Professional Documents
Culture Documents
Experiment One
* Objectives:
- To be familiar with generating station components.
- To identify the step-up transformer ratio.
- To evaluate the line-to-line and phase voltages and currents.
- To evaluate the generator impedance.
* Procedure:
1- Examine the board of generation and define the function of
each element.
2- Connect the power and measurement circuits at no-load. The
transformer is connected in -Y configuration.
3- Measure the L-L voltages at the generator terminals and at
the configuration output. What are the values of currents in
lines?
L1-L2
L1-L3
L2-L3
I1
I2
I3
L1-L3
L2-L3
I1
I2
I3
X1
Z1
R2
X2
Z2
R3
X3
Z3
L1-L3
L2-L3
I1
I2
I3
L1-L3
L2-L3
I1
I2
I3
10
11
12
13
14
Transmission Lines
* Objectives:
- To be familiar with transmission lines components.
- To identify the drop voltage at the transmission line.
- To be familiar the operation of two lines in parallel.
- To see the effect of capacitors on the transmission line.
* Procedure:
1- Define the impedance of each phase of the 3-phase
transmission line.
R1
X1
Z1
R2
X2
Z2
R3
X3
Z3
Vo
15
R1
X1
Z1
R2
X2
Vi
Z2
R3
X3
Z3
Vo
Q2
Q3
With capacitors
VL1-L2
VL1-L3
VL2-L3
Q1
Q2
16
Q3
17
18
19
20
21
22
23
24
25
26
27
28
- Procedure:
1) Connect the Distribution module to an RLC load through the
protection relay RE 1 as in the diagram.
2) From the Set menu select Relays then select the relay K1 and change it
to Trip I> .
3) Select the mode to De-energized and to No-latched.
4) Now select the 50/51 relay and select the following:
Icurve : IEC / BS A
I>inv : 0.2 In
t>inv : 0.15 s
5) Make the load current 1A, then gradually start increasing the current
by increasing the load, make this four times, and each time record the
time required for tripping after the relay starts.
6) Draw the time current characteristics for this relay.
29
Current
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
- Procedure:
1) Connect the Distribution module to an RLC load through the
protection relay RE 1 as in the diagram.
2) From the Set menu select Relays then select the relay K1 and change it
to Trip I> .
3) Select the mode to De-energized and to No-latched.
4) Now select the 50/51 relay and select the following:
Icurve : IEC / BS A (standard inverse)
I>inv : 0.2 In
t>inv : 0.15 s
5) Make the load current 1A, then gradually start increasing the current
by increasing the load, make this four times, and each time record the
time required for tripping after the relay starts.
6) Draw the time current characteristics for this relay.
7) Now make the same for Icurve : IEC / BS B (Very Inverse) and draw
the time current characteristics.
8) Now make the same for Icurve : IEC / BS C (Extremely Inverse) and
draw the time current characteristics.
9) Draw the time current characteristics for all the three curves.
Curve Typre
Current
IEC / BS A
Standard Inverse
48
IEC / BS B
Very Inverse
IEC / BS A
Extremely Inverse
49
50
51
52
53
Calibration:
The trip current must be set considering the nominal current of the
device to be protected but taking into consideration also the
selectivity.
Take into consideration that the current to be set must be
calculated as a ratio between the desired trip current and 5 A that
is the nominal current of the relay. For example, if I want to set a
trip current of 2 A (as threshold that makes the current trips at
dependent time) I have to insert 2 / 5 = 0.4
General notes on protection 50/51
The relay enables to insert a characteristic of max trip current that
is composed by 3 curves:
The first section is an inverse time characteristic ( trip time
that is inverse proportional to the current)
The other two characteristics are with independent time
from the current (constant delay)
General notes on protection 50/51
The relay enables to insert a characteristic of max trip current that
is composed by 3 curves:
Thefirst section is an inverse time characteristic ( trip time
that is inverse proportional to the current)
The other two characteristics are with independent time
from the current (constant delay)
Normally two characteristics are enough, the first at inverse time
and the second at definite time in which the inserted current is
lower than the short circuit current and the trip time is 0.01
0.05 s (it could be instantaneous if selectivity is not required)
We remind you that the inverse time characteristic starts with
current > 1.1 for set current.
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
72
where:
is the magnetic flux in the core;
C is a constant dependent on the particular power transformer
construction details;
U is the voltage
f is the frequency of the voltage signal.
Typically, a power transformer magnetic core is designed in such way
that it will tolerate 110% of rated U/f ratio being applied to the power
transformer without saturation. Under such steady state operating
condition (e.g. U/f < 110%) the magnetizing current drawn by the power
transformer will be quite small. A typical RMS value of the magnetizing
current is from 0.2% to 0.5% for power transformers with a rating above
30MVA . However, if the 110% over-excitation limit is exceeded the
magnetic core will start to saturate. This will result in a sharp magnitude
increase of the magnetizing current.
73
75
76