You are on page 1of 11

Num.

Cables

Tensin (V)

Conductores
por cable

Calibre

4
4
4

600
600
600

1
1
1

6
8
6

PORCENTAJE DE OCUPACIN:

30.09%

Dimetro
tubo (in)
2
2
2

Dimetro
c/cable (in)

Area
c/cable

0.34
0.09
0.27
0.06
0.34
0.09
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
NEC Chapter 9
Number of conductors
1
2
Over 2

Area
cables

Area del
tubo

0.36
0.23
0.36
0.00
0.00
0.00
0.00
0.00
0.00

3.14

All conductor types


53
31
40

Notes to Tables:
(9) A multiconductor cable of two or more conductors shall be treated as a single conductor for calculating
percentage conduit fill area. For cables that have elliptical cross sections, the cross-sectional area calculation
shall be based on using the major diameter of the ellipse as a circle diameter

Num. Cables

Tensin (V)

Conductores
por cable

Calibre

8
4
4

600
600
600

1
1
1

2
8
4

PORCENTAJE DE OCUPACIN:

15.18%

Dimetro
tubo (in)
4
4
4

Dimetro
c/cable (in)

Area
c/cable

0.44
0.15
0.27
0.06
0.38
0.12
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
NEC Chapter 9
Number of conductors
1
2
Over 2

Area
cables

Area del
tubo

1.22
0.23
0.46
0.00
0.00
0.00
0.00
0.00
0.00

12.57

All conductor types


53
31
40

Notes to Tables:
(9) A multiconductor cable of two or more conductors shall be treated as a single conductor for calculating
percentage conduit fill area. For cables that have elliptical cross sections, the cross-sectional area calculation
shall be based on using the major diameter of the ellipse as a circle diameter

Num. Cables

Tensin (V)

Conductores
por cable

Calibre

4
4
4

600
600
600

1
1
1

6
8
4

PORCENTAJE DE OCUPACIN:

33.31%

Dimetro
tubo (in)
2
2
2

Dimetro
c/cable (in)

Area
c/cable

0.34
0.09
0.27
0.06
0.38
0.12
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
NEC Chapter 9
Number of conductors
1
2
Over 2

Area
cables

Area del
tubo

0.36
0.23
0.46
0.00
0.00
0.00
0.00
0.00
0.00

3.14

All conductor types


53
31
40

Notes to Tables:
(9) A multiconductor cable of two or more conductors shall be treated as a single conductor for calculating
percentage conduit fill area. For cables that have elliptical cross sections, the cross-sectional area calculation
shall be based on using the major diameter of the ellipse as a circle diameter

Num. Cables

Tensin (V)

Conductores
por cable

Calibre

4
4
4

600
600
600

1
1
1

4
4
8

PORCENTAJE DE OCUPACIN:

36.52%

Dimetro
tubo (in)
2
4
4

Dimetro
c/cable (in)

Area
c/cable

0.38
0.12
0.38
0.12
0.27
0.06
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
NEC Chapter 9
Number of conductors
1
2
Over 2

Area
cables

Area del
tubo

0.46
0.46
0.23
0.00
0.00
0.00
0.00
0.00
0.00

3.14

All conductor types


53
31
40

Notes to Tables:
(9) A multiconductor cable of two or more conductors shall be treated as a single conductor for calculating
percentage conduit fill area. For cables that have elliptical cross sections, the cross-sectional area calculation
shall be based on using the major diameter of the ellipse as a circle diameter

Num. Cables

Tensin (V)

Conductores
por cable

Calibre

8
4

600
600

1
1

2
1/0

PORCENTAJE DE OCUPACIN:

18.07%

Dimetro
tubo (in)
4
4

Dimetro
c/cable (in)

Area
c/cable

0.44
0.15
0.58
0.26
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
NEC Chapter 9
Number of conductors
1
2
Over 2

Area
cables

Area del
tubo

1.22
1.05
0.00
0.00
0.00
0.00
0.00
0.00
0.00

12.57

All conductor types


53
31
40

Notes to Tables:
(9) A multiconductor cable of two or more conductors shall be treated as a single conductor for calculating
percentage conduit fill area. For cables that have elliptical cross sections, the cross-sectional area calculation
shall be based on using the major diameter of the ellipse as a circle diameter

Num. Cables

Tensin (V)

Conductores
por cable

Calibre

8
16
4

600
600
600

1
1
1

8
6
10

PORCENTAJE DE OCUPACIN:

16.18%

Dimetro
tubo (in)
4
4

Dimetro
c/cable (in)

Area
c/cable

0.27
0.06
0.34
0.09
0.21
0.04
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
NEC Chapter 9
Number of conductors
1
2
Over 2

Area
cables

Area del
tubo

0.45
1.44
0.14
0.00
0.00
0.00
0.00
0.00
0.00

12.57

All conductor types


53
31
40

Notes to Tables:
(9) A multiconductor cable of two or more conductors shall be treated as a single conductor for calculating
percentage conduit fill area. For cables that have elliptical cross sections, the cross-sectional area calculation
shall be based on using the major diameter of the ellipse as a circle diameter

600 V, TRIPOLAR, EPR


Calibre Diam ext (mm) Diam ext (in)
14
10.2
0.40
12
12.7
0.50
10
14.8
0.58
8
18.2
0.71
6
20.1
0.79
4
23.8
0.94
2
25.2
0.99
1/0
30.7
1.21
2/0
33.1
1.30
4/0
38.8
1.53
250
42.1
1.66
350
49.0
1.93
500
55.8
2.20
750
NO VALIDO
NO VALIDO
1000
NO VALIDO
NO VALIDO

600 V, MONOPOLAR, EPR


Calibre Diam ext (mm) Diam ext (in)
14
4.4
0.17
12
4.8
0.19
10
5.4
0.21
8
6.8
0.27
6
8.6
0.34
4
9.7
0.38
2
11.2
0.44
1/0
14.7
0.58
2/0
15.8
0.62
4/0
18.5
0.73
250
21.3
0.84
350
23.9
0.94
500
27.2
1.05
750
32.5
1.28
3/0
17.1
0.67

600 V, TETRAPOLAR, E
Calibre
14
12
10
8
6
4
2
1/0
2/0
4/0
250
350
500
750
1000

600 V, TETRAPOLAR, EPR


Diam ext (mm) Diam ext (in)
12.6
0.50
14.7
0.58
16.2
0.64
19.8
0.78
23.2
0.91
26.2
1.03
29.2
1.15
36.5
1.44
39.2
1.54
47.2
1.86
53.9
2.12
60.5
2.38
68.6
2.70
NO VALIDO
NO VALIDO
NO VALIDO
NO VALIDO

600 V, CONTROL, 7 COND, EPR


Calibre Diam ext (mm) Diam ext (in)
14
14.0
0.55
12
17.4
0.69
10
17.1
0.67
8
NO VALIDO
NO VALIDO
6
NO VALIDO
NO VALIDO
4
NO VALIDO
NO VALIDO
2
NO VALIDO
NO VALIDO
1/0
NO VALIDO
NO VALIDO
2/0
NO VALIDO
NO VALIDO
4/0
NO VALIDO
NO VALIDO
250
NO VALIDO
NO VALIDO
350
NO VALIDO
NO VALIDO
500
NO VALIDO
NO VALIDO
750
NO VALIDO
NO VALIDO
1000
NO VALIDO
NO VALIDO

600 V, CONTROL, 12 COND, EPR


Calibre Diam ext (mm)
14
18.1
12
19.8
10
23.4
8
NO VALIDO
6
NO VALIDO
4
NO VALIDO
2
NO VALIDO
1/0
NO VALIDO
2/0
NO VALIDO
4/0
NO VALIDO
250
NO VALIDO
350
NO VALIDO
500
NO VALIDO
750
NO VALIDO
1000
NO VALIDO

TROL, 12 COND, EPR


Diam ext (in)
0.71
1.18
0.92
NO VALIDO
NO VALIDO
NO VALIDO
NO VALIDO
NO VALIDO
NO VALIDO
NO VALIDO
NO VALIDO
NO VALIDO
NO VALIDO
NO VALIDO
NO VALIDO

5 KV, MONOPOLAR, EPR, 133%


Calibre Diam ext (mm) Diam ext (in)
14
NO VALIDO
NO VALIDO
12
NO VALIDO
NO VALIDO
10
NO VALIDO
NO VALIDO
8
13.6
0.54
6
15.3
0.60
4
16.5
0.65
2
18
0.71
1/0
19.9
0.78
2/0
24.4
0.96
4/0
26.9
1.06
250
26.3
1.04
350
28.9
1.14
500
34.4
1.35
750
39.9
1.57
1000
41
1.61

5 KV, TRIPOLAR, EPR, 133%


Calibre Diam ext (mm) Diam ext (in)
14
NO VALIDO
NO VALIDO
12
NO VALIDO
NO VALIDO
10
NO VALIDO
NO VALIDO
8
27.1
1.07
6
29
1.14
4
31.6
1.24
2
34.9
1.37
1/0
38.9
1.53
2/0
41.4
1.63
4/0
48.6
1.91
250
51.8
2.04
350
NO VALIDO
NO VALIDO
500
NO VALIDO
NO VALIDO
750
NO VALIDO
NO VALIDO
1000
NO VALIDO
NO VALIDO

15 KV, MONOPOLAR, EPR, 133%


Calibre Diam ext (mm) Diam ext (in)
14
NO VALIDO
NO VALIDO
12
NO VALIDO
NO VALIDO
10
NO VALIDO
NO VALIDO
8
NO VALIDO
NO VALIDO
6
NO VALIDO
NO VALIDO
4
NO VALIDO
NO VALIDO
2
NO VALIDO
NO VALIDO
1/0
27.5
1.08
2/0
29.7
1.17
4/0
31.5
1.24
250
33.7
1.33
350
36.7
1.44
500
39.7
1.56
750
45.4
1.79
1000
49.8
1.96