PREFACE
This manual is for project developers, users and assemblers who utilize
the ACCON-NetLink-PRO.
It shows the user the handling of the ACCON-NetLink-PRO and explains
signaling functions. All necessary data for assembling should be provided
to the assembler. 1995 - 2010
DELTALOGIC
Automatisierungstechnik GmbH
Stuttgarter Strasse 3
73525 Schwaebisch Gmuend
Germany
Phone sale:
Phone support:
+49-(0)7171-916-120
+49-(0)7171-916-112
Fax sale:
Fax support:
+49-(0)7171-916-220
+49-(0)7171-916-212
E-Mail sale:
E-Mail support:
vertrieb@deltalogic.de
support@deltalogic.de
www.deltalogic.de
All rights reserved. No part of this work is allowed to be copied, reproduced, conferred,
processed and stored into electronic media or translated into any other language without a
written permission of the author.
S7-200, S7-300, S7-400, HMI, STEP and SIMATIC are registered trademarks of
Siemens AG, ACCON and DELTALOGIC are registered trademarks of DELTALOGIC
Automatisierungstechnik GmbH.
Note:
We have checked the content of this manual for conformity with the hardware and software
described. Nevertheless, because deviations cannot be ruled out, we cannot accept any
liability for complete conformity. The data in this manual have been checked regularly and any
necessary corrections will be included in subsequent editions. We always welcome
suggestions for improvement.
Last update 2010-08-05. All technical changes reserved.
ACCON-NetLink-PRO
TABLE OF CONTENTS
PREFACE...................................................................... 1
TECHNICAL DESCRIPTION......................................... 3
COMMISSIONING .....................................................11
ACCON-NetLink-PRO
TECHNICAL DESCRIPTION
The ACCON-NetLink-PRO is a high-tech communications and
programming adapter between a PC and a S7 controller. This convincing
all-round device can be connected to the PLC via MPI, PROFIBUS and
PPI. The ACCON-NetLink-PRO detects the current bus settings,
independently. The connection cable of the ACCON-NetLink-PRO to the
Bus (MPI, PROFIBUS or PPI) is an active connection, so there are no bus
interferences due to a spur line.
Figure 1: Build-up
ACCON-NetLink-PRO
Extended diagnostics
Supports DHCP
Galvanically separated
Applicable up to 60 C
ACCON-NetLink-PRO
SCOPE OF DELIVERY
ACCON-NetLink-PRO
ACCON-NetLink-PRO
DEVICE DESCRIPTION
1
Figure 2: ACCON-NetLink-PRO
1.
2.
3.
Status LEDs
4.
Power supply bushing for 24 VDC. Please keep the polarity in mind.
5.
6.
ACCON-NetLink-PRO
Ready to operate
GREEN
GREEN
BLINKING
Active LED
Connect
LED
GREEN
GREEN
BLINKING
Device is logged in on
the bus
GREEN
GREEN
Active connection to a
controller
GREEN
GREEN
GREEN
GREEN
GREEN
GREN
BLINKING
Update LED
Param. LED
Data LED
GREEN
BLINKING
RED
BLINKING
RED
BLINKING
GREEN
RED
RED
Transmitting firmware
update
Storing firmware
update
ACCON-NetLink-PRO
No Ethernet
connection
OFF
OFF
Ethernet activity
ON
BLINKING
ACCON-NetLink-PRO
ACCON-NetLink-PRO
Minimum clearance
The following minimum clearance has to be kept that
Module assembly
To assemble the device a top hat rail holder is necessary. Available as
accessory.
ACCON-NetLink-PRO
10
COMMISSIONING
Connection to the PC
Put one end of the patch cable into the Ethernet bushing of your ACCONNetLink-PRO and the other end into a hub or switch which is connected
to your PC's network card.
You can also directly connect the ACCON-NetLink-PRO to your PC's
network card with the delivered patch cable (cross-over).
Connection to the automation device
Connect the 9-pin SUB-D plug to the MPI or PROFIBUS interface of your
S7 controller.
Figure 4: Build-up
Installation software
ACCON-NetLink-PRO
11
If not then
ACCON-NetLink-PRO
12
ACCON-NetLink-PRO
13
ACCON-NetLink-PRO
14
TCP/IP PARAMETRIZATION
There are two ways:
ACCON-NetLink-PRO
15
ACCON-NetLink-PRO
16
Additional features
In the input mask ACCON-NetLink-PRO properties there are more
options:
Name:
Here you can give the ACCON-NetLink-PRO a name for a better
identification in the search window. This name will be stored in the
device.
A possible naming would be according to the location (e. g.
conveying machinery HG1), user name (e g. Mr. Smith) or something
else (e. g. weekend is near).
Change password:
Here you can set or change an already existing password.
When a password is set you can only change the ACCON-NetLink-
ACCON-NetLink-PRO
17
PRO's configuration with it. This is valid for both, parametrization via
driver and web interface.
ACCON-NetLink-PRO
18
BUS SETTINGS
The ACCON-NetLink-PRO can be used with three different bus systems:
PPI, MPI and PROFIBUS.
Configuration example MPI
The most important setting in connection with the bus configuration is
the station address. This is the address which has the ACCON-NetLinkPRO on the bus when going online. The station address can be in the
range from 0 to 12 as long as the chosen address is smaller or equal
as the highest station address. This address is allowed only once.
The timeout can be set in the station-related settings of the ACCON-S7NET driver. If there is no response to a driver enquiry within the set
timeout, a communication error is sent to the SIMATIC application. The
decrease of the timeout has no effect on the transmission time and data
throughput. 10000ms is the recommended timeout value.
In the net-related settings you have to adjust the transmission rate as
well as the HSA of the automation system to which should
communicated.
ACCON-NetLink-PRO
19
ACCON-NetLink-PRO
20
Profile:
Using PROFIBUS the following profiles DP, Standard and Userdefined can be used. You have to select the profile which is already set
in the automation system.
Bus parameters:
Unlike to MPI the bus parameters under PROFIBUS are not constant and
change in relation to the number and type of the used PROFIBUS
stations.
You should always use the PROFIBUS parameters which are set in the
actual automation system (look for it in the STEP 7 project).
To sidestep these partly complex steps you can use the function
Automatic reconnaissance of the net-related parameters. under
PROFIBUS.
To get the Automatic reconnaissance of the net-related parameters to
work, you have to activate Cyclic distribution of the bus parameters in
the hardware parametrization of the interface.
The following screenshot shows the switch for the Cyclic distribution of
the bus parameters. It is located in the hardware configuration of any
PROFIBUS interface:
ACCON-NetLink-PRO
21
ACCON-NetLink-PRO
22
PPI communication
The PPI configuration is the same as the MPI configuration, but the
automatic reconnaissance of the net-related parameters is not possible
with S7-200 controllers.
The PPI communication is supported not until version 2.5 of the ACCONS7-NET drivers. At least firmware version 1.40 is needed.
For more information of the use of Advanced PPI look for the help of the
S7-200 programming software.
Actual driver and firmware versions can be found on our web site in the
Download section.
ACCON-NetLink-PRO
23
Driver options
In the tab Options you can select the language of the dialogs and
messages. Furthermore the driver versions are displayed.
ACCON-NetLink-PRO
24
Diagnostics function:
You can find this function via Set PG/PC-Interface > Diagnostics.
There you can execute hardware diagnostics of the module. You can
determine the following values:
1.
2.
Station type:
MLFB number:
ACCON-NetLink-PRO
25
ACCON-NetLink-PRO
26
In the application's RFC 1006 driver you have to indicate the bus
address (rack and slot number) of the CPU which should be
accessed.
Example:
If you want to communicate with the PLC number 2:
Rack 0, Slot 2.
If you want to communicate with the PLC number 49:
Rack 1, Slot 17.
A conversion table for the rack and slot numbers is in the chapter 15
Appendix
Parametrization tools without a rack and slot fields mostly have a
parametrization field for the Remote TSAP. Normally, this is 2 bytes
long and is shown in hexadecimal. The field where only 1 byte is used
can be parametrized as follows:
ACCON-NetLink-PRO
27
DELTALOGIC S7/S5-OPC-Server
SPS-Analyzer AutoSPy
ACCON-S7-Power-Tools
ACCON-S7-EasyLog
ACCON-NetLink-PRO
28
ACCON-NetLink-PRO
29
But the connection still needs a variable. To do so, open the context
menu of the connection with a right mouse click and choose New
tag.
In the Tag properties window you can choose the type of the variable
(MB0_over_NetLink_PRO, here) via the button Select.
ACCON-NetLink-PRO
30
In the following screenshot you can see that there is now a new variable
called MB0_over_NETLink_PRO under the point NetLink_PRO.
If this variable is now included in the initial screen of the WinCC project,
a connection will be established to the CPU with address 49 via the
ACCON-NetLink-PRO to access marker byte 0. Further variables of
ACCON-NetLink-PRO
31
A special feature of the RFC 1006 option is the Rack/Slot Mode. Using
this function it is possible to access several CPUs which are on the same
Rack (Multicomputing) via one bus address. A connection from a
PROFIBUS-CP (z. B. CP342-5) to a S7 CPU is possible, too.
Only to the set station (PLC number) will be communicated to. This
station forwards the data packages to the desired Rack/Slot.
To use this function, the following settings on the configuration page of
the web interface have to be made:
At Fix destination address for R/S mode the address (PLC number)
of the desired communication partner has to be entered. In this
example 49.
ACCON-NetLink-PRO
32
10
Welcome page
Configuration page
Status page
The status page shows the currently used settings of the ACCONNetLink-PRO. You cannot change anything there.
This page provides the following information:
Device specific parameters:
Product name
ACCON-NetLink-PRO
Order number
161700-PRO
Firmware name
ACCON-NetLink-PRO
Firmware version
e. g. V1.50
Bios version
e. g. V1.42
Serial number
e. g. T00000062
MAC address
e. g. 00:06:71:19:00:3E
ACCON-NetLink-PRO
33
Device name
Bus-specific parameters:
Station address
Bus parameters
ACCON-NetLink-PRO
34
TCP/IP-specific parameters:
IP address
Subnet mask
Gateway
DHCP status
Device name
Max. possible IP
connections
Communications
port
ACCON-NetLink-PRO
35
Rack/Slot-Mode
Max. possible IP
connections (RFC)
Configuration page
The ACCON-NetLink-PRO can be configured via this page. Before
opening this page you have to enter the correct device name
(ACCON-NetLink-PRO) and the password (standard password from
firmware 1.40 is admin).
ACCON-NetLink-PRO
36
Static gateway
Alternative NETLink
Port
Device name
DHCP status
ON or OFF
DHCP timeout
30 to 65500 seconds
We status
New password
ACCON-NetLink-PRO
37
HSA:
Tslot_Init:
Ttr:
Max. Tsdr:
ACCON-NetLink-PRO
38
Min. Tsdr:
Tset:
Tqui:
Gap:
Retry:
ACCON-NetLink-PRO
39
Rack/Slot-Mode
Fix target address for
Rack/Slot-Mode
ACCON-NetLink-PRO
40
Security page
The security page contains rudimental TCP security settings. Before
opening this page you have to enter the correct device name
(ACCON-NetLink-PRO) and the password (standard password is
admin). Via the button factory defaults the ACCON-NetLink-PRO can
be set to its standard settings.
The used default values before firmware 1.40:
User name: ACCON-NetLink-PRO
Password: (empty)
The used standard values from firmware 1.40:
User name: ACCON-NetLink-PRO
Password: admin
If the TCP-Access list is activated with ON, only TCP connections to
the ACCON-NetLink-PRO can be established which have been unlocked
in the table TCP address 1 to TCP address 12 (whitelist).
Enter an IP address which has to be unlocked according to the following
example: 192.168.4.36. To deactivate it, enter OFF.
TCP/IP addresses which are not indicated here, have only read access
on the web interface and cannot change the configuration. An access
with ACCON-S7-NET is limited, too.
If you want to avoid unauthorized use you must not add possible proxy
server in company networks to the list. Otherwise a secure use of the
ACCON-NetLink-PRO is only limited.
To undo changes just press the Cancel button.
By clicking on OK the entered values will be checked. If there is a
wrong input a possible solution is shown. If all is correct, all changes are
shown again and with a click on OK the values will be stored in the
ACCON-NetLink-PRO.
To activate the new configuration, the ACCON-NetLink-PRO will be
restarted after saving the new parameters. If desired the ACCONNetLink-PRO can be activated remotely via the configuration interface.
To do this click on System Reset. It is possible the restore the ACCONNetLink's default values via the button Factory default. All userdefined settings will be deleted.
ACCON-NetLink-PRO
41
Monitor variables
From the firmware version 1.50 the function Observe variables is
unlocked in the ACCON-NetLink-PRO. This function is supported in the
RFC 1006 function via the web interface. The activation is described in
chapter 9.
Parameters for monitoring variables:
MPI Address
Number of Variables
No.
Continuous numeration.
Address Area
Address Index*
Result Value
Display Format
Description
To show the desired values the buttons 1x fetch, for a refresh once, or
cyclic fetch, for a permanent online request, are available.
With Save Configuration the created mask including all set variables
and their descriptions can be stored in the ACCON-NetLink-PRO.
The refresh rate is set to 0,5 seconds. If several stations use this
functions from the TCP/IP side, then there is always only one
connection resource reserved in the ACCON-NetLink-PRO. During the
additional data exchange via MPI/PROFIBUS the Observe Variables
function has the lowest priority. Thus the refresh rate in the web
interface is dependent from the parallel bus load.
ACCON-NetLink-PRO
42
11
Disadvantages
Advantages
The administrator can take steps
that the connection is not
visible/usable for everyone from
the outside
Disadvantages
Network administrators have to
parametrize router and firewalls
between the involved
communication partners
ACCON-NetLink-PRO
43
Disadvantages
Additional costs through
telephone charges
Loss of performance due to a low
bandwidth
ACCON-NetLink-PRO
44
12
TROUBLE SHOOTING
Error
Cause
Solution
- Plug MPI/PROFIBUS
cable on PLC
interface
- Apply 24 VDC
externally
ACCON-NetLinkPlug MPI/PROFIBUS
PRO exception error cable again on the
on MPI/PROFIBUS
PLC interface
side
No connection to
the Ethernet
Check Ethernet
connection
ACCON-NetLink-PRO
has to be inactive
during
parametrization
ACCON-NetLink-PRO
-Activate ACCONNetLink-PRO or
complete starting
procedure
-PC and ACCONNetLink-PRO have to
be in the same
45
network segment
ACCON-NetLink-PRO
not reachable
Ports have to be
released in the
firewall
ACCON-NetLink-PRO
To search the
ACCON-NetLink-PRO
the UDP ports 25342
and 25343 and for
the communication
the TCP/IP port 7777
have to be released.
Port 7777 must
always be released.
Increase failure
monitoring to 200ms
and application
monitoring to
5000ms
46
13
Q: The configuration tool as well as the web interface asks for a password.
But I did not enter any password.
A: From firmware version 1.40 the ACCON-NetLink-PRO must have a
password. If no password is set, the standard password is admin.
Q: There are no dialog settings in the Simatic Manager.
A: When you installed the ACCON-S7-NET driver for the first time you have
to add it to the PG/PC interfaces, too. Make sure that you have
administrator rights when installing the driver. After a successful
installation you have to reboot your system. Simatic Manager Version
5.1 is minimum!
Q: It is not possible to go online when the adapter is put on the PROFIBUS.
A: If possible use the autobaud function. If not desired or possible you have
to check the Profibus timing parameters in the STEP 7 project planning.
Via the Bus Parameters button you can enlist the read off values into
the extended bus parameter settings. You have to increase the TRT
(Target Rotation Time) parameter in the ACCON-NetLink-PRO as well as
on the PLC.
ACCON-NetLink-PRO
47
ACCON-NetLink-PRO
48
Unfortunately, I am not sure how to parameterize the fields rack and slot
in the visualization used.
A: If addressed mode is used, a combination of rack and slot specifies the
destination address of the automation system.
Q: If I mix RFC 1006 connections and connections via the STEP 7 driver,
the connection sometimes breaks off or error messages appear saying
that it is not possible to establish a connection.
A: For communication with S7-300 modules it may be necessary to
parameterize the communication resources. The user can influence the
allocation of existing Connection Resources under object properties of
the PLC in the hardware configuration.
ACCON-NetLink-PRO
49
14
TECHNICAL DATA
Supported operating systems
Hardware requirements
Supported PLCs
Weight in kg
ca. 0,25
Dimensions (W x H x D) in mm
54 x 105 x 30
Protection type
IP 20
Voltage supply
24 VDC 25 %
Yes
Power consumption
Max. 150 mA
Galvanically separated
Yes
Operating temperature
0 C to 60 C
Temperature storage/
transport
-20 C to 90 C
Relative humidity
5 % to 85 % at 30 C (no
bedewing)
ACCON-NetLink-PRO
50
12
Supported software
Pin assignment
Assignment MPI/PROFIBUS interface
Port Signal
Meaning
Not used
GND
RxD / TxD-P
Received/transmission data-P
Not used
DGND
DVCC
VCC
RxD / TxD-N
Received/transmission data -N
Not used
ACCON-NetLink-PRO
51
Signal
Meaning
TX+
transmission data
TX-
transmission data
RX+
Received data
Not used
Not used
RX-
Received data
Not used
Not used
ACCON-NetLink-PRO
52
15
APPENDIX
Address conversion table
The following table serves as a parametrization help for the addressed
mode. The bus address can be converted to Rack/Slot or TSAP, e. g. the
controller with the bus address 49 is addressed by Rack 1 and Slot 17
or with the TSAP 0231.
Busadr.
Rack
Slot
TSAP
Busadr.
Rack
Slot
TSAP
0200
64
0240
0201
65
0241
0202
66
0242
0203
67
0243
0204
68
0244
0205
69
0245
0206
70
0246
0207
71
0247
0208
72
0248
0209
73
0249
10
10
020A
74
10
024A
11
11
020B
75
11
024B
12
12
020C
76
12
024C
13
13
020D
77
13
024D
14
14
020E
78
14
024E
15
15
020F
79
15
024F
16
16
0210
80
16
0250
17
17
0211
81
17
0251
18
18
0212
82
18
0252
19
19
0213
83
19
0253
20
20
0214
84
20
0254
ACCON-NetLink-PRO
53
Busadr.
Rack
Slot
TSAP
Busadr.
Rack
Slot
TSAP
21
21
0215
85
21
0255
22
22
0216
86
22
0256
23
23
0217
87
23
0257
24
24
0218
88
24
0258
25
25
0219
89
25
0259
26
26
021A
90
26
025A
27
27
021B
91
27
025B
28
28
021C
92
28
025C
29
29
021E
93
29
025D
30
30
021F
94
30
025E
31
31
0220
95
31
025F
32
0220
96
0260
33
0221
97
0261
34
0222
98
0262
35
0223
99
0263
36
0224
100
0264
37
0225
101
0265
38
0226
102
0266
39
0227
103
0267
40
0228
104
0268
41
0229
105
0269
42
10
022A
106
10
026A
43
11
022B
107
11
026B
44
12
022C
108
12
026C
45
13
022D
109
13
026D
46
14
022E
110
14
026E
47
15
022F
111
15
026F
ACCON-NetLink-PRO
54
Busadr.
Rack
TSAP
Slot
Busadr.
Rack
Slot
TSAP
48
16
0230
112
16
0270
49
17
0231
113
17
0271
50
18
0232
114
18
0272
51
19
0233
115
19
0273
52
20
0234
116
20
0274
53
21
0235
117
21
0275
54
22
0236
118
22
0276
55
23
0237
119
23
0277
56
24
0238
120
24
0278
57
25
0239
121
25
0279
58
26
023A
122
26
027A
59
27
023B
123
27
027B
60
28
023C
124
28
027C
61
29
023D
125
29
027D
62
30
023E
126
30
027E
63
31
023F
ACCON-NetLink-PRO
55