You are on page 1of 35

PCM600 V2.

6
Communication and project setup
SA-T Training
November 12, 2014 | Slide 1
1MRG001848

Section 2

Content

SA-T Training
November 12, 2014 | Slide 2
1MRG001848

Communication setup

IED

PC

PCM600 project setup

Create new project

Handling IED objects

License Update

Set technical key

Export/Import

Report parameters

Section 2

Communication setup IED PC

Communication protocol

TCP/IP

Ethernet ports

Front

Rear

SA-T Training
November 12, 2014 | Slide 3
1MRG001848

Galvanic

Optic (one channel only)

Ethernet IED Front connection

IED Front port

Default IP address 10.1.150.3 (650/670)

Default IP address 192.168.0.254


(611/615/620/630)

Default Subnet mask 255.255.255.0

PC port setting

IP address 10.1.150.xx up to 254

IP address 192.168.0.xx up to 254

Subnet mask 255.255.255.0

Crossed over Ethernet cable

IED Front has DHCP server

SA-T Training
November 12, 2014 | Slide 4
1MRG001848

Section 2

Dynamically assign IP addresses

Section 2

Ethernet Optic network


IP: 172.16.0.11
Mask: 255.255.0.0

IP: 172.16.0.10
Mask: 255.255.0.0

Optical cable
RX TX

IED Rear port

Default IP address 192.168.1.10

Default Subnet mask 255.255.255.0

This is an example of Class B network


addressing concept

RX TX

Ethernet switch

IP: 172.16.0.13
Mask: 255.255.0.0

SA-T Training
November 12, 2014 | Slide 5
1MRG001848

Defines the Network

The two last segments

IP: 172.16.0.12
Mask: 255.255.0.0

The two first segments

Define the Nodes

Rear Ethernet port NO DHCP server

Ethernet port settings

PC Port setting

No settings in PCM600 for Ethernet port of PC

WINDOWS controls panel

Setup corresponding network

SA-T Training
November 12, 2014 | Slide 6
1MRG001848

Section 2

Section 2

IED Ethernet port settings

Object properties

SA-T Training
November 12, 2014 | Slide 7
1MRG001848

Property group address

Section 2

PCM600 Setup

PCM600 Setup

Create project

Create Plant structure

Create IED objects

SA-T Training
November 12, 2014 | Slide 8
1MRG001848

Unique IP address

Section 2

Project Manager

Open/Manage projects

Top menu File

Open/Manage Projects

New Project

Delete project

Import project

.pcmp file

Export project

SA-T Training
November 12, 2014 | Slide 9
1MRG001848

Distinguish between versions

.pcmp file is created

Section 2

Create Plant Structure

Drag and drop

Objects into Plant Structure

Right click on object

Select New/General/Object

Shows current object

The IED object

Initiates configuration wizard

Note:
Only one substation level is allowed

SA-T Training
November 12, 2014 | Slide 10
1MRG001848

Section 2

Online configuration

Configuration modes

Online configuration

Offline configuration

Select IED protocol

IEC61850

Note: Not possible to configure IED via SPA and LON

SA-T Training
November 12, 2014 | Slide 11
1MRG001848

Section 2

Online configuration

SA-T Training
November 12, 2014 | Slide 12
1MRG001848

Communication Port

Front port

Rear port

Scan IED

IED Type

IED Version

Section 2

Online configuration

Housing

Housing type

Display type

Complete

SA-T Training
November 12, 2014 | Slide 13
1MRG001848

Summarize

Section 2

Offline configuration

Select IED version

Order option file

Enables ordered SW and HW

No order option specific file

SA-T Training
November 12, 2014 | Slide 14
1MRG001848

No need to synchronize

Enables all functionality

Need to synchronize

License Update Tool

Section 2

Basic Plant Structure Completed

After completed wizard

IED configurations structures

Application configuration structure

SA-T Training
November 12, 2014 | Slide 15
1MRG001848

Contains base functionality

Contains the configuration data

Section 2

License update Tool

SA-T Training
November 12, 2014 | Slide 16
1MRG001848

Synchronize PCM600 IED object with


physical IED

Function options

Hardware options

Section 2

License update

Synchronizing steps

Backup PCM 600 IED .pcmi

Yes/No

Update mode selection

Offline

Online

SA-T Training
November 12, 2014 | Slide 17
1MRG001848

Order option file is needed

Scan IED, reads options

Complete

Section 2

Technical Key

Unique identifier for each object in Plant


Structure

IED technical key

Automatic method of naming objects

AA1 Substations

J1 Voltage Level

Q01 Bay

AA1J1Q01A1 IED

PCM600 and IED technical key must match

Enables transactions

SA-T Training
November 12, 2014 | Slide 18
1MRG001848

AA1J1Q01A1

Read/Write

User defined technical key

Tool executed from Plant Structure

Section 2

Set Technical Key

Set technical key steps

Information

Ok/Cancel

Reading Technical key from IED

Technical key options

Use IED Technical key

Use PCM600 Technical key

SA-T Training
November 12, 2014 | Slide 19
1MRG001848

Impacts on IEC61850 configuration

Reboots IED

User-defined Technical key

Reboots IED

No special characters

Max length 13 characters

No numbers in the beginning

Section 2

Export IED object

Save and reuse configured IED

Export issued from Plant structure

SA-T Training
November 12, 2014 | Slide 20
1MRG001848

Right click IED object

Creates a .pcmi file

Contains all configured data

Application Configuration

Signal Matrix

Parameter Setting

Graphical Display

Communication Management (DNP)

SCL information

Hardware configuration

Section 2

Import IED object

Use a configured IED object

Import issued from Plant structure

SA-T Training
November 12, 2014 | Slide 21
1MRG001848

Bay level

Right click object

Select .pcmi file

Section 2

Create Template

Save and reuse configured IED

In a pre-defined place

For quick access

Creation of template issued from Plant


structure

Right click IED object

Creates a .pcmt file

Ends up in PCMDatabases\Templates

Contains all configured data

SA-T Training
November 12, 2014 | Slide 22
1MRG001848

Same content as pcmi file

Create new IED object from Template

Use a configured IED object

New object created from Plant


structure

Bay level

Right click object

Template Manager

Select current IED object

Press Create button

SA-T Training
November 12, 2014 | Slide 23
1MRG001848

Section 2

Instantiates object in Plant structure

Section 2

Copy/Paste IED object

SA-T Training
November 12, 2014 | Slide 24
1MRG001848

Copy/Paste issued from Plant Structure

Right click IED object

All configured data is copied

Technical Key automatically updated

Section 2

IEC 61850 configuration SCD

SCD file

Contents

SA-T Training
November 12, 2014 | Slide 25
1MRG001848

Substations Configuration Description

SCL information for all IEDs within the


substation

Export/Import SCD file

Engineering of SCL information

Substation level

Section 2

IEC 61850 configuration ICD

ICD file

IED Capability Description

New feature

Contents

All thats configured in IED before


system configuration

No SA Section

No Communication section

IEDName = TEMPLATE

Usage

System engineering

Export/Import of ICD file

SA-T Training
November 12, 2014 | Slide 26
1MRG001848

Merging to a SCD file

On IED level

Section 2

IEC 61850 configuration CID

CID file

Contents

Extract of the SCD file

SCL information for one specific IED

Export/Import of ICD file

SA-T Training
November 12, 2014 | Slide 27
1MRG001848

Configured IED Description

On IED level

Section 2

Report Parameters

SA-T Training
November 12, 2014 | Slide 28
1MRG001848

Drawing Header information

Application configuration

Local display, Graphical display editor

Parameter settings

Communication management

Drawing

Drawing size

Fixed to A3 Landscape

Margins cant be change

SA-T Training
November 12, 2014 | Slide 29
1MRG001848

Section 2

Section 2

Hardware Configuration

Changing configuration

Add/Remove Binary Input/Output Module


(BIO)

Alter Transformer Module (TRM)

Add/Remove Analog Input Module (AIM)

Alter module

Alter Power Supply Module (PSM)

SA-T Training
November 12, 2014 | Slide 30
1MRG001848

Fixed card position

Fixed card position

Hardware Configuration

Select card in drop down menu

Add/Remove cards in fixed order

Add from p3

Remove from p6

AIM module in p4

SA-T Training
November 12, 2014 | Slide 31
1MRG001848

Position 3 must be empty

Section 2

Section 2

Hardware Configuration

SA-T Training
November 12, 2014 | Slide 32
1MRG001848

Compare configuration

Reads hardware configuration form


IED

Issue compare from toolbar menu

Section 2

Hardware Configuration

Simple Parameter Setting

SA-T Training
November 12, 2014 | Slide 33
1MRG001848

Parameterize hardware modules

Binary Inputs

Analog Inputs

Select module from hardware


configuration list

Press Parameter Setting button in


toolbar menu that will issue
simplePST

Can not Read/Write parameters form


simplePST

Hardware Configuration

Print hardware configuration

Print preview

SA-T Training
November 12, 2014 | Slide 34
1MRG001848

Section 2

Section 2

SA-T Training
November 12, 2014 | Slide 35
1MRG001848

You might also like