2) Assemble the orifice and valve body and install into system
T2 type expansion valves are designed for flare connections. To make a functioning valve,
pair the appropriate valve body and orifice using the charts below.
IF THE EXACT SYSTEM CAPACITY CANNOT BE FOUND, USE THE NEXT LARGER ORIFICE.
R22
Valve Body
TX 2
068Z3206
TEX 2
068Z3209
Orifice
Size
Code
Number
45
0x
068-2002
00
068-2003
01
068-2010
02
068-2015
1/10
1/8
1/6
1/4
1/2
3/4
1
03
068-2006
04
05
06
068-2007
068-2008
068-2009
3
4
5
Orifice
Size
Code
Number
45
0x
068-2002
00
068-2003
01
068-2010
02
068-2015
03
068-2006
35
25
0
-10 -20 -30
Rated Capacity in Tons (TR)2
1/10 1/10 1/10 1/10 1/10 1/10
1/8 1/8 1/8 1/8 1/8 1/8
1/6 1/6 1/6 1/6 1/6 1/6
1/4 1/4 1/4 1/4 1/4 1/4
1/2 1/2
1/2 1/2 1/2 1/4
3/4 3/4
1
1
3/4 3/4 3/4 1/2
1
3/4
2
2
1
1
1 1/2
1
3
3
2
2
2 1 1/2
4 3 1/2 3 2 1/2 2 1/2 2
5 4 1/2 3 1/2 3
3 2 1/2
R404A / R507
1
Valve Body
TS2
068Z3400
TES 2
068Z3403
Valve Body
35
25
0
-10 -20 -30
Rated Capacity in Tons (TR)2
1/10
1/10 1/10
1/8
1/6 1/8 1/8
1/4 1/6 1/6
1/4
1/2
1/4
1/2
3/4 1/2 1/2
3/4 3/4
1
1
1
068-2007
05
06
068-2008
068-2009
2 1/2
3
2
3
Orifice
Size
Code
Number
45
35
0x
068-2002
00
068-2003
01
068-2010
1/2
02
068-2015
3/4
03
068-2006
04
05
06
068-2007
068-2008
068-2009
2
2 1/2
3
26-33 ft-lb
(35-45Nm)
1/4
1/2
3/4
1
1 1/2
2
2 1/2
-40
Superheat Adjustment
1) Remove the cap.
2) Make superheat adjustments turn at a time (1 turn=7F). Turning clockwise
increases superheat. Turning counter-clockwise decreases superheat.
3) Reinstall the cap.
1/8
1/6
1/8
1/6
1/8 1/10
1/6 1/8
1/4
1/4
1/4
1/4
1/6
1/2
1/4
1/2
3/4
1/4
1/4
1/4
1/2
1/2
1/2
3/4
3/4
1 1/2 1
1
3/4
1
2 1 1/2 1 1/2 1
1
2 1/2 2 1 1/2 1 1/2 1
04
Torque Requirements
3/4
1
1
1/10
1/8
1/6
1/4
R134a
TN 2
068Z3346
TEN 2
068Z3348
1/10
1/8
1/6
1/4
25
0
-10 -20 -30
Rated Capacity in Tons (TR)2
1/10 1/10
1/10 1/10 1/10 1/10
1/8 1/8
1/6 1/6 1/6 1/6
1/6 1/6
1/8 1/8 1/8 1/8
1/4
1/4 1/4 1/4 1/4 1/6
1/2
1/2 1/2 1/2 1/4 1/4 1/4
1/2
3/4 1 3/4 1 3/4
1/2 1/2
3/4
1 1/2 1 1/2 1
1
3/4 3/4
2
2 1 1/2 1
1
1
2 1/2 2 1/2 2 1 1/2 1 1/2 1
-40
1/10
1/6
1/8
1/6
1/4
1/2
3/4
1
1
Valve Body - Internal: 3/8" X 1/2" ODF - External: 3/8" X 1/2" w/ 1/4" ODF Equalizer
Capacities are based on a condensing temperature of 90 F and a vapor free liquid temperature of 80 F ahead of the expansion valve.
DANFOSS CODE
R22
REFRIGERANT
R404a
R134a
CAPACITY IN KW
T2-0X
T2-00
T2-01
T2-02
T2-03
T2-04
T2-05
T2-06
068-2002
068-2003
068-2010
068-2015
068-2006
068-2007
068-2008
068-2009
0.5
1
2.5
3.5
5.2
8
10.5
15.5
0.38
0.7
1.6
2.1
4.2
6
7.7
9.1
0.4
0.95
1.8
2.6
4.6
6.7
8.6
10.5
T5-01
T5-02
T5-03
T5-04
067B2089
067B2090
067B2091
067B2092
19.7
26.9
38.8
55.3
13
17.6
25.3
36.2
12.9
19.1
29.1
39.6
T12-01
T12-02
T12-03
T12-04
067B2005
067B2006
067B2007
067B2008
26.8
43.4
64
84.4
14.8
23.9
35.2
47.1
16.7
27.2
40
53
T20-01
T20-01
T20-01
067B2170
067B2172
067B2175
108
108
108
59
59
59
65
65
65
T55-01
T55-02
067G2001
067G2002
239
356
130
197
145
220
TUA-00
TUA-01
TUA-02
TUA-03
TUA-04
TUA-05
TUA-06
TUA-07
TUA-08
TUA-09
068U1030
068U1031
068U1032
068U1033
068U1034
068U1035
068U1036
068U1037
068U1038
068U1039
0.6
0.9
1.3
1.8
2.6
3.5
5.3
7
11
16
0.47
0.7
1
1.4
2.1
2.8
4.2
5.6
8.4
12
0.47
0.7
1
1.4
2.1
2.7
4.1
5.5
8.2
12