frequency in excess of
the pre-set trip a shutdown is initiated.
The
icon will illuminate.
Generator High Frequency is not delayed, it is an immediate shutdown.
GENERATOR LOW FREQUENCY, if the module detects a generator output frequency below the
pre-set trip after the Safety On timer has expired, a shutdown is initiated.
The
GENERATOR HIGH VOLTAGE if the module detects a generator output voltage in excess of the pre-set trip a
shutdown is initiated.
The V icon will illuminate.
High voltage is not delayed, it is an immediate shutdown.
GENERATOR LOW VOLTAGE if the module detects a generator output voltage below the below the pre-set trip
after the Safety On timer has expired, a shutdown is initiated.
The
OIL PRESSURE SENDER OPEN CIRCUIT, if the module detects a loss of signal from the oil pressure sender
(open circuit) a shutdown is initiated. The LCD will indicate:(Steady) (And ----- on the engine oil pressure instrument). Sender failure is not delayed, it is an immediate
shutdown.
AUXILIARY INPUTS, if an auxiliary input has been configured as a shutdown the appropriate LCD segment will be
displayed:-
!
LOSS OF SPEED SIGNAL, if the speed sensing signal is lost during cranking, a shutdown is initiated.
The
icon will illuminate. (Steady) (And ----- on the engine RPM instrument).
NOTE:- This will only occur if the speed sensing signal is lost during cranking or during the safety
on timer. If the signal is lost during normal operation the Generator will shutdown with an Underspeed alarm.
CAN DATA FAIL If the module is configured for J1939 operation and does not detect data on the engine
CANbus datalink, a shutdown will occur and Can data fail is shown on the modules display
CAN ECU FAIL If the module is configured for J1939 operation and receives a fail message from the
engine control unit, the engine is shutdown and Can ECU fail is shown on the modules display. Usually,
an associated failure code is also displayed, detailing the exact failure detected. For details on these code
meanings, refer to the ECU instructions provided by the engine manufacturer.
14
SUNLIGHT Model AMF 5220 Automatic Mains Failure & Instrumentation System Operators Manual
4.5
GENERATOR HIGH CURRENT, if the module detects a generator output current in excess of the pre-set trip a
warning is initiated. This warning will continue for a period of time depending upon the level of overload that the
generator is subjected to, and the configuration setting for Generator High Current in the 5200 series configuration
software.
For instance the factory default settings for Generator High Current allow for a loading of the generator to 110% for
one hour. That is to say if the generator load level exceeds the trip point by 10%, a warning alarm will occur while
the overload condition exists. If the load level does not drop to normal levels within one hour, the set is stopped, the
5220 module displaying either shutdown alarm or electrical trip alarm depending upon module configuration.
Additionally, the
NOTE:- Higher overload levels will result in a faster acting shutdown condition. For instance with
the factory default configuration, an overload level twice that of the trip level ( typically 200%) will
result in a Generator High Current shutdown condition after 36 seconds.
For details of the relationship between the overload and the shutdown time, please see the Appendix
section of this manual.
4.6
ELECTRICAL TRIPS
Electrical trips are latching and stop the Generator but in a controlled manner. On initiation of the electrical trip
condition the module will de-energise the Close Generator Output to remove the load from the generator. Once
this has occurred the module will start the Cooling timer and allow the engine to cool off-load before shutting down
the engine. The alarm must be accepted and cleared, and the fault removed to reset the module.
AUXILIARY INPUTS, if an auxiliary input has been configured as an electrical trip the appropriate LCD segment will
be displayed:-
!
GENERATOR HIGH CURRENT. If the module detects a generator output current in excess of the pre-set trip a
warning is initiated.
The
icon will illuminate.
If this high current condition continues for an excess period of time, then the alarm is escalated to either a shutdown
or electrical trip condition (depending upon module configuration). For further details of the high current alarm,
please see High Current Shutdown Alarm.
SUNLIGHT Model AMF 5220 Automatic Mains Failure & Instrumentation System Operators Manual
5 DESCRIPTION OF CONTROLS
The following section details the function and meaning of the various controls on the module.
Scroll
Configure
/ log
Stop
Manual
Test
FIG2
16
Auto
Start
SUNLIGHT Model AMF 5220 Automatic Mains Failure & Instrumentation System Operators Manual
5.1
INSTRUMENTS
The LCD displays the various engine parameters such as ENGINE
SPEED, OIL PRESSURE, HOURS RUN, etc.
Each instrument is displayed with the appropriate units of measure.
In this example, the values being displayed are Generator
phase to neutral L1-N, AC
voltages V.
STATUS ICONS
The LCD also displays the status of the controller by showing (for
example) an hourglass symbol when a timer is in progress or by
displaying a common alarm symbol. This display is indicating that a
timer is in progress and a warning alarm is present. See the
Protections section of this manual for details of the alarms.
In this example the values being displayed are the three
generator
USER DEFINED
INDICATIONS
AC
currents A
SUNLIGHT Model AMF 5220 Automatic Mains Failure & Instrumentation System Operators Manual
5.2
Instrument values
Alarm icons
Status icons
18
SUNLIGHT Model AMF 5220 Automatic Mains Failure & Instrumentation System Operators Manual
5.3
It is possible to manually scroll to display the different instruments by repeatedly operating the scroll button. Once
selected the instrument will remain on the LCD display until the user selects a different instrument or after a period
of inactivity the module will revert to the initial display (Hz/RPM).
Instrument Page Order: Generator RPM / Frequency (Hz)
Generator AC Voltage Line-Neutral
Generator AC Voltage Line-Line
Oil Pressure
Coolant temperature
Fuel level (%)
Engine Hours Run
DC Battery Voltage
AC Line Current
Total kW
Total VA
AC phase angle (cos )
CanBus J1939 messages (optional)
Mains (Utility) Frequency (Hz)
Mains (Utility) AC Voltage Line-Neutral
Mains (Utility) AC Voltage Line-Line
Manually Selecting an Instrument
Initial display (Hz/RPM)
Pressing the
button again will scroll through each individual instrument eventually returning to the original
instrument displayed.
NOTE:-Once selected the instrument will remain on the LCD display until the user selects a
different instrument or after a period of inactivity the module will revert to the initial display.
SUNLIGHT Model AMF 5220 Automatic Mains Failure & Instrumentation System Operators Manual
5.3.1
CANBUS MESSAGES
On J1939 enabled 52xx controllers connected to a CanBus ECU, alarm status messages are transmitted to the
52xx controller and displayed on the CanBus message instrumentation page.
Can alarm message
Suspect Parameter Number (SPN) = 102
Failure Mode Indicator (FMI) = 16
NOTE:- For details on these code meanings, refer to the ECU instructions provided by the engine
manufacturer.
NOTE:- When using 52xx configuration and instrumentation PC software, hovering the mouse
cursor over the SPN/FMI numbers will display the J1939 messages where appropriate.
20
SUNLIGHT Model AMF 5220 Automatic Mains Failure & Instrumentation System Operators Manual
5.4
Press down
button.
SUNLIGHT Model AMF 5220 Automatic Mains Failure & Instrumentation System Operators Manual
5.5
INDICATORS
5.6
(warning) or
(shutdown)
CONTROLS
STOP/RESET
This button places the module into its Stop/reset mode. This will clear any alarm conditions for
which the triggering criteria have been removed. If the engine is running and this position is selected,
the module will automatically instruct the changeover device to un-load the generator (Load transfer
becomes inactive (if used)). The fuel supply will be removed and engine will be brought to a
standstill. Should a remote start signal be present while operating in this mode, a remote start will
not occur.
MANUAL
This mode is used to allow manual control of the generator functions. Once in Manual mode the
module will respond to the start (I) button and start the engine and run off load. If the engine is
running off-load in the Manual mode and a remote start signal becomes present, the module will
automatically instruct the changeover device to place the generator on load (Load transfer becomes
active (if used)). Should the remote start signal then be removed the generator will remain on load
until either the STOP/RESET or AUTO positions is selected.
AUTO
This button places the module into its Automatic mode. This mode allows the module to control the
function of the generator automatically. The module will monitor the remote start input and once a
start condition is signalled the set will be automatically started and placed on load (Load transfer
becomes active (if used)). If the starting signal is removed the module will automatically transfer the
load from the generator and shut the set down observing the stop delay timer and cooling timer as
necessary. The module will then await the next start event. For further details please see the more
detailed description of Auto Operation earlier in this manual.
TEST
This button places the module into its Test mode. This mode allows the operator to perform an on
load test of the system. Once in Test mode the module will respond to the start (I) button and start
the engine and run on load (Load transfer becomes active (if used)). The generator will continue to
run on load until Auto mode is selected. Then, If the starting signal is removed the module will
automatically transfer the load from the generator and shut the set down observing the stop delay
timer and cooling timer as necessary. The module will then await the next start event.
For further details please see the more detailed description of Test Operation earlier in this manual.
START
This button is only active in MANUAL
or TEST
mode. Pressing this button in manual or
test mode will start the engine and run off load(manual) or on load (test).
22
SUNLIGHT Model AMF 5220 Automatic Mains Failure & Instrumentation System Operators Manual
6.1
and Stop/Reset
@ will
flash to indicate that the module is in configuration mode. Release the Stop/Reset
configure/log
button.
NOTE:- To exit the front panel configuration editor at any time, press the Stop/Reset
have saved any changes you have made by pressing the
button first.
SUNLIGHT Model AMF 5220 Automatic Mains Failure & Instrumentation System Operators Manual
6.1.1
Press the
button to enter edit mode. This is indicated by the flashing parameter. In this example, entering edit
mode will cause the 1.2 value to flash.
When in edit mode, pressing the + or buttons will adjust the parameter to the desired value. Press the
button to save the value. The value will stop flashing to confirm that it has been saved.
To select another value to edit, press the + button :
The next parameter being displayed in this example
is the Low Oil Pressure shutdown, being indicated by
the illuminated oil can.
The shutdown symbol
is indicating that it is the
shutdown (trip) parameter that is being displayed.
Continuing to press the + or
Parameter
Type
Analogue senders
Low Pressure
Pre Alarm
Low Pressure
Trip
High Temperature
Pre Alarm
High Temperature
Trip
Calendar
Timers
Generator output
24
buttons will cycle through the adjustable parameters in the following order :
Config Section
Icons displayed
Fuel Level %
Pre Alarm
Date/time
Date/time
Timer (secs)
Start delay
Timer (secs)
Preheat
Timer (secs)
Crank attempt
Timer (secs)
Crank rest
Timer (secs)
Safety delay
Timer (secs)
Overspeed overshoot
Timer (secs)
Warming up
Timer (secs)
Transfer delay
Timer (secs)
Return delay
Timer (secs)
10
Cooling run
Timer (secs)
11
Timer (secs)
12
Trip
Trip
V
V
Trip
Trip
Trip
Pre Alarm
Pre Alarm
Trip
Trip
Pre Alarm
Pre Alarm
Trip
Delayed Overcurrent %
Trip
V
V
V
V
SUNLIGHT Model AMF 5220 Automatic Mains Failure & Instrumentation System Operators Manual
Front panel configurable items continued:
Config Section
Parameter
Type
Engine speed
Trip
DC Voltages
Pre Alarm
Pre Alarm
Icons displayed
Trip
Low DC Voltage
Warning
High DC Voltage
Warning
Warning
NOTE:- The timers are numbered to enable them to be identified when in configuration mode. In
the following example timer number 2 (Start delay from the above list) is currently set to 5.0
seconds. Ie the hour glass
indicates that it is a timer being displayed. The 2 indicates that it is
timer number 2 (Start delay). The current setting is 5.0 (seconds).
SUNLIGHT Model AMF 5220 Automatic Mains Failure & Instrumentation System Operators Manual
6.1.2
The date/time should be initially set using the 5200 series configuration software. However there may be certain
circumstances where a minor change to the modules time is required. One such instance is correction for daylight
saving.
NOTE:- The 5220 controller maintains the current date/time so long as it connected to a DC supply within the
operating range. Disconnection of the supply will result in the date/time being frozen until the modules power is
reapplied. When this occurs, the date/time will resume operation from the time the power was disconnected. If this
occurs you can use the front panel editor to correct the date/time or reset it using the 5200 series configuration
software.
NOTE:- The calendar is used by the 5220s run scheduler and the event log.
and Stop/Reset
@ will
flash to indicate that the module is in configuration mode. Release the Stop/Reset
configure/log
button.
button. The time, 4.30 in this example, will begin flashing. Press the + or buttons to
adjust the time in one minute steps until the desired time is shown. Press the
time stops flashing to confirm that is has been successfully stored.
26
SUNLIGHT Model AMF 5220 Automatic Mains Failure & Instrumentation System Operators Manual
7 INSTALLATION INSTRUCTIONS
The model AMF 5220 Module has been designed for front panel mounting. Fixing is by 4 clips for easy assembly.
7.1
PANEL CUT-OUT
160.00mm
(6.3)
220.00mm
(8.7)
FIG 3
Maximum panel thickness 8mm (0.3)
In conditions of excessive vibration the module should be mounted on suitable anti-vibration mountings.
7.2
COOLING
The module has been designed to operate over a wide temperature range -30 to +70 C. Allowances should be
made for the temperature rise within the control panel enclosure. Care should be taken NOT to mount possible heat
sources near the module unless adequate ventilation is provided. The relative humidity inside the control panel
enclosure should not exceed 95%.
7.3
UNIT DIMENSIONS
FIG 4
SUNLIGHT Model AMF 5220 Automatic Mains Failure & Instrumentation System Operators Manual
7.4
FIG 5
7.5
FIG 6
28
SUNLIGHT Model AMF 5220 Automatic Mains Failure & Instrumentation System Operators Manual
8 ELECTRICAL CONNECTIONS
Connections to the Module are via plug and sockets.
8.1
CONNECTION DETAILS
The following describes the connections and recommended cable sizes to the 7 plugs and sockets on the rear of
the Module. See rear panel layout FIG 6.
8.1.1
PIN
No
1
PLUG A 8 WAY
DESCRIPTION
4
5
6
7
8
8.1.2
PIN
No
9
10
11
12
13
14
15
16
17
18
19
CABLE
SIZE
2.5mm
NOTES
2.5mm
2.5mm
2.5mm
2.5mm
1.0mm
1.0mm
1.0mm
PLUG B 11 WAY
DESCRIPTION
Charge fail / excite
Auxiliary input 1
Auxiliary input 2
Auxiliary input 3
Auxiliary input 4
Auxiliary input 5
Auxiliary input 6
Functional Earth
Magnetic pickup +ve
Magnetic pickup -ve
Not connected
CABLE
SIZE
2.5mm
0.5mm
0.5mm
0.5mm
0.5mm
0.5mm
0.5mm
2.5mm
0.5mm
0.5mm
-
NOTES
Do not connect to ground (battery ve)
Switch to -ve
Switch to -ve
Switch to -ve
Switch to -ve
Switch to -ve
Switch to -ve
Connect to a good clean earth point
Connect to Magnetic Pickup device
Connect to Magnetic Pickup device
NOTE:- Ensure magnetic pickup screen is connected to ground at one end only.
NOTE:- When the module is configured for CanBus J1939 operation, terminals 17 & 18 should be
left unconnected. Engine speed is transmitted to the 52xx controller on the CanBus link.
8.1.3
PIN
No
20
21
22
CABLE
SIZE
0.5mm
0.5mm
0.5mm
NOTES
Use only 120W CanBus approved cable
Use only 120W CanBus approved cable
Use only 120W CanBus approved cable
SUNLIGHT Model AMF 5220 Automatic Mains Failure & Instrumentation System Operators Manual
8.1.4
PIN
No
23
24
25
26
DESCRIPTION
RS485 port Common
RS485 port B
RS485 port A
Not connected
8.1.5
PIN
No
27
28
29
30
31
33
34
8.1.6
PIN
No
35
Generator L1 voltage
monitoring input
Generator L2 voltage
monitoring input
Generator L3 voltage
monitoring input
Generator Neutral input
37
38
8.1.7
30
NOTES
Use only 120W RS485 approved cable
Use only 120W RS485 approved cable
Use only 120W RS485 approved cable
CABLE
SIZE
1.0mm
1.0mm
1.0mm
1.0mm
1.0mm
1.0mm
1.0mm
1.0mm
NOTES
Connect to mains contactor coil
Connect to mains contactor feed supply
Connect to generator contactor coil
Connect to generator contactor feed supply
Connect to mains L1 (AC)
(Recommend 2A fuse)
Connect to mains L2 (AC)
(Recommend 2A fuse)
Connect to mains L3 (AC)
(Recommend 2A fuse)
Connect to mains Neutral (AC)
PLUG F 4 WAY
DESCRIPTION
36
CABLE
SIZE
0.5mm
0.5mm
0.5mm
-
PLUG E 8 WAY
DESCRIPTION
32
PIN
No
39
40
41
42
43
CABLE
SIZE
1.0mm
1.0mm
1.0mm
1.0mm
NOTES
Connect to generator L1 output (AC)
(Recommend 2A fuse)
Connect to generator L2 output (AC)
(Recommend 2A fuse)
Connect to generator L3 output (AC)
(Recommend 2A fuse)
Connect to generator Neutral terminal (AC)
PLUG G 5 WAY
DESCRIPTION
CT Secondary for L1
CT Secondary for L2
CT Secondary for L3
CT secondary common
Not connected
CABLE
SIZE
2.5mm
2.5mm
2.5mm
2.5mm
-
NOTES
Connect to secondary of L1 monitoring CT
Connect to secondary of L2 monitoring CT
Connect to secondary of L3 monitoring CT
Connect to secondary of all monitoring CTs
SUNLIGHT Model AMF 5220 Automatic Mains Failure & Instrumentation System Operators Manual
8.1.8
PIN
No
44
45
46
47
PLUG H 4 WAY
DESCRIPTION
Oil Pressure Input
Coolant Temperature
Input
Fuel Level input
Sender Common Return
CABLE
SIZE
0.5mm
0.5mm
NOTES
Connect to Oil pressure sender
Connect to Coolant Temperature sender
0.5mm
0.5mm
NOTE*:- If using single terminal senders refer to connection diagram. If using earth return type
senders connect return terminals to pin 47 and also connect pin 47 to earth. This is detailed in the
Appendix section entitled Sender wiring recommendations elsewhere in this manual.
NOTE:- When the module is configured for CanBus J1939 operation, terminals 44 & 45 should be
left unconnected. Engine oil pressure and coolant temperature is transmitted to the 52xx controller
on the CanBus link.
SUNLIGHT Model AMF 5220 Automatic Mains Failure & Instrumentation System Operators Manual
8.1.9
32
SUNLIGHT Model AMF 5220 Automatic Mains Failure & Instrumentation System Operators Manual
8.2
The following describes the functions of the 3 connectors on the rear of the module. See rear panel layout FIG 5.
8.2.1
PIN
No
1
2
3
4
5
6
7
8
8.2.2
PIN
No
9
10
11
12
13
14
15
16
17
18
19
PLUG A 8 WAY
DESCRIPTION
DC Supply -ve. System DC negative input. (Battery Negative).
DC Supply +ve. System DC positive input. (Battery Positive).
Emergency Stop input. Internally linked to Starter and Fuel outputs. If this input is
not connected to positive the module will be locked out, and if the engine is
running it will shutdown immediately. The Positive Supply is also removed from
Starter and Fuel outputs, therefore only a single pole Emergency Shutdown button
is required.
Fuel Relay output. Plant Supply +ve from pin 3. Used to control the fuel solenoid or
engine fuel control system.
Starter Relay output. Plant Supply +ve from pin 3. Used to control the Starter Motor.
Auxiliary Relay output 1. Plant Supply +ve. Configurable output, see Calibration
Manual for options available.
Auxiliary Relay output 2. Plant Supply +ve. Configurable output, see Calibration
Manual for options available.
Auxiliary Relay output 3. Plant Supply +ve. Configurable output, see Calibration
Manual for options available.
PLUG B 11 WAY
DESCRIPTION
Charge Fail input / Excitation output. Supplies excitation to the Plant Battery
Charging Alternator, also an input for the Charge Fail detection circuitry.
Auxiliary input 1. This is a negative switched configurable input, see Calibration
Manual for options available. It is possible to configure the input to be a normally
closed signal or a normally open signal.
Auxiliary input 2. This is a negative switched configurable input, see Calibration
Manual for options available. It is possible to configure the input to be a normally
closed signal or a normally open signal.
Auxiliary input 3. This is a negative switched configurable input, see Calibration
Manual for options available. It is possible to configure the input to be a normally
closed signal or a normally open signal.
Auxiliary input 4. This is a negative switched configurable input, see Calibration
Manual for options available. It is possible to configure the input to be a normally
closed signal or a normally open signal.
Auxiliary input 5. This is a negative switched configurable input, see Calibration
Manual for options available. It is possible to configure the input to be a normally
closed signal or a normally open signal.
Auxiliary input 6. This is a negative switched configurable input, see Calibration
Manual for options available. It is possible to configure the input to be a normally
closed signal or a normally open signal.
Functional Earth - Ensure connection to a good clean earth point.
Magnetic Input +ve. An AC signal from the magnetic pickup +ve for speed sensing.
Magnetic Input -ve. An AC signal from the magnetic pickup -ve for speed sensing.
Not connected
NOTE:- Ensure magnetic pickup screen is connected to ground at one end only.
NOTE:- When the module is configured for CanBus J1939 operation, terminals 17 & 18 should be
left unconnected. Engine speed is transmitted to the 52xx controller on the CanBus link.
SUNLIGHT Model AMF 5220 Automatic Mains Failure & Instrumentation System Operators Manual
8.2.3
PIN
No
20
21
22
8.2.4
PIN
No
23
24
25
26
8.2.5
PIN No
27
28
29
30
31
32
33
34
8.2.6
PIN
No
35
36
37
38
8.2.7
PIN No
39
40
41
42
43
34
PLUG E 8 WAY
DESCRIPTION
Mains loading relay, normally closed. Volts free contact to terminal 28.
Mains loading relay, normally closed. Volts free contact to terminal 27.
Generator loading relay, normally open. Volts free contact to terminal 30.
Generator loading relay, normally open. Volts free contact to terminal 29.
Mains L1 voltage monitoring input. Connect to mains L1 supply
Mains L2 voltage monitoring input. Connect to mains L2 supply. If using single phase AC system
do not connect to this terminal.
Mains L3 voltage monitoring input. Connect to mains L3 supply. If using single phase or two
phase AC system do not connect to this terminal.
Mains Neutral input. Connect to mains N supply. If using 3phase 3wire AC system, do not
connect to this terminal.
PLUG F 4 WAY
DESCRIPTION
Generator L1 sensing input. Connect to alternator L1 output.
Generator L2 sensing input. Connect to alternator L2 output. If using single phase only do not
connect this terminal.
Generator L3 sensing input. Connect to alternator L3 output. If using single phase only do not
connect this terminal.
Generator N sensing input. Connect to alternator N output.
PLUG G 5 WAY
DESCRIPTION
Generator L1 current transformer connection.
Generator L2 current transformer connection. If single phase is used do not connect this pin.
Generator L3 current transformer connection. If single phase is used do not connect this pin.
Generator current transformer common connection and CT earth connection.
Not used. Do not connect to this terminal.
SUNLIGHT Model AMF 5220 Automatic Mains Failure & Instrumentation System Operators Manual
8.2.8
PIN
No
44
45
46
47
PLUG H 4 WAY
DESCRIPTION
Oil Pressure sensing input. Connect to resistive type oil pressure sender. Refer to connection
diagram for details.
Coolant Temperature sensing input. Connect to resistive type coolant temperature sender. Refer
to connection diagram for details.
Fuel Level sensing input. Connect to resistive type fuel level sender. Refer to connection diagram
for details.
Sender Common connection. Return feed from sender units - refer to connection diagram for
details.
NOTE:- When the module is configured for CanBus J1939 operation, terminals 44 & 45 should be
left unconnected. Engine oil pressure and coolant temperature is transmitted to the 52xx controller
on the CanBus link.
8.2.9
If you require additional plugs from SUNLIGHT, please contact our Sales department using the part numbers below.
5220 Terminal
1-8
9-19
20-22
23-26
27-34
35-38
39-43
44-47
Connector
A
B
C
D
E
F
G
H
Plug descriptio
BL08 8way 5.08mm spacing connector plug
BL11 11way 5.08mm spacing connector plug
BL03 3way 3.81mm spacing connector plug
BL04 4way 3.81mm spacing connector plug
BL08 8way 10.16mm spacing connector plug
BL04 4way 10.16mm spacing connector plug
BL05 5way 5.08mm spacing connector plug
BL04 4way 5.08mm spacing connector plug
SUNLIGHT Model AMF 5220 Automatic Mains Failure & Instrumentation System Operators Manual
8.3
This section of the manual is intended to describe only the connections between the 52xx controller and J1939
enabled controllers. All other connection details are described in the previous sections.
NOTE:- The CANbus specification, used by J1939, requires that a 120W terminator is fitted to each end of the
communications link. This termination resistor is fitted internally into the 52xx controller so is not required externally.
Ensure that the 52xx controller is the last device on the communications link where more than one device is
connected to the engine ECUs J1939 connector.
8.3.1
PLUG A 8 WAY
52xx
52xx
PIN No
DESCRIPTION
4
Fuel relay output
5
Start relay output
6
Aux output 1
PLUG C 3 WAY
52xx
52xx
PIN No
DESCRIPTION
36
21
CANbus H
22
CANbus L
NOTES
key switch input.
Connects directly to engine starter
solenoid.
Configure 52xx aux op 1 to be Louvre
control and configure 52xx ETS Hold
Timer to 20 seconds. This is used to
power down the engine ECU 20seconds
after the set comes to rest.
NOTES
Screen for the J1939 cable. Connect at
Cummins ECU end only.
J1939 + Use only screened 120W
impedance cable approved specifically
for use in CANbus applications.
J1939 - Use only screened 120W
impedance cable approved specifically
for use in CANbus applications.
SUNLIGHT Model AMF 5220 Automatic Mains Failure & Instrumentation System Operators Manual
8.3.2
JOHN DEERE
PLUG A 8 WAY
52xx
52xx
PIN No
DESCRIPTION
4
Fuel relay output
5
Start relay output
PLUG C 3 WAY
52xx
52xx
PIN No
DESCRIPTION
20
CANbus common
21
CANbus H
22
CANbus L
NOTES
G = Switched ECU power, J = Ignition
Start
NOTES
Screen for the J1939 cable. Connect at
52xx end only.
J1939 + Use only screened 120W
impedance cable approved specifically
for use in CANbus applications.
J1939 - Use only screened 120W
impedance cable approved specifically
for use in CANbus applications.
SUNLIGHT Model AMF 5220 Automatic Mains Failure & Instrumentation System Operators Manual
8.3.3
PLUG A 8 WAY
52xx
52xx
PIN No
DESCRIPTION
4
Fuel relay output
5
PLUG C 3 WAY
52xx
52xx
PIN No
DESCRIPTION
20
CANbus common
21
CANbus H
31
22
CANbus L
32
NOTES
Powers up ECU and enables the
injectors.
Connects directly to engine starter
solenoid.
NOTES
Screen for the J1939 cable. Connect at
52xx end only.
J1939 + Use only screened 120W
impedance cable approved specifically
for use in CANbus applications.
J1939 - Use only screened 120W
impedance cable approved specifically
for use in CANbus applications.
38
SUNLIGHT Model AMF 5220 Automatic Mains Failure & Instrumentation System Operators Manual
8.3.4
SCANIA S6
PLUG A 8 WAY
52xx
52xx
PIN No
DESCRIPTION
4
Fuel relay output
5
Start relay output
PLUG C 3 WAY
52xx
52xx
PIN No
DESCRIPTION
20
CANbus common
21
CANbus H
22
CANbus L
10
NOTES
Ignition U15
Connects directly to engine starter
solenoid.
NOTES
Screen for the J1939 cable. Connect at
52xx end only.
J1939 + Use only screened 120W
impedance cable approved specifically
for use in CANbus applications.
J1939 - Use only screened 120W
impedance cable approved specifically
for use in CANbus applications.
SUNLIGHT Model AMF 5220 Automatic Mains Failure & Instrumentation System Operators Manual
8.3.5
VOLVO TAD12
PLUG A 8 WAY
52xx
52xx
PIN No
DESCRIPTION
4
Fuel relay output
5
Start relay output
6
Aux output 1
PLUG C 3 WAY
52xx
52xx
PIN No
DESCRIPTION
20
CANbus common
21
CANbus H
1 (Hi)
22
CANbus L
2 (Lo)
NOTES
TAD12 STOP input.
TAD12 START input.
Aux output 1 configured to Louvre
control.
NOTES
Screen for the J1939 cable. Connect at
52xx end only.
J1939 + Use only screened 120W
impedance cable approved specifically
for use in CANbus applications.
J1939 - Use only screened 120W
impedance cable approved specifically
for use in CANbus applications.
NOTES
NOTE:- Should the TAD12 ECU detect an engine fault not monitored by the 52xx, an external
reset must be provided to reset the ECU.
Volvo specify that the reset is performed using external pushbuttons to give an input to TAD12
Standalone connector terminal J (diagnostics), P (power) and H(stop).
According to Volvo, the reset sequence is :
Press and hold down the diagnostic button (terminal J) and apply power to H (stop)
Apply power to P (but dont start the engine).
Hold these inputs for three seconds.
Release the diagnostic button (terminal J).
Remove power from H (stop).
Remove power from P (power).
40
SUNLIGHT Model AMF 5220 Automatic Mains Failure & Instrumentation System Operators Manual
SPECIFICATION
DC Supply
Cranking Dropouts
Shock
8.0 to 35 V Continuous.
Able to survive 0 V for 50mS, providing supply was at least 10 V before
dropout and supply recovers to 5V. This is achieved without the need for
internal batteries.
250. mA at 12 V. 125. mA at 24 V.
425. mA at 12 V. 215. mA at 24V
SUNLIGHT Model AMF 5220 Automatic Mains Failure & Instrumentation System Operators Manual
9 COMMISSIONING
9.1.1
PRE-COMMISSIONING
Before the system is started, it is recommended that the following checks are made:7.1. The unit is adequately cooled and all the wiring to the module is of a standard and rating compatible with the
system.
7.2. The unit DC supply is fused and connected to the battery and that it is of the correct polarity.
7.3. The Emergency Stop input is wired to an external normally closed switch connected to DC positive.
NOTE:- If Emergency Stop feature is not required link this input to the DC Positive. The module
will not operate unless either the Emergency Stop is fitted correctly OR Pin 3 is connected to DC
positive (+ve)
7.4. To check the start cycle operation take appropriate measures to prevent the engine from starting (disable the
operation of the fuel solenoid). After a visual inspection to ensure it is safe to proceed, connect the battery
supply. Select MANUAL, the unit start sequence will commence.
7.5. The starter will engage and operate for the pre-set crank period. After the starter motor has attempted to start
the engine for the pre-set number of attempts the LCD will display its icon indicating; Failed to start
Select the STOP/RESET position to reset the unit.
7.6. Restore the engine to operational status (reconnect the fuel solenoid), again select MANUAL, this time the
engine should start and the starter motor should disengage automatically. If not then check that the engine is
fully operational (fuel available, etc.) and that the fuel solenoid is operating. The engine should now run up to
operating speed. If not, and an alarm is present, check the alarm condition for validity, then check input
wiring. The engine should continue to run for an indefinite period. It will be possible at this time to view the
engine and alternator parameters - refer to the Description of Controls section of this manual.
7.7. Select AUTO on the front panel, the engine will run for the pre-set cooling down period, then stop. The
generator should stay in the standby mode. If not check that there is not a signal present on the Remote start
input and that the mains (utility) supply is healthy and available.
7.8. Initiate an automatic start by supplying the remote start signal or failing the mains(utility) supply. The start
sequence will commence and the engine will run up to operational speed. Once the generator is available a
load transfer will take place, the Generator will accept the load. If not, check the wiring to the Generator
Contactor Coil (if used). Check the Warming timer has timed out.
7.9. Remove the remote start signal and/or ensure the mains (utility) supply is healthy, the return sequence will
start. After the pre-set time period, the load will be removed from the generator. The generator will then run for
the pre-set cooling down period, then shutdown into its standby mode.
7.10. Set the modules internal clock/calendar to ensure correct operation of the scheduler and event logging
functions. For details of this procedure see section entitled Front Panel Configuration Editing the date/time.
7.11. If despite repeated checking of the connections between the 5220 and the customers system, satisfactory
operation cannot be achieved, then the customer is requested to contact the factory for further advice.
42
SUNLIGHT Model AMF 5220 Automatic Mains Failure & Instrumentation System Operators Manual
10 FAULT FINDING
SYMPTOM
Unit is inoperative
Unit shuts down
Unit locks out on Emergency Stop
POSSIBLE REMEDY
Check the battery and wiring to the unit. Check the DC supply. Check the DC
fuse.
Check DC supply voltage is not above 35 Volts or below 9 Volts
Check the operating temperature is not above 70 C. Check the DC fuse.
If an Emergency Stop Switch is not fitted, ensure that a positive is connected
to the Emergency Stop input. Check emergency stop switch is functioning
correctly. Check Wiring is not open circuit.
Ensure that Magnetic pick-up screen is only connected at one end, if
connected at both ends, this enables the screen to act as an aerial and will
pick up random voltages.
Check engine oil pressure. Check oil pressure switch/sender and wiring.
Check configured polarity (if applicable) is correct (i.e. Normally Open or
Normally Closed) or that sender is compatible with the 5220 Module and is
correctly configured.
Check engine temperature. Check switch/sender and wiring. Check configured
polarity (if applicable) is correct (i.e. Normally Open or Normally Closed) or that
sender is compatible with the 5220 Module.
Check relevant switch and wiring of fault indicated on LCD display. Check
configuration of input.
Check relevant switch and wiring of fault indicated on LCD display. Check
configuration of input.
Check wiring of fuel solenoid. Check fuel. Check battery supply. Check battery
supply is present on the Fuel output of the module. Check the speed sensing
signal is present on the 5220 inputs. Refer to engine manual.
Check that mains (utility) supply is healthy and check that its protection fuses
are in place and are not blown
Check that there is no signal present on the Remote Start input. Check
configured polarity is correct.
Check Start Delay timer has timed out.
If remote start fault, check signal is on Remote Start input. Confirm input is
configured to be used as Remote Start.
Check wiring to engine heater plugs. Check battery supply. Check battery
supply is present on the Pre-heat output of module. Check pre-heat has been
selected in your configuration.
Check wiring to starter solenoid. Check battery supply. Check battery supply is
present on the Starter output of module. Ensure that the Emergency Stop
input is at +Ve.
Check Warm up timer has timed out. Ensure generator load inhibit signal is not
present on the module inputs.
Check engine is operating correctly. Check sender and wiring paying particular
attention to the wiring to terminal 47 (refer to appendix). Check that sender is
compatible with the 5220 Module and is correctly configured.
NOTE:- The above fault finding is provided as a guide check-list only. As it is possible for the
module to be configured to provide a wide range of different features always refer to the source of
your module configuration if in doubt.
SUNLIGHT Model AMF 5220 Automatic Mains Failure & Instrumentation System Operators Manual
Value
5220 automatic mains failure module
Miscellaneous settings
Alternator fitted
Poles
Magnetic pickup fitted
J1939 enabled
AC System
VT Ratio
Mains failure detection
Number of start attempts
Enable fast loading feature
Immediate mains dropout
Value
Yes
4
No
No
3 phase, 4 wire
Disabled
Enabled
3
No
Disabled
Value
VDO 10 bar
@
@
Trip
1.17 Bar 17.0 PSI
1.03 Bar 14.9 PSI
Value
@
@
Value
VDO Ohm
Range
No
10%
44
Return
1.24 Bar 18.0 PSI
N/A
110C 230F
N/A
Value
Close to activate
Close to activate
Close to activate, Warning Active from safety on
Close to activate, Shutdown Always active
Close to activate, Shutdown Active from safety on
Close to activate, Electrical trip Always active
SUNLIGHT Model AMF 5220 Automatic Mains Failure & Instrumentation System Operators Manual
Value
Preheat (during pre-heat timer)
Common alarm
System in auto mode
Close generator
Close mains
Value
Output not used
Output not used
Output not used
Output not used
Output not used
Output not used
Output not used
Output not used
Value
Digital input 1 active
Digital input 2 active
System in auto mode
Common alarm
@
@
@
@
@
@
@
@
@
@
@
Value
1s
5s
0s
10s
10s
0s
0s
10s
2s
0s
0.7s
0.5s
0.5s
30s
30s
0s
30s
1s
1m
1m
5m
@
@
@
@
Trip
180V AC
280V AC
45Hz
52Hz
Return
200V AC
260V AC
48Hz
55Hz
SUNLIGHT Model AMF 5220 Automatic Mains Failure & Instrumentation System Operators Manual
@
@
@
@
@
@
@
@
46
Return
N/A
207V AC
265V AC
N/A
N/A
45.0 Hz
52.0 Hz
N/A
Value
600 A
500 A
100% ( 500 A )
36
Value
21.0 Hz
<Disabled>
Yes
Value
1250 RPM
1350 RPM
1650 RPM
1750 RPM
0%
@
@
@
@
Trip
184V AC
196V AC
253V AC
276V AC
40.0 Hz
42.0 Hz
55.0 Hz
57.0 Hz
@
@
@
Trip
8.0 V DC
33.0 V DC
8.0 V DC
Return
9.0 V DC
32.0 V DC
N/A
Value
No
Value
No modem
+MS=11,1,,S7=60S0=0&S0&C1&D3
+MS=11,1,,S7=60S0=2&S0&C1&D3
H0
0
SUNLIGHT Model AMF 5220 Automatic Mains Failure & Instrumentation System Operators Manual
5200 series
configuration software
L1
42
43
CT
Earth
F2A
35
F2A
F2A
38
29
LOAD
Mechanical interlock
Electrical interlock
30
27
Mains
loading
relay
12
F2A
28
13
31
F2A
32
F2A
15
33
14
34
Optional
RS232
9 way D
37
10
36
47
Generator
loading
relay
L1
Mains (utility)
24
25
Optional
RS485
20
COM
21
22
Optional
CanBus
16
17
18
Not connected 19
Not connected 26
23
SCR
L2
CT
common
46
5220 controller
45
11
L2
41
44
L3
40
L3
39
Fuel
Supply for
controller
1
Crank
Generator
810
Not connected
Charge WL
alt.
810 interface
157/548
Output expansion
157 relay board
or
548 annunciator
Starter
motor
Battery
MPU
Ground screen
at one end only
Functional
Earth
Emergency
stop
SUNLIGHT Model AMF 5220 Automatic Mains Failure & Instrumentation System Operators Manual
13 APPENDIX
13.1 ALTERNATIVE WIRING TOPOLOGIES
The 5200 series controllers can support many different wiring topologies (AC systems) to suit the many systems in
use worldwide. The Typical connection diagram details how to connect the module when used in a 3 phase, 4 wire
system (3 phase star connected alternators). Changes to this typical wiring diagram for other AC systems are
detailed below.
NOTE:- The factory default configuration for the 5220 module is for use with the 3 phase, 4 wire
AC system. If another system is to be used, the controller must be reconfigured using the 5200 series
configuration software.
Mechanical interlock
Generator
Mains (utility)
L1
L1
CT
Earth
L2
L2
L3
L3
F2A
F2A
F2A
F2A
Electrical interlock
F2A
F2A
CT
common
42
35
43
36
37
29
30
Generator
loading
relay
38 34
27
Not connected
41
Not connected
40
Not connected
39
31
28
32
33
Mains
loading
relay
LOAD
Mechanical interlock
L1
L1
CT
Earth
Mains (utility)
Generator
F2A
F2A
F2A
F2A
G
Electrical interlock
48
36
37
38
29
30
Generator
loading
relay
27
28
Mains
loading
relay
31
32
33
Not connected
35
Not connected
43
Not connected
Not connected
42
Not connected
41
Not connected
40
Not connected
CT
common
39
34
SUNLIGHT Model AMF 5220 Automatic Mains Failure & Instrumentation System Operators Manual
Mechanical interlock
Generator
Mains (utility)
L1
L1
CT
Earth
L2
L2
F2A
F2A
F2A
G
Electrical interlock
F2A
CT
common
40
41
42
43
35
Not connected
39
36
37
38
29
30
Generator
loading
relay
27
28
Mains
loading
relay
31
32
33
34
SUNLIGHT Model AMF 5220 Automatic Mains Failure & Instrumentation System Operators Manual
Description
Display
Description
Display
Description
Stop/Reset
Configure / log
Auto mode
Scroll
Test mode
Start (when in
Manual or Test
mode)
Display
Description
Manual mode
L1
L1-
Description
Display
L2
Phase
Phase - Neutral
L2-
L1- L2
Phase - Phase
L2- L3
BAR
Pressure
Voltage
A
kW
Description
Phase
Phase
Phase - Neutral
L3-
Phase - Phase
L3- L1
Phase - Phase
PSI
Pressure
Temperature
Hz
Frequency
Amperes
Temperature
RPM
Speed
KiloWatts
kVA
Apparent power
KW divided by
kVA
Hours Run
AC
Generator
Timer in progress
DC
Mains (Utility)
Fuel level
Event log
Configuration
mode active
Panel locked by
configurable input
L3
KPa
Can
Canbus J1939
messages
Display
Description
Phase -Neutral
Description
Warning Alarm
Shutdown Alarm
Fuel
Charge Fail
Emergency Stop
Description
Electrical Trip
High Current
Warning
Under Voltage
(AC)
Over-speed
Over frequency
Under Voltage
(DC)
Under-speed
Under frequency
Auxiliary Indication
50
Display
Auxiliary Alarm
(Warning or Shutdown)
SUNLIGHT Model AMF 5220 Automatic Mains Failure & Instrumentation System Operators Manual
100000
10000
1000
100
10
1
1
2
Current as a multiple of the trip-point setting (tripping curve = 36)
SUNLIGHT Model AMF 5220 Automatic Mains Failure & Instrumentation System Operators Manual
Terminal Number
44
Coolant temperature
sender
45
46
Sender common
47
NOTE:- . If you use PTFE insulating tape on the sender thread when using earth return senders,
ensure you do not insulate the entire thread as this will prevent the sender body from being earthed
via the engine block.
Terminal Number
44
Coolant temperature
sender
45
46
Sender common
47
52
SUNLIGHT Model AMF 5220 Automatic Mains Failure & Instrumentation System Operators Manual
SUNLIGHT Model AMF 5220 Automatic Mains Failure & Instrumentation System Operators Manual
Mechanical interlock
L1
L1
CT
Earth
L2
L2
L3
L3
Generator
Mains (utility)
F2A
F2A
F2A
F2A
G
810 interface
Electrical interlock
F2A
F2A
M
Optional
RS232
CT
common
47
+
Battery
Charge WL
alt.
33
34
9 way D
10
11
23
24
25
Not connected 19
Not connected 26
Not connected
Not connected
17
18
CanBus
12
13
14
15
Fuel
Crank
Starter
motor
54
46
32
Mains
loading
relay
5220 controller
45
31
28
Generator
loading
relay
Output expansion
157 relay board
or
548 annunciator
44
27
30
29
38
Emergency
stop
37
Supply for
controller
36
35
Not connected
157/548
43
Not connected
42
41
Not connected
40
39
810
5200 series
configuration software
Optional
RS485
SCR
20
21
COM
COM
22
16
Functional
Earth
SUNLIGHT Model AMF 5220 Automatic Mains Failure & Instrumentation System Operators Manual
POWER ON LED
RELAY ACTIVE LED'S
Refer to technical data sheet on the 157 relay module for further details.
Refer to technical data sheet on the 548 LED module for further details.
It is possible to use a mix of 157 and 548 modules to give both relay and LED expansion of the same 8 items if
required (Please refer to our Technical Support department for details.).
SUNLIGHT Model AMF 5220 Automatic Mains Failure & Instrumentation System Operators Manual
56
SUNLIGHT Model AMF 5220 Automatic Mains Failure & Instrumentation System Operators Manual