Professional Documents
Culture Documents
Control:
Parallel
Profibus DP
Profibus DP with FO
Modbus
Modbus with FO
DeviceNet
Foundation Fieldbus
Operation instructions
..
..
..
Operation instructions
Reference documents:
Manual (Operation and setting) AUMATIC AC 01.0/ACExC 01.1 Foundation Fieldbus.
Manual (Fieldbus device integration) AUMATIC AC 01.0/ACExC 01.1 Foundation Fieldbus.
Can be downloaded from the Internet (www.auma.com) or ordered directly from AUMA (addresses from page 78).
Table of contents
Page
1.
Safety instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.1.
1.2.
1.3.
1.4.
1.5.
2.
Identification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
2.1.
2.2.
Name plate
Short description
3.
3.1.
3.2.
3.3.
Transport
Storage
Packaging
4.
Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
4.1.
4.2.
4.2.1
4.2.2
4.3.
4.3.1
4.4.
Handwheel fitting
Multi-turn actuator mounting to valve/gearbox
Output drive types B1, B2, B3, B4, B, and E
Output drive type A
Accessories (option)
Protection tube for rising valve stem
Mounting positions of the local controls
5.
Electrical connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
5.1.
5.2.
5.3.
5.4.
5.4.1
5.4.2
5.4.3
5.4.4
5.4.5
General notes
Mains connection using AUMA plug/socket connector (SD)
Bus connection using AUMA plug/socket connector (SD)
Accessories for electrical connection (option)
Controls mounted to wall bracket
Parking frame
Protection cover
Double sealed intermediate frame
Ground connection, external
6.
Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
6.1.
6.2.
6.2.1
6.2.2
Manual operation
Motor operation
Local operation
Operation from REMOTE
5
6
7
8
8
9
11
12
12
12
13
14
14
15
17
17
18
19
22
25
28
28
29
29
29
29
30
31
31
31
Operation instructions
6.3.
6.3.1
6.3.2
6.4.
7.
Indications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
7.1.
7.1.1
7.2.
7.3.
8.
Signals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
8.1.
8.2.
8.3.
9.
Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
9.1.
9.2.
9.3.
9.4.
9.4.1
9.4.2
9.5.
9.5.1
9.5.2
9.6.
9.6.1
9.6.2
9.6.3
9.7.
9.8.
9.9.
9.10.
10.
Corrective action . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
36
36
38
38
39
39
39
41
44
45
46
46
46
47
47
47
48
48
49
49
51
52
53
54
55
55
55
55
56
56
57
57
58
59
61
62
62
63
Operation instructions
Page
11.
11.1.
11.2.
11.3.
12.
12.1.
12.2.
13.
Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
14.
Certificates . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
14.1.
64
65
65
68
70
78
Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Addresses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
Operation instructions
1.
Safety instructions
1.1.
AUMA products are designed and manufactured in compliance with recognised standards and directives. This is certified in a declaration of incorporation and a declaration of conformity.
The end user or the contractor must ensure that all requirements with
respect to assembly, electrical connection, and commissioning at the place
of installation are met. They include among others:
Applicable configuration directives for fieldbus applications.
National regulations, laws, and prescriptions.
..
Safety instructions/
warnings
All personnel working with this device must be familiar with the safety and
warning instructions in this manual and observe the instructions given.
Safety instructions and warning signs on the device must be observed to
avoid personal injury or property damage.
Qualification of staff
Assembly, electrical connection, commissioning, operation, and maintenance must be carried out exclusively by suitably qualified personnel having
been authorised by the end user or contractor of the plant.
Prior to working on this product, the staff must have thoroughly read and
understood these instructions and, furthermore, know and observe officially
recognised rules regarding occupational health and safety.
Commissioning
Prior to commissioning, it is important to check that all settings are in compliance with the requirements of the application. Incorrect settings might
present a danger to the application, e.g. cause damage to the valve or the
installation.
The manufacturer will not be held liable for any consequential damage. Such
risk lies entirely with the user.
Operation
Protective measures
Maintenance
.
.
.
..
.
The end user or the contractor are responsible for implementing required
protective measures on site, such as enclosures, barriers, or personal
safety equipment for the staff.
To ensure safe device operation, the maintenance instructions included in
this manual must be observed.
Any device modification requires the consent of the manufacturer.
1.2.
Operation instructions
Range of application
AUMA multi-turn actuators are designed for the operation of industrial
valves, e.g. globe valves, gate valves, butterfly valves, and ball valves.
Other applications require explicit (written) confirmation by the manufacturer.
..
..
..
..
..
These operation instructions are only valid for the clockwise closing standard version, i.e. driven shaft turns clockwise to close the valve. Separate
instructions are available for the counterclockwise closing special version.
Operation instructions
1.3.
.
.
.
.
.
.
.
.
1.4.
Operation instructions
WARNING
CAUTION
NOTICE
DANGER
1.5.
Information
The term Information preceding the text indicates important notes and
information.
Step by step
Provides a detailed description of each step for setting/viewing the parameter.
Operation instructions
2.1.
Name plate
Each device component (actuator, controls, motor) is equipped with a name
plate. Figure 1 shows the arrangement of name plates on the device.
Figure 1
1
2
3
4
1
2
1
2
a CC
Identification
1
2
3
1
2
3
auma
2.
AC 01.1
P:1,5kW
Com No: 1309595
No: 0902MA97286
KMS: TP180/001
ACP:11F1-2P0--B000
3 ~ 400V IP67
Control: RS 485
Commission number
Wiring diagram/control
10
Operation instructions
Operation instructions
2.2.
Short description
Multi-turn actuator
Actuator controls
Local controls/
COM-AC/fieldbus
Operation, setting, and display can be performed on site directly at the controls or alternatively from REMOTE via a fieldbus interface.
On site it is possible to
operate the actuator via the local controls (push buttons and display)
and perform settings (contents of these instructions).
read in or out data or modify and save settings via the COM-AC software
(option), using a computer (laptop or PC). Depending on the version, the
connection between computer and AUMATIC can be made with cable
(infra-red interface) or without cable (Bluetooth interface). (Not included
in these instructions.)
Intrusive Non-Intrusive
.
.
.
.
Intrusive version:
Limit and torque setting is performed via switches in the actuator.
Non-Intrusive version:
Limit and torque setting is performed via the controls, actuator and controls housings do not have to be opened.
For this purpose, the actuator is equipped with an MWG (magnetic limit
and torque transmitter), also supplying analogue torque feedback signals/torque indication.
11
3.
3.1.
Transport
Operation instructions
3.2.
Storage
NOTICE
Long-term storage:
3.3.
Hovering load!
Death or serious injury possible.
Do not place below hovering load.
Attach ropes or hooks for the purpose of lifting by hoist only to housing
and not to handwheel.
Actuators mounted on valves:
Attach ropes or hooks for the purpose of lifting by hoist to valve and not
to multi-turn actuator.
Actuators mounted to gearboxes:
Attach ropes or hooks for the purpose of lifting by hoist only to the gearbox using eyebolts and not to the actuator
Actuators mounted to controls:
Attach ropes or hooks for the purpose of lifting by hoist only to actuator
and not to controls.
Packaging
Our products are protected by special packaging for the transport ex works.
The packaging consists of environmentally friendly materials which can easily be separated and recycled.
We use the following packaging materials: wood, cardboard, paper, and PE
foil. For the disposal of the packaging material, we recommend recycling
and collection centres.
12
Operation instructions
4.
Assembly
4.1.
Handwheel fitting
Information
NOTICE
For transport purposes, handwheels from a diameter of 400 mm are supplied separately.
Damage at the change-over mechanism due to incorrect assembly!
Only pivot the change-over lever manually.
Using extensions as a lever for operation is not permitted.
First engage manual operation correctly, then mount handwheel.
1. Manually lift the red change-over lever while slightly turning the shaft
back and forth until manual operation engages.
The manual operation is correctly engaged if the change-over lever can
be lifted by approx. 85.
85
2. Attach handwheel over the red change-over lever then on to the shaft.
13
4.2.
Operation instructions
2
4
1
2
Information
3
4
NOTICE
14
Screws
Thread
M8
M10
M12
M16
25
51
87
214
Operation instructions
4.2.2 Output drive type A
Application
Design
..
1
2
3
1
2
.
.
Stem nut
3
Axial needle roller and cage assembly 4
Spigot ring
Axial bearing washer
The internal thread of the stem nut must match the thread of the valve
stem.
If not ordered explicitly with thread, the stem nut is supplied unbored or
with a pilot bore.
A 14.2
3g
A 16.2
5g
15
Operation instructions
1
2
3
Valve stem
Output drive type A
Screw to actuator
4
5
Valve flange
Screws to output drive
1. Remove screws (3) and take off output drive type A (2) from multi-turn
actuator.
2. Check if the flange of output drive type A matches the valve flange (4).
3. Thoroughly degrease mounting faces of the mounting flanges.
4. Apply a small quantity of grease to the valve stem (1).
5. Place output drive type A on valve stem and fasten until it is seated solidly on the valve flange.
6. Turn output drive type A until alignment of the fastening holes.
7. Screw in fastening screws (5), however do not completely fasten.
8. Fit multi-turn actuator on the valve stem so that the hollow shaft pinions
engage into the stem nut. The flanges are flush with each other if properly engaged.
9. Turn multi-turn actuator until alignment of the fastening holes.
10 Fasten multi-turn actuator with screws (3) according to table 2, page 14.
11. Fasten screws crosswise with a torque according to table 2.
12. Engage manual operation at multi-turn actuator and turn handwheel in
direction OPEN until valve flange and output drive type A are firmly
placed together.
13. Tighten fastening screws (5) between valve and output drive type A
crosswise with a torque according to table 2, page 14.
NOTICE
16
Operation instructions
4.3.
Accessories (option)
1
2
3
1
2
1.
2.
3.
4.
Sealing ring
17
4.4.
Operation instructions
Hazardous voltage!
Electric shock possible.
Disconnect device from the mains before opening.
1. Loosen bolts and remove the local controls.
2. Check whether O-ring is in good condition, correctly place O-ring.
3. Turn local controls into new position and re-place.
NOTICE
18
Operation instructions
5.
Electrical connection
5.1.
General notes
WARNING
Protection on site
For short-circuit protection and for disconnecting the actuator from the
mains, fuses and disconnect switches have to be provided by the customer.
The current values for respective sizing can be derived from the current
consumption of the motor plus the current consumption of the controls.
Motor current consumption:
Refer to name plate on motor (nominal current).
Current consumption of the controls depending on the mains voltage:
100 to 120 V AC = max. 650 mA
208 to 240 V AC = max. 325 mA
380 to 500 V AC = max. 190 mA
24 V DC (+10 %/15 %) = max. 500 mA, filter capacitor 2200 F
Current consumption for actuator with 1-ph DC motor:
24 V DC (+10 %/10 %) = max. 750 mA, filter capacitor 2200 F
The maximum permissible fuse for controls with a rated power of 1.5 kW is
16 A (gL/gG); for controls with a rated power of 7.5 kW, the value amounts
to 32 A (gL/gG).
.
.
.
.
19
20
Operation instructions
Power supply
Foundation Fieldbus
Operation instructions
Bus cables
Various types of fieldbus cables can be applied for Foundation Fieldbus. The
following table lists the cable types specified by the IEC/ISA 61158-2, Physical Layer Standard.
The preferred fieldbus cable is type A cable. This cable should be used in
new installations. However, other cable types may be used for the fieldbus
wiring (e.g type B, C, and D).
Their disadvantage is the reduced cable length; for this reason their use is
not recommended.
Table 5
Type A
(Reference)
Cable design
Conductor cross-section
(nominal)
Loop impedance
(DC current)
Wave resistance at
31.25 kHz
Wave attenuation
at 39 kHz
Capacitve asymmetry
Group delay distortion
(7.9 39 kHz)
Degree of shield
coverage
Recommended network
expansion (incl. spur line)
Type B
0.8 mm
(AWG 18)
One or multiple
twisted
conductor pairs,
overall shield
0.32 mm
(AWG 22)
44 /km
Type C
Type D
0.13 mm
(AWG 26)
Multiple
non-twisted
pairs, not
shielded
1.25 mm
(AWG 16)
112 /km
264 /km
40 /km
100
20 %
100
30 %
not specified
not specified
3 dB/km
5 dB/km
8 dB/km
8 dB/km
2 nF/km
2 nF/km
not specified
not specified
1.7 s/km
not specified
not specified
not specified
90 %
not specified
not specified
not specified
1,900 m
1,200 m
400 m
200 m
Twisted
conductor
pair
Multiple
twisted pairs,
not shielded
.
.
.
.
.
21
5.2.
Operation instructions
a CC
Hazardous voltage!
Electric shock possible.
Disconnect device from the mains before opening.
Figure 11
1
8
2
7
3
6
5
1
2
3
4
Connection housing
Screws for connection housing
O-ring
Screws for socket carrier
5
6
7
8
Socket carrier
Cable entry for mains
Screw plug
Cable gland (not included in delivery)
au
4. Seal cable entries (6) which are not used with suitable screw plugs (7).
5. Insert the wires into the cable glands (8).
22
Operation instructions
WARNING
For some special motors, the connection of the power terminals (U1, V1,
W1, U2, V2, W2) is made via a terminal board at the motor.
In case of failure: Hazardous voltage while protective conductor is not
connected!
Electric shock possible.
Connect all protective conductors.
Connect PE connection with external protective conductor of connecting
cables.
5. Tighten PE conductors firmly to PE connection using ring lugs (flexible
cables) or loops (rigid cables) (symbol:
).
Figure 12
2
3
4
5
1
6
1
2
3
Socket carrier
Screw
Washer
4
5
6
23
Operation instructions
1
8
2
7
3
6
5
1
2
3
4
24
Connection housing
Screws for connection housing
O-ring
Screws for socket carrier
5
6
7
8
Socket carrier
Cable entry for mains
Screw plug
Cable gland (not included in delivery)
Operation instructions
Hazardous voltage!
Electric shock possible.
Disconnect device from the mains before opening.
1
2
Cover
Screws for cover
3
4
5
O-ring
Cable entries for bus cables
Screw plug
au
5.3.
IP 67 1680 rpm
Temp.Protection: Th
Insulation Class: F
3. Seal cable entries (4) which are not used with suitable screw plugs (5).
4. Insert the wires into the cable glands.
25
Operation instructions
The max. current load of the pins for the Foundation Fieldbus cable in the electrical connection is 2.5 A. This has to be observed when planning the Foundation Fieldbus topology (location of the Foundation Fieldbus power supply and
current consumption of the connected Foundation Fieldbus devices).
2. If the actuator is the final device in the bus segment:
The termination resistor for channel 1 has to be switched on using
switch S1 (ON position).
The switch is supplied in OFF position.
Information
As soon as the termination resistor is switched on, the connection to the next
Fieldbus device is automatically interrupted to avoid multiple terminations.
Table 6 describes the switch positions S1:
Table 6
ON
OFF
S1
ON
OFF
S1
X4
Information
26
X1
X2
Operation instructions
1
2
Cover
Screws for cover
3
4
5
O-ring
Cable entries for bus cables
Screw plug
27
5.4.
Operation instructions
Design
..
.
Figure 17
1
2
4
3
28
Wall bracket
Connecting cables
..
..
.
.
3
4
5
Operation instructions
29
6.
Operation
6.1.
Manual operation
Operation instructions
In case of motor failure or power failure, the actuator may be operated manually for purposes of setting and commissioning.
Manual operation is engaged by an internal change-over mechanism.
Engaging manual operation
NOTICE
30
Operation instructions
6.2.
Motor operation
Perform all commissioning settings prior to motor operation.
2 STOP
3
4 Reset
5
1
2
3
4
5
6
The actuator can now be operated using the push buttons (1 3).
1. Run actuator in direction OPEN:
2. Stop actuator:
3. Run actuator in direction CLOSE.
Information
Now, it is possible to operate the actuator by remote control via the fieldbus.
Information
31
6.3.
Operation instructions
Push button p
Push button q
Push button C
Selector switch
Push button 8
Display
Now, settings and indications can be performed via the push buttons (1 4).
6.3.1 Short overview: functions of the push buttons
Table 8
Push
Functions
buttons
Scrolling within a group
pq
(The triangles
in the display show the direction of scrolling.)
Change values
Enter figures from 0 to 9
32
Operation instructions
6.3.2 Structural design and navigation
..
.
S0
E2
100%
OPEN POSITION
Change groups
Scrolling
Press qp:
The triangles
in the top left corner of the display indicate the possible
scrolling direction (within one group) of scrolling.
OFF
E2
S0
100%
OPEN POSITION
1.
2.
3.
4.
Information
:OK C:ESC
If no input is received over a longer period of time (approx. 10 min), the controls automatically returns to the status indication S0.
33
6.4.
Operation instructions
Step by step:
1. Set the selector switch to position 0 (OFF).
0
I
M00
4. Press q.
Display indicates:
LANGUAGE/CONTRAS
VIEW
EDIT
M01
5. Press 8 .
Display indicates:
ENTER PASSWORD
0 * * *
:EDIT
:OK C:ESC
6. Enter password:
Press 8 4 times = 0000 (default factory password).
34
Operation instructions
M010
7. Press 8 .
Display shows the set value.
EDIT
M010
LANGUAGE
ENGLISH
:EDIT C:ESC
8. Press 8 again to enter the edit mode.
Display indicates:
EDIT
M010
LANGUAGE
ENGLISH
:EDIT
:OK C:ESC
35
7.
Indications
7.1.
Operation instructions
For actuators equipped with process controllers, status indication S6 is displayed instead of status indication S0. The description below applies to both
indications (S0 und S6).
Line 1 indicates the current operation mode (LOCAL MODE, OFF,
SETPOINT MODE, )
LOCAL MODE
S0
OPEN
E2
100 %
RUNNING OPEN
S0
OPEN
E2
100 %
RUNNING OPEN
S0
OPEN
E2
100%
RUNNING OPEN
S0
OPEN
E2
100%
RUNNING OPEN
RUNNING OPEN
Actuator runs logically OPEN (remains set during operation pauses).
RUNNING CLOSE
Actuator runs logically CLOSE (remains set during operation pauses).
OPEN POSITION
End position OPEN reached.
36
Operation instructions
CLOSED POSITION
End position CLOSED reached.
SETPOINT POSITION
Setpoint (modulating actuators only).
37
7.2.
Operation instructions
Indication lights/LEDs
The indication lights/LEDs locally display the different operation states as
optical signals. The signals can be freely assigned.
Figure 23 shows the indication lights/LEDs on the local controls:
Figure 23
Version (standard):
LED marking with letters
Version (option):
LED marking with figures
illuminated
blinking
LED 2 (T)
illuminated
LED 3 (Th)
illuminated
LED 4 (T)
illuminated
illuminated
blinking
LED 5 (right)
(
symbol)
Information
7.3.
.
..
auma
4
1
2
5
1
2
3
38
Cover
Indicator disc
Indicator mark
4
5
Operation instructions
8.
Signals
8.1.
8.2.
OUTPUT
OUTPUT
OUTPUT
OUTPUT
OUTPUT
CONTACT
CONTACT
CONTACT
CONTACT
CONTACT
1
2
3
4
5
=
=
=
=
=
CLOSED POSITION
OPEN POSITION
REMOTE SW. POSITION
TORQUE FAULT (CLOSE)
TORQUE FAULT (OPEN)
For further information on this topic refer to Manual (Operation and setting)
AUMATIC AC 01.1/ACExC 01.1.
8.3.
.
.
Valve position
39
9.
Operation instructions
Commissioning
Prior to any electrical operation (motor operation), ensure that all commissioning settings described in this clause have been performed
1. Set the selector switch to position 0 (OFF).
0
I
Information
The selector switch is not a mains switch. The actuator control is disabled in
0 (OFF) position. The controls power supply is maintained.
2. Switch on the power supply.
3. Perform the settings described in this clause.
Please note that for low temperature versions, the controls require a heat-up
time.
This heat-up time is applicable in case the actuator and the controls are not
live and have cooled down to ambient temperature. Under these conditions,
the following heat-up times have been met prior to commissioning after connection to the voltage supply:
For 40 C = 30 min.
For 50 C = 60 min.
For 60 C = 100 min.
Figure 25: Sketch illustrating the heat-up time.
Figure 25
t [min.]
100
60
50
30
40
10
20
30
40
50
60 [C]
Operation instructions
NOTICE
Limit seating
The limit switching is set in such a way that the actuator switches off at the
desired switching points. The torque switching acts as an overload protection for the valve.
Torque seating
The torque switching is set to the desired tripping torque. After reaching the
tripping torque the actuator is turned off.
The limit seating is used for signalling that the limit switching is tripped
shortly before reaching the set tripping torque. If this is not the case, one of
the following fault signals is displayed: TSO FAULTS or TSC FAULTS
(menu S1).
Step by step:
1. Set the selector switch to position 0 (OFF).
9.1.
SETTINGS
OPERATIONAL DATA
4. Press 8 .
41
Operation instructions
Display indicates:
SETTINGS
SEATING MODE
TORQUE
LOCAL CONTROLS
M11
5. Press 8 .
Display indicates:
SEATING MODE
VIEW
EDIT
M110
VIEW
M1101
OPEN POSITION
CLOSED POSITION
VIEW
CLOSED POSITION
LIMIT
C:ESC
OPEN POSITION
LIMIT
C:ESC
M110
10. Press q.
Display indicates:
SEATING MODE
VIEW
EDIT
11. Press 8 .
42
M111
Operation instructions
:OK C:ESC
EDIT
M1111
OPEN POSITION
CLOSED POSITION
EDIT
M1111
CLOSED POSITION
LIMIT
:EDIT C:ESC
p q are also used here to change between the OPEN POSITION (left
figure) and CLOSED POSITION (right figure) displays.
14. Press 8 again to enter the edit mode.
Display indicates:
EDIT
M1110
OPEN POSITION
LIMIT
:EDIT
:OK C:ESC
EDIT
M1111
CLOSED POSITION
LIMIT
:EDIT
:OK C:ESC
EDIT
M1111
CLOSED POSITION
LIMIT
:EDIT C:ESC
43
9.2.
Operation instructions
44
Operation instructions
9.3.
NOTICE
Figure 26
1
3
2
4
1. Loosen both lock screws (3) at the indicator disc (figure 26).
2. Turn torque dial (4) for setting the required torque (1 da Nm = 10 Nm).
Example:
Figure 26 shows the following setting:
3.5 da Nm = 35 Nm for direction CLOSE
4.5 da Nm = 45 Nm for direction OPEN
3. Fasten lock screws (3) again.
The torque switches setting is complete.
Information
..
45
9.4.
Operation instructions
1
2
Black section
Setting spindle for end position
CLOSED
Pointer for end position CLOSED
4
5
White section
Setting spindle for end position
OPEN
Pointer for end position OPEN
46
Operation instructions
9.5.
1
2
Black section
Setting spindle running direction
CLOSE
Pointer running direction CLOSE
4
5
White section
Setting spindle running direction
OPEN
Pointer running direction OPEN
47
9.6.
Operation instructions
Test run
Perform test run only once all settings previously described in the Commissioning clause have been performed.
auma
48
Operation instructions
4
5
2
3
1
2
3
Screw plug
Seal
Hollow shaft
4
5
6
(OPEN)
3. If the end position setting is incorrect: Set limit switching again (page
46).
9.6.3 Perform reference operation
For actuators with feedback signal (RWG, potentiometer), a reference operation has to be performed after the setting has been changed:
Operate actuator electrically (via the push buttons OPEN and CLOSE of
the local controls) once to the end position OPEN and once to the end
position CLOSED.
If no reference operation is performed after changing the limit switching,
the feedback signal via the bus is not correct. The bus signals the missing reference operation as a warning.
.
.
49
9.7.
Operation instructions
Potentiometer
50
Operation instructions
9.8.
Ia
Uv
I
KMS TP_ _ 4 / _ _ _
3-/4-wire system
0 20 mA, 4 20 mA
24 V DC, 15 %
smoothed
24 mA
For 20 mA output current
600
RB
Figure 31
1
2
3
4
5
1.
2.
3.
4.
5.
6.
7.
Information
51
9.9.
Operation instructions
52
Operation instructions
53
10.
Operation instructions
Corrective action
..
Figure 32
Information
54
The red test buttons (1) and (2) are used for manual operation of the limit
switches:
Turn test button (1) in direction of the TSC arrow:
Torque switch CLOSED trips.
The indication light torque fault OPEN on the local controls is illuminated.
Press push button OPEN to reset the fault (red indication light) by operating the device in the opposite direction.
Turn test button (2) in direction of the TSO arrow:
Torque switch OPEN trips.
The indication light torque fault CLOSE on the local controls is illuminated.
Press push button CLOSE to reset the fault (red indication light) by operating the device in the opposite direction.
If the actuator is equipped with a DUO limit switching (option), the intermediate position switches will be operated at the same time.
Turn test button (1) in direction of the LSC arrow:
Limit switch CLOSED trips.
Turn test button (2) in direction of the LSO arrow:
Limit switch OPEN trips.
Operation instructions
Remedy
Actuator runs to end stop although the limit switches work properly.
The overrun was not considered when setting the limit switching.
The overrun is generated by the inertia of both the actuator and the valve
and the delay time of the controls.
1. Determine overrun:
Overrun = travel covered from switching off until complete standstill.
2. Set limit switching again (page 46) considering the overrun (turn
handwheel back by the amount of the overrun).
E2
S0
100%
OPEN POSITION
EMERGENCY STOP
E2
S0
100%
OPEN POSITION
Possible cause
Remedy
.
.
RESTRICTED means that the local controls of the AUMATIC have not
been released yet.
EMERGENCY STOP signifies that the EMERGENCY STOP operation
mode has been activated upon operating an EMERGENCY STOP button (option).
For RESTRICTED:
A release must be initiated externally via bus or input signal. See parameter ENABLE LOCAL MODE.
For EMERGENCY STOP:
EMERGENCY STOP button released.
55
Operation instructions
S0
OPEN
E2
100%
FAULT IND.
FAULT IND.
A fault has occurred
For further information, press qp and go to status indication S1.
WARNING IND.
A warning has occurred
For further information, press qp and go to status indication S2.
FAULT + WARNING
Faults as well as warnings have occurred.
For further information, press qp and go to status indications S1
(faults) or S2 (warnings).
FLT + NR
Faults and the NOT READY IND. signal have occurred.
For further information, press qp and go to status indications S1 or S3.
WRN + NR
Faults and the NOT READY IND. signal have occurred.
For further information, press qp and go to status indications S2 or S3.
FLT + WRN + NR
Faults, warnings, and the NOT READY IND. signal have occurred.
For further information, press qp and go to status indications S1 to S3.
56
Operation instructions
10.2.2 Status indication S1 - faults
S1
NO FAULT
NO FAULT
No fault has occurred.
INTERNAL FAULT
Internal fault has occurred.
For further information:
1. Go to group D0: Press C and hold it down until diagnostic indication D0
is displayed.
2. Go to diagnostic indication D2: Press q twice.
LOSS OF PHASE
One phase is missing.
Test/connect phases.
THERMAL FAULT
Motor protection tripped.
Wait for cooling off.
If the fault indication display persists after cooling off:
Set selector switch to position Local control (LOCAL) and reset fault
indication via Reset push button, or
Issue reset command via fieldbus.
Check fuse F4.
CONFIGURATION FAULT
The controls configuration is incorrect.
For further information:
1. Go to group D0: Press C and hold it down until diagnostic indication D0
is displayed.
2. Go to diagnostic indication D4: Press q four times.
57
Operation instructions
S2
NO WARNING
NO WARNING
No warnings have occurred.
WARNING OPER.TIME
The preset running time for a travel between end position OPEN and end
position CLOSED has been exceeded.
Set the running time (MONITOR TRIGGERS parameter) in accordance
with the actual running time.
Check tripping behaviour of end position switches.
Check actuator mechanics.
WARNING STARTS/RUN
The preset values for max. starts/h or max. running time/h have been
exceeded.
Check modulating behaviour.
Increase dead time.
Reduce number of nominal value changes.
INTERNAL FEEDBACK
Position transmitter is not standardised.
Operate actuator into both end positions (OPEN and CLOSED).
INTERNAL WARNING
Internal warnings have occurred.
For further information:
1. Go to group D0: Press C and hold it down until diagnostic indication D0
is displayed.
2. Go to diagnostic indication D3: Press q three times.
FEEDBACK E2 LOSS
Signal loss of position transmitter.
Check position transmitter signal.
1. Go to group D0: Press C and hold it down until diagnostic indication D0
is displayed.
2. Go to diagnostic indication D7, D8, or D9: Press q either seven, eight,
or nine times.
Check position transmitter wiring.
Check POSITION E2. The setting must correspond to the wiring diagram.
SETPOINT E1 LOSS
Signal loss of the set point.
Check wiring.
TORQUE E6 LOSS
Signal loss of torque source.
Check wiring.
58
Operation instructions
P-FEEDBACK E4 LOSS
Signal loss of the actual process value E4 (only if PID controller is available
and active).
Check wiring.
59
Operation instructions
S3
READY
READY
Actuator can be operated from REMOTE.
NOT REMOTE
Actuator cannot be operated from REMOTE as the selector switch is in
position LOCAL or OFF (0).
WRONG COMMAND
Indicates that inadmissible operation commands have been received via
Foundation Fieldbus.
EMERGENCY MODE
The EMERGENCY operation mode is active.
EXTERNAL CONTROLS
For combination fieldbus/standard interface function:
Operation via parallel interface.
ACTUATOR LOCKED
Actuator locked (only set for special applications e.g. for by-pass function).
60
Operation instructions
10.3. Fuses
Hazardous voltage!
Electric shock possible.
Disconnect device from the mains before opening.
DANGER
F1/F2
Rear cover
Electrical connection
F3
F4
F 1/F 2
Size
6.3 x 32 mm
Reversing contactors
Voltage supply 500 V
1 A T; 500 V
K002.277
Reversing contactors
Voltage supply 500 V
2 A FF; 660 V
K002.665
15 A FF; 500 V
K001.189
30 A FF; 500 V
K006.965
1 A T; 500 V
K002.277
Internal 24 V DC supply
Internal 24 V AC supply (115 V AC) for:
Heater, switch compartment, reversing contactors control,
PTC tripping device
for 115 V AC also control inputs OPEN - STOP - CLOSE
..
.
Table 12
F3
F4
5 x 20 mm
5 x 20 mm
1.0 A T; 250 V
1.25 A T; 250 V
1.0 A T; 250 V
0.315 A T; 250 V
F5
61
Operation instructions
..
..
The motor has to cool down before the operation can be resumed.
Depending on the parameter setting, the fault signal is either automatically
reset or the fault signal has to be acknowledged.
..
For further information on this topic refer to Manual (Operation and setting)
AUMATIC AC 01.1/ACExC 01.1 Foundation Fieldbus.
62
Operation instructions
11.
CAUTION
Service
..
Figure 34
Grease nipple
..
63
11.2. Maintenance
Maintenance intervals
Lubricant change
.
..
..
Operation instructions
..
..
electronic scrap
various metals
plastics
greases and oils
.
.
.
64
Collect greases and oils during disassembly. Generally, these substances are hazardous to water and must not be released into the environment.
Arrange for controlled waste disposal of the disassembled material or for
separate recycling according to materials.
Observe the national regulations for waste disposal.
Operation instructions
Notes
65
12.
66
Operation instructions
Operation instructions
Note:
Please state type and commission no. of the device (see name plate) when ordering spare parts. Only original AUMA
spare parts should be used. Failure to use original spare parts voids the warranty and exempts AUMA from any liability. Delivered spare parts may slightly vary from the representation.
No.
001.0
002.0
003.0
005.0
005.1
005.2
005.3
005.4
006.0
009.0
010.0
017.0
018.0
019.0
020.0
022.0
023.0
024.0
025.0
058.0
061.0
070.0
079.0
080.0
155.0
500.0
501.0
502.0
503.0
504.0
505.0
506.0
507.0
511.0
514.0
514.1
516.1
535.1
539.0
542.0
549.1
551.1
553.0
554.0
556.0
556.1
557.0
558.0
559.0-1
559.0-2
560.0-1
560.0-2
560.1
560.2
566.0
566.1
Designation
Housing
Bearing flange
Hollow shaft without worm wheel
Worm shaft
Motor coupling
Coupling pin
Manual drive coupling
Pull rod
Worm wheel
Planetary gear for manual drive
Retaining flange
Torque lever
Gear segment
Crown wheel
Swing lever
Drive pinion II for torque switching
Output drive wheel for limit switching
Intermediate wheel for limit switching
Locking plate
Wire for protective earth (pin)
Torque switching head
Motor (VD motor incl. no. 079.0)
Planetary gear for motor drive (SA/SAR
07.1 14.1 for VD motor)
Planetary gear for motor drive (SA/SAR
16.1 for AD90 motor)
Reduction gearing
Cover for switch compartment
Socket carrier (complete with sockets)
Pin carrier without pins
Socket for controls
Socket for motor
Pin for controls
Pin for motor
Plug cover
Screw plug
Output drive form A (without stem nut)
Axial needle roller bearing
Output drive shaft D
Snap ring
Screw plug
Handwheel with ball handle
Output socket B3/B4/E
Parallel key
Mechanical position indicator
Socket carrier with motor cable harness
Potentiometer for position transmitter
Potentiometer without slip clutch
Heater
Blinker transmitter including pins at wires
(without impulse disc and insulation plate)
Control unit without torque head, without
switches
Control unit with magnetic limit and torque
transmitter (MWG) for Non-intrusive version in combination with AUMATIC integral controls
Switch stack for OPEN direction
Switch stack for CLOSE direction
Switch for limit/torque switching
Switch case
Position transmitter RWG
Potentiometer for RWG without slip clutch
Type
Sub-assembly
Sub-assembly
Sub-assembly
Sub-assembly
Sub-assembly
Sub-assembly
Sub-assembly
Sub-assembly
Sub-assembly
Sub-assembly
Sub-assembly
Sub-assembly
Sub-assembly
Sub-assembly
Sub-assembly
Sub-assembly
No.
566.2
566.3
567.1
568.1
568.2
568.3
569.0
569.1
569.2
574.1
575.1
S1
S2
Designation
Electronic board RWG
Wire harness for RWG
Slip clutch for potentiometer/RWG
Stem protection tube
(without cap)
Cap for stem protection tube
V-seal
Change-over lever assly.
Change-over lever
Notched pin
Radial seal output drive A for ISO flange
Stem nut type A
Seal kit, small
Seal kit, large
Type
Sub-assembly
Sub-assembly
Sub-assembly
Set
Set
Sub-assembly
Sub-assembly
Sub-assembly
Sub-assembly
Sub-assembly
Sub-assembly
Sub-assembly
Sub-assembly
Sub-assembly
Sub-assembly
Sub-assembly
Sub-assembly
Sub-assembly
Sub-assembly
Sub-assembly
Sub-assembly
Sub-assembly
Sub-assembly
Sub-assembly
Sub-assembly
Sub-assembly
Sub-assembly
Sub-assembly
Sub-assembly
Sub-assembly
Sub-assembly
Sub-assembly
67
68
Operation instructions
Operation instructions
Note:
Please state type and commission no. of the device (see name plate) when ordering spare parts. Only original AUMA
spare parts should be used. Failure to use original spare parts voids the warranty and exempts AUMA from any liability. Delivered spare parts may slightly vary from the representation.
No.
001.0
002.0
002.3
006.0
008.1
009.0
011.1
050.1
500.0
501.0
502.0
503.0
504.0
505.0
506.0
507.0
507.1
508.0
509.1
510.0
S
Designation
Housing
Local controls
Local controls board
Power supply
Bus interface
Logic board
Relay board
Bus connection board
Cover
Socket carrier (complete with sockets)
Pin carrier without pins
Socket for controls
Socket for motor
Pin for controls
Pin for motor
Electrical connection for bus without connection board (050.0)
Frame
Switchgear
Padlock
Fuse kit
Seal kit
Type
Sub-assembly
Sub-assembly
Sub-assembly
Sub-assembly
Sub-assembly
Sub-assembly
Sub-assembly
Sub-assembly
Sub-assembly
Sub-assembly
Sub-assembly
Sub-assembly
Sub-assembly
Sub-assembly
Set
Set
69
13.
Operation instructions
Technical data
Torque range
Output speed
Motors
Insulation class
Motor protection
Self-locking
Limit switching
Torque switching
SA
SAR
SA
SAR
1) Based on 20 C ambient temperature and at an average load with running torque or modulating torque according to Technical data SA or SAR
70
Operation instructions
Switchgear
Voltage output
Local controls
2) The reversing contactors are designed for a lifetime of 2 million starts. For applications requiring a high number of starts, we recommend the use of thyristor units.
3) Requires positioner in the actuator
4) Not possible in combination with PTC tripping device
71
Operation instructions
Standard:
5) During an adjustable period (factory setting 10 seconds), faults in the supply voltage (e.g. voltage drops) will not lead to a fault signal.
6) Requires position transmitter in the actuator
72
Operation instructions
73
Operation instructions
Corrosion protection
Finish coating
Colour
Ambient temperature
Lifetime
Weight
Accessories
Wall bracket11))
74
Operation instructions
Notes
75
14.
Certificates
76
Operation instructions
Operation instructions
Index
A
Accessories for assembly
Assembly
17
13
B
Bus cables
21
C
Cable installation
Cable installation in accordance
with EMC
Commission number
Commissioning
Connecting cables
Control
Corrective action
Corrosion protection
Cross sections
Current consumption
D
Declaration of Conformity
Declaration of Incorporation
Disconnect switches
Disposal and recycling
Double sealed intermediate frame
DUO limit switching
19
19
9
40
28
10
55
12
23
19
78
78
19
65
29
47
E
Electrical connection
19
Electronic position transmitter RWG
52
F
Faults
Faults during commissioning
Fuses
Fuses on site
57
55
62
19
G
Ground connection, external
29
H
Handwheel
Handwheel fitting
Heater
Heat-up time
30
13
23
40
I
Indications
Indicator disc
Intermediate positions
Internet
Intrusive
36
44,53
47
10
11
L
Language change in the display
Limit switching
Long-term storage
Low temperature version
Lubricant change
M
Mains connection
Maintenance intervals
Manual operation
Mechanical position indicator
Motor heater
Motor operation
Motor protection
Mounting
Mounting positions of the local
controls
N
Non-Intrusive
34
46
12
40
65
22
65
30
53
23
31
63
14
18
11
O
Operation
Output drive type A
Output drive types
B1, B2, B3, B4, B, and E
Overrun
14
56
P
Packaging
Parking frame
Password entry
Position indicator
Position transmitter RWG
Potentiometer
Protection cover
Protection on site
Protection tube
Protective earth
PTC thermistors
Push-to-run operation
12
29
33
53
52
51
29
19
17
23
63
31
30
15
R
Rated power
Reference documents
Running indication
72
2
38
S
Safety instructions
Self-retaining mode
Service
Short-circuit protection
Signals
Size
Spare parts list
Controls
Multi-turn actuator
Status indication
Stem nut
Storage
5
31
64
19
39
10
68
70
68
36
15
12
T
Technical data
Terminal plan
Test run
Thermoswitches
Torque switching setting
Transport
Tripping torque
Type
72
19
48
63
45
12
45
10
V
Valve position
36
W
Wall bracket
Warnings
Wiring diagram (name plate)
Wiring diagram locating
28
57
10
19
77
AUMA worldwide
Europe
AUMA Riester GmbH & Co. KG
Plant Mllheim
DE-79373 Mllheim
Tel +49 7631 809 - 0
Fax +49 7631 809 - 1250
riester@auma.com
www.auma.com
Plant Ostfildern-Nellingen
DE-73747 Ostfildern
Tel +49 711 34803 - 0
Fax +49 711 34803 - 3034
riester@wof.auma.com
Service Center Cologne
DE-50858 Kln
Tel +49 2234 2037 - 9000
Fax +49 2234 2037 - 9099
Service@sck.auma.com
Service Center Magdeburg
DE-39167 Niederndodeleben
Tel +49 39204 759 - 0
Fax +49 39204 759 - 9429
Service@scm.auma.com
Service Center Bavaria
DE-85386 Eching
Tel +49 81 65 9017- 0
Fax +49 81 65 9017- 2018
Riester@scb.auma.com
AUMA Armaturenantriebe GmbH
AT-2512 Tribuswinkel
Tel +43 2252 82540
Fax +43 2252 8254050
office@auma.at
www.auma.at
AUMA (Schweiz) AG
CH-8965 Berikon
Tel +41 566 400945
Fax +41 566 400948
RettichP.ch@auma.com
SIGURD SRUM A. S.
NO-1300 Sandvika
Tel +47 67572600
Fax +47 67572610
post@sigurd-sorum.no
INDUSTRA
PT-2710-297 Sintra
Tel +351 2 1910 95 00
Fax +351 2 1910 95 99
jpalhares@tyco-valves.com
OY AUMATOR AB
FI-02230 Espoo
Tel +35 895 84022
Fax +35 895 8402300
auma@aumator.fi
AUMA France S.A.R.L.
FR-95157 Taverny Cedex
Tel +33 1 39327272
Fax +33 1 39321755
info@auma.fr
www.auma.fr
AUMA ACTUATORS Ltd.
GB- Clevedon North Somerset BS21 6QH
Tel +44 1275 871141
Fax +44 1275 875492
mail@auma.co.uk
www.auma.co.uk
AUMA ITALIANA S.r.l. a socio unico
IT-20023 Cerro Maggiore (MI)
Tel +39 0331 51351
Fax +39 0331 517606
info@auma.it
www.auma.it
AUMA BENELUX B.V.
NL-2314 XT Leiden
Tel +31 71 581 40 40
Fax +31 71 581 40 49
office@benelux.auma.com
www.auma.nl
78
Africa
AUMA South Africa (Pty) Ltd.
ZA-1560 Springs
Tel +27 11 3632880
Fax +27 11 8185248
aumasa@mweb.co.za
A.T.E.C.
EG- Cairo
Tel +20 2 3599680 - 3590861
Fax +20 2 3586621
atec@intouch.com
America
AUMA ACTUATORS INC.
US-PA 15317 Canonsburg
Tel +1 724-743-AUMA (2862)
Fax +1 724-743-4711
mailbox@auma-usa.com
www.auma-usa.com
Asia
AUMA Actuators (Tianjin) Co., Ltd.
CN-300457 Tianjin
Tel +86 22 6625 1310
Fax +86 22 6625 1320
mailbox@auma-china.com
www.auma-china.com
AUMA (INDIA) PRIVATE LIMITED
IN-560 058 Bangalore
Tel +91 80 2839 4655
Fax +91 80 2839 2809
info@auma.co.in
www.auma.co.in
AUMA JAPAN Co., Ltd.
JP-210-0848 Kawasaki-ku, Kawasaki-shi
Kanagawa
Tel +81 44 329 1061
Fax +81 44 366 2472
mailbox@auma.co.jp
www.auma.co.jp
Petrogulf W.L.L
QA- Doha
Tel +974 4350 151
Fax +974 4350 140
pgulf@qatar.net.qa
Australia
BARRON GJM Pty. Ltd.
AU-NSW 1570 Artarmon
Tel +61 294361088
Fax +61 294393413
info@barron.com.au
www.barron.com.au
2007-10-24
79
Y004.589/003/en/3.08