1762-OF4 Analog Output Data Format.


Question
1762-OF4 Analog Output Data Format
Answer

Category
General
Date Created
01/31/2006
Last Updated
01/15/2007
Access Level
Everyone
Prev. TN#
G144839772

Raw/Proportional
Data Table Value Voltage/Current Value
32767
31206
0

10.5 Volts
10 Volts
0 Volts

32767
31206
6241
0

21 mA
20 mA
4 mA
0 mA

Print Answer
Email Answer

Scaled for PID


Data Table Value Voltage/Current Value

16383
15602
0

10.5 Volts
10 Volts
0 Volts

16383
15602
3120
0

21 mA
20 mA
4 mA
0 mA

Summary: 1762-OF4 data ranges.


Catalog Number: 1762OF4
DocFullNum: G144839772
Revision:
Fixed in Revision:
Package:
Module:
DISCLAIMER
This knowledge base web site is intended to provide general technical information on a
particular subject or subjects and is not an exhaustive treatment of such subjects.
Accordingly, the information in this web site is not intended to constitute application, design,
software or other professional engineering advice or services. Before making any decision or
taking any action, which might affect your equipment, you should consult a qualified
professional advisor.
ROCKWELL AUTOMATION DOES NOT WARRANT THE COMPLETENESS, TIMELINESS
OR ACCURACY OF ANY OF THE DATA CONTAINED IN THIS WEB SITE AND MAY MAKE

1/23/2008 1:59 PM

Answer

2 of 2

http://rockwellautomation.custhelp.com/cgi-bin/rockwellautomation.cfg/...

CHANGES THERETO AT ANY TIME IN ITS SOLE DISCRETION WITHOUT NOTICE.


FURTHER, ALL INFORMATION CONVEYED HEREBY IS PROVIDED TO USERS "AS IS."
IN NO EVENT SHALL ROCKWELL BE LIABLE FOR ANY DAMAGES OF ANY KIND
INCLUDING DIRECT, INDIRECT, INCIDENTAL, CONSEQUENTIAL, LOSS PROFIT OR
DAMAGE, EVEN IF ROCKWELL AUTOMATION HAVE BEEN ADVISED ON THE
POSSIBILITY OF SUCH DAMAGES.
ROCKWELL AUTOMATION DISCLAIMS ALL WARRANTIES WHETHER EXPRESSED OR
IMPLIED IN RESPECT OF THE INFORMATION (INCLUDING SOFTWARE) PROVIDED
HEREBY, INCLUDING THE IMPLIED WARRANTIES OF FITNESS FOR A PARTICULAR
PURPOSE, MERCHANTABILITY, AND NON-INFRINGEMENT. Note that certain jurisdictions
do not countenance the exclusion of implied warranties; thus, this disclaimer may not apply
to you.

Copyright 2006-2008 Rockwell Automation. All rights reserved.

Notify Me by Email if this Answer is Updated

How well did this answer your question?


100%

75%

50%

25%

0%

Submit Rating

Users who viewed this answer have also viewed

1762-IF4 Analog Input Data Format.


Scale of PID out to 1762-OF4 doesn't appear to be correct for 4-20mA
Manual scaling of analog signals.
8 bit analog output.
1762-IF2OF2 ** Input/Output data formats, conversion times. Analog Combo
Module Extended Information.

Close Window

1/23/2008 1:59 PM

You might also like