You are on page 1of 4

PATTON REPORT NO.

40

A FEW OPINIONS
©1975 Patton Life Safety Systems, Inc.

In this issue of the Patton Report I give opinions on several Well, as scary as it sounds, the elevator faults really were'nt
important subjects. all that serious. Why? Because the cures were so easy. Here's
the solution to these problems:
THE NUMBER TWO HIGH RISE NEED 1. Install call buttons that don't respond to smoke,
2. Install electric eyes that will permit the doors to
The number one high rise need, of course, is the Life Safety close after the proper cycle.
Sprinkler System designed by engineering methods to meet But some people had what they thought was a better idea.
BOCA-100.* This "better idea" was no doubt prompted by the fact that
The second most important need for the high rise building most codes do not consider an elevator to be an approved
is a fire safe elevator. "exit way" under fire conditions. Since the elevator was not
A few years ago a few people were killed on elevators in an "exit" why not bring it down and park in on the ground
fires. At the time this did not appear unduly significant floor, they reasoned. If it's taken out of service, nobody can
because elevator deaths represented an extremely small get hurt on it. Well, that's true enough!
percentage of the fire deaths in buildings. However, for reasons There is one big problem associated with this solution,
unknown to me, while it's not considered unduly significant to however. It is that the cure is far worse than the disease. It
be killed on a stairway (and its almost fashionable to be killed takes the only really practical way to get out of the building
in a corridor on the way to a stairway), dying on an elevator is away from the people at the very time when they need it the
considered to be totally intolerable. most.
It is alleged that there were two elevator characteristics that Oh, the elevators are safe enough now. They were parked
were responsible for the deaths. down at the ground well removed from the fire and smoke ...
One was "call buttons" that presumably could be activated But, the people, That's another matter.
by the smoke to bring the elevator to the fire floor. Someday, hopefully before it is too late, we must stop
The second was the electric eye in the door that, when being illogical about elevators as fire exits. We must recognize
blocked by smoke, prevented the doors from closing. them as safe and approved exit ways for tall buildings.

*When sprinklers are installed, many of the old regulations that are structure oriented, and predicated on a non sprinklered
building, should be revised or eliminated.
A PRACTICAL LIFE SAFETY
SYSTEM FOR THE HOME
At present, high rise buildings and nursing homes are Nozzles: While existing conventional sprinklers are
getting the lions share of the attention on the fire front. But tolerable, they actually have very uneven water
nearly 90% of those who die from building fires die from distribution characteristics. Improved designs are
dwelling fires. So, if life safety is our goal, the dwelling must desirable. Also, it will often be necessary to use small
be our primary target. orifice sprinklers (often listed as "spray nozzles") in the
Most people believe that a life safety system is impractical following sizes: 1/4" (K = 1.3), 5/16" (K=1.9), 3/8"
for the home. They're right. It is. But it would be practical — (K = 3.0), and 7/16" (K=4.1).
if we had a practical life safety sprinkler system for the home.
Accordingly, I will now define a practical life safety system
for the home. This system could price out below $1,000.00 in
a $50,000.00 home. Pipe: In order to obtain a low cost installation, low cost
As a first step I must explain that there are two fire types plastic pipe (solvent welded) must be permitted. A pipe
that are of concern in the home. satisfactory for 100 psi at 100 0 F will be fine if piping is
One is the fast fire. The fast fire can achieve the killer stage run concealed in the ceiling. The modest temperature
in as little as three minutes. But what really makes this fire a below the ceiling needed to operate the sprinkler (say
killer is that during the early stage it can burn silently, 2500 F) will be no problem to the concealed pipe. Pipe
inconspicuously, and produce almost no smoke. Usually, sizes of 3/8 inch, 1/2 inch, 5/8 inch and 3/4 inch will be
someone in the bedroom is not even aware of the fire in the permissible depending on the hydraulic needs.
living room— that is not until it reaches flashover.
But once it hits flashover time — then it can be killing the
occupants in a matter of seconds.
The automatic sprinkler is the only practical solution to
Baths and Closets: For economy the elimination of
this fire type. A smoke detector in the upstairs hall may not
sprinklers in baths and closets must be permitted. The
sound until a fire in the living room reaches flashover — and
sprinkler will contain the fire to the closet. The smoke
then it's probably too late.
detector will also operate long before serious toxic
The second fire type is the slow fire. The slow fire is a
conditions develop.
smoldering fire that produces little heat. It might not open a
sprinkler. But over a period of an hour or two or three, it
could gradually produce carbon monoxide and kill everyone in
their sleep. The "product of combustion" detector is the
solution. Because this fire type is extremely slow, one smoke Attic and Unheated Areas: If there is an unheated attic
detector in the upper hall or near the bedrooms will usually or porch, one of these options will be permitted:
give good protection. A smoke detector will cost between $50 a. No protection provided if justified (evaluate the
and $100. If a life safety sprinkler system could be installed life hazard).
for another $500 to $900 I believe this combined cost could b. Smoke detector installed only.
be justified in a dwelling. c. Antifreeze system installed only.
d. Pre-action dry sprinklers installed — smoke
detector may be set to open solenoid in line.

To get a low cost system, here is what is needed:

Hydraulic Design Parameters: Design for the following:


a. One open sprinkler — average density of 0.04
Water Supply: Many homes have but a 3/4 inch water line.
GPM/Sq. Ft. over one plat.
This will deliver 10 to 20 gallons per minute. This is the
b. Two open sprinklers — average density of 0.025
water supply we must work with.
GPM/Sq. Ft. over 2 plats.

Density: A density of 0.025 GPM/Sq. Ft. is satisfactory


for dwelling fires. Our tests at Newton, New Jersey proved Standard Loop System: Use 3/4 inch riser and a 1/2 inch
this. In our Life Safety System (BOCA-100) we applied a loop on each floor. Install sprinkler on loop, or on one
4 to 1 safety factor on density, but in the dwelling we will sprinkler branch lines on 3/8 inch pipe (10' maximum) or
have to reduce the safety factor. 1/2 inch pipe (20' maximum).

2
--- WATER SUPPLIES FOR COMBINED SYSTEMS System No. 3 Fire Department Hose Lines
When the sprinkler riser is combined with the standpipe
The codes now permit combined systems involving: riser, the combined riser must be capable of delivering
a. Standpipes si multaneously:
b. Sprinklers. a. The sprinkler demand.
c. Domestic water. b. The interior hose (to be used by the occupants).
Two NFPA Codes, 13 (sprinklers) and 14 (standpipes) are c. The fire department hose stream demand.
involved. But here is where some confusion occurs. NFPA-14 states a
Making sense of one NFPA Standard usually is problem
pressure and a flow for the standpipe system. NFPA-13 states
enough, but combine two and the problems multiply. This is
a pressure and flow for combined systems. The two do not
especially the case with No's 13 and 14.
agree.
We will try to make sense out of the confusions, not so The one key factor that must be considered in order to
much by trying to make a "lawyers" interpretation of the bring sense out of chaos is the time of the water demand, and
meaning of the words, but by making an engineer's analysis of the distinction between an AUTOMATIC supply and a
the needs and intents of the codes. NON-AUTOMATIC supply (neither are defined clearly by the
codes).
Often, two or more supplies make up the TOTAL SUPPLY.
Where an AUTOMATIC supply is required, this doesn't
necessarily mean the TOTAL SUPPLY shall be automatic'.
System No. 1 Sprinklers We have already agreed that both the INTERIOR HOSE
and the SPRINKLER SUPPLY must be "AUTOMATIC". But
As a first step we will define the systems, and the supply the NFPA-14 code for standpipes does not require that any or
needs, and also consider the time frames of the needs. all of the water supply for standpipes be "AUTOMATIC".
The sprinkler system of course, must have water to feed a Here is the proof of this.
reasonable number of open sprinklers. If the sprinkler system 1. NFPA permits a DRY STANDPIPE. A dry standpipe will
has been designed to produce 0.1 GPM over 1500 Sq. Ft., then not have any water in the system at all. When the fire
clearly at least 150 GPM is necessary. This will be an department arrives, the pumps on their vehicles are connected
--- "AUTOMATIC" supply at a calculated "DESIGN to hydrants (sometimes they draft from a lake or other body
PRESSURE." of water). Then these fire department pumpers pump into the
standpipe. The standpipe is a DELIVERY system from ground
to upper floors. The required SUPPLY may sometimes be only
a static supply.
2. Even when the system is WET (contains water under
System No. 2 Interior Hose (For Occupants) pressure) NFPA-14 has by tradition not required a given
pressure and flow at the top of the riser AUTOMATICALLY.
Small hose often are installed for use by building The proof is that a WET STANDPIPE is often simply
occupants. The amount of water required for small hose is not connected to the city mains taking whatever flow and pressure
clearly defined by either NFPA-13 or 14. No. 13 requires 100 is available. There are many thousands of examples of such
GPM as a minimum supply for "hose streams" but his includes installations throughout the nation — and by tradition these
the water necessary for fire department hose streams as well as installations have always been considered to be in compliance
interior hose. with NFPA-14.
From a practical engineering viewpoint, a reasonable
allowance for interior hose to be used by a building occupant
is:
a. If 1 1/2 inch hose is installed, figure on 25 GPM. This is The Time Frame
a reasonable discharge for a 1 1/2 inch line in a sprin- To understand the intent of NFPA-13 and 14 combined,
klered building. A greater discharge is getting difficult for the requirements must be related to the time frame. The
an amateur fire fighter to handle. sprinklers are AUTOMATIC and require an AUTOMATIC
b. If a "garden type" hose is installed, figure on 10 GPM.
supply. But this AUTOMATIC sprinkler supply need not
This may sound like a very modest supply, but it is represent the TOTAL required supply of the standpipe.
fantastically superior to the 2 1/2 gallon extinguisher. The fire department hose streams are not customarily used
This supply (25 GPM or 10 GPM), like the sprinkler supply, until after the engines have already been connected to the
must be AUTOMATIC. standpipe. Thus, reliance on mobil pumpers for part or all of
Thus, the total AUTOMATIC supply required by NFPA-13 the "hose line demand" is customary.
and NFPA-14 in light hazard occupancies is the sprinkler The distinction between AUTOMATIC SUPPLY and
demand (calculated) plus 25 or 10 GPM. TOTAL SUPPLY is a reflection of the time frame.

3
Now, for a combined standpipe sprinkler system, should
Understanding The 65 PSI Rule these three rules be combined. That is, do the two standards
combined require that an AUTOMATIC supply be provided
capable (all by itself) of delivering 2750 GPM at 65 psi at the
NFPA-14 makes reference to the required standpipe water roof, if the building has 10 standpipes?
supply being delivered to the top of the standpipe system at The truth is the NFPA-14 will allow some or all of the
65 psi. (Call this rule 1). required supply to be a NON-AUTOMATIC Supply. It is only
NFPA-14 also sets the quantity of the supply (GPM) on the when the fire department pumpers are hooked up and
number of standpipes. The first standpipe should have a 500 pumping into the standpipe that the requirement of 65 psi at
GPM supply, all additional standpipes 250 GPM. (Call this rule the top of the riser must be met.
2.) The change where sprinklers were allowed to be combined
When the standpipe is combined with the sprinkler riser, with standpipes was intended to make sprinklers less costly
NFPA-13 requires the water supply to be AUTOMATIC. (Call and more practical — it was not intended to double the cost of
this rule 3). installing standpipes.

PATTON LIFE SAFETY SYSTEMS, INC.


6075 Cleveland Avenue
Columbus, Ohio 43229

You might also like