IXYS Company
Provisional Data
MAXIMUM
LIMITS
UNITS
VDRM
3600-4200
VDSM
3600-4200
VRRM
3600-4200
VRSM
3700-4300
MAXIMUM
LIMITS
UNITS
OTHER RATINGS
IT(AV)M
2065
IT(AV)M
1430
IT(AV)M
877
IT(RMS)
4056
IT(d.c.)
3564
ITSM
28.0
kA
ITSM2
31.0
It
It
(di/dt)cr
2
2
kA
3.9210
As
4.8110
As
continuous, 50Hz
150
300
non-repetitive
600
2
2
A/s
VRGM
PG(AV)
PGM
40
Tj op
-40 to +125
Tstg
-40 to +150
Page 1 of 11
March, 2007
Characteristics
PARAMETER
MIN.
TYP.
UNITS
VTM
1.70
ITM=2000A
VTM
2.92
ITM=6200A
VT0
Threshold voltage
1.121
rT
Slope resistance
0.291
1000
V/s
IDRM
100
Rated VDRM
mA
IRRM
100
Rated VRRM
mA
Vtr
12
VGT
3.0
IGT
300
VGD
0.25
Rated VDRM
IH
Holding current
1000
Tj=25C
mA
tgd
0.5
1.5
tgt
Turn-on time
1.5
3.0
Qrr
Recovered charge
6700
Qra
4300
4600
Irm
205
trr
42
tq
Mounting force
Wt
Weight
Tj=25C
V
V
VD=10V, IT=3A
mA
V
C
ITM=2000A, tp=2000s, di/dt=10A/s,
Vr=100V
C
A
s
400
700
0.013
K/W
0.026
K/W
27
34
1000
Outline option VC
800
Outline option VF
(Note 2)
Page 2 of 11
kN
g
Turn-off time
RthJK
March, 2007
Voltage Grade
36
38
40
42
VRSM
V
3700
3900
4100
4300
VD VR
DC V
2160
2280
2400
2520
IGM
4A/s
IG
tp1
The magnitude of IGM should be between five and ten times IGT, which is shown on page 2. Its duration
(tp1) should be 20s or sufficient to allow the anode current to reach ten times IL, whichever is greater.
Otherwise, an increase in pulse current could be needed to supply the necessary charge to trigger. The
back-porch current IG should remain flowing for the same duration as the anode current and have a
magnitude in the order of 1.5 times IGT.
6.0 Frequency Ratings
The curves illustrated in figures 17 & 18 are for guidance only and are superseded by the maximum
ratings shown on page 1. For operation above line frequency, please consult the factory for assistance.
7.0 Rate of rise of on-state current
The maximum un-primed rate of rise of on-state current must not exceed 600A/s at any time during turnon on a non-repetitive basis. For repetitive performance, the on-state rate of rise of current must not
exceed 300A/s at any time during turn-on. Note that these values of rate of rise of current apply to the
total device current including that from any local snubber network.
8.0 Square wave frequency ratings
These ratings are given for load component rate of rise of on-state current of 50A/s.
Page 3 of 11
March, 2007
WAV =
I AV
VT 0 + VT 0 + 4 ff 2 rT WAV
=
2 ff 2 rT
and:
T
Rth
T = T j max TK
30
60
90
120
180
270
d.c.
0.0167
0.0160
0.0152
0.0145
0.0141
0.0134
0.0130
0.0296
0.0290
0.0282
0.0276
0.0271
0.0264
0.0260
0.0161
0.0153
0.0147
0.0143
0.0130
0.0291
0.0283
0.0278
0.0273
0.0260
Form Factors
Conduction Angle
30
60
90
120
180
270
d.c.
Square wave
3.464
2.449
1.732
1.414
1.149
Sine wave
3.98
2.778
2.22
1.879
1.57
rt = rp 1 e p
p =1
p=n
The coefficients for this device are shown in the tables below:
D.C. Double Side Cooled
1
Term
2
-3
3
-3
-3
rp
7.87120310
3.46012710
1.47874610
0.3818344
0.1099644
5.28685810
-3
rp
0.01382285
4.92089810
2.409342
1.211641
-3
Page 4 of 11
4
-3
-3
5.32187310
1.74642210
0.1443263
6.25844510
-3
March, 2007
VT = A + B ln (I T ) + C I T + D I T
The constants, derived by curve fitting software, are given below for both hot and cold characteristics. The
resulting values for VT agree with the true device characteristic over a current range, which is limited to
that plotted.
25C Coefficients
125C Coefficients
2.325707254
1.108116254
-0.2476111
-0.06961462
-5
-4
7.9566210
1.6757110
0.02287943
0.01757271
(ii)
Qrr =
rr
.dt
(iii)
K Factor =
t1
t2
Fig. 1
Page 5 of 11
March, 2007
Curves
Figure 1 - On-state characteristics of Limit device
10000
K2065V#360-420
AD Issue 1
K2065V#360-420
AD Issue 1
SSC 0.026K/W
Tj = 25C
Tj = 125C
0.01
1000
DSC 0.013K/W
0.001
0.0001
0.00001
100
0
0.5
1.5
2.5
0.000001
1E-05 0.0001
3.5
0.01
0.1
10
100
Time (s)
0.001
K2065V#360-420
AD Issue 1
K2065V#360-420
AD Issue 1
Tj=25C
Tj=25C
12
5
Max VG dc
10
Max VG dc
IGT, VGT
PG Max 40W dc
-40C
-10C
25C
125C
Min VG dc
IGD, VGD
Min VG dc
PG 3W dc
0
0
0.2
0.4
0.6
0.8
10
Page 6 of 11
March, 2007
100000
K2065V#360-420
AD Issue 1
Tj=125C
100000
4000A
2000A
1000A
500A
10000
1000
K2065V#360-420
AD Issue 1
Tj=125C
4000A
2000A
1000A
500A
10000
1000
1
10
100
1000
10
di/dt (A/s)
1000
K2065V#360-420
AD Issue 1
K2065V#360-420
AD Issue 1
Tj=125C
Tj=125C
4000A
2000A
1000A
500A
1000
100
di/dt (A/s)
100
100
4000A
2000A
1000A
500A
10
10
1
10
100
1000
10
100
1000
di/dt (A/s)
di/dt (A/s)
Page 7 of 11
March, 2007
K2065V#360-420
AD Issue 1
8000
K2065V#360-420
AD Issue 1
180
125
90
120
7000
60
30
6000
5000
4000
3000
2000
100
75
50
25
30
60
90 120
1500
2000
180
1000
500
1000
1500
2000
2500
3000
500
1000
2500
3000
K2065V#360-420
AD Issue 1
K2065V#360-420
AD Issue 1
8000
125
Maximum permissible heatsink temperature (C)
7000
6000
5000
d.c.
270
180
120
90
60
30
4000
3000
2000
100
30
60
90
120
180
270
d.c.
75
50
25
1000
0
0
1000
2000
3000
4000
1000
2000
3000
4000
Page 8 of 11
March, 2007
150
K2065V#360-420
AD Issue 1
4000
K2065V#360-420
AD Issue 1
180
30
60
90
120
125
Maximum permissable heatsink temperature (C)
3500
3000
2500
2000
1500
1000
100
75
50
25
30
60
90 120
180
500
0
0
500
1000
1500
2000
500
1000
1500
2000
K2065V#360-420
AD Issue 1
K2065V#360-420
AD Issue 1
4000
125
Maximum permissible heatsink temperature (C)
3500
3000
d.c.
270
180
120
90
60
30
2500
2000
1500
100
30
60
90
120
180
270
d.c.
75
50
1000
25
500
0
0
500
1000
1500
2000
2500
500
1000
1500
2000
2500
Page 9 of 11
March, 2007
K2065V#360-420
AD Issue 1
K2065V#360-420
AD Issue 1
TK=55C
di/dt=50A/s
500A
1kA
1.00E+04
500A
TK=55C
1kA
1.00E+04
1.5kA
1.5kA
2kA
3kA
Frequency (Hz)
Frequency (Hz)
2kA
4kA
1.00E+03
5kA
3kA
1.00E+03
4kA
5kA
1.00E+02
1.00E+02
1.00E+01
1.00E-05
1.00E-04
1.00E-03
1.00E+01
1.00E-05
1.00E-02
1.00E-04
di/dt (A/s)
1.00E-03
1.00E-02
di/dt (A/s)
10000
1.00E+07
100000
Tj (initial) = 125C
1000
K2065V#360-420
AD Issue 1
1
10
10
50
100
1.00E+06
Page 10 of 11
March, 2007
101A314
Outline option VF
Outline option VC
ORDERING INFORMATION
K2065
VC or VF
Outline code
Voltage code
VC=34mm height
VRRM/100
36-42
VF=27mm height
Typical order code: K2065VC360 3600V VDRM, VRRM, 34mm clamp height capsule.
Fixed
Type Code
WESTCODE
An
IXYS Company
www.westcode.com
www.ixys.net
The information contained herein is confidential and is protected by Copyright. The information may not be used or disclosed except with
the written permission of and in the manner permitted by the proprietors Westcode Semiconductors Ltd.
0
Fixed turn-off
time code
In the interest of product improvement, Westcode reserves the right to change specifications at any time without prior notice.
Devices with a suffix code (2-letter, 3-letter or letter/digit/letter combination) added to their generic code are not necessarily subject to
the conditions and limits contained in this report.
Page 11 of 11
March, 2007