You are on page 1of 4

KM20X

KM20x 0319EN September 2007

0006/6

ISO 9001

KM20X NETWORK
CONTROLLER

KM20x

In addition it can have the following auxiliary functions:


- input/output network connections (64 input / 32 output possibly
broadcast). They allow reading information from GIACOKLIMA
bus devices (to use as input data for auxiliary functions) and writing
the results of auxiliary functions in the GIACOKLIMA bus devices;
- Enthalpy and dew temperature calculation;
- summer and winter compensation;
- comparison operations;
- calculation operations (addition, difference, multiplication, division);
- constants and variables selection operations;
- timer programs;
- optimization of switch on and off phases with self learning function.

Description
KM20X network controller is an instrument for use in a GIACOKLIMA
bus system destined to the control of Giacobini systems for underfloor
systems or ceiling radiant systems associated with K481 and K483
ambient thermostats, KPM20 unit I/O, KD200 display unit and with
KSMS module.

Signalling elements
On the front of the case of the instrument a red LED signals the
operating state of KM20x Controller.
LED for
operating
state signaling.

Versions and codes


The Controller is available in four versions that differ between them
for the available interfaces. To KM202 and KM203 version can be
connected the KD200 Display Unit GIACOKLIMA through a RS485
port. KSMS module for text messages sending and receiving can be
used only associated with KM203 network controller.

CODE

BUILT-IN MODEM

PORT
RS232

PORT
RS485

KM200Y001

NO

KM201Y001

YES

KM202Y001

YES

KM203Y001

NO

Main features
- Possibility to run up to 32 GIACOKLIMA bus instruments connected
on primary bus
- N2 analogical inputs for the connection of active sensors
- N2 analogical inputs for the connection of passive sensors
- Possibility to connect a KD200 Display Unit (only for KM202 version
and KM203 version)
- KM200: Possibility to connect an external modem for remote
control functions
- KM201 and KM202: built-in modem for analogical phone line
- KM203: possibility to connect the KSMS external module for text
messages sending and receiving and for remote control via GSM
phone line.

Main and auxiliary functions


KM20x Controller has 2 main functions:
- runs and coordinates the operation of all GIACOKLIMA bus devices
connected to the system and widens their functions with respect to
the stand-alone operation;
- is an interface for local monitoring (to implement through KD200
Display Unit or PC) and for remote control.

Analogical alarms
Up to 32 analogical alarms can be configured for each connected
GIACOKLIMA bus device. For each alarm a set of parameters should
be set as:
- alarm type (differentiating between maximum and minimum);
- priority level (low, medium or high);
- hysteresis band.

Digital alarms
Up to 32 digital alarms can be configured for each connected
GIACOKLIMA bus device For each alarm a set of parameters should
be set as:
- priority level (low, medium or high);
- significant transition (up/down front).

Communication alarms
In addition to analogical and digital alarms, the Controller runs also
communication alarms. If in operating mode, during a cyclic polling,
the Controller does not receive the reply from a GIACOKLIMA bus
device, it assumes that this device no longer works and triggers a
corresponding communication alarm. This kind of alarm does not
require any configuration, it is always taken into consideration and
always has the highest priority.

KM20X
KM20x 0319EN September 2007

0006/6

ISO 9001

KM20X NETWORK
CONTROLLER

Remote control

Safety

For the operation as interface for remote control, KM20x Controller


should be connected to the phone network via external (KM200)
or built-in (KM201 and KM202) modem. The main functions of the
Controller are:
- alarms report. The Controller makes a continuous evaluation, for
each GIACOKLIMA bus device connected, of the state of a set of
alarms (up to 1.024 digital and/or 1.024 analogical) with automatic
phone call in case one or more alarms with sufficient priority level are
active (not silenced);
- trend storage. The Controller makes a periodical storage of values of
a programmable set of max 32 analogical values. For digital trends
the storage is enabled by events of a programmable set of digital
values (i.e. ON/OFF switching).

KM20x Controller is equipped with an internal clock that can work


for at least 10 days as of the moment in which the device is switched
off. This clock is used to calculate the actual hour. The hours can be
modified with the configuration tool or the KD200 Display Unit.

Device synchronization
An 8 character password can be programmed through the auxiliary
serial port (AUX). When a phone call to the Controller is enabled, it
does not accept the message until the proper password is typed. The
password should be entered .

Installation
Operating mode
At any given moment, KM20x Controller can be only in one of the two
following operating modes:
- operating mode (default);
- configuration mode.

KM20x Controller is fitted in a plastic material storage unit of the size


compliant with standard DIN 43880 appropriate for installation on
standard profiled guide CEI EN 50022. Otherwise the controller can
be wall mounted thanks to slotted holes for the fastening screws fitted
on the case.
Warning!
KM20x Controller does not have a device on/off switch.
This is why an isolating and control device on the power
circuit of the Controller would be appropriate. Exclusively
qualified staff can install the device.

Operating mode
When a KM20x Controller is powered, by default it is in operating
mode. In this operating mode, Controller KM20x carries out its main
functions:
- periodical reading of alarms configured in each GIACOKLIMA bus
device connected;
- real time evaluation of each alarm and generation of alarm flags;
- confrontation between the state of the alarms and their silencing. In
case an alarm has a sufficiently high priority and was not yet silenced,
the Controller enables a phone call to the GIACOMINI Service Center;
- periodical reading of configured trends and storage in the EEPROM
memory. When close to saturation the Controller can be programmed
to call the GIACOMINI Service Center and transfer on the Web Server
the content of memory;
- generation of a communication alarm if a GIACOKLIMA bus device
does not reply to a request of value of the alarm;
- management of messages coming from the GIACOMINI Service
Center.

Connections
KM20x Controller is equipped with terminals to connect several input
and output devices. A faston connection terminal (2 poles) is dedicated
to the connection of 230 V~ network supply. The BUS terminal (4 poles:
RT+, RT-, com, Vs) is dedicated to bus connection.
TERMINAL NUMBER

DESCRIPTION

Primary bus connection input (V)

Primary bus connection input (com)

Primary bus connection input (RT-)

Primary bus connection input (RT+)

5-6

Analogical input 1

7-8

Analogical input 2

9-10

Analogical input 3

Configuration mode

11-12

Analogical input

Unlike the operating mode, the configuration mode is temporary: if no


configuration modification takes place for 3 minutes, the Controller
returns automatically to the operating mode. Notice that:
- usually the configuration of the Controller is set at the factory or
during system commissioning, without using a modem;
- for the configuration a PC is connected through the standard serial
cable (9 pin) to the auxiliary serial port RS-232 (AUX) of the Controller
and the configuration tool is started;
- in case of use of KM202 version the device can be configured
connecting a PC to RS485 port of the KD200 Display Unit: for the
connection a RS232/RS485 converter is necessary;
- anyway it is still possible, during ordinary system operation, to
reconfigure (partially or completely) the Controller in the same way
through the phone line;

13-14

Active sensors supply

KM20X
KM20x 0319EN September 2007

0006/6

ISO 9001

KM20X NETWORK
CONTROLLER

The RS232 MAIN connector (only for KM200 version) is dedicated to


the connection of an external modem for system remote control.

Sizes
B

PORT AUX
9 POLES
DISPLAY

PORT PC AT
9 POLES
CD
RX
TX
DTR
RI
S.GND
DSR
RTS
CTS

1
2
3
4
5
6
7
8
9

3
2

Connection cable
PORT PC/PORT AUX

Connector RS-232 AUX (only for KM200 and KM201 versions) is


dedicated to the connection of a PC for configuration or local monitoring.

Technical data
KM200Y001
Supply

RS232
or RS-485
Serial port (AUX)

RS232 Serial
port (MAIN)

Phone port
A (out)

Phone port
B (in)

The RS-485 connector (only for KM202 and KM203 version) is


dedicated to the connection of a KD200 Display Unit or of a PC for
device configuration. In the latter case for the connection it is necessary
to have a RS232/RS485 converter.
NOTE: the controller can be connected exclusively on the primary bus
of the GIACOKLIMA system.
KM203 ELECTRICAL CONNECTIONS
BUS KD200
4 x 0.25 mmq

KM203

BUS

BUS

4 x 0.25 mmq
ai dispositivi in campo

RS232 - 19200
baud

RS232 - 19200
baud (1)

port MAIN
tel. port A

RS232
configurable (2)
n.a.

n.a.
phone device

n.a.
phone device

2400 baud

2400 baud

0 - 10 Vcc

0 - 10 Vcc

tel. port B

n.a.
Analogical inputs
AI1 (terminals 5-6)
AI2 (terminals 7-8)
AI3 (terminals 9-10)
AI4 (terminals
11-12)

Warning!
Make sure that power supply is turned off as connections
are performed.

0 - 10 Vcc 0
0 - 10 Vcc 0

0 - 10 Vcc

0 - 10 Vcc

(NTC) 0 - 50

(NTC) 0 - 50C

(NTC) 0 - 50C

(NTC) 0 - 50

(NTC) 0 - 50C

(NTC) 0 - 50C

Supply sensors
active
(terminals 9-10
and 11-12)

n.a.

n.a.

+15 Vcc

Primary Bus
(terminals 1, 2, 3, 4)

RS485 - 9600
Baud

RS485 - 9600
Baud

RS485 - 9600
Baud

max. length
shielded cable
from port AUX
to PC

10 m

10 m

10 m

Nr. max devices to


connect to the bus

32

32

32

Transformer
Absorption
Operating
environment
conditions
Relative
humidity

VDE Standards
6 VA

VDE Standards
6 VA

VDE Standards
6 VA

from
0 to + 40 C

from
0 to + 40 C

from
0 to + 40 C

from 10 to 90%, from 10 to 90%, from 10 to 90%,


not condensating not condensating not condensating

Storage
environment
conditions

from
-25 to 70 C

from
-25 to 70 C

from
-25 to 70 C

Sizes
(AxBxC)

125x108x57 mm

125x108x57 mm

125x108x57 mm

0,5 kg

0,5 kg

0,6 kg

ABS/polycarbonate ABS/polycarbonate ABS/polycarbonate


self-extinguishing self-extinguishing self-extinguishing

Protection
degree

IP30

IP30

IP30

ApprovalsMarking CE

EN55022,
EN55024,
EN60950,
EN61000-3-2,
EN61000-3-3

EN55022,
EN55024,
EN60950,
EN61000-3-2,
EN61000-3-3

EN55022,
EN55024,
EN60950,
EN61000-3-2,
EN61000-3-3

BUS KSMS
4 x 0.25 mmq

230 V 50-60 Hz 230 V 50-60 Hz 230 V 50-60 Hz


RS232 - 19200
baud

Weight

230 V~

KM202Y001 e
KM203Y001

Transmission:
port AUX

Case material

BUS GK

KM201Y001

(1) Reserved to connection of KD200 Display Unit


(2) Reserved to connection of external modem (not included in the supply) for
system remote control. Transmission speed can be configured between values:
2400. 4800, 9600, 19200 Baud. External modem 3Com U.S. Robotics 56K
recommended

KM20X
KM20x 0319EN September 2007

0006/6

ISO 9001

KM20X NETWORK
CONTROLLER

Technical specification texts


KM200 - Control and monitoring unit
Control and monitoring device to use in radiant heating and/or cooling
systems associated with the GIACOKLIMA field control devices. It has
n2 serial interfaces RS232.
KM201 - Control and monitoring unit, with built-in modem
Control and monitoring device to use in radiant heating and/or cooling
systems associated with the GIACOKLIMA field control devices. Internal
modem for system remote control tasks and no 1 serial interface RS232.
KM202 - Control and monitoring unit, with built-in modem
Control and monitoring device to use in radiant heating and/or cooling
systems associated with the GIACOKLIMA field control devices. Internal
modem for system remote control tasks and no 1 serial RS485 for
KD200 Display Unit connection.
KM203 - Control and monitoring unit, for use with module KSMS
Control and monitoring device to use in radiant heating and/or cooling
systems associated with the GIACOKLIMA field control devices. It has
n1 serial interface RS485 for KD200 Display Unit connection. No 1
serial interface RS485 for the connection of KSMS module for text
messages sending and receiving on GSM phone line.

Additional information
For further information visit site www.giacomini.com or contact
technical service:
+39 0322 923372
+39 0322 923255
consulenza.prodotti@giacomini.com
This communication is for information purposes. Giacomini S.p.A. reserves the
right to make at any moment, without prior notice, modifications for technical
or commercial reasons to the items contained hereby. The information of this
technical communication does not exempt the user from strictly following
existing good practice regulations and standards.

Giacomini S.p.A. Via per Alzo, 39 I-28017 San Maurizio dOpaglio (NO) Italy

You might also like