By Cliff Burger
Visit us at: www.bgrtech.com for the latest version of all the Work Study Guides
ISBN10: 0-9792191-1-6
ISBN13: 978-0-9792191-1-5
Printed in USA
TERMS OF USE
Commercial Building Inspector is a copyrighted work owned by Burger, Inc.
ALL RIGHTS RESERVED
BURGER, INC. LICENSE AGREEMENT
DEFINITIONS
The Product is the PDF file, electronic media workbook to which License Agreement is attached or accompanies.
The User is an individual or a single entity that has purchased The Product.
You is another name for The User.
BURGER, INC. is a Nevada, USA privately held company ("BURGER, INC").
Third Party is any individual or entity, single or multiple, that is not The User.
This License Agreement is a legal agreement between you, The User, and BURGER, INC, a Nevada, USA
privately held company ("BURGER, INC"). for the use of this product, including any files, software, electronic
media, and accompanying on-line or printed documentation ("Product").
Your rights to use of this product is limited by the license agreement.
BY INSTALLING, COPYING, OR OTHERWISE USING THE PRODUCT, YOU AGREE TO BE BOUND BY ALL OF
THE TERMS AND CONDITIONS OF THE LICENSE AGREEMENT.
GRANT OF LICENSE
Provided that you comply with all terms and conditions of this agreement, BURGER, INC grants you a
nonexclusive license including the following rights and restrictions:
A. RIGHTS
1.
2.
3.
You may install and use one copy of the Product within ONE (1) hardware computer for each purchased
copy of The Product. Additional copies of The Product may be installed and used, up to the number of
"Licensed Copies" purchased. If you need to install The Product on additional computers you need to
purchase separate/additional licenses.
You may make one copy of The Product for backup and archival purposes only.
The use of The Product is limited solely for the purpose of helping to prepare The User for the exam
indicated by the product.
B. RESTRICTIONS
1.
2.
3.
4.
5.
Unless you have been granted prior, written consent from BURGER, INC, you may not: Reproduce,
distribute, or transfer The Product, or portions thereof, to any Third Party.
You may not Sell, rent, lease, assign, or sublet The Product or portions thereof.
You man not Grant rights to any Third Party.
Any other use including copying and or paraphrasing of the questions or answers into any other
document of any kind is prohibited. The use of the Product or portions of the Product as an outline for
creating a derivative of the Product in whole or in part is prohibited.
BURGER, INC reserves all rights not expressly granted to you in this agreement.
BURGER, INC has no obligation to provide you with any upgrades that are not released for general distribution to
BURGER, INC's other licensees. Nothing in this Agreement shall be construed to obligate BURGER, INC to
provide upgrades to you under any circumstances.
LIMITATION OF LIABILITY
Under no circumstances and under no legal theory, tort, contract, or otherwise, shall BURGER, INC be liable to you
or any other person for any indirect, special, incidental, or consequential damages of any character including,
without limitation, damages for loss of goodwill, work stoppage, computer failure or malfunction, or any and all
other commercial damages or losses. In no event will BURGER, INC be liable for any damages in excess of the
amount BURGER, INC received from you for a license to the Product, even if BURGER, INC shall have been
informed of the possibility of such damages, or for any claim by any other party.
TERMINATION
This agreement terminates, you lose all rights licensed to you, and you must stop use of the Product if you fail to
comply with any term or condition of this License
by Cliff Burger, ICC Certifications held: B-1, E-1, M-1, P-1, B-2
the Construction Industry as a Building Contractor, Master Electrician, Electrical Contractor and Businessman.
This study practice guide contains two sections. Section One contains over 500
unique questions covering the subject matter from the International Building.
Section Two has the questions set up in 6 complete Timed Exams of 80 questions
each, just like the real exam.
Studying the code can help you pass the exam, but because of the extremely large
amount of data, exceptions and variations it is impossible to have all that
information flawlessly in your mind. That is why the tests are open book. The best
inspectors rely on the code book, not their recollection of the code. It is extremely
important to be right on the safety issues in the code. If you have a basic
understanding of terminology you should easily be able to pass the exams by
having a fast system down for finding the answers in the book.
Visit us at: www.bgrtech.com for the latest version of all the Work Study
Guides
The best way to study for an open book test is by doing open book tests.
By reading a question and then pursuing the answer your mind is forced to
interpret what you read, process that information, and find a solution through
recall, and research. These study exam questions will help you by improving your
skill of three major things needed to pass the exam:
1. You will increase your speed at finding the answers and you will become an
expert on where to find the answers in the code book, this is very important
because this is the only way to be correct 100% of the time.
2. You will learn the answers to many of the questions that will be on the test and
thereby be able to answer them from recall memory, saving you precious time.
3. You will become an expert at managing that time during the test, through test
taking experience.
Good Luck!
very long. Think about how many people you have met only to forget their name.
Why because you did not use their name. Remember, if you dont use it, you lose
it. Sound familiar, well, its true.
So Im learning codes, how do I use them?
method to answer the first practice questions in the workbook. You will probably
be able to find from 3 to 6 answers at first in that twenty minute block, and that
will keep improving as you practice your skills. Now use the recall technique
between each block, reviewing the questions and answers in your mind. You can
be watching TV, eating going for a walk, bike riding playing with the kids, visiting
with friends, or doing nearly anything during this time, actually diversion and
distractions are a good thing when it comes to recall. If you can recall under those
conditions, think how easy it would be on a test with no distractions. Who knew
learning could be this much fun?
Going in 20 minute blocks using recall go through all of the practice questions.
Remember to think about questions and answers that you did in the last 20 minute
block. By the time you are done with the main question area in the book, you will
be pretty good at finding answers in the code book, and you will have memorized
the answers to many of the questions on the exam. Remember, If you can answer
them from memory, accurately you save more time for the ones that you have to
look up in the book.
6%
1%
2%
3%
21%
5%
2%
2%
4%
1%
0206. Accessibility
Inspects buildings to assure elements are accessible and usable by
individuals with physical disabilities as specified by the code, approved
plans, and construction documents.
3%
2%
2%
3%
1%
1%
3%
7%
4%
3%
10
8%
21%
4%
and that wood members are protected against insects and decay where
required.
0502. Steel Framing Systems
Inspects wall systems for proper spans, spacing, bearing and connections.
Verify that pre-engineered wall systems are in accordance with the
approved drawings and manufacturer=s specifications. Inspects that steel
framing is in compliance with the markings, standards and the materials
characteristics.
3%
4%
3%
3%
4%
6%
4%
2%
31%
10%
11
12
4%
3%
3%
3%
3%
2%
2%
1%
Section 1
500 Practice Questions
13
1.
In masonry construction, the walls shall be laterally supported at
intervals not exceeding ____________.
A. 20 feet (6096 mm)
B. 24 feet (7315 mm)
C. 30 feet (9144 mm)
D. 60 feet (18288 mm)
2.
Clay flue liners shall be installed in accordance with ASTM C 1283. The
lining shall be carried up vertically, with a maximum slope no greater than
______ degrees from the vertical.
A. 10
B. 20
C. 30
D. 45
3.
Beams, girders or slabs supported by columns or walls shall not be cast
or erected until concrete in the vertical support members
_____________________.
A. is completely cured
B. has no more than 5% moisture content.
C. is no longer plastic
D. None of the above
4.
In the design of masonry structures using allowable stress design, the
reinforcement bar diameter shall not exceed __________ of the nominal wall
thickness and shall not exceed _________ of the least dimension of the cell,
course or collar joint in which it is placed.
A. one-eighth, one-quarter
B. one-eighth, one-eighth
C. one-quarter, one-quarter
D. one-quarter, one-eighth
5.
What is the fire resistance rating requirement for primary structural frame
including columns, girders, trusses in a type V-B structure.
14
A. 0
B. 1
C. 2
D. HT
6.
What is the maximum number of occupants allowed in a bowling center
in bowling areas.
A. 7 net, persons for each lane
B. 5 persons for each lane including 15 feet of runway
C. no limit
D. 15 gross, persons for each lane
7.
Plastic interior trim shall not constitute more than _________ percent of
the specific wall or ceiling areas to which it is attached.
A. 2.5
B. 5
C. 10
D. 15
8.
In buildings constructed in accordance with the provisions of
conventional light-frame construction a hole not greater in diameter than _____
percent of the stud width is permitted to be bored in any wood stud. Bored
holes not greater than _______ percent of the width of the stud are permitted in
nonbearing partitions or in any wall where each bored stud is doubled, provided
not more than two such successive doubled studs are so bored.
A. 25, 40
B. 30, 40
C. 40, 60
D. 50, 75
9.
Areas of refuge shall be provided with
______________________________________ complying with Sections
1007.8.1 and 1007.8.2.
15
15.
What interior wall and ceiling class finish is required in non-sprinklered
exit enclosures and exit passageways of a Group I-3 occupancy?
A. A
B. B
C. C
16.
In buildings constructed in accordance with the provisions of
conventional light-frame construction the ends of header joists more than
______ feet long shall be supported by framing anchors or joist hangers unless
bearing on a beam, partition or wall.
A. 4
B. 5
C. 6
D. 7
17
17.
In buildings constructed in accordance with the provisions of
conventional light-frame construction, solid blocked cripple walls exceeding 14
inches in height _____________________.
A. need not be considered a story
B. must be considered a story
C. are not allowed
D. must be treated wood
18.
Where more than one smoke alarm is required to be installed within an
individual dwelling unit in Group R-2, R-3 or R-4, or within an individual dwelling
unit or sleeping unit in Group R-1, the smoke alarms shall be
_____________________ in such a manner that the activation of one alarm will
activate all of the alarms in the individual unit.
A. installed
B. separated
C. transmitted
D. interconnected
19.
Where wood structural panel sheathing is used as the exposed finish on
the exterior of outside walls, it shall ________________________.
A. be adequately painted
B. coated with 2 full coats of Thompson's Water Seal
C. have an exterior exposure durability classification.
D. not be considered as a structural component for load calculations
20.
The period of time a building element, component or assembly maintains
the ability to confine a fire, continues to perform a given structural function, or
both, as determined by the tests, or the methods based on tests, prescribed in
Section 703.
A. flame spread rating
B. smoke rating
C. fire spread time
D. fire resistance rating
18
21.
Every landing shall have a minimum dimension measured in the
direction of travel equal to the width of the stairway. Such dimension need not
exceed ____________ inches where the stairway has a straight run.
A. 48
B. 60
C. 72
D. 84
22.
In reference to Covered Mall Buildings. Anchor building means of
egress. The path of egress travel of malls shall not exit through anchor
buildings. Malls terminating at an anchor building where no other means of
egress has been provided shall be considered as a _____________________.
A. valid means of egress
B. dead-end mall
C. low volume egress point
D. main entrance and egress
23.
No person shall make connections from a utility, source of energy, fuel
or power to any building or system that is regulated by this code for which a
permit is required, _____________________________________
A. until released by the building official.
B. until released by the public utility.
C. until the contractor, electrician, plumber or other professional in
charge of the applicable utilization equipment approves.
D. until a reasonable person deems it to be safe.
24.
As to fire-resistance ratings, cornices, eave overhangs, exterior
balconies and similar architectural appendages extending beyond the floor area
shall not extend beyond the distance determined by the following two methods,
whichever results in the lesser projection:
A. A point one-third the distance from the exterior face of the wall to the
lot line where protected openings or a combination of protected and
unprotected openings are required in the exterior wall.
B. More than 20 inches into areas where openings are prohibited.
C. More than 12 inches into areas where openings are prohibited.
19
D. A and B
E. A and C
25.
Concrete in footings shall have a specified compressive strength (fc) of
not less than __________ pounds per square inch.
A. 2000
B. 2500
C. 3000
D. 3500
26.
Smoke partitions shall extend from the top of the foundation or floor
below to the underside of the floor or roof sheathing, deck or slab above or to
the underside of the ceiling above where the ceiling membrane is constructed
to limit the _________________ of smoke.
A. transfer
B. accumulation
C. intensity
D. buildup
27.
Conduits, pipes and sleeves of any material not harmful to concrete and
within the limitations of ACI 318, Section 6.3, are permitted to be embedded in
concrete with approval of the _____________________________________.
A. building official
B. general contractor
C. building code
D. registered design professional
28.
What is the shear capacity for horizontal wood framed gypsum board
diaphragm ceiling assemblies for 1/2 material with framing members 16 in oc.
A. 70 plf
B. 80 plf
C. 90 plf
D. 100 plf
20
29.
Factory Industrial Moderate-Hazard Occupancy. Factory industrial uses
which are not classified as Factory Industrial _______ Low Hazard shall be
classified as __________ Moderate Hazard.
A. F-1, F-2
B. F-2, F-3
C. F-2, F-1
D. F-4, F-5
30.
What is the minimum curing time between the first and second cement
plaster coat in exterior applications.
A. 24 Hours
B. 36 Hours
C. 48 Hours
D. 60 Hours
31.
Parapets shall have the same fire-resistance rating as that required for
the supporting wall, and on any side adjacent to a roof surface, shall have
noncombustible faces for the uppermost _________________, including
counter flashing and coping materials.
A. 18 inches
B. 36 inches
C. 54 inches
D. 72 inches
32.
Parapet walls shall be properly coped with noncombustible,
weatherproof materials of a width _______________.
A. of 8 inches minimum
B. no less than the thickness of the parapet wall
C. of 12 inches minimum
D. none of these
33.
The building official is authorized to issue a temporary certificate of
occupancy before the completion of the entire work covered by the permit,
provided that such portion or portions ________________________. The
21
building official shall set a time period during which the temporary certificate of
occupancy is valid.
A. completely finished
B. approved by the owner, contractor and building official.
C. have no exposed electrical connections.
D. shall be occupied safely
34.
What is the Rated Fire-Resistance Period for a hollow brick wall, not
filled, that is 3.4 inches thick.
A. 4
B. 3
C. 2
D. 1
35.
In Heavy Timber Construction, wood beams and girders shall be of
____________________ and shall be not less than 6 inches nominal in width
and not less than 10 inches nominal in depth. Framed sawn or glued-laminated
timber arches, which spring from the floor line and support floor loads, shall be
not less than 8 inches nominal in any dimension.
A. hand split timber
B. unstripped logs
C. oriented strand board (OSB)
D. sawn or glued-laminated timber
36.
As applied to a fire door or other opening, means equipped with an
approved device that will ensure closing after having been opened.
A. automatic
B. self-closing
C. motorized
D. self-automated
37.
The minimum aisle width of assembly seating where the aisle does not
serve more than 50 seats is __________ inches.
22
A. 32
B. 36
C. 40
D. 44
38.
An intermediate level or levels between the floor and ceiling of any story
and in accordance with Section 505.
A. gallery
B. stage
C. mezzanine
D. platform
39.
Headers, double joists, trusses or other approved assemblies that are of
adequate size to ___________ loads to the vertical members shall be provided
over window and door openings in load-bearing walls and partitions.
A. carry
B. transfer
C. support
D. maintain
40.
Every kitchen in a one- and two-family dwelling shall have not less than
___________ square feet of gross floor area.
A. 50
B. 60
C. 70
D. 80
41.
The total width of means of egress in inches (mm) shall not be less than
the total occupant load served by the means of egress multiplied by
___________ per occupant for stairways and by __________ per occupant for
other egress components. The width shall not be less than specified elsewhere
in this code. Multiple means of egress shall be sized such that the loss of any
one means of egress shall not reduce the available capacity to less than 50
percent of the required capacity.
23
50.
Any tower, spire, dome or cupola that exceeds ______________ in
height above the highest point at which it comes in contact with the roof, or that
exceeds ______________ in area at any horizontal section, or which is
intended to be used for any purpose other than a belfry or architectural
embellishment, shall be entirely constructed of and supported by
noncombustible materials.
A. 40 feet, 1200 square feet
B. 100 feet, 300 square feet
C. 60 feet, 200 square feet
D. 30 feet, 100 square feet
51.
The use of a solid or liquid hazardous material involving a closed vessel
or system that remains closed during normal operations where vapors emitted
by the product are not liberated outside of the vessel or system and the product
is not exposed to the atmosphere during normal operations; and all uses of
compressed gases.
A. Open System
B. Encapsulated System
C. Concealed System
D. Closed System
52.
For the purposes of section 106.3, deferred submittals are defined as
those portions of the design that are not submitted at the time of the application
and that are to be submitted to the building official within
_______________________.
A. a reasonable period of time.
B. 180 days.
C. the time period of the permit.
D. a specified period
53.
A statement that the described portion of the structure has been
inspected for compliance with the requirements of this code for the occupancy
and division of occupancy and the use for which the proposed occupancy is
classified is required to be found on the:
26
A. Permit Application
B. Certificate of Occupancy
C. Building Documents
D. Request for Appeal
54.
58.
In buildings constructed in accordance with the provisions of
conventional light-frame construction, exterior exit balconies, stairs and similar
exit facilities shall be positively anchored to the primary structure at not over
____ feet o.c. or shall be designed for lateral forces. Such attachment shall not
be accomplished by use of toenails or nails subject to withdrawal.
A. 2
B. 4
C. 6
D. 8
59.
60.
61.
Posts or columns. Posts or columns supporting permanent structures
and supported by a concrete or masonry slab or footing that is in direct contact
with the earth shall be of _______________ or preservative-treated wood.
Exceptions ignored.
A. Fir
B. Cedar
C. Redwood
D. naturally durable
28
62.
Used materials and equipment can not be used under any
circumstances, unless the materials used meet the requirements of this code
for new materials and they are approved by the building official.
A. True
B. False
63.
Construction documents for all buildings shall describe the exterior wall
envelope in sufficient detail to determine _______________________.
A. the basic elements of construction.
B. if more bracing is needed in high wind areas.
C. if more the building is exempt from the code.
D. compliance with this code.
64.
For the purpose of natural lighting, any room is permitted to be
considered as a portion of an adjoining room where _______ of the area of the
common wall is open and unobstructed and provides an opening of not less
than one-tenth of the floor area of the interior room or 25 square feet (2.32 m2),
whichever is greater. Exceptions ignored.
A. one-half
B. one-third
C. one-quarter
D. one-tenth
65.
The location of construction joints in concrete shall
_______________________________________.
A. comply with the provisions of ACI 317, Section 5.4
B. comply with the provisions of ACI 318, Section 6.4
C. comply with the provisions of ACI 318, Section 5.4
D. none of the above
29
66.
There shall be a floor or landing at the top and bottom of each stairway.
The width of landings shall not be less
than__________________________________.
A. 36 inches
B. 42 Inches
C. 48 inches
D. the width of stairways they serve
67.
Press boxes in assembly areas shall be on an accessible route. An
accessible route shall not be required to press boxes in bleachers that have
points of entry at only one level, provided that the aggregate area of all press
boxes is ___________ square feet maximum.
A. 100
B. 500
C. 1000
D. 1200
68.
Construction or work for which a permit is required shall be subject to
inspection by the ________________ and such construction or work shall
remain accessible and exposed for inspection purposes until approved.
A. building official
B. building inspector
C. general contractor
D. design professional
69.
A permit shall not be required for the installation, alteration or repair of
generation, transmission, distribution or metering or other related equipment
that is under the ownership and control
________________________________________.
A.
B.
C.
D.
30
70.
71.
Sheathing nails or other approved sheathing connectors shall be driven
so that their head or crown __________ the surface of the sheathing.
A. penetrates
B. is flush with
C. grips
D. bear directly on
72.
Stair riser heights shall be ____ inches maximum and _______ inches
minimum. Stair tread depths shall be _______ inches minimum.
A. 8, 6, 10
B. 7, 6, 12
C. 8, 7, 11
D. 7, 4, 11
73.
Covered mall buildings exceeding 50,000 square feet shall be provided
with standby power systems that are capable of operating the emergency
__________________________________________.
A. interior lighting systems
B. automatic sprinkler system
C. loss control egress exits
D. voice/alarm communication system
74.
The area of a one-story, Group A-3 building used as a church,
community hall, dance hall, exhibition hall, gymnasium, lecture hall, indoor
swimming pool or tennis court of Type I or II construction shall always be
limited to 60,000 square feet maximum.
A. This is a true statement as to the IBC.
B. This is a false statement as to the IBC.
31
75.
That property of materials or their assemblies that prevents or retards
the passage of excessive heat, hot gases or flames under conditions of use.
A. fire proof
B. fire resistance
C. flame resistance
D. flame spread
76.
Any person who shall continue any work after having been served with a
stop work order, except such work as that person is directed to perform to
remove a violation or unsafe condition, shall be
_____________________________
A. subject to seizure of property
B. subject to loss of permit
C. subject fines and or imprisonment
D. subject to penalties as prescribed by law.
77.
Glazing in fixed and sliding panels of sliding door assemblies and panels
in sliding and bifold closet door assemblies _________________.
A. is not allowed
B. must be double glazed
C. is considered a hazardous location installation
D. must be unbreakable
78.
The opening around a penetrating item in a fire resistance-rated
construction.
A. dead space
B. annular space
C. fire blocking space
D. seal housing
79.
The minimum corridor width shall be as determined in Section 1005.1,
but not less than _______ inches. Exceptions ignored.
32
A. 38
B. 44
C. 48
D. 60
80.
If a self-service storage facility has 208 individual self-storage spaces
how many accessible self-storage facilities are required.
A. 5%, but not less than 1
B. 10, plus 2% of total number of units over 200
C. 5, plus 2% of total number of units over 100
D. 8, plus 1% of total number of units over 200
81.
Artificial light shall be provided that is adequate to provide an average
illumination of _____ foot-candles over the area of the room at a height of
_____ inches above the floor level.
A. 5, 24
B. 10, 30
C. 10, 6
D. 30, 10
82.
A fire-resistance-rated wall having protected openings, which restricts
the spread of fire and extends continuously from the foundation to or through
the roof, with sufficient structural stability under fire conditions to allow collapse
of construction on either side without collapse of the wall.
A. fire wall
B. fire barrier
C. fire stop
D. fire block
83.
In light frame construction, footings supporting 3 floors shall have a
minimum width of _________ inches and a minimum depth of _________
inches. Exceptions ignored.
33
A. 12, 6
B. 15, 6
C. 16, 8
D. 18, 8
84.
Required guards shall be not less than __________ inches high,
measured vertically above the adjacent walking surfaces, adjacent fixed seating
or the line connecting the leading edges of the treads.
A. 36
B. 38
C. 42
D. 48
85.
The number of persons for which the means of egress of a building or
portion thereof is designed.
A. legal group
B. public access
C. max occupancy
D. occupant load
86.
There must be a floor or landing on each side of a door. Such floor or
landing must be at the same elevation on each side of the door. Landings shall
be level except for exterior landings, which are permitted to have a slope not to
exceed ____________________________. Exceptions ignored.
A. 0.125 unit vertical in 12 units horizontal
B. 0.5 unit vertical in 12 units horizontal
C. 0.25 unit vertical in 12 units horizontal
D. 1 unit vertical in 12 units horizontal
87.
Cement used to produce concrete shall comply
with_______________________.
A. CPI, Section 801.90
B. ACI 318
C. NACA 318.90
D. CIA, Section 405
34
88.
What is the fire resistance rating requirement for the primary structural
frame Including columns, girders, trusses in a Type I-B structure.
A. 0
B. 1
C. 2
D. 3
89.
Religious educational rooms and religious auditoriums, which are
accessory to churches in accordance with Section 302.2 and have occupant
loads of less than 100, shall be classified as _______ occupancies.
A. E
B. B
C. A-3
D. I-2
90.
Adobe units shall have a moisture content not exceeding _____ percent
by weight.
A. 10
B. 15
C. 8
D. 4
91.
92.
In reference to Covered Mall Buildings. Within each individual tenant
space in a covered mall building, the maximum distance of travel from any point
to an exit or entrance to the mall shall not exceed _____________________.
35
A. 60,960 mm
B. 150 ft
C. 1400 inches
D. All of the above
93.
What is the minimum normal weight concrete cover in inches that will
provide a Fire-Resistance Rating of 3 hours for a W6 x 16 structural shape
steel column.
A. 1 inch
B. 2 inches
C. 2.5 inches
D. 3 inches
E. none of these
94.
In buildings constructed in accordance with the provisions of
conventional light-frame construction nominal 1-inch by 4-inch continuous
diagonal braces let into top and bottom plates and intervening studs, placed at
an angle not more than _______ degrees or less than _______ degrees from
the horizontal and attached to the framing in conformance with Table 2304.9.1.
A. 60, 45
B. 45, 60
C. 50, 45
D. 45,50
95.
The distance measured from the building face to the closest interior lot
line, or to the centerline of a street, an alley or public way or to an imaginary
line between two buildings on the property.
A. fire separation distance
B. building set back
C. minimum wall distance
D. allowable building line
96.
What is the allowable height and area of a Group E building of Type IIB
Construction
36
A. 2 Stories , 14,500 SF
B. 3 Stories , 14,500 SF
C. 4 Stories , 14,500 SF
D. 5 Stories , 14,500 SF
97.
The building official is authorized to accept reports of approved
inspection agencies, provided such agencies satisfy the requirements as to
______________.
A. education
B. licensing
C. experience
D. qualifications and reliability
98.
The face of an exit sign illuminated from an external source shall have
an intensity of not less than ___ foot-candles.
A. 1
B. 3
C. 5
D. 8
99.
Detailed use and occupancy requirements. In addition to the occupancy
and construction requirements in this code, the provisions of this chapter apply
to the special uses and occupancies described herein.
A. Chapter 3
B. Chapter 4
C. Chapter 5
D. Chapter 6
100.
39
41
118. What is the fire resistance rating requirement for floor construction and
secondary members in a type III-B structure.
A. 0
B. 1
C. 2
D. 3
119. In reference to Food courts in Covered Mall Buildings. The occupant
load of a food court shall be determined in accordance with Section 1003. For
the purposes of determining the means of egress requirements for the mall, the
food court occupant load shall _________ to the occupant load of the covered
mall building as calculated above.
A. be subtracted
B. not be included
C. no be added
D. be added
42
123. Main exterior exit doors or gates which obviously and clearly are
identifiable as exits need not have exit signs where approved by the
___________________.
A. building official
B. general contractor
C. design professional
D. fire department
124. Studs shall have full bearing on a 2-inch-thick (actual 1 1/2-inch) or
larger plate or sill having a width at least equal to the width of the __________.
43
A. studs
B. plates
C. sill
D. top plate
125. In new construction, required smoke alarms shall receive their primary
power from the building wiring where such wiring is served from a commercial
source and shall be equipped with a ______________. Exceptions ignored.
A. battery backup
B. secondary power system
C. emergency lighting system
D. power saver system
126.
127. Ducts and air transfer openings. Ducts and air transfer openings shall
_____________ fire walls. Exceptions ignored.
A. not penetrate
B. be allowed in
C. be fireblocked in
D. be of non-combustible materials in
128. A space within a building enclosed by smoke barriers on all sides,
including the top and bottom.
A. fire block
B. smoke compartment
C. smoke block
D. smoke barrier
44
129. Bleachers, grandstands, and folding and telescopic seating shall comply
with _________.
A. ICC 300
B. ICC 400
C. ICC 500
D. ICC 600
130. Exit signs are not required in rooms or areas which require
_________________ exit or exit access.
A. only 1
B. only 2
C. only 3
D. only 4
131. Fire-protection-rated glazing used in fire window assemblies located in
fire partitions and fire barriers shall be limited to use in assemblies with a
maximum fire-resistance rating of ____ hour(s).
A. 1
B. 2
C. 3
D. 4
132. In buildings constructed in accordance with the provisions of
conventional light-frame construction bearing partitions perpendicular to joists
shall not be offset from supporting girders, walls or partitions
___________________ unless such joists are of sufficient size to carry the
additional load.
A. 12 inches
B. 24 inches
C. more than twice the joist depth
D. more than the joist depth
45
133. The clear space between a handrail and a wall or other surface shall be
a minimum of _____ inches.
A. 1
B. 1.5
C. 2
D. 2.5
134. Where natural ventilation is required, the minimum openable area to the
outdoors shall be ______ percent of the floor area being ventilated.
A. 20
B. 10
C. 8
D. 4
135. What is the minimum thickness face-to-face required for a wall
constructed from wood studs interior partition with gypsum wallboard each side
2"X4" wood studs 24" on center with 5/8" type x gypsum wallboard applied
vertically or horizontally nailed with 6d cooler or wallboard nails at 7" on center
with end joints on nailing members, stagger joints each side, to have a fire
resistance rating of 1 hour.
A. 3.5 inches
B. 4.75 inches
C. 5.75 inches
D. 6.75 inches
136. Masonry shall not be supported on ____________________ except as
permitted in Section 2304.12.
A. wood girders or other forms of wood construction
B. concrete girders or other forms of concrete construction
C. steel girders or other forms of steel construction
D. masonry girders or other forms of masonry construction
137. It shall be the duty of the _______________________________ to notify
the building official when work is ready for inspection. It shall be the duty of the
46
permit holder to provide access to and means for inspections of such work that
are required by this code.
A. holder of the building permit or their duly authorized agent
B. contractor
C. construction supervisor
D. design professional or their associates
138. The use of a building or structure, or portion thereof, for educational,
supervision or personal care services for more than ______ children older than
_______ years of age, shall be classified as a Group E occupancy.
A. ten, 2
B. six, 2 1/2
C. twelve, 2
D. five, 2 1/2
139. In buildings constructed in accordance with the provisions of
conventional light-frame construction, in exterior walls and bearing partitions,
any wood stud is permitted to be cut or notched to a depth not exceeding
_______ percent of its width. Cutting or notching of studs to a depth not greater
than _______ percent of the width of the stud is permitted in nonbearing
partitions supporting no loads other than the weight of the partition.
A. 40, 25
B. 30, 50
C. 25, 40
D. 35, 50
140. Flexible ducts and air connectors shall not pass through any fireresistance-rated assembly. Flexible air connectors shall not pass through any
_______________________________.
A. wall
B. ceiling
C. floor
D. all the above.
47
141. Chimneys shall extend at least 2 feet higher than any portion of the
building within 10 feet , but shall not be less than _________ feet above the
highest point where the chimney passes through the roof.
A. 2
B. 3
C. 4
D. 5
142. Penetrations other than those
____________________________________ shall not be permitted in shaft
enclosures. Ducts shall not penetrate exit shaft enclosures.
A. for heating and cooling
B. necessary communication wiring
C. necessary for alarm systems
D. necessary for the purpose of the shaft
143. An exterior perimeter building of a group other than H having direct
access to a covered mall building but having required means of egress
independent of the mall.
A. Food Court
B. Anchor Building
C. Covered Mall Building
D. Gross Leas able Area
144. A material, device or construction installed to restrict the movement of air
within open spaces of concealed areas of building components such as crawl
spaces, floor/ceiling assemblies, roof/ceiling assemblies and attics.
A. firestop
B. draftstop
C. smokestop
D. damper
145. Sleepers and sills on a concrete or masonry slab that is in direct contact
with earth shall be of ________________ or preservative-treated wood.
48
A. pressure treated
B. creosote
C. green
D. naturally durable
146. What is the REQUIRED SEPARATION OF OCCUPANCIES (HOURS)
between a Group A-3 and Group S-1. The Buildings are not equipped
throughout with an automatic sprinkler system.
A. 1
B. 2
C. 3
D. NP (Not Permitted)
147. Inlets to masonry chimneys shall enter from the side. Inlets shall have a
________ of fireclay, rigid refractory material or metal that will prevent the
connector from pulling out of the inlet or from extending beyond the wall of the
liner.
A. funnel
B. fire door
C. vent
D. thimble
148. Guards shall be located along open-sided walking surfaces,
mezzanines, industrial equipment platforms, stairways, ramps and landings
which are located more than _________ inches above the floor or grade below.
Exceptions ignored.
A. 12
B. 24
C. 30
D. 40
149. Rooms or spaces having a floor area larger than ________ square feet
(93 m2), containing a refrigerant evaporator and maintained at a temperature
49
below 68F (20C), shall have access to not less than two exits or exit access
doors.
A. 500
B. 1000
C. 1500
D. 2000
150. The fire-resistance rating of floor and roof assemblies shall not be less
than that required by the _____________________________.
A. size of the building
B. building type of construction
C. area of the enclosure
D. fire zone
151. A-3 Assembly uses intended for worship, recreation or amusement and
other assembly uses not classified elsewhere in Group A including, but not
limited to ________________________________.
A. Courtrooms, Dance halls (not including food or drink consumption)
Exhibition halls
B. Motion picture theaters Symphony and concert halls Television and
radio studios admitting an audience Theaters
C. Banquet halls, Night clubs, Restaurants, Taverns and bars
D. Amusement arcades, Art galleries, Bowling alleys, Churches,
Community halls
E. A and D
152. Where used in monolithic glazing systems are used in sloped glazing
and skylights, heat-strengthened glass and fully tempered glass shall have
screens installed __________ the glazing material.
A. inside
B. above
C. below
D. within
50
157. It shall be the duty of the permit applicant to cause the work to remain
accessible and exposed for inspection purposes. Neither the
__________________ nor the jurisdiction shall be liable for expense entailed in
the removal or replacement of any material required to allow inspection.
A. contractor
B. designer
C. subcontractor
D. building official
158. Every room or space that is an assembly occupancy shall have the
occupant load of the room or space posted in a ______________________,
near the main exit or exit access doorway from the room or space.
A. illuminated sign holder
B. exit sign enclosure
C. orderlly manner
D. conspicuous place
159. Deferral of any submittal of plan items for a permit shall have the prior
approval of the building official. The registered design professional in
responsible charge shall list the deferred submittals on the
_______________________ for review by the building official.
A. plans
B. construction documents
C. schedule of submittals
D. plot plan
160. The minimum thickness of exterior walls in a masonry construction onestory buildings shall be ____________.
A. 6 inches (152 mm)
B. 8 inches (203 mm)
C. 10 inches (254 mm)
D. 12 inches (304 mm)
52
161. Any combination of a fire door, frame, hardware, and other accessories
that together provide a specific degree of fire protection to the opening.
A. fire door assembly
B. fire damper
C. fire barrier
D. fire stop
162. What is the minimum normal weight concrete cover in inches that will
provide a Fire-Resistance Rating of 1.5 hours for a W14 x 233 structural shape
steel column.
A. 1 inch
B. 2 inches
C. 2.5 inches
D. 3 inches
163. A-1 Assembly uses, usually with fixed seating, intended for the
production and viewing of the performing arts or motion pictures including, but
not limited to:
A. Courtrooms, Dance halls (not including food or drink consumption)
Exhibition halls
B. Motion picture theaters Symphony and concert halls Television and
radio studios admitting an audience Theaters
C. Banquet halls, Night clubs, Restaurants, Taverns and bars
D. Amusement arcades, Art galleries, Bowling alleys, Churches,
Community halls
164. In General not noting exceptions, the unlatching of any door leaf shall
not require more than ________ operation. Exceptions ignored.
A. 1
B. 2
C. 3
D. 4
53
165. A building used for assembly purposes with an occupant load of less
than ________ persons shall be classified as a Group B occupancy.
A. 50
B. 100
C. 200
D. 500
166. Mirrors and other glass panels mounted or hung on a surface that
provides a ______________ support is not considered hazardous location.
A. perimeter
B. bottom and top
C. hinged
D. continuous backing
167. In buildings constructed in accordance with the provisions of
conventional light-frame construction, spacing of edge nailing for required wall
bracing shall not exceed _______ inches o.c. along the foundation plate and
the top plate of the cripple wall.
A. 4
B. 6
C. 8
D. 10
168. Hospitals shall be equipped with ______________________ as required
in Section 407.2.
A. manual fire alarm system
B. emergency lighting system
C. voice alarm system
D. smoke detection
169. Non separated occupancies shall be individually classified in accordance
with Section 302.1. The requirements of the IBC code shall apply to each
portion of the building based on the occupancy classification of that space
except that the most _________ applicable provisions of Section 403 and
54
55
57
181. What is the fire resistance rating requirement for roof construction and
secondary members in a type I-A structure.
A. 1
B. 1.5
C. 2
D. 3
182. Automatic dampers, regardless of the purpose for which they are
installed within the smoke control system, shall be __________ and conform to
the requirements of approved, recognized standards.
A. listed
B. tested
C. visible
D. opened
183. An enclosed space extending through one or more stories of a building,
connecting vertical openings in successive floors, or floors and roof.
A. atrium
B. shaft
C. stairwell
D. chute
184. In reference to signage in Covered Mall Buildings. Plastic signs shall not
exceed _____ percent of the wall area facing the mall.
A. 20
B. 30
C. 40
D. 50
185. The vertical distance from grade plane to the average height of the
highest roof surface.
58
A. story height
B. building height
C. building dimension
D. straight rise
186. The fire-resistance rating of exterior walls with a fire separation distance
of ___ feet or less shall be rated for exposure to fire from both sides.
A. 3
B. 4
C. 5
D. 10
187. What is the minimum thickness face-to-face required for a wall
constructed from a combination of clay brick and load-bearing hollow clay tile
with 4 solid brick and 8 tile (at least 40 percent solid), to have a fire resistance
rating of 3 hours.
A. 4
B. 6
C. 8
D. 10
188. Bathrooms, toilet rooms, kitchens, storage rooms and laundry rooms
shall be permitted to have a ceiling height of not less than __________ feet.
Exceptions excluded.
A. 8 feet
B. 7 feet 6 inches
C. 7 feet
D. 6 feet 8 inches
189. Built-in tubs with showers shall have ______________ joints between
the tub and adjacent wall.
A. water resistant
B. sealed
C. waterproof
D. caulked
59
61
62
63
64
218. Nonsprinklered, one story. The area of a one-story, Group F-2 or S-2
building shall not be limited when the building is surrounded and adjoined by
public ways or yards not less than _________ in width.
A. 36 feet
B. 40 feet
C. 60 feet
D. 100 feet
219. An opening not less than ________________________ shall be
provided to any attic area having a clear height of over 30 inches. A 30-inch
minimum clear headroom in the attic space shall be provided at or above the
access opening.
A. 22 inches by 24 inches
B. 22 inches by 30 inches
C. 18 inches by 24 inches
D. 20 inches by 30 inches
220. Projections into the required width at each handrail shall not exceed
_____ inches at or below the handrail height. Projections into the required width
shall not be limited above the minimum headroom height required in Section
1009.2.
A. 1.5
B. 3
C. 4.5
D. 7
221. Commercial cooking operations. A(n) __________________________
shall be installed in commercial kitchen exhaust hood and duct system where
used to comply with Section 904.
A. fan
B. fire extinguisher
C. automatic sprinkler system
D. smoke detector
67
222. Wood columns and posts shall be framed to provide full end bearing.
Alternatively, column-and-post end connections shall be designed to resist the
full compressive loads, neglecting end-bearing capacity. Column-and-post end
connections shall be fastened to resist lateral and net induced
_________________.
A. uplift forces
B. buckling
C. stress
D. compression
223. Habitable spaces, other than a kitchen, shall not be less than ________
feet in any plan dimension.
A. 6
B. 7
C. 8
D. 9
224. Fireplace smoke chamber walls shall be constructed of solid masonry
units, hollow masonry units grouted solid, stone or concrete. The total minimum
thickness of front, back and sidewalls shall be ____________ of solid masonry.
A. 8 inches (203 mm)
B. 12 inches (354 mm)
C. 14 inches (404 mm)
D. 6 inches (178 mm)
225. A revolving door shall be capable of
________________________________ with parallel egress paths providing an
aggregate width of 36 inches.
A. allowing passage of a sphere
B. allowing 6 occupants to exit simultaneously
C. providing a smoke barrier
D. collapsing into a bookfold position
68
226. Labeled fire-resistance-rated glazing tested as part of a fire-resistancerated wall assembly in accordance with ASTM E 119 UL 263 shall not be
required to comply with ___________.
A. Section 715
B. Section 812
C. Section 1001
D. Section 405
227. The maximum width of a swinging means of egress door leaf shall be
__________ inches nominal. Exceptions ignored.
A. 36
B. 42
C. 48
D. 60
228. Any tower, spire, dome or cupola that exceeds 60 feet (18 288 mm) in
height above the highest point at which it comes in contact with the roof, or that
exceeds 200 square feet (18.6 m2) in area at any horizontal section, or which is
intended to be used for any purpose other than a belfry or architectural
embellishment, shall be entirely constructed of and supported by
noncombustible materials. Such structures shall be separated from the building
below by construction having a fire-resistance rating of not less than ________
hours with openings protected with a minimum _______hour fire protection
rating.
A. 1.5, 1.5
B. 2, 2
C. 2, 1.5
D. 2.5, 1.5
229. It shall be unlawful for any person, firm or corporation to
_____________________________________________ any building, structure
or equipment regulated by this code, or cause same to be done, in conflict with
or in violation of any of the provisions of this code.
69
A. erect or construct
B. alter
C. extend, repair, or move
D. remove, demolish or occupy
E. All of the Above
230. Combustible framing in fire walls. Adjacent combustible members
entering into a concrete or masonry fire wall from opposite sides shall not have
less than a __ inch distance between embedded ends. Exceptions ignored.
A. 4
B. 12
C. 20
D. 28
231. In wood construction, consideration shall be given in design to the
possible effect of cross-grain dimensional changes considered vertically which
may occur in lumber fabricated in a ___________ condition.
A. wet
B. dry
C. green
D. kiln
232. When masonry fireplaces are constructed as part of masonry or
concrete walls, combustible materials shall not be in contact with the masonry
or concrete walls less than _________ inches from the inside surface of the
nearest firebox lining.
A. 10
B. 18
C. 12
D. 30
233. A manual fire alarm system and an automatic fire detection system shall
be installed in Group I occupancies. An automatic smoke detection system
shall be provided in_________________________________. Exceptions
ignored.
70
238. Stair treads and risers shall be of uniform size and shape. The tolerance
between the largest and smallest riser or between the largest and smallest
tread depth at the walkline within any flight of stairs shall not exceed
_________ inch in any flight of stairs.
A. 0.025
B. 0.375
C. 0.0485
D. 0.5
239. An opening made through one side (wall, floor or ceiling membrane) of
an assembly.
A. wall penetration
B. ceiling penetration
C. membrane penetration
D. floor penetration
240. The building official shall have the authority to require tests as evidence
of compliance to be made at no expense to the jurisdiction.
A. The test methods shall be designed by an architect.
B. The test methods shall be UL Listed.
C. The test methods shall be as specified in this code or by other
recognized test standards.
D. The test methods shall be newly proven.
241. Fiberboard wall insulation applied on the exterior of foundation walls
shall be protected below ground level with a ___________________.
A. bituminous coating
B. waterproof film
C. tar based coating
D. preservative
72
242. Kitchens shall have a clear passageway of not less than ________ feet
between counter fronts and appliances or counter fronts and walls.
A. 3
B. 4
C. 5
D. 6
243. The ends of wood girders entering exterior masonry or concrete walls
shall be provided with a __________ air space on top, sides and end, unless
naturally durable or preservative-treated wood is used.
A. 1 inch clear
B. intentional
C. caulked
D. 1/2-inch
244. Ramps used as part of a means of egress shall have a running slope not
steeper than __________ unit vertical in 12 units horizontal. The slope of other
ramps shall not be steeper than one unit vertical in _________ units horizontal.
A. 0.25, 12
B. 0.5, 8
C. 1, 8
D. 1.25, 12
245. In structural plain concrete construction, the thickness of bearing walls
shall be not less than ______________ times the unsupported height or length,
whichever is shorter, but not less than _______ inches. Exceptions ignored.
A. 0.25, 5.5
B. 0.0416, 5.5
C. 0.5, 6
D. 0.375, 6
246. Time limitation of application. An application for a permit for any
proposed work shall be deemed to have been abandoned ____________ after
the date of filing, unless such application has been pursued in good faith or a
73
permit has been issued; except that the building official is authorized to grant
one or more extensions of time for additional periods not exceeding 90 days
each.
A. 180 days
B. 365 days
C. 270 days
D. 2 years
247. What is the minimum normal weight concrete cover in inches that will
provide a Fire-Resistance Rating of 3 hours for a W14 x 43 structural shape
steel column.
A. 1 inch
B. 2 inches
C. 2.5 inches
D. 3 inches
E. none of these
248.
74
A. within 36 inches
B. regardless of area or height
C. within 60 inches
D. within 42 inches
251. Fire walls shall have sufficient structural stability under fire conditions to
_____________ of construction on either side without collapse of the wall for
the duration of time indicated by the required fire-resistance rating.
A. fire resistance
B. total support
C. allow collapse
D. brace the elements
252. A basement shall be considered as a story above grade plane where the
finished surface of the floor above the basement is:
A. More than 6 feet above grade plane
B. More than 6 feet above the finished ground level for more than 50
percent of the total building perimeter
C. More than 12 feet above the finished ground level at any point.
D. A or C
E. Any of the above
253. If research reports are required with supporting data, are necessary to
assist in the approval of materials or assemblies not specifically provided for in
this code, they shall consist of valid research reports from ____________
sources.
A. approved
B. building design professional
C. university
D. agency
254. The use of structural plain concrete columns and structural plain
concrete footings on piles is _________________.
75
256. Where the fireplace opening is 6 square feet or larger, the hearth
extension shall extend at least _______ inches in front of, and at least
_________ inches beyond, each side of the fireplace opening.
A. 10, 8
B. 16, 8
C. 20, 12
D. 24, 12
257. Finely divided solid material that is 420 microns or less in diameter and
which, when dispersed in air in the proper proportions, could be ignited by a
flame, spark or other source of ignition.
A. Combustible Fibers
B. Combustible Dust
C. Combustible Liquid
D. Combustible Film
258. What is the allowable shear (pounds per foot) for wood structural panel
shear walls with framing of douglas-fir-larch, or southern pine for wind or
seismic loading for 7/16 Structural I Sheathing applied directly to the framing
fastened with 4 inch spacing at the perimeter of the panels with 8d common
nails that penetrate 1.375" into the framing.
76
A. 200
B. 260
C. 395
D. 505
259. Every space intended for human occupancy shall be provided with
natural light by means of exterior glazed openings which shall open directly
onto a public way or onto a yard or court. The minimum net glazed area shall
not be less than _____ percent of the floor area of the room served.
A. 4
B. 6
C. 8
D. 10
260. The maximum distance of travel from any point within a mall to an exit
shall not exceed ____________________.
A. 50 feet
B. 100 feet
C. 150 feet
D. 200 feet
261. Kiosks or similar structures located within a mall shall be provided with
approved fire ______________ and detection devices.
A. alarms
B. suppression
C. acceleration
D. notification
262. The period of time that an opening protective will maintain the ability to
confine a fire as determined by tests prescribed in Section 715. Ratings are
stated in hours or minutes.
A. Fire Protection Rating
B. Fire Barrier Time
C. Firestop Time
D. Fireblocking Time
77
A. 0
B. 1
C. 2
D. 3
268. Openings in a smoke barrier shall be _____________ in accordance
with Section 715.
A. closed
B. glassed
C. protected
D. cemented
269. In buildings constructed in accordance with the provisions of
conventional light-frame construction, buildings shall be limited to a maximum
of ______ stories above grade.
A. 1
B. 2
C. 3
D. 4
270. Penetrations by air ducts and air transfer openings in fire-resistancerated exterior walls required to have _______________________ shall comply
with Section 716.
A. fire doors
B. fire windows
C. protected openings
D. smoke barriers
271. Building, structures and parts thereof shall be designed and constructed
in accordance with strength design, load and _______________________,
allowable stress design, empirical design or conventional construction methods,
as permitted by the applicable material chapters.
79
A. interpretative analysis
B. soil bearing methods
C. lateral vertical load factors
D. resistance factor design
272. To obtain a permit, the applicant shall first file an application therefore in
writing on a form furnished by the department of building safety for that
purpose. Such application does not require which of the following items.
A. Indicate the use and occupancy for which the proposed work is
intended.
B. State the valuation of the proposed work.
C. Be signed by the applicant, or the applicant's authorized agent.
D. Identify and describe the work to be covered by the permit for which
application is made.
E. All of the above items.
273. In reference to Covered Mall Buildings. Anchor building means of
egress. Required means of egress for anchor buildings shall be provided
__________________ from the mall means of egress system. The occupant
load of anchor buildings opening into the mall shall not be included in
determining means of egress requirements for the mall.
A. within 1000 feet
B. within 500 feet
C. independently
D. within 1500 feet
274. In conventional light-frame construction, exterior gable end walls, braced
wall panel sheathing in the top story shall be extended and fastened to roof
framing where the spacing between parallel exterior braced wall lines is greater
than ____________. Exceptions ignored.
A. 25 feet (7 670 mm)
B. 40 feet (120192 mm)
C. 50 feet (15 240 mm)
D. 60 feet (18 288 mm)
80
275. Flue liners shall be installed in accordance with ASTM C 1283 and
extend from a point not less than ______________ inches below the lowest
inlet or, in the case of fireplaces, from the top of the smoke chamber, to a point
above the enclosing walls.
A. 6
B. 8
C. 12
D. 16
276. Where masonry is used as veneer for a framed chimney, through
flashing and ___________ shall be provided as required by Chapter 14.
A. rain venting
B. insulation
C. soldering
D. weep holes
277. Any portion of a masonry chimney located in the interior of the building
or within the exterior wall of the building shall have a minimum airspace
clearance to combustibles of ___________ inches. Exceptions ignored.
A. 1
B. 2
C. 4
D. 6
278.
81
A. 20 feet
B. 24 feet
C. 36 feet
D. 40 feet
280. Yards shall not be less than ________ feet in width for buildings two
stories or less above grade plane.
A. 3
B. 5
C. 8
D. 10
281. The building official, upon notification, shall make the requested
inspections and shall either indicate the portion of the construction that is
satisfactory as completed, or notify the permit holder or his or her agent
wherein the same fails to comply with this code. Any portions that do not
comply shall be corrected and such portion shall not be
_______________________ until authorized by the building official.
A. completed
B. re-inspected
C. covered or concealed
D. exposed
282. In a commercial cooking system, a manual actuation fire extinguishing
device shall be located at or near a means of egress from the cooking area, a
minimum of _________ feet and a maximum of __________ feet from the
kitchen exhaust system
A. 5, 10
B. 10, 15
C. 10, 20
D. 15, 25
283. Buildings of Group R-1 containing not more than _______ sleeping units
for rent or hire that are also occupied as the residence of the proprietor are not
required to be accessible.
82
A. 3
B. 5
C. 10
D. 15
284. What is the maximum number of occupants per 200 gross square feet
allowed in a commercial kitchen.
A. 1 occupant for each 200 gross square feet.
B. 2 occupant for each 200 gross square feet.
C. 3 occupant for each 200 gross square feet.
D. 4 occupant for each 200 gross square feet.
285. In food service lines, where self-service shelves are provided, at least
_________ percent, but not less than one, of each type provided shall be
accessible.
A. 10
B. 25
C. 35
D. 50
286. Chimney flues shall not be smaller in area than the area of the connector
from the appliance. Chimney flues connected to more than one appliance shall
not be less than the area of the largest connector plus _____________ percent
of the areas of additional chimney connectors.
A. 50
B. 75
C. 100
D. 125
287. Exits shall discharge directly to the exterior of the building. The exit
discharge shall be at grade or shall provide direct access to grade. The exit
discharge shall not _________ a building.
83
A. leave
B. go under
C. reenter
D. go over
288. Foam plastic insulation shall not be used as interior wall or ceiling finish
in plenums except as permitted in Section 2604 or when protected by a
________________ in accordance with Section 2603.4.
A. thermal barrier
B. layer of sheet metal
C. foil sheet
D. plastic wrap
289. Doors, when fully opened, and handrails shall not reduce the required
means of egress width by more than ___________ inches. Doors in any
position shall not reduce the required width by more than one-half. Other
nonstructural projections such as trim and similar decorative features shall be
permitted to project into the required width a maximum of 11/2 inches (38 mm)
on each side. Exceptions ignored.
A. 6
B. 7
C. 12
D. 14
290. _________________ construction is that type of construction in which
the exterior walls are of noncombustible materials and the interior building
elements are of any material permitted by this code.
A. Type I
B. Type II
C. Type III
D. Type IV
291. Buildings that are not more than two stories above grade plane and
having not more than 6,000 square feet of projected roof area and where there
84
294. The exterior area for assisted rescue shall be at least _____ percent
open, and the open area above the guards shall be so distributed as to
minimize the accumulation of smoke or toxic gases.
A. 10
B. 30
C. 50
D. 70
295. In reference to Covered Mall Buildings. Wherever the distance of travel
to the mall from any location within a tenant space used by persons other than
85
A. newel posts
B. brackets
C. pencil sharpeners
D. door knobs
300. A Hospital is an example of what type of Group Occupancy
Classification?
A. A-1
B. B
C. I-1
D. I-2
301. For smoke-protected assembly aisle accessways, the maximum number
of seats per row permitted to have a minimum 12 inch clear width aisle
accessway with the aisle or doorway at one end of the row only is ______.
A. 14
B. 7
C. 8
D. 11
302. No building or structure shall be _______________________________,
and no change in the existing occupancy classification of a building or structure
or portion thereof shall be made until the building official has issued a certificate
of occupancy therefore as provided herein. Issuance of a certificate of
occupancy shall not be construed as an approval of a violation of the provisions
of this code or of other ordinances of the jurisdiction. Exceptions ignored.
A. moved into
B. used or occupied
C. altered
D. inhabited
303. The triangular openings at the open sides of a stair formed by the riser,
tread and bottom rail at the open side of a stairway shall be of a maximum size
such that a sphere of _____ inches in diameter cannot pass through the
opening.
87
A. 4
B. 6
C. 8
D. 10
304. Second-hand masonry units shall not be reused unless they conform to
the requirements ____________, and the units shall be of whole, sound
materials and free from cracks and other defects that will interfere with proper
laying or use and old mortar shall be cleaned from the unit before reuse.
A. of their original design
B. set by the designer
C. set for used masonry units.
D. of new units
305. In buildings constructed in accordance with the provisions of
conventional light-frame construction what is the maximum laterally
unsupported height (in feet) of a 2x4 stud in a nonbearing wall.
A. 10
B. 14
C. 16
D. 20
306. When the building official issues a permit, the construction documents
shall be approved, in writing or by stamp, as Reviewed for Code Compliance.
One set of construction documents so reviewed shall be retained by the
building official. The other set shall be returned to the applicant, shall be kept at
the site of work and shall be open to inspection by the building official or a duly
authorized representative.
A. Approved
B. Reviewed for Code Compliance.
C. Conditionally Approved
D. Authorization to Begin Work
88
89
311. The minimum slope for lapped, nonsoldered seam metal roofs without
applied lap sealant shall be __________ units vertical in 12 units horizontal.
A. 2
B. 3
C. 4
D. 5
312.
323. Concrete that will be exposed to freezing and thawing, deicing chemicals
or other exposure conditions shall be assigned to exposure classes in
accordance with _________.
A. ACI 1908
B. AICI 3180
C. GFRC 1903.2
D. ACI 318
324. In buildings constructed in accordance with the provisions of
conventional light-frame construction, roof trusses and rafters shall not span
more than ___________________ feet between points of vertical support.
A. 32
B. 40
C. 54
D. 60
325. Nonclassified roofing is approved material that is not listed as a
_______________ roof covering.
A. Class A
B. Class B
C. Class C
D. All of the above
326. Structural capacities and design provisions for prefabricated wood Ijoists shall be established and monitored in accordance with _____________.
A. APA 1016
B. APM standards
C. ASTM D 5055
D. FHA minimum standards
93
A. covered
B. finished
C. decorated
D. sheathed
331. Minimum uniformly distributed live loads used in design of a bowling
alley is _________ psf
A. 50
B. 60
C. 75
D. 100
332. Openings in wood shear panels that materially affect their strength shall
be fully detailed on the plans, and shall have their edges _______________ to
transfer all shearing stresses.
A. adequately reinforced
B. enforced
C. lined with steel
D. screwed
333. Where a fire wall also separates occupancies that are required to be
separated by a fire barrierwall, the __________________________________
requirements of each separation shall apply.
A. most restrictive
B. least restrictive
C. most cost effective
D. most fire resistive
334. Shower compartments and walls above bathtubs with installed shower
heads shall be finished with a smooth, nonabsorbent surface to a height not
less than _____________ above the drain inlet.
95
A. 70 inches
B. 6 feet
C. 72 inches
D. B and C
335. What is the REQUIRED SEPARATION OF OCCUPANCIES (HOURS)
between a Group A-1 and Group H-5? The Buildings are not equipped
throughout with an automatic sprinkler system.
A. 1
B. 2
C. 3
D. 4
336. In reference to Covered Mall Buildings. Mechanical rooms, electrical
rooms, building service areas are permitted to open directly into exit
passageways provided that the exit passageway is separated from such rooms
with ________________________________________
"A. not less than 2-hour fire-resistance-rated walls and minimum fire
protection rating of openings in the
fire barriers of 2-hours"
"B. not less than 1.5 -hour fire-resistance-rated walls and minimum fire
protection rating of openings in the
fire barriers of 1.5 -hours"
"C. not less than 1-hour fire-resistance-rated walls and minimum fire
protection rating of openings in the
fire barriers of 1-hour automatic opening doors."
"D. not less than 1-hour fire-resistance-rated walls and minimum fire
protection rating of openings in the
fire barriers of 1-hour"
337. Where a maximum one-story above grade plane Group S-2 parking
garage, en -closed or open, or combination thereof, of Type I construction or
open of Type IV construction, with grade entrance, is provided under a building
of Group R, the number of stories to be used in determining the minimum type
of construction shall be measured from
_________________________________.
96
342. Fire partitions shall have a fire-resistance rating of not less than
____________. Exceptions ignored.
A. 20 minutes
B. 1-hour
C. No fire-resistance rating
D. 2-hours
343. The provisions of this code shall be deemed to nullify any provisions of
local, state or federal law.
A. True
B. False
344. The minimum width of each means of egress door opening shall be
sufficient for the occupant load thereof and shall provide a clear width of not
less than _______ inches.
A. 24
B. 32
C. 36
D. 42
345. In reference to signage within Covered Mall Buildings. Plastic signs
shall not exceed a height of 36 inches, except if the sign is vertical, the height
shall not exceed _______ inches and the width shall not exceed 36 inches.
A. 120
B. 96
C. 72
D. 60
346. Flashing shall be installed in such a manner so as to prevent
_____________ entering the wall and roof through joints in copings, through
98
99
100
354.
355. Exterior fire-resistance rated walls shall have sufficient structural stability
such that they will _______________ for the duration of time indicated by the
required fire-resistance rating.
A. remain undamaged
B. remain in place
C. not burn through
D. not hold up
356. This code shall require changes in the construction documents,
construction or designated occupancy of a structure for which a lawful permit
has been heretofore issued or otherwise lawfully authorized, and the
construction of which has been pursued in good faith within 180 days after the
effective date of this code and has not been abandoned.
A. True
B. False
357. Shaft enclosures shall have a fire-resistance rating of not less than
____________ hours where connecting four stories or more, and not less than
1 hour where connecting less than four stories.
A. 2
B. 3
C. 4
D. 5
358. Cleaning establishments that utilize a liquid solvent having a flash point
at or above 200F (93C) has what group occupancy classification.
101
362. An area where persons unable to use stairways can remain temporarily
to await instructions or assistance during emergency evacuation.
102
A. balcony
B. area of refuge
C. fire escape
D. fire room
363. The exterior air outlet is permitted to be located in the back or sides of
the firebox chamber or within ________ inches of the firebox opening on or
near the floor. The outlet shall be closable and designed to prevent burning
material from dropping into concealed combustible spaces.
A. 24
B. 36
C. 48
D. 60
364. The following information is not required to be on a Certificate of
Occupancy:
A. The building permit number.
B. The address of the structure.
C. The name and address of the owner.
D. General Contractors name.
365. The minimum thickness of Stone (natural) on the exterior of a building is
________ inches.
A. 0.5
B. 1
C. 2
D. 3
366. Class III standpipe systems shall be installed throughout buildings where
the floor level of the highest story is located more than ____________ above
the lowest level of fire department vehicle access, or where the floor level of the
lowest story is located more than _____________ below the highest level of fire
department vehicle access. Exceptions ignored.
103
A. 50
B. 40
C. 30
D. 20
367.
368. Listed materials used as flue linings shall be installed in accordance with
the terms of their listings and the _______________________.
A. UL
B. contractor's experience
C. UBC
D. manufacturers instructions
369. In areas where there has been a history of ice forming along the eaves
causing a backup of water, an ice barrier that consists of at least two layers of
underlayment cemented together or of a self-adhering polymer modified
bitumen sheet shall be used in lieu of normal underlayment and extend from
the lowest edges of all roof surfaces to a point at least ____ inches inside the
exterior wall line of the building.
A. 12
B. 18
C. 24
D. 36
370. The construction documents shall include
______________________________ that provides supporting documentation
that the proposed penetration and opening details described in the construction
documents maintain the weather resistance of the exterior wall envelope. The
supporting documentation shall fully describe the exterior wall system which
was tested, where applicable, as well as the test procedure used.
104
105
A. 100
B. 500
C. 1000
D. 1500
375. The minimum horizontal area of the window well shall be 9 square feet,
with a minimum dimension of ________ inches. The area of the window well
shall allow the emergency escape and rescue opening to be fully opened.
A. 24
B. 30
C. 32
D. 36
376. Where parking is provided, how many accessible parking spaces shall
be provided at a facility that has 77 total parking spaces.
A. 4
B. 6
C. 8
D. 10
377. Footings for masonry fireplaces and their chimneys shall be constructed
of concrete or solid masonry at least _________ inches thick and shall extend
at least ______ inches beyond the face of the fireplace or foundation wall on all
sides. Footings shall be founded on natural undisturbed earth or engineered fill
below frost depth. In areas not subjected to freezing, footings shall be at least
12 inches below finished grade.
A. 10, 5
B. 6, 12
C. 12, 4
D. 12, 6
378. In fire walls, where combustible members frame into hollow walls or
walls of hollow units, hollow spaces shall be solidly filled for the full thickness of
the wall and for a distance not less than 4 inches
106
A. 8 feet
B. 7 feet 6 inches
C. 7 feet
D. 6 feet 8 inches
383. A room or space used for assembly purposes that is less than ________
square feet in area and is accessory to another occupancy shall be classified
as a Group B occupancy or as part of that occupancy.
A. 250
B. 500
C. 750
D. 1000
384. A reference plane representing the average of finished ground level
adjoining the building at exterior walls.
A. flood plane
B. maximum drainage plane
C. floor plane
D. grade plane
385. If it is necessary to make an inspection to enforce the provisions of this
code, or where the building official has ___________ __________ to believe
that there exists in a structure or upon a premises a condition which is contrary
to or in violation of this code which makes the structure or premises unsafe,
dangerous or hazardous, the building official is authorized to enter the structure
or premises at ___________ __________ to inspect or to perform the duties
imposed by this code, provided that if such structure or premises be occupied
that credentials be presented to the occupant and entry requested.
A. no reason, any time
B. a warrant, surprise times
C. reasonable cause, within 24 hrs.
D. reasonable cause, reasonable times
386. Class C roof assemblies are those that are effective against
_______________.
108
109
A. 0.25
B. 0.5
C. 1
D. 2
395. Mercantile Group M. Mercantile Group M occupancy includes, among
others, buildings and structures or a portion thereof, for the display and sale of
merchandise, and involves stocks of goods, wares or merchandise incidental to
such purposes and _________________________.
A. accessible to the public
B. private storage areas
C. for employee use only
D. no one admitted
396. In passenger transportation facilities and airports, the accessible route
from separate-sex toilet rooms to a unisex toilet room ___________ pass
through security checkpoints.
A. shall
B. shall not
C. may
D. must
397. The _____________ is authorized to waive the submission of
construction documents and other data not required to be prepared by a
registered design professional if it is found that the nature of the work applied
for is such that review of construction documents is not necessary to obtain
compliance with this code.
A. building permit
B. application
C. occupancy permit
D. construction documents
398. Walls within 2 feet of urinals and water closets shall have a smooth,
hard, nonabsorbent surface, to a height of _____________ feet above the floor,
111
and except for structural elements, the materials used in such walls shall be of
a type that is not adversely affected by moisture. Exceptions not considered.
A. 2
B. 3
C. 4
D. 5
399. Exit signs shall be illuminated at all times. To ensure continued
illumination for a duration of not less than _________ minutes in case of
primary power loss, the sign illumination means shall be connected to an
emergency power system provided from storage batteries, unit equipment or an
on-site generator. Exceptions ignored.
A. 30
B. 60
C. 90
D. 120
400. Where masonry chimneys are constructed as part of masonry or
concrete walls, combustible materials shall not be in contact with the masonry
or concrete wall less than _________ inches from the inside surface of the
nearest flue lining.
A. 2
B. 6
C. 12
D. 18
401. The building official is authorized to issue a permit for the construction of
foundations or any other part of a building or structure before the construction
documents for the whole building or structure have been submitted, provided
that adequate information and detailed statements have been filed complying
with pertinent requirements of this code. The IBC calls this kind of approval
_______________________.
A. "Pre-approval"
B. "Conditional approval"
C. "Temporary approval"
D. "Phased approval."
112
406. A-2 Assembly uses intended for food and/or drink consumption
including, but not limited to:
A. Courtrooms, Dance halls (not including food or drink consumption)
Exhibition halls
B. Motion picture theaters Symphony and concert halls Television and
radio studios admitting an audience Theaters
C. Banquet halls, Night clubs, Restaurants, Taverns and bars
D. Amusement arcades, Art galleries, Bowling alleys, Churches,
Community halls
407. Untreated wood is permitted where such wood is continuously and
entirely below the ground-water level or submerged in fresh water.
A. This is a True statement
B. This is a False statement
408. What interior wall and ceiling class finish is required in sprinklered rooms
and enclosed spaces of a Group A-4 occupancy?
A. A
B. B
C. C
A. 18 inches
B. 24 inches
C. 36 inches
D. 48 inches
415. Where egress doors are used in pairs, approved automatic flush bolts
shall be permitted to be used, provided that the door leaf having the automatic
flush bolts has no _____________ or surface-mounted hardware.
A. doorknob
B. keylock
C. hinge bolts
D. removable obstructions
416. What is the maximum span for a Southern Pine #1 2x12, floor joist, in a
residential sleeping area, with a dead load of 20 psf. The joists are spaced
19.2" OC.
A. 21 feet 2 in
B. 19 feet 6 in
C. 21 feet 6 in
D. 17 feet 8 in
417. The maximum deflection limit for roof members supporting a
nonplastered ceiling due to seismic or wind loads is:
A. l/360
B. l/240
C. l/180
D. l/400
418. Exit signs are not required in occupancies in Group U and individual
sleeping units or dwelling units in Group __________________.
A. R-1, R-2 or R-3
B. M, I-2
C. A-1, A-2
D. none of the above
116
419. Aerosols with a total chemical heat of combustion that is greater than
8,600 Btu/lb, but less than or equal to 13,000 Btu/lb.
A. Level 1 aerosol products.
B. Level 2 aerosol products.
C. Level 3 aerosol products.
D. Level 4 aerosol products.
420. All spaces between fireplaces and floors and ceilings through which
fireplaces pass shall be fireblocked with noncombustible material securely
fastened in place. The fireblocking of spaces between wood joists, beams or
headers shall be to a depth of ____ inch and shall only be placed on strips of
metal or metal lath laid across the spaces between combustible material and
the chimney.
A. 1
B. 2
C. 3
D. 4
421. What is the minimum thickness face-to-face required for a wall
constructed from solid gypsum plaster, studless with 1/2" full-length plain
gypsum lath and perlite or vermiculite gypsum plaster each side, to have a fire
resistance rating of 2 hours.
A. 2 inches
B. 2.5 inches
C. 3 inches
D. 3.5 inches
422. Interior wall and ceiling finishes shall be classified in accordance with
ASTM E 84 or UL 723 and these materials shall be grouped in the following
classes in accordance with their _______________________________
indexes.
117
428. Where elevator service in the building provides an accessible route only
to the lowest story containing dwelling or sleeping units intended to be occupied
as a residence, only the units on that story which are intended to be occupied
as a residence are required to be __________ units.
A. Type A
B. Type B
C. Type C
D. Type D
429. What is the allowable height and area of a Group F-2 building of Type
IIIB Construction
A. 2 Stories , 18,000 SF
B. 3 Stories , 18,000 SF
C. 4 Stories , 36,000 SF
D. 5 Stories , 40,000 SF
430. Elementary materials required to be noncombustible shall be tested in
accordance with _________________.
A. ASTM E 134
B. ASTM E 135
C. ASTM E 136
D. ASTM E 137
119
431. Every dwelling unit shall have at least one room that shall have not less
than 120 square feet of net floor area. Other habitable rooms shall have a net
floor area of not less than 70 square feet except for
______________________.
A. living rooms
B. bedrooms
C. kitchens
D. dens
432. Assembly areas with less than ___________ square feet (69.7 m2) and
which are accessory to another occupancy according to Section 302.2.1 are not
assembly occupancies.
A. 250
B. 500
C. 750
D. 1000
433. Exterior fire-resistance rated walls shall extend to the height required by
____________________ and shall have sufficient structural stability such that it
will remain in place for the duration of time indicated by the required fireresistance rating.
A. Section 703.10
B. Section 705.11
C. Section 706.12
D. Section 708.13
434. Aerosol storage rooms and general-purpose warehouses containing
aerosols shall be provided with an approved _____________ fire alarm system
where required by the International Fire Code.
A. manual
B. automatic
C. remote controlled
D. fume activated
120
435. Door handles, pulls, latches, locks and other operating devices shall be
installed ______ inches minimum and ______ inches maximum above the
finished floor.
A. 30, 40
B. 34, 48
C. 34, 42
D. 36, 48
436. In Heavy Timber Construction, floor decks and covering shall not extend
closer than ___________ inch to walls. Such ________ inch spaces shall be
covered by a molding fastened to the wall either above or below the floor and
arranged such that the molding will not obstruct the expansion or contraction
movements of the floor.
A. .5, .5
B. .25, .25
C. 1, 1
D. 0.75, .75
437. In buildings constructed in accordance with the provisions of
conventional light-frame construction studs shall be placed with their wide
dimension perpendicular to the wall. Not less than __________ studs shall be
installed at each corner of an exterior wall.
A. 2
B. 3
C. 4
D. 5
438.
443. Revolving doors shall not be given credit for more than ________
percent of the required egress capacity.
A. 30
B. 40
C. 50
D. 60
444. When it is required that documents be prepared by a
________________________, the building official shall be authorized to
require the owner to engage and designate on the building permit application a
_______________________ who shall act as the registered design
professional in responsible charge.
A. civil engineer
B. general contractor
C. registered design professional
D. code compliance engineer
445. The unobstructed width of pedestrian walkways shall not be less than
inches. The total width shall not exceed _____ feet.
A. 32, 24
B. 36, 30
C. 42, 25
D. 44, 30
446. Dead ends not exceeding a length equal to twice the width of the mall
measured at the narrowest location within the dead-end portion of the mall are
not required be a minimum of 66 inches wide.
A. This statement is True for Covered Mall Buildings
B. This statement is False for Covered Mall Buildings
C. This statement is always False for Covered Mall Buildings
D. This statement is False for all commercial buildings
123
447. Where used in monolithic glazing systems are used in sloped glazing
and skylights. Screens shall not be required within individual dwelling units in
______________________ as applicable in Section 101.2 where fully
tempered glass is used as single glazing or as both panes in an insulating glass
unit, certain other criteria are met.
A. Groups A-1 and A-2
B. Group E
C. Groups I-2 and I-3
D. Groups R-2, R-3 and R-4
448. The stopping of leaks in drains, water, soil, waste or vent pipe provided,
however, that if any concealed trap, drain pipe, water, soil, waste or vent pipe
becomes defective and it becomes necessary to remove and replace the same
with new material, such work shall be considered as new work and a permit
shall be obtained and inspection made as provided in this code.
A. True
B. False
449. Curved stairways with winder treads must have treads and risers in
accordance with Section 1009.3 and the smallest radius shall not be less than
________ the required width of the stairway.
A. 1.5 times
B. 2 times
C. 3 times
D. 4 times
450. The use of a building or structure, or portion thereof, for educational,
supervision or personal care services for more than five children older than
_________________ years of age, shall be classified as a Group E occupancy.
A. 2.5
B. 5
C. 12
D. 17
124
459. Approved fire door and fire shutter assemblies shall be constructed of
______________ or assembly of component materials that conforms to the test
126
A. moisture barrier
B. seal
C. vapor retarder
D. ground cover
464. In concrete construction, exposed reinforcement, inserts and plates
intended for bonding with future extensions shall be
_______________________.
A. non-corrosive
B. aluminum
C. stainless steel
D. protected from corrosion
465. Water-resistant gypsum backing board shall not be used where there will
be direct exposure to __________ or in areas subject to continuous high
humidity.
A. heat
B. water
C. air conditioning
D. fumes
466. A wood structural panel that is a mat-formed product composed of thin
rectangular wood strands or wafers arranged in oriented layers.
A. plywood
B. oriented strand board
C. plycore
D. particle board
467. Concrete to be placed during freezing or near-freezing weather shall
___________________________.
A. be heated by the use of heat Lamps
B. comply with the requirements of ACI 318, Section 5.12.
C. be heated by the use straw insulation
D. be heated by the use warming ovens
128
A. UL
B. building inspector as the
C. general contractor
D. substitute
472. A vertical assembly of materials designed to restrict the spread of fire in
which openings are protected.
A. fire door assembly
B. fire partition
C. fire barrier
D. fire stop
473. Arenas, Skating rinks, Swimming pools & Tennis courts are examples of
what Group of Occupancy.
A. A-2
B. A-3
C. A-4
D. A-5
474. In conventional light-frame construction, the spacing of braced wall lines
shall not exceed ____________ o.c. in both the longitudinal and transverse
directions in each story.
A. 28 feet (8 534 mm)
B. 32 feet (9 754 mm)
C. 35 feet (10 668 mm)
D. 40 feet (12 192 mm)
475. Means of egress. Each tenant space and the covered mall building shall
be provided with means of egress as required by this section and this code.
Where there is a conflict between the requirements of this code and the
requirements of this section, _________________________________
A. the requirements of this code shall apply.
B. the requirements of this section shall apply.
C. the requirements of this section shall be void.
D. the requirements of this section shall not apply.
130
132
488. Foam plastic used as trim in any occupancy shall comply with
_____________.
A. Section 2703.1
B. Section 2607.0
C. Section 2504.1
D. Section 2604.2
489. In Type I and II construction, The use of combustible piping materials
shall be permitted when installed in accordance with the limitations of the
_____________________________________________________________.
A. International Mechanical Code and the International Plumbing Code
B. UBC
C. NFPA
D. Plumbing Pipe Association of America
490. Every occupied portion of any occupancy in Group A or assembly
occupancies accessory to Group E that contains seats, tables, displays, similar
fixtures or equipment shall be provided with
__________________________________.
A. open ceiling areas and skylights
B. aisles leading to exits or exit access doorways
C. natural lighting
D. at least 3 means of egress
491. The thickness of concrete floor slabs supported directly on the ground
shall not be less than ___________ inches. Exceptions ignored.
A. 3
B. 3.5
C. 4
D. 4.5
134
492. Fire walls shall extend from the foundation to a termination point at least
___ inches above both adjacent roofs. Exceptions Ignored.
A. 10
B. 20
C. 30
D. 40
493. Shaft enclosures shall have a fire-resistance rating of not less than 2
hours where connecting four stories or more, and not less than 1 hour where
connecting less than four stories. The number of stories connected by the shaft
enclosure shall include any basements but not any mezzanines. Shaft
enclosures shall have a fire-resistance rating not less than the floor assembly
penetrated, but need not exceed ________ hours.
A. 2
B. 3
C. 4
D. 5
494. A single unit providing complete, independent living facilities for one or
more persons, including permanent provisions for living, sleeping, eating,
cooking and sanitation.
A. Dormitory
B. Dwelling Unit
C. Boarding House
D. Residential Care/Assisted Living Facility
495. Each portion of a building separated by one or more fire walls that
comply with the provisions of the fire wall section of this code shall be
considered ______________________, and the extent and location of such fire
walls shall provide a complete separation.
A. a separate room
B. a separate partition
C. a separate building
D. a separate fire zone
135
496. Where more than one exit is required, they shall be so arranged that it is
possible to travel in either direction from any point in a mall to separate exits
and the minimum width of an exit passageway or corridor from a mall shall be
____________________________.
A. 144 inches
B. 100 inches
C. 42 inches
D. 66 inches
497. The building official is authorized to, in writing, suspend or revoke a
certificate of occupancy or completion issued under the provisions of this code
wherever the certificate is issued in error, or on the basis of incorrect
information supplied, or where it is determined that the building or structure or
portion thereof is in _____________ of any ordinance or regulation or any of
the provisions of this code.
A. violation
B. compliance
C. partial compliance
D. direct compliance
498. The minimum thickness of gypsum wallboard is _______________ with
a maximum wall stud spacing of ______________.
A. .5, 16
B. .625, 16
C. .5, 19.2
D. .5, 24
499. What is the allowable height and area of a Group M building of Type I-A
Construction
A. 5 Stories , 40,000 SF
B. 50 Stories , 500,000 SF
C. 100 Stories , 1,140,000 SF
D. Unlimited , Unlimited
136
500. The holder of a "phased approval" permit for the foundation or other
parts of a building or structure shall proceed at the __________ risk with the
building operation and without assurance that a permit for the entire structure
will be granted.
A. holders
B. owners
C. contractors
D. building officials
137
Section 2
Timed Exams
Each exam has 80 Questions, there are 6 exams with the questions in random
order.
Time yourself, allow yourself 3 1/2 hours to complete each exam. This will
develop your time management skills as well as giving you review knowledge
and lookup practice.
138
Timed Exam 1
A. 3
B. 4
C. 6
D. 8
Timed Exam 1- 8. The minimum depth of footings below the undisturbed
ground surface shall be __________ inches.
A. 6
B. 12
C. 18
D. 24
140
Timed Exam 1- 9. The maximum deflection limit for roof members supporting
a nonplastered ceiling due to seismic or wind loads is:
A. l/360
B. l/240
C. l/180
D. l/400
Timed Exam 1- 10. A permit shall not be valid until:
A. they are stamped by a licensed design professional.
B. the fees prescribed by law have been paid, nor shall an amendment
to a permit be released until the additional fee, if any, has been paid.
C. the building inspector has indicated to you to begin work.
D. all documents are approved by the Board of Review.
Timed Exam 1- 11. 305.1 Educational Group E. Educational Group E
occupancy includes, among others, the use of a building or structure, or a
portion thereof, by six or more persons at any one time for educational
purposes through the ______________.
A. 8th Grade
B. 12th Grade
C. College
D. Vocational School
Timed Exam 1- 12. Where used in monolithic glazing systems are used in
sloped glazing and skylights. Screens shall not be required within individual
dwelling units in ______________________ as applicable in Section 101.2
where fully tempered glass is used as single glazing or as both panes in an
insulating glass unit, certain other criteria are met.
A. Groups A-1 and A-2
B. Group E
C. Groups I-2 and I-3
D. Groups R-2, R-3 and R-4
141
Timed Exam 1- 13. An exit component that is separated from other interior
spaces of a building or structure by fire-resistance-rated construction and
opening protectives, and provides for a protected path of egress travel in a
horizontal direction to the exit discharge or the public way.
A. exit passageway
B. exit enclosure
C. exit access
D. exit discharge
Timed Exam 1- 14. Exit signs are not required in occupancies in Group U and
individual sleeping units or dwelling units in Group __________________.
A. R-1, R-2 or R-3
B. M, I-2
C. A-1, A-2
D. none of the above
Timed Exam 1- 15. Handrail assemblies and guards shall be designed to resist
a load of __________ plf applied in any direction at the top and to transfer this
load through the supports to the structure. Exceptions ignored.
A. 25
B. 50
C. 75
D. 100
Timed Exam 1- 16. Guards shall be provided where appliances, equipment,
fans, roof hatch openings or other components that require service are located
within ________ feet (3048 mm) of a roof edge or open side of a walking
surface and such edge or open side is located more than _______ inches (762
mm) above the floor, roof or grade below.
A. 10, 48
B. 8, 30
C. 8, 24
D. 10, 30
142
143
Timed Exam 1- 21. Sprinklered, one story. The area of a one-story, Group
___________ building or a one-story Group A-4 building of other than Type V
construction shall not be limited when the building is provided with an automatic
sprinkler system throughout in accordance with Section 903.3.1.1, and is
surrounded and adjoined by public ways or yards not less than 60 feet in width.
A. B
B. F
C. M or S
D. any of those above
Timed Exam 1- 22. Building, structures and parts thereof shall be designed
and constructed in accordance with strength design, load and
_______________________, allowable stress design, empirical design or
conventional construction methods, as permitted by the applicable material
chapters.
A. interpretative analysis
B. soil bearing methods
C. lateral vertical load factors
D. resistance factor design
Timed Exam 1- 23. Shaft enclosures shall have a fire-resistance rating of not
less than ____________ hours where connecting four stories or more, and not
less than 1 hour where connecting less than four stories.
A. 2
B. 3
C. 4
D. 5
Timed Exam 1- 24. The thickness of concrete floor slabs supported directly on
the ground shall not be less than ___________ inches. Exceptions ignored.
A. 3
B. 3.5
C. 4
D. 4.5
144
146
Timed Exam 1- 33. A statement that the described portion of the structure has
been inspected for compliance with the requirements of this code for the
occupancy and division of occupancy and the use for which the proposed
occupancy is classified is required to be found on the:
A. Permit Application
B. Certificate of Occupancy
C. Building Documents
D. Request for Appeal
Timed Exam 1- 34. A listed device installed in a ceiling membrane of a fireresistance-rated floor/ceiling or roof/ceiling assembly to limit automatically the
radioactive heat transfer through an air inlet/outlet opening.
A. draft block
B. draft stop
C. ceiling radiation damper
D. fire stop
Timed Exam 1- 35. Structures or existing equipment that are or hereafter
become unsafe, unsanitary or deficient because of inadequate means of egress
facilities, inadequate light and ventilation, or which constitute a fire hazard, or
are otherwise dangerous to human life or the public welfare, or that involve
illegal or improper occupancy or inadequate maintenance, shall be deemed an
unsafe condition. Unsafe structures shall be
______________________________________, as the building official deems
necessary and as provided for in this section. A vacant structure that is not
secured against entry shall be deemed unsafe.
A. imploded
B. immediately removed without exception
C. seized by the federal government and sold to the highest bidder.
D. taken down and removed or made safe
Timed Exam 1- 36. Press boxes in assembly areas shall be on an accessible
route. An accessible route shall not be required to press boxes in bleachers
that have points of entry at only one level, provided that the aggregate area of
all press boxes is ___________ square feet maximum.
147
A. 100
B. 500
C. 1000
D. 1200
Timed Exam 1- 37. In reference to Covered Mall Buildings. Fire-resistancerated separation _________ required between tenant spaces and the mall.
Fire-resistance-rated separation is not required between a food court and
adjacent tenant spaces or the mall.
A. is not
B. of 1 Hr. is
C. of 2 Hr. is
D. of 3 Hr. is
Timed Exam 1- 38. Adobe units shall have a moisture content not exceeding
_____ percent by weight.
A. 10
B. 15
C. 8
D. 4
Timed Exam 1- 39. A Single Family Home is and example of what occupancy
group?
A. R-1
B. R-2
C. R-3
D. R-4
Timed Exam 1- 40. In Assembly seating the aisle width shall provide sufficient
egress capacity for the number of persons accommodated by the
____________ area served by the aisle.
A. building
B. seating
C. open
D. catchment
148
Timed Exam 1- 41. Flexible ducts and air connectors shall not pass through
any fire-resistance-rated assembly. Flexible air connectors shall not pass
through any _______________________________.
A. wall
B. ceiling
C. floor
D. all the above.
Timed Exam 1- 42. Where installed and fireblocked to comply with Chapter 7,
fiberboards are permitted as wall insulation in all types of construction. In fire
walls and fire barriers, unless treated to comply with Section 803.1 for Class A
materials, the boards shall be cemented directly to the concrete, masonry or
other noncombustible base and shall be protected with an approved
noncombustible veneer anchored to the base without ________________.
A. causing excessive load
B. the use of fasteners
C. intervening airspaces
D. the need for additional insulation
Timed Exam 1- 43. Fire department glass access panels shall be of
____________ glass. For insulating glass units, all panes shall be tempered
glass.
A. double strength
B. tempered
C. shatterproof
D. beveled
Timed Exam 1- 44. What is the allowable height and area of a Group H-1
building of Type V-B Construction
A. 2 Stories , 18,000 SF
B. 3 Stories , 18,000 SF
C. Not Permitted
D. 5 Stories , 40,000 SF
149
150
Timed Exam 1- 49. The period of time that an opening protective will maintain
the ability to confine a fire as determined by tests prescribed in Section 715.
Ratings are stated in hours or minutes.
A. Fire Protection Rating
B. Fire Barrier Time
C. Firestop Time
D. Fireblocking Time
Timed Exam 1- 50. Cabinets containing fire-fighting equipment such as
standpipes, fire hoses, fire extinguishers or fire department valves can not be
_______________ or obscured from view.
A. installed in public view
B. painted yellow
C. blocked from use
D. behind glass doors
Timed Exam 1- 51. What is the minimum thickness face-to-face required for a
wall constructed from solid gypsum plaster, studless with 1/2" full-length plain
gypsum lath and perlite or vermiculite gypsum plaster each side, to have a fire
resistance rating of 2 hours.
A. 2 inches
B. 2.5 inches
C. 3 inches
D. 3.5 inches
Timed Exam 1- 52. Revolving doors shall not be given credit for more than
________ percent of the required egress capacity.
A. 30
B. 40
C. 50
D. 60
Timed Exam 1- 53. The provisions of this code shall be deemed to nullify any
provisions of local, state or federal law.
151
A. True
B. False
Timed Exam 1- 54. When the total volume of a given class of concrete is less
than 50 cubic yards, strength tests are not required when
_______________________________________________________________
________.
A. the final cure strength is over 2500 psi.
B. the final cure strength is over 3000 psi.
C. the final cure strength is over 3500 psi.
D. evidence of satisfactory strength is submitted to and approved by the
building official
Timed Exam 1- 55. Stairways must have handrails on _________. Exceptions
ignored.
A. each side
B. on the right side going down
C. on the right side going up
D. on the left side going down
Timed Exam 1- 56. What interior wall and ceiling class finish is required in nonsprinklered exit enclosures and exit passageways of a Group I-3 occupancy?
A. A
B. B
C. C
Timed Exam 1- 57. The following are all required inspections except:
A. Frame inspection.
B. Footing and foundation inspection.
C. Final inspection.
152
Timed Exam 1- 66. The building official is authorized to issue a permit for the
construction of foundations or any other part of a building or structure before
the construction documents for the whole building or structure have been
submitted, provided that adequate information and detailed statements have
been filed complying with pertinent requirements of this code. The IBC calls
this kind of approval _______________________.
A. "Pre-approval"
B. "Conditional approval"
C. "Temporary approval"
D. "Phased approval."
Timed Exam 1- 67. The minimum horizontal area of the window well shall be 9
square feet, with a minimum dimension of ________ inches. The area of the
window well shall allow the emergency escape and rescue opening to be fully
opened.
A. 24
B. 30
C. 32
D. 36
Timed Exam 1- 68. Occupant formula. In determining required means of
egress of the mall, the number of occupants for whom means of egress are to
be provided shall be based on
____________________________________________ and the occupant load
factor as determined by the equation listed in this section.
A. gross leasable area of the covered mall building (including anchor
buildings)
B. gross leasable area of the covered mall building and the anchor
building area added together.
C. gross total area of the covered mall building (excluding anchor
buildings)
D. gross leasable area of the covered mall building (excluding anchor
buildings)
155
157
158
159
Timed Exam 2
Timed Exam 2- 13. In Heavy Timber Construction, floor decks and covering
shall not extend closer than ___________ inch to walls. Such ________ inch
spaces shall be covered by a molding fastened to the wall either above or
below the floor and arranged such that the molding will not obstruct the
expansion or contraction movements of the floor.
A. .5, .5
B. .25, .25
C. 1, 1
D. 0.75, .75
Timed Exam 2- 14. Fasteners used for the attachment of gypsum board to a
horizontal diaphragm ceiling shall be spaced not more than ____ inches on
center (o.c.) at all supports, including perimeter blocking, and not more than
____ inch from the edges and ends of the gypsum board.
A. 4, .5
B. 7, .375
C. 9, .375
D. 10, .5
Timed Exam 2- 15. An exterior perimeter building of a group other than H
having direct access to a covered mall building but having required means of
egress independent of the mall.
A. Food Court
B. Anchor Building
C. Covered Mall Building
D. Gross Leas able Area
Timed Exam 2- 16. Habitable spaces, other than a kitchen, shall not be less
than ________ feet in any plan dimension.
A. 6
B. 7
C. 8
D. 9
163
Timed Exam 2- 17. What interior wall and ceiling class finish is required in
sprinklered rooms and enclosed spaces of a Group A-4 occupancy?
A. A
B. B
C. C
Timed Exam 2- 18. Exit signs shall be illuminated at all times. To ensure
continued illumination for a duration of not less than _________ minutes in
case of primary power loss, the sign illumination means shall be connected to
an emergency power system provided from storage batteries, unit equipment or
an on-site generator. Exceptions ignored.
A. 30
B. 60
C. 90
D. 120
Timed Exam 2- 19. Where required in the code, doors in smoke partitions shall
be _____________________________________________.
A. a minimum of 24 inches wide
B. made of non-combustible material
C. self-closing or automatic-closing
D. steel or wood with a gypsum core.
Timed Exam 2- 20. The construction documents shall show in sufficient detail
the location, construction, size and character of all portions of the means of
egress in compliance with the provisions of this code. In other than
occupancies in ______________, as applicable in Section 101.2, and I-1, the
construction documents shall designate the number of occupants to be
accommodated on every floor, and in all rooms and spaces.
A. Groups I-2, I-3
B. Groups R-2, R-3
C. Groups E-2
D. Groups U-2, U-3
164
Timed Exam 2- 21. Where wood structural panel sheathing is used as the
exposed finish on the exterior of outside walls, it shall
________________________.
A. be adequately painted
B. coated with 2 full coats of Thompson's Water Seal
C. have an exterior exposure durability classification.
D. not be considered as a structural component for load calculations
Timed Exam 2- 22. In a covered mall building, there shall be a minimum of
________ feet clear exit width to a height of 8 feet between any projection of a
tenant space bordering the mall and the nearest kiosk, vending machine,
bench, display opening, food court or other obstruction to means of egress
travel.
A. 8
B. 10
C. 12
D. 14
Timed Exam 2- 23. What is the fire resistance rating requirement for primary
structural frame including columns, girders, trusses in a type V-B structure.
A. 0
B. 1
C. 2
D. HT
Timed Exam 2- 24. Glazing in fixed and sliding panels of sliding door
assemblies and panels in sliding and bifold closet door assemblies
_________________.
A. is not allowed
B. must be double glazed
C. is considered a hazardous location installation
D. must be unbreakable
165
Timed Exam 2- 25. Where used in monolithic glazing systems are used in
sloped glazing and skylights, heat-strengthened glass and fully tempered glass
shall have screens installed __________ the glazing material.
A. inside
B. above
C. below
D. within
Timed Exam 2- 26. Clay flue liners shall be installed in accordance with ASTM
C 1283. The lining shall be carried up vertically, with a maximum slope no
greater than ______ degrees from the vertical.
A. 10
B. 20
C. 30
D. 45
Timed Exam 2- 27. Flue liners shall be installed in accordance with ASTM C
1283 and extend from a point not less than ______________ inches below the
lowest inlet or, in the case of fireplaces, from the top of the smoke chamber, to
a point above the enclosing walls.
A. 6
B. 8
C. 12
D. 16
Timed Exam 2- 28. In buildings constructed in accordance with the provisions
of conventional light-frame construction floor, attic and roof framing with a
nominal depth-to-thickness ratio greater than or equal to 5:1 shall have one
edge held in line for the ______________.
A. 50 % of the span
B. entire span
C. length of the building
D. length of the cantilever
166
Timed Exam 2- 29. The maximum capacity required from any story of a
building shall be maintained to the _________ of the means of egress.
A. termination
B. maximum opening
C. minimum opening
D. none of these
Timed Exam 2- 30. Aerosols with a total chemical heat of combustion that is
greater than 8,600 Btu/lb, but less than or equal to 13,000 Btu/lb.
A. Level 1 aerosol products.
B. Level 2 aerosol products.
C. Level 3 aerosol products.
D. Level 4 aerosol products.
Timed Exam 2- 31. Cement used to produce concrete shall comply
with_______________________.
A. CPI, Section 801.90
B. ACI 318
C. NACA 318.90
D. CIA, Section 405
Timed Exam 2- 32. A single unit providing complete, independent living
facilities for one or more persons, including permanent provisions for living,
sleeping, eating, cooking and sanitation.
A. Dormitory
B. Dwelling Unit
C. Boarding House
D. Residential Care/Assisted Living Facility
Timed Exam 2- 33. The width of stairways shall be determined as specified in
Section 1005.1, but such width shall not be less than _____ inches. Exceptions
ignored.
167
A. 32
B. 40
C. 44
D. 50
Timed Exam 2- 34. Exits shall discharge directly to the exterior of the building.
The exit discharge shall be at grade or shall provide direct access to grade. The
exit discharge shall not _________ a building.
A. leave
B. go under
C. reenter
D. go over
Timed Exam 2- 35. If a self-service storage facility has 208 individual selfstorage spaces how many accessible self-storage facilities are required.
A. 5%, but not less than 1
B. 10, plus 2% of total number of units over 200
C. 5, plus 2% of total number of units over 100
D. 8, plus 1% of total number of units over 200
Timed Exam 2- 36. For open valleys (valley lining exposed) lined with metal,
the valley lining shall be at least ______________ inches wide and of any of
the corrosion-resistant metals in Table 1507.2.9.2.
A. 16
B. 20
C. 24
D. 28
Timed Exam 2- 37. Non separated occupancies shall be individually classified
in accordance with Section 302.1. The requirements of the IBC code shall apply
to each portion of the building based on the occupancy classification of that
space except that the most _________ applicable provisions of Section 403
and Chapter 9 shall apply to the building or portion thereof in which the no
separated occupancies are located.
168
A. restrictive
B. convenient
C. lenient
D. none of the above
Timed Exam 2- 38. Untreated wood is permitted where such wood is
continuously and entirely below the ground-water level or submerged in fresh
water.
A. This is a True statement
B. This is a False statement
Timed Exam 2- 39. Automatic dampers, regardless of the purpose for which
they are installed within the smoke control system, shall be __________ and
conform to the requirements of approved, recognized standards.
A. listed
B. tested
C. visible
D. opened
Timed Exam 2- 40. Exit signs are not required in ________________ in
occupancies in Group I-3.
A. sleeping areas
B. conference areas
C. office areas
D. hallways
Timed Exam 2- 41. Curved stairways with winder treads must have treads and
risers in accordance with Section 1009.3 and the smallest radius shall not be
less than ________ the required width of the stairway.
A. 1.5 times
B. 2 times
C. 3 times
169
D. 4 times
Timed Exam 2- 42. Mineral-surfaced roll roofing shall not be applied on roof
slopes below _________ unit vertical in 12 units horizontal.
A. 0.25
B. 0.5
C. 1
D. 2
Timed Exam 2- 43. An enclosed space extending through one or more stories
of a building, connecting vertical openings in successive floors, or floors and
roof.
A. atrium
B. shaft
C. stairwell
D. chute
Timed Exam 2- 44. Fire-retardant-treated lumber and wood structural panels
shall be ___________.
A. UL Listed
B. labeled
C. factory applied
D. used in Class A construction
Timed Exam 2- 45. In buildings constructed in accordance with the provisions
of conventional light-frame construction, spacing of edge nailing for required
wall bracing shall not exceed _______ inches o.c. along the foundation plate
and the top plate of the cripple wall.
A. 4
B. 6
C. 8
D. 10
170
Timed Exam 2- 46. Sleepers and sills on a concrete or masonry slab that is in
direct contact with earth shall be of ________________ or preservative-treated
wood.
A. pressure treated
B. creosote
C. green
D. naturally durable
Timed Exam 2- 47. There must be a floor or landing on each side of a door.
Such floor or landing must be at the same elevation on each side of the door.
Landings shall be level except for exterior landings, which are permitted to have
a slope not to exceed ____________________________. Exceptions ignored.
A. 0.125 unit vertical in 12 units horizontal
B. 0.5 unit vertical in 12 units horizontal
C. 0.25 unit vertical in 12 units horizontal
D. 1 unit vertical in 12 units horizontal
Timed Exam 2- 48. In buildings constructed in accordance with the provisions
of conventional light-frame construction, in nonbearing walls and partitions,
studs shall be spaced not more than ___________ inches o.c. and are
permitted to be set with the long dimension parallel to the wall.
A. 19.2
B. 24
C. 28
D. 32
Timed Exam 2- 49. Where more than one smoke alarm is required to be
installed within an individual dwelling unit in Group R-2, R-3 or R-4, or within an
individual dwelling unit or sleeping unit in Group R-1, the smoke alarms shall be
_____________________ in such a manner that the activation of one alarm will
activate all of the alarms in the individual unit.
A. installed
B. separated
C. transmitted
D. interconnected
171
172
Timed Exam 2- 54. Every space intended for human occupancy shall be
provided with natural light by means of exterior glazed openings which shall
open directly onto a public way or onto a yard or court. The minimum net
glazed area shall not be less than _____ percent of the floor area of the room
served.
A. 4
B. 6
C. 8
D. 10
Timed Exam 2- 55. Construction in which the exterior load-bearing and
nonload-bearing walls and partitions are of unfired clay masonry units, and
floors, roofs and interior framing are wholly or partly of wood or other approved
materials.
A. Masonry Construction
B. Adobe Construction.
C. Mud Construction
D. Gypsum Construction
Timed Exam 2- 56. Fire partitions shall have a fire-resistance rating of not less
than ____________. Exceptions ignored.
A. 20 minutes
B. 1-hour
C. No fire-resistance rating
D. 2-hours
Timed Exam 2- 57. As applied to a fire door or other opening, means equipped
with an approved device that will ensure closing after having been opened.
A. automatic
B. self-closing
C. motorized
D. self-automated
173
174
Timed Exam 2- 62. Assembly areas with less than ___________ square feet
(69.7 m2) and which are accessory to another occupancy according to Section
302.2.1 are not assembly occupancies.
A. 250
B. 500
C. 750
D. 1000
Timed Exam 2- 63. Construction documents for all buildings shall describe the
exterior wall envelope in sufficient detail to determine
_______________________.
A. the basic elements of construction.
B. if more bracing is needed in high wind areas.
C. if more the building is exempt from the code.
D. compliance with this code.
Timed Exam 2- 64. In concrete construction, exposed reinforcement, inserts
and plates intended for bonding with future extensions shall be
_______________________.
A. non-corrosive
B. aluminum
C. stainless steel
D. protected from corrosion
Timed Exam 2- 65. A permit shall not be required for the installation, alteration
or repair of generation, transmission, distribution or metering or other related
equipment that is under the ownership and control
________________________________________.
A.
B.
C.
D.
175
Timed Exam 2- 66. The face of an exit sign illuminated from an external source
shall have an intensity of not less than ___ foot-candles.
A. 1
B. 3
C. 5
D. 8
Timed Exam 2- 67. In new construction, required smoke alarms shall receive
their primary power from the building wiring where such wiring is served from a
commercial source and shall be equipped with a ______________. Exceptions
ignored.
A. battery backup
B. secondary power system
C. emergency lighting system
D. power saver system
Timed Exam 2- 68. In Type IV Construction, wood columns shall be sawn or
glued laminated and shall not be less than 8 inches, nominal, in any dimension
where supporting floor loads and not less than ___ inches nominal in width and
not less than ___ inches nominal in depth where supporting roof and ceiling
loads only. Columns shall be continuous or superimposed and connected in an
approved manner.
A. 6, 6
B. 6, 7
C. 6, 8
D. 6, 9
Timed Exam 2- 69. A manual fire alarm system and an automatic fire detection
system shall be installed in Group I occupancies. An automatic smoke
detection system shall be provided in_________________________________.
Exceptions ignored.
A. all rooms over 1000 square ft.
B. in accordance with Sections 907.2.6.1 and 907.2.6.2
C. every intersection of hallways
D. every dead end hallway
176
177
Timed Exam 2- 74. A permit issued shall become invalid unless the work on
the site authorized by such permit is commenced within ____________ after its
issuance, or if the work authorized on the site by such permit is suspended or
abandoned for a period of ______________ after the time the work is
commenced. The building official is authorized to grant, in writing, one or more
extensions of time, for periods not more than ____________ each.
A. 180 days, 180 days, 180 days
B. 365 days, 180 days, 180 days
C. 270 days, 2 years, 2 years
D. 2 years, 2 years, 180 days
Timed Exam 2- 75. Light-transmitting plastics shall be permitted as glazing in
shower stalls, shower doors, bathtub enclosures and similar accessory units.
Safety glazing shall be provided in accordance with _____________.
A. Chapter 24
B. Chapter 30
C. Chapter 36
D. Chapter 42
Timed Exam 2- 76. Posts or columns. Posts or columns supporting permanent
structures and supported by a concrete or masonry slab or footing that is in
direct contact with the earth shall be of _______________ or preservativetreated wood. Exceptions ignored.
A. Fir
B. Cedar
C. Redwood
D. naturally durable
Timed Exam 2- 77. The building official is authorized to, in writing, suspend or
revoke a certificate of occupancy or completion issued under the provisions of
this code wherever the certificate is issued in error, or on the basis of incorrect
information supplied, or where it is determined that the building or structure or
portion thereof is in _____________ of any ordinance or regulation or any of
the provisions of this code.
178
A. violation
B. compliance
C. partial compliance
D. direct compliance
Timed Exam 2- 78. Exit signs are not required in rooms or areas which require
_________________ exit or exit access.
A. only 1
B. only 2
C. only 3
D. only 4
Timed Exam 2- 79. The construction documents submitted with the application
for permit shall be accompanied by a ____________ showing to scale the size
and location of new construction and existing structures on the site, distances
from lot lines, the established street grades and the proposed finished grades
and, as applicable, flood hazard areas, floodways, and design flood elevations;
and it shall be drawn in accordance with an accurate boundary line survey.
A. site plan
B. survey plan prepared by a Civil Engineer
C. a real view
D. environmental impact statement and plan
Timed Exam 2- 80. In buildings constructed in accordance with the provisions
of conventional light-frame construction, where the nominal depth-to-thickness
ratio of the framing member exceeds 6:1, there shall be one line of bridging for
each 8 feet of span, unless both edges of the member are held in line. The
bridging shall consist of not less than ______________________ lumber,
double nailed at each end, of equivalent metal bracing of equal rigidity, fulldepth solid blocking or other approved means.
A. 1-inch by 3-inch
B. 1-inch by 2-inch
C. 2-inch by 3-inch
D. 2-inch by 4-inch
179
Timed Exam 3
Timed Exam 3- 1.
Classification?
A. A-1
B. I-1
C. I-2
D. I-3
Timed Exam 3- 2. Exit sign placement shall be such that no point an exit
access corridor or exit passageway is more than _____________ feet or the
listed viewing distance for the sign, whichever is less, from the nearest visible
exit sign. Exceptions ignored.
A. 50
B. 100
C. 150
D. 200
Timed Exam 3- 3. The building official shall be rendered liable personally and
is hereby assigned personal liability for any damage accruing to persons or
property as a result of any act or by reason of an act or omission in the
discharge of official duties.
A. True
B. False
Timed Exam 3- 4. Where a fire wall also separates occupancies that are
required to be separated by a fire barrierwall, the
__________________________________ requirements of each separation
shall apply.
A. most restrictive
B. least restrictive
C. most cost effective
D. most fire resistive
180
Timed Exam 3- 11. An accessible route shall not be required between site
arrival points and the building or facility entrance if the only means of access
between them is a vehicular way not providing for ______________________.
A. employee access
B. emergency access
C. pedestrian access
D. motorized access
Timed Exam 3- 12. In lieu of an individual permit for each alteration to an
already approved electrical, gas, mechanical or plumbing installation, the
building official is authorized to issue a(an) ______________ upon application
therefore to any person, firm or corporation regularly employing one or more
qualified tradespersons in the building, structure or on the premises owned or
operated by the applicant for the permit.
182
A. annual permit.
B. temporary certificate of occupancy
C. waiver of permit
D. expert permit exemption
Timed Exam 3- 13. The use of a building or structure, or portion thereof, for
educational, supervision or personal care services for more than five children
older than _________________ years of age, shall be classified as a Group E
occupancy.
A. 2.5
B. 5
C. 12
D. 17
Timed Exam 3- 14. Where more than one exit is required, they shall be so
arranged that it is possible to travel in either direction from any point in a mall to
separate exits and the minimum width of an exit passageway or corridor from a
mall shall be ____________________________.
A. 144 inches
B. 100 inches
C. 42 inches
D. 66 inches
Timed Exam 3- 15. Buildings and structures erected or to be erected, altered
or extended in height or area shall be classified in one of the _________
construction types.
A. four
B. five
C. six
D. seven
Timed Exam 3- 16. Group A-3. An automatic sprinkler system shall be
provided for Group A-3 occupancies where the fire area exceeds
_____________ square feet.
183
A. 10000
B. 12000
C. 14000
D. 16000
Timed Exam 3- 17. Approved fire door and fire shutter assemblies shall be
constructed of ______________ or assembly of component materials that
conforms to the test requirements of Section 715.4.1, 715.4.2 or 715.4.3 and
the fire-protection rating indicated in Table 715.4.
A. any material
B. steel
C. treated wood
D. aluminum
Timed Exam 3- 18. Aerosol storage rooms and general-purpose warehouses
containing aerosols shall be provided with an approved _____________ fire
alarm system where required by the International Fire Code.
A. manual
B. automatic
C. remote controlled
D. fume activated
Timed Exam 3- 19. Second-hand masonry units shall not be reused unless
they conform to the requirements ____________, and the units shall be of
whole, sound materials and free from cracks and other defects that will interfere
with proper laying or use and old mortar shall be cleaned from the unit before
reuse.
A. of their original design
B. set by the designer
C. set for used masonry units.
D. of new units
Timed Exam 3- 20. The building official shall have the authority to require tests
as evidence of compliance to be made at no expense to the jurisdiction.
184
185
A. 2
B. 3
C. 4
D. 5
Timed Exam 3- 25. The vertical distance from grade plane to the average
height of the highest roof surface.
A. story height
B. building height
C. building dimension
D. straight rise
Timed Exam 3- 26. In Type I and II construction, The use of combustible piping
materials shall be permitted when installed in accordance with the limitations of
the
_____________________________________________________________.
A. International Mechanical Code and the International Plumbing Code
B. UBC
C. NFPA
D. Plumbing Pipe Association of America
Timed Exam 3- 27. Mastics and caulking materials applied to provide flexible
seals between components of exterior wall construction.
A. is allowed in Type I construction
B. is not allowed in Type I construction
C. is a non-hazardous material
D. is not a good practice
Timed Exam 3- 28. What is the maximum number of occupants allowed in a
bowling center in bowling areas.
A. 7 net, persons for each lane
B. 5 persons for each lane including 15 feet of runway
C. no limit
D. 15 gross, persons for each lane
186
187
A. 48
B. 60
C. 72
D. 84
Timed Exam 3- 41. In radio and television transmitting stations the provisions
of this code shall not apply to electrical equipment used for radio and television
transmissions, but do apply to equipment and wiring for power supply, the
installations of towers and antennas.
A. True
B. False
Timed Exam 3- 42. The number of persons for which the means of egress of a
building or portion thereof is designed.
A. legal group
B. public access
C. max occupancy
D. occupant load
Timed Exam 3- 43. When the building official issues a permit, the construction
documents shall be approved, in writing or by stamp, as Reviewed for Code
Compliance. One set of construction documents so reviewed shall be retained
by the building official. The other set shall be returned to the applicant, shall be
kept at the site of work and shall be open to inspection by the building official or
a duly authorized representative.
A. Approved
B. Reviewed for Code Compliance.
C. Conditionally Approved
D. Authorization to Begin Work
190
191
Timed Exam 3- 48. Any tower, spire, dome or cupola that exceeds 60 feet (18
288 mm) in height above the highest point at which it comes in contact with the
roof, or that exceeds 200 square feet (18.6 m2) in area at any horizontal
section, or which is intended to be used for any purpose other than a belfry or
architectural embellishment, shall be entirely constructed of and supported by
noncombustible materials. Such structures shall be separated from the building
below by construction having a fire-resistance rating of not less than ________
hours with openings protected with a minimum _______hour fire protection
rating.
A. 1.5, 1.5
B. 2, 2
C. 2, 1.5
D. 2.5, 1.5
Timed Exam 3- 49. The building official shall have the authority to authorize
the temporary connection of the building or system to the utility source of
_______________________.
A. energy, fuel or power.
B. telephone
C. cable
D. communications lines.
Timed Exam 3- 50. Mirrors and other glass panels mounted or hung on a
surface that provides a ______________ support is not considered hazardous
location.
A. perimeter
B. bottom and top
C. hinged
D. continuous backing
Timed Exam 3- 51. In reference to signage within Covered Mall Buildings.
Plastic signs shall not exceed a height of 36 inches, except if the sign is
vertical, the height shall not exceed _______ inches and the width shall not
exceed 36 inches.
192
A. 120
B. 96
C. 72
D. 60
Timed Exam 3- 52. Occupiable spaces, habitable spaces and corridors shall
have a ceiling height of not less than _______________. Exceptions excluded.
A. 8 feet
B. 7 feet 6 inches
C. 7 feet
D. 6 feet 8 inches
Timed Exam 3- 53. Openings in a smoke barrier shall be _____________ in
accordance with Section 715.
A. closed
B. glassed
C. protected
D. cemented
Timed Exam 3- 54. Glazing in guards and railings, including structural bal-uster
panels and nonstructural in-fill panels, ________________________ above a
walking surface is considered hazardous location.
A. within 36 inches
B. regardless of area or height
C. within 60 inches
D. within 42 inches
Timed Exam 3- 55. The door component of a fire door assembly.
A. fire block
B. fire damper
C. fire door
D. fire stop
193
Timed Exam 3- 56. The minimum aisle width of assembly seating where the
aisle does not serve more than 50 seats is __________ inches.
A. 32
B. 36
C. 40
D. 44
Timed Exam 3- 57. A basement shall be considered as a story above grade
plane where the finished surface of the floor above the basement is:
A. More than 6 feet above grade plane
B. More than 6 feet above the finished ground level for more than 50
percent of the total building perimeter
C. More than 12 feet above the finished ground level at any point.
D. A or C
E. Any of the above
Timed Exam 3- 58. Combustible framing in fire walls. Adjacent combustible
members entering into a concrete or masonry fire wall from opposite sides shall
not have less than a __ inch distance between embedded ends. Exceptions
ignored.
A. 4
B. 12
C. 20
D. 28
Timed Exam 3- 59. Where parking is provided, how many accessible parking
spaces shall be provided at a facility that has 77 total parking spaces.
A. 4
B. 6
C. 8
D. 10
Timed Exam 3- 60. In conventional light-frame construction, where roof trusses
are used and are installed perpendicular to an exterior braced wall line, lateral
forces shall be transferred from the roof diaphragm to the braced wall by
194
to resist the full compressive loads, neglecting end-bearing capacity. Columnand-post end connections shall be fastened to resist lateral and net induced
_________________.
A. uplift forces
B. buckling
C. stress
D. compression
Timed Exam 3- 65. The maximum distance of travel from any point within a
mall to an exit shall not exceed ____________________.
A. 50 feet
B. 100 feet
C. 150 feet
D. 200 feet
Timed Exam 3- 66. What is the allowable height and area of a Group M
building of Type I-A Construction
A. 5 Stories , 40,000 SF
B. 50 Stories , 500,000 SF
C. 100 Stories , 1,140,000 SF
D. Unlimited , Unlimited
Timed Exam 3- 67. Emergency escape and rescue openings shall have the
bottom of the clear opening not greater than _____ inches measured from the
floor.
A. 36
B. 44
C. 48
D. 54
Timed Exam 3- 68. Headers, double joists, trusses or other approved
assemblies that are of adequate size to ___________ loads to the vertical
members shall be provided over window and door openings in load-bearing
walls and partitions.
196
A. carry
B. transfer
C. support
D. maintain
Timed Exam 3- 69. A wall designed to resist lateral forces parallel to the plane
of a wall.
A. Braced wall
B. Cripple wall
C. Vertical wall
D. Shearwall
Timed Exam 3- 70. In General not noting exceptions, the unlatching of any
door leaf shall not require more than ________ operation. Exceptions ignored.
A. 1
B. 2
C. 3
D. 4
Timed Exam 3- 71. Fire walls shall be of
__________________________________. Ignoring all exceptions.
A. sheetrock, concrete or steel.
B. concrete or steel materials
C. any approved noncombustible materials
D. wood, sheetrock, concrete or steel.
Timed Exam 3- 72. All valves controlling the water supply for automatic
sprinkler systems, pumps, tanks, water levels and temperatures, critical air
pressures and water-flow switches on all sprinkler systems shall be
______________ supervised. Exceptions ignored.
A. physically
B. mechanically
C. pneumatically
197
D. electrically
Timed Exam 3- 73. Where _______________________ of any pane of glass
are not firmly supported, or are subjected to unusual load conditions, detailed
construction documents, detailed shop drawings and analysis or test data
assuring safe performance for the specific installation shall be prepared by a
registered design professional.
A. one or more sides
B. layers
C. sections
D. rails
Timed Exam 3- 74. Foam plastic used as trim in any occupancy shall comply
with _____________.
A. Section 2703.1
B. Section 2607.0
C. Section 2504.1
D. Section 2604.2
Timed Exam 3- 75. The holder of a "phased approval" permit for the foundation
or other parts of a building or structure shall proceed at the __________ risk
with the building operation and without assurance that a permit for the entire
structure will be granted.
A. holders
B. owners
C. contractors
D. building officials
Timed Exam 3- 76. In combustible construction, _________________ shall be
installed to cut off concealed draft openings (both vertical and horizontal) and
shall form an effective barrier between floors, between a top story and a roof or
attic space.
198
A. insulation
B. sheet metal
C. fireblocking
D. sheet rock
Timed Exam 3- 77. In Heavy Timber Construction, wood beams and girders
shall be of ____________________ and shall be not less than 6 inches
nominal in width and not less than 10 inches nominal in depth. Framed sawn or
glued-laminated timber arches, which spring from the floor line and support
floor loads, shall be not less than 8 inches nominal in any dimension.
A. hand split timber
B. unstripped logs
C. oriented strand board (OSB)
D. sawn or glued-laminated timber
Timed Exam 3- 78. A Class B Wall or Ceiling finish has a Flame spread range
of __________; and a smoke-developed range of ____________.
A. 26-100, 0-450
B. 40-100, 0-450
C. 40-75, 0-450
D. 26-75, 0-450
Timed Exam 3- 79. If it is necessary to make an inspection to enforce the
provisions of this code, or where the building official has ___________
__________ to believe that there exists in a structure or upon a premises a
condition which is contrary to or in violation of this code which makes the
structure or premises unsafe, dangerous or hazardous, the building official is
authorized to enter the structure or premises at ___________ __________ to
inspect or to perform the duties imposed by this code, provided that if such
structure or premises be occupied that credentials be presented to the
occupant and entry requested.
A. no reason, any time
B. a warrant, surprise times
C. reasonable cause, within 24 hrs.
D. reasonable cause, reasonable times
199
Timed Exam 3- 80. Shower compartments and walls above bathtubs with
installed shower heads shall be finished with a smooth, nonabsorbent surface
to a height not less than _____________ above the drain inlet.
A. 70 inches
B. 6 feet
C. 72 inches
D. B and C
200
Timed Exam 4
Timed Exam 4- 17. In fire walls, where combustible members frame into hollow
walls or walls of hollow units, hollow spaces shall be solidly filled for the full
thickness of the wall and for a distance not less than 4 inches
__________________________ the structural members, with noncombustible
materials approved for fireblocking.
A. above
B. below
C. between
D. All of the above
Timed Exam 4- 18. Studs shall have full bearing on a 2-inch-thick (actual 1 1/2inch) or larger plate or sill having a width at least equal to the width of the
__________.
A. studs
B. plates
C. sill
D. top plate
Timed Exam 4- 19. An automatic sprinkler system shall be installed at the top
of rubbish and linen chutes and in their terminal rooms. Chutes extending
through _________ or more floors shall have additional sprinkler heads
installed within such chutes at alternate floors. Chute sprinklers shall be
accessible for servicing.
A. two
B. three
C. four
D. five
Timed Exam 4- 20. An open parking garage with an IIA type of construction is
limited in area to __________ square feet.
A. 50000
B. 60000
C. 70000
D. 80000
205
Timed Exam 4- 29. The minimum thickness of Stone (natural) on the exterior
of a building is ________ inches.
A. 0.5
B. 1
C. 2
D. 3
Timed Exam 4- 30. The fire barrier separating incidental accessory
occupancies from other spaces in the building shall have a fire-resistance rating
of not less than ___________.
A. 1 hour
B. 2 hours
C. that indicated in Table 508.2.5.
D. any of the above
Timed Exam 4- 31. Shaft enclosures shall have a fire-resistance rating of not
less than 2 hours where connecting four stories or more, and not less than 1
hour where connecting less than four stories. The number of stories connected
by the shaft enclosure shall include any basements but not any mezzanines.
Shaft enclosures shall have a fire-resistance rating not less than the floor
assembly penetrated, but need not exceed ________ hours.
A. 2
B. 3
C. 4
D. 5
Timed Exam 4- 32. In buildings constructed in accordance with the provisions
of conventional light-frame construction studs shall be placed with their wide
dimension perpendicular to the wall. Not less than __________ studs shall be
installed at each corner of an exterior wall.
A. 2
B. 3
C. 4
D. 5
208
Timed Exam 4- 33. Ducts and air transfer openings. Ducts and air transfer
openings shall _____________ fire walls. Exceptions ignored.
A. not penetrate
B. be allowed in
C. be fireblocked in
D. be of non-combustible materials in
Timed Exam 4- 34. A space within a building enclosed by smoke barriers on all
sides, including the top and bottom.
A. fire block
B. smoke compartment
C. smoke block
D. smoke barrier
Timed Exam 4- 35. Class III standpipe systems shall be installed throughout
buildings where the floor level of the highest story is located more than
____________ above the lowest level of fire department vehicle access, or
where the floor level of the lowest story is located more than _____________
below the highest level of fire department vehicle access. Exceptions ignored.
A. 50
B. 40
C. 30
D. 20
Timed Exam 4- 36. The stopping of leaks in drains, water, soil, waste or vent
pipe provided, however, that if any concealed trap, drain pipe, water, soil, waste
or vent pipe becomes defective and it becomes necessary to remove and
replace the same with new material, such work shall be considered as new
work and a permit shall be obtained and inspection made as provided in this
code.
A. True
B. False
209
Timed Exam 4- 37. Stair risers shall be solid and vertical or sloped from the
underside of the leading edge of the tread above at an angle not more than
________ degrees from the vertical.
A. 20
B. 30
C. 45
D. 60
Timed Exam 4- 38. What is the shear capacity for horizontal wood framed
gypsum board diaphragm ceiling assemblies for 1/2 material with framing
members 16 in oc.
A. 70 plf
B. 80 plf
C. 90 plf
D. 100 plf
Timed Exam 4- 39. The minimum thickness of gypsum wallboard is
_______________ with a maximum wall stud spacing of ______________.
A. .5, 16
B. .625, 16
C. .5, 19.2
D. .5, 24
Timed Exam 4- 40. What is the allowable shear (pounds per foot) for wood
structural panel shear walls with framing of douglas-fir-larch, or southern pine
for wind or seismic loading for 7/16 Structural I Sheathing applied directly to the
framing fastened with 4 inch spacing at the perimeter of the panels with 8d
common nails that penetrate 1.375" into the framing.
A. 200
B. 260
C. 395
D. 505
210
212
Timed Exam 4- 49. If the circumstances require, the owner shall designate a
___________ registered design professional in responsible charge who shall
perform the duties required of the original registered design professional in
responsible charge. The building official shall be notified in writing by the owner
if the registered design professional in responsible charge is changed or is
unable to continue to perform the duties.
A. UL
B. building inspector as the
C. general contractor
D. substitute
Timed Exam 4- 50. Wood framing members, including wood sheathing, which
rest on exterior foundation walls and are less than ____ inches from exposed
earth shall be of naturally durable or preservative-treated wood.
A. 1
B. 6
C. 8
D. 12
Timed Exam 4- 51. What is the minimum normal weight concrete cover in
inches that will provide a Fire-Resistance Rating of 3 hours for a W14 x 43
structural shape steel column.
A. 1 inch
B. 2 inches
C. 2.5 inches
D. 3 inches
E. none of these
Timed Exam 4- 52. Openings in wood shear panels that materially affect their
strength shall be fully detailed on the plans, and shall have their edges
_______________ to transfer all shearing stresses.
A. adequately reinforced
B. enforced
C. lined with steel
D. screwed
213
building official shows that shrinkage of the wood framing will not have adverse
effects on the structure or any plumbing, electrical or mechanical systems, or
other equipment installed therein due to excessive shrinkage or differential
movements caused by shrinkage.
A. one
B. two
C. three
D. four
Timed Exam 4- 58. A-2 Assembly uses intended for food and/or drink
consumption including, but not limited to:
A. Courtrooms, Dance halls (not including food or drink consumption)
Exhibition halls
B. Motion picture theaters Symphony and concert halls Television and
radio studios admitting an audience Theaters
C. Banquet halls, Night clubs, Restaurants, Taverns and bars
D. Amusement arcades, Art galleries, Bowling alleys, Churches,
Community halls
Timed Exam 4- 59. What is the allowable height and area of a Group F-2
building of Type IIIB Construction
A. 2 Stories , 18,000 SF
B. 3 Stories , 18,000 SF
C. 4 Stories , 36,000 SF
D. 5 Stories , 40,000 SF
Timed Exam 4- 60. The _____________ is authorized to waive the submission
of construction documents and other data not required to be prepared by a
registered design professional if it is found that the nature of the work applied
for is such that review of construction documents is not necessary to obtain
compliance with this code.
A. building permit
B. application
C. occupancy permit
D. construction documents
215
Timed Exam 4- 61. No person shall make connections from a utility, source of
energy, fuel or power to any building or system that is regulated by this code for
which a permit is required, _____________________________________
A. until released by the building official.
B. until released by the public utility.
C. until the contractor, electrician, plumber or other professional in
charge of the applicable utilization equipment approves.
D. until a reasonable person deems it to be safe.
Timed Exam 4- 62. A shaft enclosure is not required for openings totally within
an individual residential dwelling unit and connecting ________ stories or less.
A. 2
B. 3
C. 4
D. 5
Timed Exam 4- 63. Where the fire wall intersects the exterior walls, the fireresistance rating for the exterior walls on both sides of the fire wall shall have a
1-hour fire-resistance rating with 3/4-hour opening protection where opening
protection is required. The fire-resistance rating of the exterior wall shall extend
a minimum of _____ feet on each side of the intersection of the fire wall to
exterior wall.
A. 2
B. 4
C. 6
D. 8
Timed Exam 4- 64. Which of the following shall not require a permit.
A. Fences not over 6 feet high.
B. Oil derricks.
C. Temporary motion picture, television and theater stage sets and
scenery.
D. All of the above.
E. None of the above.
216
Timed Exam 4- 65. Deferral of any submittal of plan items for a permit shall
have the prior approval of the building official. The registered design
professional in responsible charge shall list the deferred submittals on the
_______________________ for review by the building official.
A. plans
B. construction documents
C. schedule of submittals
D. plot plan
Timed Exam 4- 66. The purpose of this code is to establish the
_______________ requirements to safeguard the public health, safety and
general welfare.
A. maximum
B. reasonable
C. minimum
D. voluntary
Timed Exam 4- 67. Except as provided for in Section 1405 for
weatherboarding or where stucco construction that complies with Section 2510
is installed, enclosed buildings shall be __________ with one of the materials of
the nominal thickness specified in Table 2304.6 or any other approved material
of equivalent strength or durability.
A. covered
B. finished
C. decorated
D. sheathed
Timed Exam 4- 68. Required guards shall be not less than __________ inches
high, measured vertically above the adjacent walking surfaces, adjacent fixed
seating or the line connecting the leading edges of the treads.
A. 36
B. 38
C. 42
D. 48
217
Timed Exam 4- 73. A room or space used for assembly purposes that is less
than ________ square feet in area and is accessory to another occupancy shall
be classified as a Group B occupancy or as part of that occupancy.
A. 250
B. 500
C. 750
D. 1000
Timed Exam 4- 74. Door handles, pulls, latches, locks and other operating
devices shall be installed ______ inches minimum and ______ inches
maximum above the finished floor.
A. 30, 40
B. 34, 48
C. 34, 42
D. 36, 48
Timed Exam 4- 75. An opening not less than ________________________
shall be provided to any attic area having a clear height of over 30 inches. A
30-inch minimum clear headroom in the attic space shall be provided at or
above the access opening.
A. 22 inches by 24 inches
B. 22 inches by 30 inches
C. 18 inches by 24 inches
D. 20 inches by 30 inches
Timed Exam 4- 76. Handrail height, measured above stair tread nosings, or
finish surface of ramp slope shall be uniform, not less than ____ inches (864
mm) and not more than ____ inches (965 mm).
A. 34, 38
B. 36, 42
C. 30, 40
D. 32, 40
219
Timed Exam 4- 80. Operable parts that are intended for use only by
_______________________ shall not be required to be accessible.
A. employees
B. the general public
C. special care individuals
D. service or maintenance personnel
220
Timed Exam 5
A. 144, 20
B. 100, 15
C. 156, 25
D. 32, 10
Timed Exam 5- 5. Dead ends not exceeding a length equal to twice the width
of the mall measured at the narrowest location within the dead-end portion of
the mall are not required be a minimum of 66 inches wide.
A. This statement is True for Covered Mall Buildings
B. This statement is False for Covered Mall Buildings
C. This statement is always False for Covered Mall Buildings
D. This statement is False for all commercial buildings
Timed Exam 5- 6. What is the fire resistance rating requirement for
nonbearing walls and partitions interior in a type III-B structure.
A. 0
B. 1
C. 2
D. 3
Timed Exam 5- 7. What is the fire-resistance-rated-separation required for
refrigerant machinery rooms
A. 2 hours; or 1 hour and provide automatic fire-extinguishing system
B. 2 hours and automatic sprinkler system
C. 1-hour fire barriers and floor/ceiling assemblies in Group B, F, H, M, S
and U occupancies. 2-hour fire barriers and floor/ceiling assemblies in Group A,
E, I and R occupancies
D. 1 hour or provide automatic sprinkler system
Timed Exam 5- 8. In buildings constructed in accordance with the provisions
of conventional light-frame construction trimmer and header joists shall be
doubled, or of lumber of equivalent cross section, where the span of the header
exceeds ____ feet.
222
A. 4
B. 5
C. 6
D. 7
Timed Exam 5- 9. Walls within 2 feet of urinals and water closets shall have a
smooth, hard, nonabsorbent surface, to a height of _____________ feet above
the floor, and except for structural elements, the materials used in such walls
shall be of a type that is not adversely affected by moisture. Exceptions not
considered.
A. 2
B. 3
C. 4
D. 5
Timed Exam 5- 10. Stair treads and risers shall be of uniform size and shape.
The tolerance between the largest and smallest riser or between the largest
and smallest tread depth at the walkline within any flight of stairs shall not
exceed _________ inch in any flight of stairs.
A. 0.025
B. 0.375
C. 0.0485
D. 0.5
Timed Exam 5- 11. Stairways within dwelling units and exterior stairways
serving a dwelling unit shall have an illumination level on tread runs of not less
than _____ foot-candle .
A. 1
B. 5
C. 10
D. 20
Timed Exam 5- 12. The area of a one-story, Group A-3 building used as a
church, community hall, dance hall, exhibition hall, gymnasium, lecture hall,
223
224
A. 2.5
B. 5
C. 10
D. 15
Timed Exam 5- 17. All spaces between fireplaces and floors and ceilings
through which fireplaces pass shall be fireblocked with noncombustible material
securely fastened in place. The fireblocking of spaces between wood joists,
beams or headers shall be to a depth of ____ inch and shall only be placed on
strips of metal or metal lath laid across the spaces between combustible
material and the chimney.
A. 1
B. 2
C. 3
D. 4
Timed Exam 5- 18. The unobstructed width of pedestrian walkways shall not
be less than inches. The total width shall not exceed _____ feet.
A. 32, 24
B. 36, 30
C. 42, 25
D. 44, 30
Timed Exam 5- 19. The use of a solid or liquid hazardous material involving a
closed vessel or system that remains closed during normal operations where
vapors emitted by the product are not liberated outside of the vessel or system
and the product is not exposed to the atmosphere during normal operations;
and all uses of compressed gases.
A. Open System
B. Encapsulated System
C. Concealed System
D. Closed System
Timed Exam 5- 20. A Hospital is an example of what type of Group Occupancy
Classification?
225
A. A-1
B. B
C. I-1
D. I-2
Timed Exam 5- 21. The opening around a penetrating item in a fire resistancerated construction.
A. dead space
B. annular space
C. fire blocking space
D. seal housing
Timed Exam 5- 22. A building used for assembly purposes with an occupant
load of less than ________ persons shall be classified as a Group B
occupancy.
A. 50
B. 100
C. 200
D. 500
Timed Exam 5- 23. What is the fire resistance rating requirement for roof
construction and secondary members in a type I-A structure.
A. 1
B. 1.5
C. 2
D. 3
Timed Exam 5- 24. Class C roof assemblies are those that are effective
against _______________.
A. light fire-test exposure
B. moderate fire-test exposure
C. extreme fire-test exposure
D. no fire-test exposure
226
Timed Exam 5- 25. Buildings that are not more than two stories above grade
plane and having not more than 6,000 square feet of projected roof area and
where there is a minimum __________ fire-separation distance from the
leading edge of the roof to a lot line on all sides of the building, except for street
fronts or public ways, shall be permitted to have roofs of No. 1 cedar or
redwood shakes and No. 1 shingles.
A. 5-foot
B. 10-foot
C. 15-foot
D. 20-foot
Timed Exam 5- 26. Glass sloped ______ degrees or less from vertical in
windows, curtain and window walls, doors and other exterior applications shall
be designed to resist the wind loads in Section 1609 for components and
cladding.
A. 10
B. 15
C. 20
D. 25
Timed Exam 5- 27. Where fire shutters of the rolling type are installed, such
shutters shall include approved _________________ devices.
A. fire blocking system
B. smoke detection
C. automatic-closing
D. temperature triggering
Timed Exam 5- 28. Yards shall not be less than ________ feet in width for
buildings two stories or less above grade plane.
A. 3
B. 5
C. 8
D. 10
227
Timed Exam 5- 29. Foam plastic insulation shall not be used as interior wall or
ceiling finish in plenums except as permitted in Section 2604 or when protected
by a ________________ in accordance with Section 2603.4.
A. thermal barrier
B. layer of sheet metal
C. foil sheet
D. plastic wrap
Timed Exam 5- 30. Horizontal sliding or swinging gates exceeding the ___
foot maximum leaf width limitation are allowed in fences and walls surrounding
a stadium.
A. 3
B. 3.5
C. 4
D. 4.5
Timed Exam 5- 31. A-1 Assembly uses, usually with fixed seating, intended for
the production and viewing of the performing arts or motion pictures including,
but not limited to:
A. Courtrooms, Dance halls (not including food or drink consumption)
Exhibition halls
B. Motion picture theaters Symphony and concert halls Television and
radio studios admitting an audience Theaters
C. Banquet halls, Night clubs, Restaurants, Taverns and bars
D. Amusement arcades, Art galleries, Bowling alleys, Churches,
Community halls
Timed Exam 5- 32. In passenger transportation facilities and airports, the
accessible route from separate-sex toilet rooms to a unisex toilet room
___________ pass through security checkpoints.
A. shall
B. shall not
C. may
D. must
228
Timed Exam 5- 33. Where a maximum one-story above grade plane Group S2 parking garage, en -closed or open, or combination thereof, of Type I
construction or open of Type IV construction, with grade entrance, is provided
under a building of Group R, the number of stories to be used in determining
the minimum type of construction shall be measured from
_________________________________.
A. the grade plane
B. the floor below such a parking area
C. the floor above such a parking area
D. the average flood plane plus 20 feet.
Timed Exam 5- 34. The building official, _____________________ shall make
the inspections set forth in Sections 109.3.1 through 109.3.10.
A. at random intervals
B. on a daily basis
C. upon seeing a violation
D. upon notification
Timed Exam 5- 35. The following information is not required to be on a
Certificate of Occupancy:
A. The building permit number.
B. The address of the structure.
C. The name and address of the owner.
D. General Contractors name.
Timed Exam 5- 36. In buildings constructed in accordance with the provisions
of conventional light-frame construction, bearing wall floor-to-floor heights shall
not exceed _________ feet.
A. 8
B. 9
C. 10
D. 12
229
230
Timed Exam 5- 41. In areas where there has been a history of ice forming
along the eaves causing a backup of water, an ice barrier that consists of at
least two layers of underlayment cemented together or of a self-adhering
polymer modified bitumen sheet shall be used in lieu of normal underlayment
and extend from the lowest edges of all roof surfaces to a point at least ____
inches inside the exterior wall line of the building.
A. 12
B. 18
C. 24
D. 36
Timed Exam 5- 42. Doors, when fully opened, and handrails shall not reduce
the required means of egress width by more than ___________ inches. Doors
in any position shall not reduce the required width by more than one-half. Other
nonstructural projections such as trim and similar decorative features shall be
permitted to project into the required width a maximum of 11/2 inches (38 mm)
on each side. Exceptions ignored.
A. 6
B. 7
C. 12
D. 14
Timed Exam 5- 43. Penetrations other than those
____________________________________ shall not be permitted in shaft
enclosures. Ducts shall not penetrate exit shaft enclosures.
A. for heating and cooling
B. necessary communication wiring
C. necessary for alarm systems
D. necessary for the purpose of the shaft
Timed Exam 5- 44. Corrosives shall not include personal or household
products in their original packaging used in retail display or commonly used
building materials. Which group classification includes these products.
231
A. Group H
B. Group E
C. Group U
D. They shall be classified in the occupancy that they most nearly
resemble.
Timed Exam 5- 45. Penetrations shall be installed as ____________ in an
approved fire-resistance-rated assembly.
A. a unit
B. neatly as possible
C. tight as possible
D. tested
Timed Exam 5- 46. A revolving door shall be capable of
________________________________ with parallel egress paths providing an
aggregate width of 36 inches.
A. allowing passage of a sphere
B. allowing 6 occupants to exit simultaneously
C. providing a smoke barrier
D. collapsing into a bookfold position
Timed Exam 5- 47. It shall be the duty of the permit applicant to cause the
work to remain accessible and exposed for inspection purposes. Neither the
__________________ nor the jurisdiction shall be liable for expense entailed in
the removal or replacement of any material required to allow inspection.
A. contractor
B. designer
C. subcontractor
D. building official
Timed Exam 5- 48. Exterior fire-resistance rated walls shall have sufficient
structural stability such that they will _______________ for the duration of time
indicated by the required fire-resistance rating.
232
A. remain undamaged
B. remain in place
C. not burn through
D. not hold up
Timed Exam 5- 49. Assembly Group A occupancy includes, among others, the
use of a building or structure, or a portion thereof, for the gathering together of
persons for purposes such as _______________________________.
A. civic functions
B. social functions
C. food or drink consumption
D. religious functions
E. All the above
Timed Exam 5- 50. Artificial light shall be provided that is adequate to provide
an average illumination of _____ foot-candles over the area of the room at a
height of _____ inches above the floor level.
A. 5, 24
B. 10, 30
C. 10, 6
D. 30, 10
Timed Exam 5- 51. Type I and II construction are those types of construction in
which the building elements are of _________________________ materials.
A. combustible
B. water resistant
C. noncombustible
D. mineral based
Timed Exam 5- 52. Which of the following is not listed as a draftstopping
material.
A. 0.5-inch gypsum board
B. 0.012 aluminum foil
C. 0.375-inch particleboard
D. 0.375-inch wood structural panel
233
234
A. 4
B. 5
C. 6
D. 7
Timed Exam 5- 57. Used materials and equipment can not be used under any
circumstances, unless the materials used meet the requirements of this code
for new materials and they are approved by the building official.
A. True
B. False
Timed Exam 5- 61. Where the fireplace opening is 6 square feet or larger, the
hearth extension shall extend at least _______ inches in front of, and at least
_________ inches beyond, each side of the fireplace opening.
A. 10, 8
B. 16, 8
C. 20, 12
D. 24, 12
Timed Exam 5- 62. A listed device, installed in ducts and air transfer openings,
designed to close automatically upon detection of heat, to interrupt migratory
airflow, and to restrict the passage of flame. Fire dampers are classified for use
in either static systems that will automatically shut down in the event of a fire, or
in a dynamic system that continues to operate during a fire. A dynamic fire
damper is tested and rated for closure under airflow.
A. fire block
B. fire damper
C. fire barrier
D. fire stop
Timed Exam 5- 63. In other than dwelling units, toilet and bathing room floors
shall have a smooth, hard, ______________ surface that extends upward onto
the walls at least 6 inches.
A. tile
B. concrete
C. wood or tile
D. nonabsorbent
Timed Exam 5- 64. Construction or work for which a permit is required shall be
subject to inspection by the ________________ and such construction or work
shall remain accessible and exposed for inspection purposes until approved.
A. building official
B. building inspector
C. general contractor
D. design professional
236
Timed Exam 5- 65. Open guards shall have balusters or ornamental patterns
such that a 4-inch-diameter sphere cannot pass through any opening up to a
height of 34 inches. From a height of _______________________ above the
adjacent walking surfaces, a sphere 4.375 inches in diameter shall not pass.
A. 34 inches to 42 inches
B. 36 inches to 48 inches
C. 36 inches to 42 inches
D. 42 inches to 48 inches
Timed Exam 5- 66. The fire-resistance rating of exterior walls with a fire
separation distance of __________ than 10 feet shall be rated for exposure to
fire from the inside.
A. less
B. greater
C. 10 feet or less
D. 20 feet or less
Timed Exam 5- 67. In buildings constructed in accordance with the provisions
of conventional light-frame construction, wall studs shall support the ends of
the header. Each end of a lintel or header shall have a length of bearing of not
less than __________ inches for the full width of the lintel.
A. 1
B. 1.5
C. 2
D. 3
Timed Exam 5- 68. In concrete construction, when this code requires a
thickness of cover for fire protection greater than the minimum concrete cover
specified in Section 1907.7, ____________________________.
A. Section 1907.7 shall govern
B. such greater thickness shall be specified
C. such lesser thickness shall be used
D. the contractor shall have a choice of which to use.
237
Timed Exam 5- 69. Ramps used as part of a means of egress shall have a
running slope not steeper than __________ unit vertical in 12 units horizontal.
The slope of other ramps shall not be steeper than one unit vertical in
_________ units horizontal.
A. 0.25, 12
B. 0.5, 8
C. 1, 8
D. 1.25, 12
Timed Exam 5- 70. For smoke-protected assembly aisle accessways, the
maximum number of seats per row permitted to have a minimum 12 inch clear
width aisle accessway with the aisle or doorway at one end of the row only is
______.
A. 14
B. 7
C. 8
D. 11
Timed Exam 5- 71. An area where persons unable to use stairways can
remain temporarily to await instructions or assistance during emergency
evacuation.
A. balcony
B. area of refuge
C. fire escape
D. fire room
Timed Exam 5- 72. Clearance between wood siding and earth on the exterior
of a building shall not be less than _________ or less than _________ vertical
from concrete steps, porch slabs, patio slabs and similar horizontal surfaces
exposed to the weather except where siding, sheathing and wall framing are of
naturally durable or preservative-treated wood.
A. 4, 4
B. 6, 2
C. 8, 4
D. 10, 6
238
Timed Exam 5- 73. Every dwelling unit shall have at least one room that shall
have not less than 120 square feet of net floor area. Other habitable rooms
shall have a net floor area of not less than 70 square feet except for
______________________.
A. living rooms
B. bedrooms
C. kitchens
D. dens
Timed Exam 5- 74. To obtain a permit, the applicant shall first file an
application therefore in writing on a form furnished by the department of
building safety for that purpose. Such application does not require which of the
following items.
A. Indicate the use and occupancy for which the proposed work is
intended.
B. State the valuation of the proposed work.
C. Be signed by the applicant, or the applicant's authorized agent.
D. Identify and describe the work to be covered by the permit for which
application is made.
E. All of the above items.
Timed Exam 5- 75. In masonry construction, the walls shall be laterally
supported at intervals not exceeding _________________.
A. 20 feet (6096 mm)
B. 24 feet (7315 mm)
C. 30 feet (9144 mm)
D. 60 feet (18288 mm)
Timed Exam 5- 76. Kiosks or similar structures located within a mall shall be
provided with approved fire ______________ and detection devices.
A. alarms
B. suppression
C. acceleration
D. notification
239
Timed Exam 5- 77. Chimneys shall extend at least 2 feet higher than any
portion of the building within 10 feet , but shall not be less than _________ feet
above the highest point where the chimney passes through the roof.
A. 2
B. 3
C. 4
D. 5
Timed Exam 5- 78. In other than dwelling units, toilet and bathing room floor
finish materials shall have a smooth, hard, nonabsorbent surface. The
intersections of such floors with walls shall have a smooth, hard, nonabsorbent
vertical base that extends upward onto the walls at least ___________ inches.
A. 3, 76
B. 4, 102
C. 5, 127
D. 6, 152
Timed Exam 5- 79. The minimum density of the interior trim shall be
_________ pcf .
A. 10
B. 20
C. 30
D. 40
Timed Exam 5- 80. In buildings constructed in accordance with the provisions
of conventional light-frame construction a hole not greater in diameter than
_____ percent of the stud width is permitted to be bored in any wood stud.
Bored holes not greater than _______ percent of the width of the stud are
permitted in nonbearing partitions or in any wall where each bored stud is
doubled, provided not more than two such successive doubled studs are so
bored.
A. 25, 40
B. 30, 40
C. 40, 60
D. 50, 75
240
Timed Exam 6
241
242
A. lot area
B. basement
C. building area
D. build space
Timed Exam 6- 9. Nonclassified roofing is approved material that is not listed
as a _______________ roof covering.
A. Class A
B. Class B
C. Class C
D. All of the above
Timed Exam 6- 10. Openings other than _______________ shall not be
permitted in shaft enclosures.
A. the required means of egress system
B. the exterior walls that serve as a part of a required shaft
C. those necessary for the purpose of the shaft
D. required automobile ramps open and enclosed
Timed Exam 6- 11. Elementary materials required to be noncombustible shall
be tested in accordance with _________________.
A. ASTM E 134
B. ASTM E 135
C. ASTM E 136
D. ASTM E 137
Timed Exam 6- 12. What is the minimum thickness face-to-face required for a
wall constructed from solid wallboard partition one full-length layer 1/2" type x
gypsum wallboard laminated to each side of 1" full-length v-edge gypsum
coreboard with approved laminating compound. vertical joints of face layer and
coreboard staggered at least 3", to have a fire resistance rating of _______.
A. 2 inches
B. 2.5 inches
C. 3 inches
D. 3.5 inches
243
Timed Exam 6- 13. The exterior area for assisted rescue shall be at least
_____ percent open, and the open area above the guards shall be so
distributed as to minimize the accumulation of smoke or toxic gases.
A. 10
B. 30
C. 50
D. 70
Timed Exam 6- 14. This Type of Construction is also know as Heavy Timber
(HT)
A. Type III
B. Type IV
C. Type V
D. Type VI
Timed Exam 6- 15. Crawl spaces shall be provided with a minimum of one
access opening not less than _________________________.
A. 22 inches by 24 inches
B. 22 inches by 30 inches
C. 18 inches by 24 inches
D. 18 inches by 30 inches
Timed Exam 6- 16. What is the allowable height and area of a Group A-1
building of Type IIB Construction
A. 1 Stories , 7,500 SF
B. 1 Stories , 8,500 SF
C. 2 Stories , 8,500 SF
D. 3 Stories , 8,500 SF
Timed Exam 6- 17. Each kiosk or similar structure or groupings thereof shall
have a ________________________________ square feet.
244
A. 0
B. 1
C. 2
D. 3
Timed Exam 6- 22. In buildings constructed in accordance with the provisions
of conventional light-frame construction, Wind speeds shall not exceed
________ miles per hour (mph) (3-second gust). Exception ignored.
A. 90
B. 100
C. 110
D. 120
Timed Exam 6- 23. What is the fire-resistance-rated-separation required for
stationary lead-acid battery systems having a liquid capacity of more than 100
gallons used for facility standby power, emergency power or uninterrupted
power supplies.
A. 2 hours; or 1 hour and provide automatic fire-extinguishing system
B. 2 hours and automatic sprinkler system
C. 1-hour fire barriers and floor/ceiling assemblies in Group B, F, H, M, S
and U occupancies. 2-hour fire barriers and floor/ceiling assemblies in Group A,
E, I and R occupancies
D. 4 hours
Timed Exam 6- 24. Fire walls shall extend from the foundation to a termination
point at least ___ inches above both adjacent roofs. Exceptions Ignored.
A. 10
B. 20
C. 30
D. 40
Timed Exam 6- 25. In conventional light-frame construction, exterior gable end
walls, braced wall panel sheathing in the top story shall be extended and
246
fastened to roof framing where the spacing between parallel exterior braced
wall lines is greater than ____________. Exceptions ignored.
A. 25 feet (7 670 mm)
B. 40 feet (120192 mm)
C. 50 feet (15 240 mm)
D. 60 feet (18 288 mm)
Timed Exam 6- 26. Fiberboard wall insulation applied on the exterior of
foundation walls shall be protected below ground level with a
___________________.
A. bituminous coating
B. waterproof film
C. tar based coating
D. preservative
Timed Exam 6- 27. What is the REQUIRED SEPARATION OF
OCCUPANCIES (HOURS) between a Group A-5 and Group H-1. The
Buildings are equipped throughout with an automatic sprinkler system.
A. 1
B. 2
C. 3
D. NP (Not Permitted)
Timed Exam 6- 28. For the purposes of section 106.3, deferred submittals are
defined as those portions of the design that are not submitted at the time of the
application and that are to be submitted to the building official within
_______________________.
A. a reasonable period of time.
B. 180 days.
C. the time period of the permit.
D. a specified period
Timed Exam 6- 29. A 3-second gust wind velocities 100 mph wind load is
equivalent to ____________ mph fasted mile wind speed wind load.
247
A. 110
B. 105
C. 90
D. 80
Timed Exam 6- 30. The use of a building or structure, or portion thereof, for
educational, supervision or personal care services for more than ______
children older than _______ years of age, shall be classified as a Group E
occupancy.
A. ten, 2
B. six, 2 1/2
C. twelve, 2
D. five, 2 1/2
Timed Exam 6- 31. The special inspection of concrete elements of buildings
and structures and concreting operations shall be as required by
___________________.
A. the designer
B. the building inspector
C. the general contractor
D. Chapter 17
Timed Exam 6- 32. What is the REQUIRED SEPARATION OF
OCCUPANCIES (HOURS) between a Group F-2 and Group U. The Buildings
are not equipped throughout with an automatic sprinkler system.
A. 1
B. 2
C. No separation requirement
D. NP (Not Permitted)
Timed Exam 6- 33. In food service lines, where self-service shelves are
provided, at least _________ percent, but not less than one, of each type
provided shall be accessible.
248
A. 10
B. 25
C. 35
D. 50
Timed Exam 6- 34. In buildings constructed in accordance with the provisions
of conventional light-frame construction what is the maximum laterally
unsupported height (in feet) of a 2x4 stud in a nonbearing wall.
A. 10
B. 14
C. 16
D. 20
Timed Exam 6- 35. Shaft enclosures shall have a fire-resistance rating of not
less than ___ hours where connecting four stories or more and not less than
___ hour where connecting less than four stories.
A. 1, .5
B. 2, 1
C. 1, 2
D. 2, 2
Timed Exam 6- 36. Glazing adjacent to stairways within ________ inches
horizontally of the bottom tread of a stairway in any direction when the exposed
surface of the glass is less than ______ inches above the nose of the tread is a
considered hazardous location. Exceptions ignored.
A. 38, 38
B. 48, 48
C. 60, 60
D. 72, 72
Timed Exam 6- 37. Exit passageway enclosures shall have walls, floors and
ceilings of not less than ____ hour fire-resistance rating, and not less than that
required for any connecting exit enclosure.
249
A. 1
B. 2
C. 3
D. 4
Timed Exam 6- 38. In Type I and II construction, The use of electrical wiring
methods with combustible insulation, tubing, raceways and related components
shall be permitted when installed in accordance with the limitations of the
______________________.
A. ICC Electrical Code
B. NEC Code
C. NFPA Code
D. NFAOSP Code
Timed Exam 6- 39. Rooms or spaces having a floor area larger than ________
square feet (93 m2), containing a refrigerant evaporator and maintained at a
temperature below 68F (20C), shall have access to not less than two exits or
exit access doors.
A. 500
B. 1000
C. 1500
D. 2000
Timed Exam 6- 40. Where natural ventilation is required, the minimum
openable area to the outdoors shall be ______ percent of the floor area being
ventilated.
A. 20
B. 10
C. 8
D. 4
Timed Exam 6- 41. There shall be a floor or landing at the top and bottom of
each stairway. The width of landings shall not be less
than__________________________________.
250
A. 36 inches
B. 42 Inches
C. 48 inches
D. the width of stairways they serve
Timed Exam 6- 42. A courtroom is an example of what classification of
occupancy.
A. A-3
B. A-1
C. I-2
D. I-3
Timed Exam 6- 43. Unless structural support and anchorage are provided to
resist the overturning moment, the center of gravity of projecting masonry or
molded cornices shall lie within the ________________ of the supporting wall.
Terra cotta and metal cornices shall be provided with a structural frame of
approved noncombustible material anchored in an approved manner.
A. bottom one-third
B. bottom one-half
C. middle one-third
D. top one-third
Timed Exam 6- 44. Parapet walls shall be properly coped with noncombustible,
weatherproof materials of a width _______________.
A. of 8 inches minimum
B. no less than the thickness of the parapet wall
C. of 12 inches minimum
D. none of these
Timed Exam 6- 45. Porches and decks which are enclosed with insect
screening shall be provided with guards where the walking surface is located
more than ____ inches above the floor or grade below.
251
A. 30
B. 36
C. 42
D. 48
Timed Exam 6- 46. On buildings, structures, electrical, gas, mechanical, and
plumbing systems or alterations requiring a permit, a fee for each permit shall
be paid as required, in accordance with the schedule as established
__________________________.
A. by the building inspector
B. by the International Code Council (ICC)
C. by the applicable governing authority.
D. by the Uniform Permit Fee Schedule for Commercial Buildings &
Structures.
Timed Exam 6- 47. In a commercial cooking system, a manual actuation fire
extinguishing device shall be located at or near a means of egress from the
cooking area, a minimum of _________ feet and a maximum of __________
feet from the kitchen exhaust system
A. 5, 10
B. 10, 15
C. 10, 20
D. 15, 25
Timed Exam 6- 48. _________________ construction is that type of
construction in which the exterior walls are of noncombustible materials and the
interior building elements are of any material permitted by this code.
A. Type I
B. Type II
C. Type III
D. Type IV
Timed Exam 6- 49. In order to hear and decide appeals of orders, decisions or
determinations made by the building official relative to the application and
252
A. 32
B. 40
C. 54
D. 60
Timed Exam 6- 58. Where interior glazing is installed adjacent to a walking
surface, the differential deflection of two adjacent unsupported edges shall not
be greater than the thickness of the panels when a force of 50 pounds per
linear foot is applied horizontally to one panel at any point up to _________
inches above the walking surface.
A. 24
B. 36
C. 42
D. 48
Timed Exam 6- 59. Bathrooms, toilet rooms, kitchens, storage rooms and
laundry rooms shall be permitted to have a ceiling height of not less than
__________ feet. Exceptions excluded.
A. 8 feet
B. 7 feet 6 inches
C. 7 feet
D. 6 feet 8 inches
Timed Exam 6- 60. In reference to Covered Mall Buildings. Wherever the
distance of travel to the mall from any location within a tenant space used by
persons other than employees exceeds_____________________ or the tenant
space exceeds an occupant load of 50, not less than two means of egress shall
be provided.
A. 75 feet
B. 900 inches
C. 22,860 mm
D. All of the above
Timed Exam 6- 61. A minimum width of ________ inches is permitted for
lighting and access catwalks.
255
A. 22
B. 30
C. 38
D. 42
Timed Exam 6- 62. The fire-resistance rating of exterior walls with a fire
separation distance of ___ feet or less shall be rated for exposure to fire from
both sides.
A. 3
B. 4
C. 5
D. 10
Timed Exam 6- 63. A reference plane representing the average of finished
ground level adjoining the building at exterior walls.
A. flood plane
B. maximum drainage plane
C. floor plane
D. grade plane
Timed Exam 6- 64. The clear space between a handrail and a wall or other
surface shall be a minimum of _____ inches.
A. 1
B. 1.5
C. 2
D. 2.5
Timed Exam 6- 65. Means of egress. Each tenant space and the covered mall
building shall be provided with means of egress as required by this section and
this code. Where there is a conflict between the requirements of this code and
the requirements of this section, _________________________________
A. the requirements of this code shall apply.
B. the requirements of this section shall apply.
256
A. one-eighth, one-quarter
B. one-eighth, one-eighth
C. one-quarter, one-quarter
D. one-quarter, one-eighth
Timed Exam 6- 78. Each portion of a building separated by one or more fire
walls that comply with the provisions of the fire wall section of this code shall be
considered ______________________, and the extent and location of such fire
walls shall provide a complete separation.
A. a separate room
B. a separate partition
C. a separate building
D. a separate fire zone
Timed Exam 6- 79. There shall be no refund for permit fees unless:
A. The applicant changes his mind on starting the project.
B. The permit is rejected.
C. The building official has establish a refund policy.
D. The applicant has just cause for a refund.
Timed Exam 6- 80. Arenas, Skating rinks, Swimming pools & Tennis courts
are examples of what Group of Occupancy.
A. A-2
B. A-3
C. A-4
D. A-5
260
Section 1 Answers
Answers
1.
2.
3.
B
C.
D.
4.
5.
A.
6.
B.
7.
8.
9.
10.
11.
12.
13.
C.
C.
B.
A.
D.
C.
B.
14.
A.
True
15.
A.
16.
17.
18.
19.
C.
B.
D.
C.
20.
21.
22.
D.
A.
B.
6
must be considered a story
interconnected
have an exterior exposure durability
classification.
fire resistance rating
48
dead-end mall
23.
24.
25.
26.
27.
A.
E
B.
A.
D.
28.
C.
90 plf
Reference
2109.3.4.2 Wall thickness.
2113.12 Clay Flue lining (installation).
1906.4 Construction joints.
2107.5 TMS402/ACI 530/ASCE 5,
Section 2.3.6, maximum bar size. Add
the following to Chapter 2: 2.3.6
TABLE 601 Fire-Resistance Rating
Requirements For Building Elements
(Hours)
Table 1004.1.1 Maximum Floor Area
Allowances Per Occupant
[F] 2604.2.3 Area limitation
2308.9.11 Bored holes.
1007.6.3 Two-way communication.
2302.1 Definitions.
1013.5 Mechanical equipment.
2403.4 Interior glazed areas.
504.2 Automatic sprinkler system
increase.
105.2 Work exempt from permit.
Electrical
TABLE 803.9 Interior Wall And
Ceiling Finish Requirements By
Occupancy
2308.8.3 Framing around openings.
2308.2 Limitations. 1. Exception
[F] 907.2.11.3 Interconnection.
2304.6.1 Wood structural panel
sheathing.
702.1 Definitions.
1009.5 Stairway landings.
402.4.3.1 Anchor building means of
egress.
112.1 Connection of service utilities.
705.2 Projections.
1905.1.1 Strength.
710.4 Continuity.
1906.3 Conduits and pipes
embedded in concrete.
Table 2508.5 Shear capacity for
261
29.
30.
31.
32.
C.
C.
A.
B
33.
34.
D.
C.
F-2, F-1
48 Hours
18 inches
no less than the thickness of the
parapet wall
shall be occupied safely
2
35.
36.
37.
D.
B.
B.
38.
39.
40.
41.
C.
B.
A.
B.
mezzanine
transfer
50
0
42.
43.
44.
45.
B.
A.
B.
B
46.
47.
48.
B.
D.
C.
6, 2
30
3
such greater thickness shall be
specified
greater
80
parallel
49.
No separation requirement
50.
51.
52.
53.
54.
D.
D.
B.
B.
55.
56.
57.
58.
D.
A
E.
D.
Closed System
a specified period
Certificate of Occupancy
the fees prescribed by law have
been paid, nor shall an amendment
to a permit be released until the
additional fee, if any, has been paid.
catchment
is allowed in Type I construction
All the above
8
59.
60.
61.
A.
C.
D.
Shearwall
R-3
naturally durable
262
62.
A.
True
63.
64.
65.
D.
A
B.
66.
67.
68.
69.
D.
B.
A
C.
70.
71.
72.
C.
B.
D.
73.
74.
D.
B.
75.
76.
B.
D.
77.
C.
78.
79.
80.
B.
B.
B.
81.
82.
83.
B.
A.
D.
84.
85.
86.
C.
D.
C.
87.
88.
B.
C.
42
occupant load
0.25 unit vertical in 12 units
horizontal
ACI 318
2
89.
90.
C
D
A-3
4
91.
92.
93.
C.
A.
D
High-Hazard
60,960 mm
3 inches
94.
95.
96.
A.
A.
A.
60, 45
fire separation distance
2 Stories , 14,500 SF
97.
98.
99.
100.
101.
D.
C.
B.
C.
B
102.
4, 102
103.
104.
D.
B.
105.
D.
106.
107.
108.
B.
A.
C.
B or C
This statement as written is False to
the Code.
taken down and removed or made
safe
Groups R-2, R-3
F-1
3
109.
110.
C.
A.
6, 8
0.25
111.
112.
113.
114.
115.
116.
A
B.
A.
A.
C.
A
34, 38
50
site plan
7
noncombustible
2 inches
117.
118.
D.
A.
119.
120.
121.
122.
123.
124.
125.
126.
D.
A.
C
B.
A.
A.
A.
A.
be added
14
24
False
building official
studs
battery backup
smoke detector
127.
A.
not penetrate
264
721.5.1(6)(C)}
2308.9.3 Bracing.1.
702.1 Definitions.
TABLE 503 Allowable Height And
Building Areas
110.4 Inspection agencies.
1011.5.2 Exit sign illumination.
401.1
702.1 Definitions.
2308.3.2 Braced wall line
connections.
1210.1 Floors and wall base finish
materials.
714.3 Fire test criteria
110.1 Inspections
116.1 Conditions.
107.2.3 Means of egress.
306.2 Factory Industrial F-1
1008.2 Gates. Exception 1008.2.1
Stadiums
602.4.1 Columns.
Table 1405.2 Minimum Thickness Of
Weather Coverings
1012.2 Height.
1607.7.1 Handrails and guards.
107.2.5 Site plan.
1027.5.1 Width.
602.2 Types I and II.
TABLE 720.1(2) Rated FireResistance Periods For Various Walls
And Partitions 9-1.1
105.2 Work exempt from permit.
TABLE 601 Fire-Resistance Rating
Requirements For Building Elements
(Hours)
402.4.1.4 Food courts.
2405.4 Framing. Exception
1507.2.9.2 Valleys. 1.
104.8 Liability.
1011.1 Where required. Exceptions
2304.3.1 Bottom plates.
[F] 907.2.11.4 Power source.
902.1 Definitions. [F] Smoke
Detector.
706.11 Ducts and air transfer
openings.
128.
129.
130.
131.
B.
A.
A.
A.
smoke compartment
ICC 300
only 1
1
132.
D.
133.
134.
135.
B.
D.
B
1.5
4
4.75 inches
136.
137.
A.
138.
139.
140.
D.
C.
D.
141.
142.
B.
D.
143.
144.
145.
146.
B.
B.
D.
B
3
necessary for the purpose of the
shaft
Anchor Building
draftstop
naturally durable
2
147.
148.
149.
D
C.
B.
thimble
30
1000
150.
151.
152.
153.
B.
E.
C.
C.
154.
155.
C.
D.
156.
157.
158.
159.
160.
161.
162.
C.
D.
D.
B.
C
A.
A
fire barrier
gross leasable area of the covered
mall building (excluding anchor
buildings)
450
building official
conspicuous place
construction documents
10 inches
fire door assembly
1 inch
702.1 Definitions.
1028.1.1 Bleachers.
1011.1 Where required. Exceptions 1.
715.5.8 Interior fire window
assemblies.
2308.8.4 Supporting bearing
partitions.
1012.7 Clearance..
1203.4.1 Ventilation area required.
TABLE 720.1(2) Rated FireResistance Periods For Various Walls
And Partitions 14-1.3
2104.1.6 Support on wood.
110.5 Inspection requests
305.2 Day care.
2308.9.10 Cutting and notching.
716.7 Flexible ducts and air
connectors.
2113.9 Termination.
708.8.1 Prohibited penetrations.
402.2 Definitions.
702.1 Definitions.
2304.11.2.4 Sleepers and sills.
TABLE 508.3.3Required Separation
Of Occupancies (Hours)
2113.17 Inlet.
1013.1 Where required.
1015. 5 Refrigerated rooms or
spaces.
712.3 Fire-resistance rating.
303.1 Assembly Group A3
2405.3 Screening.
2308.9.2.3 Nonbearing walls and
partitions.
702.1 Definitions.
402.4.1.1 Occupant formula.
719.3 Exposed installation.
110.1 Inspections
1004.3 Posting of occupant load.
107.3.4.2 Deferred submittals.
2109.3.4.2 Wall thickness.
702.1 Definitions.
Table 721.5.1(7) Minimum Cover
265
163.
B.
164.
165.
A.
A
166.
167.
168.
169.
170.
171.
172.
173.
174.
D.
B.
D.
A
C.
A.
C.
A.
C.
175.
176.
177.
178.
179.
180.
181.
A.
B
B.
A.
C.
C.
B.
continuous backing
6
smoke detection
restrictive
pedestrian access
1
nine, 2
Chapter 24
Name and location of the concrete
mixing plant.
ICC Electrical Code
two
any other appliance
1
0.75, 0.5
intervening airspaces
1.5
182.
183.
184.
185.
186.
187.
A.
B.
A.
B
D
C
listed
shaft
20
story height
10
8
188.
189.
190.
191.
C.
C.
B.
B.
7 feet
waterproof
2
4
192.
193.
194.
195.
196.
A.
C.
C.
B.
A.
266
1008.1.9.5 Unlatching.
Section 303.1 Assembly Group A
Exceptions 1
2406.4.1 Exceptions: 7.
2308.9.4.2 Nailing of bracing.
[F] 907.2.6.2 Group I-2
508.3.1 Occupancy classification.
1104.2 Within a site. Exception:
2113.20 Chimney fireblocking.
402.7.1 Attached garage.
2606.9 Bathroom accessories.
1901.4 Construction documents.
603.1.3 Electrical.
1109.5.1 Minimum number.
2113.13.2 Space around lining.
1023.3 Construction
1008.1.7 Thresholds.
2303.1.5.3 Wall insulation.
TABLE 601 Fire-Resistance Rating
Requirements For Building Elements
(Hours)
[F] 909.10.4 Automatic dampers.
702.1 Definitions.
402.16.1 Area.
502.1 Definitions.
704.5 Fire-resistance ratings.
TABLE 720.1(2) Rated FireResistance Periods For Various Walls
And Partitions
1208.2 Minimum ceiling heights.
1210.4 Waterproof joints.
1914.2 Minimum thickness.
1807.1.6.3 Masonry foundation walls.
9.
105.5 Expiration.
702.1 Definitions.
101.3 Intent.
2102 Definitions And Notations
1205.4 Stairway illumination.
197.
A.
smoke detection
198.
D.
199.
200.
201.
C.
B.
C.
60, 60
12th Grade
2 Stories , 8,500 SF
202.
203.
204.
205.
206.
C.
B.
B.
A.
D.
207.
208.
A.
A.
10
five
two
sleeping areas
within the next working business day
to the building official.
20, 10
reviewing and coordinating
209.
C.
Not Permitted
210.
C.
211.
D.
212.
213.
214.
215.
216.
C.
C.
A.
D.
D.
217.
218.
219.
220.
221.
C.
C.
D.
C.
C.
222.
223.
224.
225.
226.
227.
228.
A.
B.
A
D.
A.
C.
A
uplift forces
7
8 inches (203 mm)
collapsing into a bookfold position
Section 715
48
1.5, 1.5
229.
230.
E.
A.
231.
C.
green
232.
233.
C.
B.
234.
235.
236.
237.
238.
239.
240.
B.
C.
A.
B.
B.
C.
C.
241.
242.
243.
244.
245.
246.
247.
A.
A.
D.
C.
B.
A.
D
248.
249.
E.
C.
250.
251.
252.
253.
254.
255.
256.
B.
C.
D.
A.
C.
A.
C.
257.
258.
B.
C.
Combustible Dust
395
259.
260.
261.
262.
263.
C.
D.
B.
D.
C.
8
200 feet
suppression
Fire Protection Rating
16
264.
B.
268
12
in accordance with Sections
907.2.6.1 and 907.2.6.2.
fire damper
4
each side
building type of construction
0.375
membrane penetration
The test methods shall be as
specified in this code or by other
recognized test standards.
bituminous coating
3
1/2-inch
1, 8
0.0416, 5.5
180 days
3 inches
265.
266.
267.
B.
B.
A.
labeled
44
0
268.
269.
270.
C.
C.
C.
protected
3
protected openings
271.
272.
273.
D.
E.
C.
274.
275.
276.
277.
278.
279.
280.
281.
282.
B.
D
B.
B.
A.
A.
C.
C.
8
weep holes
2
Type IV
20 feet
3
covered or concealed
10, 20
283.
284.
B.
A.
285.
286.
287.
288.
289.
290.
291.
D.
A.
C.
A.
B.
C.
B
5
1 occupant for each 200 gross
square feet.
50
50
reenter
thermal barrier
7
Type III
10-foot
292.
D.
nonabsorbent
293.
294.
295.
296.
297.
298.
299.
300.
301.
B.
C.
D.
B.
D.
A.
A.
D.
B.
4
50
All of the above
1.5
I-3
4
newel posts
I-2
7
2303.2.4 Labeling.
1029.3 Maximum height from floor.
TABLE 601 Fire-Resistance Rating
Requirements For Building Elements
(Hours)
709.6 Openings.
2308.2 Limitations. 1.
705.10 Ducts and air transfer
openings.
1604.1 General.
105.3 Application for permit.
402.4.3.1 Anchor building means of
egress.
2308.3.2 Braced wall line
connections.
2113.12 Clay Flue lining (installation).
2113.10.1 Masonry veneer chimneys.
2113.19 Chimney clearances.
602.4 Type IV.
402.5.1 Minimum width.
1206.2 Yards.
110.6 Approval required
[F] 904.11.1 Manual system
operation.
1103.2.11 Residential Group R-1.
TABLE 1004.1.2
1109.12.4 Food service lines.
2113.15 Flue area (appliance).
1027.1 General.
2603.7 Plenums.
1005.2 Door encroachment.
602.3 Type III.
Table 1505.1 Minimum Roof Covering
Classification For Types Of
Construction
1210.1 Floors and wall base finish
materials.
2111.9.1 Hearth thickness.
1007.7.1 Openness.
402.4.2 Number of means of egress.
2308.9.5.2 Header support.
308.4 Group I-3.
2308.8.3 Framing around openings.
1012.4 Continuity.
308.3 Group I-2.
Table 1028.10.1 Smoke-Protected
269
302.
303.
B.
B.
used or occupied
6
304.
305.
D.
B.
of new units
14
306.
B.
307.
308.
309.
B.
D.
B.
310.
311.
312.
B.
B.
B.
313.
C.
314.
315.
316.
C.
B
B.
10
3
The building official is authorized to
suspend or revoke a permit issued
under the provisions of this code
wherever the permit is issued in error
or on the basis of incorrect,
inaccurate or incomplete information,
or in violation of any ordinance or
regulation or any of the provisions of
this code.
1-hour fire barriers and floor/ceiling
assemblies in Group B, F, H, M, S
and U occupancies. 2-hour fire
barriers and floor/ceiling assemblies
in Group A, E, I and R occupancies
44
Business Group B
16, 8
317.
D.
tested
318.
C.
319.
320.
B.
C.
321.
322.
A.
B.
323.
D.
324.
325.
326.
327.
B.
D.
C.
D
40
All of the above
ASTM D 5055
3 inches (76 mm)
270
328.
329.
330.
331.
A.
B.
D.
C.
1-inch by 3-inch
fire area
sheathed
75
332.
333.
334.
335.
A
A.
A.
C
adequately reinforced
most restrictive
70 inches
3
336.
D.
337.
338.
C.
D.
339.
C.
340.
B.
tempered
341.
342.
343.
344.
345.
346.
347.
A.
B.
B.
B.
B.
B.
A.
3
1-hour
False
32
96
moisture
34 inches to 42 inches
348.
349.
350.
C.
A.
B
18 inches by 24 inches
exit passageway
5.4 inches
351.
352.
353.
354.
355.
356.
357.
358.
D.
B.
B.
B.
B.
B.
B.
A.
359.
360.
B.
B.
board of appeals
30
7, .375
0.012 aluminum foil
remain in place
False
2
Group H, but shall be classified as
the occupancy that they most nearly
resemble.
automatic
15
361.
C.
362.
363.
364.
365.
B.
A.
D.
C.
366.
367.
368.
369.
370.
C.
C.
D.
C
B.
371.
372.
D.
D.
30
red
manufacturers instructions
24
manufacturers installation
instructions
smoke barrier
26-75, 0-450
373.
C.
self-closing or automatic-closing
374.
B.
500
375.
376.
D.
A.
36
4
377.
378.
D.
D.
12, 6
All of the above
379.
380.
381.
382.
383.
A
B.
D.
B.
C.
384.
385.
386.
387.
388.
D.
D.
A.
C.
D.
389.
390.
391.
392.
D.
D.
B.
B.
grade plane
reasonable cause, reasonable times
light fire-test exposure
156, 25
evidence of satisfactory strength is
submitted to and approved by the
building official
perpendicular
B or C
2, 1
disconnection of utility service
393.
394.
395.
396.
272
B.
C.
A.
B.
20
1
accessible to the public
shall not
109.6 Refunds.
1002.1 Definitions.
2111.13.6 Outlet
111.2 Certificate issued.
Table 1405.2 Minimum Thickness Of
Weather Coverings
[F] 905.3.1 Building height.
[F] 907.4.2.3 Color.
2113.13.1 Listed materials.
1507.2.8.2 Ice barrier.
107.2.4 Exterior wall envelope.
702.1 Definitions.
803.1.1 Interior wall and ceiling finish
materials. Class B:
711.5.3 Self- or automatic-closing
doors
402.4.3 Arrangements of means of
egress.
1029.5.1 Minimum size.
TABLE 1106.1 ACCESSIBLE
PARKING SPACES
2113.2 Footings and foundations.
706.7 Combustible framing in fire
walls.
1008.1.4.3 Horizontal sliding doors. 2.
[F]903.2.1.3 Group A-3., 1.
507.2 Sprinklered, one story.
1208.2 Minimum ceiling heights.
Section 303.1 Assembly Group A
Exceptions 3
502.1 Definitions.
104.6 Right of entry.
1505.4 Class C roof assemblies.
706.8 Openings.
1905.6.2 Frequency of testing.
Exception
2508.5.2 Installation.
1009.2 Headroom.
708.4 Fire-resistance rating.
112.3 Authority to disconnect service
utilities.
402.11 Kiosks., 3
1507.6.2 Deck slope.
309.1 Mercantile Group M.
1109.2.1.5 Prohibited location.
397.
398.
399.
400.
C.
C.
C.
C.
building official
4
90
12
401.
402.
403.
D.
B.
A
"Phased approval."
an application has been filed.
termination
404.
405.
406.
B.
A.
C.
407.
A.
4
1000
Banquet halls, Night clubs,
Restaurants, Taverns and bars
This is a True statement
408.
C.
409.
410.
411.
412.
413.
414.
415.
416.
D.
B.
C
B.
B.
A.
A.
B.
Chapter 17
maximum area of 300
middle one-third
100
B
18 inches
doorknob
19 feet 6 in
417.
418.
419.
420.
421.
A.
A.
B
A.
B
l/360
R-1, R-2 or R-3
Level 2 aerosol products.
1
2.5 inches
422.
B.
423.
424.
425.
A.
C.
C
1
other pertinent laws or ordinances.
that indicated in Table 508.2.5.
426.
427.
428.
C.
A.
B.
automatic-closing
This is True
Type B
429.
B.
3 Stories , 18,000 SF
430.
431.
432.
433.
434.
435.
436.
437.
438.
439.
440.
C.
C.
C.
B.
A.
B.
A.
B.
B.
C.
C.
ASTM E 136
kitchens
750
Section 705.11
manual
34, 48
.5, .5
3
20
19
comply with ACI 318, Section 6.2.
441.
442.
C.
D
443.
444.
C.
C.
18
They shall be classified in the
occupancy that they most nearly
resemble.
50
registered design professional
445.
446.
B.
A.
447.
448.
D.
A.
36, 30
This statement is True for Covered
Mall Buildings
Groups R-2, R-3 and R-4
True
449.
450.
451.
452.
453.
B
A
B.
D.
A.
2 times
2.5
250
vertically
50000
454.
455.
456.
B.
D.
D.
entire span
method of drying after treatment.
NP (Not Permitted)
457.
458.
459.
A.
A.
A.
1.625
through penetration
any material
460.
A.
22
461.
A.
462.
D.
463.
464.
C.
D.
274
465.
466.
467.
B.
B.
B.
water
oriented strand board
comply with the requirements of ACI
318, Section 5.12.
48
energy, fuel or power.
shall not
substitute
468.
469.
470.
471.
C.
A.
B.
D.
472.
473.
474.
475.
B.
C.
C
B.
476.
A.
fire partition
A-4
35 feet (10 668 mm)
the requirements of this section shall
apply.
is not
477.
478.
479.
480.
B.
B.
C.
C.
12
four
fireblocking
1 hour
481.
482.
B.
B.
483.
C.
484.
C.
100
for the preparation of food for service
to the public
by the applicable governing
authority.
where approved
485.
486.
487.
488.
489.
B.
B.
A.
D.
A.
490.
B.
491.
492.
493.
494.
495.
496.
497.
498.
B.
C.
A.
B.
C.
D.
A.
D.
covered
2 inches by 2 inches
4, 0.5
Section 2604.2
International Mechanical Code and
the International Plumbing Code
aisles leading to exits or exit access
doorways
3.5
30
2
Dwelling Unit
a separate building
66 inches
violation
.5, 24
499.
D.
Unlimited , Unlimited
500.
A.
holders
2509.3 Limitations.
2302.1 Definitions.
1905.12 Cold weather requirements.
2308.9.2.1 Top plates.
112.2 Temporary connection.
2308.2 Limitations. 6.
107.3.4 Design professional in
responsible charge. 106.3.4.1
702.1 Definitions.
303.1 Assembly Group A.
2308.3.1 Spacing.
402.4 Means of egress.
402.7 Fire-resistance-rated
separation.
1809.4 Depth and width of footings.
1007.2.1 Elevators required..
717.2 Fireblocking.
Table 508.2.5 Incidental Accessory
Occupancies
2308.2 Limitations. 4.
1210.5 Toilet rooms.
109.2 Schedule of permit fees.
2304.9.3 Joist hangers and framing
anchors.
1510.4 Roof recovering.
2308.8.3 Framing around openings.
[F] 501.2 Premises identification.
[F] 806.3 Foam plastic.
603.1.2 Piping.
1025.9 Assembly aisles are required.
1910.1 General.
706.6 Vertical continuity.
708.4 Fire-resistance rating.
Definitions Page 14
706.1 General.
402.4.5 Access to exits.
111.4 Revocation.
TABLE 2304.6 MINIMUM
THICKNESS OF WALL SHEATHING
TABLE 503 Allowable Height And
Building Areas
107.3.3 Phased approval.
275
A
A.
C.
A.
Timed Exam 1- 5.
A.
Timed Exam 1- 6.
C.
Timed Exam 1- 7.
Timed Exam 1- 8.
B.
B.
4
12
Timed Exam 1- 9.
A.
l/360
B.
B.
D.
A.
A.
exit passageway
R-1, R-2 or R-3
B.
50
D.
10, 30
A.
B.
C.
B.
D.
D.
B.
B.
B.
B.
B.
276
B.
D.
covered
18, 8
B.
D.
C.
B.
C.
D.
B.
A.
1/2-inch
comply with ACI 318, Section
6.2.
Certificate of Occupancy
ceiling radiation damper
taken down and removed or
made safe
500
is not
C.
D.
D.
R-3
catchment
all the above.
C.
B.
intervening airspaces
tempered
C.
Not Permitted
B.
dead-end mall
A.
C.
A.
D.
C.
B
F-1
red
1 occupant for each 200 gross
square feet.
Fire Protection Rating
blocked from use
2.5 inches
C.
50
B.
D.
A.
A.
False
evidence of satisfactory
strength is submitted to and
approved by the building
official
each side
A
= 360)
1510.4 Roof recovering.
Table 1809.7 Prescriptive
Footings Supporting Walls Of
Light-Frame Construction
1103.2.11 Residential Group
R-1.
2304.11.2.5 Girder ends.
1906.2 Removal of forms,
shores and reshores.
111.2 Certificate issued.
702.1 Definitions.
116.1 Conditions.
1104.3.2 Press boxes.
402.7 Fire-resistance-rated
separation.
2109.3.1.3 Moisture content
requirements.
310.1 Residential Group R.
1025.9.2 Aisle width.
716.7 Flexible ducts and air
connectors.
2303.1.5.3 Wall insulation.
2406.5 Fire department
access panels.
TABLE 503 Allowable Height
And Building Areas
402.4.3.1 Anchor building
means of egress.
306.2 Factory Industrial F-1
[F] 907.4.2.3 Color.
TABLE 1004.1.2
702.1 Definitions.
[F] 905.7 Cabinets.
TABLE 720.1(2) Rated FireResistance Periods For
Various Walls And Partitions
Item number 6-2.2
1008.1.4.1.1 Egress
component. 1.
102.2 Other laws.
1905.6.2 Frequency of testing.
Exception
1009.10 Handrails.
TABLE 803.9 Interior Wall And
277
E.
D
A.
180 days
B.
A.
D.
A.
2 Stories , 14,500 SF
D.
D.
D.
C
A.
C.
B.
A.
"Phased approval."
36
gross leasable area of the
covered mall building
(excluding anchor buildings)
10 inches
fire door assembly
F rating
The building official is
authorized to suspend or
revoke a permit issued under
the provisions of this code
wherever the permit is issued
in error or on the basis of
incorrect, inaccurate or
incomplete information, or in
violation of any ordinance or
regulation or any of the
provisions of this code.
Section 715
A.
4, 0.5
A.
D.
7
within the next working
business day to the building
official.
278
715.2 Fire-resistance-rated
glazing.
[F] 501.2 Premises
identification.
1027.5.1 Width.
105.2.1 Emergency repairs.
A.
A.
A.
1.625
newel posts
smoke detection
A.
60,960 mm
Timed Exam 2- 1.
Timed Exam 2- 2.
B.
D.
Timed Exam 2- 3.
Timed Exam 2- 4.
Timed Exam 2- 5.
C.
A.
A.
Timed Exam 2- 6.
Timed Exam 2- 7.
B.
D.
shall not
subject to penalties as
prescribed by law.
450
fire separation distance
Group H, but shall be
classified as the occupancy
that they most nearly
resemble.
2
registered design professional
Timed Exam 2- 8.
Timed Exam 2- 9.
Timed Exam 2- 10.
B.
B.
A.
32
moisture
This is True
A.
D.
A.
B.
B.
B.
C.
ICC 300
be added
.5, .5
7, .375
Anchor Building
7
C
C.
C.
B.
C.
B.
A.
90
self-closing or automaticclosing
Groups R-2, R-3
have an exterior exposure
durability classification.
10
0
C.
C.
C.
is considered a hazardous
location installation
below
30
1406.2.4 Fireblocking.
1012.4 Continuity.
402.4.5.1 Exit passageway
enclosures.
402.4.4 Distance to exits.
2308.2 Limitations. 6.
115.3 Unlawful continuance.
719.3 Exposed installation.
702.1 Definitions.
307.1 High-Hazard Group H.
Exceptions 5
2113.19 Chimney clearances.
1906.3 Conduits and pipes
embedded in concrete.
1008.1.1 Size of doors.
1503.2 Flashing.
2113.13.2 Space around
lining.
1028.1.1 Bleachers.
402.4.1.4 Food courts.
2304.10.4 Floor decks.
2508.5.4 Fasteners.
402.2 Definitions.
1208.1 Minimum room widths.
TABLE 803.9 Interior Wall And
Ceiling Finish Requirements
By Occupancy
1011.5.3 Power source.
711.5.3 Self- or automaticclosing doors
107.2.3 Means of egress.
2304.6.1 Wood structural
panel sheathing.
402.5.1 Minimum width.
TABLE 601 Fire-Resistance
Rating Requirements For
Building Elements (Hours)
2406.4Hazardous locations.
2405.3 Screening.
2113.12 Clay Flue lining
(installation).
279
B.
B.
A
entire span
termination
B
B.
B.
C.
C.
B.
C
A
A.
A.
listed
A.
sleeping areas
B
C.
B.
B.
B.
D.
2 times
1
shaft
labeled
6
naturally durable
C.
C.
D.
D.
D.
C.
interconnected
qualifications and reliability
voice/alarm communication
system
1 hour
A.
C.
B.
collector
8
Adobe Construction
B.
B.
C.
1-hour
self-closing
automatic sprinkler system
C.
12
280
A.
A.
14
building official
C.
D.
750
compliance with this code.
D.
C.
C.
A.
C.
B.
A.
C.
18 inches
48 Hours
D.
A.
A.
D.
A.
A.
smoke barrier
180 days, 180 days, 180 days
Chapter 24
naturally durable
violation
only 1
A.
A.
site plan
1-inch by 3-inch
Timed Exam 3- 1.
Timed Exam 3- 2.
Timed Exam 3- 3.
Timed Exam 3- 4.
Timed Exam 3- 5.
Timed Exam 3- 6.
D.
B.
B.
A.
C.
C.
I-3
100
False
most restrictive
mezzanine
60 feet
Timed Exam 3- 7.
D.
Timed Exam 3- 8.
Timed Exam 3- 9.
Timed Exam 3- 10.
Timed Exam 3- 11.
C
A.
B.
C.
A.
annual permit.
A
D.
B.
B.
A.
2.5
66 inches
five
12000
any material
A.
manual
D.
C.
B.
of new units
The test methods shall be as
specified in this code or by
other recognized test
standards.
disconnection of utility service
A.
D.
B.
B
A.
B.
B.
B.
D.
B.
C.
B.
A.
D.
D.
D.
282
through penetration
manufacturers instructions
3
story height
International Mechanical Code
and the International Plumbing
Code
is allowed in Type I
construction
5 persons for each lane
including 15 feet of runway
aisles leading to exits or exit
access doorways
a two-way communication
system
not less than 1-hour fireresistance-rated walls and
minimum fire protection rating
of openings in the
fire barriers of 1-hour
44
2
2 hours and automatic
sprinkler system
approved
permanent open space of not
less than 60 feet, three stories
in height
T rating
ACI 318, Section 5.2
A.
A.
D.
B.
B.
occupant load
Reviewed for Code
Compliance.
16, 8
C.
D.
D
A
not permitted
perpendicular
3 inches (76 mm)
1.5, 1.5
A.
D.
B.
B.
C.
B.
C.
B.
protected
regardless of area or height
fire door
36
D.
A.
A or C
4
A.
C.
A.
waterproof
18 inches
C.
A.
membrane penetration
uplift forces
D.
D.
200 feet
Unlimited , Unlimited
B.
44
B.
transfer
A.
A.
Shearwall
1
proportions. .
2104.1.6 Support on wood.
1009.5 Stairway landings.
105.2 Work exempt from
permit. Electrical
1002.1 Definitions.
107.3.1 Approval of
construction documents.
2111.10 Hearth extension
dimensions.
1909.2 Limitations.
2508.5.2 Installation.
2308.7 Girders.
1509.5.1 Noncombustible
construction required.
112.2 Temporary connection.
2406.4.1 Exceptions: 7.
402.16.2 Height and width.
1208.2 Minimum ceiling
heights.
709.6 Openings.
2406.4 Hazardous locations
702.1 Definitions.
1025.9.1 Minimum aisle width.
1. Exception
502.1 Definitions. Grade Plane
706.7 Combustible framing in
fire walls.
TABLE 1106.1 ACCESSIBLE
PARKING SPACES
2308.3.2 Braced wall line
connections.
1210.4 Waterproof joints.
705.11.1 Parapet
construction.
702.1 Definitions.
2304.9.7 Framing
requirements.
402.4.4 Distance to exits.
TABLE 503 Allowable Height
And Building Areas
1029.3 Maximum height from
floor.
2304.3.2 Framing over
openings.
2302 Definitions
1008.1.9.5 Unlatching.
283
C.
D.
A.
D.
A.
C.
D.
D.
D.
A.
Timed Exam 4- 1.
B.
2 inches by 2 inches
Timed Exam 4- 2.
B.
Timed Exam 4- 3.
Timed Exam 4- 4.
Timed Exam 4- 5.
Timed Exam 4- 6.
E.
D.
C.
C.
Timed Exam 4- 7.
B.
Timed Exam 4- 8.
C.
Timed Exam 4- 9.
A.
B.
A.
C.
is flush with
24
where approved
B.
500
A.
A.
B.
D.
3
3
20
All of the above
A.
B.
studs
three
284
706.3 Materials.
[F] 903.4 Sprinkler system
supervision and alarms.
2403.2 Glass supports.
[F] 806.3 Foam plastic.
107.3.3 Phased approval.
717.2 Fireblocking.
602.4.2 Floor framing.
803.1.1 Interior wall and
ceiling finish materials. Class
B:
104.6 Right of entry.
1210.3 Showers.
A.
50000
B.
C.
B.
B.
C.
C.
C.
B
C.
A.
B.
A.
B.
C.
A.
smoke compartment
30
True
B.
C.
30
90 plf
D.
.5, 24
C.
395
C.
C
48
8
B.
C.
D.
A
2500
4.5
B or C
1 inch
B.
B.
fire area
automatic
D.
substitute
C.
3 inches
adequately reinforced
B.
D.
A.
A.
B.
C.
B.
two
Banquet halls, Night clubs,
Restaurants, Taverns and
bars
3 Stories , 18,000 SF
C.
A.
C.
building official
until released by the building
official.
4
B.
D.
4
All of the above.
B.
C.
D.
C.
B.
E.
C.
construction documents
minimum
sheathed
42
250
A and D
75
B
C.
Business Group B
750
B.
D.
A
D.
34, 48
20 inches by 30 inches
34, 38
comply with the provisions of
ACI 318, Section 6.4
B
This is a false statement as to
the IBC.
service or maintenance
personnel
B.
B.
D.
Timed Exam 5- 1.
Timed Exam 5- 2.
A.
C.
1
25, 40
Timed Exam 5- 3.
Timed Exam 5- 4.
Timed Exam 5- 5.
B.
C.
A.
Timed Exam 5- 6.
A.
draftstop
156, 25
This statement is True for
Covered Mall Buildings
0
Timed Exam 5- 7.
D.
Timed Exam 5- 8.
A.
Timed Exam 5- 9.
Timed Exam 5- 10.
C.
B.
4
0.375
A.
B.
C.
1
This is a false statement as to
the IBC.
ASTM D 5055
A.
B.
C.
A.
B.
D.
D.
B.
Group A Exceptions 3
1008.1.9.2 Hardware height.
1209.2 Attic spaces.
1012.2 Height.
1906.4 Construction joints.
304.1 Business Group B
603.1 Allowable materials.
1109.12 Controls, operating
mechanisms and hardware.
Exceptions 1.
50
B.
1.5
A.
10-foot
B.
C.
A.
A.
C.
B.
B.
C.
D.
D.
C.
B.
D.
A
A.
C
B.
D.
D.
15
automatic-closing
3
thermal barrier
4
Motion picture theaters
Symphony and concert halls
Television and radio studios
admitting an audience
Theaters
shall not
the floor above such a parking
area
upon notification
General Contractors name.
10
0.0416, 5.5
vertically
without special knowledge or
effort
20
24
7
necessary for the purpose of
the shaft
They shall be classified in the
occupancy that they most
nearly resemble.
tested
D.
D.
B.
E.
B.
C.
B.
288
B.
E
A.
fire partition
A and C
1
C.
A.
True
B.
B
A.
C.
two
50
20, 12
B.
D.
fire damper
nonabsorbent
A
A.
building official
34 inches to 42 inches
B.
B.
B
C.
B.
greater
1.5
such greater thickness shall
be specified
1, 8
7
B.
B.
C.
E.
B
B.
B.
B
area of refuge
6, 2
kitchens
All of the above items.
24 feet (7315 mm)
suppression
3
4, 102
B.
C.
20
40, 60
Timed Exam 6- 1.
Timed Exam 6- 2.
weep holes
materials.
702.1 Definitions.
705.2 Projections.
1108.4.2.1 Central holding
cells.
2308.8.3 Framing around
openings.
104.9.1 Used materials and
equipment.
1910.1 General.. Exceptions
1.
1109.5.1 Minimum number.
1208.3 Room area. Exception
2111.10 Hearth extension
dimensions.
702.1 Definitions.
1210.1 Floors and wall base
finish materials.
110.1 Inspections
1013.3 Opening limitations.
Exceptions 1
704.5 Fire-resistance ratings.
2308.9.5.2 Header support.
1907.7.8 Fire protection.
1010.2 Slope.
Table 1028.10.1 SmokeProtected Assembly Aisle
Accessways
1002.1 Definitions.
2304.11.2.6 Wood siding.
1208.3 Room area.
105.3 Application for permit.
2109.3.4.2 Wall thickness.
402.11 Kiosks., 2
2113.9 Termination.
1210.1 Floors and wall base
finish materials.
[F] 2604.2.1 Density.
2308.9.11 Bored holes.
Timed Exam 6- 3.
D.
7, 4, 11
Timed Exam 6- 4.
B.
Timed Exam 6- 5.
4.75 inches
Timed Exam 6- 6.
Timed Exam 6- 7.
B.
D.
Section 705.11
conspicuous place
Timed Exam 6- 8.
Timed Exam 6- 9.
Timed Exam 6- 10.
C.
D.
C.
C.
A
building area
All of the above
those necessary for the
purpose of the shaft
ASTM E 136
2 inches
C.
B.
C.
C.
50
Type IV
18 inches by 24 inches
2 Stories , 8,500 SF
B.
B.
D.
ACI 318
C.
C.
A-3
2
B.
C.
C.
C
100
1-hour fire barriers and
floor/ceiling assemblies in
Group B, F, H, M, S and U
occupancies. 2-hour fire
barriers and floor/ceiling
assemblies in Group A, E, I
and R occupancies
30
50 feet (15 240 mm)
A.
D.
bituminous coating
NP (Not Permitted)
290
D.
D.
a specified period
80
D.
D.
C
five, 2 1/2
Chapter 17
No separation requirement
D.
B.
50
14
B.
C.
A.
A.
B.
2, 1
60, 60
1
ICC Electrical Code
1000
D.
D.
A.
C
B
A.
C.
C.
middle one-third
no less than the thickness of
the parapet wall
30
by the applicable governing
authority.
10, 20
C.
D.
Type III
board of appeals
B.
B.
D
B.
A.
A
B.
B.
C.
C.
fire resistance
2
thimble
ventilation openings to the
interior
1000
one-half
for the preparation of food for
service to the public
40
42
7 feet
D.
A.
22
D
D.
B.
B.
C.
C.
C.
10
grade plane
1.5
the requirements of this
section shall apply.
green
fire barrier
protected openings
B.
C.
A.
D.
A.
C.
D.
C.
Combustible Dust
19
20, 10
fire resistance rating
doorknob
0.75, 0.5
shall be occupied safely
3
one-eighth, one-quarter
C.
C.
C.
a separate building
The building official is
authorized to establish a
refund policy.
A-4
292