Placement of Super Conducting Fault Current Limiters to mitigate


fault Currents in Smart Grids with different types of
Distributed Generation Sources
1

Sai Sowmya Varanasi


Ramachandra college of Engineering,4th B.Tech saisowmya.varanasi@gmail.com
from all power sources and has no negative effect on the integrated
Sources was suggested.

Abstract

The important application of superconducting fault


current limiters (SFCL) for upcoming smart grid is its possible effect on
the reduction of abnormal fault current and the suitable location in the
micro grids. Due to the grid connection of the micro grids with the
current power grids, excessive fault current is a serious problem to be
solved. In this paper, a resistive type SFCL model was implemented
using Simulink and SimPowerSystem blocks in Matlab. The designed
SFCL model could be easily utilized for determining an impedance level
of SFCL according to the fault-current-limitation requirements of
various kinds of the smart grid systems. In addition, typical smart grid
model including generation, transmission and distribution network with
different types of DGs having different ratings such as wind, solar,
diesel was modeled to determine the location and the performance of
the SFCL. A 10 MVA wind farm, 675 KW solar and 3MVA diesel
generator was considered for the simulation. Three phase fault has been
simulated at distribution grid and the effect of the SFCL and its
location on the wind farm, solar, diesel generator fault currents was
evaluated. The SFCL location in Smart Grid with different types
Distributed Generation Sources have been proposed and their
performances were analyzed.

2. SIMULLINK MODELS SET-UP


Matlab/Simulink/SimPowerSystem was selected to design and
implement the SFCL model. A complete smart grid power network
including generation, transmission, and distribution with an
integrated wind farm, solar, diesel generator model [6] was also
implemented in it. Simulink /SimPowerSystem have number of
advantages over its contemporary simulation software (like EMTP,
PSPICE) due to its open architecture, a powerful graphical user
interface and versatile analysis.
2.1. Power System Model
The modeled power system consists of an electric transmission
and distribution power system. Newly developed micro grid model
was designed by integrating a 10 MVA wind farm, 675 KW solar,
3MVA diesel generator with the distribution network. Fig.1 shows
the power system model designed in Simulink/SimPowerSystem.
The power system is composed of a 100 MVA conventional power
plant, composed of 3-phase synchronous machine, connected with
200 km long 154 kV distributed-parameters transmission line
through a step-up transformer TR1. At the substation (TR2),
voltage is stepped down to 22.9 kV from 154 kV. High power
industrial load (6 MW) and low power domestic loads (1 MW each)
are being supplied by separate distribution branch networks. The 10
MVA wind farm, 675 KW solar, 3MVA diesel generator are
connected directly through Step up transformer to the grid in Fig.1
artificial fault three-phase-to-ground fault and locations of SFCL
are indicated in distribution grid. Three prospective locations for
SFCL installation are marked as Location 1, Location 2 and
Location 3. Generally, conventional fault current protection devices
are located in Location 1 and Location 2. The output current of
wind farm, solar, diesel measured at the output of DG for various
SFCL locations have been measured and analyzed.

Index TermsFault current, micro grid, smart grid, SFCL, wind farm,
solar, diesel.

1.

INTRODUCTION

Conventional protection devices installed for protection of


excessive fault current in electric power systems allows initial two
or three fault current cycles to pass through before getting activated.
But, superconducting fault current limiter (SFCL) is innovative
electric equipment [1] which has the capability to reduce fault
current level within the first cycle of fault current. The first-cycle
suppression of fault current by a SFCL results in an increased
transient stability of the power system carrying higher power with
greater stability.
Smart grid is the novel term used for future power grid which
integrates the modern communication technology and renewable
energy resources to supply electric power which is cleaner, reliable,
resilient and responsive than conventional power system. One of the
important aspects of the smart grid is decentralization of the power
grid network into smaller grids, which are known as micro grids,
having distributed generation sources (DG) connected with them.
These micro grids need to integrate various kinds of DGs and loads
with safety should be satisfied. The direct connection of DGs with
the power grid are the excessive increase in fault current and the
islanding issue which is caused, when despite a fault in the power
grid, DG keeps on providing power to fault-state network . Solving
the problem of increasing fault current in micro grids by using
SFCL technology is the main topic of this work. In this paper, the
effect of SFCL and its position was investigated considering a wind
farm, solar [5], diesel generator [6] integrated with a distribution
grid model as one of typical configurations of the smart grid. The
impacts of SFCL on the wind farm, solar, diesel generator and the
strategic location of SFCL in a micro grid which limits fault current

2.2. Resistive SFCL Model


The three phase resistive type SFCL was modeled and
considering four fundamental parameters of a resistive SFCL.
These parameters and their selected values are 1) Transition or
response time 2) minimum impedance and maximum impedance
3) Triggering current and 4) recovery time .Its working voltage is
22.9 kV. Fig. 2 shows the SFCL model developed in
Simulink/Simpower System. The SFCL model works as follows.
First, SFCL model calculates the RMS value of the passing current
and then compares it with the Lookup table. Second, if a passing
Current is larger than the triggering current level, SFCLs resistance
increases to maximum impedance level in a pre-defined response
time. Finally, when the current level falls below the

INTERNATIONAL ASSOCIATION OF ENGINEERING & TECHNOLOGY FOR SKILL DEVELOPMENT

www.iaetsd.in

INTERNATIONAL CONFERENCE ON CURRENT INNOVATIONS IN ENGINEERING AND TECHNOLOGY

ISBN: 378 - 26 - 138420 - 5

Fig.1 Power system model designed in Simulink/SimPowerSystem,Fault and SFCL locations are indicated in the diagram

triggering current level the system waits until the recovery time and
then goes into normal state. SFCL is located at different locations.

2.4. Solar model


The terminal equations of the Voltage, Current and Power [5]
used for the devolpement of Solar Simulink model are given by
equations 1,2 and 3.

Fig.2 Single phase SFCL model developed in Simulink/SimPowerSystem.

2.3. Wind Turbine Generator Model


Where Iph is the light generated current, Is is the cell saturation of
dark current, q is the unit electric charge, k is the Boltzmans
constant t is the working temperature of p-n junction, A is the ideal
factor. Iph is the current based on cells working temperature and
solar irradiation level described in equation.2 . Isc is the cells short
circuit current Kt is the temperature coefficient and S is the solar
irradiation level in KW/m2. Power delivered by PV array is given
by equation(3) and PV array is modeled as single diode circuit . The
subsystem can be implemented by using equations 1, 2 and 3.

A 10 MVA wind farm[1] is composed of 5 fixed-speed inductiontype wind turbines,each having a rating of 2MVA at the time of
fault the domestic load is being provided with 3MVA out of which
2.7 MVA is provided by the wind farm. The wind farm is directly
connected with the branch network B6 through the transformer
TR3.Simulink model of wind turbine generator is shown.

Fig.3 Three phase wind turbine generator subsystem model.

Fig.4 Solar model developed in Simulink/SimPowerSystem.

INTERNATIONAL ASSOCIATION OF ENGINEERING & TECHNOLOGY FOR SKILL DEVELOPMENT

www.iaetsd.in

INTERNATIONAL CONFERENCE ON CURRENT INNOVATIONS IN ENGINEERING AND TECHNOLOGY

The output power of pv array is 675KW which is given to the


inverter and then the ouput of model is connected directly to the
branchnetwork B6 through transformer T3. The PV simulink model
is shown in Fig.4.

ISBN: 378 - 26 - 138420 - 5

800

600

Current (Amp)

400

2.5. Diesel Generator Model

200

-200

A lower order model [6] is used for studying dynamics of internal


combustion engines. A self tuning PID controller is developed for
a small size diesel engine and generator set.The output power of
diesel generator is 3.125MVA.The ouput of model is connected
directly to the branchnetwork B6 through transformer T3.The
Simulink model of Governor and diesel engine is shown in Fig.5.

-400

-600
0.25

0.3

0.35

0.4

0.45

0.5

0.45

0.5

Time(Sec)

A. Fault current without SFCL


1200
1000
800

Current(Amp)

600
400
200
0
-200
-400
-600
0.25

Fig.5 Governor and diesel engine Simulink model developed

0.3

0.35

0.4
Time(Sec)

B.Fault current with SFCL at Location 1

The Simulink model of Voltage control and Speed control of diesel


generator shown in Fig.6.
1200
1000
800

Current(Amp)

600
400
200
0
-200
-400
-600
0.25

0.3

0.35

0.4

0.45

0.5

Time(Sec)

C. Fault current with SFCL at Location 2

Fig.6 Voltage and Speed control Simulink model developed


600

3. RESULTS AND CONCLUSIONS

400

Three scenarios of SFCLs possible locations were analyzed for


distribution grid fault occurring in the power system. The
simulation is carried by placing SFCL in Location 1,2 and 3 by
considering one DG at a time at the position shown in fig.1.

Current(Amp)

200

-200

-400

3.1. Wind Turbine Generator as DG


-600
0.25

0.3

0.35

0.4

0.45

0.5

Time(Sec)

Fault currents of one phase where the severity is more and


different locations of SFCL are shown in Fig.7. When a threephase-to-ground fault was initiated in the distribution grid (Fig.1)
SFCL located at Location 1 or Location 2, fault current contribution
from the wind farm was increased . These critical observations
imply that the installation of SFCL in Location 1 and Location 2
instead of reducing, has increased the DG fault current. This sudden
increase of fault current from the wind farm is caused by the abrupt
change of power systems impedance. The SFCL at these locations
(Location 1 or Location 2) entered into current limiting mode and
reduced fault current coming from the conventional power plant
due to rapid increase in its resistance. Therefore, wind farm which
is the other power source and also closer to the Fault is now forced
to supply larger fault current to fault point. In the case when SFCL
is installed at the integration point of wind farm with the grid,
marked as Location 3 in Fig.1 wind farm fault current has been
successfully reduced. SFCL gives 68% reduction of fault current
from wind farm and also reduce the fault current coming from
conventional power plant because SFCL is located in the direct
path of any fault current flowing towards Fault 1.

D.Fault current with SFCL at Location 3

Fig.7 Fault Currents of Wind Turbine Generator.

Comparison of fault currents when SFCL is placed at different


Locations in Fig.1 are shown in Fig.8

Fig.8.Comparison of fault currents at different locations

INTERNATIONAL ASSOCIATION OF ENGINEERING & TECHNOLOGY FOR SKILL DEVELOPMENT

www.iaetsd.in

INTERNATIONAL CONFERENCE ON CURRENT INNOVATIONS IN ENGINEERING AND TECHNOLOGY

ISBN: 378 - 26 - 138420 - 5

3.2. Solar model as DG


Fault currents of one phase where the severity is more and
different locations of SFCL are shown in Fig.9.When a three-phaseto-ground fault was initiated in the distribution grid (in Fig. 1).The
fault without SFCL is greater when compared with SFCL placed at
different Locations the following results were observed. Once again
the best results are obtained when a single SFCL is located at
Location 3, when compared with the remaining two locations. Fault
current has been successfully reduced.SFCL gives 70% reduction of
fault current from Solar module and also reduce the fault current
coming from conventional power plant because SFCL is located in
the direct path of any fault current flowing towards Fault 1.

Fig.10.Comparison of fault currents at different locations

3.3. Diesel Generator as DG

3000

2500

Fault currents of one phase where the severity is more and


different locations of SFCL are shown in Fig.11. In this case when a
three-phase-to-ground fault was initiated in the distribution grid (in
Fig. 1).The fault without SFCL is greater when compared with
SFCL placed at different Locations the following results were
observed. Once again the best results are obtained when a single
SFCL is located at Location 3, when compared with the remaining
two locations. Diesel fault current has been successfully reduced.
SFCL gives 84% reduction of fault current from diesel engine and
also reduce the fault current coming from conventional power plant
because SFCL is located in the direct path of any fault current
flowing towards Fault 1.

2000

C
urrent(am
p)

1500

1000

500

-500

-1000
0.25

0.3

0.35

0.4

0.45

0.5

Time(s ec)

A. Fault current without SFCL


1500

1000

1000

Current(amp)

500

800

-500
C
urrent(Am
p)

600

-1000

-1500
0.25

0.3

0.35

0.4

0.45

0.5

400

200

Time(Sec)

B. Fault current with SFCL at Location 1

1500
-200
0.25

0.3

0.35

0.4

0. 45

0.5

0.45

0.5

Time(Sec)

1000

Current(amp)

A. Fault current without SFCL


500

1000

800

0
600

-500

0.3

0.35

0.4

0.45

Current(Amp)

-1000
0.25

400

0.5

Time(Sec)

C.Fault current with SFCL at Location 2

200

-200

-400

1000
-600

800
-800
0.25

0.3

0.35

600
400
Current(amp)

0.4
Time(Sec)

B. Fault current with SFCL at Location 1

200
1000

0
800

-200
600

-400
400

-800
0.25

0.3

0.35

0.4

0.45

C
urrent(Am
p)

-600

0.5

200

Time(Sec)
-200

D. Fault current with SFCL at Location 3


-400

-600

Fig.9 Fault Currents of Solar model.

-800
0.25

0.3

0.35

0.4

0. 45

0.5

Time(Sec)

Comparison of fault currents when SFCL is placed at different


Locations in Fig.1 are shown in Fig.10.

C.Fault current with SFCL at location 2

INTERNATIONAL ASSOCIATION OF ENGINEERING & TECHNOLOGY FOR SKILL DEVELOPMENT

www.iaetsd.in

INTERNATIONAL CONFERENCE ON CURRENT INNOVATIONS IN ENGINEERING AND TECHNOLOGY

and diesel. Multiple SFCLs will not used in micro grid because of
their inefficiency both in performance and cost. The strategic
location of SFCL in a power grid which limits all fault currents and
has no negative effect on the DG source is the point of integration
of the DG sources with the power grid.

500

400

300

200

Current(Amp)

ISBN: 378 - 26 - 138420 - 5

100

REFERENCES

-100

-200

[1] Umer A.Khan, J.K.seong, S.H.Lee Feasibility analysis of the


Positioning of Super Conducting Fault Current Limiters for the
Smart Grid Application using Simulink & Simpower Systems
IEEE Transactions on applied superconductivity, vol.21, No.3
June-2011.
[2] S.Sugimoto, J.Kida, H.Aritha Principle and Characteristics of
Fault Current limiters with series compensation IEEE Trans.
on Power Delivery, vol.11,No.2,pp 842-847,Apr 1996.
[3] J.Driensen, P.Vermeyen and R.Belmans Protection issues in
micro grids with multiple distributed generation units in Power conversion conference., Nagoya, April 2007, pp 646-653.
[4] K.Maki ,S.Repo and P.Jarventausta Effect of wind power baSed distributed generation on protection of distribution netwrk
Work in IEEE Developments in Power systems protection,
Dec.2004, vol.1, pp 327-330.
[5] N.Pandiarajan, Ranganath muth Modeling of Photo Voltaic
Module with Simulink international conference on electrical
Energy system (ICEES-2011), 3-5 Jan-2011.
[6] Takyin Takychan Transient analysis of integrated solar/diesel
hybrid power System using MATLAB/Simulink .
[7]
S.N.B.V.Rao Asst Prof. in Ramachandra college of
engineering

-300

-400
0.25

0.3

0.35

0.4

0.45

0.5

Time(Sec)

D.Fault current with SFCL at Location 3

Fig.11 Fault Currents of Diesel Engine.

Comparison of fault currents when SFCL is placed at different


Locations in Fig.1

Fig.12.Comparison of fault currents at different locations

When the SFCL was strategically located at the point of integration


Location 3, the highest fault current reduction was achieved
whatever may be the DG source. The multiple SFCLs in a micro
grid are not only costly but also less efficient than strategically
located single SFCL. Moreover, at Location 3, fault current coming
from the conventional power plant was also successfully limited.
The results of fault currents at three locations with different DG
units are summarized in Table I for comparison.
Table I: Percentage change in fault currents of different DG units
due to SFCL locations
3-Ph Distribution grid fault
DG
type

No
SFCL

Location 1

Location 2

Location 3

Wind

787A

1020A
30% increased

1020A
30% increased

265A
67% decreased

Solar

2675A

1100A
59% decreased

1100A
59% decreased

800A
70% decreased

Diesel

916A

798A
13% decreased

798A
13% decreased

148A
84% decreased

4. CONCLUSION
This paper presented a feasibility analysis of positioning of the
SFCL in rapidly changing modern power grid. A complete power
system along with a micro grid (having a wind farm, solar, diesel
connected with the grid) was modeled and transient analysis for
three-phase-to-ground faults at different locations of the grid were
performed with SFCL installed at different locations of the grid.
This placement of SFCL results in abnormal fault current
contribution from the wind farm and other two sources such as solar