TAC2413 Quick Reference

TAC 2413
Quick Reference

0FL-3898-000

This quick reference briefly describes the functions that are used on a
daily basis. All functions are described in detail in the handbook.

Explanation of the display window


Parameter number

6
Cooling
coil
Heat
recovery
Alarm
Heating
coil

5
4
3
2
1
0

MO

P 00
+

WE

Off

Return air
fan

TH

FR

SA

SU

12:00

TF FF

Supply air
fan

Parameter value

10 11 12 13 14 15 16 17

TU

24-hour
time bar

Timed
operation

Manual
control

Full speed
Half speed,
single speed
operation

19
20
21
22

Dx
Pv Pk

1
1

%
C

18

23
24

Electric
heating
element
DX
cooling

Pump,
cooling coil

Pump,
heating coil

Switch between the parameters P 00 to P 17 and P 18 to P 99 by


pressing
and at the same time.

Reading temperatures
Temperature
Supply air temperature
Room temperature
Return air temperature
Exhaust air temperature
Outdoor temperature

P No.
Procedure
P 01 1. Choose the parameter
number (P No.) by pressing
P 03
or . Increase the number
P 05
by pressing ; decrease it
P 08
with . Hold the button down
P 09
for fast increase/decrease.
2. Read the value.

Setting temperatures
Temperature

P No.

Procedure

2. Read the value.

Setting temperatures
Temperature
Heating setpoint
Cooling setpoint

P No.
Procedure
P 10 1. Choose the P No. using or
P 11
. Increase it using and
decrease it using .
2. Change the parameter value
using or . Hold the
button down for fast increase/
decrease.
3. Confirm by pressing
.

Setting time schedules


Program
Weekly program 1/2 speed
(single speed operation)

P No.
Procedure
or .
P 12 1. Choose P 12 using
2. Use
to go forward and
to go backward.
3. Change the half-hour segments
using
( = daytime op.).

Weekly program 1/1 speed

P 13 1. Choose P 13 using
or
and follow the above
instructions for settings.

Setting the yearly program

P 15 1. Choose P 15 using and


choose a holiday period
(1 to 6) using or . Exit
by using
.
P 16 2. Go to P 16 using ; change
start date (month.day) using
or . Use
to exit.
P 17 3. Choose P 17 using ,
change the stop date using
or . Confirm with
.

Deleting a holiday period

P 15 1. Choose a holiday period (see


above).
P 16
P 17 2. Change the start or stop date
to [month].00 using
or .
3. Confirm by using
.

Choosing the operating mode


Symbol Operating mode

P No.

Procedure
1. Select P 00 using or .
Off
P 00
2. Choose the desired mode
Half speed, sing. sp.
using or . During
manual control, choose or
Timed operation
. The symbol appears
Full speed
in the window as well.
3. Confirm by using
.
Manual control
1

P.T.O.

l3898000.PM6

1998-12-15, 15:27

Resetting alarms
Symbol
Cause of the alarm
P No.
! TF, FF Fan alarm
P 72 1.
+
!
Frost protection
P 73
+
!
Faulty frost prot. sensor P 74
! P
Pump alarm, heating coil P 75 2.
v
!
Overheating electric heat. P 76
+
!
Freezing alarm
P 77 3.
!

Fire alarm
Efficiency alarm
Deviation alarm

P 78
P 79
P 80

Procedure
Choose the P No using
or . To reach P18
to P 99, press
and
at the same time.
The appropriate alarm
symbols will flash.
Priority A alarms which
will stop the system
are reset using
when the cause has
been remedied. Priority
B alarms are reset
automatically.

Setting the clock


Action
Reading the time
Setting the time

Setting the month and day


Setting the year

Procedure
P No.
P 00 Read hour:minute
P 96 1. Choose P No. using or .
2. Change the time using
or
. Hold the button down for
a rapid change.
3. Confirm by using
.
P 97 Change month.day, see above.
P 98 Change the year, see above.

List of parameters
The following list comprises all parameters.
For a full description of them, please refer to the manual.
P
00
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
16
17

Parameter
Time. Indication, op. mode
Supply air temperature
Calculated SP, supply air temp.
Room temperature
Calculated SP, room temp.
Return air temperature
Return temp., heating coil
HEX efficiency (%)
Exhaust air temperature
Outdoor temperature
Heating setpoint
Cooling setpoint
Weekly prog., 1/2 speed sing.
Weekly program, 1/1 speed
Timer, extended day op., min
Yearly program
Start of holiday
End of holiday

P Parameter
56 SPC effect at 2 and 10 V,
respectively ( or +)
57 Setpoint CO2
58 P band supply air controller
during HEX control
59 I time supply air c., HEX cont.
60 P band, supply air controller
during heating control
61 I time, supply air controller
during heating control
62 Return limitation controller
setpoint for heating coil
63 P band return limit. controller
64 I time return limit. controller
65 Holding controller setpoint for
heating coil
66 P band, holding controller
67 I time, holding controller

13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55

Weekly program, 1/1 speed


Timer, extended day op., min
Yearly program
Start of holiday
End of holiday
Output signal to HEX (%)
Output signal to heat.valve (%)
Output signal to cool. valve (%)
Winter/Summer status
Night cooling (Status)
Defrosting (Status)
Night cooling setpoint
Night heating setpoint
Min SP supply air, heat. control
Min SP supply air, cool. control
Max SP, supply air
Frost protection setpoint
Damper control, function sel.
Minimum damper position
Starting delay TF, +10 C
Starting delay TF, 10 C
Heating valve, initial position
Outdoor temp. limit for pump
stop, heating coil
Re-blowing time, electric heat
Ec.limit outdoor air return air
Min. temp. limit SP, HEX
P band defrosting contr., HEX
I time defrosting contr., HEX
Time TF stop, rapid defrosting
Max allowed defrosting time
Min outdoor temp., night cool.
Max. time to next normal op.
period
Disabling Y1, Y2 after night c.
Choice of summer time
Summer half start month
Winter half start month
Start winter compensation
Max. winter compensation
Stop winter compensation
Start summer compensation
Max. summer compensation
Stop summer compensation
SPC/CO2, selection

0FL-3898-000 (GB), 1998-12-15

l3898000.PM6

64 I time return limit. controller


65 Holding controller setpoint for
heating coil
66 P band, holding controller
67 I time, holding controller
68 P band, supply con. at cool.ctrl
69 I time, supply con. at cool. ctrl
70 Gain, room controller
71 I time, room controller
72 Fan alarm tripped
73 Frost alarm tripped
74 Faulty frost sensor al. tripped
75 Pump alarm heating c. tripped
76 Alarm, electric heater
overheating tripped
77 Freezing alarm tripped
78 Fire alarm tripped
79 Efficiency alarm tripped
80 Deviation alarm tripped
81 Fan alarm, choice of type
82 Fire alarm, choice of type
83 Efficiency alarm, choice of
alarm type
84 Efficiency alarm, alarm limit
85 Deviation alarm (0=disabled,
1=active) during summer half
86 Deviation alarm, alarm type
87 Deviation alarm, alarm limit
88 Manual control, alarm choice:
0=no sum,1=sum alarm
89 Room sensor adjustment
90 Outdoor temp. block 1/1 speed
91 TF stop at night heating
92 Neutral zone, supply air contr.
93 SPC/CO2 input signal
94 --95 --96 Clock
97 Date
98 Year
99 Version. Type of controller and
program version

English

1998-12-15, 15:27