Compact Controller for Stand-by and Parallel Operating Gen-sets

InteliGen
InteliSys
Software version IG-6.1.2, IS-3.3.1, February 2005

Application guide

Copyright 2004 ComAp s.r.o.


Written by Ladislav Kadanik
Prague, Czech Republic

ComAp, spol. s r.o.


Svtova 7, 180 00 Praha 8, Czech Republic
Tel: +420 2 66316661, Fax: +420 2 66316647
E-mail: info@comap.cz, www.comap.cz

Table of Contents
Table of Contents ...............................................................................................................................................2
1. InteliGen, InteliSys applications .....................................................................................................................4
1.1.
Single set...........................................................................................................................................4
1.2.
Multiple sets ......................................................................................................................................4
2.
Single set ...................................................................................................................................................5
2.1.
Single Prime Mover: SPM .................................................................................................................5
2.2.
Single Stand-by: SSB........................................................................................................................6
2.2.1 Separate GCB and MCB ..................................................................................................................6
2.2.2 ATS ...............................................................................................................................................6
2.2.3 SSB + On Load Test........................................................................................................................7
2.3 Single Parallel to Mains: SPtM................................................................................................................8
2.3.1 Single short time parallel ..................................................................................................................8
2.3.2 SPtM + On Load Test ......................................................................................................................9
3.5.
Single Parallel Island: SPI...............................................................................................................10
2.4.1 SPI Island only (=SPM) ...........................................................................................................10
2.4.2 SPI parallel to Mains only ........................................................................................................11
2.4.3 SPI External MCB / Island or Parallel......................................................................................12
3.
Multiple sets .............................................................................................................................................13
3.1.
Multiple Prime mover: MEXT, MINT ...............................................................................................13
3.1.1.
Multiple Prime mover - external Sync & LSM.........................................................................13
3.1.2.
Multiple Prime mover - internal Sync & LSM..........................................................................15
3.2.
Multiple Stand-by: MEXT, MINT......................................................................................................17
3.2.1.
Multiple Stand-by - external Sync & LSM...............................................................................17
3.2.2.
Multiple Stand-by - internal Sync & LSM................................................................................19
3.3.
Multiple Parallel to mains, Stand-by, no MCB synchronization: MEXT,MINT ................................21
3.3.1.
Multiple Parallel to mains, Stand-by, no MCB synchronization - external Sync & LSM.........21
3.3.2.
Multiple Parallel to mains, Stand-by, no MCB synchronization - internal Sync & LSM..........22
3.3.3.
Multiple Parallel to mains, Stand-by, no MCB synchronization internal Sync & LSM +
InteliMains24
3.4.
Multiple Parallel to mains, Stand-by, MCB synchronized: MEXT,MINT .........................................26
3.4.1.
Multiple Short time parallel to mains external Sync & LSM ................................................26
3.4.2.
Multiple Short time parallel to mains internal Sync & LSM .................................................28
3.4.3.
Multiple Short time parallel to mains internal Sync & LSM + InteliMains ............................30
3.4.4.
Multiple Parallel to mains, Import-Export or Baseload control, Stand-by external Sync &
LSM
32
3.4.5.
Multiple Parallel to mains, Import-Export or Baseload control, Stand-by internal Sync &
LSM
34
3.4.6.
Multiple Parallel to mains, Import-Export or Baseload control, Stand-by internal Sync &
LSM + InteliMains ....................................................................................................................................36
3.4.7.
Multiple Parallel to mains, Peak shaving, Import-Export or Baseload control, Stand-by
internal Sync & LSM + InteliMains...........................................................................................................38
3.4.8.
Multiple Parallel to mains, MGCB control from InteliMains ....................................................40
4.
Examples .................................................................................................................................................41
4.1.
Stand-by redundancy gen-sets .......................................................................................................41
4.2 SPM redundancy with ATS ....................................................................................................................42
4.3 Two phase genset connection ...............................................................................................................42
4.4 Bus-tie breaker (BTB) application ..........................................................................................................43
Specification.............................................................................................................................................43
5.
Speed governor interface ........................................................................................................................45
Electronic engines interface .........................................................................................................................45
InteliSys ECU interface............................................................................................................................45
InteliGen ECU interface ...........................................................................................................................45
Controller Speed reg out voltage limit..........................................................................................................45
Heinzmann E1-F and E2F............................................................................................................................45
Heinzmann E6..............................................................................................................................................46
Heinzmann E16............................................................................................................................................46
Application Guide, ComAp February 2005
IG-6.1.2-IS-3.3.1-Application Guide.pdf

Cummins ......................................................................................................................................................46
EFC..........................................................................................................................................................46
ECPG.......................................................................................................................................................47
ONAN.......................................................................................................................................................47
QST30......................................................................................................................................................48
Barber colman ..............................................................................................................................................48
DYNA 8000 ..............................................................................................................................................48
DYN1 10684 ............................................................................................................................................49
GAC..............................................................................................................................................................49
GAC ESD 5500 series .............................................................................................................................49
Woodward ....................................................................................................................................................50
ProAct II - Digital Speed Control System.................................................................................................50
EPG - Electrically Powered Governors....................................................................................................50
2301A Speed Controls.............................................................................................................................50
2301A Load Sharing and Speed control..................................................................................................51
Detroit diesel - DDEC3.................................................................................................................................51
Volvo Penta EDC III .....................................................................................................................................52
MTU MDEC 2000 , 4000..............................................................................................................................52
Caterpillar .....................................................................................................................................................52
Interface with EP300................................................................................................................................52
Interface without EP300...........................................................................................................................53
Deutz BF6M engine .....................................................................................................................................53
Perkins .........................................................................................................................................................53
Perkins 4016 E61 TRS ............................................................................................................................53
Perkins series 2300, 2800 .......................................................................................................................54
Perkins 1300 Series EDi..........................................................................................................................55
TOHO ...........................................................................................................................................................55
XS-400B-03 .............................................................................................................................................55
6.
AVR interface...........................................................................................................................................57
Basler ...........................................................................................................................................................57
Basler APR63-5, AEC 63-7, KR-FX, KR-FFX .........................................................................................57
Stamford.......................................................................................................................................................57
STAMFORD SX460 .................................................................................................................................57
STAMFORD SX440, SX 460, MX321, SX421.........................................................................................57
Leroy Sommer..............................................................................................................................................58
R438 LS, R448 ........................................................................................................................................58
R449 ........................................................................................................................................................58
RS128 ......................................................................................................................................................58
Mecc Alte Spa ..............................................................................................................................................59
S.R.7/2, U.V.R.6 ......................................................................................................................................59
Marelli AVR ..................................................................................................................................................59
MX341......................................................................................................................................................59
Piller .............................................................................................................................................................59
Caterpillar .....................................................................................................................................................60
VR6 ..........................................................................................................................................................60
DVR .........................................................................................................................................................60
7.
Abbreviations ...........................................................................................................................................61

Application Guide, ComAp February 2005


IG-6.1.2-IS-3.3.1-Application Guide.pdf

1. InteliGen, InteliSys applications


1.1.

Single set
No MCB

MCB Controlled

Load

GCB
controlled

MCB Synchronized

Load

Load

G
Single Stand-by
SSB

Single Prime Mover


SPM

Single Parallel to Mains


SPtM

Load

GCB
Synchronized

Load

G
Single Parallel Island
SPI

1.2.

G
Single Parallel to Mains
SPtM

Multiple sets
No MCB

No Parallel to
Mains

MCB Controlled

Load

MCB Synchronized

Loa

Multiple Prime mover:


MEXT, MINT

Multiple Stand-by: MEXT, MINT

Parallel to
Mains

Load

Loa

G
`

Multiple Parallel to mains,


Stand-by, MCB not
synchronized: MEXT,MINT

Application Guide, ComAp February 2005


IG-6.1.2-IS-3.3.1-Application Guide.pdf

Multiple Parallel to mains,


Stand-by, MCB synchronized:
MEXT,MINT

2. Single set
2.1.

Single Prime Mover: SPM


LOAD

GCB
3x

3xUG

G
3xIG

3x

iG-CU
or
iS-CU
REM START/STOP

GCB FEEDBACK
GCB

Specification

Automatic start-up and gen-set loading on external command

InteliGen hardware requirements


1x

IG-CU

InteliSys hardware requirements


1x

IS-CU

Software system configuration: Single Prime Mover (SPM)

Application Guide, ComAp February 2005


IG-6.1.2-IS-3.3.1-Application Guide.pdf

2.2.

Single Stand-by: SSB

2.2.1 Separate GCB and MCB


LOAD

3x

MCB

GCB
3x

3x

3x

MCB

GCB
GCB CLOSE/OPEN
MCB CLOSE/OPEN

BO

iG-CU
or
iS-CU

3xIG

K3

K4

3xUG

GCB

3xUM

MCB

BI

MCB FEEDBACK

MCB
GCB FEEDBACK
GCB

2.2.2 ATS
LOAD

3x

ATS
3x

3x

GCB

GCB CLOSE/OPEN
MCB CLOSE/OPEN

BO

iG-CU
or
iS-CU

3xIG

K3

3xUG

3xUM

3x

BI

MCB FEEDBACK
ATS on "G" position

GCB FEEDBACK

Specification

Automatic start-up when the mains fails


Reclosing after mains returns
On Load Test function see in chapter 3.4 - SPtM

InteliGen hardware requirements


1x
1x

IG-CU
IG-MTU (Optional - refer to controller user manual)

InteliSys hardware requirements


1x

IS-CU

Software system configuration: Single Stand-by (SSB)


Application Guide, ComAp February 2005
IG-6.1.2-IS-3.3.1-Application Guide.pdf

2.2.3 SSB + On Load Test


LOAD

3x

GCB
3x

3x

K3

MCB

GCB
CLOS E /OP E N

GCB

iG-CU
BO

M CB

3xI G

K
4

1x I M3

3x

3x U G

MCB

3x U M

CLOS E /OP E N

or

iS-CU +
BI

RE M OTE TE S T

ON LOA D TE S T
RE QUIRE D

TE S T ON LOA D

M CB FE E DB A CK

M CB
GCB FE E DB A CK

GCB

Specification

On Load Test - load transfer to genset with break (In TEST mode only)
Automatic start-up when the mains fails
Test mode
Break transfer

InteliGen hardware requirements


1x
1x

IG-CU
IG-MTU

(when mains and generator neutral separation is required)

InteliSys hardware requirements


1x

IS-CU

InteliSys central unit

Software system configuration: Single Parallel to Mains (SSB)

Application Guide, ComAp February 2005


IG-6.1.2-IS-3.3.1-Application Guide.pdf

2.3 Single Parallel to Mains: SPtM


2.3.1 Single short time parallel
LOAD

3x

GCB
3x

3x

K3

K4

G
iG-AVRi
TRANS
3xIG

3x

3xU G

MCB

3xU M

iG-AVRi

GCB
G CB CLO SE/O PEN
MCB CLO SE/O PEN

iG-CU

iG-PCM

MCB

or
BO

iS-CU+
iS-PCM

BI

AVRi

Vout

AVR

AVRi
O UT

SPEED
GOVERNOR

MCB FEEDBACK
MCB
G CB FEEDBACK
G CB

Specification

Automatic start-up when the mains fails


MCB full control
Short time parallel
Reverse power protection
Voltage matching (when is used AVRi)
Generator Base load and PF control
Soft transfer after mains returns
Test mode
Binary up, down outputs allows motorized potentiometer Sync/Load and Volt/PF control

InteliGen hardware requirements


1x
1x
1x
1x
1x
1x

IG-CU
IG-MTU
IG-PCM
IG-AVRi
IG-AVRi-TRANS
IG-MTU

(when mains and generator neutral separation is required)


(when volt matching and PF control is required)
(when IG-AVRi is used)
(Optional - refer to controller user manual)

InteliSys hardware requirements


1x
1x
1x
1x

IS-CU
IS-PCM
IG-AVRi
IG-AVRi-TRANS

InteliSys central unit


InteliSys Power Control Module DONGLE
(when volt matching and PF control is required)
(when IG-AVRi is used)

Software system configuration: Single Parallel to Mains (SPtM)

Application Guide, ComAp February 2005


IG-6.1.2-IS-3.3.1-Application Guide.pdf

2.3.2 SPtM + On Load Test


LOAD

3x

GCB
3x

3x

iG-AVRi
TRANS

3xIG

K3

K4

G
1xI M3

3x

3xUG

MCB

3xUM

MCB

GCB
GCB CLOSE/OPEN
MCB CLOSE/OPEN

BO

iG-CU
or
iS-CU +
iS-PCM

BI

iG-PCM

iG-AVRi
AVR
i

Vout

AVR

AVR
i
OUT

SPEED
GOVERNOR

REMOTE TEST

ON LOAD TEST
REQUIRED

TEST ON LOAD

REM START/STOP

PARALL. TO MAINS
REQUIRED

MCB FEEDBACK

MCB
GCB FEEDBACK

GCB

Specification

On Load Test - load transfer to genset (In TEST mode only)


Automatic start-up when the mains fails
Test mode
MCB full control
Reverse power protection
Voltage matching (when AVRi is connected)
Mains Import / Export load and PF control
Soft transfer after mains returns
Binary up, down outputs allows motorized potentiometer Sync/Load and Volt/PF control

InteliGen hardware requirements


1x
1x
1x
1x
1x
1x

IG-CU
IG-MTU
IG-PCM
IG-AVRi
IG-AVRi-TRANS
IG-MTU

(when mains and generator neutral separation is required)


(when volt matching and PF control is required)
(when IG-AVRi is used)
(Optional - refer to controller user manual)

InteliSys hardware requirements


1x
1x
1x
1x

IS-CU
IS-PCM
IG-AVRi
IG-AVRi-TRANS

InteliSys central unit


InteliSys Power Control Module DONGLE
(when volt matching and PF control is required)
(when IG-AVRi is used)

Software system configuration: Single Parallel to Mains (SPtM)


Hint:
On Load Test function is available in SSB as well.

Application Guide, ComAp February 2005


IG-6.1.2-IS-3.3.1-Application Guide.pdf

3.5. Single Parallel Island: SPI


2.4.1 SPI Island only (=SPM)
LOAD

3x

GCB
3x

3x

3xI G

K3

3xU G

3xU M

GCB
GCB CLOS E /OP E N

BO

iS-CU
BI

RE M S TA RT/S TOP

GCB FE E DB A CK
GCB

Specification:

No mains
Automatic start-up when Binary input REM START/STOP is closed
Closes GCB when generator voltage and frequency is within the limits
GCB is blocked when Mains voltage value > 15V.

InteliSys hardware requirements


1x

IS-CU

InteliSys central unit

Software system configuration: Single Parallel Island (SPI)

Application Guide, ComAp February 2005


IG-6.1.2-IS-3.3.1-Application Guide.pdf

10

2.4.2 SPI parallel to Mains only


LOAD

GCB

3x

3x

3x

3x

G
iG-AVRi
TRANS
3xIG

3xUG

3xUM

K3

1xIM

Im3

AVR
iG-AVRi

GCB
GCB CLOSE/OPEN

iS- CU+
iS- PCM

B
O

BI

AVR
i

Vou
t

AVRi
OUT

SPEED
GOVERNOR

REM START/STOP

MCB FEEDBACK
GCB FEEDBACK

GCB

Specification

Parallel only, no MCB


Binary input MCB feedback permanently closed
Automatic stop when long Blackout
Automatic GCB synchronizing when short Blackout
Reverse power protection
Voltage matching (when AVRi is connected)
Mains Import / Export load and PF control or Baseload and Base PF control
Binary up, down outputs allows motorized potentiometer Sync/Load and Volt/PF control
GCB opens if mains fail is detected in AUT mode
GCB synchronizes again, when mains returns

InteliSys hardware requirements


1x
1x
1x
1x

IS-CU
IS-PCM Dongle
IG-AVRi
IG-AVRi-TRANS

InteliSys central unit


InteliSys Power Control Module
(when volt matching and PF control is required)
(when IG-AVRi is used)

Software system configuration: Single Parallel Island (SPI)


Hint:
BusMeasureError is detected when MCB feedback is active and Mains voltage is out of range (fix delay 20
sec) in standard applications. This Error detection is blocked in IS-SPI application from IS firmware of
version 2.7.

Application Guide, ComAp February 2005


IG-6.1.2-IS-3.3.1-Application Guide.pdf

11

2.4.3 SPI External MCB / Island or Parallel


LOAD

3x

GCB
3x

3x

K3

iG-AVRi
TRANS
3xIG

3x

3xUG

MCB

3xUM

iG-AVRi

MCB
External MCB control

GCB
GCB CLOSE/OPEN

BO

iS-CU
iS-PCM
BI

AVR
i

Vout

AVR
i

AVR

OUT

SPEED
GOVERNOR

REM START/STOP

MCB FEEDBACK

MCB
GCB FEEDBACK

GCB

Specification

No MCB control, MCB is controlled externally


Automatic GCB control when Blackout
Reverse power protection
Voltage matching (when AVRi is connected)
Mains Import / Export load and PF control or genset Baseload and Base PF control
Soft transfer after mains returns
Binary up, down outputs allows motorized potentiometer Sync/Load and Volt/PF control

InteliSys hardware requirements


1x
1x
1x
1x
1x

IS-CU
IS-PCM
IG-AVRi
IG-AVRi-TRANS
NPU

InteliSys central unit


InteliSys Power Control Module DONGLE
(when volt matching and PF control is required)
(when IG-AVRi is used)
(when Vector surge protection is required)

Software system configuration: Single Parallel Island (SPI)

Application Guide, ComAp February 2005


IG-6.1.2-IS-3.3.1-Application Guide.pdf

12

3. Multiple sets
3.1.

Multiple Prime mover: MEXT, MINT

3.1.1. Multiple Prime mover - external Sync & LSM


LOAD

GCB1
3x

iG-CU
SYNC

LOAD SHARING
LINE

LSM

iG-COM

SYN

CAN

3xIG

3xU B

G1
3xU G

3x

UNLO AD

SYS START/STOP
M ASTER SELECT

GCB2
M ASTER SELECTO R

3x

LSM

iG-COM

iG_CU
SYNC

CAN

3xIG

3xU B

SYN

3xU G

G2

UNLO AD

SYS START/STOP
M ASTER SELECT

START/STO P

LOAD

MGCB

GCB1
3x

G1

MGCB

iG-CU
SYNC

LO AD SHARING
LINE

LSM

iG-COM

SYN

CAN
3xIG

3xU B

RES.O K.(2)

MG CB

RES.O K.(1)

3x

3xU G

3x

UNLOAD

SYS START/STO P
M ASTER SELECT
LO AD RESERVE 2

GCB2
3x

G2

iG_CU
SYNC

START/STO P

iG-COM

SYN

CAN
3xIG

3x

3xU B

M ASTER SELECTO R

3xU G

MG CB

LSM

UNLOAD

SYS START/STO P
M ASTER SELECT
LO AD RESERVE 2

Specification
Application Guide, ComAp February 2005
IG-6.1.2-IS-3.3.1-Application Guide.pdf

13

MGCB support
Gen-sets soft unload in island parallel (if the function is available in external LSM)
Pwr management (if IG-COMs are installed)

InteliGen hardware requirements


nx
nx
nx
nx
nx
1x

IG-CU
IG-COM
(Optional)
External Synchronizer
External Load sharing module with soft unload function (if needed)
IG-MTU
(Optional - refer to controller user manual)
IG-MU or IG-IB
(Optional - for connection to local or remote PC)

Hint:
IG-COM is necessary for Power management function and for Reactive power sharing (when no Droop AVR
are used).

Software system configuration: Multiple External (MEXT)


Description without MGCB
1) Start/Stop switch starts engines in Pwr management mode by closing of SYS START/STOP input.
2) MASTER SELECT selects the gen-set priority regardless of the Priority setpoint, if needed.

Description with MGCB


1) Start/Stop switch starts engines in Pwr management mode by closing of SYS START/STOP input.
2) LOAD RESERVE 2 is controlled by MGCB, to differentiate the load reserve necessary before closing of
MGCB (setpoints LoadRes Strt 2 and LoadRes Stp 2), and load reserve while system is loaded
(setpoints LoadRes Strt 1 and LoadRes Stp 1).
3) MGCB is closed by LOAD RES OK of 1st or 2nd gen-set and then held by MGCB feedback. Loss of
voltage at the bus opens MGCB.
4) MASTER SELECT selects the gen-set priority regardless of the Priority setpoint, if needed.
Hints
Set SysAMFstrt del and SysAMFstp del setpoints at 1s for fast response
Input MCB FEEDBACK should not be configured.

Application Guide, ComAp February 2005


IG-6.1.2-IS-3.3.1-Application Guide.pdf

14

3.1.2. Multiple Prime mover - internal Sync & LSM


LOAD

GCB1

3x

3x

G1

or

iS-CU+
iS-PCLSM -PM S

iG-COM

iG-CU

iG-AVRi
iG-PCLSM

3xU G

CAN

3xIG

3xU B

iG-AVRi
TRANS
AVR

O UT

AVRi

AVRi

SPEED
GOVERNOR

Vout
LSM

SYS START/STO P
MASTER SELECT

LO AD SHARING LINE

GCB2

3x

G2

MASTER SELECTO R

3xIG

or

iS-CU+
iS-PCLSM -PM S

iG-COM

iG-CU

iG-AVRi
iG-PCLSM

3xU B

3xU G

iG-AVRi
TRANS
CAN

AVRi

Vout
LSM

AVR

O UT
AVRi

SPEED
GOVERNOR

SYS START/STO P
MASTER SELECT

START/STO P

LOAD

MGCB

GCB1

3x

G1
iG -AVRi
TRANS
CAN

3xIG

iG-CU
or

iS-CU+
iS-PCLSM -PM S

iG-COM

iG-AVRi
iG-PCLSM

3xU B

MGCB

3xU G

RES.O K.(2)

3x

RES.O K.(1)

MG CB

3x

AVRi

Vout
LSM

SYS START/STOP
MASTER SELECT

AVR i

AVR

O UT

SPEED
GOVERNOR
LOAD SHARING LINE

LOAD RESERVE 2
3x

MG CB

GCB2

3x

G2

MASTER SELECTOR

iG-COM

or

iS-CU+
iS-PCLSM -PM S

iG-AVRi
iG-PCLSM

iG-CU

START/STOP

CAN

3xIG

3xU G

3xU B

iG -AVRi
TRANS

AVRi

Vout
LSM

AVR i

AVR

O UT

SPEED
GOVERNOR

SYS START/STOP
MASTER SELECT
LOAD RESERVE 2

Application Guide, ComAp February 2005


IG-6.1.2-IS-3.3.1-Application Guide.pdf

15

Specification

MGCB support
Gen-sets unload in island parallel
Pwr management (if IG-COMs are installed)

InteliGen hardware requirements


nx
IG-CU
nx
IG-COM
(Optional)
nx
IG-PCLSM
nx
IG-AVRi, IG-AVRi-TRANS
(Optional)
nx
IG-MTU
(Optional - refer to controller user manual)
1x
IG-MU or IG-IB
(Optional - for connection to local or remote PC)
Hint:
IG-COM is necessary for Power management function and for Reactive power sharing (when no Droop AVR
are used).

InteliSys hardware requirements


nx
nx
nx
nx

IS-CU
IS-PCLSM-PMS Dongle
IS-PCLSM Dongle
IG-AVRi, IG-AVRi-TRANS

(Optional)
(Optional - without Power management)
(Optional)

Software system configuration: Multiple Internal (MINT)


Description without MGCB
1) Start/Stop switch starts engines in Pwr management mode by closing of SYS START/STOP input.
2) MASTER SELECT selects the gen-set priority regardless of the Priority setpoint, if needed.

Description with MGCB


1) Start/Stop switch starts engines in Pwr management mode by closing of SYS START/STOP input.
2) LOAD RESERVE 2 is controlled by MGCB, to differentiate the load reserve necessary before closing of
MGCB (setpoints LoadRes Strt 2 and LoadRes Stp 2), and load reserve while system is loaded
(setpoints LoadRes Strt 1 and LoadRes Stp 1).
3) MGCB is closed by LOAD RES OK of 1st or 2nd gen-set and then held by MGCB feedback. Loss of
voltage at the bus opens MGCB.
4) MASTER SELECT selects the gen-set priority regardless of the Priority setpoint, if needed.
Hints
Set SysAMFstrt del and SysAMFstp del setpoints at 1s for fast response
Input MCB FEEDBACK should not be configured

Application Guide, ComAp February 2005


IG-6.1.2-IS-3.3.1-Application Guide.pdf

16

3.2.

Multiple Stand-by: MEXT, MINT

3.2.1. Multiple Stand-by - external Sync & LSM


Application is supported by InteliGen only.
LOAD
U,f
3x

GCB1

3x

3x

3x

3xU

3x

U,f

G1
CAN
LOAD SHARING
LINE

3xIG

MCB

3x

3xU G

(3.PH.RELAY)

iG-CU

SYN

MCB
M CB

SYNC

LSM

iG-COM

KA
KA

UNLO AD

SYS START/STO P
M ASTER SELECT

GCB2
M ASTER SELECTO R

3x

CAN
3xIG

3xU G

3xU B

G2

SYNC

LSM

iG-COM

iG-CU

SYN

UNLO AD

SYS START/STO P
M ASTER SELECT

U,f

LOAD
U,f

MGCB

GCB1

MGCB

iG-CU

SYN

MCB

M G CB

MCB

G1

SYNC

CAN
LOAD SHARING
LINE

LSM

iG-COM

RES.O K.(2)

MG CB

U,f

3x

3xIG

3x

3x

3xU G

3x

MCB

3xU B

3x
3x

RES.O K.(1)

UNLO AD

SYS START/STO P
M ASTER SELECT
LO AD RESERVE 2

GCB2
3x

G2
3xIG

iG-CU

SYN
SYNC

U,f

CAN

iG-COM

3x

3xU B

M ASTER SELECTO R

3xU G

MG CB

LSM

UNLO AD

SYS START/STO P
M ASTER SELECT
LO AD RESERVE 2

Application Guide, ComAp February 2005


IG-6.1.2-IS-3.3.1-Application Guide.pdf

17

Specification

Automatic start-up when the mains fails


Reclosing MCB after mains returns
MGCB support
Gen-sets soft unload in island parallel (if the function is available in external LSM)
Pwr management (if IG-COMs are installed)

InteliGen hardware requirements


1x
Uf relay (Mains decoupling relay) unit + MCB control
nx
IG-CU
nx
IG-COM
(Optional)
nx
External Synchronizer
nx
External Load sharing module with soft unload function (if needed)
nx
IG-MTU
(Optional - refer to controller user manual)
1x
IG-MU or IG-IB
(Optional - for connection to local or remote PC)
Hint:
IG-COM is necessary for Power management function and for Reactive power sharing (when no Droop AVR
are used).

Software system configuration: Multiple External (MEXT)


Description without MGCB
1) The Uf relay opens MCB after the mains fails. At the same time the Uf relay starts Pwr
management by closing of SYS START/STOP input
2) When mains returns, Uf relay opens SYS START/STOP and GCBs are opened.
3) Bus 3 phase voltage relay detects no voltage and with its time delay closes MCB
4) MASTER SELECT selects the gen-set priority regardless of the Priority setpoint, if needed.

Description with MGCB


1) The Uf relay opens MCB after the mains fails. At the same time the Uf relay starts Pwr
management by closing of SYS START/STOP input.
2) LOAD RESERVE 2 is controlled by MGCB, to differentiate the load reserve necessary before closing of
MGCB (setpoints LoadRes Strt 2 and LoadRes Stp 2), and load reserve while system is loaded
(setpoints LoadRes Strt 1 and LoadRes Stp 1).
3) MGCB is closed by LOAD RES OK of 1st or 2nd gen-set and then held by MGCB feedback.
4) When the mains returns, Uf relay opens SYS START/STOP. Loss of voltage at the bus opens MGCB.
5) Bus 3-phase voltage relay detects no voltage and with its time, delay closes MCB.
6) MASTER SELECT selects the gen-set priority regardless of the Priority setpoint, if needed.
Hints
Setpoint SysAMFstrt del is used for engines start delay after the mains fails. It is similar to setpoint
EmergStart del in Single Stand-by.
Setpoint SysAMFstp del is used for GCB opening after the mains returns. It is similar to setpoint Mains Ret
del in Single Stand-by.
Input MCB FEEDBACK should not be configured.

Application Guide, ComAp February 2005


IG-6.1.2-IS-3.3.1-Application Guide.pdf

18

3.2.2. Multiple Stand-by - internal Sync & LSM


LOAD

U,f

MCB

3x

GCB1

3x

3x

3x

3x

G1

3x

iG-AVRi
TRANS
KA

CAN

3xIG

3xU B

(3.PH.RELAY)

3xU G

U,f

iG-AVRi

iG-CU
or

iS-CU+
iS-PCLSM -PM S

iG-COM

MCB
MCB

iG-PCLSM

KA
AVRi

O UT

SPEED
GOVERNOR

Vout

LSM

SYS START/STO P
MASTER SELECT

AVR

AVRi

LOAD SHARING LINE

GCB2

3x

G2

MASTER SELECTO R

3xIG

3xU G

3xU B

iG-AVRi
TRANS
CAN

or

iS-CU+
iS-PCLSM -PM S

AVRi

AVRi

LSM

AVR

O UT

SPEED
GOVERNOR

Vout

SYS START/STO P
MASTER SELECT

U,f

LOAD

MCB

MGCB

3x

3x

GCB1

3x

G1
iG -AVRi
TRANS

MGCB

3xU B

RES.O K.(2)

MG CB

U,f

RES.O K.(1)

3x

CAN

3xIG

3x
3x

3xU G

U,f

iG-COM

iG-CU

iG-PCLSM

iG-AVRi

iG -AVRi
or

iS-CU+
iS-PCLSM -PM S

iG-COM

iG-CU

MCB

MCB

iG-PCLSM

M G CB
AVRi

Vout
LSM

SYS START/STO P
MASTER SELECT

AVR

AVRi
O UT

SPEED
GO VERNOR

LO AD SHARING LINE

LO AD RESERVE 2
3x

MG CB

GCB2

3x

G2

M ASTER SELECTO R

3xIG

3xU G

3xU B

iG -AVRi
TRANS
CAN

or

U,f

iG-COM

iG-CU
iS-CU+
iS-PCLSM -PM S

iG-PCLSM

iG -AVRi
AVRi

LSM

AVR

AVRi
O UT

Vout

SPEED
GO VERNOR

SYS START/STO P
MASTER SELECT
LO AD RESERVE 2

Application Guide, ComAp February 2005


IG-6.1.2-IS-3.3.1-Application Guide.pdf

19

Specification

Automatic start-up when the mains fails


Reclosing MCB after mains returns
MGCB support
Gen-sets unload in island parallel
Pwr management (if IG-COMs are installed)

InteliGen hardware requirements


1x
Uf relay (Mains decoupling relay) unit + MCB control
nx
IG-CU
nx
IG-COM
(Optional)
nx
IG-PCLSM
nx
IG-AVRi, IG-AVRi-TRANS
(Optional)
nx
IG-MTU
(Optional - refer to controller user manual)
1x
IG-MU or IG-IB
(Optional - for connection to local or remote PC)
Hint:
IG-COM is necessary for Power management function and for Reactive power sharing (when no Droop AVR
are used).

InteliSys hardware requirements


1x
nx
nx
nx
nx
1x

Uf relay (Mains decoupling relay) unit + MCB control


IS-CU
IS-PCLSM -PMS Dongle
(Optional)
IS-PCLSM Dongle
(Optional - without Power management)
IG-AVRi, IG-AVRi-TRANS
(Optional)
IG-MU or IG-IB
(Optional - for connection to local or remote PC)

Software system configuration: Multiple Internal (MINT)


Description without MGCB
1) The Uf relay opens MCB after the mains fails. At the same time the Uf relay starts Pwr
management by closing of SYS START/STOP input
2) When mains returns, Uf relay opens SYS START/STOP and GCBs are opened.
3) Bus 3 phase voltage relay detects no voltage and with its time delay closes MCB
4) MASTER SELECT selects the gen-set priority regardless of the Priority setpoint, if needed.

Description with MGCB


1) The Uf relay opens MCB after the mains fails. At the same time the Uf relay starts Pwr
management by closing of SYS START/STOP input.
2) LOAD RESERVE 2 is controlled by MGCB, to differentiate the load reserve necessary before closing of
MGCB (setpoints LoadRes Strt 2 and LoadRes Stp 2), and load reserve when system is loaded
(setpoints LoadRes Strt 1 and LoadRes Stp 1).
3) MGCB is closed by LOAD RES OK of 1st or 2nd gen-set and then held by MGCB feedback.
4) When the mains return, Uf relay opens SYS START/STOP. Loss of voltage at the bus opens MGCB.
5) Bus 3-phase voltage relay detects no voltage and with its time delay closes MCB.
6) MASTER SELECT selects the gen-set priority regardless of the Priority setpoint, if needed.
Hint:
Setpoint SysAMFstrt del is used for engines start delay after the mains fails. It is similar to setpoint
EmergStart del in Single Stand-by.
Setpoint SysAMFstp del is used for GCB opening after the mains returns. It is similar to setpoint Mains Ret
del in Single Stand-by.
Input MCB FEEDBACK should not be configured.

Application Guide, ComAp February 2005


IG-6.1.2-IS-3.3.1-Application Guide.pdf

20

3.3.

Multiple Parallel to mains, Stand-by, no MCB synchronization:


MEXT,MINT

3.3.1. Multiple Parallel to mains, Stand-by, no MCB synchronization external Sync & LSM
Application is supported by InteliGen only.
LSM
MAINS

LOAD SHARING
LINE

LOAD
U,f
3x

GCB1
3x

3x

3x

3xU B

3x

U,f

G1
CAN

3xIG

MCB

3x

3xU G

LO AD SHARING
LINE

(3.PH.RELAY)

iG-CU

SYN

KA

MCB
M CB

SYNC

LSM

iG-COM

KA

UNLO AD

SYS START/STO P
M ASTER SELECT
M CB FEEDBACK

GCB2
M ASTER SELECTO R

3x

SYNC

M CB
U,f

3xIG

iG-CU

SYN

CAN

iG-COM

PARALL.
TO M AINS
REQ UIRED

3xU G

3xU B

G2

LSM

UNLO AD

SYS START/STO P
M ASTER SELECT
M CB FEEDBACK

M CB

Specification

Synchronize gen-sets to mains


Import-Export or Base load power control
Automatic start-up when the mains fails
After mains returns GCBs opening, reclosing MCB and synchronizing gen-sets to mains
Gen-sets soft unload (if the function is available in external LSM)
Pwr management (if IG-COMs are installed)

InteliGen hardware requirements

1x

Uf relay unit (Mains decoupling relay) + MCB control


External Mains Load sharing module for Import-Export power control or Base load power control on
local Load sharing modules
NPU
(when Vector shift protection is required)

nx
nx
nx
nx
nx
1x

IG-CU
IG-COM (Optional)
External Synchronizer
External Load sharing module with soft unload function (if needed)
IG-MTU
(Optional - refer to controller user manual)
IG-MU or IG-IB
(Optional - for connection to local or remote PC)

1x
1x

Application Guide, ComAp February 2005


IG-6.1.2-IS-3.3.1-Application Guide.pdf

21

Hint:
IG-COM is necessary for Power management function and for Reactive power sharing (when no Droop AVR
are used).

Software system configuration: Multiple External (MEXT)


Description
1) The system is started by the Uf relay or by the switch Parallel to mains required.
2) The Uf relay opens MCB after the mains fails. At the same time the Uf relay starts Pwr
management by closing of SYS START/STOP input, if the gen-sets had not run in parallel to mains
before.
3) When the mains returns, Uf relay opens SYS START/STOP, and GCBs are opened.
4) Bus 3 phase voltage relay KA detects no voltage and with its time delay closes MCB
5) If the switch Parallel to mains required is closed, gen-sets are again synchronized to the bus.
6) To stop the gen-sets while running in parallel to mains open the switch Parallel to mains required.
7) While stopping in parallel to mains, active MCB FEEDBACK ensures gen-sets soft unload (if the function
is available in external LSM)
8) MASTER SELECT selects the gen-set priority regardless of the Priority setpoint, if needed.
Hints
Setpoint SysAMFstrt del is used for engines start delay after the mains fails. It is similar to setpoint
EmergStart del in Single Stand-by. If the input MCB FEEDBACK is active, the delay is 1s.
Setpoint SysAMFstp del is used for GCB opening after the mains returns. It is similar to setpoint Mains Ret
del in Single Stand-by. If the input MCB FEEDBACK is active, the delay for unloading is 1s.

3.3.2. Multiple Parallel to mains, Stand-by, no MCB synchronization - internal


Sync & LSM

LSM
MAINS

LOAD SHARING
LINE

LOAD
U,f

MCB

3x
3x

3x

GCB1

G1

3x

U,f

iG-AVRi
TRANS
3xU B

(3.PH.RELAY)

KA

CAN

3xIG

3x

3xU G

iG-AVRi

iG-CU
or

iS-CU+
iS-PCLSM -PM S

iG-PCLSM

MCB
MCB

iG-COM

KA

O UT

SPEED
GOVERNOR

Vout
LSM

SYS START/STOP
MASTER SELECT
MCB FEEDBACK

GCB2

AVRi

AVRi

AVR

LOAD SHARING LINE


3x

G2

MASTER SELECTO R

3xIG

3xU G

3xU B

iG-AVRi
TRANS
CAN

or

iS-CU+
iS-PCLSM -PM S

MCB
U,f

iG-PCLSM

iG-CU

PARALL.
TO MAINS
REQ UIRED

iG-COM

iG-AVRi
AVRi

Vout
LSM

AVR

AVRi
O UT

SPEED
GOVERNOR

SYS START/STOP
MASTER SELECT
MCB FEEDBACK

MCB

Application Guide, ComAp February 2005


IG-6.1.2-IS-3.3.1-Application Guide.pdf

22

Specification

Synchronize gen-sets to mains


Import-Export or Base load power control
Automatic start-up when the mains fails
After mains returns GCBs opening, reclosing MCB and synchronizing gen-sets to mains
Gen-sets unload
Pwr management (if IG-COMs are installed)

InteliGen hardware requirements


1x
1x
1x
nx
nx
nx
nx
nx
1x

Uf relay unit (Mains decoupling relay) + MCB control


External Mains Load sharing module for Import-Export power control or Base load power control on
local Load sharing modules
NPU
(when Vector shift protection is required)
IG-CU
IG-COM
(Optional)
IG-PCLSM
IG-AVRi, IG-AVRi-TRANS
(Optional)
IG-MTU
(Optional - refer to controller user manual)
IG-MU or IG-IB
(Optional - for connection to local or remote PC)

Hint:
IG-COM is necessary for Power management function and for Reactive power sharing (when no Droop AVR
are used).

InteliSys hardware requirements


1x
1x
nx
nx
nx
nx
1x
1x

Uf relay (Mains decoupling relay) unit + MCB control


External Mains Load sharing module for Import-Export power control or Base load power control on
local Load sharing modules
IS-CU
IS-PCLSM-PMS Dongle
(Optional)
IS-PCLSM Dongle
((Optional - without Power management))
IG-AVRi, IG-AVRi-TRANS
(Optional)
NPU
(when Vector shift protection is required)
IG-MU or IG-IB
(Optional - for connection to local or remote PC)

Software system configuration: Multiple Internal (MINT)


Description
1) The system is started by the Uf relay or by the switch Parallel to mains required.
2) The Uf relay opens MCB after the mains fails. At the same time the Uf relay starts Pwr
management by closing of SYS START/STOP input, if the gen-sets had not run in parallel to mains
before.
3) When the mains returns, Uf relay opens SYS START/STOP, and GCBs are opened.
4) Bus 3 phase voltage relay KA detects no voltage and with its time delay closes MCB.
5) If the switch Parallel to mains required is closed, gen-sets are again synchronized to the bus.
6) To stop the gen-sets while running in parallel to mains open the switch Parallel to mains required.
7) While stopping in parallel to mains, active MCB FEEDBACK ensures gen-sets soft unload
8) MASTER SELECT selects the gen-set priority regardless of the Priority setpoint, if needed.
Hints
Setpoint SysAMFstrt del is used for engines start delay after the mains fails. It is similar to setpoint
EmergStart del in Single Stand-by. If the input MCB FEEDBACK is active, the delay is 1s.
Setpoint SysAMFstp del is used for GCB opening after the mains returns. It is similar to setpoint Mains Ret
del in Single Stand-by. If the input MCB FEEDBACK is active, the delay for unloading is 1s.

Application Guide, ComAp February 2005


IG-6.1.2-IS-3.3.1-Application Guide.pdf

23

3.3.3. Multiple Parallel to mains, Stand-by, no MCB synchronization


internal Sync & LSM + InteliMains

+24V

SYNC
DISABLE

MCB
FEEDBACK

0V

3xU B

iM-CU

3xIM

MAINS FAIL

3xU M

MCB
CLOSE/O PEN

Ko2

iG-COM

Ko1

LOAD
CAN

MCB

CAN
3x

3x

3x

GCB1

G1

3xI G

iG-CU
or

iS-CU+
iS-PCLSM -PM S

iG -AVRi
iG -PCLSM

MCB

CAN

iG-COM

3xU B

Ko1

3xU G

iG-AVRi
TRANS
AVR

O UT

SPEED
GOVERNOR

Vout
LSM

SYS START/STOP
MASTER SELECT
MCB FEEDBACK

GCB2

AVRi

AVRi

LO AD SHARING LINE
3x

G2

MASTER SELECTOR

3xIG

iS-CU+
iS-PCLSM -PM S

MCB

iG-PCLSM

or

iG-AVRi
iG-CO M

iG-CU

PARALL.
TO M AINS
REQ UIRED
Ko2

3xU G

3xU B

iG-AVRi
TRANS
CAN

AVRi

Vout
LSM

AVRi

AVR

OUT

SPEED
GOVERNOR

SYS START/STO P
MASTER SELECT
MCB FEEDBACK

MCB

Application Guide, ComAp February 2005


IG-6.1.2-IS-3.3.1-Application Guide.pdf

24

Specification

Synchronize gen-sets to mains


Import-Export or Base load power control
Automatic start-up when mains fails
After mains returns GCBs opening (BI SYNC DISABLE is closed), reclosing MCB and synchronizing
gen-sets to mains
Gen-sets unload
Pwr management (if IG-COMs are installed)

InteliGen hardware requirements


1x
IM-CU
(Vector shift protection from version 5.1)
1x
IG-COM
(Optional)
nx
IG-CU
nx
IG-COM
(Optional)
nx
IG-PCLSM
nx
IG-AVRi, IG-AVRi-TRANS
(Optional)
nx
IG-MTU
(Optional - refer to controller user manual)
1x
IG-MU or IG-IB
(Optional - for connection to local or remote PC)
Hint:
IG-COM is necessary for Power management function and for Reactive power sharing (when no Droop AVR
are used).

InteliSys hardware requirements


1x
1x
nx
nx
nx
nx
1x

IM-CU
(Vector shift protection from version 5.1)
IG-COM (Optional)
IS-CU
IS-PCLSM-PMS Dongle
(Optional)
IS-PCLSM Dongle
((Optional - without Power management))
IG-AVRi, IG-AVRi-TRANS
(Optional)
IG-MU or IG-IB
(Optional - for connection to local or remote PC)

Software system configuration: IM + Multiple Internal (MINT)


Description
1) InteliMains opens MCB after the mains fails.
2) At the same time the IM binary output MAINS FAIL starts Pwr management by closing of SYS
START/STOP input, if the gen-sets had not run before.
3) When the mains returns, SYS START/STOP input opens and then GCBs opens.
4) InteliMains detects no voltage and with its time delay MCB close del closes MCB.
5) If the switch Parallel to mains required is closed, gen-sets are again synchronized to the bus.
6) To stop the gen-sets while running in parallel to mains open the switch Parallel to mains required.
7) While stopping in parallel to mains, active MCB FEEDBACK ensures gen-sets soft unload
8) MASTER SELECT selects the gen-set priority regardless of the Priority setpoint, if needed.
Hints
Setpoint SysAMFstrt del is used for engines start delay after the mains fails. It is similar to setpoint
EmergStart del in Single Stand-by.
After MCB closing, the delay for gen-sets unloading is 1s (MCB FEEDBACK is closed).
Setpoint SysAMFstp del is not used in this case.

Application Guide, ComAp February 2005


IG-6.1.2-IS-3.3.1-Application Guide.pdf

25

3.4.

Multiple Parallel to mains, Stand-by, MCB synchronized:


MEXT,MINT

3.4.1. Multiple Short time parallel to mains external Sync & LSM
Application is supported by InteliGen only.
LOAD
U,f
3x

3x

GCB1

3x

3x

3xU B

3x

U,f

G1
3xU G

MCB

3x

CAN

3xIG

LOAD SHARING
LINE

KA

iG-CU

MCB
M CB

SYNC

UNLO AD

SYS START/STO P

Kt

EX T.SYN

LSM

iG-COM

SYN

(3.PH.RELAY)

KA

MASTER SELECT
MCB FEEDBACK

GCB2

M ASTER SELECTO R

G2
3xU B

M CB
SYN.ENABLED

iG-CU
SYNC

LSM

iG-COM

SYN

CAN
3xIG

EX T.
SYN

3x

Kt
3xU G

KA

UNLO AD

SYS START/STO P
MASTER SELECT

M CB

MCB FEEDBACK
MCB

LOAD

U,f

MCB

3x

3x

MGCB
3x

3x

GCB1

3x

G1

M CB
Kt

EX T.SYN

MGCB

M ASTER SELECTO R

UNLO AD

3x

LO AD RESERVE 2
MCB FEEDBACK

GCB2

3x

G2

iG-CU
SYNCH

iG-COM

SYN

CAN

3xIG

M CB
SYN.ENABLED

3xU G

Kt

3xU B

EX T.
SYN

LSM

SYS START/STO P
MASTER SELECT
MG CB

KA

iG-CU

KC
SYNCH

CAN
LOAD SHARING
LINE

iG-COM

G CB2

G CB1

SYN
M G CB

MCB

RES.O K(2)

KA

RES.O K(1)

KC

KA

3xIG

3xU B

(3.PH.RELAY)

U,f

3xU G

3x

LSM

UNLO AD

SYS START/STO P
M CB

MASTER SELECT
LO AD RESERVE 2
MCB FEEDBACK

MCB

Application Guide, ComAp February 2005


IG-6.1.2-IS-3.3.1-Application Guide.pdf

26

Specification

Automatic start-up when mains fails


After mains returns MCB synchronizing
Engines unload (if the function is available)
One interrupt only stand-by
MGCB support
Gen-sets soft unload (if the function is available in external LSM)
Pwr management (if IG-COMs are installed)

InteliGen hardware requirements


1x
Uf relay unit (Mains decoupling relay) + MCB control
1x
External MCB Synchronzier
1x
NPU (when Vector shift protection is required)
nx
IG-CU
nx
IG-COM (Optional)
nx
External Synchronizer
nx
External Load sharing module with soft unload function (if needed)
nx
IG-MTU
(Optional - refer to controller user manual)
1x
IG-MU or IG-IB
(Optional - for connection to local or remote PC)
Hint:
IG-COM is necessary for Power management function and for Reactive power sharing (when no Droop AVR
are used).

Software system configuration: Multiple External (MEXT)


Description without MGCB
1) The Uf relay opens MCB after the mains fails. At the same time the Uf relay starts Pwr
management by closing of SYS START/STOP input.
2) When the mains returns, external synchronizer synchronizes gen-sets to the mains.
3) Closing of MCB stops the gen-sets by opening of SYS START/STOP.
4) If gen-sets are to be softly unloaded while stopping in parallel to mains, active MCB FEEDBACK ensures
that.
5) MASTER SELECT selects the gen-set priority regardless of the Priority setpoint, if needed.

Description with MGCB


1) The Uf relay opens MCB after the mains fails. At the same time the Uf relay starts Pwr
management by closing of SYS START/STOP input.
2) LOAD RESERVE 2 is controlled by MGCB, to differentiate the load reserve necessary before closing
of MGCB (setpoints LoadRes Strt 2 and LoadRes Stp 2), and load reserve while system is loaded
(setpoints LoadRes Strt 1 and LoadRes Stp 1).
3) MGCB is closed by LOAD RES OK of 1st or 2nd gen-set and then held by MGCB feedback.
4) When the mains returns, external synchronizer synchronizes gen-sets to the mains.
5) Closing of MCB stops the gen-sets by opening of SYS START/STOP. Both GCBs are opened and
consequently KC relay opens MGCB.
6) While stopping in parallel to mains, active MCB FEEDBACK ensures gen-sets soft unload (if the
function is available in external LSM).
7) MASTER SELECT selects the gen-set priority regardless of the Priority setpoint, if needed.
8) When the gensets are not ready for standby operation after the mains return the bus 3 phase voltage
relay KA detects no voltage and with its time delay closes MCB.
Hints
Setpoint SysAMFstrt del is used for engines start delay after the mains fails. It is similar to setpoint
EmergStart del in Single Stand-by.
Time relay Kt is used for beginning of MCB synchronization after the mains returns. It is similar to setpoint
Mains Ret del in Single Parallel to Mains (SPtM) application.
After MCB closing, the delay for gen-sets unloading is 1s (MCB FEEDBACK is closed).
Setpoint SysAMFstp del is not used in this case.

Application Guide, ComAp February 2005


IG-6.1.2-IS-3.3.1-Application Guide.pdf

27

3.4.2. Multiple Short time parallel to mains internal Sync & LSM
LOAD

U,f

MCB

3x

GCB1

3x

3x

3x

3x

G1
iG-AVRi
TRANS
3xU G

KA

CAN

3xIG

3xU B

3x

U,f

iG-AVRi

MCB

iG-CU
or

MCB

iS-CU+
iS-PCLSM -PM S

Kt

EXT .SYN

iG-COM

KA

iG-PCLSM

(3.PH.RELAY)
AVRi

Vout

LSM

SYS START/STO P
MASTER SELECT

AVRi

AVR

O UT

SPEED
GOVERNOR
LO AD SHARING LINE

MCB FEEDBACK

GCB2

MASTER SELECTO R

iG-AVRi
TRANS
CAN

or

iS-CU+
iS-PCLSM -PM S

AVR

iG-AVRi
iG-COM

iG-CU

iG-PCLSM

3xU B

MCB
SYN.ENABLED

3xIG

EXT .
SYN

G2

Kt
3xU G

KA

3x

AVRi

Vout
LSM

AVRi

O UT

SPEED
GOVERNOR

SYS START/STO P
MASTER SELECT

M CB

MCB FEEDBACK
MCB

LOAD
U,f

MCB

3x

MGCB

3x

3x

3x

GCB1

3x

G1

3x

iG-AVRi
TRANS

(3.PH.RELAY)

U,f

3xIG

or

iS-CU+
iS-PCLSM -PM S

MGCB

iG-AVRi
iG-COM

3xU G

3xU B

G CB1

G CB2

iG-CU

KC

CAN

iG-PCLSM

Kt

EXT .SYN

MGCB

MCB
MCB

RES.O K(2)

KA

RES.O K(1)

KC

KA

AVRi

LSM

Vout

SYS START/STOP
MASTER SELECT
MG CB

MASTER SELECTO R

O UT

SPEED
GOVERNOR

LOAD SHARING LINE

GCB2

3x

G2
iG-AVRi
TRANS

Kt

CAN

or

iS-CU+
iS-PCLSM -PM S

iG-AVRi
iG-COM

iG-CU

iG-PCLSM

SYN.ENABLED

3xIG

MCB

3xU B

EXT .
SYN

AVR

LOAD RESERVE 2
MCB FEEDBACK

3xU G

KA

3x

AVRi

AVRi

Vout
LSM

AVR

AVRi
O UT

SPEED
GOVERNOR

SYS START/STOP
MCB

MASTER SELECT
LOAD RESERVE 2
MCB FEEDBACK

MCB

Application Guide, ComAp February 2005


IG-6.1.2-IS-3.3.1-Application Guide.pdf

28

Specification

Automatic start-up when mains fails


After mains returns MCB synchronizing
One interrupt only stand-by
MGCB support
Gen-sets unload
Pwr management (if IG-COMs are installed)

InteliGen hardware requirements


1x
Uf relay unit (Mains decoupling relay) + MCB control
1x
External MCB Synchronizer
1x
NPU (when Vector shift protection is required)
nx
IG-CU
nx
IG-COM
(Optional)
nx
IG-PCLSM
nx
IG-AVRi, IG-AVRi-TRANS
(Optional)
nx
IG-MTU
(Optional - refer to controller user manual)
1x
IG-MU or IG-IB
(Optional - for connection to local or remote PC)
Hint:
IG-COM is necessary for Power management function and for Reactive power sharing (when no Droop AVR
are used).

InteliSys hardware requirements


1x
1x
nx
nx
nx
nx
1x
1x

Uf relay unit (Mains decoupling relay) + MCB control


External MCB Synchronizer
IS-CU
IS-PCLSM-PMS Dongle
(Optional)
IS-PCLSM Dongle
((Optional - without Power management))
IG-AVRi, IG-AVRi-TRANS
(Optional)
NPU (when Vector shift protection is required)
IG-MU or IG-IB
(Optional - for connection to local or remote PC)

Software system configuration: Multiple Internal (MINT)


Description without MGCB
1) The Uf relay opens MCB after the mains fails. At the same time the Uf relay starts Pwr
management by closing of SYS START/STOP input.
2) When the mains returns, external synchronizer synchronizes gen-sets to the mains.
3) Closing of MCB stops the gen-sets by opening of SYS START/STOP.
4) While stopping in parallel to mains, active MCB FEEDBACK ensures gen-sets soft unload.
5) MASTER SELECT selects the gen-set priority regardless of the Priority setpoint, if needed.

Description with MGCB


The Uf relay opens MCB after the mains fails. At the same time the Uf relay starts Pwr
management by closing of SYS START/STOP input.
2)
LOAD RESERVE 2 is controlled by MGCB, to differentiate the load reserve necessary before closing
of MGCB (setpoints LoadRes Strt 2 and LoadRes Stp 2), and load reserve while system is loaded
(setpoints LoadRes Strt 1 and LoadRes Stp 1).
3)
MGCB is closed by LOAD RES OK of 1st or 2nd gen-set and then held by MGCB feedback.
4)
When the mains returns, external synchronizer synchronizes gen-sets to the mains.
5)
Closing of MCB stops the gen-sets by opening of SYS START/STOP. Both GCBs are opened and
consequently KC relay opens also MGCB.
6)
While stopping in parallel to mains, active MCB FEEDBACK ensures gen-sets soft unload.
7)
MASTER SELECT selects the gen-set priority regardless of the Priority setpoint, if needed.
8)
When the gensets are not ready for standby operation after the mains return the bus 3 phase voltage
relay KA detects no voltage and with its time delay closes MCB.
Hints
Setpoint SysAMFstrt del is used for engines start delay after the mains fails. It is similar to setpoint
EmergStart del in Single Stand-by.
Time relay Kt is used for beginning of MCB synchronization after the mains returns. It is similar to setpoint
Mains Ret del in Single Parallel to Mains (SPtM) application.
After MCB closing, the delay for gen-sets unloading is 1s (MCB FEEDBACK is closed)..
Setpoint SysAMFstp del is not used in this case.
1)

Application Guide, ComAp February 2005


IG-6.1.2-IS-3.3.1-Application Guide.pdf

29

3.4.3. Multiple Short time parallel to mains internal Sync & LSM +
InteliMains

L O A D S H A R IN G L IN E

MCB
C L O S E /O P E N

iG-CO M

K o1

3xU M

3xU B

3xI M

iM -C U

iM-PCLSM

+24V

SYNC
DISABLE

MCB
FEEDBACK

0V

LS M

LO AD

CAN

MCB

GCB1

3x

3x

3x

3x

G1

3xI G

iG -C U
or

iS -C U +
iS -P C L S M -P M S

iG-PCLSM

MCB

iG -A V R i
iG-COM

K o1

3xU G

3xU B

iG -A V R i
TRANS
CAN

AVRi

LS M

V ou t

S Y S S T A R T /S T O P
M A S T ER SE LEC T

AVRi

AVR

OUT

SPEED
G OVERNO R
L O A D S H A R IN G L IN E

M CB FEEDBACK

GCB2

3x

3xI G

or

iS -C U +
iS -P C L S M -P M S
MCB

AVR

iG -A V R i
iG-PCLSM

iG -C U

iG -A V R i
TRANS

CAN

iG-COM

3xU B

G2
3xU G

M AS T ER SE LE CT O R

AVRi

V ou t
LSM

AVRi

OUT

SPEED
G OVERNO R

S Y S S T A R T /S T O P
M A ST E R S ELE CT

M CB FEEDBACK
MCB

LO A D S H A R IN G LIN E

LS M

LO AD

3xU B

3xU M

iM -C U

3xIM

MCB
C LO S E /O P E N

iG-COM

K o1

iM-PCLSM

+24V

SYNC
DISABLE

MCB
FEEDBACK

0V

3x

MCB

CAN

MGCB

GCB1

3x

3x

3x

G1

CAN

3xIG

3xU G

3xU B

GCB2

KC

K o1

GCB1

iG -A V R i
TRANS

or

iS -C U +
iS -P C L S M -P M S

MGCB

iG-PCLSM

iG -C U

KC

iG-COM

M G CB

MCB

RES.OK(2)

RES.OK(1)

iG -A V R i
AVRi

LS M

V out

S Y S S T A R T /S T O P
M A S T E R S E LE C T
M G CB

OUT

SP E E D
G OVERNO R
LO A D S H A R IN G LIN E

LO A D R E S E R V E 2
M CB FEEDBACK

GCB2

3x

G2

iG-PCLSM

or

iS -C U +
iS -P C L S M -P M S

iG -A V R i
iG-COM

iG -C U

iG -A V R i
TRANS

CAN

3xIG

3xU B

3xU G

M A S T E R S E LE C T O R

M CB

AVRi

AVR

AVRi

V out
LS M

AV R i

AVR

OUT

SP E E D
G OVERNO R

S Y S S T A R T /S T O P
M A S T E R S E LE C T
LO A D R E S E R V E 2
M CB FEEDBACK

M CB

Application Guide, ComAp February 2005


IG-6.1.2-IS-3.3.1-Application Guide.pdf

30

Specification

Automatic start-up when mains fails


After mains returns MCB synchronizing
One interrupt only stand-by
MGCB support
Gen-sets unload
Pwr management (if IG-COMs are installed)

InteliGen hardware requirements


1x
IM-CU (Vector shift protection from version 5.1)
1x
IG-COM
(Optional)
1x
IM-PCLSM
nx
IG-CU
nx
IG-COM
(Optional)
nx
IG-PCLSM
nx
IG-AVRi, IG-AVRi-TRANS
(Optional)
nx
IG-MTU
(Optional - refer to controller user manual)
1x
IG-MU or IG-IB
(Optional - for connection to local or remote PC)
Hint:
IG-COM is necessary for Power management function and for Reactive power sharing (when no Droop AVR
are used).

InteliSys hardware requirements


1x
1x
nx
nx
nx
nx
1x

IM-CU (Vector shift protection from version 5.1)


IG-COM (Optional)
IS-CU
IS-PCLSM-PMS Dongle
(Optional)
IS-PCLSM Dongle
((Optional - without Power management))
IG-AVRi, IG-AVRi-TRANS
(Optional)
IG-MU or IG-IB
(Optional - for connection to local or remote PC)

Software system configuration: IM + Multiple Internal (MINT)


Description without MGCB
1) The IM-CU opens MCB after the mains fails.
2) At the same time the MCB aux contact starts Pwr management by closing of SYS START/STOP input, if
the gen-sets had not run before.
3) When the mains returns, InteliMains synchronizes gen-sets to the mains.
4) MCB aux contact opens SYS START/STOP input, gen-sets stop.
5) While stopping in parallel to mains, active MCB FEEDBACK ensures gen-sets soft unload
6) MASTER SELECT selects the gen-set priority regardless of the Priority setpoint, if needed.

Description with MGCB


1)
2)

The IM-CU opens MCB after the mains fails.


At the same time the MCB aux contact starts Pwr management by closing of SYS START/STOP
input, if the gen-sets had not run before.
3)
LOAD RESERVE 2 is controlled by MGCB, to differentiate the load reserve necessary before closing
of MGCB (setpoints LoadRes Strt 2 and LoadRes Stp 2), and load reserve while system is loaded
(setpoints LoadRes Strt 1 and LoadRes Stp 1).
4)
MGCB is closed by LOAD RES OK of 1st or 2nd gen-set and then held by MGCB feedback.
5)
When the mains returns, InteliMains synchronizes gen-sets to the mains.
6)
Closing of MCB stops the gen-sets by opening of SYS START/STOP. Both GCBs are opened and
consequently KC relay opens also MGCB.
7)
While stopping in parallel to mains, active MCB FEEDBACK ensures gen-sets soft unload
8)
MASTER SELECT selects the gen-set priority regardless of the Priority setpoint, if needed.
Hints
Setpoint SysAMFstrt del is used for engines start delay after the mains fails. It is similar to setpoint
EmergStart del in Single Stand-by.
After MCB closing, the delay for gen-sets unloading is 1s (MCB FEEDBACK is closed).
Setpoint SysAMFstp del is not used in this case.
Application Guide, ComAp February 2005
IG-6.1.2-IS-3.3.1-Application Guide.pdf

31

3.4.4. Multiple Parallel to mains, Import-Export or Baseload control, Stand-by


external Sync & LSM
Application is supported by InteliGen only.
LOAD SHARING
LINE

LSM
MAINS
LOAD
U,f

MCB

3x

3x

GCB1
3x

3xU B

3x

U,f

3xU G

G1
CAN
LO AD SHARING
LINE

3xIG

3x

(3.PH.RELAY)

iG-CU

SYN

MCB
M CB

SYNC

UNLO AD

SYS START/STO P
M ASTER SELECT
M CB FEEDBACK

Kt

EX T.SYN

LSM

iG-COM

KA
KA

GCB2
M ASTER SELECTO R

G2

PARALL.
TO MAINS
REQ UIRED

iG-CU

SYN
SYNC

U,f

CAN

iG-COM

SYN.ENABLED

3xIG

M CB

3xU B

EX T.
SYN

3x

Kt
3xU G

KA

LSM

UNLO AD

SYS START/STO P
M ASTER SELECT
M CB FEEDBACK

M CB

Application Guide, ComAp February 2005


IG-6.1.2-IS-3.3.1-Application Guide.pdf

32

Specification

Synchronize gen-sets to mains


Import-Export or Base load power control
Uninterruptible stand-by
After mains returns MCB synchronizing
Automatic stand-by with Short time parallel to mains
Gen-sets soft unload (if the function is available in external LSM)
Pwr management (if IG-COMs are installed)

InteliGen hardware requirements


1x
1x

Uf relay unit (Mains decoupling relay) + MCB control


External Mains Load sharing module for Import-Export power control or Base load power control on
local Load sharing modules
External MCB Synchronizer
NPU (when Vector shift protection is required)
IG-CU
IG-COM (Optional)
External Synchronizer
External Load sharing module with soft unload function (if needed)
IG-MTU
(Optional - refer to controller user manual)
IG-MU or IG-IB
(Optional - for connection to local or remote PC)

1x
1x
nx
nx
nx
nx
nx
1x
Hint:
IG-COM is necessary for Power management function and for Reactive power sharing (when no Droop AVR
are used).

Software system configuration: Multiple External (MEXT)


Description
1) The system is started by the Uf relay or by the switch Parallel to mains required.
2) The Uf relay opens MCB after the mains fails. At the same time the Uf relay starts Pwr
management by closing of SYS START/STOP input, if the gen-sets had not run before.
3) When the mains returns, external synchronizer synchronizes gen-sets to the mains.
4) To stop the gen-sets while running in parallel to mains open the switch Parallel to mains required.
5) While stopping in parallel to mains, active MCB FEEDBACK ensures gen-sets soft unload (if the function
is available in external LSM)
6) MASTER SELECT selects the gen-set priority regardless of the Priority setpoint, if needed.
7) When the gensets are not ready for standby operation after the mains return the bus 3 phase voltage
relay KA detects no voltage and with its time delay closes MCB.
Hints
Setpoint SysAMFstrt del is used for engines start delay after the mains fails. It is similar to setpoint
EmergStart del in Single Stand-by.
Time relay Kt is used for beginning of MCB synchronization after the mains returns. It is similar to setpoint
Mains Ret del in Single Parallel to Mains (SPtM) application.
After MCB closing, the delay for gen-sets unloading is 1s (MCB FEEDBACK is closed).
Setpoint SysAMFstp del is not used in this case.

Application Guide, ComAp February 2005


IG-6.1.2-IS-3.3.1-Application Guide.pdf

33

3.4.5. Multiple Parallel to mains, Import-Export or Baseload control, Stand-by


internal Sync & LSM
LOAD SHARING
LINE

LSM
MAINS
I/E

LOAD

U,f

MCB

3x

3x

3x

GCB1

3x

G1
iG-AVRi
TRANS

KA
KA

or

MCB

iS-CU
iS-PCLSM-PMS

Kt

KA

SPEED
GOVERNOR

Vout
LSM

LOAD SHARING LINE


3x

G2

MASTER SELECTOR

iG-AVRi
TRANS

Kt

3xIG

CAN

iG-CU

PARALL.
TO MAINS
REQUIRED

AV
R

iG-AVRi

or

iS-CU
iS-PCLSM-PMS

iG-COM
iG-PCLSM

3xU B

MCB
SYN.ENABLED

3xUG

EXT.
SYN

AVR
i
OUT

AVRi

SYS START/STOP
MASTER SELECT
MCB FEEDBACK

GCB2

AV
R

iG-AVRi

iG-CU

MCB
EXT.SYN

CAN

3xIG

(3.PH.RELAY)

iG-COM
iG-PCLSM

3xU B

3x

U,f

3xUG

AVRi

Vout
LSM

AVR
i
OUT

SPEED
GOVERNOR

SYS START/STOP
MASTER SELECT
MCB FEEDBACK

MCB

MCB

LOAD SHARING
LINE

LSM
MAINS
I/E

LOAD

U,f

MGCB

3x

GCB1

3x

iG-AVRi
TRANS

or

iS-CU +
iS-PCLSM-PMS

CAN

3x

G2
iG-AVRi
TRANS

Kt

CAN

3xUB
3xUG
3xIG

MCB
SYN.ENABLED

PARALL.
TO MAINS
REQUIRED

MCB

MCB

Application Guide, ComAp February 2005


IG-6.1.2-IS-3.3.1-Application Guide.pdf

iG-CU
or

iS-CU +
iS-PCLSM-PMS

iG-AVRi

iG-COM
iG-PCLSM

KA

SPEED
GOVERNOR

Vout
LSM

LOAD SHARING LINE

MASTER SELECTOR

EXT.
SYN

AVR
i
OUT

AVRi

SYS START/STOP
MASTER SELECT
MCB FEEDBACK

GCB2

AVR

iG-AVRi

iG-COM
iG-PCLSM

GCB2

iG-CU

KC

MGCB

Kt

EXT.SYN

GCB1

KC

MCB

RES.OK(2)

MCB

(3.PH.RELAY)

MCB

KA

RES.OK(1)

KA

MGCB

3x

U,f

G1
3xUB
3xUG
3xIG

MCB
3x

KC

3x

MGCB

AVRi

Vout
LSM

AVR

AVR
i
OUT

SPEED
GOVERNOR

SYS START/STOP
MASTER SELECT
MCB FEEDBACK
...\EX_IM.VSD

34

Specification

Synchronize gen-sets to mains


Import-Export or Base load power control
Uninterruptible stand-by
After mains returns MCB synchronizing
Automatic stand-by with Short time parallel to mains
Gen-sets soft unload
Pwr management (if IG-COMs are installed)

InteliGen hardware requirements


1x
1x

Uf relay unit (Mains decoupling relay) + MCB control


External Mains Load sharing module for Import-Export power control or Base load power control on
local Load sharing modules
External MCB Synchronizer
NPU (when Vector shift protection is required)
IG-CU
IG-COM
(Optional)
IG-PCLSM
IG-AVRi, IG-AVRi-TRANS
(Optional)
IG-MTU
(Optional - refer to controller user manual)
IG-MU or IG-IB
(Optional - for connection to local or remote PC)

1x
1x
nx
nx
nx
nx
nx
1x
Hint:
IG-COM is necessary for Power management function and for Reactive power sharing (when no Droop AVR
are used).

InteliSys hardware requirements


1x
1x
1x
nx
nx
nx
nx
1x
1x

Uf relay unit (Mains decoupling relay) + MCB control


External Mains Load sharing module for Import-Export power control or Base load power control on
local Load sharing modules
External MCB Synchronizer
IS-CU
IS-PCLSM-PMS Dongle
(Optional)
IS-PCLSM Dongle
((Optional - without Power management))
IG-AVRi, IG-AVRi-TRANS
(Optional)
NPU (when Vector shift protection is required)
IG-MU or IG-IB
(Optional - for connection to local or remote PC)

Software system configuration: Multiple Internal (MINT)


Description without MGCB
1) The system is started by the Uf relay or by the switch Parallel to mains required.
2) The Uf relay opens MCB after the mains fails. At the same time the Uf relay starts Pwr
management by closing of SYS START/STOP input, if the gen-sets had not run before.
3) When the mains returns, external synchronizer synchronizes gen-sets to the mains.
4) To stop the gen-sets while running in parallel to mains open the switch Parallel to mains required.
5) While stopping in parallel to mains, active MCB FEEDBACK ensures gen-sets soft unload.
6) MASTER SELECT selects the gen-set priority regardless of the Priority setpoint, if needed.
7) When the gensets are not ready for standby operation after the mains return the bus 3 phase voltage
relay KA detects no voltage and with its time delay closes MCB.

Description with MGCB


1) MGCB follows MCB to enable synchronizing to the mains when PARALLEL TO MAINS REQUIRED
switch is closed.
2) The Uf relay opens MCB and MGCB after the mains fails. At the same time the Uf relay starts Pwr
management by closing of SYS START/STOP input.
3) MGCB is closed by LOAD RES OK of 1st or 2nd gen-set and then held by MGCB feedback after the
mains fail.
Hints
Setpoint SysAMFstrt del is used for engines start delay after the mains fails. It is similar to setpoint
EmergStart del in Single Stand-by.
Time relay Kt is used for beginning of MCB synchronization after the mains returns. It is similar to setpoint
Mains Ret del in Single Parallel to Mains (SPtM) application.
After MCB closing, the delay for gen-sets unloading is 1s (MCB FEEDBACK is closed).
Setpoint SysAMFstp del is not used in this case.
Application Guide, ComAp February 2005
IG-6.1.2-IS-3.3.1-Application Guide.pdf

35

3.4.6. Multiple Parallel to mains, Import-Export or Baseload control, Stand-by


internal Sync & LSM + InteliMains
0V

MCB
C L O S E /O P E N

iG-COM

K o1

LS M

LO AD

CAN

3xU B

3xIM

3xU M

iM -C U

iM-PCLSM

+ 2 4V

SYNC
DISABLE

MCB
FEEDBACK

LO A D S H A R IN G LIN E

CAN

3x

MCB
3x

GCB1

3x

G1

3xIG

iG -C U
or

iS -C U
iS -P C L S M -P M S

iG-PCLSM

MCB

iG -A V R i

iG-COM

3xU B

K o1

3xU G

iG -A V R i
TRANS
CAN

AVRi

AVRi

AVR

OUT

SPEED
G O VERNO R

V out
LSM

S Y S S T A R T /S T O P

LO A D S H A R IN G LIN E

M ASTER SELECT
M CB FEEDBACK

GCB2

3x

G2

M A S T E R S E LE C T O R

3xIG

iG -C U

P A R A LL.
T O M A IN S
R E Q U IR E D

or

iS -C U
iS -P C L S M -P M S

MCB

iG-PCLSM

iG -A V R i

iG-COM

3xU G

3xU B

iG -A V R i
TRANS
CAN

AVRi

AVRi

LSM

AVR

OUT

SPEED
G O VERNO R

V ou t

S Y S S T A R T /S T O P
M ASTER SELECT

M CB FEEDBACK
MCB
0V

iG-COM
iM-PCLSM

iM-CU

3xU B

MCB
CLOSE/OPEN

3xIM

Ko1

3xUM

+24V

SYNC
DISABLE

MCB
FEEDBACK

LOAD SHARING LINE

LSM

LOAD

CAN
CAN

MGCB

3x

3xIG

GCB2

3xUG

iG-AVRi

iG-CU

KC

or

iS-CU +
iS-PCLSM-PMS

MGCB

CAN

iG-COM
iG-PCLSM

MGCB

GCB1

KC
RES.OK(2)

Ko1

MCB

G1
iG-AVRi
TRANS

KC

MGCB
MCB

RES.OK(1)

3x

GCB1

3xUB

MCB
3x

GCB2

SPEED
GOVERNOR

Vout
LSM

SYS START/STOP
MASTER SELECT
MCB FEEDBACK

AVR

AVR
i
OUT

AVRi

LOAD SHARING LINE


3x

G2

MASTER SELECTOR

MCB

MCB

Application Guide, ComAp February 2005


IG-6.1.2-IS-3.3.1-Application Guide.pdf

3xIG

iG-CU
or

iS-CU +
iS-PCLSM-PMS

iG-AVRi

iG-COM
iG-PCLSM

PARALL.
TO MAINS
REQUIRED

3xUG

3xUB

iG-AVRi
TRANS
CAN

AVRi

Vout
LSM

AVR

AVR
i
OUT

SPEED
GOVERNOR

SYS START/STOP
MASTER SELECT
MCB FEEDBACK
...\IM_MCB.VSD

36

Specification

Synchronize gen-sets to mains


Import-Export or Base load power control
Uninterruptible stand-by
After mains returns MCB synchronizing
Automatic stand-by with Short time parallel to mains
Gen-sets soft unload
Pwr management

InteliGen hardware requirements


1x
IM-CU (Vector shift protection from version 5.1)
1x
IG-COM
(Optional)
1x
IM-PCLSM
nx
IG-CU
nx
IG-COM
(Optional)
nx
IG-PCLSM
nx
IG-AVRi, IG-AVRi-TRANS
(Optional)
nx
IG-MTU
(Optional - refer to controller user manual)
1x
IG-MU or IG-IB
(Optional - for connection to local or remote PC)
Hint:
IG-COM is necessary for Power management function and for Reactive power sharing (when no Droop AVR
are used).

InteliSys hardware requirements


1x
1x
1x
nx
nx
nx
nx
1x

IM-CU (Vector shift protection from version 5.1)


IG-COM (Optional)
IM-PCLSM
IS-CU
IS-PCLSM-PMS Dongle
(Optional)
IS-PCLSM Dongle
((Optional - without Power management))
IG-AVRi, IG-AVRi-TRANS
(Optional)
IG-MU or IG-IB
(Optional - for connection to local or remote PC)

Software system configuration: IM + Multiple Internal (MINT)


Description without MGCB
1) The system is started by MCB opening or by the switch Parallel to mains required.
2) The IM-CU opens MCB after the mains fails. At the same time the MCB aux contact starts Pwr
management by closing of SYS START/STOP input, if the gen-sets had not run before.
3) When the mains returns, IM-PCLSM synchronizer synchronizes gen-sets to the mains.
4) To stop the gen-sets while running in parallel to mains open the switch Parallel to mains required.
5) While stopping in parallel to mains, active MCB FEEDBACK ensures gen-sets soft unload
6) MASTER SELECT selects the gen-set priority regardless of the Priority setpoint, if needed.

Description with MGCB


1) MGCB follows MCB to enable synchronizing to the mains when PARALLEL TO MAINS REQUIRED
switch is closed.
2) The IM-CU opens MCB after the mains fails.
3) At the same time the MCB aux contact starts Pwr management by closing of SYS START/STOP input, if
the gen-sets had not run before.
4) MGCB is closed by LOAD RES OK of 1st or 2nd gen-set and then held by MGCB feedback after the
mains fail.
5) Closing of MCB stops the gen-sets by opening of SYS START/STOP. Both GCBs are opened and
consequently KC relay opens also MGCB.
See paragraph 3.4.8. MGCB control from InteliMains.
Hints
Setpoint SysAMFstrt del is used for engines start delay after the mains fails. It is similar to setpoint
EmergStart del in Single Stand-by.
After MCB closing, the delay for gen-sets unloading is 1s (MCB FEEDBACK is closed).
Setpoint SysAMFstp del is not used in this case.
Application Guide, ComAp February 2005
IG-6.1.2-IS-3.3.1-Application Guide.pdf

37

3.4.7. Multiple Parallel to mains, Peak shaving, Import-Export or Baseload


control, Stand-by internal Sync & LSM + InteliMains

MCB
CLOSE/O PEN
MAINS PW R
O UT

iG-COM

Ko1
Ko10

iM-CU

iM-PCLSM

+24V

LOAD SHARING LINE

SYNC
DISABLE

MCB
FEEDBACK

0V

LSM

3xU B

3xU M

3xI M

LOAD
CAN

MCB
3x

3x

3x

GCB1

3x

G1

CAN

3xI G

Ko1

3xU G

3xU B

iG-AVRi
TRANS

or

iS-CU+
iS-PCLSM -PM S

iG-PCLSM

iG-CU

MCB

iG-COM

iG-AVRi
AVRi

LSM

Vout

SYS START/STOP
MASTER SELECT

AVRi

AVR

O UT

SPEED
GOVERNOR
LO AD SHARING LINE

MCB FEEDBACK
3x

3xI G

G2

or

MCB

iS-CU+
iS-PCLSM -PM S

iG-AVRi
iG-PCLSM

iG-CU
Ko10

iG-AVRi
TRANS

CAN

iG-COM

3xU B

GCB2

3xU G

MASTER SELECTOR

AVRi

Vout
LSM

AVRi

AVR

O UT

SPEED
GOVERNOR

SYS START/STOP
MASTER SELECT
MCB FEEDBACK

MCB

Application Guide, ComAp February 2005


IG-6.1.2-IS-3.3.1-Application Guide.pdf

38

Specification

Peak shaving
Synchronize gen-sets to mains
Import-Export or Base load power control
Uninterruptible stand-by
After mains returns MCB synchronizing
Automatic stand-by with Short time parallel to mains
Gen-sets unload
Pwr management

InteliGen hardware requirements


1x
IM-CU (Vector shift protection from version 5.1)
1x
IG-COM
(Optional)
1x
IM-PCLSM
nx
IG-CU
nx
IG-COM
(Optional)
nx
IG-PCLSM
nx
IG-AVRi, IG-AVRi-TRANS
(Optional)
nx
IG-MTU
(Optional - refer to controller user manual)
1x
IG-MU or IG-IB
(Optional - for connection to local or remote PC)
Hint:
IG-COM is necessary for Power management function and for Reactive power sharing (when no Droop AVR
are used).

InteliSys hardware requirements


1x
1x
1x
nx
nx
nx
nx
1x

IM-CU (Vector shift protection from version 5.1)


IG-COM
(Optional)
IM-PCLSM
IS-CU
IS-PCLSM-PMS Dongle
(Optional)
IS-PCLSM Dongle
((Optional - without Power management))
IG-AVRi, IG-AVRi-TRANS
(Optional)
IG-MU or IG-IB
(Optional - for connection to local or remote PC)

Software system configuration: IM + Multiple Internal (MINT)


Description without MGCB
1) The system is started by MCB opening or by the IM-CU controlled MAINS PWR OUT relay when mains
imported power exceeds adjusted limit Mains ON Pwr .
2) The IM-CU opens MCB after the mains fails. At the same time the MCB aux contact starts Pwr
management by closing of SYS START/STOP input, if the gen-sets had not run before.
3) When the main returns, IM-PCLSM synchronizer synchronizes gen-sets to the mains or when mains
imported power decreases bellow adjusted limit Mains OFF Pwr, IM-CU binary output MAINS PWR OUT
opens SYS START/STOP on the gen-sets.
4) While stopping in parallel to mains, active MCB FEEDBACK ensures gen-sets soft unload.
5) MASTER SELECT selects the gen-set priority regardless of the Priority setpoint, if needed.

Description with MGCB


1) MGCB follows MCB to enable synchronizing to the mains.
2) The system is started by MCB opening or by the IM-CU controlled MAINS PWR OUT relay when mains
imported power exceeds adjusted limit Mains ON Pwr .
3) At the same time the MCB aux contact starts Pwr management by closing of SYS START/STOP input, if
the gen-sets had not run before.
4) When the main returns, IM-PCLSM synchronizer synchronizes gen-sets to the mains or when mains
imported power decreases bellow adjusted limit Mains OFF Pwr, IM-CU binary output MAINS PWR OUT
opens SYS START/STOP on the gen-sets.
Hint:
Setpoint SysAMFstrt del is used for engines start delay after the mains fails. It is similar to setpoint
EmergStart del in Single Stand-by.
After MCB closing, the delay for gen-sets unloading is 1s (MCB FEEDBACK is closed).

Application Guide, ComAp February 2005


IG-6.1.2-IS-3.3.1-Application Guide.pdf

39

Setpoint SysAMFstp del is not used in this case.

3.4.8. Multiple Parallel to mains, MGCB control from InteliMains


Following example corresponds to paragraph 3.4.6. but MGCB is controlled from InteliMains available from
InteliMains V 5.1.
0V

iM-CU

3xUB

MGCB
CLOSE/OPEN

3xIM

Ko2

MCB
CLOSE/OPEN

3xUM

Ko1

iG-COM
iM-PCLSM

+24V

SYNC
DISABLE

MCB
FEEDBACK

LOAD SHARING LINE

LSM

LOAD

CAN
CAN

MGCB

3x

3x

3x

GCB1

G1
iG-AVRi
TRANS

Ko1

CAN

3xIG

3xU B

+24V

3xUG

MCB

iG-AVRi

MCB

MGCB

iG-CU
or

iS-CU +
iS-PCLSM-PMS

iG-COM
iG-PCLSM

Ko2

GCB2

SPEED
GOVERNOR

Vout
LSM

SYS START/STOP
MASTER SELECT
MCB FEEDBACK

AVR

AVR
i
OUT

AVRi

LOAD SHARING LINE


3x

G2

MASTER SELECTOR

MCB

3xIG

iG-CU
or

iS-CU +
iS-PCLSM-PMS

iG-AVRi

iG-COM
iG-PCLSM

PARALL.
TO MAINS
REQUIRED

3xUG

3xUB

iG-AVRi
TRANS
CAN

AVRi

Vout
LSM

AVR

AVR
i
OUT

SPEED
GOVERNOR

SYS START/STOP
MASTER SELECT
MCB FEEDBACK

MCB

Software system configuration: IM + Multiple Internal (MINT)


Description with MGCB
1) IM closes MGCB when MCB is closed to enable synchronizing to the mains when PARALLEL TO
MAINS REQUIRED switch is closed.
2) The IM-CU opens MCB and MGCB after the mains fails.
3) At the same time the MCB aux contact starts Pwr management by closing of SYS START/STOP input, if
the gen-sets had not run before.
4) MGCB is closed by IM when selected load reserve is achieved (enough engines are running) and IM
keeps it closed when at least one GCB is closed.
5) Closing of MCB stops the gen-sets by opening of SYS START/STOP. Both gensets are unloaded to
mains, then both GCBs are opened and engines stopped.

Application Guide, ComAp February 2005


IG-6.1.2-IS-3.3.1-Application Guide.pdf

40

4. Examples
4.1.

Stand-by redundancy gen-sets

Two InteliGen - SPM controllers are connected as Stand-by redundancy gen-sets.

LOAD
U,f
3x

GCB1
3x

3x

3x

3xU B

3x

U,f

G1
3xIG

MCB

3x

3xU G

(3.PH.RELAY)

KA

K1

KA

MCB

BO
NO T READYAUTO

MCB

iG-CU
SPM
BI

REM START/STO P

K2
GCB2

KM

3x

3xU B

Kt
+

G2
3xIG

KM

U,f

3xU G

MASTER SELECTOR

K2
NO T READYAUTO

K1

BO

iG-CU
SPM
BI

REM START/STO P

KM
Kt

Specification

Automatic start-up when the mains fails


Reclosing after mains returns
Master genset is selected by Master selector switch.
When selected gen-set fails the second one starts.
Bus voltage measuring protects genset against GCB closing to energized bus.

IG InteliGen hardware requirements


1x
2x
2x

Uf relay (Mains decoupling relay) unit + MCB control


IG-CU
IG-MTU
(Optional - refer to controller user manual)

Software system configuration: SPM


Description
1)
2)
3)
4)
5)

The Uf relay opens MCB after the mains fails.


With the time delay given by Kt relay the master genset is started
If the master is not ready or fails during the operation the second genset is started
When the mains returns Kt relay stops the running set with its delay.
Bus 3 phase voltage relay detects no voltage and with its time delay closes MCB

Application Guide, ComAp February 2005


IG-6.1.2-IS-3.3.1-Application Guide.pdf

41

4.2 SPM redundancy with ATS


Two InteliGen - SPM (InteliLite) controllers are connected as Stand-by redundancy gen-sets.

LOAD

3x

3x

3x

G1

K1
BO

3xIG

ATS

3xU G

I.
3xU B

II.

iG-CU
SPM

NOT READYAUTO

+
GCB1

GCB
BO CLOSE/OPEN

BI
GCB1 feedback
ATS I. feedback

REM START/STOP

K2
KM
3x

K2

KM
GCB1

NOT READYAUTO

K1
MASTER
SELECTOR
I

BO

REM START/STOP

KM

3xIG

3xU G

3xU B

+
+
GCB2

G2

iG-CU
SPM

GCB
BO CLOSE/OPEN

+
GCB2

BI
GCB2 feedback
ATS II. feedback

II
SYSTEM
START

ATS

Specification

Start on request by SYSTEM START switch


Master genset is selected by Master selector switch.
When selected gen-set fails the second one starts.
Bus (load) voltage measuring protects genset against GCB closing to energized bus.

IG InteliGen hardware requirements


2x

IG-CU

Software system configuration: SPM


Description
1) Selected master genset is started after SYSTEM START is closed
2) If the master is not ready or fails during the operation the second genset is started

4.3 Two phase genset connection


Connect voltage and current terminals according following drawing.

L3
L0
L1

N L1 L2 L3

L1k L1l L2k L2l L3k L3l

Application Guide, ComAp February 2005


IG-6.1.2-IS-3.3.1-Application Guide.pdf

42

4.4 Bus-tie breaker (BTB) application


Two Mains incomers and two gen-sets are separated by a bus-tie breaker. When one or both Mains fail, the
BTB closes and Load can be supplied from the healthy Mains or from the gen-sets.
LOAD SHARING LINE

BI Sys Start/Stop

BO MCB fdb mirror

BI MCB feedback

BO GCB blocking

BI GCB disable

iS-CU 1 +
iS-PCLSM-PMS
3xU B

CAN 2

BO Mains fail

LSM

3xIG

LSM

3xU B

3xUM

MCB ON coil

3xIM

MCB feedback

MCB OFF coil

iM-CU 1

3xUG

iG-COM
iM-PCLSM

CAN

230 VAC

LOAD
1

MCB

GCB1
3x

3x

G1
CAN B

BTB

I-CR
CAN A

MCB

GCB2

BI Remote OFF
BI Sync disable

G2

3xIG

3xUG

3xU B

3xU B

LOAD

BI 16; BTB fdb

LSM

BO Mains fail

BI Sys Start/Stop

BO MCB fdb mirror

BI MCB feedback

BO GCB blocking

BI GCB disable

iS-CU 2 +
iS-PCLSM-PMS

CAN 2

iM-CU 2

iG-COM
iM-PCLSM

BI Access lock

3xUM

3xIM

3x

LSM

IG-IB
+ IB-7 dongle

IM-CU 1 Contr. Addr = 1


IM-CU 2 Contr. Addr = 2
IS-CU 1 Contr. Addr = 3
IS-CU 2 Contr. Addr = 4

Specification

Mains circuit breaker (MCB) is operated by 230V AC coil so it can be opened only after the voltage
on the generator is present. GCB cannot be closed before MCB is opened.
Therefore the BO MCB fdb mirror and GCB blocking from IM are connected to BI MCB feedback and
GCB disable of IS (see IM-6.1 and IS-MINT-3.3 manuals for detailed description).
Related settings are:
IS: ProcessControl:#SysLdCtrl PtM = BASELOAD
IS: ProcessControl:#SysPFCtrl PtM = BASEPF
IM: Mains protect:MCB opens on = GENRUN
IM: Mains protect:VectorS prot = GENRUN
IM: Pwr management:#SysAMFstpDel > Mains protect:Mains ret del
I-CR module is used for separating two parts of the CAN bus when BTB is opened it has jumper
P4 closed which means that IS-CU 2 (Contr. Addr = 4) gives I-CR information about BTB feedback.
BTB feedback is 16 binary input of IS-CU 2 (see Inteli-communication guide for detailed description
of I-CR possibilities). Thanks to I-CR module IG-IB is able to monitor all controllers (IM 1 and 2, IS 1
and 2) even if the BTB is opened.

Application Guide, ComAp February 2005


IG-6.1.2-IS-3.3.1-Application Guide.pdf

43

Hardware requirements
2x
2x
2x
2x
2x
1x
1x
1x

IS-CU
IS-PCLSM-PMS
IM-CU
IG-COM
IM-PCLSM
IG-IB
IB-7 dongle
I-CR

Software system configuration: IS-MINT-3.3, IM-6.1

Application Guide, ComAp February 2005


IG-6.1.2-IS-3.3.1-Application Guide.pdf

44

5. Speed governor interface


Hint:
Read carefully Speed governor instructions before connecting InteliGen or InteliSys Speed governor
interface!

Electronic engines interface


All below mentioned interface examples describes analog interface even if they are (in some cases) used for
Electronic Control Units (Electronic engines) with CAN data bus.
There are several possibilities to connect CAN bus interface between Electronic engine and ComAp
controller. Please ask your local distributor for more details.

InteliSys ECU interface


I-CB unit is an interface between InteliSys and Electronic engine. Following I-CB types are available:
For more details see I-CB-ICBEdit-1.1.pdf manual.
I-CB type
Engine
MTU
I-CB/MTU
I-CB/CAT-Diesel
CAT
I-CB/CAT-Gas
CAT

InteliGen ECU interface


There exist some InteliGen customer branches that support ECU. Please ask your local distributor for more
details.

Controller Speed reg out voltage limit


Please note there is a new setpoint in InteliSys-3.1 controller (no in IG-6.1): Sync/Ld ctrl: SpeedGovLowLim
[0,01V]. Setpoint limits low level of output voltage. E.g. instead of full 10V to +10V Speed governor output
range can be set SpeedGovLowLim = 0,00 to reduce output range from 0 to 10V.
Hint:
SpeedGovLim setpoint is available from IS version 3.1 !

Heinzmann E1-F and E2F


In t e liG e n
In t e liS y s
H e in z m a n n
K G -1 -0 3 F

GND

IG - P C ( L S ) M

S p e e d P ic k u p
GND

S p e e d In p u t

2k

GND

V o u tR

4
5

U re f = 7 ,9 V

SPEED
GOVERNOR

10kohm

Speed
gov
b ia s

Vout

1k2

re d =

U b a tt

b lu e = G N D

P o w e r s u p p ly

Adjusting
Sync/Load ctrl: Speed gov bias = 0V
SpeedRegChar = POSITIVE

Application Guide, ComAp February 2005


IG-6.1.2-IS-3.3.1-Application Guide.pdf

45

Heinzmann E6
InteliGen
InteliSys
IG-PC(LS)M
SPEED
GOVERNOR

GND

A3
B3

VoutR
150 kohm

10kohm

Speed
gov
bias

Vout

Adjusting
Sync/Load ctrl: Speed gov bias = 5V
SpeedRegChar = POSITIVE

Heinzmann E16
InteliGen
InteliSys
IG-PC(LS)M
SPEED
G O VERNO R

G ND
A3
VoutR

B3

10kohm

Speed
gov
bias

Vout

Adjusting
Sync/Load ctrl: Speed gov bias = 0V
SpeedRegChar = POSITIVE

Cummins
EFC
InteliGen
InteliSys

Cummins EFC
1

+Vbatt

IG-PC(LS)M

-Vbatt
7
8
9

C
4u7/50V

7,8V
300R
470R

G ND

VoutR

SPEED
G O VERNO R

10kohm

Speed
gov
bias

Vout

5V
11

Application Guide, ComAp February 2005


IG-6.1.2-IS-3.3.1-Application Guide.pdf

46

Hint:
Spurious operation of the InteliGen push buttons is caused by excessive interference from the speed
controller when capacitor is not connected between power supply terminals 1 and 2.
Adjusting
Sync/Load ctrl: Speed gov bias = 0V
SpeedRegChar = POSITIVE

ECPG
InteliGen
InteliSys

Cummins ECPG

IG-PC(LS)M
A

GND

VoutR
I

SPEED
GOVERNOR

10kohm

Speed
gov
bias

Vout

Adjusting
Sync/Load ctrl: Speed gov bias = 2.5VDC
SpeedRegChar = POSITIVE

ONAN
InteliGen
InteliSys

Cummins ONAN

GND
0-5V

10k

VoutR

10k

Speed
gov
bias

Vout

Adjusting
Sync/Load ctrl: Speed gov bias = 2.5VDC
SpeedRegChar = POSITIVE

Application Guide, ComAp February 2005


IG-6.1.2-IS-3.3.1-Application Guide.pdf

???

47

QST30

Adjusting
Sync/Load ctrl: Speed gov bias = 5 VDC
SpeedRegChar = POSITIVE

Barber colman
DYNA 8000
InteliGen
InteliSys

IG-PC(LS)M
GND

470kOhm

VoutR

SPEED
GOVERNOR

10kohm

Speed
gov
bias

Vout
2

Adjusting
Sync/Load ctrl: Speed gov bias = 4V
SpeedRegChar = POSITIVE

Application Guide, ComAp February 2005


IG-6.1.2-IS-3.3.1-Application Guide.pdf

48

DYN1 10684
InteliGen
InteliSys

IG-PC(LS)M

8V

GND

6
9

4V 7

7K5

VoutR

7K5

SPEED
GOVERNOR

10kohm

Speed
gov
bias

Vout

Adjusting
Sync/Load ctrl: Speed gov bias = 0V
SpeedRegChar = POSITIVE

GAC
GAC ESD 5500 series
InteliGen
InteliSys
IG-PC(LS)M
GND

G
AUX

VoutR

Rext =1kohm

SPEED
GOVERNOR

10kohm

Speed
gov
bias

Vout

Adjusting
Sync/Load ctrl: Speed gov bias = 5V
SpeedRegChar = NEGATIVE

InteliGen
InteliSys

ESD 5330

IG-PC(LS)M
G

GND
VoutR

AUX

SPEED
GOVERNOR

10kohm

Speed
gov
bias

Vout

Adjusting

Application Guide, ComAp February 2005


IG-6.1.2-IS-3.3.1-Application Guide.pdf

49

Sync/Load ctrl: Speed gov bias = 5V


SpeedRegChar = NEGATIVE

InteliGen
InteliSys

EGS 104B

IG-PC(LS)M
GND

2
1 kohm

AUX

25

VoutR

SPEED
GOVERNOR

10kohm

Speed
gov
bias

Vout

Adjusting
Sync/Load ctrl: Speed gov bias = 5V
SpeedRegChar = NEGATIVE

Woodward
ProAct II - Digital Speed Control System

Adjusting
Sync/Load ctrl: Speed gov bias = 0V
SpeedRegChar = POSITIVE

EPG - Electrically Powered Governors


EPG
IG/IS -PC(LS)M
11 +
VoutR
12 GND
Shielding connected on
EPG side only
Adjusting
Sync/Load ctrl: Speed gov bias = 0V
SpeedRegChar = POSITIVE

2301A Speed Controls


2301A
15
16 COM
17 =Shielding is connected
on 2301A side only

IG/IS -PC(LS)M
VoutR
GND

Application Guide, ComAp February 2005


IG-6.1.2-IS-3.3.1-Application Guide.pdf

50

Adjusting
Sync/Load ctrl: Speed gov bias = 0V
SpeedRegChar = POSITIVE

2301A Load Sharing and Speed control


2301A
IG/IS -PC(LS)M
25 +
VoutR
26 GND
27 =Shielding is connected
on 2301A side only
Adjusting
Sync/Load ctrl: Speed gov bias = 0V
SpeedRegChar = POSITIVE

Detroit diesel - DDEC3


InteliGen
InteliSys
IG-PC(LS)M
A

+ 24V

1
B

G ND

SPEED
G O VERNO R

2
C
3
D

- 24V

VoutR

10kohm

Speed
gov
bias

4
E

G AC
EAM104

Vout

5K
EXTERNAL FREQ
TRIM
952

510

DDEC3

C3

D1
A3

Adjusting
Sync/Load ctrl: Speed gov bias = 0V
SpeedRegChar = POSITIVE

Application Guide, ComAp February 2005


IG-6.1.2-IS-3.3.1-Application Guide.pdf

51

Volvo Penta EDC III


InteliGen
InteliSys

VO LVO
EDC III

1
2
G AC
EAM 122

IG-PC(LS)M

+Vbatt

G ND

VoutR
6

SPEED
G O VERNO R

-Vbatt

10kohm

Speed
gov
bias

Vout

Adjusting
Sync/Load ctrl: Speed gov bias = 0V
SpeedRegChar = POSITIVE

MTU MDEC 2000 , 4000


InteliGen
InteliSys
IG-PC(LS)M
GND

36

MTU
MDEC
0 to 10V

GND
VoutR

SPEED
GOVERNOR

10kohm

Speed
gov
bias

Vout

Adjusting
Sync/Load ctrl: Speed gov bias = 4,9 V
SpeedRegChar = POSITIVE

Caterpillar
Following is an example of interface to Speed control unit with PWM input for synchronizing.

Interface with EP300


There is used Analog to PWM signal converter and Electronic potentiometer EP300 which is controlled by
Binary outputs Speed Up and Down from controller.

Application Guide, ComAp February 2005


IG-6.1.2-IS-3.3.1-Application Guide.pdf

52

IG -PC (LS)
M
IS -PC (LS) M

BO
BO
BO

CATERPILLAR
Signal
converter

EP300

Speed Up
Speed Dn
Start

INC

+B

DEC

-B

SET

1k

+Vbat

CATERPILLAR
Speed Control
Unit

PWM
signal

-Vbat

Interface without EP300


CATERPILLAR
Signal
converter

IG -PC (LS) M
IS -PC (LS) M

VoutR

+Vbat

+B

PWM
signal

CATERPILLAR
Speed Control
Unit
ADEM
or
PEEC

470 Ohm

GND

-B
-Vbat

Adjusting
Sync/Load ctrl: Speed gov bias = 4,0 V
SpeedRegChar = POSITIVE

Deutz BF6M engine


Example of interface to DEUTZ electronic injection system.

InteliGen
InteliSys

DEUTZ BF6M

IG-PC(LS)M
21

GND

23

VoutR

17
Opened for
0% droop

GND

0,5 to 4,5V

24

SPEED
GOVERNOR

10kohm

Speed
gov
bias

Vout

Genset plug F
Adjusting
Sync/Load ctrl: Speed gov bias = 2,5 V
SpeedRegChar = POSITIVE

Perkins
Perkins 4016 E61 TRS
Application Guide, ComAp February 2005
IG-6.1.2-IS-3.3.1-Application Guide.pdf

53

InteliGen
InteliSys

ECM

IG-PC(LS)M
SPEED

GND

19

GOVERNOR

2,7kOhm

10kOhm
VoutR

18
OEM connector

2,7kOhm
Vout

Adjusting
Sync/Load ctrl: Speed gov bias = 5V
SpeedRegChar = POSITIVE

Perkins series 2300, 2800

Adjusting
Sync/Load ctrl: Speed gov bias = 5V
SpeedRegChar = POSITIVE
Hint:
For external speed setting terminals 2 and 12 on ECM have to be interconnected.

Application Guide, ComAp February 2005


IG-6.1.2-IS-3.3.1-Application Guide.pdf

54

Perkins 1300 Series EDi


InteliGen
InteliSys
IG-PC(LS)M
VBREF GND
SENSOR SUPPLY

8 kohms

GND

RPS INPUT

VoutR

SPEED
GOVERNOR

10kohm

Speed
gov
bias

Vout

Adjusting
Sync/Load ctrl: Speed gov bias = app. 5,6 V
SpeedRegChar = POSITIVE

TOHO
XS-400B-03

Application Guide, ComAp February 2005


IG-6.1.2-IS-3.3.1-Application Guide.pdf

55

Adjusting
Sync/Load ctrl: Speed gov bias = 4 V
SpeedRegChar = POSITIVE

Application Guide, ComAp February 2005


IG-6.1.2-IS-3.3.1-Application Guide.pdf

56

6. AVR interface
Hint:
Read carefully AVR instructions before connecting to InteliGen or InteliSys controller!

Basler
Basler APR63-5, AEC 63-7, KR-FX, KR-FFX

GND

OUT1

230/400VAC From
0VAC generator

AVRi+

iGAVRi

18VAC

iGAVRi
TRANS

AVRi-

InteliGen
InteliSys

IG-PC(LS)M

AVRi+
AVRi-

AVRi output is connected instead of external resistor for voltage adjusting.


Adjusting
AVRi trim to minimum counterclockwise.
Volt/PF ctrl:
AVR DCout bias = 50%
VoltRegChar = POSITIVE

Stamford
STAMFORD SX460

Voltage
input
+- 5V

1
2

OUT2

230/400VAC From
0VAC generator

AVRi+

iGAVRi

18VAC

iGAVRi
TRANS

AVRi-

OUT1

InteliGen
InteliSys

IG-PC(LS)M

AVRi+
AVRi-

AVRi output is connected instead of external resistor for voltage adjusting.


Adjusting
AVRi trim to minimum counterclockwise.
Volt/PF ctrl:
AVR DCout bias = 50%
VoltRegChar = POSITIVE

STAMFORD SX440, SX 460, MX321, SX421


18Vac

A1
A2

OUT2

iGAVRi
TRANS

230Vac
0Vac

iGAVRi

SX440
SX421
M X321

OUT1

From
generator

AVRi+
AVRi-

InteliGen
IG-PC(LS)M
AVRi+
AVRi-

AVRi output is connected to auxiliary voltage input A1, A2.


Adjusting
AVRi trim to minimum counterclockwise.
Volt/PF ctrl:
AVR DCout bias = 50%
VoltRegChar = POSITIVE
Hint:
Inputs 1 and 2 for external trim must be shorted for control via analog inputs A1, A2.

Application Guide, ComAp February 2005


IG-6.1.2-IS-3.3.1-Application Guide.pdf

57

Leroy Sommer
R438 LS, R448
18VAC

Terminal
strip J2
GND

S2, S1
ST4

iGAVRi
TRANS

230/400VAC From
0VAC generator

iGAVRi

R438 LS

OUT1

InteliGen
InteliSys

IG-PC(LS)M

AVRi+

AVRi+
AVRi-

AVRi-

AVRi output is connected instead Remote voltage trimmer 470 ohm to terminals ST4.
Adjusting
AVRi trim to minimum counterclockwise.
Volt/PF ctrl:
AVR DCout bias = 50%
VoltRegChar = POSITIVE

R449
Leroy Sommer
R 449
100 VAC
18 VAC

iG-AVRi
TRANS/100

0 VAC

From generator
InteliGen
InteliSys

R449

IG-PC(LS)M
Terminal

strip J2

OUT2

AVRi+

iGAVRI

4
2

AVRi-

AVRi+
AVRi-

OUT1

AVR Dcout bias = 50%


VoltRegChar = POSITIVE

RS128
18VAC

4
5

G ND

230/400VAC From
0VAC generator

iG AVRi

RS128.0

iGAVRi
TRANS

AVRi+
AVRi-

InteliG en
InteliSys
IG -PC(LS)M
AVRi+
AVRi-

OUT1

AVRi output is connected instead Remote voltage trimmer 470 ohm to terminals 4, 5.
Adjusting
AVRi trim to minimum counterclockwise.
Volt/PF ctrl:
AVR DCout bias = 50%
VoltRegChar = POSITIVE

Application Guide, ComAp February 2005


IG-6.1.2-IS-3.3.1-Application Guide.pdf

58

Mecc Alte Spa


S.R.7/2, U.V.R.6
IG-AVRi-TRANS
230/400VAC

U.V.R.6
S.R.7/2

18VAC

0VAC

InteliGen
InteliSys

From
generator

I GA V Ri

IG-PC(LS)M

OUT1

AVRi+
AVRi-

AVRi+
AVRi-

GND

AVRi output is connected instead Remote voltage trimmer 100Kohm (OUT1=top position wire and Gnd
=second top position wire see below).
Adjusting
AVRi trim to maximum counterclockwise.
Volt/PF ctrl:
AVR DCout bias = 75%
VoltRegChar = NEGATIVE

Marelli AVR
MX341

A1

iGAVRi

18Vac
n.c. S1
S2
1
2

230Vac From
0Vac generator

iGAVRi
TRANS

GND

OUT1

A2

AVRi+
AVRi-

InteliGen
InteliSys

IG-PC(LS)M

AVRi+
AVRi-

Use pin 1 and 2 with link (remote voltage trim)


Disconnect Droop C/T (S1, S2)
Adjusting
AVRi trimpot in middle position.
Volt/PF ctrl:
AVR DCout bias = 50%
VoltRegChar = POSITIVE

Piller
230/400VAC

2
1

OUT2

iG-AVRiTRANS

0VAC

i GAVRi

18VAC

From
generator

AVRi+
AVRi-

InteliGen
InteliSys

IG-PC(LS)M
AVRi+
AVRi-

OUT1

AVRi output is connected instead Remote voltage trimmer 100Kohm.


Adjusting
AVRi trim to minimum counterclockwise.
Volt/PF ctrl:
AVR DCout bias = 39%
VoltRegChar = POSITIVE

Application Guide, ComAp February 2005


IG-6.1.2-IS-3.3.1-Application Guide.pdf

59

Caterpillar
VR6

Volt/PF ctrl:

AVR DCout bias = approx. 50%


VoltRegChar = POSITIVE

DVR

Volt/PF ctrl:

AVR DCout bias = 50%


VoltRegChar = POSITIVE

???
Hint:
IG-AVRi trim in about position.
Pin 44 on DVR PF regulation directly from DVR not connected.

Application Guide, ComAp February 2005


IG-6.1.2-IS-3.3.1-Application Guide.pdf

60

7. Abbreviations
AMF
ATS
AVR
GCB
CHP
IG
IG-AVRi
IG-COM
IG-IB
IG-MU
IG-PCLSM
IG-PCM
IM
IS
LS
LSM
MCB
MEXT
MGCB
MINT
NPU
PMS
SPI
SPM
SPtM
SSB
VS

Auto Mains Failure (controller starts automatically on mains failure)


Automatic Transfer Switch (switches the load to actually supplied bus (by mains or
generators))
Automatic Voltage Regulator
Generator Circuit Breaker
Combined Heat & Power - cogeneration application, usually with gas engine
InteliGen gen-set controller
IG Automatic Voltage Regulator interface
IG Communication module - enables to interconnect the IG controllers in multiple applications
via CAN bus and connecting the communication modules (IG-MU, IG-IB)
IG Internet Bridge - for internet/ethernet communication
IG Modem Unit - for direct or modem control of multiple gen-sets
IG Power Control and Load Sharing Module - for synchronizing and power control for multiple
isolated parallel operation
IG Power Control Module - for synchronizing and power control of a single gen-set running in
parallel to mains
InteliMains - Mains supervision controller
InteliSys gen-set controller
Load Sharing - analog load sharing line to interconnect the gen-sets on the site (for isolated
parallel or mains parallel of multiple gen-sets)
Load Sharing Module
Mains Circuit Breaker
Multiple application with EXTernal control loops - for multiple gen-sets in island parallel or
mains parallel operation; external synchronizer & load sharer modules expected; PMS
available
Master Generator Circuit Breaker (sometimes used with multiple gen-sets in island parallel or
mains parallel operation)
Multiple application with INTernal control loops - for multiple gen-sets in island parallel or
mains parallel operation; Load Sharing and VAr Sharing controlled internally; PMS available
Mains protection relay (voltage, frequency, vector shift protections)
Power Management System - ensures optimization of running gen-sets on the site with
multiple gen-sets; based on kW spinning reserve or on relative (%) load; no-master system
ensures high reliability
Single Parallel Island application - for single gen-sets in parallel with mains or in island
operation; suitable for CHP application; no MCB control
Single Prime Mover application - for single gen-sets without mains
Single Parallel to Mains application - for single gen-sets in parallel with mains or in island
operation, with AMF support; both MCB and GCB controlled
Single Stand-By application - for single gen-sets with mains and break transfer gen-set to
mains
VAr Sharing - ensures VAr sharing between the gen-sets on the site via CAN bus (for isolated
parallel or mains parallel of multiple gen-sets)

Application Guide, ComAp February 2005


IG-6.1.2-IS-3.3.1-Application Guide.pdf