A system with the high capacity needed to suit large-sized buildings

REGISTERED TRADEMARK

V
Variable

R
Refrigerant

V
Volume

System Operation

Power Supply Configuration


TPN
ISOLATOR

3 ph
power Supply

Single Phase power supply


13A S/S/O

13A S/S/O

13A S/S/O

13A S/S/O

Controls Configuration
INDIVIDUAL

up to 500 m

Individual Remote Controller,


Wired & Wireless Options
= up to 500 m length

4. Intelligent Control System


LCD REMOTE CONTROLLER
(WIRED & WIRELESS)

LCD screen

Auto Swing Mechanism


Air Flow
Temperature Setting
ON/OFF Timer
Filter Sign
80 Malfunction Code
Display
Group Control Display

Duty Cycling of Compressors


Conventional System
Always starts
Inverter Compressor
in unit 1 first.

STD

IN
V

3
STD

IN
V

2
STD

IN
V

Operating period of inverter


compressor in Unit 1 is
significantly longer than
compressors in units 2 & 3.

Inverter Compressor in
Unit 1 has shorter life.

Cycle start-up
sequence by
running time.
Equalises
compressor
running time.
Extended life of
Inverter comp.

Dependable and comfortable

Auto-rotation system
extends life of
equipment

When every unit


gets
a chance to rest,
none of them gets
worn too quickly.

With VRV III

Because the VRV III units are rotated within the


system at least once every eight hours,
averaging out the running time of each outdoor unit.
This system extends the life of the system as a whole.

Back-up Function - Single

Compressor
breaks down

STOP
RUN

INV

Back-up by
field setting

STOP

Alarm is
indicated

Broken

Back-up Function - Multiple


Even though VRV compressor failure rate is extremely low,
the back-up function will give further peace of mind.
Compressor
breaks down

INV

Stop

Back-up by field
setting

Running
INV

INV

Alarm is
indicated
on the RC

Broken

Continue running

The broken
compressor
can be
repaired
while the
remaining
units are still
operating.

INV

INV

INV

(Only applies
to multiple
units)

Brief Trouble-shooting

Self-diagnosis Function
- to Quickly Cope with Errors

Error code
display
Run lamp

Correct display of errors amounting to


74 items in the system
Errors related with indoor unit:

14

Errors related with outdoor unit:

32

Errors related with control/wiring: 16


Central Control
4
Inspection display
Unit No.

HRV
8

Troubleshooting by Remote Controller


Self-diagnosis by Wired Remote Controller
Operation lamp

Indoor Unit No.

Inspection
Display

Error Code

Ref: Si38-304; pg174

Overview of Malfunction Codes


Malfunction
code

Operation
Lamp

Inspection
Display

Unit
No.

Indoor unit

Malfunction Content

Page
Referred

A0

Error of external protection device

178

A1

PCB or E2PROM defect

179

A3

Malfunction of drain level sys. (33H)

180

A6

Fan motor(MF) lock, overload

182

A7

Malfunction of swing flap motor(MA)

183

A9

Malfunction of EXV (20E)

185

AF

Drain level above limit

187

AH

Malfunction of air filter maintenance

AJ

Malfunction of capacity setting

188

C4

Malfunction of thermistor (R2T) for heat


exchanger

189

C5

Malfunction of thermistor (R3T) for gas


pipe

190

C9

Malfunction of thermistor (R1T) for air


inlet

191

CJ

Malfunction of thermostat sensor in RC

192

System still operate during the indication of error code

Ref: Si38-304; pg174

Overview of Malfunction Codes


Malfunction
code

Operation
Lamp

Inspection
Display

Unit
No.

Outdoor unit

Malfunction Content

Page
Referred

E1

PCB defect

193

E3

Actuation of HP switch

194

E4

Actuation of LP switch

195

E5

Compressor motor lock

196

E6

STD compressor lock or over current

197

E7

Malfunction of outdoor unit fan motor

198

E9

Malfunction of EXV (Y1E ~ 3E)

200

F3

Abnormal discharge pipe temp.

202

F6

Refrigerant overcharge

203

H3

Malfunction of HP switch

H4

Actuation of LP switch

H7

Abnormal outdoor fan motor signal

204

H9

Malfunction of outdoor air thermistor


(R1T)

205

System still operate during the indication of error code

Ref: Si38-304; pg174

Overview of Malfunction Codes


Malfunction
code

Operation
Lamp

Inspection
Display

Unit
No.

Outdoor unit

Malfunction Content

Page
Referred

J2

Current sensor malfunction

206

J3

Malfunction of discharge pipe thermistor


(R31 ~ 33T)

207

J5

Malfunction of suction pipe thermistor


(R2T)

208

J6

Malfunction of heat exchanger thermistor


(R4T)

209

J7

Malfunction of header thermistor

J8

Malfunction of oil equalizing pipe


thermistor (R7T)

J9

Malfunction of receiver gas pipe


thermistor (R5T)

210

JA

Malfunction of discharge pipe pressure


sensor

211

JC

Malfunction of suction pipe pressure


sensor

212

System still operate during the indication of error code

Ref: Si38-304; pg174 & 175

Overview of Malfunction Codes


Malfunction
code

Operation
Lamp

Inspection
Display

Unit
No.

Inverter unit

Malfunction Content

Page
Referred

L0

Inverter system error

L4

Malfunction of INV radiating fin temp rise

213

L5

INV comp motor grounding / short circuit

214

L6

Comp motor coil grounding / short circuit

L8

INV current abnormal

215

L9

INV startup error

216

LA

Malfunction of power unit

LC

Malfunction of transmission btw INV &


control PCB

217

P1

INV over-ripple protection

219

P4

Malfunction of INV radiating fin temp rise


sensor

220

System still operate during the indication of error code

Ref: Si38-304; pg175

Overview of Malfunction Codes


Malfunction
code

Operation
Lamp

Inspection
Display

Unit
No.

Malfunction Content

Page
Referred

System

U0

LP drop due to refrigerant shortage or


EXV failure

221

U1

Reverse phase / open phase

222

U2

Power supply insufficient or


instantaneous failure

223

U3

Check operation not conducted

225

U4

Malfunction of transmission btw indoor &


outdoor unit

226

U5

Malfunction of transmission btw RC &


indoor unit

228

U5

Failure of RC PCB or setting during


control by RC

228

U7

Malfunction of transmission btw outdoor


unit

229

U8

Malfunction of transmission btw master &


slave RC

231

U9

Malfunction of transmission btw indoor &


outdoor unit in the same sys.

232

UA

Excessive no. of indoor units

234

System still operate during the indication of error code

Ref: Si38-304; pg175

Overview of Malfunction Codes


Malfunction
code

Operation
Lamp

Inspection
Display

Unit
No.

System

Malfunction Content

Page
Referred

UC

Address duplication of CRC

235

UE

Malfunction of transmission btw CRC &


indoor unit

236, 240,
246

UF

Refrigerant system not set, incompatible


wiring / piping

238

UH

Malfunction of system ,refrigerant system


address undefined

239

CRC &
Schedule Timer

M1

Or

PCB defect

241, 248

M8

Or

Malfunction of transmission btw optional


controllers for centralize control

242, 249

MA

Or

Improper combination of optional


controllers for centralized control

243, 250

MC

Or

Address duplication, improper setting

245, 252

System still operate during the indication of error code