Professional Documents
Culture Documents
ILL SWITCHBOARDS
By F. M. LOHNING
Introduction
With the growth of electric power in sugar mills and their interconnection with local electricity authorities, i t is perhaps opportune to
review switchboard design and operation and to suggest that sugar mill
electricians check fault levels and ensure that switchboards and switchgear
are adequately rated. The paper is also written with the intention of
stimulating discussion as to the type of electrical switchboards required
by the sugar industry.
It must be remembered that switchboards which were built many
years ago may be wholly inadequate for the fault levels existing today.
They could disintegrate under a direct short circuit with the possibility of
fire and complete shutdown of mill operations. To avoid such a possibility
fault levels should be calculated and the method outlined in this paper
will enable a rapid evaluation to be made.
*GeneratorShort Circuit
Consider the synchronous generator in Figure 2 , from the point of
view of short circuit. At the instant of short circuit the flux remains
unchanged and thus currents are induced in the main field winding FW
and damper winding DW. I t is these currents which give rise respectively
t o the concept of transient and sub-transient reactance as shown by the
curve of alternator short circuit current with time in Figure 2.
Whilst it can be argued that the switchgear should be designed for
the instantaneous maximum short circuit current, it must be realized
that relays and circuit breakers require time to operate and therefore the
current resulting from sub-transient reactance (due to the damper winding)
is not of such great importance, because the time constant is so shorta few cycles. The more prolonged short circuit current as determined by
the transient reactance is more realistic. This figure is around 15 per cent
for smaller machines up to about five megawatts. In view of the fact
that the subtransient reactance produces too large a figure for short
circuit current and the transient reactance a figure perhaps somewhat on
the low side i t is considered that the short circuit current on which
calculations should be based is that occurring say half a cycle after
K M
Fig. l-Alternator
on short circuit.
THIRTY-SECOND CONFERmCE
Fig. 2-AC
initiation of the short circuit, i.e. after 0.01 seconds. This treatment gives
rise to the concept of a s h r t circuit constant and for almost all alternators
this figure is from 5 to 7. Thus a 3 MVA alternator with a short circuit
constant of 6 would deliver 18 MVA just after the instant of short circuit
and this would be used in short circuit calculations.
PSIC
=
---
m''
etworks
Consider now a network followed by a transformer. The fault level
1965
TH I RTY-SECOND CONFERENCE
BUS
- EN2 ZN +ZT
from which, dividing by E N 2
ZN
THIRTY-SECOND CONFERENCE
Fig. 3-Typical
The network P,
fault level
= 250
MVA
= .-l=
from which
so that
Apart from inserting a reactor, there are various other ways in which
to view the problem of old boards with inadequate breakers, A simple
1965
67
Sectionalizing
The above comments assume that sectionalizing the bus is not
possible; but this may sometimes be arranged without much inconvenience.
The circuit of Figure 3 would then be as shown in Figure 4.
Double Busbars
The logical trend of these ideas leads to proposals for a double bus
system as shown in Figure 6. From discussion with electricians in the
industry, this arrangement is desirable, if not essential, for flexibility.
Type of Board
In reviewing the type of board desired by the mills, it is quite obvious
that the trend is not only to dead front cubicle type gear, but to individual
"compartmentation" of bus section, breakers etc. This applies not only to
main power house switchboards but also to motor control distribution
centres. In the latter case it will be interesting to have the sugar industry's
reaction to the completely with-drawable gear which is gaining favour in
L . r UOUBLC BUS.
Fig. 5-Switchboard
other industries such as mines, and iron and steel mills. Changeover trucks
have the advantage that shut downs are limited to a few minutes. Standardization of truck dimensions allows easy changeover of circuits to
accommodate larger motors when required.
I t is now generally agreed that 3.3kV as recommended by the author
in 1960[1] is, on purely economic grounds, the best generation voltage for
a mill. Whilst a mill may have no 3.3kV plant to begin with this is no
reason to continue with costly low tension reticulation. The solution is to
generate at 3.3kV and transform with a unit transformer direct to 41SV.
All new motors of large horsepower can then be placed direct on the
3.3kV circuit.
Fig. 6-Typical
mill circliit with h.t. and 1.t. generation and three winding
transformer.
1965
THIRTY-SECOND CONFERENCE
69
Fig. 7-4ircuit for fault calculation in mill with Lt. and h.t. generation.
Short circuit power of benerator 1 is l .O X 5 = 5MVA.
Short circuit power of generator 2 is 0.75 X 6 = 4.5MVA.
Short circuit power of generator 3 is 2.5 X 6 = 15MVA.
TH I RTY-SECOND CONFERENCE
-E
/ ,"M/
4
" "d,'=Yr
'as
WG
.-
m.r.rcmP
Thus the short circuit power from the 3.3kV generator on the 1.t.bus
1 965
71
T H I RTY-SECOND CONFERENCE
Thus the short circuit power from the l l k V network on the 1.t.bus is
+ +
-+ +
9.5 X 27
= 7 MVA
9.5 -C 27
Short circuit power transmitted from the l l k V network on the 3.3kV
bus is similarly found:
P s l c network 150 MVA
Pslc transformer on infinite bus
-27 MVA
7.5,iio
+ +
THIRTY-SECOND CONFERENCE
Fig. 9-Critical
5 *D
1965
THIRTY-SECOND CONFERENCE
73
Protection
Considerable discussion has recently been centred around generator
protection. For large machines exceeding say 1000 kW, differential protection can be justified for protection against internal fault and is usually
complemented with overcurrent back-up. On smaller machines overcurrent and earth leakage only are employed.
In relation to overcurrent protection, the question is, what settings
will be used? If set low to protect the machines against overheating then
there is a danger of cascade tripping of all sets should one set trip. I t is
the author's considered opinion that over-current relays should always
be set high as back-LIPand that a high quality thermal relay with a time
constant matching that of the generator should be employed. Thermocouples embedded in the windings of the generator are an even better
arrangement. In either case signalling only is required to bring the high
temperature condition to the notice of the mill electrician who can then
take appropriate action such, for example, as tripping off some nonessential load.
The Buchholz relay gives protection against internal faults in transformers and is usually inserted in the pipe between the conservator and
tank. Generation of gas causes signalling whilst any movement of oil
causes the surge flap to operate the trip contacts of the breakers feeding
and fed by the transformer. If the h.t. side is protected by fuses only,
then the Buchholz relay may be only partially effective. Feeder protection
is normally overcurrent only due to the considerable amount of single,
phase loading. Earth leakage could easily be included if neutrals were
run back to switchboards and would serve to confine earth faults to
individual feeders.
REFERENCE
.:
Brisbane.