You are on page 1of 62

SMART

power design

ENATEL | 2010 PRODUCT CATALOGUE


We are specialists in the design and manufacture of a range of standby power solutions for the telecom, networking, wireless and industrial markets. Enatels
smart power design offers intelligent solutions at an empowering price. In a market where only the fast survive, we respond quickly and cost-effectively so our
customers can do the same.

Offering a range of solutions from small standalone systems for applications like access nodes to medium systems for radio base stations for mobile networks and
larger systems for central office power applications. Our knowledge and experience of the global marketplace, along with our talented team, enable us to create
power supply solutions that meet each customers unique specifications no matter what volume they require.

We not only create our own suite of products, we also offer a comprehensive contract manufacturing service. Our highly flexible environment allows us to specialize
in small to medium volume as well as highly repetitive production.

AC-DC POWER SYSTEMS........................................................................... 4

FLAT MOUNT RECTIFIERS........................................................................ 34

1U MICRO COMPACT SYSTEM 0.8 - 2.4kW 48V DC........................................ 5

RF SERIES FLAT MOUNT RECTIFIERS............................................................ 35

1U ULTRA COMPACT SYSTEM 1.0 - 4.0kW 48V DC........................................ 6


1U ULTRA COMPACT SYSTEM 1.0 - 4.0kW 48V DC........................................ 7

WALL MOUNT RECTIFIERS....................................................................... 36


RW SERIES WALL MOUNT RECTIFIERS......................................................... 37

2U ULTRA COMPACT SYSTEM 1.0 - 6.0kW 48V DC........................................ 8


2U ULTRA COMPACT SYSTEM 1.0 - 6.0kW 48V DC........................................ 9

DC-AC POWER SYSTEMS......................................................................... 38

2U ULTRA COMPACT SYSTEM 1.0 - 8.0kW 48V DC...................................... 10


3U COMPACT SYSTEM 1.0 - 6.0kW 48V DC................................................... 11
3U COMPACT SYSTEM 1.0 - 6.0kW 48V DC................................................... 12
3U COMPACT SYSTEM 1.0 - 8.0kW 48V DC................................................... 13
5U MAXI COMPACT SYSTEM 1.0 - 14.0kW 48V DC....................................... 14

DC-AC INVERTERS...................................................................................... 39
IM SERIES MODULAR INVERTERS.................................................................. 40
SBM SERIES STATIC BYPASS MODULE........................................................ 41

DC-DC CONVERTERS. ............................................................................... 42

5U MAXI COMPACT SYSTEM 1.0 - 14.0kW 48V DC....................................... 15

CM SERIES 1.7kW MODULAR DC-DC CONVERTERS.................................... 43

5U MAXI COMPACT SYSTEM 1.0 - 14.0kW 48V DC....................................... 16

CM SERIES 500W to 1.0kW MODULAR DC-DC CONVERTERS..................... 44

6U MAXI COMPACT SYSTEM 1.0 - 22.0kW 48V DC....................................... 17


15U MEDIUM SYSTEM 3.0 - 27.0kW 48V DC.................................................. 18
2.0M MEDIUM SYSTEM 3.0 - 54.0kW 48V DC................................................. 19
2.2M INTEGRATED BASE TRANSCEIVER
STATION SYSTEM 1.0 - 16.0kW 48V DC......................................................... 20

MONITORING................................................................................................ 45
SM36 SUPERVISORY MODULE....................................................................... 46
SM35 SUPERVISORY MODULE....................................................................... 47
SM32 SUPERVISORY MODULE....................................................................... 48
SM31 SUPERVISORY MODULE....................................................................... 49

1.6M MEDIUM SYSTEM 3.0 - 27.0kW 48V DC................................................. 21

SM11 SUPERVISORY MODULE....................................................................... 50

2.0M LARGE DATA CENTER SOLUTIONS....................................................... 22

FAN CONTROLLER BOARD............................................................................. 50

WALL MOUNT SYSTEM 4.0kW 48V DC / 2.1kW 24V DC................................ 23

BATTERY CONDITION MONITOR.................................................................... 51


AC MAINS MONITOR........................................................................................ 51

MODULAR RECTIFIERS.............................................................................. 24
RM3048 3.0kW 48V DC MODULAR RECTIFIER............................................... 25

FTTX POWER SOLUTIONS........................................................................ 52


nSURE 1U MICRO COMPACT SYSTEM 0.8 - 2.4KW 48V DC......................... 53

RM3048/24 3.0kW 48V DC / 1.7kW 24V DC MODULAR RECTIFIER............... 26

nSURE NS300-12.............................................................................................. 54

RM3060/48 3.0kW 60/48V DC MODULAR RECTIFIER.................................... 27

nSURE NS30-12................................................................................................ 55

RM2324 2.3kW 24V DC MODULAR RECTIFIER............................................... 28


RM2048XP 2.0KW 48V DC MODULAR RECTIFIER.......................................... 29
RM2048/24 2.0kW 48V DC / 1.0kW 24V DC MODULAR RECTIFIER............... 30
RM1860/48 1.8kW 60/48V DC MODULAR RECTIFIER.................................... 31

INDUSTRIAL SOLUTIONS.......................................................................... 56
2U ULTRA COMPACT SYSTEM 3.0 - 6.0kW 110V DC.................................... 57
WALL MOUNT BATTERY CHARGER 3.0kW 110V DC..................................... 58
RM30110 3.0KW 110V DC MODULAR RECTIFIER.......................................... 59

RM1048 1.0kW 48V DC MODULAR RECTIFIER............................................... 32

SM34 SUPERVISORY MODULE....................................................................... 60

RM848 800W 48V DC MODULAR RECTIFIER.................................................. 33

SM33 SUPERVISORY MODULE....................................................................... 61


ENATEL | 2010 PRODUCT CATALOGUE | 

AC-DC POWER SYSTEMS


- World leading power density.

Our DC power systems are designed to meet the requirements of

- Fully featured telecom

telecommunications applications requiring high reliability and optimum

performance with easy expansion by way of hot pluggable modular rectifiers.

grade rectifiers.

- Network monitoring available.


- Modular 19 design for ease

of installation.

- Includes AC surge protection.


- More room for revenue

creating equipment.

- Upgrade existing systems


to higher power.

They are the ideal solution for powering telecommunications and data networks
requiring 24V, 48V or 60V DC. We offer a range of solutions for applications from
small standalone systems for applications like access nodes to medium sized
systems for radio base stations for mobile networks to larger systems for central
office power applications.

- High reliability means less cost

Systems are configured using Enatels state of the art high frequency switch

mode rectifier modules, intelligent network capable controllers, AC & DC

of maintenance.

- Full remote monitoring available

distribution modules, and cabinets, and can be customized and configured to

meet individual customer requirements.

means less site visits and less cost.

- Cost competitive.
- Suitable for more harsh

environments.

 | ENATEL | 2010 PRODUCT CATALOGUE

For details on a Enatel power system that meets your requirements contact us.

1U MICRO COMPACT SYSTEM 0.8 - 2.4kW 48V DC


AC Input:

Single phase.

AC Current:

170V AC, 15.0A max. 230V AC, 11.1A nominal.

(refer to RM8xx, series brochures for full details)

Frequency Range:

45-66Hz

Power Factor:

>0.99 (full load)

Termination:

Single phase, 1.5m flying lead.

48
2.4

nominal output voltage.

DC Output
Nominal Voltage:

-48V

Rated System Output Power:

2400W max. (50A @ -48V; 44.4A @ -54.0V)

Polarity:

Positive earth. (negative earth available to special order).

kW

maximum output power.

DC Distribution:

Load:

2x 10A, 2x 20A load circuit breakers.

Battery:

2x 30A battery circuit breakers.

Breaker Fail Detection:

Supervisory Module

RM848

RM848

RM848

SM36

Electronic fail detection on both load and battery breakers.

DC Terminals (Front Connected):


Load:

6mm push-in spring cage.

Battery:

55A power-pole plug-in connectors.

Low Voltage Disconnect:

50A battery LVD (magnetically latching) fitted as standard.

Mechanical
Dimensions, W,H,D:

482.6mm (standard 19 module), also fits ETSI 515mm mounting cabinet,

44.45mm (1U, 1.75), 285mm (11.6)

Weight:

5kg (excluding rectifier modules)

Shipping Dimensions, W,H,D: 540mm, 95mm, 400mm


Weight:

6kg (excluding rectifier modules)

Monitoring & Control:

Various monitoring options are available via the Enatel SM35/36 series

of control & supervisory modules. Standard features include full

temperature compensation, automated and manual battery testing/

equalisation, 6x general purpose inputs and 6x voltage-free relay alarm

outputs. For further details, refer to the SM35/36 series of brochures.

Accessories
ACA-BC08P2:

2m, 8mm battery cable kit. (other lengths available to special order)

Part Numbers:

Actual part numbers will vary with configuration.

PSX1606211F-000:

Micro compact system, 2x 800W 48V rectifiers, 6x load

2x battery MCBs, front termination, SM35 supervisory module.

PSX1606221F-000:

Micro compact system, 2x 800W 48V rectifiers, 6x load

2x battery MCBs, front termination, SM36 supervisory module.

PSX2404211F-000:

Micro compact system, 3x 800W 48V rectifiers, 4x load

2x battery MCBs, front termination, SM35 supervisory module.

PSX2404221F-000:

Micro compact system, 3 x 800W 48V rectifiers, 4x load

2x battery MCBs, front termination, SM36 supervisory module.


ENATEL | 2010 PRODUCT CATALOGUE | 

1U ULTRA COMPACT SYSTEM 1.0 - 4.0kW 48V DC

48
4.0
V

nominal output voltage.

maximum output power.

SM32

Single phase. (refer to RM series brochures for full details)

Frequency Range:

45-66Hz

Power Factor:

>0.99 (full load)

Termination:

Single phase, 10mm L, N, E tunnel terminals.

DC Output

kW

Supervisory Module

AC Input:

Nominal Voltage:

-48V (+24V available to special order)

Rated System Output Power:

4000W @ -48V (2000W @ -48V. Low power option.)

Polarity:

Positive earth. (negative earth available to special order)

DC Distribution:

Load

Battery

ULTRA

compact

Load:

1x 63A load circuit breaker.

(1x 50A load circuit breaker. Low power option.)

1x 63A battery circuit breaker.

Battery:

(1x 50A battery circuit breaker. Low power option.)

Breaker Fail Detection:

Electronic fail detection on both load and battery breakers.

DC Terminals:

Tunnel terminals, 10mm.

Low Voltage Disconnect:

80A battery LVD fitted as standard.

(50A battery LVD fitted as standard. Low power option.)

Mechanical
Dimensions, W, H, D:

482.6mm (standard 19 module), 44.45mm (1U, 1), 350mm (13)

Weight:

5kg (excluding rectifier modules)

Shipping Dimensions, W, H, D: 540mm, 95mm, 400mm

 | ENATEL | 2010 PRODUCT CATALOGUE

Weight:

6kg (excluding rectifier modules)

Monitoring & Control:

Various monitoring options are available via the Enatel SM30 series of

control & supervisory modules. Standard features include full temperature

compensation, automated and manual battery testing/equalisation and

three voltage-free relay alarm outputs. Options include extension I/O PCBs

that give an extra 6x digital inputs, 6x analogue inputs and 8x voltage-free

relay outputs. For further details, refer to the SM30 series of brochures.

Part Numbers:

Actual part numbers will vary with configuration.

PSC04020110-000:

1U Ultra Compact System including standard SM31 supervisory module.

PSC04020111-000:

1U Ultra Compact System including standard

SM31 supervisory module and I/O expansion card.

PSC04020120-000:

1U Ultra Compact System including standard SM32 supervisory module.

PSC04020121-000:

1U Ultra Compact System including standard

SM32 supervisory module and I/O expansion card.

PSC02020110-000:

Low Power 1U Ultra Compact System including standard

SM31 supervisory module.

PSC02020111-000:

Low Power 1U Ultra Compact System including standard

SM31 supervisory module and I/O expansion card.

PSC02020120-000:

Low Power 1U Ultra Compact System including standard

SM32 supervisory module.

PSC02020121-000:

Low Power 1U Ultra Compact System including standard

SM32 supervisory module and I/O expansion card.

1U ULTRA COMPACT SYSTEM 1.0 - 4.0kW 48V DC


AC Input:

Single phase. (refer to RM series brochures for full details)

Frequency Range:

45-66Hz

Power Factor:

>0.99 (full load)

Termination:

Single phase, 6mm L, N, E tunnel terminals.

48
4.0

nominal output voltage.

DC Output
Nominal Voltage:

-48V, -60V (+24V available to special order)

Rated System Output Power:

4000W @ -48V (2000W @ -48V. Low power option.)

Polarity:

Positive earth. (negative earth available to special order)

DC Distribution:

Load:

Battery:

kW

3x 20A load circuit breakers.

maximum output power.

(3x 10A load circuit breakers. Low power option.)


2x 30A battery circuit breakers.

(2x 20A battery circuit breakers. Low power option.)

Breaker Fail Detection:

Electronic fail detection on both load and battery breakers.

Supervisory Module

SM32

ULTRA

compact

DC Terminals:

Live:

Common:

Tunnel terminals, 6mm


Tunnel terminals, 6mm

Low Voltage Disconnect:

80A battery LVD fitted as standard.

(50A battery LVD fitted as standard. Low power option.)

Mechanical
Dimensions, W, H, D:

482.6mm (standard 19 module), 44.45mm (1U, 1), 350mm (13)

Weight:

5kg (excluding rectifier modules)

Shipping Dimensions, W, H, D: 540mm, 95mm, 400mm


Weight:

6kg (excluding rectifier modules)

Monitoring & Control:

Various monitoring options are available via the Enatel SM30 series of

control & supervisory modules. Standard features include full temperature

compensation, automated and manual battery testing/equalisation and

three voltage-free relay alarm outputs. Options include extension I/O PCBs

that give an extra 6x digital inputs, 6x analogue inputs and 8x voltage-free

relay outputs. For further details, refer to the SM30 series of brochures.

Part Numbers:

Actual part numbers will vary with congifuration.

PSC04020110-100:

1U Ultra Compact System including standard SM31 supervisory module.

PSC04020111-100:

1U Ultra Compact System including standard SM31

supervisory module and I/O expansion card.

PSC04020120-100:

1U Ultra Compact System including standard SM32 supervisory module.

PSC04020121-100:

1U Ultra Compact System including standard SM32

supervisory module and I/O expansion card.

PSC02020110-100:

Low Power 1U Ultra Compact System including standard

SM31 supervisory module.

PSC02020111-100:

Low Power 1U Ultra Compact System including standard

SM31 supervisory module and I/O expansion card.

PSC02020120-100:

Low Power 1U Ultra Compact System including standard

SM32 supervisory module.

PSC02020121-100:

Low Power 1U Ultra Compact System including standard

SM32 supervisory module and I/O expansion card.


ENATEL | 2010 PRODUCT CATALOGUE | 

2U ULTRA COMPACT SYSTEM 1.0 - 6.0kW 48V DC

48
6.0
V

nominal output voltage.

maximum output power.

1
Load
2

3
Load
4

AC Input:

Three phase or single phase. (refer to RM series brochures for full details)

Frequency Range:

45-66Hz

Power Factor:

>0.99 (full load)

Termination:

Three phase, 6mm L1, L2, L3, N, E tunnel terminals.

(Single phase by linking L1, L2, L3 terminals)

DC Output

kW

5
Load
6

Supervisory Module

SM32

Nominal Voltage:

-48V, -60V (+24V available to special order)

Rated System Output Power:

6000W @ -48V (3000W @ -48V. Low power option)

Polarity:

Positive earth. (negative earth available to special order)

DC Distribution:

1
Battery
2

ULTRA

compact

Load:

2x 10A, 2x 20A, 2x 32A load circuit breakers.

(2x 6A, 2x 10A, 2x 20A load circuit breakers. Low power option.)

2x 63A battery circuit breakers.

Battery:

(2x 63A battery circuit breakers. Low power option.)

Breaker Fail Detection:

Electronic fail detection on both load and battery breakers.

DC Terminals:

Load:

Battery:

Tunnel terminals, 16mm (rear connected)


Tunnel terminals, 35mm (rear connected)

Low Voltage Disconnect:

125A battery LVD fitted as standard. (magnetically latching contactor)

(80A battery LVD fitted as standard. Low power option)

Mechanical
Dimensions, W, H, D:

482.6mm (standard 19 module), 89mm (2U, 3),

350mm (13) (390mm with cable strain relief)

Weight:

9kg (excluding rectifier modules)

Shipping Dimensions, W, H, D: 540mm, 150mm, 435mm

 | ENATEL | 2010 PRODUCT CATALOGUE

Weight:

10.5kg (excluding rectifier modules)

Monitoring & Control:

Various monitoring options are available via the Enatel SM30 series of

control & supervisory modules. Standard features include full temperature

compensation, automated and manual battery testing/equalisation and

three voltage-free relay alarm outputs. Options include extension I/O PCBs

that give an extra 6x digital inputs, 6x analogue inputs and 8x voltage-free

relay outputs. For further details, refer to the SM30 series of brochures.

Part Numbers:

Actual part numbers will vary with congifuration.

PSC06030210-000:

2U Ultra Compact System including standard SM31 supervisory module.

PSC06030211-000:

2U Ultra Compact System including standard SM31

supervisory module and I/O expansion card.

PSC06030220-000:

2U Ultra Compact System including standard SM32 supervisory module.

PSC06030221-000:

2U Ultra Compact System including standard SM32

supervisory module and I/O expansion card.

PSC03030210-000:

Low Power 2U Ultra Compact System including standard

SM31 supervisory module.

PSC03030211-000:

Low Power 2U Ultra Compact System including standard

SM31 supervisory module and I/O expansion card.

PSC03030220-000:

Low Power 2U Ultra Compact System including standard

SM32 supervisory module.

PSC03030221-000:

Low Power 2U Ultra Compact System including standard

SM32 supervisory module and I/O expansion card.

2U ULTRA COMPACT SYSTEM 1.0 - 6.0kW 48V DC


AC Input:

Three phase or single phase. (refer to RM series brochures for full details)

Frequency Range:

45-66Hz

Power Factor:

>0.99 (full load)

Termination:

Three phase, 6mm L1, L2, L3, N, E tunnel terminals.

(Single phase by linking L1, L2, L3 terminals)

48
6.0

nominal output voltage.

DC Output
Nominal Voltage:

-48V, -60V (+24V available to special order)

Rated System Output Power:

6000W @ -48V (3000W @ -48V. Low power option.)

Polarity:

Positive earth. (negative earth available to special order)

DC Distribution:

Load:

(8x 6A, 4x 10A, 4x 20A load circuit breakers. Low power option.)

2x 100A battery circuit breakers.

Battery:

(2x 50A battery circuit breakers. Low power option.)

Breaker Fail Detection:

Electronic fail detection on both load and battery. breakers

Load:

ULTRA

compact

10A, 6mm tunnel terminals. 20A & 30A, 10mm tunnel terminals.
(6A & 10A, 6mm tunnel terminals.

20A, 10mm tunnel terminals. Low power option.)

100A, 35mm tunnel terminals.

(50A, 16mm tunnel terminals. Low power option.)

Low Voltage Disconnect:

125A battery LVD fitted as standard.

(80A battery LVD fitted as standard. Low power option.)

1
Battery
2
SM32


Battery:

maximum output power.

Supervisory Module

DC Terminals (rear connected):


kW

8x 10A, 4x 20A, 4x 30A load circuit breakers.

Mechanical
Dimensions, W, H, D:

482.6mm (standard 19 module), 89mm (2U, 3),

350mm (13) (390mm with cable strain relief)

Weight:

9kg (excluding rectifier modules)

Shipping Dimensions, W, H, D: 540mm, 150mm, 435mm


Weight:

10.5kg (excluding rectifier modules)

Monitoring & Control:

Various monitoring options are available via the Enatel SM30 series of

control & supervisory modules. Standard features include full temperature

compensation, automated and manual battery testing/equalisation and

three voltage-free relay alarm outputs. Options include extension I/O PCBs

that give an extra 6x digital inputs, 6x analogue inputs and 8x voltage-free

relay outputs. For further details, refer to the SM30 series of brochures.

Part Numbers:

Actual part numbers will vary with congifuration.

PSC06030210-100:

2U Ultra Compact System including standard SM31 supervisory module.

PSC06030211-100:

2U Ultra Compact System including standard SM31

supervisory module and I/O expansion card.

PSC06030220-100:

2U Ultra Compact System including standard SM32 supervisory module.

PSC06030221-100:

2U Ultra Compact System including standard SM32

supervisory module and I/O expansion card.

PSC03030210-100:

Low Power 2U Ultra Compact System including standard

SM31 supervisory module.

PSC03030211-100:

Low Power 2U Ultra Compact System including standard

SM31 supervisory module and I/O expansion card.

PSC03030220-100:

Low Power 2U Ultra Compact System including standard

SM32 supervisory module.

PSC03030221-100:

Low Power 2U Ultra Compact System including standard

SM32 supervisory module and I/O expansion card.


ENATEL | 2010 PRODUCT CATALOGUE | 

2U ULTRA COMPACT SYSTEM 1.0 - 8.0kW 48V DC

48
8.0
V

nominal output voltage.

maximum output power.

AC Input:

Three phase or single phase. (refer to RM series brochures for full details)

Frequency Range:

45-66Hz

Power Factor:

>0.99 (full load)

Termination:

Three phase, 10mm L1, L2, L3, N tunnel terminals,

16mm E tunnel terminal. (Single phase by linking L1, L2, L3 terminals)

DC Output

kW

Nominal Voltage:

-48V, -60V (+24V available to special order)

Rated System Output Power:

8000W @ -48V

Polarity:

Positive earth. (negative earth available to special order)

DC Distribution:
Supervisory Module

SM32

1
Load
2

3
Load
4

1
Battery
2

ULTRA

compact

Load:

2x 20A, 2x 63A load circuit breakers.

Battery:

2x 100A battery circuit breakers.

Breaker Fail Detection:

Electronic fail detection for load breakers.

Auxiliaries for battery MCB fail detection.

DC Terminals:

Load:

Tunnel terminals, 16mm (rear connected)

Battery:

Tunnel terminals, 35mm (rear connected)

Low Voltage Disconnect:

150A battery LVD fitted as standard. (magnetically latching contactor)

Mechanical
Dimensions, W, H, D:

482.6mm (standard 19 module), 89mm (2U, 3),

350mm (13) (390mm with cable strain relief)

Weight:

9kg (excluding rectifier modules)

Shipping Dimensions, W, H, D: 483mm, 88.9mm, 350mm

10 | ENATEL | 2010 PRODUCT CATALOGUE

Weight:

10.5kg (excluding rectifier modules)

Monitoring & Control:

Various monitoring options are available via the Enatel SM30 series of

control & supervisory modules. Standard features include full temperature

compensation, automated and manual battery testing/equalisation and

three voltage-free relay alarm outputs. Options include extension I/O PCBs

that give an extra 6x digital inputs, 6x analogue inputs and 8x voltage-free

relay outputs. For further details, refer to the SM30 series of brochures.

Part Numbers:

Actual part numbers will vary with congifuration.

PSC08040210-000:

2U Ultra Compact System including standard SM31 supervisory module.

PSC08040211-000:

2U Ultra Compact System including standard SM31

supervisory module and I/O expansion card.

PSC08040220-000:

2U Ultra Compact System including standard SM32 supervisory module.

PSC08040221-000:

2U Ultra Compact System including standard SM32

supervisory module and I/O expansion card.

3U COMPACT SYSTEM 1.0 - 6.0kW 48V DC


AC Input:

Three phase or single phase. (refer to RM series brochures for full details)

Frequency Range:

45-66Hz

Power Factor:

>0.99 (full load)

Termination:

Three phase L1, L2, L3, N, E 10mm terminal blocks.

(Single phase by linking line terminals)

48
6.0

nominal output voltage.

DC Output
Nominal Voltage:

-48V, -60V (+24V available to special order)

Rated System Output Power:

6000W @ -48V

Polarity:

Positive earth. (negative earth available to special order)

kW

maximum output power.

DC Distribution:
3U Compact System

Load:

4x 10A, 4x 20A, 4x 32A load circuit breakers.

2
3

Battery:

2x 100A battery circuit breakers.

Load

6
7
8

Load

10

11

Battery

12

Supervisory Module

SM32

Breaker Fail Detection:

Electronic fail detection on both load and battery breakers.

DC Terminals (rear connected):


Load:

16mm tunnel terminals.

Battery:

35mm tunnel terminals.

Low Voltage Disconnect:

125A battery LVD fitted as standard.

Mechanical
Dimensions, W, H, D:

482.6mm (standard 19 module), 133.3mm (3U, 5),

350mm (13) (390mm with cable strain relief)

Weight:

11kg (excluding rectifier modules)

Shipping Dimensions, W, H, D: 540mm, 200mm, 435mm


Weight:

14kg (excluding rectifier modules)

Monitoring & Control:

Various monitoring options are available via the Enatel SM30 series of

control & supervisory modules. Standard features include full temperature

compensation, automated and manual battery testing/equalisation and

three voltage-free relay alarm outputs. Options include extension I/O PCBs

that give an extra 6x digital inputs, 6x analogue inputs and 8x voltage-free

relay outputs. For further details, refer to the SM30 series of brochures.

Part Numbers:

Actual part numbers will vary with congifuration.

PSC06030310-000:

3U Compact System including standard SM31 supervisory module.

PSC06030311-000:

3U Compact System including standard SM31

supervisory module and I/O expansion card.

PSC06030320-000:

3U Compact System including standard SM32 supervisory module.

PSC06030321-000:

3U Compact System including standard SM32

supervisory module and I/O expansion card.


ENATEL | 2010 PRODUCT CATALOGUE | 11

3U COMPACT SYSTEM 1.0 - 6.0kW 48V DC

48
6.0
V

nominal output voltage.

maximum output power.

AC Input:

Three phase or single phase. (refer to RM series brochures for full details)

Frequency Range:

45-66Hz

Power Factor:

>0.99 (full load)

Termination:

Three phase L1, L2, L3, N, E 6mm2 terminal blocks.

(Single phase by linking line terminals)

Proctection:

20A circuit breaker provided per rectifier.

DC Output

kW

Nominal Voltage:

-48V, -60V (+24V available to special order)

Rated System Output Power:

6000W @ -48V

Polarity:

Positive earth. (negative earth available to special order)

DC Distribution:
Rectifiers

AC
Input

10

11

Load

Load

12
13

14

15

3U Compact System

Load

Battery

Load:

5x 10A, 4x 20A, 4x 32A load circuit breakers.

Battery:

2x 100A battery circuit breakers.

Supervisory Module

SM32

Breaker Fail Detection:

Electronic fail detection on both load and battery breakers.

DC Terminals (rear connected):


Load:

10A, 6mm tunnel terminals.

32A, 10mm tunnel terminals.

50A, 16mm tunnel terminals.

35mm tunnel terminals.

Battery:

Low Voltage Disconnect:

125A battery LVD fitted as standard.

Mechanical
Dimensions, W, H, D:

482.6mm (standard 19 module), 133.3mm (3U, 5),

350mm (13) (390mm with cable strain relief)

Weight:

11.5kg (excluding rectifier modules)

Shipping Dimensions, W, H, D: 540mm, 200mm, 435mm

12 | ENATEL | 2010 PRODUCT CATALOGUE

Weight:

14.5kg (excluding rectifier modules)

Monitoring & Control:

Various monitoring options are available via the Enatel SM30 series of

control & supervisory modules. Standard features include full temperature

compensation, automated and manual battery testing/equalisation and

three voltage-free relay alarm outputs. Options include extension I/O PCBs

that give an extra 6x digital inputs, 6x analogue inputs and 8x voltage-free

relay outputs. For further details, refer to the SM30 series of brochures.

Part Numbers:

Actual part numbers will vary with congifuration.

PSC06030310-200:

3U Compact System including standard SM31 supervisory module.

PSC06030311-200:

3U Compact System including standard SM31

supervisory module and I/O expansion card.

PSC06030320-200:

3U Compact System including standard SM32

supervisory module.

PSC06030321-200:

3U Compact System including standard SM32

supervisory module and I/O expansion card.

3U COMPACT SYSTEM 1.0 - 8.0kW 48V DC


AC Input:

Three phase or single phase. (refer to RM series brochures for full details)

Frequency Range:

45-66Hz

Power Factor:

>0.99 (full load)

Termination:

Single phase L, N, E 16mm terminal blocks

Single phase surge protection. (40KA 8/20sec)

(Three phase without surge protection available to special order)

48
8.0

nominal output voltage.

DC Output
Nominal Voltage:

kW

-48V, -60V (+24V available to special order)

Rated System Output Power:

8000W @ -48V

Polarity:

Positive earth. (negative earth available to special order)

maximum output power.

DC Distribution:

3U Compact System

Supervisory Module

SM32

Load:
Battery:

Breaker Fail Detection:

2x 10A, 2x 20A, 4x 32A load circuit breakers.

2
AC
Input

SPD

Input MCB

Load

6
7
8

1
Battery
2

2x 100A battery circuit breakers.


Electronic fail detection on both load and battery breakers.

DC Terminals (rear connected):


Load:

16mm tunnel terminals.

Battery:

35mm tunnel terminals.

Low Voltage Disconnect:

150A battery LVD fitted as standard.

Mechanical
Dimensions, W, H, D:

482.6mm (standard 19 module), 133.3mm (3U, 5),

350mm (13) (390mm with cable strain relief)

Weight:

11kg (excluding rectifier modules)

Shipping Dimensions, W, H, D: 483mm, 133.35mm, 350mm


Weight:

11.5kg (excluding rectifier modules)

Monitoring & Control:

Various monitoring options are available via the Enatel SM30 series of

control & supervisory modules. Standard features include full temperature

compensation, automated and manual battery testing/equalisation and

three voltage-free relay alarm outputs. Options include extension I/O PCBs

that give an extra 6x digital inputs, 6x analogue inputs and 8x voltage-free

relay outputs. For further details, refer to the SM30 series of brochures.

Part Numbers:

Actual part numbers will vary with congifuration.

PSC08040310-000:

3U Compact System including standard SM31 supervisory module.

PSC08040311-000:

3U Compact System including standard SM31

supervisory module and I/O expansion card.

PSC08040320-000:

3U Compact System including standard SM32

supervisory module.

PSC08040321-000:

3U Compact System including standard SM32

supervisory module and I/O expansion card.


ENATEL | 2010 PRODUCT CATALOGUE | 13

5U MAXI COMPACT SYSTEM 1.0 - 14.0kW 48V DC

48
14.0
V

nominal output voltage.

Three phase (refer to RM series brochures for full details)

Frequency Range:

45-66Hz

Power Factor:

>0.99 (full load)

Termination:

Three phase L1, L2, L3, N, E 10mm terminal blocks.

Surge protection. (40kA 8/20msec)

DC Output

kW

maximum output power.

AC Input:

Nominal Voltage:

-48V, -60V (+24V available to special order)

Rated System Output Power:

14000W @ -48V DC

Polarity:

Positive earth. (negative earth available to special order)

DC Distribution:
5U Compact System

AC Input

Load

Battery

10

Supervisory Module

SM32

Load:

2x 10A, 6x 32A, 2x 50A load circuit breakers.

Battery:

4x 100A battery circuit breakers.

Breaker Fail Detection:

Electronic fail detection on both load and battery breakers.

DC Terminals (rear connected):


Load:

16mm tunnel terminals.

Battery:

35mm tunnel terminals.

Low Voltage Disconnect:

300A battery LVD fitted as standard.

Mechanical
Dimensions, W, H, D:

482.6mm (standard 19 module), 222.2mm (5U, 8),

350mm (13) (390mm with cable strain relief)

Weight:

14kg (excluding rectifier modules)

Shipping Dimensions, W, H, D: 540mm, 350mm, 435mm

14 | ENATEL | 2010 PRODUCT CATALOGUE

Weight:

18kg (excluding rectifier modules)

Monitoring & Control:

Various monitoring options are available via the Enatel SM30 series of

control & supervisory modules. Standard features include full temperature

compensation, automated and manual battery testing/equalisation and

three voltage-free relay alarm outputs. Options include extension I/O PCBs

that give an extra 6x digital inputs, 6x analogue inputs and 8x voltage-

free relay outputs. For further details, refer to the SM30 series of brochures.

Part Numbers:

Actual part numbers will vary with congifuration.

PSC12070510-000:

5U Maxi Compact System including standard SM31 supervisory module.

PSC12070511-000:

5U Maxi Compact System including standard SM31

supervisory module and I/O expansion card.

PSC12070520-000:

5U Maxi Compact System including standard SM32 supervisory module.

PSC12070521-000:

5U Maxi Compact System including standard SM32

supervisory module and I/O expansion card.

5U MAXI COMPACT SYSTEM 1.0 - 14.0kW 48V DC


AC Input:

Three phase. (refer to RM series brochures for full details)

Frequency Range:

45-66Hz

Power Factor:

>0.99 (full load)

Termination:

Three phase L1, L2, L3, N, E 16mm terminal blocks.

48
14.0

nominal output voltage.

DC Output
Nominal Voltage:

-48V, -60V (+24V available to special order)

Rated System Output Power:

14000W @ -48V

Polarity:

Positive earth. (negative earth available to special order)

kW

maximum output power.

DC Distribution:

Load:

6x 10A, 4x 20A, 4x 32A, 4x 50A load circuit breakers.

Battery:

4x 100A battery circuit breakers.

Breaker Fail Detection:

Electronic fail detection on both load and battery breakers.

DC Terminals:

Load

Battery

10

11

12

13

14

15

16

17

18

Supervisory Module

SM32

Load:

16mm tunnel terminals.

Battery:

35mm tunnel terminals.

Low Voltage Disconnect:

5U Compact System

300A battery LVD fitted as standard. (option 2x LVDs)

Mechanical
Dimensions, W, H, D:

482.6mm (standard 19 module), 222.2mm (5U, 8),

350mm (13) (390mm with cable strain relief)

Weight:

14kg (excluding rectifier modules)

Shipping Dimensions, W, H, D: 540mm, 350mm, 435mm


Weight:

18kg (excluding rectifier modules)

Monitoring & Control:

Various monitoring options are available via the Enatel SM30 series of

control & supervisory modules. Standard features include full temperature

compensation, automated and manual battery testing/equalisation and

three voltage-free relay alarm outputs. Options include extension I/O PCBs

that give an extra 6x digital inputs, 6x analogue inputs and 8x voltage-free

relay outputs. For further details, refer to the SM30 series of brochures.

Part Numbers:

Actual part numbers will vary with congifuration.

PSC12070510-001:

5U Maxi Compact System including standard SM31 supervisory module.

PSC12070511-001:

5U Maxi Compact System including standard SM31

supervisory module and I/O expansion card.

PSC12070520-001:

5U Maxi Compact System including standard SM32 supervisory module.

PSC12070521-001:

5U Maxi Compact System including standard SM32

supervisory module and I/O expansion card.


ENATEL | 2010 PRODUCT CATALOGUE | 15

5U MAXI COMPACT SYSTEM 1.0 - 14.0kW 48V DC

48
14.0
V

nominal output voltage.

Three phase (refer to RM series brochures for full details)

Frequency Range:

45-66Hz

Power Factor:

>0.99 (full load)

Termination:

Three phase L1, L2, L3, N, E, 16mm terminal blocks

DC Output

kW

maximum output power.

AC Input:

Nominal Voltage:

-48V, -60V (+24V available to special order)

Rated System Output Power:

14000W @ -48V

Polarity:

Positive earth (negative earth available to special order)

DC Distribution:
5U Compact System

AC Input

10 11 12 13 14 15 16 17 18 19 20

Load

Supervisory Module

SM32

Battery

Load:

6x 10A, 4x 20A, 6x 32A, 4x 50A load circuit breakers

Battery:

4x 100A battery circuit breakers

Breaker Fail Detection:

Electronic fail detection on both load and battery breakers

DC Terminals:

Load:

16mm tunnel terminals

Battery:

35mm tunnel terminals

Low Voltage Disconnect:

300A battery LVD fitted as standard

Mechanical
Dimensions, W, H, D:

482.6mm (standard 19 module), 222.2mm (5U, 8),

350mm (13) (390mm with cable strain relief)

Weight:

15kg (excluding rectifier modules)

Shipping Dimensions, W, H, D: 540mm, 350mm, 435mm

16 | ENATEL | 2010 PRODUCT CATALOGUE

Weight:

18kg (excluding rectifier modules)

Monitoring & Control:

Various monitoring options are available via the Enatel SM30 series of

control & supervisory modules. Standard features include full temperature

compensation, automated and manual battery testing/equalisation and

three voltage-free relay alarm outputs. Options include extension I/O PCBs

that give an extra 6x digital inputs, 6x analogue inputs and 8x voltage-free

relay outputs. For further details, refer to the SM30 series of brochures.

Part Numbers:

Actual part numbers will vary with congifuration.

PSC12070510-200:

5U Maxi Compact System including standard SM31 supervisory module.

PSC12070511-200:

5U Maxi Compact System including standard SM31

supervisory module and I/O expansion card.

PSC12070520-200:

5U Maxi Compact System including standard SM32 supervisory module.

PSC12070521-200:

5U Maxi Compact System including standard SM32

supervisory module and I/O expansion card.

6U MAXI COMPACT SYSTEM 1.0 - 22.0kW 48V DC


AC Input:

Three phase. (refer to RM series brochures for full details)

Frequency Range:

45-66Hz

Power Factor:

>0.99 (full load)

Termination:

Three phase L1, L2, L3, N, E 10mm terminal blocks.

Surge protection. (40kA 8/20msec)

DC Output
Nominal Voltage:

-48V, -60V (+24V available to special order)

Rated System Output Power:

22000W @ -48V DC

Polarity:

Positive earth. (negative earth available to special order)

DC Distribution:

Load:

2x 20A, 4x 32A, 4x 63A load circuit breakers.

Battery:

4x 100A battery circuit breakers.

Breaker Fail Detection:

Electronic fail detection on both load and battery breakers.

48
22.0

nominal output voltage.

kW

maximum output power.

6U Compact System

DC Terminals (rear connected):

AC Input

Load:

20A, 32A, 63A, 16mm tunnel terminals.

Battery:

35mm tunnel terminals.

Low Voltage Disconnect:

500A battery LVD fitted as standard.

Load

Battery

10

Supervisory Module

SM32

Mechanical
Dimensions, W, H, D:

482.6mm (standard 19 module), 266.7mm (6U, 10),

350mm (13) (390mm with cable strain relief)

Weight:

21kg (excluding rectifier modules)

Shipping Dimensions, W, H, D: 540mm, 350mm, 435mm


Weight:

30kg (excluding rectifier modules)

Monitoring & Control:

Various monitoring options are available via the Enatel SM30 series of

control & supervisory modules. Standard features include full temperature

compensation, automated and manual battery testing/equalisation and

three voltage-free relay alarm outputs. Options include extension I/O PCBs

that give an extra 6x digital inputs, 6x analogue inputs and 8x voltage-free

relay outputs. For further details, refer to the SM30 series of brochures.

Part Numbers:

Actual part numbers will vary with congifuration.

PSC22110610-000:

6U Maxi Compact System including standard SM31 supervisory module.

PSC22110611-000:

6U Maxi Compact System including standard SM31

supervisory module and I/O expansion card.

PSC22110620-000:

6U Maxi Compact System including standard SM32 supervisory module.

PSC22110621-000:

6U Maxi Compact System including standard SM32

supervisory module and I/O expansion card.

PSC22110610-F00:

6U Front Terminal Maxi Compact System including standard

SM31 supervisory module.*

PSC22110611-F00:

6U Front Terminal Maxi Compact System including standard

SM31 supervisory module and I/O expansion card.*

PSC22110620-F00:

6U Front Terminal Maxi Compact System including standard

SM32 supervisory module.*

PSC22110621-F00:

6U Front Terminal Maxi Compact System including standard

SM32 supervisory module and I/O expansion card.*

*for front terminal systems a minimum of 3U height above

the 6U system is recommended for load and battery cabling.


ENATEL | 2010 PRODUCT CATALOGUE | 17

15U MEDIUM SYSTEM 3.0 - 27.0kW 48V DC

48
27.0

AC Input

nominal output voltage.

maximum output power.

kW

AC Input Range:

312-500V AC (full power output)

156-312V AC (reduced output power)

Maximum Input Current:

60A/ph (ph-N)

Frequency Range:

45-66Hz

Power Factor:

>0.99 (full power)

Style:

3-phase neutral and earth.

Surge Protection:

MOV; 3x Ph-N, 1x N-Earth.

In(8/20S):

20kA

Imax(8/20S):

40kA

DC Output
Nominal System Output Voltage:

-48V

Maximum Power Output:

27000W

Polarity:

Positive earth. (standard)

Load & Battery Distribution:

16x load positions for 18mm wide circuit breakers,

plus 4x battery breakers up to 125A each.

May be arranged in different configurations of load and battery


Low Voltage Disconnect Options:

Single battery LVD fitted as standard.

Up to 2x LVDs with independent control may

LVD Current Rating:

breakers. Fuse options also available. (options)

be fitted on battery or load side. (option)


600A

Supervisory & Monitoring Module: SM31 (standard) SM32 TCP/IP enabled for

web based viewing & configuration. (option)

Supervisory Module Mounting:

Door mounted for improved system terminal access.

Battery Condition Monitoring:

Optional full battery monobloc monitoring.

(bloc voltage & string current)

Alarms (voltage free contacts):

1x fixed alarm - Monitor failed

Up to 9x user configurable, 2 of which are pre-programmed:

- Non-urgent summary alarm

- Urgent summary alarm

7x unassigned, may be assigned to any one of 37 alarm events,

(e.g. rectifier fail, mains fail etc.) on an AND or OR basis


Contacts rated for 1A at 60V DC

Environmental Requirements
Temperature:

-10C to +70C (max. power de-rated above 50C)

Humidity:

5-95% RH (non-condensing)

Altitude:

<2500m, De-rate maximum ambient temperature

by 4C per 1000m above sea level.

Mechanical
Dimensions W, D, H:

600mm (23 ) , 19 standard mounting rails 450mm (17 ),

800mm (31 ) providing 15U of rack space.

Weight:

75kg (approx)

Shipping Size L, W, H

900mm x 700mm x 550mm

Shipping weight:

80kg (approx)

Compliances

18 | ENATEL | 2010 PRODUCT CATALOGUE

Safety:

EN60950

Part Numbers:

Actual part numbers will vary with congifuration.

Contact us for further details on a solution that suits your requirements.

1.6M MEDIUM SYSTEM 3.0 - 27.0kW 48V DC


AC Input
AC Input Range:

312-500V AC (full power output)

156-312V AC (reduced output power)

Maximum Input Current:

54A/ph (ph-N)

Frequency Range:

45-66Hz

Power Factor:

>0.99 (full power)

Style:

3-phase neutral and earth.

Surge Protection:

MOV; 3x Ph-N, 1x N-Earth. (spark gap)

In(8/20S):

20kA

Imax(8/20S):

40kA

48
27.0

nominal output voltage.

kW

DC Output
Nominal System Output Voltage:

-48V

Maximum Power Output:

27000W

Polarity:

Positive earth. (standard)

maximum output power.

Load Distribution:

Priority:

6x 18mm MCBs.

Non-Priority:

5x 18mm MCBs, 2x 100A DIN00 fuses, 2x 160A DIN00 fuses.

Battery Distribution:

2x 400A DIN02 fuses.

LVD Options:

2x LVDs with independent control on load side.

LVD Rating:

Priority:

400A

Non-Priority:

200A

Supervisory & Monitoring Module: SM31 (standard) SM32 TCP/IP enabled for

Supervisory Module Mounting:

web based viewing & configuration. (option)


Door mounted for improved system terminal access.

Battery Condition Monitoring:

Optional full battery monobloc monitoring.

(bloc voltage & string current)

Alarms (voltage free contacts):

1x fixed alarm Monitor failed

Up to 9x user configurable, 2 of which are pre-programmed:

- Non-urgent summary alarm

- Urgent summary alarm

7x unassigned, may be assigned to any one of 37 alarm events,

(e.g. rectifier fail, mains fail etc.) on an AND or OR basis.

Contacts rated for 1A at 60V DC

Environmental Requirements
Temperature:

-10C to +70C (max. power de-rated above 50C)

Humidity:

5-95% RH (non-condensing)

Altitude:

<2500m, De-rate maximum ambient temperature

by 4C per 1000m above sea level.

Mechanical
Dimensions W, D, H:

600mm (23.6), 600mm (23.6), 1600mm (63),

providing 33U of rack space.

Weight:

120kg (approx)

Shipping Size L, W, H

1700mm x 720mm x 830mm

Shipping weight:

130kg (approx)

Compliances
Safety:

EN60950

Part Numbers:

Actual part numbers will vary with congifuration.

Contact us for further details on a solution that suits your requirements.


ENATEL | 2010 PRODUCT CATALOGUE | 19

2.0M MEDIUM SYSTEM 3.0 - 54.0kW 48V DC

48
54.0
V

nominal output voltage.

maximum output power.

kW

AC Input
Voltage Range:

312-500V AC (full power output)

156-312V AC (reduced output power)

Maximum Input Current:

120A/ph (ph-N)

Frequency Range:

45-66Hz

Power Factor:

>0.99 (full power)

Style:

3-phase neutral and earth.

Surge Protection:

MOV; 3x Ph-N, 1x N-Earth.

In(8/20S):

20kA

Imax(8/20S):

40kA

DC Output
Nominal System Output Voltage:

-48V

Maximum Power Output:

54000W

Polarity:

Positive earth. (standard)

Load & Battery Distribution:

56x positions for 18mm wide DIN rail mount circuit breakers.

May be arranged in many configurations of loads and batteries.

Fuse options also available. (options)

Low Voltage Disconnect Options:

Single battery LVD fitted as standard.

Up to 2x LVDs with independent control

may be fitted on battery or load side. (option)

LVD Current Rating:

1200A

Supervisory & Monitoring Module: SM31 (standard) SM32 TCP/IP enabled


for web based viewing & configuration. (option)

Supervisory Module Mounting:

Door mounted for improved system terminal access.

Battery Condition Monitoring:

Optional full battery monobloc monitoring.

(bloc voltage & string current)

Alarms (voltage free contacts):

1x fixed alarm Monitor failed

Up to 9x user configurable, 2 of which are pre-programmed:

- Non-urgent summary alarm

- Urgent summary alarm

7x unassigned, may be assigned to any one of 37 alarm events,

(e.g. rectifier fail, mains fail etc.) on an AND or OR basis

Contacts rated for 1A at 60V DC

Environmental Requirements
Temperature:

-10C to +70C (max. power de-rated above 50C)

Humidity:

5-95% RH (non-condensing)

Altitude:

<2500m, De-rate maximum ambient temperature

by 4C per 1000m above sea level.

Mechanical
Dimensions W, D, H:

600mm (23.6), 19 standard mounting rails, 600mm (23.6),

2000mm (78 ) 40U of rack space.

Weight:

180kg (approx)

Shipping Size L, W, H

2100mm, 720mm, 830mm

Shipping weight:

195kg (approx)

Compliances

20 | ENATEL | 2010 PRODUCT CATALOGUE

Safety:

EN60950

Part Numbers:

Actual part numbers will vary with congifuration.

Contact us for further details on a solution that suits your requirements.

2.2M INTEGRATED BASE TRANSCEIVER STATION SYSTEM 1.0 - 16.0kW 48V DC


AC Input
AC Input Range:

312-500V AC (full power output)

156-312V AC (reduced output power)

Maximum Input Current:

36A/ph (ph-N)

Frequency Range:

45-66Hz

Power Factor:

>0.99 (full power)

Style:

3-phase neutral and earth.

Surge Protection:

MOV; 3x Ph-N, 1x N-Earth. (spark gap)

In(8/20S):

20kA

Imax(8/20S):

40kA

48
16.0

nominal output voltage.

kW

maximum output power.

DC Output
Nominal System Output Voltage:

-48V

Maximum Power Output:

16000W

Polarity:

Positive earth. (standard)

Load & Battery Distribution:

24x load positions for 18mm wide circuit breakers, plus 3x battery

breakers up to 100A each. May be arranged in different

configurations of load and battery breakers. (option)

Low Voltage Disconnect Options:

Single battery LVD fitted as standard. Up to 2x LVDs with

independent control may be fitted on load side. (option)

LVD Current Rating:

400A

Supervisory & Monitoring Module: SM31 (standard) SM32 TCP/IP enabled


for web based viewing & configuration. (option)

Supervisory Module Mounting:

Door mounted for improved system terminal access.

Rectifier Modules:

RM2048, 48V 2.0kW module.

Environmental Requirements
Temperature:

-10C to +70C (max. power de-rated above 50C)

Humidity:

5-95% RH (non-condensing)

Altitude:

<2500m, De-rate maximum ambient temperature

by 4C per 1000m above sea level.

Mechanical
Dimensions W, D, H:

600mm (23.6), 600mm (23.6),2200mm (86.6)

Weight:

1000kg when fitted with 4x strings of 180Ahr batteries. (approx)

Shipping Size L, W, H

2400mm x 720mm x 830mm

Shipping weight:

180kg (no batteries fitted, approx)

Battery Accommodation
Battery Trays:

Up to 4x 180Ahr monoblocs of up to 60kg each per tray.

(max. of 250kg per tray)

Battery Monobloc Size W, D, H:

110mm, 555mm, 288mm

Compliances
Safety:

EN60950

Part Numbers:

Actual part numbers will vary with congifuration.

Contact us for further details on a solution that suits your requirements.


ENATEL | 2010 PRODUCT CATALOGUE | 21

2.0M LARGE DATA CENTER SOLUTIONS

48
54.0
V

nominal output voltage.

scalable output power.

kW

AC Input
Voltage Range:

312-500V AC (full power output)

156-312V AC (reduced output power)

Maximum Input Current:

120A/ph (ph-N)

Frequency Range:

45-66Hz

Power Factor:

>0.99 (full power)

Style:

3-phase neutral and earth.

Surge Protection:

MOV; 3x Ph-N, 1x N-Earth.

In(8/20S):

20kA

Imax(8/20S):

40kA

DC Output
Nominal System Output Voltage:

-48V

Maximum Power Output:

From 54000W scalable to over 300kW.

Polarity:

Positive earth. (standard)


Load & Battery Distribution:

56x positions for 18mm wide

DIN rail mount circuit breakers.

May be arranged in many

configurations of loads and

batteries. Fuse options also

available. (options)

LVD Options:

Single battery LVD.

Up to 2x LVDs with independent

control may be fitted on battery

or load side. (option)

LVD Current Rating:

1200A

Monitoring:

SM31 (standard) SM32 TCP/IP

enabled for web based viewing

& configuration. (option)

Supervisory Module Mounting: Door mounted for improved


system terminal access.

Battery Condition Monitoring: Optional full battery monobloc


monitoring. (bloc voltage &

string current)

Environmental Requirements
Temperature:

-10C to +70C (max. power

de-rated above 50C)

Humidity:

5-95% RH (non-condensing)

Altitude:

<2500m, De-rate maximum

ambient temperature by 4C

per 1000m above sea level.

Mechanical
Dimensions W, D, H:

600mm (23.6), 19 standard

mounting rails, 600mm (23.6),

2000mm (78 )

40U of rack space.

Weight:

180kg (approx)

Shipping Size L, W, H

2100mm, 720mm, 830mm

Shipping weight:

195kg (approx)

Compliances
Safety:

EN60950

Part Numbers: Actual part numbers will vary with congifuration.

22 | ENATEL | 2010 PRODUCT CATALOGUE

Contact us for further details on a solution that

suits your requirements.

WALL MOUNT SYSTEM 4.0kW 48V DC / 2.1kW 24V DC


AC Input:

Single phase with surge protection and input 32A MCB


(refer to rectifier brochure for full details)

Frequency Range:

45-66Hz

Power Factor:

>0.99 (full load)

Termination:

Single phase. Direct MCB termination for L. 10mm N, E tunnel

terminals.

DC Output Nominal Voltages:

-48V version.

+24V version.

Max Rated System Output Power:

4000W @ -48V DC, 83A max.

2140W @ +24V DC, 80A max.

Polarity:

Positive earth.

Negative Earth.

1x RM3048 3000W rectifier or

1x RM2324 2140W rectifier or

2x RM2048 2000W rectifiers.

2x RM1848/24 900W rectifiers.


DC Distribution:

Load:

Max 8x 18mm MCB load circuit breakers.

Battery:

Max 2x 18mm MCB load circuit breakers.

Breaker Fail Detection:

Electronic fuse fail. (Auxiliaries optional)

DC Terminals:

Live: Direct MCB connections.

Load:

Common: 16mm tunnel terminals.

Battery:

Common: 35mm tunnel terminals.

48
4.0
24
2.1

Low Voltage Disconnect:

80A battery LVD fitted as standard on -48V and 24V systems.

Weight:

Approx. 10.5Kg

Dimensions (L, H,W):

620mm x 375mm x 80mm

Shipping Dimensions (L, H,W):

730mm x 470mm x 200mm

Monitoring and Control:

Various monitoring options via the Enatel SM30 series of control

& supervisory modules. Standard features include full temperature

compensation, automated and manual battery testing/equalisation

and three voltage-free relay alarm outputs. Options include extension

remote I/O PCBs that give an extra 6x digital inputs, 6x analogue

inputs and 8x voltage-free relay outputs. For further details,

refer to the SM30 series of brochures.

Part Numbers:

Actual part numbers will vary with congifuration.

PSW-4204810-000:

48V, 2x 2000W rectifiers, SM31 supervisory module.

PSW-4204820-000:

48V, 2x 2000W rectifiers, SM32 supervisory module.

(Remote communication via SNMP)

PSW-3104810-000:

48V, 1x 3000W rectifier, SM31 supervisory module.

PSW-3104820-000:

48V, 1x 3000W rectifier, SM32 supervisory module.

(Remote communication via SNMP)

PSW-2102410-000:

24V, 1x 2140W rectifier, SM31 supervisory module.

PSW-2102420-000:

24V, 1x 2140W rectifier, SM32 supervisory module.

(Remote communications via SNMP)

PSW-2202410-000:

24V, 2x 900W rectifiers, SM31 supervisory module.

PSW-2202420-000:

24V, 2x 900W rectifiers, SM32 supervisory module.

(Remote communication via SNMP)

nominal output voltage.

kW

maximum output power.

nominal output voltage.

kW

maximum output power.

ENATEL | 2010 PRODUCT CATALOGUE | 23

MODULAR RECTIFIERS
- Force cooled.

If you are looking for modular, plug and play rectifiers with some of the highest

- Microprocessor controlled.

power densities in the market you have come to the right place.

- Power factor corrected.


- Thermally protected.

These rectifiers are designed for integration into systems that require intelligent

- Input/output voltage

features and remote control. With efficiencies in excess of 92% and power

and current protected.

- Serial alarm and control interface.

factors of greater than 0.98 these rectifiers will save operating costs, and reduce
heat dissipation.
Suitable for powering a wide range of telecommunications and data networking
applications including wireless, access networks and central office switching
environments.

24 | ENATEL | 2010 PRODUCT CATALOGUE

RM3048 3.0kW 48V DC MODULAR RECTIFIER


AC Input
Nominal:

230V

Voltage Range:

90-300V (reduced power below 175V)

Frequency Range:

45-65 Hz

Power Factor:

>0.99

Efficiency:

>92% (>45% output power)

Input Fuses:

HRC fuses in phase and neutral.

Maximum Input Current:

19A

Protection:

Input Voltage:

Auto shutdown, auto restart when correct voltage restored.

Input Inrush:

<2x maximum input current.

48
3.0
60.0

nominal output voltage.

kW

DC Output
Output Ratings:

Constant power output from 50V to 58V

Nominal Voltage:

48V

Rated Voltage:

58V

Voltage Range:

43-60V

Maximum Current:

60A

Regulation:

Line:

0.1%

Load:

0.5% (no load to full load)

Hold-up Time:

>15ms for 20% output voltage drop.

Start-up Time:

Start up delay 1 second. (varies with AC supply voltage)

Walk-in delay 6 seconds at full output. (varies with DC output voltage)

nominal output power.

maximum output current.

Protection:

Current Limit:

Adjustable to 50-100% of maximum rated current.

Over Temperature:

Automatic current turndown, backup shutdown protection.

Polarity Reversal:

Output fuse with crowbar diode.

Over voltage:

Adjustable limit.

Noise: (under nominal conditions)


Ripple <100Hz:

<1mV rms unweighted

Voice band 100Hz-5KHz:

<1mV rms psophometric

Wide band 5kHz-1MHz:

<5mV rms unweighted

Peak to Peak 0-20MHz:

<50mV peak to peak

Isolation:

Input to Output:

4000V DC

Input to Chassis:

3500V DC (VDR to chassis removed)

Output to Chassis:

2100V DC

Environmental Requirements
Ambient Temperature:

Nominal:

25+/-5C

Range:

-10C to +70C (maximum output power is derated above +50C)

Storage Temperature:

-20C to +70C

Humidity:

5-95% RH (non-condensing)

Altitude:

<2500m, De-rate maximum ambient temperature by 4C per 1000m above sea level.

Mechanical
Dimensions, W, H, D:

41mm, 220mm, 305mm overall.

Weight:

2.7kg

Shipping Dimensions W, H, D:

52mm, 230mm, 340mm

Shipping Weight:

2.85kg

Cooling:

Forced cooled, using dual temperature controlled high reliability fans.

Compliances
Safety:

EN60950

Electrostatic Discharge:

CISPR24

Radiated Radio Frequency:

CISPR22

AC Harmonics:

EN61000-3-2

AC Flicker and Fluctuation:

EN61000-3-3

Other:

CE & RoHS compliant.


ENATEL | 2010 PRODUCT CATALOGUE | 25

RM3048/24 3.0kW 48V DC / 1.7kW 24V DC MODULAR RECTIFIER

48
3.0
24
1.7
60.0

AC Input

nominal output voltage.

nominal output power.

kW

90-300V (reduced power below 175V)

Frequency Range:

45-65 Hz

Power Factor:

>0.99

Efficiency:

>92% (>45% output power)

Input Fuses:

HRC fuses in phase and neutral.

Maximum Input Current:

19A

Input Voltage:

Auto shutdown, auto restart when correct voltage restored.

Input Inrush:

<2x maximum input current.

DC Output - Software Switchable

48V

24V

Output Ratings:

Constant power output from 50V to 60V

Current limited to 60A

Nominal Voltage:

48V

24V

Rated Voltage:

58V

29V

Voltage Range:

43-60V

21-30V

Maximum Current:

60A

60A

Regulation:

nominal output voltage.

Line:

0.1%

Load:

0.5% (no load to full load)

Hold-up Time:

>15ms for 20% output voltage drop.

Start-up Time:

Start up delay 1 second. (varies with AC supply voltage)

Walk-in delay 6 seconds at full output. (varies with DC output voltage)

Protection:

kW

maximum output current.

230V

Voltage Range:

Protection:

nominal output power.

Nominal:

Current Limit:

Adjustable to 50-100% of maximum rated current.

Over Temperature:

Automatic current turndown, backup shutdown protection.

Polarity Reversal:

Output fuse with crowbar diode.

Over voltage:

Adjustable limit.

Noise: (under nominal conditions)


Ripple <100Hz:

<1mV rms unweighted

Voice band 100Hz-5KHz:

<1mV rms psophometric

Wide band 5kHz-1MHz:

<5mV rms unweighted

Peak to Peak 0-20MHz:

<50mV peak to peak

Isolation:

Input to Output:

4000V DC

Input to Chassis:

3500V DC (VDR to chassis removed)

Output to Chassis:

2100V DC

Environmental Requirements
Ambient Temperature:

Nominal:

25+/-5C

Range:

-10C to +70C (maximum output power is derated above +50C)

Storage Temperature:

-20C to +70C

Humidity:

5-95% RH (non-condensing)

Altitude:

<2500m, De-rate maximum ambient

temperature by 4C per 1000m above sea level.

Mechanical
Dimensions, W, H, D:

41mm, 220mm, 305mm overall.

Weight:

2.7kg

Shipping Dimensions W, H, D:

52mm, 230mm, 340mm

Shipping Weight:

2.85kg

Cooling:

Forced cooled, using dual temperature controlled high reliability fans.

Compliances

26 | ENATEL | 2010 PRODUCT CATALOGUE

Safety:

EN60950

Electrostatic Discharge:

CISPR24

Radiated Radio Frequency:

CISPR22

AC Harmonics:

EN61000-3-2

AC Flicker and Fluctuation:

EN61000-3-3

Other:

CE & RoHS compliant.

RM3060/48 3.0kW 60/48V DC MODULAR RECTIFIER


AC Input
Nominal:

230V

Voltage Range:

90-300V (reduced power below 175V)

Frequency Range:

45-65 Hz

Power Factor:

>0.99

Efficiency:

>92% (>45% output power)

Input Fuses:

HRC fuses in phase and neutral.

Maximum Input Current:

19A

60/48
3.0
50.0

Protection:

Input Voltage:

Auto shutdown, auto restart when correct voltage restored.

Input Inrush:

<2x maximum input current.

DC Output - Software Switchable

60V

48V

Output Ratings:

Constant power output from 60V to 74V

Current limited to 50A

Nominal Voltage:

60V

48V

Rated Voltage:

68V

58V

Voltage Range:

52-74V

43-60V

Maximum Current:

50A

50A

Regulation:

Line:

0.1%

Load:

0.5% (no load to full load)

nominal output voltage.

Hold-up Time:

>15ms for 20% output voltage drop

Start-up Time:

Start up delay 1 second. (varies with AC supply voltage)

Walk-in delay 6 seconds at full output. (varies with DC output voltage)

kW

nominal output power.

maximum output current.

Protection:

Current Limit:

Adjustable to 50-100% of maximum rated current.

Over Temperature:

Automatic current turndown, backup shutdown protection.

Polarity Reversal:

Output fuse with crowbar diode.

Over voltage:

Adjustable limit.

Noise: (under nominal conditions)


Ripple <100Hz:

<1mV rms unweighted

Voice band 100Hz-5KHz:

<1mV rms psophometric

Wide band 5kHz-1MHz:

<5mV rms unweighted

Peak to Peak 0-20MHz:

<50mV peak to peak

Isolation:

Input to Output:

4000V DC

Input to Chassis:

3500V DC (VDR to chassis removed)

Output to Chassis:

2100V DC

Environmental Requirements
Ambient Temperature:

Nominal:

25+/-5C

Range:

-20C to +70C (maximum output power is derated above +50C)

Storage Temperature:

-20C to +70C

Humidity:

5-95% RH (non-condensing)

Altitude:

<2500m, De-rate maximum ambient temperature

by 4C per 1000m above sea level.

Mechanical
Dimensions, W, H, D:

41mm, 220mm, 305mm overall.

Weight:

2.8kg

Shipping Dimensions W, H, D:

52mm, 230mm, 340mm

Shipping Weight:

2.95kg

Cooling:

Forced cooled, using dual temperature controlled high reliability fans.

Compliances
Safety:

EN60950

Electrostatic Discharge:

CISPR24

Radiated Radio Frequency:

CISPR22

AC Harmonics:

EN61000-3-2

AC Flicker and Fluctuation:

EN61000-3-3

Other:

CE & RoHS compliant.


ENATEL | 2010 PRODUCT CATALOGUE | 27

RM2324 2.3kW 24V DC MODULAR RECTIFIER

24
2.3
80.0

AC Input

nominal output voltage.

nominal output power.

230V

Voltage Range:

90-300V (reduced power below 150V)

Frequency Range:

45-65 Hz

Power Factor:

>0.99

Efficiency:

>91% (>45% output power)

Input Fuses:

HRC fuses in phase and neutral.

Maximum Input Current:

19A

Protection:

kW

maximum output current.

Nominal:

Input Voltage:

Auto shutdown, auto restart when correct voltage restored.

Input Inrush:

<2x maximum input current.

DC Output
Output Ratings:

Current limited to 80A

Nominal Voltage:

24V

Rated Voltage:

29V

Voltage Range:

21-30V

Maximum Current:

80A

Regulation:

Line: 0.1%

Load: 0.5% (no load to full load)

Hold-up Time:

>15ms for 20% output voltage drop.

Start-up Time:

Start up delay 1 second. (varies with AC supply voltage)

Walk-in delay 7 seconds at full output. (varies with DC output voltage)

Protection:

Current Limit:

Adjustable to 50-100% of maximum rated current.

Over Temperature:

Automatic current turndown, backup shutdown protection.

Polarity Reversal:

Output fuse with crowbar diode.

Over voltage:

Adjustable limit.

Noise: (under nominal conditions)


Ripple <100Hz:

<1mV rms unweighted

Voice band 100Hz-5KHz:

<1mV rms psophometric

Wide band 5kHz-1MHz:

<5mV rms unweighted

Peak to Peak 0-20MHz:

<50mV peak to peak

Isolation:

Input to Output:

4000V DC

Input to Chassis:

3500V DC (VDR to chassis removed)

Output to Chassis:

2100V DC

Environmental Requirements
Ambient Temperature:

Nominal:

25+/-5C

Range:

-10C to +70C (maximum output power is derated above +50C)

Storage Temperature:

-20C to +70C

Humidity:

5-95% RH (non-condensing)

Altitude:

<2500m, De-rate maximum ambient temperature

by 4C per 1000m above sea level.

Mechanical
Dimensions, W, H, D:

41mm, 220mm, 305mm overall.

Weight:

2.7kg

Shipping Dimensions W, H, D:

52mm, 230mm, 340mm

Shipping Weight:

2.75kg

Cooling:

Forced cooled, using dual temperature controlled high reliability fans.

Compliances

28 | ENATEL | 2010 PRODUCT CATALOGUE

Safety:

EN60950

Electrostatic Discharge:

CISPR24

Radiated Radio Frequency:

CISPR22

AC Harmonics:

EN61000-3-2

AC Flicker and Fluctuation:

EN61000-3-3

Other:

CE & RoHS compliant.

RM2048XP 2.0KW 48V DC MODULAR RECTIFIER


AC Input
Nominal:

230V

Voltage Range:

90-300V (reduced power below 175V)

Frequency Range:

45-65 Hz

Power Factor:

>0.99

Efficiency:

>92% (>50% output power)

Total Harmonic Distortion (THD):

<5% (>30% output power)

Input Fuses:

HRC fuses in phase and neutral.

Maximum Input Current:

12A

Protection:

Input Voltage:

Auto shutdown, auto restart when correct voltage restored.

Input Inrush:

<12A rms

DC Output
Output Ratings:

Constant power output from 48V to 58V

Nominal Voltage:

48V

Rated Voltage:

58V

Voltage Range:

43-60V

Maximum Current:

41.7A

Regulation:

Line:

0.1%

Load:

0.5% (no load to full load)

Hold-up Time:

>15ms for 20% output voltage drop.

Start-up Time:

Start up delay 1 second. (varies with AC supply voltage)

Walk-in delay 6 seconds at full output. (varies with DC output voltage)

48
2.0
41.7

nominal output voltage.

kW

nominal output power.

maximum output current.

Protection:

Current Limit:

Adjustable to 50-100% of maximum rated current.

Over Temperature:

Automatic current turndown, backup shutdown protection.

Polarity Reversal:

Output fuse with crowbar diode.

Over voltage:

Adjustable limit.

Noise: (under nominal conditions)


Ripple <100Hz:

<1mV rms unweighted

Voice band 100Hz-5KHz:

<1mV rms psophometric

Wide band 5kHz-1MHz:

<5mV rms unweighted


Peak to Peak 0-20MHz:
Isolation:

Input to Output:

Input to Chassis:

<100mV peak to peak

2100V DC

Output to Chassis:

4000V DC
3500V DC (VDR to chassis removed)

Environmental Requirements
Ambient Temperature:

Nominal:

25+/-5C

Range:

-10C to +70C (maximum output power is derated above +50C)

Storage Temperature:

-20C to +70C

Humidity:

5-95% RH (non-condensing)

Altitude:

<2500m, De-rate maximum ambient temperature

by 4C per 1000m above sea level.

Mechanical
Dimensions, W, H, D:

111.5mm , 44mm (1U), 282mm overall (rack depth 260mm)

Weight:

1.5kg

Shipping Dimensions W, H, D:

120mm, 52mm, 325mm

Shipping Weight:

1.6kg

Cooling:

Forced cooled.

Compliances
Safety:

EN60950

Electrostatic Discharge:

CISPR24

Radiated Radio Frequency:

CISPR22

AC Harmonics:

EN61000-3-2

AC Flicker and Fluctuation:

EN61000-3-3

Other:

CE & RoHS compliant.


ENATEL | 2010 PRODUCT CATALOGUE | 29

RM2048/24 2.0kW 48V DC / 1.0kW 24V DC MODULAR RECTIFIER

48
2.0
24
1.0
41.7

AC Input

nominal output voltage.

nominal output power.

90-300V (reduced power below 175V)

Frequency Range:

45-65 Hz

Power Factor:

>0.99

Efficiency:

>91% (>50% output power)

Input Fuses:

HRC fuses in phase and neutral.

Maximum Input Current:

13A

Input Voltage:

Auto shutdown, auto restart when correct voltage restored.

Input Inrush:

<2x maximum input current.

DC Output - Software Switchable

48V

24V

Output Ratings:

Constant power output from 54V to 60V

Current limited to 41.7A

Nominal Voltage:

48V

24V

Rated Voltage:

58V

29V

Voltage Range:

43-60V

21-30V

Maximum Current:

41.7A

41.7A

Regulation:

nominal output voltage.

Line:

0.1%

Load:

0.5% (no load to full load)

Hold-up Time:

>15ms for 20% output voltage drop.

Start-up Time:

Start up delay 1 second. (varies with AC supply voltage)

Walk-in delay 6 seconds at full output. (varies with DC output voltage)

Protection:

kW

maximum output current.

230V

Voltage Range:

Protection:

kW

nominal output power.

Nominal:

Current Limit:

Adjustable to 50-100% of maximum rated current.

Over Temperature:

Automatic current turndown, backup shutdown protection.

Polarity Reversal:

Output fuse with crowbar diode.

Over voltage:

Adjustable limit.

Noise: (under nominal conditions)


Ripple <100Hz:

<1mV rms unweighted

Voice band 100Hz-5KHz:

<1mV rms psophometric

Wide band 5kHz-1MHz:

<5mV rms unweighted

Peak to Peak 0-20MHz:

<50mV peak to peak

Isolation:

Input to Output:

4000V DC

Input to Chassis:

3500V DC (VDR to chassis removed)

Output to Chassis:

2100V DC

Environmental Requirements
Ambient Temperature:

Nominal:

25+/-5C

Range:

-10C to +70C (maximum output power is derated above +50C)

Storage Temperature:

-20C to +70C

Humidity:

5-95% RH (non-condensing)

Altitude:

<2500m, De-rate maximum ambient temperature

by 4C per 1000m above sea level.

Mechanical
Dimensions, W, H, D:

111.5mm , 44mm (1U), 282mm overall (rack depth 260mm)

Weight:

1.5kg

Shipping Dimensions W, H, D:

120mm, 52mm, 325mm

Shipping Weight:

1.6kg

Cooling:

Forced cooled.

Compliances

30 | ENATEL | 2010 PRODUCT CATALOGUE

Safety:

EN60950

Electrostatic Discharge:

CISPR24

Radiated Radio Frequency:

CISPR22

AC Harmonics:

EN61000-3-2

AC Flicker and Fluctuation:

EN61000-3-3

Other:

CE & RoHS compliant.

RM1860/48 1.8kW 60/48V DC MODULAR RECTIFIER


AC Input
Nominal:

230V

Voltage Range:

90-300V (reduced power below 175V)

Frequency Range:

45-65 Hz

Power Factor:

>0.99

Efficiency:

>91% (>50% output power)

Input Fuses:

HRC fuses in phase and neutral.

Maximum Input Current:

11A

60/48
1.8
30.0

Protection:

Input Voltage:

Auto shutdown, auto restart when correct voltage restored.

Input Inrush:

<2x maximum input current.

DC Output - Software Switchable

60V

48V

Output Ratings:

Constant power output from 60V to 74V

Current limited to 30A

Nominal Voltage:

60V

48V

Rated Voltage:

68V

54V

Voltage Range:

52-74V

43-60V

Maximum Current:

30A

30A

Regulation:

Line:

0.1%

Load:

0.5% (no load to full load)

nominal output voltage.

Hold-up Time:

>15ms for 20% output voltage drop

Start-up Time:

Start up delay 1 second. (varies with AC supply voltage)

Walk-in delay 6 seconds at full output. (varies with DC output voltage)

kW

nominal output power.

maximum output current.

Protection:

Current Limit:

Adjustable to 50-100% of maximum rated current.

Over Temperature:

Automatic current turndown, backup shutdown protection.

Polarity Reversal:

Output fuse with crowbar diode.

Over voltage:

Adjustable limit.

Noise: (under nominal conditions)


Ripple <100Hz:

<1mV rms unweighted

Voice band 100Hz-5KHz:

<1mV rms psophometric

Wide band 5kHz-1MHz:

<5mV rms unweighted

Peak to Peak 0-20MHz:

<50mV peak to peak

Isolation:

Input to Output:

4000V DC

Input to Chassis:

3500V DC (VDR to chassis removed)

Output to Chassis:

2100V DC

Environmental Requirements
Ambient Temperature:

Nominal:

25+/-5C

Range:

-10C to +70C (maximum output power is derated above +50C)

Storage Temperature:

-20C to +70C

Humidity:

5-95% RH (non-condensing)

Altitude:

<2500m, De-rate maximum ambient temperature

by 4C per 1000m above sea level.

Mechanical
Dimensions, W, H, D:

111.5mm , 44mm (1U), 282mm overall (rack depth 260mm)

Weight:

1.4kg

Shipping Dimensions W, H, D:

120mm, 52mm, 325mm

Shipping Weight:

1.5kg

Cooling:

Forced cooled.

Compliances
Safety:

EN60950

Electrostatic Discharge:

CISPR24

Radiated Radio Frequency:

CISPR22

AC Harmonics:

EN61000-3-2

AC Flicker and Fluctuation:

EN61000-3-3

Other:

CE & RoHS compliant.


ENATEL | 2010 PRODUCT CATALOGUE | 31

RM1048 1.0kW 48V DC MODULAR RECTIFIER

48
1.0
21.0
V

nominal output voltage.

nominal output power.

kW

maximum output current.

AC Input
Nominal:

230V

Voltage Range:

90-300V (reduced power below 175V)

Frequency Range:

45-65 Hz

Power Factor:

>0.99

Efficiency:

>90% (>50% output power)

Input Fuses:

HRC fuses in phase and neutral.

Protection:

Input Voltage:

Input Inrush:

Maximum Input Current:

Auto shutdown, auto restart when correct voltage restored.


<2x maximum input current.
7A

DC Output
Output Ratings:

Constant power output from 48V to 58V

Nominal Voltage:

48V

Rated Voltage:

58V

Voltage Range:

43-60V

Maximum Current:

21A

Regulation:

Line:

0.1%

Load:

0.5% (no load to full load)

Hold-up Time:

>15ms for 20% output voltage drop.

Start-up Time:

Start up delay 1 second. (varies with AC supply voltage)

Walk-in delay 6 seconds at full output. (varies with DC output voltage)

Protection:

Current Limit:

Adjustable to 50-100% of maximum rated current.

Over Temperature:

Automatic current turndown, backup shutdown protection.

Polarity Reversal:

Output fuse with crowbar diode.

Over voltage:

Adjustable limit.

Noise: (under nominal conditions)


Ripple <100Hz:

<1mV rms unweighted

Voice band 100Hz-5KHz:

<1mV rms psophometric

Wide band 5kHz-1MHz:

<5mV rms unweighted

Peak to Peak 0-20MHz:

<50mV peak to peak

Isolation:

Input to Output:

4000V DC

Input to Chassis:

3500V DC (VDR to chassis removed)

Output to Chassis:

2100V DC

Environmental Requirements
Ambient Temperature:

Nominal:

25+/-5C

Range:

-10C to +75C (maximum output power is derated above +50C)

Storage Temperature:

-20C to +75C

Humidity:

5-95% RH (non-condensing)

Altitude:

<2500m, De-rate maximum ambient temperature

by 4C per 1000m above sea level.

Mechanical
Dimensions, W, H, D:

111.5mm , 44mm (1U), 282mm overall (rack depth 260mm)

Weight:

1.4kg

Shipping Dimensions W, H, D:

120mm, 52mm, 325mm

Shipping Weight:

1.5kg

Cooling:

Forced cooled

Compliances

32 | ENATEL | 2010 PRODUCT CATALOGUE

Safety:

EN60950

Electrostatic Discharge:

CISPR24

Radiated Radio Frequency:

CISPR22

AC Harmonics:

EN61000-3-2

AC Flicker and Fluctuation:

EN61000-3-3

Other:

CE & RoHS compliant.

RM848 800W 48V DC MODULAR RECTIFIER


AC Input
Nominal:

230V

Voltage Range:

90-300V (reduced power below 175V)

Frequency Range:

45-65 Hz

Power Factor:

>0.99

Efficiency:

>92% (>50% output power)

Input Fuses:

HRC fuses in phase and neutral.

Maximum Input Current:

5.5A

Protection:

Input Voltage:

Auto shutdown, auto restart when correct voltage restored.

Input Inrush:

<2x maximum input current.

DC Output
Output Ratings:

Constant power output from 54V to 58V

Nominal Voltage:

48V

Rated Voltage:

58V

Voltage Range:

43-60V

Maximum Current:

16.6A

Regulation:

Line:

0.1%

Load:

0.5% (no load to full load)

Hold-up Time:

>15ms for 20% output voltage drop.

Start-up Time:

Start up delay 1 second. (varies with AC supply voltage)

Walk-in delay 6 seconds at full output. (varies with DC output voltage)

48
800
16.6

nominal output voltage.

nominal output power.

maximum output current.

Protection:

Current Limit:

Adjustable to 50-100% of maximum rated current.

Over Temperature:

Automatic current turndown, backup shutdown protection.

Polarity Reversal:

Output fuse with crowbar diode.

Over voltage:

Adjustable limit.

Noise: (under nominal conditions)


Ripple <100Hz:

<1mV rms unweighted

Voice band 100Hz-5KHz:

<2mV rms psophometric

Wide band 5kHz-1MHz:

<5mV rms unweighted

Peak to Peak 0-20MHz:

<50mV peak to peak

Isolation:

Input to Output:

4000V DC

Input to Chassis:

3500V DC (VDR to chassis removed)

Output to Chassis:

2100V DC

Environmental Requirements
Ambient Temperature:

Nominal:

25+/-5C

Range:

-20C to +70C (maximum output power is derated above +50C)

Storage Temperature:

-20C to +70C

Humidity:

0-98% RH (non-condensing)

Altitude:

<3000m, De-rate maximum ambient temperature

by 4C per 1000m above sea level.

Mechanical
Dimensions, W, H, D:

55mm , 44mm (1U), 235mm overall (rack depth 260mm)

Weight:

800g

Shipping Dimensions W, H, D:

100mm, 80mm, 300mm

Shipping Weight:

1.0kg

Cooling:

Forced cooled.

Compliances
Safety:

EN60950

Electrostatic Discharge:

CISPR24

Radiated Radio Frequency:

CISPR22

AC Harmonics:

EN61000-3-2

AC Flicker and Fluctuation:

EN61000-3-3

Other:

CE & RoHS compliant.


ENATEL | 2010 PRODUCT CATALOGUE | 33

FLAT MOUNT RECTIFIERS


- Forced cooled.

Flat mount rectifiers have been developed to allow provision of simple, and low

- Thermally protected.

cost solutions where only a limited amount of rack space is available. With all

- Power factor corrected.

input and output connections available on the front panel of the rectifier units

- Input/output voltage

they can be easily integrated in simple DC systems solutions.

and current protected.

- Temperature compensation.
- Automatic float/boost charge cycle.
- Alarm and control interface

including active load sharing.

- Optional built-in low


voltage disconnect.

With power ratings of 300W up to 1.4kW and output voltages of 12, 24 and
48V DC these rectifiers offer temperature compensation, and auto float/boost
switching as standard.
They have options available for internal low voltage disconnect (LVD) and an

- Optional internal alarm

alarm card, with relay outputs. These rectifiers can provide the powering solution

for most small and medium telecommunications, and data networking power

card with relay outputs.

applications.
Efficient and reliable, these rack mounting rectifiers allow for easy paralleling of
modules to provide redundancy or higher power outputs. Internal options include
low voltage disconnect (LVD) and an alarm card with relay outputs.
The unique design allows for mounting two rectifiers in a 1U x 19 rack space.
Custom configurations can be specified and additional features can be added.
Easy to install and compact, these robust, reliable rectifiers are forced
cooled by a speed controlled and monitored fan.

34 | ENATEL | 2010 PRODUCT CATALOGUE

RF SERIES FLAT MOUNT RECTIFIERS


AC Input

Nominal:
Voltage Range:



Frequency Range:
Power Factor:

Efficiency:
Maximum Input Current:
Input Fuses:
Protection:
Input Voltage:
Input Rush:
DC Output
Nominal Voltage:
Rated Voltage:
Voltage Range:
Maximum Current:
Regulation:
Line:
Load:
Hold-up Time:
Start-up Time:
Protection:
Current Limit:
Over Temp:
Polarity Reversal:
Over Voltage:
Noise: (under nominal conditions)
Ripple <100Hz:
Voice Band 100Hz to 5KHz:
Wide Band 5kHz to 1 MHz:
Peak to Peak 0 to 20MHz:
Isolation:
Input to Output:
Input to Chassis:
Output to Chassis:
Environmental Requirements
Nominal Ambient Temperature:
Range:
Humidity:
Altitude:

RF1448
RF1124
220/240V, 50/60Hz
220/240V, 50/60Hz
180-275V AC
180-275V AC
(full power output),
(full power output),
150-180V AC
150-180V AC
(reduced power output)
(reduced power output)
45-66Hz
>0.93 (full load)
RF1448
RF1124
90%
92%
8.5A
8.5A
HRC fuses in phase & neutral.

RF748U
110-220V, 50/60Hz
100-275V AC
(full power output),
85-100V AC
(reduced power output)

RF624U
110-220V, 50/60Hz
100-275V AC
(full power output),
85-100V AC
(reduced power output)

RF512U
110-220V, 50/60Hz
100-275V AC
(full power output),
85-100V AC
(reduced power output)

RF348U
110-220V, 50/60Hz
100-275V AC
(full power output),
85-100V AC
(reduced power output)

RF748U
89%
8.5A

RF624U
87%
8.5A

RF512U
85%
8.5A

RF348U
85%
8.5A

RF624U
24V
29V
22-30V
22A

RF512U
12V
14.5V
11.5-15V
40A

RF348U
48V
58V
45-60V
6A

RF624U
<5mV rms unweighted.
<1mV rms psophometric.
<5mV rms unweighted.
<50mV p-p unweighted.

RF512U
RF348U
<5mV rms unweighted.
<5mV rms unweighted.
<0.5mV rms psophometric. <0.5mV rms psophometric.
<2.5mV rms unweighted. <2.5mV rms unweighted.
<50mV p-p unweighted. <50mV p-p unweighted.

Automatic shutdown, restarts automatically when correct voltage restored.


<2x maximum input current.
RF1448
48V
58V
45-60V
25A

RF1124
24V
29V
22-30V
40A

RF748U
48V
58V
45-60V
12A

0.1%
0.5% (no load to full load)
>15ms for 20% output voltage drop.
Walk-in delay 2 seconds. (depends on AC input voltage)
Adjustable to 50-100% of maximum rated current.
Automatic current turndown, backup shutdown protection.
Output fuse with crowbar diode.
Adjustable limit.
RF1124
RF748U
RF1448
<10mV rms unweighted. <5mV rms unweighted.
<10mV rms unweighted.
<2mV rms psophometric. <1mV rms psophometric. <2mV rms psophometric.
<10mV rms unweighted. <5mV rms unweighted.
<10mV rms unweighted.
<50mV p-p unweighted.
<50mV p-p unweighted. <50mV p-p unweighted.
3000V AC
2500V AC (VDR to chassis removed)
1500V AC
25+/-5C
-10 to +50C
5-95% RH (non-condensing.)
<2500m de-rate maximum ambient temperature by +4 per 1000m above sea level.

Mechanical
Dimensions, W, H, D:
Weight:
Shipping Dimensions, W, H, D:
Shipping Weight:
Cooling:
Connections:
Mains:
Output to Load:
Temperature Sensor:
Monitor Connection:
Internal Alarm Card:

IEC 320 universal connection.


4 way lumberg macromodule.
2 way lumberg macromodule.
RJ45
Mini combicon.

Standard Features
Temperature Compensation:
Auto Float/Boost:


Alarm and Indicator Controls:

Output voltage slope adjustable 0.1 to 0.2%/C (standard)


Rectifier enters boost mode at power up. When battery current reduces to float threshold limit (adjustable from 0.1A to 40% MRC), unit reverts to float voltage setting.
When in boost but out of current limit, rectifier will automatically switch back to float after approximately four hours.
If battery current exceeds the float threshold limit when the rectifier is in float mode it will automatically switch to boost mode.
Positive V out, Load share signal (in/out), External shutdown, Open collector off normal alarm, (OSVD, over temp., current limit, fan fail), LVD synchronisation signal (in/out),
Temperature compensation input signal, Open collector rectifier fail (via 4k7 resistor), Open collector mains fail, Negative V out.

Options
Low Voltage Disconnect:
Voltage Adjustment Range:
Maximum Load Current:
Internal Alarm Card:

RF1448
RF1124
RF748U
RF624U
RF512U
RF348U
38-48V
19-24V
38-48V
19-24V
9.5-12V
38-48V
25A
40A
12A
22A
40A
6A
4x N.O or N.C (selectable) relay contacts with single common for rectifier fail, off normal, float low, float high. 1x VF changeover relay contact for mains fail.
Relay contacts rated at 100V DC 1A. Connections via mini combicon connector accepts 1.5mm dia wire.

Maintenance
LED Indicators:






Internal Adjustments:






Green - Mains on. (primary converter operating)


Green - Temperature probe connected and within normal limits.
Red - Rectifier failed.
Green - Rectifier in float mode.
Yellow - Rectifier in boost mode.
Yellow - Rectifier in current limit.
Red - Rectifier off normal. (over temp., OVSD, low output volts)
Float voltage.
Boost voltage.
Over voltage shut down.
Current limit.
Temperature compensation slope.
Auto boost to float threshold limit.
Load disconnect voltage. (if fitted)
Load disconnect hysteresis voltage. (if fitted)

Compliances
Safety:
Electrostatic Discharge:
Radiated Radio Frequency:
AC Harmonics:
AC Flicker and Fluctuation:

EN60950
CISPR24
CISPR22
EN61000-3-2
EN61000-3-3

Ordering Information
RFxxxx-10:
RFxxxx-11:
RFxxxx-20:
RFxxxx-21:

Standard
Standard
Standard
Standard

227mm, 44mm (1U), 270mm, (293mm over handle)


1.5kg
377mm, 235mm, 122mm
2.4kg
Forced cooled.

with
with
with
with

temperature
temperature
temperature
temperature

compensation,
compensation,
compensation,
compensation,

auto
auto
auto
auto

float
float
float
float

boost,
boost,
boost,
boost,

alarm
alarm
alarm
alarm

and
and
and
and

control
control
control
control

I/F.
I/F, low volts disconnect.
I/F, alarm card.
I/F, low volts disconnect, alarm card.

ENATEL | 2010 PRODUCT CATALOGUE | 35

WALL MOUNT RECTIFIERS


- Convection cooled.

The Enatel RW series of wall mount rectifiers have been developed to provide

- Thermally protected.

fully integrated power solutions for small telecommunications, and data

- Power factor corrected.

networking applications.

- Input/output voltage

and current protected.

- Automatic float/boost

charge cycle.

- Alarm and control interface


with active load sharing.

- Temperature compensation.
- Output current indicator.

Easily paralleled to provide redundancy, or higher power outputs these rectifiers


are simple to install and can be bolted directly to a wall or flat panel space.
Providing outputs of 12, 24 and 48V from 300W up to 700W output these
rectifiers offer temperature compensation, and auto float/boost switching
as standard.

- Optional built-in low

They have options available for internal low voltage disconnect (LVD) and an

alarm card, with relay outputs. These highly efficient rectifiers offer a range of

voltage disconnect.

- Optional internal alarm


output voltages and power levels.

card with relay outputs.


Easy to install and compact, these robust, reliable rectifiers are convection
cooled and are available with temperature compensation, and options for internal
low voltage disconnect (LVD) and alarm card with relay outputs.
They can be used as standalone power sources or can be operated in parallel to
provide redundancy or higher output ratings.
Choose from a range of internal options including load disconnect, current
indicators, alarm and control interface and auto float/boost. Custom
configurations can be specified and additional features can be added.

36 | ENATEL | 2010 PRODUCT CATALOGUE

RW SERIES WALL MOUNT RECTIFIERS


AC Input
Nominal:
Voltage Range:
Frequency Range:
Power Factor:

Efficiency:
Maximum Input Current:
Input Fuses:
Protection:
Input Voltage:
Input Rush:
DC Output
Nominal Voltage:
Rated Voltage:
Voltage Range:
Maximum Current:
Regulation:
Line:
Load:
Hold-up Time:
Start-up Time:
Protection:
Current Limit:
Over Temp:
Polarity Reversal:
Over Voltage:
Noise: (under nominal conditions)
Ripple <100Hz:
Voice Band 100Hz to 5KHz:
Wide Band 5kHz to 1 MHz:
Peak to Peak 0 to 20MHz:
Isolation:
Input to Output:
Input to Chassis:
Output to Chassis:

Environmental Requirements
Nominal Ambient Temperature:
Range:
Humidity:
Altitude:

110/220V, 50/60Hz
100-275V AC (full power output), 85-100V AC (reduced power output)
45-66Hz
>0.99 (full load)
RW748U
RW624U
RW512U
88%
87%
85%
8.5A
8.5A
8.5A
HRC fuses in phase & neutral.

RW348U
88%
8.5A

RW324U
87%
4A

RW312U
85%
4A

RW348U
48V
58V
45-60V
6A 300W

RW324U
24V
29V
22-30V
10A 300W

RW312U
12V
14.5V
11.5-15V
20A 300W

RW324U
<5mV rms unweighted.
<1mV rms psophometric.
<5mV rms unweighted.
<50mV p-p unweighted.

RW312U
<5mV rms unweighted.
<0.5mV rms psophometric.
<2.5mV rms unweighted.
<50mV p-p unweighted.

Automatic shutdown, restarts automatically when correct voltage restored.


<2x maximum input current.
RW748U
48V
58V
45-60V
12A 700W

RW624U
24V
29V
22-30V
22A 600W

RW512U
12V
14.5V
11.5-15V
35A

0.1%
0.5% (no load to full load)
>15ms for 20% output voltage drop.
Walk-in delay 2 seconds (depends on AC input voltage)
Adjustable to 50-100% of maximum rated current.
Automatic current turndown, backup shutdown protection.
Output fuse with crowbar diode.
Adjustable limit.
RW748U
RW624U
RW512U
RW348U
<10mV rms unweighted. <5mV rms unweighted.
<5mV rms unweighted.
<10mV rms unweighted.
<2mV rms psophometric. <1mV rms psophometric. <0.5mV rms psophometric. <2mV rms psophometric.
<10mV rms unweighted. <5mV rms unweighted.
<2.5mV rms unweighted. <10mV rms unweighted.
<50mV p-p unweighted.
<50mV p-p unweighted. <50mV p-p unweighted. <50mV p-p unweighted.
3000V AC.
2500V AC (VDR to chassis removed)
1500V AC
25+/-5C
-10 to +50C
5-95% RH (non-condensing)
<2500m de-rate maximum ambient temperature by +4 per 1000m above sea level.

Mechanical
Dimensions, W, H, D:
Weight:
Shipping Dimensions, W, H, D:
Shipping Weight:
Cooling:
Connections:
Mains:
Output to Load:
Output to Batteries:
Temperature Sensor:
Monitor Connection:
Internal Alarm Card:

IEC 320 universal connection.


4 way lumberg macromodule.
4 way lumberg macromodule.
2 way lumberg macromodule.
RJ45.
Mini combicon.

Standard Features
Output Current Indicator:
Temperature Compensation:
Auto Float/Boost:


Alarm and Indicator Controls:

Ten segment red LED dot display (standard)


Output voltage slope adjustable 0.1 to 0.2%/C (standard)
Rectifier enters boost mode at power up. When battery current reduces to float threshold limit (adjustable from 0.1A to 40% MRC), unit reverts to float voltage setting.
When in boost but out of current limit, rectifier will automatically switch back to float after approximately four hours.
If battery current exceeds the float threshold limit when the rectifier is in float mode it will automatically switch to boost mode.
Positive V out, Load share signal (in/out), External shutdown, Open collector off normal alarm (OSVD, over temp. limit), LVD synchronisation signal (in/out)
Temperature compensation input signal, Open collector rectifier fail (via 4k7 resistor), Open collector mains fail, Negative V out.

Options
Low Voltage Disconnect:
Voltage Adjustment Range:
Maximum Load Current:
Internal Alarm Card:

RW748U
RW624U
RW512U
RW348U
RW324U
RW312U
38-48V
19-24V
9.5-12V
38-48V
19-24V
9.5-12V
12A
22A
35A
6A
10A
20A
4x N.O or N.C (selectable) relay contacts with single common for rectifier fail, off normal, float low, float high. 1x VF changeover relay contact for mains fail.
Relay contacts rated at 100V DC 1A. Connections via mini combicon connector accepts 1.5mm dia wire.

Maintenance
LED Indicators:






Internal Adjustments:






Green - Mains on. (primary converter operating)


Green - Temperature probe connected and within normal limits.
Red - Rectifier failed.
Green - Rectifier in float mode.
Yellow - Rectifier in boost mode.
Yellow - Rectifier in current limit.
Red - Rectifier off normal. (over temp. OVSD, low output volts)
Float voltage.
Boost voltage.
Over voltage shut down.
Current limit.
Temperature compensation slope.
Auto boost to float threshold limit.
Load disconnect voltage. (if fitted)
Load disconnect hysteresis voltage. (if fitted)

Compliances
Safety:
Electrostatic Discharge:
Radiated Radio Frequency:
AC Harmonics:
AC Flicker and Fluctuation:

EN60950
CISPR24
CISPR22
EN61000-3-2
EN61000-3-3

Ordering Information
RWxxxx-10:
RWxxxx-11:
RWxxxx-20:
RWxxxx-21:

Standard
Standard
Standard
Standard

311mm, 163mm, 62mm


1.5kg
377mm, 235mm, 122mm
2.4kg
Convection cooled.

with
with
with
with

temperature
temperature
temperature
temperature

compensation,
compensation,
compensation,
compensation,

auto
auto
auto
auto

float
float
float
float

boost,
boost,
boost,
boost,

alarm
alarm
alarm
alarm

and
and
and
and

control
control
control
control

I/F.
I/F, low volts disconnect.
I/F, alarm card.
I/F, low volts disconnect, alarm card.

ENATEL | 2010 PRODUCT CATALOGUE | 37

DC-AC POWER SYSTEMS


- Integrated monitoring presents

Enatels ISM series inverter solutions offer a hot swappable modular inverter

system for supplying critical AC loads in telecom, and data networking

simplified systems management.

- Hot-swap/hot-plug modules

applications.

with n+1 redundancy.

- Small size means more room for


revenue generating equipment.

- Fully featured telecom


single point.

monitoring optional.

The inverter modules are available in 1.5kVA with either 110/120 or 220/230V AC

- High reliability means


output, and are scalable up to 15kVA. The inverter system solutions also include

less cost of maintenance.

- Full remote monitoring reduces


12kVA static switch and maintenance bypass modules.

maintenance costs.

- Easily customized and configured to


integrate AC/DC rectifiers, DC/DC converters and also DC/AC inverters into a
system with a single controller, providing remote monitoring capabilities from a

grade inverters.

- TCP/IP and SNMP network


One of the unique features offered by the Enatel system solution is the ability to

For further information on Enatels range of inverter systems, contact us today.

suit eachcustomers individual needs.

7U Inverter System

Supervisory Module

SM32

IM10230-48

38 | ENATEL | 2010 PRODUCT CATALOGUE

IM10230-48

IM10230-48

IM10230-48

IM10230-48

IM10230-48

IM10230-48

IM10230-48

IM10230-48

DC-AC INVERTERS
Efficient and reliable, these modular rack mount inverters allow for easy

- Pure sine wave.

paralleling of modules to provide redundancy or higher power outputs.

- Hot swapable.

Designed for use in modern telecommunications networks these inverters

- High efficiency.

offer unrivalled power densities.

- Smart fan speed control.


- Wide operation temperature range.

The unique design allows for mounting nine inverters in a 5U x 19 rack space
or two inverters in a 1U x 19 rack space.
Plug and Play installation allows quick and easy installation and system
expansion. These robust, reliable inverters are forced cooled by two speed
controlled and monitored high reliability fans.

- DSP chip designed.


- N+X redundancy system.
- Lower audible noise.
- High power density.
- Enatel RCP bus.
- 48V DC telecom system application.
- CE & RoHS compliant.

ENATEL | 2010 PRODUCT CATALOGUE | 39

IM SERIES MODULAR INVERTERS


DC Input
Operating Voltage Range:

40.5-58V DC

AC Output
Nominal Output Voltage:

110/230V AC (refer to part number table below for model numbers)

Output Voltage Range:

110/115/120V AC or 208/220/230/240V AC

Output Voltage Tolerance:

+/- 2%

Output Voltage Frequency:

50/60Hz selectable.

Output Frequency Tolerance:

+/- 0.5%

Total Harmonic Distortion:

<3% on linear loads.

<5% for non linear loads.

Turn On Delay:

<3 seconds.

Crest Factor:

3:1 (nominal power)

Efficiency:

90%

Output Power

(refer to part number table below for model numbers)

Nominal Value:

1000VA, 800W/

1500VA, 1200W

Overload (5 Seconds):

2000VA

Permanent Overload:

10%

Admissible Load Power Factor:

0 inductive to 0 capacitive (100% load)

Isolation:

Input/Output:

2500V AC

Output/Earth:

2500V AC

Input Earth:

1500V AC

Operating Temperature Range:

-40C to +50C, derated to +70C

Acoustic Noise:

<55dBa @ 1m

Display:

3x LEDs, fail, off normal, power on.

Serial Comms:

Enatel SBI interface to SM3X supervisory module.

Mechanical
Dimensions, W, H, D:

215mm, 43.8mm, 270mm overall.

Weight:

2.5kg

Shipping Dimensions W, H, D:

52mm, 230mm, 340mm

Shipping Weight:

2.65kg

Cooling:

Forced cooled.

Compliances
Immunity:

CISPR24

Emissions:

CISPR22 Class B

Safety:

IEC60950

Other:

CE & RoHS compliant.

Part Numbers

40 | ENATEL | 2010 PRODUCT CATALOGUE

IM10230-48:

1U, 48V DC input, 230V AC output, 1.0kVA 800W

IM10110-48:

1U, 48V DC input, 120V AC output, 1.0kVA 800W

IM15230-48:

1U, 48V DC input, 230V AC output, 1.5kVA 1200W

IM15110-48:

1U, 48V DC input, 120V AC output, 1.5kVA 1200W

SBM SERIES STATIC BYPASS MODULE


The Enatel SBM series static bypass module increases system reliability by

- Universal input range.

automatically switching between the inverter output and the utility supply.

- Hot-swap replacement in shelf.


- Back feed protection.

The SBM12000 can be programmed so that the system operates in a standby

- Redundant fan design.

backup mode were the utility is the normal source of supply or alternatively the

- Redundant power supply design.

system can be the normal source of supply with automatic switchover to the
utility in the event of system failure.

- Fast transfer time, typically


less than cycle.

- Wide operation temperature


range -20 to +70C.

- Lower audible noise <55dBA.

Input

- Emergency power off

AC Voltage Range:

function embedded.

110/115/120V AC:

From 89 to 138V AC.

- No-cross connect.

208/220/240V AC:

176 to 276V AC.

- Optional maintenance bypass


Over Voltage Threshold:


switch function with interlock.

- Operation priority setup of

Adjustable Using Controller:


220 to 240V AC for 208V AC systems.

transfer side by setting in

233 to 252V AC for 220V AC systems.

controller module.

244 to 264V AC for 230V AC systems.

254 to 276V AC for 240V AC systems.

117 to127V AC for 110V AC systems.

122 to 132V AC for 115V AC systems.

127 to 138V AC for 120V AC systems.

Under Voltage Threshold:


Adjustable Using Controller:

176 to 198V AC for 208V AC systems.

176 to 209V AC for 220V AC systems.

185 to 218V AC for 230V AC systems.

193 to 228V AC for 240V AC systems.

89 to 105V AC for 110V AC systems.

93 to 110V AC for 115V AC systems.

100 to 114V AC for 120V AC systems.

Redundant Power Supply Design:

Startup power-on by priority source or alternative.

Output
Waveform:

Sinusoidal.

Nominal Output Voltage:

Same as mains AC or the output of inverter modules.

Permissible Frequency Area:

Max. 2.5% (Synchronize area of inverter).

1.5Hz for 60Hz inverter.

1.25Hz for 50Hz inverter.

Transfer Time:

Typical cycle.

Rated Current:

50A (All voltage settings).

Operation Methods:

Inverter priority or utility priority (Programmable).

Part Number:
SBM12000:

50A/12kVA static bypass module.


ENATEL | 2010 PRODUCT CATALOGUE | 41

DC-DC CONVERTERS
- Force cooled.

These converters offer plug and play operation, and can be easily paralleled to

- Thermally protected.

provide higher power outputs.

- Input/output voltage

and current protected.

- Wide input voltage range.


- Serial alarm and control interface.
- Microprocessor controlled.

These units offer the same high levels of conversion efficiency as other Enatel
power products, and will provide the same benefits to the customer of reduced
operating costs and lower levels of heat dissipation.
The converters include a relay contact to indicate converter failure, and have a
load share input that ensures that all units connected in parallel carry an equal
share of the load.

42 | ENATEL | 2010 PRODUCT CATALOGUE

CM SERIES 1.7kW MODULAR DC-DC CONVERTERS


DC Input

CM1760-48

CM1748-60

CM1748-48

Nominal Input Voltage:

48V

60V

48V

Input Voltage Range:

40-60V

52-74V

40-60V

Input Protection:

Fuses:

Fuse in the positive input with crowbar diode.

Input Voltage:

Converter shuts down when input voltage is out of range,

Automatically restarts when correct voltage is restored.

DC Output

CM1760-48

CM1748-60

CM1748-48

Nominal Output Voltage:

60V

48V

48V

Output Voltage Range:

57-65V

46-52V

46-52V

Maximum Output Current:

27A

33A

33A

Maximum Output Power:

1700W

1700W

1700W

Efficiency:

91%

91%

91%

Regulation:

Line:

0.1%

Load:

0.5% (no load to full load)

Start-up Time:

Walk-in delay 2-8 seconds depending on load.

Protection:

Current Limit:

Adjustable to 50-100% of maximum rated current.

Over Temperature:

Auto current turndown, backup shutdown protection.

Polarity Reversal:

Output fuse in positive with crowbar diode.

Over Voltage:

Adjustable limit.

Noise: (under nominal conditions)


Ripple <100Hz:

<1mV rms unweighted

Voice Band 100Hz-5KHz:

<1mV rms psophometric

Wide Band 5kHz-1MHz:

<5mV rms unweighted

Peak to Peak 0-20MHz:

<50mV peak to peak

Isolation:

Input to Output:

4230V DC

Input to Chassis:

2115V DC (VDR to chassis removed)

Output to Chassis:

2115V DC

Environmental Requirements
Ambient Temperature:

Nominal:

+25 +/- 5C

Range:

-10 to +70C (maximum output power is derated above +50C)

Storage Temperature:

-20 to +70C

Humidity:

5-95% RH (non condensing)

Altitude:

<2500m, De-rate maximum ambient temperature

by +4C per 1000m above sea level.

Mechanical
Dimensions W, H, D:

111.5mm, 44mm (1U), 282 overall (rack depth 260mm)

Weight:

1.1kg

Shipping Dimensions W, H, D:

170mm, 52mm, 325mm

Shipping Weight:

1.6kg

Cooling:

Forced cooled.

Compliances
Safety:

EN60950

Electostatic Discharge:

CISPR24

Radiated Radio Frequency:

CISPR22

Additional Accesories
ACM-4T:

1U 4 position DC-DC converter shelf, no cables.

Part Numbers
CM1760-48:

1.7kW 48 to 60V DC modular DC-DC converter.

CM1748-60:

1.7kW 60 to 48V DC modular DC-DC converter.

CM1748-48:

1.7kW 48 to 48V DC modular DC-DC converter.


ENATEL | 2010 PRODUCT CATALOGUE | 43

CM SERIES 500W to 1.0kW MODULAR DC-DC CONVERTERS


DC Input
Nominal Input Voltage:
Input Voltage Range:
Input Protection:
Fuses:
Input Voltage:

CM1048-24 CM1024-48 CM648-24


24V
48V
24V
20-30V
40-60V
20-30V

CM624-48
48V
40-60V

Fuse in the positive input with crowbar diode.


Converter shuts down when input voltage is out of range,
Automatically restarts when correct voltage is restored.

DC Output
CM1048-24 CM1024-48 CM648-24 CM624-48
Nominal Output Voltage:
48V
24V
48V
24V
Output Voltage Range:
46-52V
22-26V
46-52V
22-26V
Maximum Output Current:
21.6A
43A
13.5A
25A
Maximum Output Power:
1040W
1040W
650W
650W
91%
91%
Efficiency:
91%
91%
Regulation:
0.1%
Line:
Load:
0.5% (no load to full load)
Start-up Time:
Walk-in delay 2-8 seconds depending on load and output
Protection:
Adjustable to 50-100% of maximum rated current.
Current Limit:
Over Temperature:
Auto current turndown, backup shutdown protection.
Polarity Reversal:
Output fuse in positive with crowbar diode.
Over Voltage:
Adjustable limit.
Noise: (under nominal conditions)
Ripple <100Hz:
<1mV rms unweighted
Voice Band 100Hz-5KHz: <1mV rms psophometric
Wide Band 5kHz-1MHz: <5mV rms unweighted
Peak to Peak 0-20MHz:
<50mV peak to peak
Isolation:
4230V DC
Input to Output:
2115V DC (VDR to chassis removed)
Input to Chassis:
Output to Chassis:
2115V DC
Environmental Requirements
Ambient Temperature:
Nominal:
Range:
Storage Temperature:
Humidity:
Altitude:

CM612-48
12V
11-14V
40A
560W
89%

voltage.

+25 +/- 5C
-10 to +70C (maximum output power is derated above +50C)
-20 to +70C
5-95% RH (non condensing)
<2500m, De-rate maximum ambient temperature
by +4C per 1000m above sea level.

Mechanical
Dimensions W, H, D:
111.5mm, 44mm (1U), 282 overall (rack depth 260mm)
Weight:
1.1kg
Shipping Dimensions W, H, D: 170mm, 52mm, 325mm
Shipping Weight:
1.6kg
Cooling:
Forced cooled.

44 | ENATEL | 2010 PRODUCT CATALOGUE

CM612-48
48V
40-60

Compliances
Safety:
Electostatic Discharge:
Radiated Radio Frequency:
Other:

EN60950
CISPR24
CISPR22
CE & RoHS compliant

Additional Accesories
ACM-4T:

1U 4 position DC-DC converter shelf, no cables.

Part Numbers
CM1048-24:
CM1024-48:
CM648-24:
CM624-48:
CM612-48:

1.0kW 24 to 48V DC modular DC-DC converter.


1.0kW 48 to 24V DC modular DC-DC converter.
650W 24 to 48V DC modular DC-DC converter.
650W 48 to 24V DC modular DC-DC converter.
560W 48 to 12V DC modular DC-DC converter.

MONITORING
Enatel offer a range of supervisory modules and monitoring options, which have

- Temperature compensation.

been designed to work with our power products. Allowing for easy integration

- LVD control.

into our complete DC power systems solutions for telecommunications and data

- Setup from front panel.

networking applications.

- Boost control and timer.


- LCD display of parameters.

ENATEL | 2010 PRODUCT CATALOGUE | 45

SM36 SUPERVISORY MODULE

LVD
WEB
USB
dual lvd control.

web based configurator.

usb port for local connection.

46 | ENATEL | 2010 PRODUCT CATALOGUE

Input
Voltage:
Current:
Interface
Display:
Communications:

Serial:


Relay:


TCP/IP:



LVD:

Indicators:

3x LEDs:



Audible:
Controls:
Signal Inputs:





Alarms:
Alarm Contacts:
Default Alarm Map:

Relay 1:

Relay 2:

Relay 3:

Relay 4 - 6:
Logging Capacity:

Periodic Log:

Event Log:
Battery Mid-point Monitoring:

16-75V DC
<150mA maximum.

4 line x 16 character multi-lingual alpha numeric display.


1x USB port on front panel for local PC interface.
1x RS232 port, rear mounted for remote serial/modem communications.
6x alarm and control relays, five of which can be mapped for customized
alarm settings. (extra available with I/O expansion board)
Ethernet interface for communication using SNMP protocol and internal
web based configurator.
3x standard or 2x pulse control LVD contacts.
(for magnetically latched LVD contactors)
Green - power on/monitor OK.
Yellow - non urgent alarm.
Red - urgent alarm.
90dBA buzzer mappable to user defined conditions.
3x push buttons for parameter setting or viewing on front panel.
2x serial buses for rectifier control and interface to peripheral modules.
10x general purpose inputs.
(6x for customer connection, 4x reserved for internal system connection.)
4x battery MCB sensors. (reserved for internal system connection.)
3x current shunt inputs. (reserved for internal system connection.)
1x DC voltage inputs. (reserved for internal system connection.)
6x alarm relays.
0.3A 100V volts free changeover contacts.
Monitor fail. (non programmable.)
Non-urgent. (programmable.)
Urgent. (programmable.)
Unassigned.
Typically 16000 records. (dependant on number of parameters logged.)
Typically 16000 records. (dependant on number of parameters logged.)
3x strings with individual string currents.
(more available with shared string currents.)

Physical
Dimensions, W, H, D:
Weight:
Connections:



Operating Temperature:
Storage Temperature:

111.5mm , 44mm (1U), 265mm overall (rack depth 244mm)


365g
Relay outputs, mini combicon to accept 1.5mm csa wire.
Serial communications to rectifier shelf & peripheral devices - RJ45.
USB port - USB mini B.
-25 to +55C
-50 to +85C

Compliances
Radiated Emissions:
RF Susceptibility:

EN55022
EN55024

Optional Accessories
ACA-TC3C:
ACA-TC7C:
ASM-AC3P:
ASM-ABM-24:
ASM-SM36IO:

Voltage Range:

Current:

Connection:

Alarms:


Signal Inputs:

Operating Temperature:

Storage Temperature:

3m temperature sensor and cable.


7m temperature sensor and cable.
3 phase AC voltage and current monitor.
Battery condition monitor, 24 blocks. (maximum 4x BCM cards)
Standard I/O expansion board (maximum of 4 per supervisory module.)
15-75V DC
<150mA maximum
Connects via rectifier serial bus, 2x RJ45.
Up to 8x alarm and control relays, able to
be mapped for customized alarm settings.
Up to 6x digital inputs. Up to 6x analogue inputs.
-25 to +55C
-50 to +85C

Part Numbers
SM36-00:
SM36-00-1U:
SM36-10-1U:

SM36-00-PM:
SM36-10-PM:

Standard 1U modular controller, 6x relays, 6x digital inputs.


Standard 1U x 19 mounting version controller, 6x relays, 6x digital inputs.
Standard 1U x 19 mounting version controller, 6x relays,
6x digital inputs; with standard I/O expansion board.
Standard panel mount version controller, 6x relays, 6x digital inputs.
Standard panel mount version controller, 6x relays,
6x digital inputs; with standard I/O expansion board.

SM35 SUPERVISORY MODULE


Input
Voltage:
Current:
Interface
Display:
Communications:

Serial:

Relay:


LVD:

Indicators:

3x LEDs



Audible:
Controls:
Signal Inputs:





Alarms:
Alarm Contacts:
Default Alarm Map:

Relay 1:

Relay 2:

Relay 3:

Relay 4 - 6:
Logging Capacity:

Periodic Log:

Event Log:
Battery Mid-point Monitoring:

16-75V DC
<150mA maximum.

4 line x 16 character multi-lingual alpha numeric display.


1x USB port on front panel for local PC interface.
6x alarm and control relays, five of which can
be mapped for customized alarm settings.
3x standard or 2x pulse control LVD contacts.
(for magnetically latched LVD contactors)
Green - power on/monitor OK.
Yellow - non urgent alarm.
Red - urgent alarm.
90dBA buzzer mappable to user defined conditions.
3x push buttons for parameter setting or viewing on front panel.
2x serial buses for rectifier control and interface to peripheral modules.
10x general purpose inputs.
(6x for customer connection, 4x reserved for internal system connection.)
4x battery MCB sensors. (reserved for internal system connection.)
3x current shunt inputs. (reserved for internal system connection.)
1x DC voltage inputs. (reserved for internal system connection.)
6x alarm relays.
0.3A 100V volts free changeover contacts.

126
LCD
USB

serial control for up to 126 rectifiers/


converters plus peripheral devices.

lcd display.

usb port for local connection.

Monitor fail. (non programmable.)


Non-urgent. (programmable.)
Urgent. (programmable.)
Unassigned.
Typically 16000 records. (dependant on number of parameters logged.)
Typically 16000 records. (dependant on number of parameters logged.)
3x strings with individual string currents.
(more available with shared string currents.)

Physical
Dimensions, W, H, D:
Weight:
Connections:




Operating Temperature:
Storage Temperature:

111.5mm , 44mm (1U), 265mm overall (rack depth 244mm)


325g
Relay outputs, mini combicon to accept 1.5mm csa wire.
Serial communications to rectifier shelf & peripheral devices - RJ45.
USB port - USB mini B.
-25 to +55C
-50 to +85C

Compliances
Radiated Emissions:
RF Susceptibility:

EN55022
EN55024

Optional Accessories
ACA-TC3C:
ACA-TC7C:
ASM-AC3P:
ASM-ABM-24:
ASM-SM3XIO:

Voltage Range:

Current:

Connection:

Alarms:


Signal Inputs:

Operating Temperature:

Storage Temperature:

3m temperature sensor and cable.


7m temperature sensor and cable.
3 phase AC voltage and current monitor.
Battery condition monitor, 24 blocks. (maximum 4x BCM cards.)
Standard I/O expansion board (maximum of 4 per supervisory module.)
15-75V DC
<150mA maximum
Connects via rectifier serial bus, 2x RJ45.
Up to 8x alarm and control relays, able to
be mapped for customized alarm settings.
Up to 6x digital inputs. Up to 6x analogue inputs.
-25 to +55C
-50 to +85C

Part Numbers
SM35-00:
SM35-00-1U:
SM35-10-1U:

SM35-00-PM:
SM35-10-PM:

Standard 1U modular controller, 6x relays, 6x digital inputs.


Standard 1U x 19 mounting version controller, 6x relays, 6x digital inputs.
Standard 1U x 19 mounting version controller, 6x relays,
6x digital inputs; with standard I/O expansion board.
Standard panel mount version controller, 6x relays, 6x digital inputs.
Standard panel mount version controller, 6x relays,
6x digital inputs; with standard I/O expansion board.
ENATEL | 2010 PRODUCT CATALOGUE | 47

SM32 SUPERVISORY MODULE

LVD
WEB
USB
dual lvd control.

web based configurator.

usb port for local connection.

48 | ENATEL | 2010 PRODUCT CATALOGUE

Input
Voltage:
Current:
Interface
Display:
Communications:

Serial:


Relay:



TCP/IP:




LVD:

Indicators:

3x LEDs



Audible:
Controls:
Signal Inputs:





Alarms:
Alarm Contacts:
Default Alarm Map:


Logging Capacity:

Periodic Log:

Event Log:

16-75V DC
<150mA maximum.

4 line x 16 character multi-lingual alpha numeric display.


1x USB port on front panel for local PC interface.
1x RS232 port, rear mounted for remote serial/modem communications.
3x alarm and control relays, two of which
can be mapped for customized alarm settings.
(extra available with I/O expansion board)
Ethernet interface for communication using SNMP
protocol and internal web based configurator.
3x standard or 2x pulse control LVD contacts.
(for magnetically latched LVD contactors)
Green - power on/monitor OK.
Yellow - non urgent alarm.
Red - urgent alarm.
90dBA buzzer mappable to user defined conditions.
3x push buttons for parameter setting or viewing on front panel.
Serial bus for rectifier control and interface to peripheral modules.
Fuse fail.
5x spare digital inputs.
2x temperature sensors.
3x current shunts.
2x DC voltage inputs.
3x alarm relays.
0.3A 100V volts free changeover contacts.
Urgent.
Non-urgent.
Monitor fail.
16384 records. (dependant on number of parameters logged.)
16384 records. (dependant on number of parameters logged.)

Physical
Dimensions, W, H, D:
Weight:
Connections:




Operating Temperature:
Storage Temperature:

111.5mm , 44mm (1U), 282mm overall (rack depth 260mm)


1.5kg
Relay outputs, mini combicon to accept 1.5mm csa wire.
Serial communications to rectifier shelf & peripheral devices - RJ45.
USB port - USB mini B.
-25 to +55C
-50 to +85C

Compliances
Radiated Emissions:
RF Susceptibility:

EN55022
EN55024

Optional Accessories
ACA-TC3C:
ACA-TC7C:
ASM-AC3P:
ASM-ABM-24:
ASM-SM3XIO:

Voltage Range:

Current:

Connection:

Alarms:


Signal Inputs:

Operating Temperature:

Storage Temperature:

3m temperature sensor and cable.


7m temperature sensor and cable.
3 phase AC voltage and current monitor.
Battery condition monitor, 24 blocks. (maximum 4x BCM cards.)
Standard I/O expansion board (maximum of 4 per supervisory module.)
15-75V DC
<150mA maximum
Connects via rectifier serial bus, 2x RJ45.
Up to 8x alarm and control relays, able to
be mapped for customized alarm settings.
Up to 6x digital inputs. Up to 6x analogue inputs.
-25 to +55C
-50 to +85C

Part Numbers
SM32-00:
SM32-10:

SM32-00-1U:

SM32-10-1U:

SM32-00-PM:
SM32-10-PM:

Standard 1U modular controller, 3x relays, 6x digital inputs.


Standard 1U modular controller, 3x relays, 6x digital inputs;
with standard I/O expansion board mounted onto baseplate metalwork.
Standard 1U x 19 mounting version controller,
3x relays, 6x digital inputs.
Standard 1U x 19 mounting version controller, 3x relays,
6x digital inputs; with standard I/O expansion board.
Standard panel mount version controller, 3x relays, 6x digital inputs.
Standard panel mount version controller, 3x relays,
6x digital inputs; with standard I/O expansion board.

SM31 SUPERVISORY MODULE


Input
Voltage:
Current:
Interface
Display:
Communications:

Serial:

Relay:


LVD:

Indicators:

3x LEDs



Audible:
Controls:
Signal Inputs:





Alarms:
Alarm Contacts:
Default Alarm Map:


Logging Capacity:

Periodic Log:

Event Log:

16-75V DC
<150mA maximum.

4 line x 16 character multi-lingual alpha numeric display.


1x USB port on front panel for local PC interface.
3x alarm and control relays, two of which
can be mapped for customized alarm settings.
3x standard or 2x pulse control LVD contacts.
(for magnetically latched LVD contactors)
Green - power on/monitor OK.
Yellow - non urgent alarm.
Red - urgent alarm.
90dBA buzzer mappable to user defined conditions.
3x push buttons for parameter setting or viewing on front panel.
2x serial buses for rectifier control and interface to peripheral modules.
Fuse fail.
5x spare digital inputs.
2x temperature sensors.
3x current shunts.
2x DC voltage inputs.
3x alarm relays.
0.3A 100V volts free changeover contacts.
Urgent.
Non-urgent.
Monitor fail.

126
LCD
USB

serial control for up to 126 rectifiers/


converters plus peripheral devices.

lcd display.

usb port for local connection.

16384 records. (dependant on number of parameters logged.)


16384 records. (dependant on number of parameters logged.)

Physical
Dimensions, W, H, D:
Weight:
Connections:




Operating Temperature:
Storage Temperature:

111.5mm , 44mm (1U), 282mm overall (rack depth 260mm)


1.5kg
Relay outputs, mini combicon to accept 1.5mm csa wire.
Serial communications to rectifier shelf & peripheral devices - RJ45.
USB port - USB mini B.
-25 to +55C
-50 to +85C

Compliances
Radiated Emissions:
RF Susceptibility:

EN55022
EN55024

Optional Accessories
ACA-TC3C:
ACA-TC7C:
ASM-AC3P:
ASM-ABM-24:
ASM-SM3XIO:

Voltage Range:

Current:

Connection:

Alarms:


Signal Inputs:

Operating Temperature:

Storage Temperature:

3m temperature sensor and cable.


7m temperature sensor and cable.
3 phase AC voltage and current monitor.
Battery condition monitor, 24 blocks. (maximum 4x BCM cards.)
Standard I/O expansion board (maximum of 4 per supervisory module.)
15-75V DC
<150mA maximum
Connects via rectifier serial bus, 2x RJ45.
Up to 8x alarm and control relays, able to
be mapped for customized alarm settings.
Up to 6x digital inputs. Up to 6x analogue inputs.
-25 to +55C
-50 to +85C

Part Numbers
SM31-00:
SM31-10:

SM31-00-1U:

SM31-10-1U:

SM31-00-PM:
SM31-10-PM:

Standard 1U modular controller, 3x relays, 6x digital inputs.


Standard 1U modular controller, 3x relays, 6x digital inputs;
with standard I/O expansion board mounted onto baseplate metalwork.
Standard 1U x 19 mounting version controller,
3x relays, 6x digital inputs.
Standard 1U x 19 mounting version controller, 3x relays,
6x digital inputs; with standard I/O expansion board.
Standard panel mount version controller, 3x relays, 6x digital inputs.
Standard panel mount version controller, 3x relays,
6x digital inputs; with standard I/O expansion board.
ENATEL | 2010 PRODUCT CATALOGUE | 49

SM11 SUPERVISORY MODULE

TEMP
LVD
LCD
temperature compensation.

lvd control.

lcd display of parameters.

Input
Voltage:

Current:

35-60V DC
<85mA maximum.

Interface
Display:
Communications:

Serial:

Relay:
Indicators:
Controls:
Signal Inputs:


Alarms:
Alarm Contacts:
Alarm List:

6 character starburst.
Interfaces with up to 6x RF series rectifiers.
RS232 serial for downloading configuration files.
7x alarm and control relays.
8x LED.
3x push buttons for parameter setting on front panel.
External shutdown. Fuse fail. Rectifier fail. Mains fail.
Rectifier off normal. 2x voltmeter. 2x current meter. (100mV)
7x alarm relays.
1A 100V volts free changeover contacts.
Off normal. Rectifier fail. Mains fail. Float high. Float low.
LVD. (control line for external LVD contactor)

Physical
Dimensions W, H, D:
Weight:
Connections:
Operating Temperature:
Storage Temperature:

275mm, 44mm (1U), 104mm


0.55kg
Mini combicon to accept 1.5mm csa wire.
-25 to +55C
-50 to +85C

Versions
SM11-12:
SM11-24:
SM11-48:

12V
24V
48V

Accessories
Temp Sensor:

ACA-TC2U:

ACA-TC7U:
Rectifier Interface:

ACA-Alarm0.5:
Current Sensor:

ACS-S150:

2 metre temp sensor and cable.


7 metre temp sensor and cable.
500mm RJ45 patch cable.
150 Amp 100mV shunt assembly.

FAN CONTROLLER BOARD


- Uses the SM3X temp sensor

The optional fan controller module allows the smart control of four 24V or 48V

fans with fan stall detection.

to control fan speed.

- Individual minimum fan speed


configurable to prevent fan stall.

- 4x fans controlled per module


and up to 2x modules per system.

Up to two fan controller modules can be connected in a system, giving a total of


8 controlled fans. Each module operates individually and has separate settings,
so can have different temperature set points and operate at different speeds.
The fans on one module all operate at the same speed.

50 | ENATEL | 2010 PRODUCT CATALOGUE

Input Voltage Range:


Fan Voltage:
Maximum Fan Current:

16-75V DC
12V, 24V, 48V & 60V DC
300mA maximum per fan connection.

Number Of Fans Controlled:


Number Of Modules On Bus:
Temperature Control Range:
Communications:
Alarms:

4x per fan controller module. (8x per system)


2x per system.
The range of the SM3X temp sensor.
Enatel serial bus interface.
Controlled via SM3X fan fail.

Dimensions, W, H, D:
Weight:

90mm, 67mm, 25mm


61g

Part Number:
Fan Controller Board:

ASM-FCM4

BATTERY CONDITION MONITOR


The Enatel BCM consists of peripheral circuit boards that can be added to an

- Compatible with SM22, SM32

Enatel system utilizing the SM22, SM32 or SM36 supervisory module to monitor

the performance of the installed stand-by battery system.

- 26 voltage inputs.

or SM36 supervisory modules.

- 8 pairs of current inputs.


The monitor is designed to be connected to a number of different battery
configurations with minimal changes to its configuration.
The BCM includes the capability to log battery parameters during discharge
and on a periodic time basis.

- 4 temperature inputs.
- Discharge logging.
- Periodic logging.
- Ease of installation.
- Compact design.

Voltage Resolution:
Voltage Accuracy:
Current Resolution:
Current Accuracy:

0.01V
0.02V
1A
2A

Temperature:

2C (standard sensor, upgraded sensor available for 1C)

Standard Configurations:



4
8
1
1
8

Communications:

Enatel serial bus interface.

Alarms:




Controlled via SM22, SM32 or SM36.


Voltage symmetry fault. (based on deviation from average string block measurement)
Battery current imbalance. (based on deviation from average string current across all strings in system)
Battery temperature high.
Battery temperature low.
Battery string open. (detects string voltage deviation from system DC bus to conclude battery is disconnected from system)

Data Logging:

SM22:

SM32:

Utilization of supervisory module memory:


15,500 data points.
196,000 data points.
Actual number of discharge events stored depends on frequency of discharges, logging interval and parameters measured.

Mechanical
Dimensions, W, H, D:
Weight:

80mm , 145mm, 27mm


100g

Part Number
Battery Condition Monitor:

ASM-ABM-24

strings, 4 voltage measurements per string. (requires 1x PCB)


strings, 2 voltage measurements per string. (requires 1x PCB)
string, 24 voltage measurements per string. (requires 1x PCB)
string, 12 voltage measurements per string. (requires 1x PCB)
string, 4 voltage measurements per string. (requires 2x PCBs)

AC MAINS MONITOR
The AC mains monitor can be added to the SM range of supervisory modules if

- Compatible with SM range

AC supply metering is required.

of supervisory modules.

- Ease of installation.
- Compact design.
Communications:

Enatel serial bus interface.

Alarms:



Controlled via SM21, SM22, SM31, SM32, SM35 or SM36.


Voltage phase high, voltage phase low, voltage phase lost.
(separate alarms for each phase).
AC phase current high. (common alarm for all phases)
Frequency high, frequency low.

Mechanical
Dimensions, W, H, D:
Weight:

145mm, 15mm, 85mm


61.5g

Part Number
AC Mains Mointor:

ASM-AC3P
ENATEL | 2010 PRODUCT CATALOGUE | 51

FTTX POWER SOLUTIONS


EPON INFRASTRUCTURE

SOHO / RESIDENTIAL APPLICATIONS

Enatel have recognised the need for DC Power Supplies specifically sized

The SOHO (Small Office/Home Office) and residential market is going to have

for Fibre to the Home requirements and developed a range of standalone and

the largest requirement for DC systems. If the customer premise is fitted

modular rectifiers and Micro Compact Power Shelves to suit every application

with alarms, nurse call or any other monitored device they will need a battery

within the FTTX environment. Be it Central Office or Customer Premise we

backed DC supply to ensure communication is available during an AC outage.

have the power solution to fit.


Enatel have two solutions to suit these applications:

CENTRAL OFFICE APPLICATIONS

nSURE NS300-12

Experience shows that the majority of Central Office OLT units have a power

For the SOHO Client Enatels nSURE NS300-12 can provide long term

consumption of up to 1600W.

backup for all their communications needs.

Enatels Micro Compact Power System is perfect for this application having

SOHO (Small Office/Home Office) clients with security systems will need

3 x 800W rectifiers gives an N+1 redundancy solution, built in distribution

Enatels nSURE NS300-12 power supply. Couple into this the ONU, Security

and full configured Supervisory Module.

system, residential gateway and wireless router and it can be business as


usual from a laptop during an AC outage. The NS300-12 is wall mountable

OFFICE / APARTMENT APPLICATIONS

and convection cooled making it ideal for office locations.


- 12V, 300W output.

These ONTs range in power consumption from 60W to 500W, typically have

- Mains fail alarm.

dual DC feeds and are 19 rack mountable.

- Convection cooled.
- Wall mountable.

Enatels Micro Compact range with 200W and 400W modules are purpose

- Automatic float/boost charge cycle.

built for this application, giving optimum power output with space for

- Power factor corrected.

redundancy and standby battery recharge in the event of an AC failure.

- Thermally protected.

MICRO COMPACT POWER SYSTEM

- Input/output voltage and current protected.

nSURE NS30-12
Enatels new range of Micro Compact Power Systems utilize Enatels
intelligent controllers and modular rectifiers. With rectifier output ratings

To suit the residential needs Enatel offers the nSURE NS30-12 (with

of 200, 400 and 800W and Supervisory modules capable of Ethernet

integrated battery) for basic autodialer backup functionality.

communication as standard these 1U power shelves are ideal for FTTX


solutions. They offer output power in line with the OLT /ONU usage and

For home owners with alarm auto dialers FTTH means their alarms will not be

have the capacity for N+1 redundancy. With various output distribution

monitored in the event of an AC Outage. Enatels nSURE NS30-12 provides

options they cater to all the requirements of this growing market.

battery backed power to the ONU even when the lights go out. Security or
Nurse call devices will operate as normal.

- Micro compact size means more room


for revenue generating equipment.

- Telecom grade 12V DC (30W max.) output.

- World leading power density.

- Up to 8 hours* of standby battery backup.

- Fully featured telecom grade rectifiers.

- Flexibility of wall or desktop mount.

- Network monitoring available.


- Modular 19/515mm ETSI design for ease of installation.
- High reliability means less cost of maintenance.
- Full remote monitoring available

means less site visits and less cost.

- Easily customized and configured to


- Easy user replaceable battery without power interruption.


- Microprocessor based intelligent control.
- Cold start capable.
- Local audible and visual indicators with remote alarms.
- Optional extended runtime.

suit each customers individual needs.

AC POWER SOLUTIONS
As some FTTX equipment is AC powered Enatel can also offer integrated
DC-AC Inverters, this allows for a telecommunications grade UPS (Long
backup times) on the entire FTTX system. The Inverters are monitored and
controlled through the same controller as the rest of the DC Power system.
Enatel can supply the complete solution in a wall mount cabinet or ready to
integrate into the OLT/ONU mounting system.
52 | ENATEL | 2010 PRODUCT CATALOGUE

nSURE 1U MICRO COMPACT SYSTEM 0.8 - 2.4KW 48V DC


AC Input:

Single phase.

AC Current:

170V AC, 15.0A max. 230V AC, 11.1A nominal.

(refer to RM8xx, series brochures for full details)

Frequency Range:

45-66Hz

Power Factor:

>0.99 (full load)

Termination:

Single phase, 1.5m flying lead.

48
2.4

nominal output voltage.

DC Output
Nominal Voltage:

-48V

Rated System Output Power:

2400W max. (50A @ -48V; 44.4A @ -54.0V)

Polarity:

Positive earth. (negative earth available to special order).

kW

maximum output power.

DC Distribution:

Load:

2x 10A, 2x 20A load circuit breakers.

Battery:

2x 30A battery circuit breakers.


Supervisory Module

SM36

Breaker Fail Detection:

RM848

RM848

RM848

Electronic fail detection on both load and battery breakers.

DC Terminals (Front Connected):


Load:

6mm push-in spring cage.

Battery:

55A power-pole plug-in connectors..

Low Voltage Disconnect:

50A battery LVD (magnetically latching) fitted as standard.

Mechanical
Dimensions, W,H,D:

482.6mm (standard 19 module), also fits

ETSI 515mm mounting cabinet, 44.45mm (1U, 1.75), 285mm (11.6)

Weight:

5kg (excluding rectifier modules)

Shipping Dimensions, W,H,D: 540mm, 95mm, 400mm


Weight:

6kg (excluding rectifier modules)

Monitoring & Control:

Various monitoring options are available via the Enatel SM35/36 series

of control & supervisory modules. Standard features include full

temperature compensation, automated and manual battery testing/

equalisation, 6x general purpose inputs and 6x voltage-free relay alarm

outputs. For further details, refer to the SM35/36 series of brochures.

Accessories
ACA-BC08P2:

2m, 8mm battery cable kit. (other lengths available to special order)

Part Numbers:

Actual part numbers will vary with configuration.

PSX1606211F-000:

Micro compact system, 2x 800W 48V rectifiers, 6x load

2x battery MCBs, front termination, SM35 supervisory module.

PSX1606221F-000:

Micro compact system, 2x 800W 48V rectifiers, 6x load

2x battery MCBs, front termination, SM36 supervisory module.

PSX2404211F-000:

Micro compact system, 3x 800W 48V rectifiers, 4x load

2x battery MCBs, front termination, SM35 supervisory module.

PSX2404221F-000:

Micro compact system, 3 x 800W 48V rectifiers, 4x load

2x battery MCBs, front termination, SM36 supervisory module.


ENATEL | 2010 PRODUCT CATALOGUE | 53

nSURE NS300-12

12
300
V

nominal output voltage.

maximum output power.

54 | ENATEL | 2010 PRODUCT CATALOGUE

AC Input
Nominal:
Voltage Range:

Frequency Range:
Power Factor:
Efficiency:
Input Fuses:
Maximum Input Current:
Protection:

Input Voltage:


Input Rush:
DC Output
Nominal Voltage:
Rated Voltage:
Voltage Range:
Maximum Current:
Regulation:

Line:

Load:
Hold-up Time:
Start-up Time:
Protection:

Current Limit:

Over Temp:

Polarity Reversal:

Over Voltage:
Noise: (under nominal conditions)

Ripple <100Hz:

Voice Band 100Hz to 5KHz:

Wide Band 5kHz to 1 MHz:

Peak to Peak 0 to 20MHz:
Isolation:

Input to Output:

Input to Chassis:

Output to Chassis:

Environmental Requirements
Nominal Ambient Temperature:
Range:
Humidity:
Altitude:

110/220V, 50/60Hz
100-275V AC (full power output),
85-100V AC (reduced power output)
45-66Hz
>0.99 (full load)
85%
HRC Fuses in phase & neutral.
4A
Automatic shutdown,
restarts automatically when correct voltage restored.
<2x maximum input current.

12V
14.5V
11.5-15V
20A
0.1%
0.5% (no load to full load)
>15ms for 20% output voltage drop.
Walk-in delay 2 seconds (depends on AC input voltage)
Adjustable to 50-100% of maximum rated current.
Automatic current turndown, backup shutdown protection.
Output fuse with crowbar diode.
Adjustable limit.
<5mV rms unweighted.
<0.5mV rms psophometric.
<2.5mV rms unweighted.
<50mV p-p unweighted.
3000V AC
2500V AC (VDR to chassis removed.)
1500V AC

25+/-5C
-10 to +60C
5-95% RH (non-condensing)
<2500m de-rate maximum ambient temperature
by +4 per 1000m above sea level.

Mechanical
Dimensions, W, H, D:
Weight:
Shipping Dimensions, W, H, D:
Shipping Weight:
Cooling:
Connections:

Mains:

Output to Load:

Output to batteries:

IEC 320 universal connection.


4 way lumberg macromodule.
4 way lumberg macromodule.

Standard Features
Auto Float/Boost:











Alarm and Indicator Controls:

Rectifier enters boost mode at power up.


When battery current reduces to float threshold limit (adjustable from
0.1A to 40% MRC), unit reverts to float voltage setting. When in boost
but out of current limit, rectifier will automatically switch back to float
after approximately four hours.
If battery current exceeds the float threshold limit when the rectifier is
in float mode it will automatically switch to boost mode.
Open collector rectifier fail (via 4k7 resistor), Open collector mains fail.

Compliances:

Safety: EN60950

Electrostatic Discharge:

Radiated Radio Frequency:

AC Harmonics:

AC Flicker and Fluctuation:

CISPR24
CISPR22
EN61000-3-2
EN61000-3-3

311mm, 163mm, 62mm


1.5kg
377mm, 235mm, 122mm
2.4kg
Convection cooled.

nSURE NS30-12
Input
Nominal Input Voltage:

120V AC/230V AC

Voltage Range:

80-260V AC

Frequency Range:

45Hz-65Hz

Plug Type: IEC inlet.

Output
Output Power (Max):

30W/2.2A

Normal Voltage:

12V DC

Output Voltage Range:

10.5-13.8V DC

Line Mode Efficiency:

>80%

12
30

nominal output voltage.

maximum output power.

Plug Type: 7pin terminal strip. (2 * DC output, 5 * dry contact alarms)

Battery
Type/Rating:

12V/7Ah x 1pc (12V/9Ah option)

Discharge Prevention:

10.5V 0.5V

Rated Charging Voltage:

13.7V 0.25

Recharge Time (Internal Battery):

4 hours to 90% without load after discharge.

Charge Current:

2.5A maximum.

Hot Swappable Battery:

Yes.

Indicators
AC Mode:

Solid green LED.

Backup Mode:

Solid yellow LED.

Battery Low:

Flashing yellow LED.

Battery Replace:

Flashing red LED.

Battery Missing:

Flashing red LED.

Fault:

Flashing red LED.

Battery Self Test:

Flashing green LED.

Audible Alarm
Backup Mode:

5 seconds.

Battery Low:

1 second.

Battery Replace:

2 seconds.

Battery Missing:

Continuous.

Fault:

Continuous.

Mute Function:

Switch. (on/off)

Environment
Operating Temperature:

0 to 40C

Operating Humidity:

0 to 90%

Operating Elevation:

0 to 3000m

Physical
Dimensions, W, H, D:

212mm, 216mm, 87mm

Weight:

4.0Kg
ENATEL | 2010 PRODUCT CATALOGUE | 55

INDUSTRIAL SOLUTIONS
- World leading power density.

Based on our proven range of modular telecom power solutions, we have

- Fully featured telecom

developed a range of solutions for use in 110V DC industrial applications.

grade rectifiers.

- Network monitoring available.

Systems are configured using Enatels state of the art high frequency switch

- Modular 19 design for ease

mode rectifier modules, intelligent network capable controllers, AC & DC

of installation.

- Includes AC surge protection.


- More room for revenue

creating equipment.

- Upgrade existing systems


to higher power.

- High reliability means less cost


of maintenance.

- Full remote monitoring available


means less site visits and less cost.

- Cost competitive.
- Suitable for more harsh

environments.

56 | ENATEL | 2010 PRODUCT CATALOGUE

distribution modules, and cabinets, and can be customized and configured to


meet individual customer requirements.
For details on a Enatel power system that meets your requirements contact us.

2U ULTRA COMPACT SYSTEM 3.0 - 6.0kW 110V DC


AC Input:

Single phase 90 300V AC

AC Current:

38A max / Ph (Ph-N) (refer to RM30110 brochure for full details)

Frequency Range:

45-66Hz

Power Factor:

>0.99 (full load)

Termination:

Single phase, 16mm2 L, N, E tunnel terminals at rear.

Single phase surge protection. (40kA, 8/20 sec)

110
6.0

nominal output voltage.

kW

DC Output
Nominal Voltage:

121.5V

Rated Voltage:

80-155V DC

Rated System Output Power:

6.0kW max @ 121.5V DC (50A)

+60V / -60V

maximum output power.

Supervisory Module

SM34

Polarity:

AC
Input

Load

Battery

ULTRA

compact

HV

DC Distribution:

Load:

1x 63A 2 pole load MCB (breaks +ve & -ve)

35mm tunnel terminals at rear.

1x 63A 2 pole battery MCB (breaks +ve & -ve)

Battery:

35mm tunnel terminals at rear.

Breaker Fail Detection:

Auxiliaries on both load and battery breakers.

Earth Leakage Detection:

Configurable via software, factory set at 25mA

Mechanical
Dimensions, W, H, D:

482.6mm (standard 19 module), 89mm (1U, 3.5), 415mm (16.3)

Weight:

7.5kg (excluding rectifier modules)

Shipping Dimensions, W, H, D: 530mm, 154mm, 430mm


Weight:

9kg (excluding rectifier modules)

Monitoring & Control:

Various monitoring options are available via the Enatel SM33/34 series of

control & supervisory modules. Standard features include full temperature

compensation, automated and manual battery testing/equalisation and

three voltage-free relay alarm outputs.

Part Numbers:

Actual part numbers will vary with configuration.

PSC06021130-000:

2U HV Ultra Compact Power System

including standard SM33 supervisory module.

PSC06021140-000:

2U HV Ultra Compact Power System

including standard SM34 supervisory module.


ENATEL | 2010 PRODUCT CATALOGUE | 57

WALL MOUNT BATTERY CHARGER 3.0kW 110V DC

110
3.0
nominal output voltage.

maximum output power.

kW

AC Input:

Single phase with surge protection and input 32A MCB

(refer to rectifier brochure for full details)

Frequency Range:

45-66Hz

Power Factor:

>0.99 (full load)

Termination:

Single phase. Direct MCB termination for L. 10mm N, E tunnel terminals.

Max Rated System


Output Power:

110V (80-155V DC)

3000W @ 120V DC, 27A max.

Polarity:

Isolated output. 1x RM30110 3000W rectifier.

DC Distribution:

Load:

1x 63A 2 pole MCB.

Battery:

1x 63A 2 pole MCB.

Breaker Fail Detection:

Auxiliaries.

DC Terminals:

Live: Direct MCB connections.

Weight:

Approx. 10.5Kg

Dimensions, D, H, W:

620mm x 375mm x 80mm

Shipping Dimensions, D, H, W: 730mm x 470mm x 200mm

58 | ENATEL | 2010 PRODUCT CATALOGUE

Monitoring and Control:

Various monitoring options via the Enatel SM30 series of control &

supervisory modules. Standard features include full temperature

compensation, automated and manual battery testing/equalisation

and three voltage-free relay alarm outputs. For further details,

refer to the SM30 series of brochures.

Part Numbers:

Actual part numbers will vary with congifuration.

PSW-3111030-000:

Wall mount charger including standard SM33 supervisory module.

PSW-3111040-000:

Wall mount charger including standard SM34 supervisory module.

RM30110 3.0KW 110V DC MODULAR RECTIFIER


AC Input
Nominal:
Voltage Range:
Frequency Range:
Power Factor:
Efficiency:
Input Fuses:
Maximum Input Current:
Protection:

Input Voltage:

Input Inrush:

230V
90-300V (reduced power below 175V)
45-65 Hz
>0.99
>92% (>45% output power)
HRC fuses in phase and neutral.
19A
Auto shutdown, auto restart when correct voltage restored.
<2x maximum input current.

DC Output
Output Ratings:

Constant Current:
80-110V DC (27.3A)

Constant Power:
110-155VD C (3.0kW)

Nominal Voltage:
120V

Rated Voltage:
145V

Voltage Range:
80-155V

Maximum Current:
27.3A
Regulation:

Line:
0.1%
0.5% (no load to full load)

Load:
Hold-up Time:
>15ms for 20% output voltage drop.
Start-up Time:
Start up delay 1 second. (varies with AC supply voltage)

Walk-in delay 6 seconds at full output. (varies with DC output voltage)
Protection:

Current Limit:
Adjustable to 50-100% of maximum rated current.
Automatic current turndown, backup shutdown protection.

Over Temperature:

Polarity Reversal:
Output fuse with crowbar diode.

Over voltage:
Adjustable limit.
Noise: (under nominal conditions)

Ripple <100Hz:
<1mV rms unweighted.

Voice band 100Hz-5KHz: <2mV rms psophometric.

Wide band 5kHz-1MHz: <5mV rms unweighted

Peak to Peak 0-20MHz: <200mV peak to peak.
Isolation:

Input to Output:
4000V DC

Input to Chassis:
3500V DC (VDR to chassis removed)

Output to Chassis:
2100V DC
Environmental Requirements
Ambient Temperature:

Nominal:

Range:
Storage Temperature:
Humidity:
Altitude:

110
3.0
27.3

nominal output voltage.

kW

nominal output power.

maximum output current.

25+/-5C
-10C to +70C (maximum output power is derated above +50C)
-20C to +70C
5-95% RH (non-condensing)
<2500m, De-rate maximum ambient temperature
by 4C per 1000m above sea level.

Mechanical
Dimensions, W, H, D:
41mm, 220mm, 305mm overall.
Weight:
2.8kg
Shipping Dimensions W, H, D: 52mm, 230mm, 340mm
Shipping Weight:
2.95kg
Cooling:
Forced cooled, using dual temperature controlled high reliability fans.
Compliances
Safety:
Electrostatic Discharge:
Radiated Radio Frequency:
AC Harmonics:
AC Flicker and Fluctuation:

EN60950
CISPR24
CISPR22
EN61000-3-2
EN61000-3-3

Other:

CE & RoHS compliant.


ENATEL | 2010 PRODUCT CATALOGUE | 59

SM34 SUPERVISORY MODULE

LVD
WEB
USB
dual lvd control.

web based configurator.

usb port for local connection.

Input
Voltage:

80-160V DC

Current:

<50mA maximum.

Interface
Display:

4 line x 16 character multi-lingual alpha numeric display.

Communications:

Serial:

1x USB port on front panel for local PC interface.

1x RS232 port, rear mounted for remote serial/modem communications.

3x alarm and control relays, two of which

Relay:

can be mapped for customized alarm settings.

TCP/IP:

Ethernet interface for communication using SNMP

protocol and internal web based configurator.

LVD:

3x standard or 2x pulse control LVD contacts.


(for magnetically latched LVD contactors)

Indicators:

3x LEDs

Green - power on/monitor OK.

Yellow - non urgent alarm.

Red - urgent alarm.

90dBA buzzer mappable to user defined conditions.

Audible:

Controls:

3x push buttons for parameter setting or viewing on front panel.

Signal Inputs:

Serial bus for rectifier control and interface to peripheral modules.

Fuse fail.

5x spare digital inputs.

2x temperature sensors.

3x current shunts.

2x DC voltage inputs.

Alarms:

3x alarm relays.

Alarm Contacts:

0.3A 100V volts free changeover contacts or

0.15A 160V volts free changeover contacts.

Default Alarm Map:

Urgent.

Non-urgent.

Monitor fail.

Logging Capacity:

Periodic Log:

16384 records. (dependant on number of parameters logged.)

Event Log:

16384 records. (dependant on number of parameters logged.)

Physical
Dimensions, W, H, D:

111.5mm , 44mm (1U), 282mm overall (rack depth 260mm)

Weight:

1.5kg

Connections:

Relay outputs, mini combicon to accept 1.5mm csa wire.

Serial communications to rectifier shelf & peripheral devices - RJ45.

USB port - USB mini B.

Operating Temperature:

-25 to +55C

Storage Temperature:

-50 to +85C

Compliances
Radiated Emissions:

EN55022

RF Susceptibility:

EN55024

Optional Accessories
ACA-TC3C:

3m temperature sensor and cable.

ACA-TC3C:

7m temperature sensor and cable.

ASM-AC3P110:

3 phase AC voltage and current monitor.

ASM-ABM-24:

Battery condition monitor, 24 blocks. (maximum 4x BCM cards.)

Part Numbers

60 | ENATEL | 2010 PRODUCT CATALOGUE

SM34-00:

Standard 1U modular controller, 3x relays, 6x digital inputs.

SM34-00-1U:

Standard 1U x 19 mounting version controller, 3x relays, 6x digital inputs.

SM34-00-PM:

Standard panel mount version controller, 3x relays, 6x digital inputs.

SM33 SUPERVISORY MODULE


Input
Voltage:

80-160V DC

Current:

<50mA maximum.

Interface
Display:

4 line x 16 character multi-lingual alpha numeric display.

Communications:

Serial:

1x USB port on front panel for local PC interface.

Relay:

3x alarm and control relays, two of which

can be mapped for customized alarm settings.

3x standard or 2x pulse control LVD contacts.

LVD:

(for magnetically latched LVD contactors)

Indicators:

3x LEDs

Green - power on/monitor OK.

Yellow - non urgent alarm.

Red - urgent alarm.

90dBA buzzer mappable to user defined conditions.

Audible:

Controls:

3x push buttons for parameter setting or viewing on front panel.

Signal Inputs:

2x serial buses for rectifier control and interface to peripheral modules.

Fuse fail.

5x spare digital inputs.

2x temperature sensors.

3x current shunts.

2x DC voltage inputs.

Alarms:

3x alarm relays.

Alarm Contacts:

0.3A 100V volts free changeover contacts or

0.15A 160V volts free changeover contacts.

Default Alarm Map:

Urgent.

Non-urgent.

Monitor fail.

126
LCD
USB

serial control for up to 126 rectifiers/


converters plus peripheral devices.

lcd display.

usb port for local connection.

Logging Capacity:

Periodic Log:

16384 records. (dependant on number of parameters logged.)

Event Log:

16384 records. (dependant on number of parameters logged.)

Physical
Dimensions, W, H, D:

111.5mm , 44mm (1U), 282mm overall (rack depth 260mm)

Weight:

1.5kg

Connections:

Relay outputs, mini combicon to accept 1.5mm csa wire.

Serial communications to rectifier shelf & peripheral devices - RJ45.

USB port - USB mini B.

Operating Temperature:

-25 to +55C

Storage Temperature:

-50 to +85C

Compliances
Radiated Emissions:

EN55022

RF Susceptibility:

EN55024

Optional Accessories
ACA-TC3C:

3m temperature sensor and cable.

ACA-TC7C:

7m temperature sensor and cable.

ASM-AC3P110:

3 phase AC voltage and current monitor.

ASM-ABM-24:

Battery condition monitor, 24 blocks. (maximum 4x BCM cards.)

Part Numbers
SM33-00:

Standard 1U modular controller, 3x relays, 6x digital inputs.

SM33-00-1U:

Standard 1U x 19 mounting version controller, 3x relays, 6x digital inputs.

SM33-00-PM:

Standard panel mount version controller, 3x relays, 6x digital inputs.


ENATEL | 2010 PRODUCT CATALOGUE | 61

62 | ENATEL | 2010 PRODUCT CATALOGUE

Copyright Enatel Limited 2010. Due to product development specifications are subject to change without prior notice. Pictures may be representative, actual products may differ.

321 Tuam Street


PO Box 22-333
Christchurch
New Zealand

Phone +64-3-366 4550


Fax +64-3-366 0884
Email sales@enatel.net
www.enatel.net

You might also like