IM30-AP

NC N40-R1A

THREE-PHASE OVERCURRENT AND


EARTH FAULT RELAY
50/51, 50N/51N, 51BF, 68
I>

Two Phase-Fault levels


Two Earth-Fault levels
Selectable Time Current Curves
Breaker Failure protection
Blocking Output and Blocking Input for pilot wire
selectivity coordination
Modbus Communication Protocol
UL / CSA listed

I>>

O>

PROG/ BLOCK BR.


I.R.F. INPUT FAIL.

MICROELETTRICA SCIENTIFICA
MILANO
ITALIA

FUNC.
DISAB.

IA 500A
MODE

MULTIFUNCTION
OVERCURRENT +
EARTH FAULT
RELAY TYPE
IM30-AP

O>>

SELECT

_
PROG.

ENTET/RESET

Three-phase overcurrent plus earthfault relay with programmable Time Current Curves suitable for
protection of HV & MV, Transmission and Distribution systems.
Selectable 1 or 5 A rating for phase as well as neutral inputs.
3rd harmonic active filter on the neutral current.

Real Time Measurements


Maximum Demand and Inrush Recording

= IA - IB - IC - I0
= IA - IB - IC - I0

Programmable Input Quantities


Fn = System frequency
: (50 - 60) Hz
In = Rated primary current of phase CTs
: (1 - 9999)A, step 1A
On = Rated primary current of earth fault detection CT : (1 - 9999)A, step 1A

1F - 50/51 (I>): First Overcurrent Element


- Current setting range
- Instantaneous output

: I> = (0.25 - 4)In, step 0.01In


: 0.03s

- Definite trip time delay in the independent time operation mode


- Trip time delay at 10x[I>] in inverse time operation modes
Operation mode F(I>):

tI> = (0.05 - 30)s, step 0.01s

F(I>) = D : Independent definite time


F(I>) = A : IEC curve type A
F(I>) = B : IEC curve type B
F(I>) = C : IEC curve type C
F(I>) = MI : IEEE moderate inverse time curve

F(I>) = VI : IEEE very inverse time curve


F(I>) = I : IEEE inverse time curve
F(I>) = EI : IEEE extremely inverse time curve
F(I>) = SI : IEEE standard inverse time curve
F(I>) = P : Special curves TU0316
F(I>) = C1 : Special curves TU0373

IM30-AP

NC.N40- R1A

2F - 50/51 (I>>): Second Overcurrent Element


- Current setting range
- Instantaneous output
- Independent time delay
- Automatic doubling of level I>> on inrush

: I>> = (0.5 - 40)In, step 0.1In


: 0.03s
: tI>> = (0.05 - 3)s, step 0.01s
: I>>x2 = ON/OFF

1F - 50N/51N (O>): First Earth Fault Element


- Current setting range
- Instantaneous output

: O> = (0.02 - 0.4)On, step 0.01On


: 0.04s

- Definite trip time delay in the independent time operation mode


- Trip time delay at 10x[O>] in inverse time operation modes.

tO> = (0.05 - 30)s, step 0.01s

Operation mode F(O>): F(O>) = D : Independent definite time


F(O>) = A : IEC curve type A
F(O>) = B : IEC curve type B
F(O>) = C : IEC curve type C
F(O>) = MI : IEEE moderate inverse time curve

F(O>) = VI : IEEE very inverse time curve


F(O>) = I : IEEE inverse time curve
F(O>) = EI : IEEE extremely inverse time curve
F(O>) = SI : IEEE standard inverse time curve
F(O>) = C1 : Special curves TU0373

2F - 50N/51N (O>>): Second Earth Fault Element


- Current setting range
- Instantaneous element
- Independent time delay

: O>> = (0.02 - 4)On, step 0.01On


: 0.04s
: tO>> = (0.05 - 3)s, step 0.01s

Breaker Failure Element


- Trip time delay

: tBF = (0.05 - 0.75)s, step 0.01s

Connexion Diagram

IM30-AP

RS485

MS-SCE1663-R0
Standard Output

RS485

MS-SCE1664-R0
Double Output