INTRIDUCTION
This proposal, as required by Panasonic Appliances Air-Conditioning Malaysia Sdn. Bhd. Is to
supply and install 10-15m3/h Wastewater Treatment Plant at Panasonic Appliances AirConditioning Malaysia Sdn. Bhd. No.17, Jalan Puchong, Taman Perindustrian Subang Utama,
Seksyen 22, 40300 Shah Alam, Selangor D.E. This wastewater treatment plant is proposed by
Chemkimia Sdn. Bhd., which hereby the contractor responsible for the system.
OBJECTIVE
The wastewater treatment plant is designed to treat additional wastewater from factory due to
increase in production line (shifting from MCM-PJ) in order to meet the Third Schedule
Environment Quality Act 1974, Environmental Quality (Sewage and Industrial Effluents)
Regulations 1979, Parameter Limits of Effluent of Standard B.
Raw
Chemical
treatment & DAF
System
Biological
System
Carbon Adsorption
& Membrane
Filtration
Effluent
Sludge for
disposal
Sludge Dewatering
DESIGN CRITERIA
: 10-15 m3/h
Design operation
Design parameter
Parameter
pH
COD, mg/L
BOD (5 days, 20 deg)
TSS
Mercury (as Hg)
Cadmium (as Cd)
Chromium hexavalent
Arsenic
Cyanide
Lead
Chromium trivalent
Copper
Manganese
Nickel
Tin
Zinc
Boron
Iron
Phenol
Free chlorine
Sulphide
Oil & grease
Unit
mg/L
mg/L
mg/L
mg/L
mg/L
mg/L
mg/L
mg/L
mg/L
mg/L
mg/L
mg/L
mg/L
mg/L
mg/L
mg/L
mg/L
mg/L
mg/L
mg/L
mg/L
Raw water
05/12/07
9.06
760
310
93
0.002
ND(<0.01)
ND(<0.02)
ND(<0.01)
ND(<0.01)
ND(<0.01)
ND(<0.02)
0.36
2.34
0.21
ND(<0.01)
0.43
12.4
2.66
0.1
ND(<0.1)
ND(<0.2)
34
Standard
B
5.5-9.0
100
50
100
0.05
0.02
0.05
0.10
0.10
0.5
1.0
1.0
1.0
1.0
1.0
2.0
4.0
5.0
1.0
2.0
0.50
10
PROCESS DESCRIPTION
The variation of heavy metals and contaminants are observed in all influent wastewater.
In the consideration of treatment process fundamentals, it was assumed, for the purpose of
simplifying the analysis, that the influents are constant. If instead a variable influent is
substituted for the assumed constant value, it can be often be shown that because of the variation
in the influent involved, there may be deterioration in performance from the optimum value that
can be achieved. Equalization sump is used to overcome the operational problems caused by
these variations and to improve the performance of the downstream processes.
Thus all the waste water will be channel to the Equalization Sump prior to any treatment
process. The equalized wastewater is then transferred into the treatment plant by submersible
pump which is control by the sump water level. A flow meter is installed to measure the
pumping flow rate to the Oil and Grease Trap.
Oil and Grease Trap capture the oil and grease from the flow of wastewater by slowing down the
flow of greasy water through the grease trap and allowing it to cool. As it cools, the grease and
oil separate out of the water and float to the top of the trap. The cooler water continues to flow
down the drain pipe to the Coagulation Tank while baffles prevent the accumulated grease and
oil from flowing out of the grease trap.
In the Coagulation Tank, chemical coagulation is dosed in at constant dosage based on the
running of transfer pump. The pH in this tank will be maintained at correct pH in order to obtain
good formation of floc using caustic. Agitator is used to attain good mixing.
After the formation of fine floc, polymer will be added at constant dosage based on the running
of transfer pump to further agglomerate the fine floc. This will help to enhance the separation in
the next process. A slow/optimum speed agitator is used to attain good mixing while not
breaking the big floc formed.
Dissolved Air Flotation (DAF) is the process of removing suspended solids, oils and other
contaminants via the use of air bubble flotation. Air is dissolved into water, mixed with the waste
stream and released from solution while in intimate contact with the contaminants. Air bubbles
form, attach to the solids, increase their buoyancy and float the solids to the waters surface. A
percentage of the clean effluent and injected into the DAF separation chamber.
The dissolve air comes out of solution, producing millions of microscopic bubbles. These
bubbles attach to the solids and float them to the surface where they are mechanically skimmed
and removed from the tank. Dissolved air flotation systems are designed to remove fats, oil &
grease (FOG), suspended solids, food/animal production/processing wastes, industrial wastes,
hydrocarbon oils/emulsions and many other contaminants. Clarification rates as high as 97% or
more can be achieved using dissolved air flotation systems.
Effluent from the DAF will enter the Biological Aeration Tank where the organic matter will be
digested by the bacteria. Fine air bubble will be supplied by blower through air diffuser to
maintain the dissolve oxygen level in the tank.
After aeration process, water will be channeled to Sedimentation Tank where activated sludge
containing bacteria will settle and the supernatant will flow to the filtration process. The settle
sludge will be returned to Aeration Tank by using a RAS pump. In the occasion where MLVSS
is too high, part of the activated sludge will be removed.
Effluent from the Organic Settling Tank will enter this tank which is acts as a holding tank for
Activated Carbon Filter to ensure the smoothness of the operation in text process. This tank also
functions as the storage tank for the backwash usage.
Its function is to further clarify the effluent from biological system and to remove suspended
solid and dissolve organic matter. The suspended solid and dissolved organic are removed by the
passage of water in a down flow mode through carbon contained in a pressure vessel Automated
backwash sequence will be initiated by timer to remove the accumulated particles in the vessel
and recover its flowrate as well as preventing media hardening.
The filtered water from Activated Carbon Filter will be passed thru the CMF for further
polishing to remove fine suspended solid smaller than 0.2micron from the previous process, thus
producing crystal clear effluent.
The filtrate from the CMF will be pH adjusted (if necessary). If the pH reading is out of the
permitted range, it will be automatically returned back to the Equalization Sump. At the same
time, a flow meter with totalizer will be installed to display the flow rate and record the total
discharge treated water.
The waste sludge from the DAF will be transferred to this tank for further concentration. The
overflow from the Sludge Thickener Tank returns back to Equalization Sump.
An air diaphragm pump will pump the concentrated sludge from the bottom of the Sludge
Holding Tank to Filter Press for the dewatering process. The water from the dewatering process
will flow back to the Equalization Sump. The pressed sludge can be packed in sludge cloth bag
or metal container depends on the local authority requirement before sending for further
treatment or storage.
EQUIPMENTS SPECIFICATION
Equalization tank
Equalization tank
Dimension
Capacity
: 144m3
Material
Quantity
: 1 unit
EQ Pump
Type
: Submersible
Brand
: Goulds
Model
: GDOMO20T/B
Material
: Stainless steel
Capacity
Quantity
Level Switch
Type
: Ball float
Brand
: Faes
Material
: Plastic
Quantity
Flow meter
Type
Brand
: Burkert
Model
Quantity
Capacity
: 1.0m3
Brand
: Saint Dizier
Model
: IHDC 01/0
Material
: M/S
Quantity
: 1 unit
Coagulation tank
Coagulation tank
Dimension
: 2m 2m 1.5m
Capacity
: 6.0m3
Material
: FRP
Quantity
: 1 unit
Coagulation mixer
Type
: Top entry
Brand
: Daqchem
Model
: 50G-150
Capacity
: 1.1Kw/415VAC/290rpm
Material
Quantity
: 1 unit (MIX251)
pH meter
Type
Brand
: B&C
Model
: PH7685
Quantity
: 1 unit (PH271)
Flocculation tank
Flocculation tank
Dimension
: 2m 2m 1.5m
Capacity
: 6.0m3
Material
: FRP
Quantity
: 1 unit
Flocculation mixer
Type
: Top entry
Brand
: Daqchem
Model
: 50G-150
Capacity
: 1.1Kw/415VAC/290rpm
Material
Quantity
: 1 unit (MIX251)
: 1.5m 4m 3.5m
Capacity
: 21.0m3
Material
: SS304
Quantity
: 1 unit
Recirculation pump
Type
: Centrifugal
Brand
: Nijhuis
Model
: ZLK
Capacity
: 7.5kW/415VAC
Quantity
: 1 unit
Skimmer motor
Brand
: Nord
Model
: SK02050-AZD-63L/4
Capacity
: 7.5kW/415VAC
Quantity
: 1 unit
Air compressor
Type
: Piston-reciprocating
Brand
: Dancomair
Model
: PEC1202S
Capacity
: 1.5kW/240VAC/9bar
Quantity
: 1 unit
Sludge pump
Type
Brand
: Wilden
Model
: P4/AAPP/WF/WF/WF/014
Capacity
Material
Quantity
: 1 unit
: 7m 7m 4m
Capacity
: 196.0m3
Material
Quantity
: 1 unit
Sedimentation tank
Sedimentation tank
Dimension
: 4m 4m 3.5m
Capacity
: 40.0m3
Material
Quantity
: 1 unit
pH adjustment tank
pH adjustment tank
Dimension
: 1m 1m 1.2m
Capacity
: 1.2m3
Material
: FRP
Quantity
: 1 unit
pH meter
Type
Brand
: B&C
Model
: PH7685
Quantity
: 1 unit (PH271)
: 2.4mDia 2.4mH
Capacity
: 10m3
Material
: HDPE
Quantity
: 1 unit
Level Switch
Type
: Ball float
Brand
: Faes
Material
: Plastic
Quantity
: 1.219mDia 1.524mH
Capacity
: 1.78m3
Material
: M/S
Quantity
: 1 unit
: Submerged
Brand
: Memcor
Model
: CMF32S10T
Capacity
: 10-30m3/H
Membrane
: Polypropylene
Pore size
: 0.2micron
Quantity
: 1 unit
: 1.8mDia 2.15mH
Capacity
: 5.4m3
Material
: FRP
Quantity
: 1 unit
Flow meter
Type
Brand
: Burkert
Model
Quantity
: 1 unit (FM275)
Capacity
: 10m3
Material
: HDPE
Quantity
: 1 unit
Collection sump
Collection sump
Dimension
Capacity
: 6m3
Material
Quantity
: 1 unit
Sump pump
Type
: Submersible
Brand
: Goulds
Model
: GDOMO20T/B
Material
: Stainless steel
Capacity
Quantity
: 1 unit (PUM236)
Level Switch
Type
: Ball float
Brand
: Faes
Material
: Plastic
Quantity
Coagulant tank
Coagulant tank
Dimension
: 1.13mDia 1.17mH
Capacity
: 1.1m3
Material
: HDPE
Quantity
: 1 unit
Level Switch
Type
: Miniature float
Brand
: Nohken
Model
: OLV-2F 1000
Material
: PP
Quantity
Polymer tank
Polymer tank
Dimension
: 1.556mDia 1.22mH
Capacity
: 2.2m3
Material
: HDPE
Quantity
: 1 unit
Level Switch
Type
: Miniature float
Brand
: Nohken
Model
: OLV-2F 1000
Material
: PP
Quantity
Caustic tank
Caustic tank
Dimension
: 1.13mDia 1.17mH
Capacity
: 1.1m3
Material
: HDPE
Quantity
: 1 unit
Level Switch
Type
: Miniature float
Brand
: Nohken
Model
: OLV-2F 1000
Material
: PP
Quantity
Acid tank
Acid tank
Dimension
: 1.13mDia 1.17mH
Capacity
: 1.1m3
Material
: HDPE
Quantity
: 1 unit
Level Switch
Type
: Miniature float
Brand
: Nohken
Model
: OLV-2F 1000
Material
: PP
Quantity
Actipol tank
Polymer tank
Acid tank
Caustic tank
Pumps
1) For pump, ensure that the inlet and outlet valves are opened.
2) Do priming (for centrifugal pump) before run pump if previously has been
dismantled.
3) For the chemical dosing pumps, ensure outlet valves are opened and suction
pipe/hose are submerged in chemical solution.
Stirrers
1) Ensure that the liquid level in the tank is suitable to start stirrer could be
damaged if run in empty tank.
Air blower
Air compressor
Process tanks
1) Ensure that the drain valve of each tank is closed.
2) Check for other valves in normal operating condition.
3) Check for leaking.