Professional Documents
Culture Documents
Response Study
1. Introduction
In power system analysis and calculations, the accuracy of power system component
models directly affects the correctness of analysis and calculation results. In other hand,
the parameter precision of power system models also affects the quality of power system
analysis and calculations. Particularly, the dynamical models of power system require the
parameters more accurate than the static models. The modern power system industries
request not only the qualitative solutions but also the quantitative solutions for an
analysis case. For instance, the operators want the exact values of the current, voltage or
frequency at a special moment after a disturbance so as to determine the relays or control
devices settings. According to the experiences in practices, the erroneous of parameters
can severely impact the quality of analysis solutions. Once the model of a actual power
system is established, the verification and validation process of system model parameters
are indispensable before conduct case analysis. Generally, the parameters of system
models are obtained from manufacture data, measured data and estimated data. These
data may bring different types of errors on the parameters, such as: the manufacture data
may not be suitable to the complexities of models or the simplified models; the measured
data are subject to errors of metering system; and the estimated data may not be accurate.
In this presentation, a technology to tune up power system model parameters will be
illustrated, specially, about the tuning dynamical model parameters using site test record
data.
2. Verification and Validation of Power System Model Parameters
Power system models generally are classified as static-state models, like transmission
line, transformer and static load model, sand dynamical models, like generator,
turbine/governor, exciter/AVR and motor models. The parameters of static-state models,
like transmission line and transformer impedances, can be easily verified and validated
by comparing load flow analysis results against measured voltage, current and power data
at any time moment. But it is not so simple for the verification and validation of
dynamical model parameters, like governor and exciter transfer function time constants
and gains. First, these parameters do not have apparent one to one relationships with the
measurable data. Second, the response of a model to be matched with measured data is
not only a single point instead of a whole process corresponding to a system event such
as a load shed or a bus faulted. The shape and character of a response curve for a
dynamical model during an event reflect merely the group effects of the model
parameters. So it is difficult to quantitatively determine the individual parameter in a
model according to a response curve. However, under some conditions may a parameter
dominate certain character of the response curve, such as oscillation frequency,
overshooting magnitude, raising and falling rates. This characteristic of a dynamical
model can be utilized to tune the parameters of the power system dynamical models in
accordance with the measured responses of frequency, voltage and so on. The next
section will investigate the relationship between a parameter of a mode and the model
response process for some typical transfer function models.
Figure 3.4, when increasing time constant value, the raising rate and overshooting
magnitude of response will increase, but the falling rate during the decay segment will be
decreased, thus, the settle down time of response would last longer. When increasing gain
value, as shown in Figure 3.5, the raising rate and overshooting magnitude of response
also will increase, but the falling rate would not be changed.
Single Generator Power System Model: Figure 3.6 shows a simplified model of a
single generator power system. The block Ks and Kd are defined as system synchronizing
first start a generator unit, at the same time flash the generator field winding, when
generator terminal voltage reaches approximately 70% to 90% of rated output voltage,
then a voltage relay trips the appropriate circuit breakers and connect the emergency load
from the nuclear generation plant to the generator. The generator AVR and governor
models are shown as Figure 4.2 and 4.3. The typical parameters of the models are listed
in Table 4.1 and 4.2. When using the typical parameters in simulation study, as can be
seen from Figures 4.4, 4.6, 4.8 and 4.10, the responses of generator speed, voltage, power
and field voltage do not match the site test results. By investigating the response curves,
obviously, some transfer function time constants and gains of both AVR and governor
models and the generator damping and inertial coefficients need to be tuned up properly.
A set of modified model parameters are listed in Table 4.1 and 4.2. The responses of the
system corresponding to the parameter modifications show a very good match to the site
test results as displayed in Figures 4.5, 4.7, 4.9 and 4.11. In this project study, it is
discovered that the response of the motor start simulation will not correctly express the
real situation if the formula coefficients of motor load model are not presented properly.
The formula coefficients of motor load model usually can be obtained by using curve
fitting technology based on the load torque curve. In most cases, the manufacturers only
provide the load torque curves under the speed range from 0 to 100%. It is no problem to
simulate the motor start if the system frequency within this speed range. Otherwise, the
simulation results will not truly reflect the actual situations. In this test case, the generator
speed ever overshoots to 120% of rated speed at a period of time. Figure 4.13 shows the
response of a motor electrical power during start up have big discrepancy against the site
test result when using the load model with the speed range from 0 to 100%. When
remodeling the load torque curve covered the speed range to 120% as given in Figure
4.12, the response of the motor electrical power corresponding to the modified load
model shows a very good match to site test results as shown in Figure 4.14.
KGEN 1
KGEN 2
W/OMod#2
13.2kV Ke o#2
13.2kV Ke o#1
NO
Underground
CT4
U3 4kV bu s13
4kV B1TS
4kV B2TS
NO
3TD /E-3B1 T
3TC/D/E-3B2T
3TC/D/E-3B1T
B2TS-3B2T
B1TS-3B1T
NO
3TE-3B1T
3TC-3B2T
3TE-3B2T
3TD-3B2T
3TD-3B1T
3TC-3B1T
3TD /E-3B2 T
4k V 3T E
4k V 3T D
4k V 3T C
3PTD3
3PTC3
3PTE3
3E PTD1 3
3E PTE1 2
3E PTC1 3
HP IP-3 A
600 H P
LP IP-3 A
400 H P
RB SP-3 A
250 H P
LPSWP-3A
600 H P
TX-3X 4
TX-3X 8
TX-3X 9
TX-3X 5
EFDWP-3A
600 H P
600V LC 3X4
600V LC 3X8
MCC 3XS1
3X8 Test 1
3X8 Test 2
HP IP-3 C
600 H P
LP IP-3 B
400 H P
RB SP-3 B
250 H P
3X5 Test 2
EFDWP-3B
600 H P
LPSWP-3B
600 H P
600V LC 3X9
600V LC 3X5
3X5 Test 1
TX-3X 6
3X9 Test 1
3X9 Test 2
MCC 3XS2
TX -3X1 0
HP IP-3 B
600 H P
600V LC 3X6
3X6 Test 1
3X6 Test 2
600V LC 3 X10
MCC 3XS3
Parameter
RC
XC
TR
TC
TB
KA
TA
KF
TF
KC
VVLR
KVL
TVL
KVF
TH
VImax
VImin
VRmax
VRmin
Vdc
Rf
VHZ
TD
Vfb
Ifb
Vref
Typical
0.0
0.03
0.0
0.0
0.0
100
0.02
0.5
0.5
0.1
1.07
120.0
0.05
1.0
0.05
0.17
-0.17
3.66
0.0
125
0.15
0.74
2.5
87.5
585
1.025
Tuned
0.0
0.03
0.0
0.0
0.0
70
0.02
0.12
0.8
0.1
1.07
120.0
0.05
1.0
0.05
0.17
-0.17
3.66
0.0
125
0.06
0.74
2.5
87.5
585
1.025
Parameter
Typical
Tuned
TP
0.04
0.04
Q
1
1
GC
2.5
2.5
TG
1
1.41
RP
0.02
0.02
RT
0.4
0.4
TR
5.5
7.5
H
7
4.94
D
2
1.1
2* EPC6 A
2E TA
NO
FP CP-2 A
200 H P
NO
NO
NS WP-2 A
10 00 H P
AF WP-2 A
500 H P
4. 16 k V
NO
NO
NO
CCHRGP- 2A SIP-2 A
600 H P
400 H P
NO
NO
RH RP-2 A
400 H P
CSP-2 A
400 H P
NO
CC P-2A 2
200 H P
CC P-2A 1
200 H P
2*EPE537
2*EPE538
2*EPE536
TX-2ELXE
1500 kVA
TX-2ELXA
TX-2ELXC
1500 kVA
1500 kVA
NO
NO
2ELXA
0.6 k V
2ELXC
NO
MCC-2EM XE
MCC-BPH 2A
MCC -2EMXA 2
MCC-2EM XA
2ET AGenlo s
42.3 kVA
MCC-2EM XC
0.6 k V
2ETAXlos
0.031 M VA
Parameter
KA
KC
KE
KF
KI
KP
TA
TE
TF
TR
Vrmax
Vrmin
Typical
156
0.001
0.08
0.1
9
0.08
0.05
1.0
3.0
0.005
17.5
-15.5
Tuned
240
0.001
0.08
0.27
9
0.08
0.05
4
3.0
0.005
17.5
-15.5
Parameter
Droop
ThetaMax
ThetaMin
Alpha
Beta
Rho
K1
Tau
T1
T2
H
D
Typical
5.0
60.0
4.0
0.04
0.02
0.1
128
0.1
0.15
0.12
1.9
4.0
Tuned
5.0
60.0
4.0
0.027
0.0192
0.3
119
0.09
0.151
0.12
1.69
7.0
respectively. As can be seen from Figure 4.25, the response of the system current and
voltage using tuned parameters are very close to the actual measured data.
Power Grid
Bu s1
65 kV
T3
12.5 MVA
CB4
Bu s2
Bus-B
3.3 kV
3.3 kV
CB6
LUMP2
LUMP4
10.75 MVA 10.75 MVA
52 B4
Bus-A
3.3 kV
CB5
52 GH
LUMP3
LUMP1
4.458 MVA 5.848 MVA
Bu s3
Bu s4
3.3 kV
3.3 kV
pump5
345 kW
pump4
pump3
83.175 kW 937 kW
pump2
pump1
G4
73.936 kW73.936 kW 15.111 MW
Parameter
Xd
Xq
Xd
Xq
Xd
Xq
Td0
Tq0
Td0
Tq0
H
D
Typical
1.48
1.48
0.215
0.45
0.136
0.136
7.05
1.0
0.042
0.18
5.4
5
Tuned
0.75
0.74
0.15
0.16
0.12
0.13
7.05
1.0
0.042
0.18
8
1