You are on page 1of 24

Understanding Chilled Beam

and VAV Systems


John Murphy, LEED AP BD+C
Applications Engineer
Trane
Ingersoll Rand
La Crosse, Wisconsin

Chilled Beams
Brief overview of chilled beams
Assess marketed advantages
of chilled beam systems versus VAV
Discuss challenges of applying
chilled beam systems
Review some common applications

2010 Trane, a business of Ingersoll-Rand


Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any
resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.

Passive Chilled Beam

ceiling

water pipes
coil

perforated
metal casing

Active Chilled Beam


primary air

nozzles
coils

ceiling
induced air

induced air
+
primary air

2010 Trane, a business of Ingersoll-Rand


Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any
resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.

Active Chilled Beams

Source of images: Halton

active chilled beams

Primary Air System

primary
air handler

OA
RA

EA

PA

RA

PA

RA

active
chilled beam

RA

Primary air must be sufficiently drier than space:


to offset space latent load, and
to keep space DP below chilled beam surface temp

2010 Trane, a business of Ingersoll-Rand


Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any
resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.

window

Induction of Mid-20th Century


Active Chilled Beams
Installed on ceiling rather than
under windows
More coil surface area
Lower air pressure required
induced
room
air

Warmer water temperature


No condensation
More coil surface area
Lower air pressure required

nozzles

Larger ducts
floor
primary air

condensate
drain connection

Lower air pressure required


Less noise

77

Chilled Beams
Brief overview of chilled beams
Assess marketed advantages
of chilled beam systems versus VAV
Discuss challenges of applying
chilled beam systems
Review some common applications

2010 Trane, a business of Ingersoll-Rand


Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any
resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.

active chilled beams

Claimed Advantage #1
An ACB system typically allows for smaller ductwork
and
d smaller
ll air-handling
i h dli units
it than
th a VAV system.
t

Primary airflow < supply airflow due to induction


Shorter floor-to-floor height required?
Less mechanical room floor space?

active chilled beams

Determining Primary Airflow Rate


Primary airflow (PA) is

PA

b
based
d on llargestt of:
f
Minimum outdoor airflow
required (ASHRAE 62.1)
Airflow required to offset
space latent load
(depends on dew point of PA)
Airflow needed to induce
sufficient room air (RA) to
offset the space sensible
cooling load

RA
SA

SA

10

2010 Trane, a business of Ingersoll-Rand


Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any
resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.

active chilled beams

Determining Primary Airflow Rate


Minimum OA per ASHRAE 62.1
(to achieve LEED IEQc2)
ACB
C system
Airflow required to offset space
latent load

Airflow needed to induce


sufficient room air to offset
space sensible
ibl cooling
li lload
d
VAV system
Airflow needed to offset space
sensible cooling load

Example: office space


0.085 cfm/ft2
(0.085 1.3 = 0.11 cfm/ft2)
0.085 cfm/ft2
0.11 cfm/ft2
0.36 cfm/ft2

(DPTPA = 47F)
(DPTPA = 49F)
(DPTPA = 53F)

0.36 cfm/ft2
(55F primary air)
(four, 6-ft long beams)

0.90 cfm/ft2
(55F supply air)

11

active chilled beams

Determining Primary Airflow Rate


Minimum OA per ASHRAE 62.1
(to achieve LEED IEQc2)
ACB
C system
Airflow required to offset space
latent load

Airflow needed to induce


sufficient room air to offset
space sensible
ibl cooling
li lload
d
VAV system
Airflow needed to offset space
sensible cooling load

Example: K-12 classroom


0.47 cfm/ft2
(0.47 1.3 = 0.61 cfm/ft2)
0.47 cfm/ft2
0.61 cfm/ft2
1.20 cfm/ft2

(DPTPA = 44F)
(DPTPA = 47F)
(DPTPA = 51F)

0.47 cfm/ft2
(55F primary air)
(eight, 4-ft long beams)

1.20 cfm/ft2
(55F supply air)

12

2010 Trane, a business of Ingersoll-Rand


Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any
resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.

Minimum Outdoor Airflow


Required by ASHRAE 62.1
typical ACB primary airflow
(0.30 to 0.70 cfm/ft2)
Barracks sleeping area
example (0.47 cfm/ft2)

Classroom (age 9 plus)


Conference/meeting room
Corridor
Courtroom
Hotel bedroom/living room
Laboratory
Lecture classroom
Library
Lobby (hotel, dormitory)

example (0.36 cfm/ft2)

Office space
Reception area
Retail sales floor
0.10

0.20

0.30

0.40

0.50

0.60

0.70

minimum outdoor airflow required,

0.80

0.90

1.0

cfm/ft2

(based on default occupant densities)

13

active chilled beams

Claimed Advantage #2
An ACB system can typically achieve relatively low
sound
d llevels.
l
No fans or compressors in or near occupied spaces
Constant primary airflow = constant sound
Depends on air pressure

14

2010 Trane, a business of Ingersoll-Rand


Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any
resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.

active chilled beams

Claimed Advantage #3
An ACB system uses significantly less energy than a
VAV system,
t
due
d to:
t
1. Significant fan energy savings (because of the reduced
primary airflow), and
2. Higher chiller efficiency (because of the warmer water
temperature delivered to the chilled beams), and
3. Avoiding reheat (because of zone-level cooling coils).

15

Fan Energy Use: ACB vs. VAV

A zone served by ACBs may require 60% to 70%


less primary airflow, at design cooling conditions
but the difference in annual fan energy use will be
much closer because the VAV system benefits from:
1. Reduced zone airflow at part load
2. System load diversity
3. U
3
Unloading
oad g o
of tthe
e supp
supply
y fan
a at pa
partt load
oad

16

2010 Trane, a business of Ingersoll-Rand


Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any
resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.

example

Zone Primary Airflow at Part Load


zone
e primary airflow, cfm
m/ft2

1.0

1.0

conventional
VAV system

0.8

0.8

0.6

0.6

0.4

0.4

30% minimum
i i
airflow
i fl
setting
tti

0.2

cold-air
VAV system

active chilled
beam system

design
heating load

space load

0.2

design
cooling load

17

System Load Diversity


variable-volume fan
0.72 cfm/ft2

OA

multiple-zone VAV system


central VAV fan sized for block airflow

RA

EA

PA

PA

fan airflow = diversity zone primary airflows

RA

RA

RA

0.90 cfm/ft2

0.90 cfm/ft2

0.90 cfm/ft2

constant-volume fan
0.36 cfm/ft2

OA

active chilled beam system


central CV fan sized for sum-of-peaks
sum of peaks airflow

RA

EA

For this example:


system load diversity = 80%
fan airflow = 80% 0.90 cfm/ft2
= 0.72 cfm/ft2

PA

RA

0.36 cfm/ft2

PA

RA

0.36 cfm/ft2

RA

0.36 cfm/ft2

fan airflow = zone primary airflows


For this example:
fan airflow = 0.36 cfm/ft2

18

2010 Trane, a business of Ingersoll-Rand


Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any
resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.

typical VAV system supply fan

Part-Load Performance
fan input power, % of de
esign

100

80

60

40

VAV supply
l fan
f
with VFD

20

20

40

60

80

100

supply fan airflow, % of design


19

supply fan energy use

ACB vs. Conventional VAV


fan in
nput power, bhp/100
00 ft2

1.0

0.8

conventional
VAV

design cooling
conditions

0.6

active
chilled beam

0.4

VAV uses
more fan energy

ACB uses more


fan energy

0.2

68% of VAV supply


fan design airflow

0.2

0.4

0.6

0.8

1.0

supply fan airflow, cfm/ft2


20

2010 Trane, a business of Ingersoll-Rand


Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any
resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.

10

supply fan energy use

ACB vs. Cold-Air VAV


fan in
nput power, bhp/100
00 ft2

1.0

0.8

0.6

cold-air
VAV

active
chilled beam

0.4

design cooling
conditions
VAV uses more
fan energy

ACB uses more


fan energy

0.2

80% of VAV supply


fan design airflow

0.2

0.4

0.6

0.8

1.0

supply fan airflow, cfm/ft2


21

Chiller Energy Use: ACB vs. VAV

Chilled water delivered to the chilled beams must be


warmer to avoid condensation
but the chilled water delivered to the primary
AHUs still must be cold to dehumidify the building.

22

2010 Trane, a business of Ingersoll-Rand


Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any
resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.

11

Dedicated Chilled-Water Plants


chillers

57F

42F

63F

58F

variable-flow
pumps

bypass for
minimum flow
primary
air handlers

chilled
beams

23

Shared Chilled-Water Plant

42F

57F

mixing
valve
primary
air handlers

42F

chilled beams

58F

54F
63F

24

2010 Trane, a business of Ingersoll-Rand


Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any
resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.

12

Chiller Energy Use


ACB system
Warm water delivered to
chilled beams
Still needs cold water
delivered to the primary
AHUs for dehumidification
Typically no DCV
No (or minimal) capacity for
airside economizing
Waterside economizing
(more effective due to
warmer water temp)

VAV system
Cold water delivered to central
VAV air-handling units

Commonly implement DCV


100% capacity for airside
economizing
Can use waterside economizing,
but airside economizing is more
efficient

25

Waterside Economizer
chillers

57F

42F
variable-flow
pumps

bypass for
minimum flow
primary
air handlers

mixing
valve
42F

variable-flow
pump

58F

54F
63F
from
cooling tower

chilled beams

waterside economizer
heat exchanger

26

2010 Trane, a business of Ingersoll-Rand


Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any
resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.

13

Pumping Energy: ACB vs. VAV


ACB system
Higher pumping energy use
Warm water temperatures
(58F to 60F)
Small waterside T
(5F to 6F)
Water pumped to chilled
beams in every space

VAV system
Lower pumping energy use
Cold water temperatures
(40F to 44F)
Large waterside T
(12F to 14F)
Water pumped only to
centralized mechanical
rooms

27

Impact of Reheat Energy


VAV terminal with 40% minimum airflow setting
primary airflow at design conditions = 0.90 cfm/ft2
primary airflow when reheat is activated:
= 40% 0.90 cfm/ft2
= 0.36
0 36 cfm/ft
f /f 2
cooling provided when primary airflow is at minimum:
= 0.36 cfm/ft2 of 55F primary air

PA
0.36 cfm/ft2
55F

Reheat is needed to avoid overcooling the space when


the space sensible cooling load < 40% of design load.

PA
0.36 cfm/ft2
55F

RA

active chilled beam


primary airflow at design conditions = 0.36 cfm/ft2
primary airflow when CHW valve is fully closed
= 0.36 cfm/ft2
cooling provided when CHW valve is fully closed:
= 0.36 cfm/ft2 of 55F primary air

Heat is needed to avoid overcooling the space when


the space sensible cooling load < 40% of design load.
28

2010 Trane, a business of Ingersoll-Rand


Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any
resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.

14

example office space

Cold vs. Neutral Primary Air


Cold (55F) primary-air temperature

PA
0.36 cfm/ft2
55F

RA

four ((4)) ACBs,, each 6-ft long


g x 2-ft wide
primary airflow at design conditions = 0.36 cfm/ft2
total water flow = 6.0 gpm

Neutral (70F) primary-air temperature

PA
0.50
0
50 cfm/ft
f /ft2
70F

RA

six (6) ACBs, each 6-ft long x 2-ft wide


primary
i
airflow
i fl
att design
d i
conditions
diti
= 0.50
0 50 cfm/ft
f /ft2
total water flow = 9.0 gpm

29

Heating Energy: ACB vs. VAV


ACB system
Heat added when CHW valve
closes and primary airflow
begins to overcool the space
Typically no DCV

VAV system
Heat added when damper
closes to minimum and primary
airflow begins to overcool space
Commonly implement DCV
Parallel fan-powered VAV
terminals can draw warm air
from ceiling plenum

30

2010 Trane, a business of Ingersoll-Rand


Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any
resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.

15

office building

Example Energy Analysis


Baseline chilled-water VAV system
ASHRAE 90.1-2007, Appendix G (55F supply air)

Active chilled beam system


Four-pipe active chilled beams
Separate primary AHUs for perimeter and
interior areas (with SAT reset and economizers)
Separate water-cooled chiller plants
(low-flow plant supplying primary AHUs)

High-performance chilled-water VAV system


48F supply
l air
i (d
(ductwork
t
k nott downsized)
d
i d)
Optimized VAV system controls
(ventilation optimization, SAT reset)
Parallel fan-powered VAV terminals
Low-flow, water-cooled chiller plant
31

Example Energy Analysis


Annual Building Energy U
Use, kBtu/yr

12,000,000

10,000,000

Houston

Los Angeles

Philadelphia

St. Louis

Pumps
Fans
Heating

8,000,000

Cooling
Plug Loads
Lighting

6,000,000

4,000,000

2,000,000

32

2010 Trane, a business of Ingersoll-Rand


Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any
resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.

16

Chilled Beams
Brief overview of chilled beams
Assess marketed advantages
of chilled beam systems versus VAV
Discuss challenges of applying
chilled beam systems
Review some common applications

33

ACB challenges

High Installed Cost


Limited cooling capacity = lots of ceiling space
Warmer water temperature requires
more coil surface area
Induction with low static pressures requires more
coil surface area to keep airside pressure drop low

eight
i h (8) active
i
chilled
hill d beams,
b
each 4-ft long x 2-ft wide
four (4) active chilled beams,
each 6-ft long x 2-ft wide

Example: 1000-ft2 office space

Example: 1000-ft2 classroom

34

2010 Trane, a business of Ingersoll-Rand


Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any
resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.

17

System design
variable

Impact on installed cost


of the chilled beams

Impact on performance
of the overall system

2-pipe versus 4-pipe


chilled beams

A 2-pipe beam provides more cooling


capacity than a 4-pipe beam because more
coil surface is available

Using 2-pipe beams requires a separate


heating system, otherwise it can result in
poorer comfort control because either cold
water or warm water is delivered to all zones

Primary airflow rate


(cfm)

Increasing the primary airflow rate through


the nozzles results in more air being
induced from the space
space, which increased
the capacity of the chilled beam coils

Increasing the primary airflow rate increases


primary AHU fan energy use, increases noise
in the space
space, and requires a larger primary
AHU and larger ductwork

Inlet static pressure


of the primary air

Increasing the static pressure at the inlet to


the nozzles results in more air being
induced from the space, which increased
the capacity of the chilled beam coils

Increasing the inlet pressure increases


primary AHU fan energy use, and increases
noise in the space

Dry-bulb temperature
of the primary air

Delivering the primary air at a colder


temperature means that less of the space
sensible cooling load needs to be offset by
the chilled beams

Using a colder primary-air temperature may


cause the space to overcool and low sensible
cooling loads, thus requiring the chilled beam
(or separate heating system) to add heat to
prevent overcooling space

Entering water
temperature

Supplying colder water to the chilled beam


increases the cooling capacity of the beam

Using a colder water temperature requires the


space dew point to be lower to avoid
condensation, which means the primary air
needs to be dehumidified to a lower dew point

Water flow rate


(gpm)

Increasing the water flow rate increases the


cooling capacity of the beam

Increasing the water flow rate increases pump


energy use and requires larger pipes and
pumps
35

ACB challenges

Need to Prevent Condensation


Primary air system used to limit indoor dew point
(typically
(t
i ll below
b l
55F)
Warm chilled-water temperatures delivered to beams
(typically between 58F and 60F)
Start primary air system (chilled beams off) to reduce
indoor humidity following shutdown
Tight
g building
g envelope and g
good building
g pressure
control to minimize infiltration
Use caution if the building has operable windows or
natural ventilation

36

2010 Trane, a business of Ingersoll-Rand


Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any
resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.

18

ACB challenges

Risk of Water Leaks


Lots of water piping, pipe connections, and valves
above
b
every space iin th
the b
building
ildi
Four-pipe systems have twice as much piping and
twice as many connections

Example: 1000-ft2 office space

Example: 1000-ft2 classroom

37

ACB challenges

No Filtration of Local Recirc Air


Chilled beams typically not equipped with a filter
Coils intended to operate dry (no condensation),
lessening concern about preventing wet coil surfaces
from getting dirty
Still concern about removing particles generated
indoors or brought indoors

38

2010 Trane, a business of Ingersoll-Rand


Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any
resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.

19

ACB challenges

Limited Heating Capability


Active chilled beams have limited heating capacity
Chilled beam systems often use a separate heating
system (baseboard convectors, radiant floor heat)

39

Chilled Beams
Brief overview of chilled beams
Assess marketed advantages
of chilled beam systems versus VAV
Discuss challenges of applying
chilled beam systems
Review some common applications

40

2010 Trane, a business of Ingersoll-Rand


Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any
resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.

20

Office Buildings
Why ACB might be a good fit:

Why ACB might not be a good fit:

Low sensible cooling loads Low ventilation rates


resultlt in
i primary
i
AHU
Low latent loads
using mixed air
Not friendly for
re-configuring spaces

41

Schools
Why ACB might be a good fit:

Why ACB might not be a good fit:

High ventilation rates

High latent loads require

resultlt in
i primary
i
AHU
with 100% OA
Low sound levels

llow d
dew point
i t primary
i
air
i
Lack of economizing
capacity

42

2010 Trane, a business of Ingersoll-Rand


Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any
resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.

21

Hospital Patient Rooms


Why ACB might be a good fit:

Why ACB might not be a good fit:

High minimum air change

No local filtration

rates
t (6 ACH)
Low latent loads

( d requirement?)
(code
i
t?)

43

Patient Room: All-Air System


VAV terminal
with reheat coil

230 cfm supply airflow


200 cfm (6 ACH) minimum
67 cfm (2 ACH) outdoor air

return airflow
200 ft2 with 10-ft ceiling height

Design space sensible cooling load


= 5000 Btu/hr
Design supply airflow (55F)
= 230 cfm
Minimum outdoor airflow (ASHRAE 170) = 67 cfm (2 ACH)
Minimum supply airflow (ASHRAE 170) = 200 cfm (6 ACH)
Airflow turndown before activating reheat = 12%

44

2010 Trane, a business of Ingersoll-Rand


Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any
resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.

22

Patient Room: ACB System


active chilled beam
(qty 1, 10 ft long, 4-pipe)

67 cfm (2 ACH) primary airflow


100% outdoor air

268 cfm (>6 ACH) total airflow


primary air
+
induced room air
(3:1 induction ratio)

exhaust airflow
200 ft2 with 10-ft ceiling height

Design space sensible cooling load


Design primary airflow (55F)
Minimum outdoor airflow (ASHRAE 170)
Total room airflow
Capacity turndown before activating heat

= 5000 Btu/hr
= 67 cfm
= 67 cfm (2 ACH)
= 268 cfm (8 ACH, 3:1 induction ratio)
= 70%

45

active chilled beam systems compared to VAV systems

Summary
Potential advantages
Smaller ductwork and
smaller air handlers
Primary airflow < supply airflow,
but likely > outdoor airflow

Low sound levels


Impact on overall system energy?
Primary airflow < supply airflow,
but constant airflow
Warm water for beams,
but cold water primary AHU
Increased pumping energy
No DCV, limited airside
economizing

Challenges
High installed cost
Need to prevent
condensation
Risk of water leaks
No filtration of local
recirculated air
Limited heating capability

46

2010 Trane, a business of Ingersoll-Rand


Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any
resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.

23

Additional Resources

Understanding Chilled Beam Systems, Trane


Engineers Newsletter ADM-APN034-EN (2009)
www.trane.com/engineersnewsletter

Chilled-Water VAV Systems, Trane


application manual SYS-APM008-EN (2009)

47

2010 Trane, a business of Ingersoll-Rand


Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any
resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.

24

You might also like