Draft edition

GD Midea Refrigeration Equipment Co.,Ltd


MULTI SPLIT TYPE, HEAT PUMP AIR CONDITIONERS

Technical service manual 2005


R410A Corona multi Series

Indoor Models

MSCI-09HRN1
MSCI-12HRN1

Outdoor Models

M2OA-18HRN1 M2OA-21HRIN1
M3OA-27HRN1 M2OA-30HRIN1

214

Multi SERIES
1. Features
2. Specification
3. Dimensions
4. Refrigeration cycle diagram
5. Operation limits
6. Wiring diagram
7. Troubleshooting
8. Electronic function
9. Exploded view parts
10. Characteristic of temp. sensor

215

1.Features
1.1 Compact design
1.2 High efficiency and quiet operation
1.3 Unitary outdoor unit design

216

2 Specification
2.1 Indoor unit
Corona multi indoor unit
Model

MSCI-09HRN1

MSCI-12HRN1

Model

CE-KFR26G/CTN1Y

CE-KFR32G/CTN1Y

1Ph,220-240V~,50Hz

1Ph,220-240V~,50Hz

Power supply

Capacity

Ph-V-Hz
Cooling Capacity

BTU/h

9000

12000

Heating Capacity

BTU/h

11000

13000

Running Current

0.18

0.2

Design Pressure (Hi/Lo)

Mpa

4.2/2.5

4.2/2.5

Max. Operating Pressure (Hi/Lo)

Mpa

3.5/3.5

3.5/3.5

Model

RPG13H

RPG13D

Brand

Welling

Welling

39.5

44

uF

1.2

1.2

1200/950/850

1220/1000/800

Indoor fan motor Input


Capacitor
Speed(hi/mi/lo)

r/min

a.Number of rows

Indoor coil

b.Tube pitch(a)x row pitch(b)

mm

21x13.37

21x13.37

c.Fin spacing

mm

1.3

1.3

Unhydrophilic aluminium

Hydrophilic aluminium

d.Fin type (code)


e.Tube outside dia.and type

mm 7 INNEGROOVE TUBE

f.Coil length x height x width

mm

538X252X26.74

578X252X26.74

m3/h

500/460/410

500/430/370

dB(A)

36/34/32

37/34/31

g.Number of circuits
Indoor air flow (Hi/Mi/Lo)
Indoor noise level (Hi/Mi/Lo)
Indoor unit

7 INNEGROOVE TUBE

Dimension (W*H*D)

mm

710250195

790265193

Packing

mm

800340270

875x285x375

Kg

8/9.5

9/11

(W*H*D)

Net/Gross weight

214

2.2 Outdoor unit


Model

M2OA-18HRN1

M2OA-21HRN1

M3OA-27HRN1

M3OA-30HRN1

1Ph,220-240V~,50Hz

1Ph,220-240V~,50Hz

1Ph,220-240V~,50Hz

1Ph,220-240V~,50Hz

Btu/h

9000x2

9000+12000

9000x3

9000x2+12000

Input

890x2

890+1250

1650+1150

1800+1300

Rated current

4.0x2

4.0+5.7

8.0+5.5

8.2+5.8

Btu/w.h

10.2

9.8

9.6

9.6

Btu/h

1000x2

10000+14000

10000x3

10000x2+1300

Input

890x2

890+1250

1650+1150

1750+1250

Rated current

4.0x2

4.0+5.7

7.7+5.6

8.0+5.6

11.3

10.9

10.6

10.9

L/h

1.0x2 +1.2

1.0x2 +1.2

1.0x2 +1.2

1.0x2 +1.2

Max. input consumption

2160

2580

3400

3720

Max. current

9.9

11.7

15.6

16.7

Starting current

21.7

29.9

31.8

31.8

PA200X2CS-4KU1 ;

PA200X2CS-4KU1 ;

PA145X2C-4FT

PA145X2C-4FT

Power supply

Ph-V-Hz
Capacity

Cooling

EER
Capacity
Heating

COP
Moisture Removal

Model

PA108X1C-4FTx2

Type

Rotary

Rotary

Rotary

Rotary

Brand

GD Toshiba

GD Toshiba

GD Toshiba

GD Toshiba

Btu/h

8874

8874/12014

16791/12014

16791/12014

Input

890

890/1200

1670/1200

1670/1200

Rated current(RLA)

4.07

4.07/5.6

7.81/5.6

7.81/5.6

Locked rotor Amp(LRA)

40

40/57

57

57

Internal

Internal

Internal

Internal

Capacity
Compressor

Btu/w.h

Thermal protector

Outdoor

fan

PA108X1C-4FT ;

PA145X2C-4FT

Capacitor

uF

25uF/440-450VACx2

25uF/440VAC;35uF/440VAC

35uF/440VACx2

35uF/440VACx2

Refrigerant oil

ml

350

350/480

480/750

480/750

YDK69-6

YDK69-6

YDK50-4G1

YDK50-4G1

Model

215

motor

Brand

Welling

140

140

200

200

Capacitor

uF

4uFx2

4uFx2

4uFx2

4uFx2

830/650

830/650

1150

1150

mm

25.4x24

25.4x24

25.4x24

25.4x24

mm

1.7

1.7

1.7

1.7

Hydrophilic aluminium

Hydrophilic aluminium

Hydrophilic aluminium

Hydrophilic aluminium

9.53, Innergroove tube

9.53, Innergroove tube

9.53, Innergroove tube

9.53, Innergroove tube

813X812X44

813X812X44

2/2

2/2

3/3

3/3

m3/h

2200

2200

3200

3200

dB(A)

56

56

58

58

b.Tube

r/min

pitch(a)x

row

pitch(b)
c.Fin spacing
d.Fin type (code)
e.Tube

outside

dia.and

type
f.Coil length x height x
width

mm

mm

g.Number of circuits
Outdoor air flow
Outdoor noise level
Dimension(W*H*D)

mm

895X655X345

895X655X345

860X830X330

860X830X330

Packing

mm

1050X720X470

1050X720X470

1000X985X425

1000X985X425

Kg

75/81

76/82

81/88

81/88

R410A/ 980x2

R410A/ 1100+900

R410A/ 1150+1550

R410A/ 1150+1550

4.2/2.5

4.2/2.5

4.2/2.5

4.2/2.5

mm(inch)

6.35/9.53

6.35/9.53;6.35/12.7

6.35/9.53 *3

6.35/9.53 *2;6.35/12.7

15 (each unit)

15 (each unit)

15 (each unit)

15 (each unit)

(W*H*D)

Net/Gross weight
Refrigerant type

Design pressure(Hi/Lo)

MPa

Liquid side/ Gas side


Refrigerant

Max.

piping

length

refrigerant

pipe

Max. difference in level


Connection wiring

Welling

a.Number of rows

Outdoor unit

Welling

Input

Speed

Outdoor coil

Welling

(each unit)
No

(each unit)
No

216

(each unit)
No

(each unit)
No

Plug type
Thermostat type
Operation temp

Ambient temp

No

No

No

No

Electronic control

Electronic control

Electronic control

Electronic control

17~30

17~30

17~30

17~30

18~45(cooling); -7~30(heating)

18~45(cooling); -7~30(heating)

18~45(cooling); -7~30(heating)

(14-21)x2,16-24

(14-21)x2,16-24

(14-21)x2,16-24

18~45(cooling);
-7~30(heating)

Application area

m2

(14-21)x2,16-24

Qtyper 20 /40 /40'HQ

set

45/94/118

217

3.Dimensions
3.1 Indoor unit
a) Indoor unit 9K

b) Indoor Unit 12K

214

3.2 Outdoor unit


a) Outdoor unit 18K/21K

b) Outdoor unit 27K/30K

215

4.Refrigeration cycle diagram


1 drive 3 system is made up of one 1 drive 1 system and one 1 drive 2 system.

PMV1

PMV2
SV2

SV1

T2

T1
Compressor
refrigeration distributor

1 drive 2 system
SV1Primary four-way valve
SV2
Secondary four-way valve
T1T2Indoor pipe temperature sensor

PMV1
PMV2Electronic expansive valve

condenser

four-way valve

evaporator

compressor

1 drive 1 system

216

5.Operation limits
5.1Cooling operation
Outdoor unit air temp. DB
45
40

COOLING

35
30
25
20

0
25
Indoor air temp. DB

50

Note : The chart is the result from the continuous operation under constant air temperature
conditions. However, excludes the initial pull-down stage.

5.2Heating operation
Indoor air temp. DB
30
25
20
15
10
5

-5

15

25

Outdoor unit air temp. DB


Note : The chart is the result from the continuous operation under constant air
temperature conditions. However, excludes the initial pull-down stage.
217

6.Wiring diagram
Indoor unit

CORONA INDOOR UNIT


Outdoor unit

FOR 1 DRIVE 2 OUTDOOR UNIT


218

FOR 1 DRIVE 3 OUTDOOR UNIT

219

7.Troubleshooting
7.1 Indoor unit
Failure phenomenon

Operation lamp

Timer lamp

on

EEPROM error

on

Over current protection of the compressor occurs 4 times in 1h

Indoor fan speed has been out of control for over 1 minute
Indoor room temp. sensor or evaporator temp. sensor is open circuit
or short circuit

r Extinguish
Flash at 5Hz

On Light
7.2 Outdoor unit
Failure phenomenon
Stand by

LED1

LED2

LED3

High temp. protect of condenser


Temp. sensor in condenser 1

is open circuit or short circuit

Temp. sensor in condenser 2

is open circuit or short circuit

Flash at 2Hz

220

8 Electronic function
8.1
Electric Control working environment
8.1.1 input voltage: 175~253V
8.1.2 Input power frequency:50Hz
8.1.3 Ambient temperature: -7C~+43C
8.1.4 Indoor fan normal working amp is less than 1A,
8.1.5 Outdoor fan. Normal working amp is less than 1.5A
8.1.6 Four-way valve normal working amp is less than 1A.
8.1.7 Swing motor: DC12V.
8.2

Display board
Signal r eceptor

8.2.1 AUTO indicator


This indicator illuminates when the air conditioner is in AUTO operation.
8.2.2 TIMER indicator
This indicator illuminates when TIMER is set ON/OFF.
8.2.3 PRE.-DEF. Indicator (For Cooling & Heating models only)
This indicator illuminates when the air conditioner starts defrosting automatically or when
the warm air control feature is activated in heating mode.
8.2.4 TEMPERATURE indicator
a) Usually it displays the temperature settings. When change the setting temperature, this
indicator begins to flash, and stops 20 seconds later.
b) It displays the room temperature when the air conditioner is in FAN only operation.
c) When the unit stops operation, it returns to original factory settings.
d) Displays the malfunction code or protection code.
8.2.5 OXYGEN GENERATOR indicator (Optional)
This indicator appears only when the Oxygen Generatorr is in operation.(Optional)
8.3

Proper symbols and their meanings


TA: Indoor ambient temperature
TE: Indoor evaporator temperature
TS: Setting temperature through the remote controller
TE1: Anti-cold wind, from Fan Off to Breeze temperature
TE2: Anti-cold wind, from Breeze to Setting Fan Speed temperature
TE3: Anti-cold wind, from Setting Fan Speed to Breeze temperature
TE4: Anti-cold wind, from Breeze to Fan Off temperature
TE5: Evaporator low temperature protection entering temperature
TE6: Evaporator low temperature protection restoring temperature
221

TE7: Evaporator high temperature protection, compressor off temperature


TE8: Evaporator high temperature protection, fan off temperature
TE9: Evaporator high temperature protection, restoring temperature
T3: Outdoor unit pipe sensor
T4: Outdoor temperature sensor
8.4

Systematic functions.
Remote receiving.
Testing and forced run.
Position set for indoor unit wind vane.
LED displaying and alarm.
On or off Timer.
Protection for the compressor.
High temperature protection of indoor heat exchanger in heating mode.
Auto defrosting and heating recovery under heating mode.
Anti cold air under heating mode.
Anti frozen under cooling mode.

222

8.5
8.5.1
8.5.2
8.5.3
8.5.4
8.5.5

Protection
The compressor functions protection with a delay of three minutes.
High temp. protection of condenser.
Sensor protection at open circuit and breaking disconnection
Temperature Fuse break protection
Fan Speed is out of control. When Indoor Fan Speed is too high(higher than High
Fan+300RPM)or too low(lower than 400RPM), the entire unit stops and LED displays
failure information and cant returns to normal operation automatically.

8.6

Fan-only mode
Fan speed is high/mid/low/ Auto

8.7

Cooling mode
The 4-way valve is closed under cooling mode.
The action of the compressor and the outdoor fan:
Condition
Temp. up
Temp. down

Compressor

Outdoor fan

TA> Ts+1

On

On

TA<Ts+1

Off

Off

TA> Ts

On

On

TA<Ts

Off

Off

TA: Indoor ambient temperature


TS: Setting temperature through the remote controller
Auto fan under cooling mode:
Condition

Indoor fan speed

T=Indoor Temp.-Setting Temp.


Temp. up

Temp. down

T<3

Low

3<T<5

Med.

T>5

High

T> 3

High

1<T<3

Med.

T<1

Low

Anti-freezing control to indoor evaporator under cooling mode


Condition
Temp.
Temp. up

T> TE6
T< TE6

Temp. down

Compressor

>5 Minutes

T> TE5
T< TE5

Outdoor fan

Time

>5 Minutes

On

On

Off

Off

On

On

Off

Off

Condenser high-temperature protection under heating mode


T3 >65, turn off compressor.
TE5: Evaporator low temperature protection entering temperature
TE6: Evaporator low temperature protection restoring temperature
8.8
Dehumidifying mode
8.8.1 The 4-way valve is off in dehumidifying mode
8.8.2 Compressor and Indoor Fan actions in dehumidifying mode
Compressor run 5 minutes , and indoor fan run 5 minutes in low speed, then turn off the
223

compressor, indoor fan run 5 minutes in low speed. And repeat on and off cycle.
8.8.3 Low room temperature protection:
When room temperature decreases to below 10, the compressor and the outdoor fan
will stop(indoor fan is Breeze). Dehumidifying operation will be resumed when room
temperature restores to over 13.
8.8.4 Under dehumidifying mode, the anti-freezing function of the indoor heat exchanger is the
same as that of cooling mode.
8.9
Heating mode
8.9.1 Generally, the 4-way valve is open in heating mode, but it is closed in defrosting mode.
4-way valve must delay 2 minutes compared with compressor if the compressor changed
into non-heating mode or turned off. 4-way valve doesn't delay in dehumidifying mode.
8.9.2 Generally, the outdoor fan is turned off with the on-off action of compressor in heating
mode, except for the defrosting mode or the end of defrost.
8.9.3 Action conditions of compressor under heating mode: compressor must run for 7
minutes after starting and then judge temperature. Meanwhile other protections are still
valid.
Condition
Room temp. up
Room temp. down

Compressor

Outdoor fan

TA> Ts+3

Off

Off

TA<Ts+3

On

On

TA< Ts+2

On

On

TA>Ts+2

Off

Off

TA: Indoor ambient temperature


TS: Setting temperature through the remote controller
8.9.4 Indoor Fan actions under heating mode
Indoor Fan can be set at HIGH/MID/LOW/AUTO by using a remote controller, but
Anti-cold wind function has the priority.
Anti-cold wind control function under heating mode
Condition

Indoor fan speed

TE
Indoor exchanger temp. up

Indoor exchanger temp. down

TE<TE1

Off

TE1<TE<TE2

Breeze

TE>TE2

Setting fan speed

TE> TE3

Setting fan speed

TE3<TE<TE4

Breeze

TE<TE4

Off

TE: Indoor evaporator temperature


TE1: Anti-cold wind, from Fan Off to Breeze temperature
TE2: Anti-cold wind, from Breeze to Setting Fan Speed temperature
TE3: Anti-cold wind, from Setting Fan Speed to Breeze temperature
TE4: Anti-cold wind, from Breeze to Fan Off temperature

224

8.9.5 Auto wind under heating mode


Condition

Indoor fan speed

T=Indoor Temp.-Setting Temp.


Room temp. up
Room temp. down

T<2

High

T>2

Med.

T> 0

Med.

T<0

High

8.9.6 Indoor evaporator high-temperature protection under heating mode


Indoor exchanger temp. up

Indoor exchanger temp. down

Condition

Compressor

Outdoor fan

TE<TE8

On

On

TE8<TE<TE7

On

Off

TE>TE7

Off

Off

TE>TE9

Off

Off

TE<TE9

On

On

TE: Indoor evaporator temperature


TE7: Evaporator high temperature protection, compressor off temperature
TE8: Evaporator high temperature protection, fan off temperature
TE9: Evaporator high temperature protection, restoring temperature
8.10
Defrosting operation (Available for heating only).
8.10.1 Defrosting condition:
When T3<0 and compressor runs 40 minutes.
T3: Temp. of condenser.
8.10.2 Ending condition of defrost
If one of following conditions is satisfied, end the defrost and turn into heating:
A.The defrost time has reached to 10 minutes.
B.T3>20.
8.10.3 Time sequence of the whole defrosting procedure is as follows
Compressor
ON

4-way Valve

ON
OFF

Outdoor Fan

ON
OFF

225

8.11
Automatic operation mode
8.11.1 The air conditioner automatically selects one of the following operation modes: cooling,
heating or ventilation according to the difference between room temp. (TA) and set temp.
(TS).
TATS

Operation mode

TATS>2

Cooling

-1TATS+2

Fan-only

TATS<-1

Heating (Fan-only for cooling only type)

8.11.2 The indoor fan blows automatically in corresponding selected mode.


8.11.3 The motion of indoor fans vane should accord with the selected operation mode.
8.11.4 One mode should be carried out for at least 15 minutes once selected. If the compressor
cannot start for 15 minutes, reselect the operation mode according to the room temp.
and set temp.or reselect when the set temp. varies.
8.12
Forced cooling function
8.12.1 Select forced cooling function with the forced cooling button or the switch.
8.12.2 The compressor is unconditionally turned on, after 30 minutes cooling operation whose
fan mode is set as low, the A/C operates under the DRY mode with a set temp. of 24.
8.12.3 All protections of remote control cooling are available under forced cooling operation.
8.13
Forced Auto function
Select forced auto function with the forced auto button or the switch in the display
board.
In forced auto status the A/C operates under remote control mode with a set temp. of
24.
8.14
Timer Function Requirement
The maximum length of timer is 24 hours and the minimum resolving power is 15
minutes.
8.15
Economic Running
8.15.1 The economic running function is available under cooling, heating or auto mode.
8.15.2 Cooling:
The set temperature rise 1 per hour. Two hours later, the set temperature will
maintain as a constant and the air circulation is kept at low speed.
8.15.3 Heating:
The set temperature decrease 1 per hour. Two hours later, the set temperature will
maintain as a constant and the air circulation is kept at low speed (Cold air proof
function takes precedence over all).
8.15.4 Auto:
The economic running function operates in accordance with the selected running mode
by the auto mode.

226

8.16

Outdoor fan motor


T4: Outdoor temp.
Cooling mode
Heating mode

T4

Outdoor fan motor

T4>27

High speed

T4<25

Low speed

T4>13

Low speed

T4<11

High speed

227

Exploded view parts


a) INDOOR UNIT

228

b) UNIVERSAL OUTDOOR UNIT

229

230

10. Characteristic of temp. sensor


Temp.

Resistance K

Temp.

Resistance K

Temp.

Resistance K

-10

62.2756

17

14.6181

44

4.3874

-9

58.7079

18

13.918

45

4.2126

-8

56.3694

19

13.2631

46

4.0459

-7

52.2438

20

12.6431

47

3.8867

-6

49.3161

21

12.0561

48

3.7348

-5

46.5725

22

11.5

49

3.5896

-4

44

23

10.9731

50

3.451

-3

41.5878

24

10.4736

51

3.3185

-2

39.8239

25

10

52

3.1918

-1

37.1988

26

9.5507

53

3.0707

35.2024

27

9.1245

54

2.959

33.3269

28

8.7198

55

2.8442

31.5635

29

8.3357

56

2.7382

29.9058

30

7.9708

57

2.6368

28.3459

31

7.6241

58

2.5397

26.8778

32

7.2946

59

2.4468

25.4954

33

6.9814

60

2.3577

24.1932

34

6.6835

61

2.2725

22.5662

35

6.4002

62

2.1907

21.8094

36

6.1306

63

2.1124

10

20.7184

37

5.8736

64

2.0373

11

19.6891

38

5.6296

65

1.9653

12

18.7177

39

5.3969

66

1.8963

13

17.8005

40

5.1752

67

1.830

14

16.9341

41

4.9639

68

1.7665

15

16.1156

42

4.7625

69

1.7055

16

15.3418

43

4.5705

70

1.6469

231