Professional Documents
Culture Documents
Copyright du
Telecom infrastructure
standards for buildings
Building Infrastructure Guideline v.5
// Building Infrastructure Guideline v.5
Content
Introduction
02
Cables
18
Telecommunication spaces
General specifications
19
General specifications
08
19
20
A
dministration and
Labelling scheme
21
22
24
Entry ducts
24
Appendices
26
28
Tables
69
Location Map
75
09
09
Clustered buildings
10
10
11
11
11
12
Electro-mechanical
12
Pathway
14
General specifications
16
Vertical containment
16
Horizontal containment
17
Introduction
Telecommunication spaces
Electro-mechanical
Pathways
Cables and its related accessories
Bulk services
Duct entry
Labelling scheme
Telecommunication
spaces
General
specifications
A
ll telecom spaces should be fitted
with emergency lighting.
All containment openings to telecom
spaces must be sealed with a
regulation fire retardant material.
Washrooms
Swimming pools
Garbage area
Showers
A
ll telecom spaces should be fitted
with smoke detectors connected to
the building management system.
A
ll telecom rooms should have basic
firefighting provision of handheld CO2
cylinder type extinguishers.
Temperature
and humidity
High voltages
Clustered buildings
Group of towers
If a project consists of a cluster of multitenant buildings, then all the requirements
of a single tower still applies. One of the
buildings will be selected as the location
for the main telecom room, which usually
stands in the centre of the cluster or often
times closest to the main telecom duct
entry points. This would require the cluster
of buildings to be linked to the designated
main telecom room via multicore single
mode fibre cables. The details of this
arrangement should be discussed with du
during the NOC stage. Cabling concept
is described in the clustered building
schematic diagram in Appendix_1_
Figure-22.
The Mobile
Service Room
(more than G+10)
As mentioned in the MTR section, du Fixed
and Mobile Services can be combined in
one room. The first mobile service room
can be shared with the MTR to serve the
first 10 floors of the building. If sharing
is not feasible, a dedicated 3m x3m x 3m
(WXDXH) mobile service room can also
be provided. Accordingly, the mobile
service rooms must be provided for every
10 floors thereafter. The locations of the
mobile service rooms must be close to the
floor telecom closet (FTC).
The mobile service rooms must have a
minimum distributed floor load rating of
10 kN/m2. The door dimension must be
900mm x 2100mm (WxH) and opening
outwards.
The doors should be labelled Mobile
Service Room .
Refer to the Table-2 and Appendix_1_
Figure-10.
10
Floor Telecom
Closet (FTC)
A floor telecom closet must be provided
on each floor of all multi-storey buildings.
The floor telecom closet is required to
provide a flexible point for the installation,
pulling and maintenance of telecom cables.
FTC must have a minimum dimension of
2m x 1m x 3m (WXDXH).
The floor telecom closet should be
provided with two outward opening doors
with a minimum total opening of 1500mm
x 2100mm (WxH). The door should be
labelled (Floor Telecom Closet
)
In the case of a multi-storey villas,
townhouses, G+1 warehouses or small
retail shops, floor distribution boxes will
be required with a minimum size of
300mm x 300mm x 150 mm (WxHxD), as
an alternative to replace FTC.
In high rise buildings which usually
exceed 30 floors, proper planning and
consideration must be given to the FTC
space and dimension, which might be
increased. It is highly advisable to seek du
advice and pay close attention during NOC
stage to understand the concept of high
rise building infrastructure design. Refer to
Table 3 and 4 and Appendix_1_Figure-4
for the complete detailed layouts of FTC.
Rooftop mobile
service room
(up to G+10)
Rooftop mobile service rooms must be
provided on the roof of all multi-tenant
buildings up to G+10 and access must be
provided to the building riser system.
The door dimension must be 900mm x
2100mm (WxH) and opening outwards and
should be labelled Roof Telecom Room
.
Home consolidation
cabinets
The home consolidation cabinet is a
space to house dus network termination
equipment. It also serves as the
distribution point for all local wiring. A
consolidation cabinet should be provided
in each home. This should be a telecom
cabinet with the following specifications:
M
inimum internal dimensions 600mm
x 600mm x 15mm (HxWxD) for 24 or
less CAT6 cables termination per unit
M
inimum internal dimensions 600mm
x 600mm x 300mm (HxWxD) for more
than 24 CAT6 cables termination per
unit
W
all mount or flushed mount installation
at 1.2m high measured from the
finished floor level up to the edge of
the cabinet.
F
itted with RJ45 UTP patch panel and
cable management.
Fitted with 2-core fibre terminal box.
2
nos. 13A twin sockets fed from the
essential power supply with dedicated
20A circuit breaker.
11
N
ot close to sources of water or heat and
any electrical distribution or bus bars.
N
ot close to sources of water or heat
and any electrical distribution or bus
bars.
L
abelled with office/retail/building unit
number.
Office consolidation
cabinets
Commercial predefined offices,
warehouses, sheds, shops.
The office consolidation cabinet is a
space to house dus network termination
equipment. It also serves as the
distribution point for all the local wiring.
A consolidation cabinet must be provided
in each business area. This should be
a telecom cabinet with the following
minimum specifications:
M
inimum internal dimensions 600mm
x 600mm x 300mm (HxWxD)
Electro-Mechanical
Main Telecom Room (MTR)
For commercial and mixed used buildings,
the following requirements need to be
provided:
S
MDB inside the room fed from power
supply (with generator backup) for
fixed equipment. Refer to the single line
diagram in Appendix_1_Figure_27
2
x32A TP isolators to be provided in the
Main Telecom Room - Refer to the SLD
in Appendix_1_Figure_27
2
nos. 13A twin sockets fed from the
essential power supply with dedicated
20A circuit breaker.
2
nos. handheld CO2 cylinder
extinguishers to be provided inside
the room.
D
edicated A/C system (ducted split FCU)
with duty and standby units with proper
interlocking, to maintain the room temp.
at 20+/-3C.
H
eat dissipation can be considered at
300 Watts/sq.mtr.+3kW per rack.
R
oom should be provided with
adequate lighting and comply with the
fire and safety requirements like smoke
detector, fire alarm, emergency light etc.
as per local authority standards. Any
water sprinklers to be avoided.
2
nos. handheld CO2 cylinder
extinguishers to be provided inside the
room.
H
eat dissipation to be Increased by 8kW
for GSM equipment- if MTR is shared
between du Fixed and Mobile services.
For residential buildings, the following
requirements need to be provided:
2
nos. 13A twin sockets fed from the
essential power supply with dedicated
20A circuit breaker.
One earth bar connected to the telecom
earth pit with resistance less than 1ohm.
Room must be provided with adequate
lighting.
Room should be provided with air
conditioning system to maintain the
room temp. at 20+/-3C
Mobile Service
Room and Rooftop
Mobile Service Rooms
For all mobile service rooms and rooftop
mobile service room, all requirements
mentioned in Passive MTR must be followed
including the 1x63A TP isolator and the
heat dissipation requirement. Further advice
will be given during the NOC stage for the
rooftop mobile service room design.
Floor Telecom Closet (FTC)
Adequate lighting and 1x13A twin socket
fed from the normal building supply
with dedicated 20A circuit breaker.
13
Pathways
14
15
General
specifications
16
Vertical
Containment
Horizontal
Containment
Multi-storey/multi-tenant buildings
Multi-storey/multi-tenant buildings
17
Cables
General
specifications
18
Outdoor rated
Single mode
Compliant with ITU-T G.652D
Loose tube inner construction or
Ribbon type for high density cables
Fibre optic colouring code shall be in
accordance to EIA/TIA-598
19
20
CAT6 Copper
Cables
Administration and
labelling scheme
E
ach socket in the dual RJ45 outlet
must
be wired back to the consolidation point.
O
utlets must not be cascaded or looped
& there must be no splitting of cable
pairs.
T
he maximum cable length from
consolidation point to outlet must
not exceed 90m.
21
Bulk service
requirements
Bulk service
application
22
23
Other special
requirements
Entry ducts
The building developer must provide leadin ducts from the main telecom room to
the plot boundary. The exact connection
points at the plot boundary will depend on
whether the du network already reaches
the plot.
Option 1 du duct network already exists
The building developer will be
responsible to connect to the du
ducting system.
The operator will identify the location
and quantity of their lead-in ducts.
Option 2 du duct network is still to be
built
The building developer will be
responsible to extend the lead-in duct
to 1m outside the plot boundary.
The building developer is responsible
for locating and clearly identifying lead
in ducts.
24
25
Appendices
26
27
mm.
m.
x
mm
Active
Rack
High density
floor mount
ODF racks for
building fibres
Smoke detector
connected to BMS
SMDB du
x handheld
CO cylinder
extinguishers
x
mm
RACK
Raised floor
du fibre
entry cable
x
mm
RACK
This space is
reserved for
du UPS
and Batteries
mm.
x
mm
RACK
x
mm
RACK
m.
du fibre
entry cable
x handheld
CO cylinder
extinguishers
Building riser
Containment system under the raised floor
Building riser
Containment system under the raised floor
NOTES:
Building type Residential
Number of Units Up to 300 Units
28
Refer to single
line diagram
NOTES:
Building type Commercial / Mixed Use
Number of Units Up to 600 Units
29
Appendix_1_Figure 3
Appendix_1_Figure 4
m.
m.
m.
Containment system
under raised floor
x
mm
RACK
x
mm
RACK
x
mm
RACK
Passive
Component
Racks
m.
High density
floor mount
ODF racks for
building fibres
x
mm
RACK
Active
Component
Racks
SMDB du
Building riser
Building Riser
A twin socket
fed from utility
power with dedicated
circuit breaker
Mini - ODF
Smoke Detector
connected to BMS
x handheld
CO cylinder
extinguishers
Refer to
single line
diagram
x handheld
CO cylinder
extinguishers
mm opening
NOTES:
Building type Residential / Commercial / Mixed Use
Number of Units Up to 1200 Units
30
31
m.
m.
Smoke detector
connected to BMS
x
mm
RACK
x
mm
RACK
A three phase
isolator fed
from essential
building power
(for GSM equipments)
Containment system
at high level
Smoke detector
connected to BMS
A twin socket
fed from utility
power with
dedicated
circuit breaker
A three phase
isolator fed
from essential
building power
(for GSM equipments)
A twin socket
fed from utility
power with dedicated
circuit breaker
du fibre
entry cable
x handheld
CO cylinder
extinguishers
NOTES:
Building type Residential
Number of Units Up to 600 Units
32
x
mm
G Rack
DC
System
DC
System
Containment system
at high level
x
mm
G Rack
x
mm
G Rack
x
mm
G Rack
x
mm
G Rack
Building riser
x
mm
G Rack
m.
A twin socket
fed from utility
power with
dedicated
circuit breaker
m.
Building riser
NOTES:
Building type Residential
Number of Units Up to 1200 Units
33
m.
Building riser
m.
A twin socket
fed from utility power with
dedicated circuit breaker
Building riser
Containment system
under the raised floor
This Space
is reserved
for UPS
and Batteries
x
mm
G Rack
x
mm
G Rack
x
mm
G Rack
SMDB
DC
System
x handheld
CO cylinder
extinguishers
Smoke detector
connected to BMS
m.
x x
mm
mm
RACK
Active
RACK
Smoke detector
connected to BMS
x
mm
G Rack
x
mm
G Rack
x A three
phase isolator
fed from
SMDB-du
(Fixed Equipment)
DC
System
NOTES:
Building type Commercial / Mixed Use
Number of Units Up to 1200 Units
This Space
is reserved
for UPS
and Batteries
A twin socket
fed from utility
power with
dedicated
circuit breaker
m.
x
mm
Active
Rack
SMDB
x
mm
RACK
x
mm
G Rack
x
mm
RACK
x A TP isolators
fed from SMDB du
Containment system
under the raised floor
34
x handheld
CO cylinder
extinguishers
NOTES:
Building type Commercial / Mixed Use
Number of Units Up to 600 Units
35
x
mm
RACK
Building riser
x
mm
RACK
Passive
Component
Racks
du Fibre
entry cable
x
mm
G Rack
x
mm
G Rack
DC
System
Smoke detector
connected to BMS
A three phase isolator fed
from essential building power
x handheld
CO cylinder
extinguishers
x handheld
CO cylinder
extinguishers
Building riser
NOTES:
Building type Residential / Commercial
Number of Units Up to 1200 Units
36
x A three phase
isolator fed from
SMDB-du
(Fixed Equipment)
SMDB
x
mm
G Rack
du fibre
entry cable
x
mm
RACK
Active
Component
Racks
m.
x
mm
RACK
m.
m.
Containment system
under the raised floor
Appendix_1_Figure 10
m.
NOTES:
Provide Mobile Service Room for ever 10th floor
37
Appendix_1_Figure 11
Appendix_1_Figure 12
mm
mm
Port Cat
Patch PanelU
Cable Manager U
ATB
U Metallic Support
to hold du CPE
38
ATB
Port Cat
Patch PanelU
PERFORATED DOOR
U Metallic Support
to hold du CPE
mm
Cable Manager U
A twin Socket
PERFORATED DOOR
mm
39
Appendix_1_Figure 13
Appendix_1_Figure 14
RACK-2
RACK-1
Mounting option
Cabinet depth = mm / mm
U cabinet
Wall
iPatch
Fiber
Building Fibre
Termination
Area
U U
Vertical rings
Mounting option
U cabinet
This area is
reserved for the
installation of
splitters by du
U
1.2 meter to
1.4 meter
from FFL
Wall
40
1.2 meter to
1.4 meter
from FFL
This area is
reserved for the
installation of
splitters by du
U
U cabinet
mm / mm
Building Fibre
Termination
Area
U U
Mounting option
mm.
Wall
NOTES:
Maximum number of fibre cores to
be terminated per rack are 480 cores
Building type Residential
Number of Units Up to 300 Units
41
Appendix_1_Figure 15
RACK-1
Fibre Patch Panel
Supply and installation by du
RACK-2
iPatch
Fiber
Building Fibre
Termination
Area
U U
Vertical rings
Equipment by
du - U
This area is
reserved for the
installation of
active equipment
by du U
RACK-2
RACK-1
Building Fibre
Termination
Area
U U
This area is
installation of
active equipment
by du U
10
11
iPatch
12
Fiber
Building Fibre
Termination
Area
U U
Vertical rings
This area is
reserved for the
installation of
splitters by du
U
Building Fibre
Termination
Area
U U
This area is
reserved for the
installation of
active equipment
by du U
mm.
mm.
Appendix_1_Figure 16
NOTES:
Maximum number of fibre cores to
be terminated per rack are 480 cores
Building type Commercial
Number of Units Up to 300 Units
42
NOTES:
Maximum number of fibre cores to
be terminated per rack are 480 cores
Building type Mixed use
Number of Units Up to 300 Units
43
Appendix_1_Figure 17
Appendix_1_Figure 18
i Patch
10
11
12
i Patch
Fiber
Fiber
i Patch
Fiber
Client
server
rack
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
30
31
32
33
34
35
36
37
38
39
40
41
42
Ring
U Cable Manager
Ring
mm cable tray
at high level
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
This area is
30
reserved for the 31
installation of 32
33
active equipment 34
35
by du U
36
37
38
39
40
41
42
Perforated door
mm.
Core SM Fibre
Patch Panel by du
Ring
Ring
du MDF room
Ring
NOTES:
The bulk service cabling minimum requirements between du
rack and client server rack are as below:
Core LC/ACP
Adapters Sub rack for du splitter
Installed at meter to meter from FFL
44
45
Appendix_1_Figure 19
Appendix_1_Figure 20
12cm (W)
2 Core fibre cable
entry to the fibre
terminal box
Option-1
Minimum 1 meter
pigtail inside the FTB
9cm (H)
2 core fibre
cable entry to
the access
terminal box
Option-3
Roof Top
GSM room
Roof Floor
1 2
th Floor
Unit -X1
Unit -06
Unit -04
Unit-02
FTC
ROOM
Unit-02
FTC
ROOM
Unit -01
Unit -03
Unit -01
Unit -03
th Floor
Unit -01
Unit -03
Unit-7
Unit-9
Unit- X
Unit-7
Unit-9
Unit- X
Unit-05
Unit-7
Unit-9
Unit- X
Unit-05
Unit-7
Unit-9
Unit- X
Unit-9
Unit- X
Unit-05
Unit -X1
Unit -06
Unit -04
Unit -01
Unit -03
Unit-05
th Floor
Unit -X1
Unit -06
Unit -04
Unit-02
FTC
ROOM
th Floor
Unit -X1
Unit -06
Unit -04
Unit-02
FTC
ROOM
mm Cable Tray
st Floor
Unit -X1
Unit -06
Unit -04
Unit-02
FTC
ROOM
Unit -01
Unit -03
Unit-05
Unit-7
2.
5c
(D
MTR Room
for Fixed Services
Ground Floor
rd
Basement Floor
Ducts for du
entry Cables
Ducts for du
entry Cables
mm Cable Tray between MTR and Entry Ducts
46
47
Appendix_1_Figure 21
Roof Floor
mm Cable Tray for
Horizontal Distribution
th Floor
Building
Unit -X1
Unit -06
Unit -04
Unit-02
FTC
ROOM
Unit -01
Unit -03
Unit-05
Unit-7
Unit-9
Unit- X
Unit -X1
Unit -06
Unit -04
Unit-02
FTC
ROOM
FTC
ROOM
Unit -01
Unit -03
Unit-05
Unit-7
Unit-9
Unit- X
Unit -X1
Unit -06
Unit -04
Unit-02
th Floor
Unit -X1
Unit -06
Unit -04
Unit-02
mm Cable Tray
st Floor
FTC
ROOM
Ground Floor
rd Basement Floor
Unit -06
Unit -04
Unit-02
Unit -03
Unit-05
Unit-7
Unit-9
Unit- X
Unit -01
Unit -03
Unit-05
Unit-7
Unit-9
Unit- X
FTC
ROOM
Unit-9
Unit- X
Unit -01
Unit -03
Unit-05
Unit-7
Ducts for du
entry Cables
mm Cable Tray between MTR and Entry Ducts
48
Building
MTR
Main
MTR
Building
Unit -X1
Unit -01
MTR
Plot Limit
Floor
Building
MTR
th
Plot Limit
th Floor
Plot Limit
Roof Top
GSM room
MTR
MTR
Building
Building
Plot Limit
Provide minimum of x mm Cable tray
from Main MTR to MTR of each building
49
PLOT LIMIT
Villa 01
Villa 02
Lead in ducts
Villa 03
Villa 04
Villa 05
Villa 06
Villa 07
Villa 08
Villa 09
Villa 10
Villa 11
PLOT LIMIT
Villa 12
W D
ducts
JRC
Villa 13
Entry Box
xxcm
PLOT LIMIT
Entry Box
Villa 17
PLOT LIMIT
Villa 16
PLOT LIMIT
JRC
Villa 15
Ground Level
Villa 14
JRC12
JRC
Villa 21
Villa 22 Villa 23
Villa 24
Villa 25
Villa 26
Villa 27
Villa 28
Villa 29
Villa 19
Villa 18
50
PLOT LIMIT
51
Appendix_1_Figure 25
Appendix_1_Figure 26
mm (W) x mm (H)
Opening for Cables Entry
th Floor
mm
mm
Roof Top
GSM room
Unit -X1
Unit -06
Unit-02
th Floor
Unit -X1
Unit -06
Unit-02
th Floor
Unit -X1
Unit -06
Unit-02
mm (H)
th
Floor
Unit -X1
mm Cable Tray
th Floor
Unit -X1
Unit -06
Unit-02
FTC
ROOM
MINI ODF
FTC
ROOM
MINI ODF
FTC
ROOM
MINI ODF
Unit-02
Unit -01
Unit -03
Unit-05
Unit-7
Unit-9
Unit- X
Unit -01
Unit -03
Unit-05
Unit-7
Unit-9
Unit- X
Unit -01
Unit -03
Unit-05
Unit-7
Unit-9
Unit- X
Unit -01
Unit -03
Unit-05
Unit-7
Unit-9
Unit- X
Unit-9
Unit- X
FTC
ROOM
Unit -01
Unit -03
Unit-05
Unit-7
MTR ROOM
Ground Floor
rd
Basement Floor
Ducts for du
entry Cables
Ducts for du
entry Cables
mm Cable Tray between MTR and Entry Ducts
mm (W)
52
FTC
ROOM
MINI ODF
53
Appendix_1_Figure 27
A TP
Isolator
Appendix_2_Figure 28
A TP
Isolator
x spares
A TP
MCCB
A TP
MCCB
55
55
A TP
MCCB
A TP
MCCB
spaces
55
A TP
MCCB
Cx mm XLPE/
SWA + CX ECC
5
5
45
A TP Iso.
55
Essential DB
ATS
Generator
Power
54
Permanent
Power
PLAN
55
Schedule
Number
Step
18
14
10
11
mm cement
rendering with
fall to sump
Construction joint
1130
200
min
745
Landscaping/Tiling
185
75
70
50/60
Description
Item
460
Appendix_2_Figure 29
Water bar
(under water level)
Tanking membrane
Class (C) concrete blinding
56
57
Appendix_2_Figure 31
Appendix_2_Figure 32
Landscaping/Tiling
Schedule
745
1130
100
460
75
185
50
50/60
200
min
Item
Construction joint
Water bar
(under water level)
Description
Number
22
10
10
11
30
12
12
13
14
12
15
12
58
59
2585
225
915
10
380
225
203
1,2
mm cement rendering
with fall to sump
15
100
9
70
Slope
130
560
200
100
275
75
130
150
915
380
300
150
300
230
1285
635
203
Varies to suit
site conditions
150
55
175
175
150
200 20
Landscaping/Tiling
140
65656565
175
150
20 200
260
1715
50/60
260
min.
90
175
200
Appendix_2_Figure 33
205
230
130
Construction joint
Tanking membrane
Class (C) concrete blinding
PLAN
60
61
Appendix_2_Figure 34
Appendix_2_Figure 35
1245
915
Landscaping/Tiling
4 Bars @ 200 MM
190
150
170
460
760
1130
745
200
min
150
200
Construction
joint
62
275
75
75
185
PLAN
Water bar
(under water level)
63
Appendix_2_Figure 36
Appendix_2_Figure 37
Schedule
Description
150
Number
14
16
7
150
Bars @ 230 MM
Item
5 Bars @ 230 MM
64
65
Appendix_2_Figure 38
Appendix_2_Figure 39
190
535
190
1&2
4 Bars @ 180 MM
100
200
130
830
4 Bars @ 180 MM
7
90
Construct concrete
surround as required.
100mm min. for
unmade surface
100
100
120
200
66
67
Tables
Labelling Scheme
Labeling Scheme for 2 core SM fibre cables using ferrule (during cable pulling)
2 Core SM fibre cables at MTR side
Floor number/name-unit number/name-core number
Example for apartments
F02-ACP04-C01
FL02-ACP04-C02
GR-REP-C01
GR-REP-C02
FL03-OCP05-C01
FL03-OCP05-C02
GR-RCP01-C01
GR-RCP01-C02
Table 1
B1-BMS-C01
B1-BMS-C02
Labeling scheme for 2 core SM fibre cables after terminating inside fibre ODF/patch panel
Floor number/name-unit number/name-ODF core number Example - FL10 - ACP012-ODF 95,96 Example - FL01 - ACP04-ODF 11,12
12 Horizontal Orientation
1
2
Note Always terminate the end of the pigtail-1 to Core-1 of SM fibre Cable
Labeling scheme for cabinets inside apartments/offices/reception/retail shops etc..
Example F1 - ACP12
Labeling scheme for Cat 6 cables inside units using ferrule (during cable pulling)
Number
of units
Up to 600
3x3x3
3x4x3
600 to 1200
4x4x3
4x4x3
More than
1200
Will be Advised
at NOC Stage
Will be Advised
at NOC Stage
NOTES:
Labelling scheme for wall mount ODF, Floor mount ODF, Mini ODF,
Indoor multicore fibre cables will be advised at NOC stage
10
11
12
C-1,2
Floor no
Unit no
C-25,26
Floor no
Unit no
C-3,4
Floor no
Unit no
C-27,28
Floor no
Unit no
C-5,6
Floor no
Unit no
C-29,30
Floor no
Unit no
C-7,8
Floor no
Unit no
C-31,32
Floor no
Unit no
C-9,10
Floor no
Unit no
C-33,34
Floor no
Unit no
C-11,12
Floor no
Unit no
C-35,36
Floor no
Unit no
C-13,14
Floor no
Unit no
C-37,38
Floor no
Unit no
C-15,16
Floor no
Unit no
C-39,40
Floor no
Unit no
C-17,18
Floor no
Unit no
C-41,42
Floor no
Unit no
C-19,20
Floor no
Unit no
C-43,44
Floor no
Unit no
C-21,22
Floor no
Unit no
C-45,46
Floor no
Unit no
C-23,24
Floor no
Unit no
C-47,48
Floor no
Unit no
C-49,50
Floor no
Unit no
C-51,52
Floor no
Unit no
C-53,54
Floor no
Unit no
C-55,56
Floor no
Unit no
C-57,58
Floor no
Unit no
C-59,60
Floor no
Unit no
C-61,62
Floor no
Unit no
C-63,64
Floor no
Unit no
C-65,66
Floor no
Unit no
C-67,68
Floor no
Unit no
C-69,70
Floor no
Unit no
C-71,72
Floor no
Unit no
C-73,74
Floor no
Unit no
C-75,76
Floor no
Unit no
C-77,78
Floor no
Unit no
C-79,80
Floor no
Unit no
C-81,82
Floor no
Unit no
C-83,84
Floor no
Unit no
C-85,86
Floor no
Unit no
C-87,88
Floor no
Unit no
C-89,90
Floor no
Unit no
C-91,92
Floor no
Unit no
C-93,94
Floor no
Unit no
C-95,96
Floor no
Unit no
68
69
Number
of floors
Mobile service
room sizes in meter
(L X B X H)
residential
Number of
commercial
or residential
units
Up to G+10
3x3x3
G+11 to G+100
3 x 3 x 3 every 10
floors starting from
the lowest basement
3 x 3 x 3 every 10 floors
starting from the lowest
basement
Up to 150 Units
(G+15)
Shopping malls
and bulk services
buildings
Will be advised
at NOC stage
Will be advised
at NOC stage
Cluster of buildings
with each having
more than G+5
floors
Will be advised
at NOC stage
Will be advised
at NOC stage
Fibre patch
panel and
ODF core
quantity
(angled
adapter type)
Racks units
required to
terminate
building fibre
cables in each
42 u rack
4 number of
96 core fibre
patch panel
required
20 U to 24 U
7 number of
96 core fibre
patch panel
required
20 U to 24 U
in each Rack
Install and
terminate
indoor
multicore
fibre cables
Use high
42 U
density angled
adapter fibre
patch panels
Install wall
mount mini
ODF at every
10th floor
(Starting
from 30th
Floor)
Install and
terminate
indoor
multicore
fibre cables
2 x 42 U
Use high
density angled
adapter fibre
patch panels
600 to 1200
Units (Towers)
(G+61 to
G+120 Floors)
Minimum two
number of high
density rack
required
For above
1200 Units
(For above
G+120)
70
Indoor
multicore
fibre
cables
71
Table 5
Indoor
multicore
fibre cables
(to connect
wall mount
ODFs and
MTR)
Fibre patch
panel and
ODF core
quantity
(angled
adapter
type)
Racks units
required to
terminate
building fibre
cables in each
42 U Rack
Number
units
(apartments,
retails)
One number of
Not
42 U 800 x 800mm Required
required for
residential units
one number of
42 U 800 x 800mm
required for
commercial units
Not
Required
2 number
of 96 core
fibre patch
panel
required in
each rack
20 U to 24 U
in each rack
Not
One number of
42 U 800 X 800mm Required
required for
residential units one
number of
42 U 800 X 800mm
required for
commercial units
Not
Required
Minimum one
number of high
density rack
required with
proper separation
for residential and
commercial units
Install wall
mount
mini ODF
at every
10th floor
(Starting
from 30th
floor)
Install and
terminate
indoor
multicore
fibre cables
Install wall
mount
mini ODF
at every
10th floor
(Starting
from 30th
floor)
Install and
terminate
indoor
multicore
fibre cables
Number of
Racks required to
residential and
terminate building
commercial units fibre cables inside
MTR
Up to 150 units
(considering
50% units to be
residential and
50% units to be
commercial)
600 to 1200
units
(considering
50% units to be
residential and
50% units to be
commercial)
For above
1200 Units
72
Minimum two
number of high
density rack
required with
proper separation
for residential and
commercial units
Wall
mount
ODF
4 number
of 96 core
fibre patch
panel
required in
each rack
20 U to 24 U
in each rack
Use high
42 U
density
angled
adapter fibre
patch panels
Use high
2 x 42 U
density
angled fibre
patch panels
Number of
building fibre
core spilced
inside of wall
mount ODF
Requirement
of 2:32
splitter
unit
Requirement
of 2:16
splitter
unit
Requirement
of 2:2
splitter
unit
Feeder port/
cores required
to terminate
entry cables
for 2:32 splitter
ratio scenario
Feeder port/
cores required
to terminate
entry cables
for 2:16 splitter
ratio scenario
Up to 150
Residential
units
300 cores
10
12 cores
24 cores
Up to 300
Residential
units
600 cores
10
19
24 cores
48 cores
Up to 600
Residential
units
1200 cores
19
38
48 cores
76 cores
Note: Consultants and Contractors are advised to coordinate with du at NOC stage for the exact
splitter ration scenario and for the exact splitter site.
Single Villa
Bulk Service
Ducts
Entry
Box
600mm x 600mm
x800mm
(L x B x D)
per villa
600mm x
Not Required
600mm x800mm
(L x B x D)
per villa
Not Required
600mm x
Not Required
600mm x800mm
(L x B x D)
per villa
Manhole
Not Required
JRC 12
Warehouse
and Shed
73
Responsibility Matrix
Item
No.
Item Description
Buildings
owner
du
Lead-in ducts
OSP fibre optic cables for buildings connections (including supply and termination)
OSP fibre optic cables for villas connections (including supply and termination)
Fibre optic cables supply between du Main Telecom Rooms (cluster of buildings)
Fibre optic cables pulling between du Main Telecom Rooms (cluster of buildings)
Fibre optic cables supply from du Main Telecom Room up to the CP cabinet
Fibre optic cables pulling from du Main Telecom Room up to the CP cabinet
density fibre panel, FDH, optical patch panel, mini ODF, micro ODF, connectors,
13
14
15
High density fibre rack and 42U rack supply and installation
16
17
18
19
21
22
10
11
12
20
74
Location Map
Fibre optic cables termination and testing inside MTR, CP and FTC
Fibre optic termination components such as the floor mount and wall mount high
adaptors and racks
Telecom rooms/spaces and related EM, civil and raised floor system
75
Location Map
76
77
Reserved du-EITC. This document is not for resale. Printed in United Arab Emirates.