You are on page 1of 120

System

Indoor Unit
SERVICE MANUAL R410A
MODEL : ARNU Series
URNU Series
CAUTION
Before Servicing the unit, read the safety precautions in General SVC manual.
Only for authorized service personnel.
Internal Use Only
http://biz.lgservice.com
R410A
- 2 -
Copyright2010LGElectronics.Inc.Allrightreserved.
Onlyfortrainingandservicepurposes
LGEInternalUseOnly
AirConditionerServiceManual
TABLE OF CONTENTS
Part 1 General Information.......................................................................................................3
Model Names ...............................................................................................................................4
External Appearance ...................................................................................................................5
Nomenclature...............................................................................................................................6
Part 2 Indoor Units......................................................................................................................7
CeilingMountedCassetteType(1way) ........................................................................................8
CeilingMountedCassetteType(2way) ......................................................................................16
CeilingMountedCassetteType(4way)(1) ..................................................................................21
CeilingMountedCassetteType(4way)(2) ..................................................................................27
ArtCoolType(Mirror) ...................................................................................................................34
ArtCoolType(Gallery) .................................................................................................................45
CeilingConcealedDuctType(Lowstatic) ...................................................................................55
CeilingConcealedDuctType(Builtin) ........................................................................................61
CeilingConcealedDuctType(Highstatic) ..................................................................................67
WallMountedType ......................................................................................................................76
Ceiling&FloorCeilingSuspended ..............................................................................................87
FloorStandingType.....................................................................................................................94
VerticalAirHandlingUnit ...........................................................................................................101
Part 3 Trouble shooting guide...............................................................................109
- 3 -
Copyright2010LGElectronics.Inc.Allrightreserved.
Onlyfortrainingandservicepurposes
LGEInternalUseOnly
Part 1
General Information
1. Model Names .............................................4
2. External Appearance .................................5
3. Nomenclature.............................................6
Model Names
- 4 -
Copyright2010LGElectronics.Inc.Allrightreserved.
Onlyfortrainingandservicepurposes
LGEInternalUseOnly
1. Model Names
h *ARTCOOL-SE/S8(*R:Mirror,V:Silver,B:Blue),SF(*E:Red,V:Silver,G:Gold,1:Kiss(Photochangeable))
*WallMounted-A:Basic,L:Plasma,*CeilingCassette-A:Basic,C:Plasma
Category
Chassis
Name
Capacity(Btu/h(kW))
7.5
(2.2)
9.6
(2.8)
12.3
(3.6)
15.4
(4.5)
19.1
(5.6)
24.2
(7.1)
28.0
(8.2)
30.0
(8.8)
36.2
(10.6)
42.0
(12.3)
48.1
(14.1)
54.0
(15.8)
76.4
(22.4)
95.5
(28.0)
Wall Mounted
(General)
SE
ARNU07
3SE*2
ARNU09
3SE*2
ARNU12
3SE*2
ARNU15
3SE*2
S5
ARNU18
3S5*2
ARNU24
3S5*2
ART
COOL
Mirror
SE
ARNU07
3SE*2
ARNU09
3SE*2
ARNU12
3SE*2
ARNU15
3SE*2
S8
ARNU18
3S8*2
ARNU24
3S8*2
Ceiling
Cassette
1 Way TJ
ARNU07
3TJ*2
ARNU09
3TJ*2
ARNU12
3TJ*2
2 Way TL
ARNU18
3TL*2
ARNU24
3TL*2
4 Way
TR
ARNU07
3TR*2
ARNU09
3TR*2
ARNU12
3TR*2
TQ
ARNU15
3TQ*2
ARNU18
3TQ*2
TP
ARNU24
3TP*2
ARNU28
3TP*2
TN
ARNU36
3TN*2
TM
ARNU42
3TM*2
ARNU48
3TM*2
Ceiling
Concealed
Duct
High Static
BH
ARNU07
3BHA2
ARNU09
3BHA2
ARNU12
3BHA2
ARNU15
3BHA2
ARNU18
3BHA2
ARNU24
3BHA2
BG
ARNU28
3BGA2
ARNU36
3BGA2
ARNU42
3BGA2
BR
ARNU483
BRA2
B8
URNU76
3B8A2
URNU96
3B8A2
Low Static
B1
ARNU07
3B1G2
ARNU09
3B1G2
ARNU12
3B1G2
ARNU15
3B1G2
B2
ARNU18
3B2G2
ARNU24
3B2G2
Built In
B3
ARNU07
3B3G2
ARNU09
3B3G2
ARNU12
3B3G2
ARNU15
3B3G2
B4
ARNU18
3B4G2
ARNU24
3B4G2
Ceiling & Floor VE
ARNU09
3VEA2
ARNU12
3VEA2
Ceiling Suspended VJ
ARNU18
3VJA2
Floor
Standing
With Case
CE
ARNU07
3CEA2
ARNU09
3CEA2
ARNU12
3CEA2
ARNU15
3CEA2
CF
ARNU18
3CFA2
ARNU24
3CFA2
Without
Case
CE
ARNU07
3CEU2
ARNU09
3CEU2
ARNU12
3CEU2
ARNU15
3CEU2
CF
ARNU18
3CFU2
ARNU24
3CFU2
Vertical AHU
NJ
ARNU18
3NJA2
ARNU24
3NJA2
ARNU30
3NJA2
ARNU36
3NJA2
NK
ARNU42
3NKA2
ARNU48
3NKA2
ARNU54
3NKA2
External Appearance
- 5 -
Copyright2010LGElectronics.Inc.Allrightreserved.
Onlyfortrainingandservicepurposes
LGEInternalUseOnly
2. External Appearance
Wall Mounted
ART COOL Mirror
Ceiling Cassette- 1Way
Ceiling Cassette- 4Way
Ceiling & Floor
Ceiling Suspended
ARNU073TJ*2
ARNU093TJ*2
ARNU123TJ*2
Ceiling Cassette -2Way
ARNU183TL*2
ARNU243TL*2
ARNU073TR*2
ARNU093TR*2
ARNU123TR*2
ARNU153TQ*2
ARNU183TQ*2
ARNU243TP*2
ARNU283TP*2
ARNU363TN*2
ARNU423TM*2
ARNU483TM*2
Ceiling Concealed Duct - Low Static
ARNU073B1G2
ARNU093B1G2
ARNU123B1G2
ARNU153B1G2
ARNU183B2G2
ARNU243B2G2
ARNU073SE*2
ARNU093SE*2
ARNU123SE*2
ARNU153SE*2
ARNU183S5*2
ARNU243S5*2
ARNU073SE*2
ARNU093SE*2
ARNU123SE*2
ARNU153SE*2
ARNU183S8*2
ARNU243S8*2
ARNU093VEA2
ARNU123VEA2
ARNU183VJA2
ARNU243VJA2
Floor Standing
With case
ARNU073CEA2
ARNU093CEA2
ARNU123CEA2
ARNU153CEA2
ARNU183CFA2
ARNU243CFA2
Without case
ARNU073CEU2
ARNU093CEU2
ARNU123CEU2
ARNU153CEU2
ARNU183CFU2
ARNU243CFU2
Vertical AHU
ARNU183NJA2
ARNU243NJA2
ARNU303NJA2
ARNU363NJA2
ARNU423NKA2
ARNU483NKA2
ARNU543NKA2

Ceiling Concealed Duct - High Static
ARNU073BHA2
ARNU093BHA2
ARNU123BHA2
ARNU153BHA2
ARNU183BHA2
ARNU243BHA2
ARNU283BGA2
ARNU363BGA2
ARNU423BGA2
ARNU483BRA2
URNU763B8A2
URNU963B8A2
Ceiling Concealed Duct Built-in
ARNU073B3G2
ARNU093B3G2
ARNU123B3G2
ARNU153B3G2
ARNU183B4G2
ARNU243B4G2
* A:Basic, L:Plasma
* A:Basic, C:Plasma
* A:Basic, C:Plasma
* A:Basic, C:Plasma
* R:Mirror
V:Silver
B : Blue
Nomenclature
- 6 -
Copyright2010LGElectronics.Inc.Allrightreserved.
Onlyfortrainingandservicepurposes
LGEInternalUseOnly
3. Nomenclature
ARN U 3 07 A TJ 2
Generation
Chassis Name
Electrical Ratings
1:1, 115V, 60Hz 2: 1, 220V, 60Hz
6:1, 220 - 240V, 50Hz 7: 1, 100V, 50/60Hz
3:1, 208/230V, 60Hz
Total Cooling Capacity in Btu/h Class
EX) 18,000 Btu/h Class '18'
Combination of Inverter Type and
Cooling Only or Heat Pump
N: AC Inverter and H/P V: AC Inverter and C/O
U: DC Inverter and H/P and C/O
System with
Indoor Unit using R410A
LGETA:U Ex) URN
Combinations of functions
A: Basic function
L: Neo Plasma(Wall Mounted)
C:Plasma(Ceiling Cassette)
G: Low Static
U: Floor Standing without Case
ART COOL Type Panel Color
B:Blue R:Mirror V: Silver
- 7 -
Copyright2010LGElectronics.Inc.Allrightreserved.
Onlyfortrainingandservicepurposes
LGEInternalUseOnly
Part 2
Indoor Units
Ceiling Cassette
1Way.................................................................................8
2Way...............................................................................13
4Way(1)...........................................................................20
4Way(2)...........................................................................23
Art Cool Series
ARTCOOL Miror..............................................................34
ARTCOOLGallery ..........................................................45
Ceiling Concealed Duct
LowStatic ........................................................................55
BuiltIn..............................................................................62
HighStatic........................................................................67
Wall Mounted(General)
WallMounted...................................................................76
Ceiling & Floor
Ceiling&Floor
CeilingSuspended...........................................................87
Floor Standing
FloorStanding..................................................................94
Vertical Air Handling Unit................................................117
- 8 -
Copyright2010LGElectronics.Inc.Allrightreserved.
Onlyfortrainingandservicepurposes
LGEInternalUseOnly
1. Functions ......................................................................................9
2. Operation Details........................................................................10
3. Dimensions .................................................................................12
Ceiling Mounted Cassette Type (1Way)
- 9 -
Copyright2010LGElectronics.Inc.Allrightreserved.
Onlyfortrainingandservicepurposes
LGEInternalUseOnly
Functions
1. Functions
Indoor Unit
Operation ON/OFF by Remote controller
Sensing the Room Temperature
Room temperature control
Starting Current Control
Indoor Fan Speed Control
Soft Dry Operation Mode
Airflow Direction Control
Deice (defrost) control (Heating)
Auto Restart
Hot-start Control (Heating)
The indoor fan does not rotate until the evaporator pip-
ingtemperaturewillbereachedat25C(76F).
Compact and light design
To install a unit is very convenient because of smaller
sizethantextile.
Low noise
Themostadvancedlow-noisedesign.
Theadoptionofturbofanandroundtypeheatexchang-
ergivethequietestoperation.
Long life filter
Longlifewrinkle(type)andwashableandanti-bacteria
filterisadopted.
High head Drain pump
Built-indrainpumpautomaticallydrainswater.
Astandarddrain-headheightofupto700mm(27-9/16inch)is
possible.
High-Ceiling corresponding Function
Accordingtotheheightofceiling,theRPMofindoorfan
motorisselectedtoincreaseairreachingdistance.
Central Control(Optional) Itisoperatingindividuallyortotallybycentralcontrolfunction.
Roomtemperaturesensor.(Thermistor)
MaintainstheroomtemperatureinaccordancewiththeSettingTemperature.
Indoorfanisdelayedfor5secondsatthestarting.
Jet,High,Med,Low,Lolow
Intermittentoperationoffanatlowspeed.
Thelouvercanbesetatswingupanddownautomatically.
Althoughtheair-conditioneristurnedoffbyapowerfailure,itisrestartedauto-
maticallypreviousoperationmodeafterpowersupply.
Boththeindoorandoutdoorfanstopsduringdefrosting.
Hotstartafterdefrostends.
- 10 -
Copyright2010LGElectronics.Inc.Allrightreserved.
Onlyfortrainingandservicepurposes
LGEInternalUseOnly
2. Operation Detail
n Auto Swing Control
Thisfunctionistoswingthelouverupanddownautomatically.
n Soft-Dry Operation
Theindoorfanspeedisautomaticallysettothelow,sotheshiftoftheindoorfanspeedisimpossiblebecauseof
alreadybeingsettothebestspeedforDryOperationbymicrocontrollercontrol.
n Cooling Mode Operation
WhenselectingtheCooling( )ModeOperation,theunitwilloperateaccordingtothesettingbytheremotecon-
trollerandtheoperationdiagramisasfollowing
(1) The function of main control
Operation Detail
Thermal ON Thermal OFF
IndoorUnitmode ST+0.5 ST-0.5
2TH(Remo.+Indoor)
Tobeselectedhighertemperature Tobeselectedhighertemperature
contrastIndoorUnitandRemo. contrastIndoorUnitandRemo.
Remo.Mode ST+0.5 ST-0.5
IntakeAirTemperature
Thermo.ON
(SETTEMPERATURE
+0.5C(33F))
Thermo.OFF
(SETTEMPERATURE
Morethan Morethan
-0.5C(33F))
3minutes 3minutes
Selected Selected Selected
Speed Speed Speed
INDOORFAN LowLow
- 11 -
Copyright2010LGElectronics.Inc.Allrightreserved.
Onlyfortrainingandservicepurposes
LGEInternalUseOnly
n Heating Mode Operation
Theunitwilloperateaccordingtothesettingbytheremotecontrollerandtheoperationdiagramisshownasfollowing.
n Hot-start Control
Theindoorfandoesnorotateuntiltheevaporatorpipingtemperaturewillbereachedto25C(76F).
Theoperationdiagramisasfollowing.
35C(94F)
30C(86F)
27C(80F)
25C(76F)
22C(72F)
Pipe
temperature
OFF
Indoor fan
speed
LO
LOW
LOW
SELECTED
FAN
LOW LOLOW
COMP ON
Operation Detail
Thermal

OFF

ON
OFF ON
ON
ON Outdoor fan
Indoor fan
4 Way ON
Room
Temperature
Thermal Off
Thermal On
Indoor pipe
Temperature
33C(92F)
25C(76F)
20C(68F)
36C(96F)
Minimum
3min
Setting
fan
speed
Setting
fan
speed
Setting
fan
speed
Stop Low Stop Stop Low Low Low Low
ThermalON ThermalOFF
IndoorUnitmode ST+2 ST+4
2TH Tobeselectedlowertemperature Tobeselectedlowertemperature
(Remo.+Indoor) contrastIndoorUnitandRemo. contrastIndoorUnitandRemo.
Remo.mode ST+0 ST+2
- 12 -
Copyright2010LGElectronics.Inc.Allrightreserved.
Onlyfortrainingandservicepurposes
LGEInternalUseOnly
3. Dimensions
Dimensions
7
6
,

S
e
o
n
g
s
a
n
-
d
o
n
g
,

C
h
a
n
g
w
o
n

C
i
t
y
,

G
y
e
o
n
g
n
a
m
,
6
4
1
-
7
1
3
,

K
o
r
e
a
C
H
A
S
S
I
S

C
O
D
E
:

T
U
C
e
i
l
i
n
g

C
a
s
s
e
t
t
e

1
-
w
a
y
A
R
N
U
0
7
G
T
U
*
2
A
R
N
U
0
9
G
T
U
*
2
A
R
N
U
1
2
G
T
U
*
2
N
a
m
e

1

L
i
q
u
i
d

p
i
p
e

c
o
n
n
e
c
t
i
o
n

U
n
i
t

s
i
z
e
(
7
k
,

9
k
,

1
2
k
)
:

6
.
3
5

2

G
a
s

p
i
p
e

c
o
n
n
e
c
t
i
o
n

U
n
i
t

s
i
z
e
(
7
k
,

9
k
,

1
2
k
)
:

1
2
.
7


3

A
i
r

s
u
c
t
i
o
n

g
r
i
l
l



4

A
i
r

d
i
s
c
h
a
r
g
e

g
r
i
l
l

N
u
m
b
e
r
D
e
s
c
r
i
p
i
t
i
o
n
N
o
t
e
1
.

U
n
i
t

s
h
o
u
l
d

b
e

i
n
s
t
a
l
l
e
d

i
n

c
o
m
p
l
i
a
n
c
e

w
i
t
h

t
h
e

i
n
s
t
a
l
l
a
t
i
o
n

m
a
n
u
a
l





i
n

t
h
e

p
r
o
d
u
c
t

b
o
x
.
2
.

U
n
i
t

s
h
a
l
l

b
e

g
r
o
u
n
d
e
d

i
n

a
c
c
o
r
d
a
n
c
e

w
i
t
h

t
h
e

l
o
c
a
l

r
e
g
u
l
a
t
i
o
n
s

o
r





a
p
p
l
i
c
a
b
l
e

n
a
t
i
o
n
a
l

c
o
d
e
s
.
(
u
n
i
t

:

m
m
)
1
,
1
0
0
5 0 03 4
8
8
1
(
A
i
r

o
u
t
l
e
t

H
o
l
e
)
1 6 8 . 3
1 0 6 . 8
2 0 6 . 6
2 7 5 . 8
9 6 . 5
5 7 . 4
4
5
3
2
7
3
2
0
.
5
1
0
1
2
8
8
8
6
1
(
P
a
n
e
l

N
a
m
e
:

P
T
-
U
U
C
)
Dimensions
- 13 -
Copyright2010LGElectronics.Inc.Allrightreserved.
Onlyfortrainingandservicepurposes
LGEInternalUseOnly
7
6
,

S
e
o
n
g
s
a
n
-
d
o
n
g
,

C
h
a
n
g
w
o
n

C
i
t
y
,

G
y
e
o
n
g
n
a
m
,
6
4
1
-
7
1
3
,

K
o
r
e
a
C
H
A
S
S
I
S

C
O
D
E
:

T
U
C
e
i
l
i
n
g

C
a
s
s
e
t
t
e

1
-
w
a
y
A
R
N
U
0
7
G
T
U
*
2
A
R
N
U
0
9
G
T
U
*
2
A
R
N
U
1
2
G
T
U
*
2
N
a
m
e

1

L
i
q
u
i
d

p
i
p
e

c
o
n
n
e
c
t
i
o
n

U
n
i
t

s
i
z
e
(
7
k
,

9
k
,

1
2
k
)
:

6
.
3
5

2

G
a
s

p
i
p
e

c
o
n
n
e
c
t
i
o
n

U
n
i
t

s
i
z
e
(
7
k
,

9
k
,

1
2
k
)
:

1
2
.
7


3

A
i
r

s
u
c
t
i
o
n

g
r
i
l
l



4

A
i
r

d
i
s
c
h
a
r
g
e

g
r
i
l
l

N
u
m
b
e
r
D
e
s
c
r
i
p
i
t
i
o
n
N
o
t
e
1
.

U
n
i
t

s
h
o
u
l
d

b
e

i
n
s
t
a
l
l
e
d

i
n

c
o
m
p
l
i
a
n
c
e

w
i
t
h

t
h
e

i
n
s
t
a
l
l
a
t
i
o
n

m
a
n
u
a
l





i
n

t
h
e

p
r
o
d
u
c
t

b
o
x
.
2
.

U
n
i
t

s
h
a
l
l

b
e

g
r
o
u
n
d
e
d

i
n

a
c
c
o
r
d
a
n
c
e

w
i
t
h

t
h
e

l
o
c
a
l

r
e
g
u
l
a
t
i
o
n
s

o
r





a
p
p
l
i
c
a
b
l
e

n
a
t
i
o
n
a
l

c
o
d
e
s
.
(
u
n
i
t

:

m
m
)
(
P
a
n
e
l

N
a
m
e
:

P
T
-
U
U
D
)
4 5 3
4 6 . 5
5 7 . 4
3 4
1 1 7
9 6 . 5
1 6 8 . 3
1 0 6 . 8
2 0 6 . 3
2 7 5 . 8
1
0
9
.
5
8
6
1
1
0
1
2
8
8
1
1
0
0
1
0
9
.
5
4
5
3
3
2
0
.
5
2
7
5 0 0
3 5 4 . 3
- 14 -
Copyright2010LGElectronics.Inc.Allrightreserved.
Onlyfortrainingandservicepurposes
LGEInternalUseOnly
Dimensions
7
6
,

S
e
o
n
g
s
a
n
-
d
o
n
g
,

C
h
a
n
g
w
o
n

C
i
t
y
,

G
y
e
o
n
g
n
a
m
,
6
4
1
-
7
1
3
,

K
o
r
e
a
C
H
A
S
S
I
S

C
O
D
E
:

T
T
C
e
i
l
i
n
g

C
a
s
s
e
t
t
e

1
-
w
a
y
A
R
N
U
1
8
G
T
T
*
2
A
R
N
U
2
4
G
T
T
*
2
N
a
m
e

1

L
i
q
u
i
d

p
i
p
e

c
o
n
n
e
c
t
i
o
n

U
n
i
t

s
i
z
e
(
1
8
k
)
:

6
.
3
5
,

(
2
4
k
)
:

9
.
5
2

2

G
a
s

p
i
p
e

c
o
n
n
e
c
t
i
o
n

U
n
i
t

s
i
z
e
(
1
8
k
)
:

1
2
.
7
,

(
2
4
k
)
:

1
5
.
8
8


3

A
i
r

s
u
c
t
i
o
n

g
r
i
l
l



4

A
i
r

d
i
s
c
h
a
r
g
e

g
r
i
l
l

N
u
m
b
e
r
D
e
s
c
r
i
p
i
t
i
o
n
N
o
t
e
1
.

U
n
i
t

s
h
o
u
l
d

b
e

i
n
s
t
a
l
l
e
d

i
n

c
o
m
p
l
i
a
n
c
e

w
i
t
h

t
h
e

i
n
s
t
a
l
l
a
t
i
o
n

m
a
n
u
a
l





i
n

t
h
e

p
r
o
d
u
c
t

b
o
x
.
2
.

U
n
i
t

s
h
a
l
l

b
e

g
r
o
u
n
d
e
d

i
n

a
c
c
o
r
d
a
n
c
e

w
i
t
h

t
h
e

l
o
c
a
l

r
e
g
u
l
a
t
i
o
n
s

o
r





a
p
p
l
i
c
a
b
l
e

n
a
t
i
o
n
a
l

c
o
d
e
s
.
(
u
n
i
t

:

m
m
)
2 0 . 6
6 5 . 3
1 8 0 . 6
2 4 7 . 5
4 5 3 . 8
5 7 . 4
9 1
9 6 . 1
1 7 3 . 8
3 1 . 7
4
5
3
.
8
1
,
4
2
0
5 0 0
3 4
1
,
2
0
1
(
A
i
r

O
u
t
l
e
t

H
o
l
e
)
6
5
.
1
1
3
3
2
1
1
7
6
.
4
(
P
a
n
e
l

N
a
m
e
:

P
T
-
U
T
C
)
Dimensions
- 15 -
Copyright2010LGElectronics.Inc.Allrightreserved.
Onlyfortrainingandservicepurposes
LGEInternalUseOnly
7
6
,

S
e
o
n
g
s
a
n
-
d
o
n
g
,

C
h
a
n
g
w
o
n

C
i
t
y
,

G
y
e
o
n
g
n
a
m
,
6
4
1
-
7
1
3
,

K
o
r
e
a
C
H
A
S
S
I
S

C
O
D
E
:

T
T
C
e
i
l
i
n
g

C
a
s
s
e
t
t
e

1
-
w
a
y
A
R
N
U
1
8
G
T
T
*
2
A
R
N
U
2
4
G
T
T
*
2
N
a
m
e

1

L
i
q
u
i
d

p
i
p
e

c
o
n
n
e
c
t
i
o
n

U
n
i
t

s
i
z
e
(
1
8
k
)
:

6
.
3
5
,

(
2
4
k
)
:

9
.
5
2

2

G
a
s

p
i
p
e

c
o
n
n
e
c
t
i
o
n

U
n
i
t

s
i
z
e
(
1
8
k
)
:

1
2
.
7
,

(
2
4
k
)
:

1
5
.
8
8


3

A
i
r

s
u
c
t
i
o
n

g
r
i
l
l



4

A
i
r

d
i
s
c
h
a
r
g
e

g
r
i
l
l

N
u
m
b
e
r
D
e
s
c
r
i
p
i
t
i
o
n
N
o
t
e
1
.

U
n
i
t

s
h
o
u
l
d

b
e

i
n
s
t
a
l
l
e
d

i
n

c
o
m
p
l
i
a
n
c
e

w
i
t
h

t
h
e

i
n
s
t
a
l
l
a
t
i
o
n

m
a
n
u
a
l





i
n

t
h
e

p
r
o
d
u
c
t

b
o
x
.
2
.

U
n
i
t

s
h
a
l
l

b
e

g
r
o
u
n
d
e
d

i
n

a
c
c
o
r
d
a
n
c
e

w
i
t
h

t
h
e

l
o
c
a
l

r
e
g
u
l
a
t
i
o
n
s

o
r





a
p
p
l
i
c
a
b
l
e

n
a
t
i
o
n
a
l

c
o
d
e
s
.
(
u
n
i
t

:

m
m
)
(
P
a
n
e
l

N
a
m
e
:

P
T
-
U
T
D
)
1
0
9
.
5
4 4
1 3 2
1 5 . 2

1
4
5 7
3 4
5 0 0
4 6 . 5
2 0 . 6
6 5 . 3
1 8 0 . 6
2 4 7 . 5
4 5 3 . 8
3 1 . 7
5 7 . 4
1 7 3 . 8
9 7 . 1
9 1
1
0
9
.
5
1
4
2
0
4
5
3
.
8
3
3
5
9
6
.
5
2
2
.
3
6
5
.
1
1
1
7
6
.
4
1
3
3
2
- 16 -
Copyright2010LGElectronics.Inc.Allrightreserved.
Onlyfortrainingandservicepurposes
LGEInternalUseOnly
1. Functions ....................................................................................17
2. Operation Details........................................................................18
3. Dimensions .................................................................................20
Ceiling Mounted Cassette Type (2Way)
- 17 -
Copyright2010LGElectronics.Inc.Allrightreserved.
Onlyfortrainingandservicepurposes
LGEInternalUseOnly
1. Functions
Indoor Unit
Operation ON/OFF by Remote controller
Sensing the Room Temperature
Room temperature control
Starting Current Control
Indoor Fan Speed Control
Soft Dry Operation Mode
Airflow Direction Control
Deice (defrost) control (Heating)
Auto Restart
Hot-start Control (Heating)
The indoor fan does not rotate until the evaporator pip-
ingtemperaturewillbereachedat25C(76F).
Compact and light design
To install a unit is very convenient because of smaller
sizethantextile.
Low noise
Themostadvancedlow-noisedesign.
Theadoptionofturbofanandroundtypeheatexchang-
ergivethequietestoperation.
Long life filter
Longlifewrinkle(type)andwashableandanti-bacteria
filterisadopted.
High head Drain pump
Built-indrainpumpautomaticallydrainswater.
Astandarddrain-headheightofupto700mm
(27-9/16inch)ispossible.
High-Ceiling corresponding Function
Accordingtotheheightofceiling,theRPMofindoorfan
motorisselectedtoincreaseairreachingdistance.
Central Control(Optional) Itisoperatingindividuallyortotallybycentralcontrolfunction.
Roomtemperaturesensor.(Thermistor)
MaintainstheroomtemperatureinaccordancewiththeSettingTemperature.
Indoorfanisdelayedfor5secondsatthestarting.
Jet,High,Med,Low,Lolow
Intermittentoperationoffanatlowspeed.
Thelouvercanbesetatswingupanddownautomatically.
Althoughtheair-conditioneristurnedoffbyapowerfailure,itisrestartedauto-
maticallypreviousoperationmodeafterpowersupply.
Boththeindoorandoutdoorfanstopsduringdefrosting.
Hotstartafterdefrostends.
Functions
- 18 -
Copyright2010LGElectronics.Inc.Allrightreserved.
Onlyfortrainingandservicepurposes
LGEInternalUseOnly
2. Operation Detail
n Auto Swing Control
Thisfunctionistoswingthelouverupanddownautomatically.
n Soft-Dry Operation
Theindoorfanspeedisautomaticallysettothelow,sotheshiftoftheindoorfanspeedisimpossiblebecauseof
alreadybeingsettothebestspeedforDryOperationbymicrocontrollercontrol.
n Cooling Mode Operation
WhenselectingtheCooling( )ModeOperation,theunitwilloperateaccordingtothesettingbytheremotecon-
trollerandtheoperationdiagramisasfollowing
(1) The function of main control
Operation Detail
Thermal ON Thermal OFF
IndoorUnitmode ST+0.5 ST-0.5
2TH(Remo.+Indoor)
Tobeselectedhighertemperature Tobeselectedhighertemperature
contrastIndoorUnitandRemo. contrastIndoorUnitandRemo.
Remo.Mode ST+0.5 ST-0.5
IntakeAirTemperature
Thermo.ON
(SETTEMPERATURE
+0.5C(33F))
Thermo.OFF
(SETTEMPERATURE
Morethan Morethan
-0.5C(33F))
3minutes 3minutes
Selected Selected Selected
Speed Speed Speed
INDOORFAN LowLow
- 19 -
Copyright2010LGElectronics.Inc.Allrightreserved.
Onlyfortrainingandservicepurposes
LGEInternalUseOnly
n Heating Mode Operation
Theunitwilloperateaccordingtothesettingbytheremotecontrollerandtheoperationdiagramisshownasfollowing.
n Hot-start Control
Theindoorfandoesnorotateuntiltheevaporatorpipingtemperaturewillbereachedto25C(76F).
Theoperationdiagramisasfollowing.
35C(94F)
30C(86F)
27C(80F)
25C(76F)
22C(72F)
Pipe
temperature
OFF
Indoor fan
speed
LO
LOW
LOW
SELECTED
FAN
LOW LOLOW
COMP ON
Operation Detail
Thermal

OFF

ON
OFF ON
ON
ON Outdoor fan
Indoor fan
4 Way ON
Room
Temperature
Thermal Off
Thermal On
Indoor pipe
Temperature
33C(92F)
25C(76F)
20C(68F)
36C(96F)
Minimum
3min
Setting
fan
speed
Setting
fan
speed
Setting
fan
speed
Stop Low Stop Stop Low Low Low Low
ThermalON ThermalOFF
IndoorUnitmode ST+2 ST+4
2TH Tobeselectedlowertemperature Tobeselectedlowertemperature
(Remo.+Indoor) contrastIndoorUnitandRemo. contrastIndoorUnitandRemo.
Remo.mode ST+0 ST+2
- 20 -
Copyright2010LGElectronics.Inc.Allrightreserved.
Onlyfortrainingandservicepurposes
LGEInternalUseOnly
3. Dimensions
Dimensions
8
3
0
(
3
2
-
1
1
/
1
6
)
A
B
4
7
.
9
(
1
-
7
/
8
)
2 7 5 ( 1 0 - 1 3 / 1 6 )
5 5 0 ( 2 1 - 1 1 / 1 6 )
6 9 . 5 ( 2 - 3 / 4 )
8
8
9
.
2
(
3
5
)
1
0
5
0
(
4
1
-
5
/
1
6
)
6 4 0 ( 2 5 - 3 / 1 6 )
2
8
.
5
(
1
-
1
/
8
)
4
2
1
3
T
L
AB
2
2
5
(
8
-
7
/
8
)
1
2
6
.
5
(
5
)
7
6
,

S
e
o
n
g
s
a
n
-
d
o
n
g
,

C
h
a
n
g
w
o
n

C
i
t
y
,

G
y
e
o
n
g
n
a
m
,
6
4
1
-
7
1
3
,

K
o
r
e
a
w
w
w
.
l
g
e
a
i
r
c
o
n
.
c
o
m
C
H
A
S
S
I
S

C
O
D
E
:

T
L
C
e
i
l
i
n
g

C
a
s
s
e
t
t
e

2
-
w
a
y
A
R
N
U
1
8
3
T
L
*
2





A
R
N
U
2
4
3
T
L
*
2
N
a
m
e
1
L
i
q
u
i
d

p
i
p
e

c
o
n
n
e
c
t
i
o
n
(
1
8
k
)

6
.
3
5
(
1
/
4
)
,

(
2
4
k
)

9
.
5
2
(
3
/
8
)
2
G
a
s

p
i
p
e

c
o
n
n
e
c
t
i
o
n
(
1
8
k
)

1
2
.
7
(
1
/
2
)
,

(
2
4
k
)

1
5
.
8
8
(
5
/
8
)

3
A
i
r

s
u
c
t
i
o
n

g
r
i
l
l


4
A
i
r

d
i
s
c
h
a
r
g
e

g
r
i
l
l

N
u
m
b
e
r
D
e
s
c
r
i
p
i
t
i
o
n
N
o
t
e
1
.

U
n
i
t

s
h
o
u
l
d

b
e

i
n
s
t
a
l
l
e
d

i
n

c
o
m
p
l
i
a
n
c
e

w
i
t
h

t
h
e

i
n
s
t
a
l
l
a
t
i
o
n

m
a
n
u
a
l





i
n

t
h
e

p
r
o
d
u
c
t

b
o
x
.
2
.

U
n
i
t

s
h
a
l
l

b
e

g
r
o
u
n
d
e
d

i
n

a
c
c
o
r
d
a
n
c
e

w
i
t
h

t
h
e

l
o
c
a
l

r
e
g
u
l
a
t
i
o
n
s

o
r





a
p
p
l
i
c
a
b
l
e

n
a
t
i
o
n
a
l

c
o
d
e
s
.
[
U
n
i
t

:

m
m
(
i
n
c
h
)
]
L
G

E
l
e
c
t
r
o
n
i
c
s

U
S
A
,

H
V
A
C

D
i
v
i
s
i
o
n
1
0
0
0

S
y
l
v
a
n

A
v
e
n
u
e
,

E
n
g
l
e
w
o
o
d

C
l
i
f
f
s
,

N
J

0
7
6
3
2
w
w
w
.
l
g
u
s
a
.
c
o
m

/

w
w
w
.
l
g
h
v
a
c
.
c
o
m
- 21 -
Copyright2010LGElectronics.Inc.Allrightreserved.
Onlyfortrainingandservicepurposes
LGEInternalUseOnly
1. Functions ....................................................................................22
2. Operation Details........................................................................23
3. Dimensions .................................................................................25
Ceiling Mounted Cassette Type (4Way) (1)
- 22 -
Copyright2010LGElectronics.Inc.Allrightreserved.
Onlyfortrainingandservicepurposes
LGEInternalUseOnly
1. Functions
Indoor Unit
Operation ON/OFF by Remote controller
Sensing the Room Temperature
Room temperature control
Starting Current Control
Indoor Fan Speed Control
Soft Dry Operation Mode
Airflow Direction Control
Deice (defrost) control (Heating)
Auto Restart
Hot-start Control (Heating)
The indoor fan does not rotate until the evaporator pip-
ingtemperaturewillbereachedat25C(76F).
Compact and light design
To install a unit is very convenient because of smaller
sizethantextile.
Low noise
Themostadvancedlow-noisedesign.
Theadoptionofturbofanandroundtypeheatexchang-
ergivethequietestoperation.
Long life filter
Longlifewrinkle(type)andwashableandanti-bacteria
filterisadopted.
High head Drain pump
Built-indrainpumpautomaticallydrainswater.
Astandarddrain-headheightofupto700mm
(27-9/16inch)ispossible.
High-Ceiling corresponding Function
Accordingtotheheightofceiling,theRPMofindoorfan
motorisselectedtoincreaseairreachingdistance.
Central Control(Optional)
Swirl Swing Control
Itisoperatingindividuallyortotallybycentralcontrolfunction.
Itisoperatingswirlswing
Roomtemperaturesensor.(Thermistor)
MaintainstheroomtemperatureinaccordancewiththeSettingTemperature.
Indoorfanisdelayedfor5secondsatthestarting.
Jet,High,Med,Low,Lolow
Intermittentoperationoffanatlowspeed.
Thelouvercanbesetatswingupanddownautomatically.
Althoughtheair-conditioneristurnedoffbyapowerfailure,itisrestartedauto-
maticallypreviousoperationmodeafterpowersupply.
Boththeindoorandoutdoorfanstopsduringdefrosting.
Hotstartafterdefrostends.
Functions
- 23 -
Copyright2010LGElectronics.Inc.Allrightreserved.
Onlyfortrainingandservicepurposes
LGEInternalUseOnly
2. Operation Detail
n Auto Swing Control
Thisfunctionistoswingthelouverupanddownautomatically.
n Soft-Dry Operation
Theindoorfanspeedisautomaticallysettothelow,sotheshiftoftheindoorfanspeedisimpossiblebecauseof
alreadybeingsettothebestspeedforDryOperationbymicrocontrollercontrol.
n Cooling Mode Operation
WhenselectingtheCooling( )ModeOperation,theunitwilloperateaccordingtothesettingbytheremotecon-
trollerandtheoperationdiagramisasfollowing
n Swirl Swing Control
Vane2,4isalmostvaneclosedwhilevane1,3isopened.
Vane1,3andvane2,4turnoverminutely
(1) The function of main control
Operation Detail
Vane 2
Vane 1 Vane 3
Vane 4
Thermal ON Thermal OFF
IndoorUnitmode ST+0.5 ST-0.5
2TH(Remo.+Indoor)
Tobeselectedhighertemperature Tobeselectedhighertemperature
contrastIndoorUnitandRemo. contrastIndoorUnitandRemo.
Remo.Mode ST+0.5 ST-0.5
IntakeAirTemperature
Thermo.ON
(SETTEMPERATURE
+0.5C(33F))
Thermo.OFF
(SETTEMPERATURE
Morethan Morethan
-0.5C(33F))
3minutes 3minutes
Selected Selected Selected
Speed Speed Speed
INDOORFAN LowLow
- 24 -
Copyright2010LGElectronics.Inc.Allrightreserved.
Onlyfortrainingandservicepurposes
LGEInternalUseOnly
n Heating Mode Operation
Theunitwilloperateaccordingtothesettingbytheremotecontrollerandtheoperationdiagramisshownasfollowing.
n Hot-start Control
Theindoorfandoesnorotateuntiltheevaporatorpipingtemperaturewillbereachedto25C(76F).
Theoperationdiagramisasfollowing.
35C(94F)
30C(86F)
27C(80F)
25C(76F)
22C(72F)
Pipe
temperature
OFF
Indoor fan
speed
LO
LOW
LOW
SELECTED
FAN
LOW LOLOW
COMP ON
Operation Detail
Thermal

OFF

ON
OFF ON
ON
ON Outdoor fan
Indoor fan
4 Way ON
Room
Temperature
Thermal Off
Thermal On
Indoor pipe
Temperature
33C(92F)
25C(76F)
20C(68F)
36C(96F)
Minimum
3min
Setting
fan
speed
Setting
fan
speed
Setting
fan
speed
Stop Low Stop Stop Low Low Low Low
ThermalON ThermalOFF
IndoorUnitmode ST+2 ST+4
2TH Tobeselectedlowertemperature Tobeselectedlowertemperature
(Remo.+Indoor) contrastIndoorUnitandRemo. contrastIndoorUnitandRemo.
Remo.mode ST+0 ST+2
- 25 -
Copyright2010LGElectronics.Inc.Allrightreserved.
Onlyfortrainingandservicepurposes
LGEInternalUseOnly
3. Dimensions
Dimensions
7
6
,

S
e
o
n
g
s
a
n
-
d
o
n
g
,

C
h
a
n
g
w
o
n

C
i
t
y
,

G
y
e
o
n
g
n
a
m
,
6
4
1
-
7
1
3
,

K
o
r
e
a
C
H
A
S
S
I
S

C
O
D
E
:

T
R
C
e
i
l
i
n
g

C
a
s
s
e
t
t
e

4
-
w
a
y
A
R
N
U
0
5
G
T
R
*
2
A
R
N
U
0
7
G
T
R
*
2
A
R
N
U
0
9
G
T
R
*
2
A
R
N
U
1
2
G
T
R
*
2
N
a
m
e

1

L
i
q
u
i
d

p
i
p
e

c
o
n
n
e
c
t
i
o
n

U
n
i
t

s
i
z
e
(
5
k
,

7
k
,

9
k
,

1
2
k
)
:

6
.
3
5

2

G
a
s

p
i
p
e

c
o
n
n
e
c
t
i
o
n

U
n
i
t

s
i
z
e
(
5
k
,

7
k
,

9
k
,

1
2
k
)
:

1
2
.
7

3

D
r
a
i
n

p
i
p
e

c
o
n
n
e
c
t
i
o
n

V
P
2
5
(

3
2
)


4

P
o
w
e
r

s
u
p
p
l
y

c
o
n
n
e
c
t
i
o
n


5

A
i
r

d
i
s
c
h
a
r
g
e

g
r
i
l
l


6

A
i
r

s
u
c
t
i
o
n

g
r
i
l
l

N
u
m
b
e
r
D
e
s
c
r
i
p
i
t
i
o
n
N
o
t
e
1
.

U
n
i
t

s
h
o
u
l
d

b
e

i
n
s
t
a
l
l
e
d

i
n

c
o
m
p
l
i
a
n
c
e

w
i
t
h

t
h
e

i
n
s
t
a
l
l
a
t
i
o
n

m
a
n
u
a
l





i
n

t
h
e

p
r
o
d
u
c
t

b
o
x
.
2
.

U
n
i
t

s
h
a
l
l

b
e

g
r
o
u
n
d
e
d

i
n

a
c
c
o
r
d
a
n
c
e

w
i
t
h

t
h
e

l
o
c
a
l

r
e
g
u
l
a
t
i
o
n
s

o
r





a
p
p
l
i
c
a
b
l
e

n
a
t
i
o
n
a
l

c
o
d
e
s
.
(
u
n
i
t

:

m
m
)
5
7
0
5 7 0
5
1
7
6
9
1 2 8
5 1 7
B
A
B

A
R
R
O
W

V
I
E
W
A

A
R
R
O
W

V
I
E
W
4
6
1
5 2 3
2 1 4
5 3
8 4 . 5 5 9 . 5
7 94 8
1
4
2
.
5
3
0
1
9
5
7
0 1
6
5
6
3
3 4 . 5
2
3
1
4
B
r
a
n
c
h

D
u
c
t

C
o
n
n
e
c
t
i
o
n
R
3
5
7 0 0
2 2 . 5
3
8
0
(
A
i
r

o
u
t
l
e
t

h
o
l
e
)
4
7
3
7
0
0
3 7 6 ( I n l e t G r i l l e )
4
R
2
0
56
C
E
I
L
I
N
G

O
P
E
N
I
N
G
5
0
0
m
m
o
r
m
o
r
e
*
5
0
0
m
m
o
r
m
o
r
e
*


R
E
Q
U
I
R
E
D

S
P
A
C
E
5
0
0
m
m
o
r
m
o
r
e
*
5
0
0
m
m
o
r
m
o
r
e
*
- 26 -
Copyright2010LGElectronics.Inc.Allrightreserved.
Onlyfortrainingandservicepurposes
LGEInternalUseOnly
Dimensions
7
6
,

S
e
o
n
g
s
a
n
-
d
o
n
g
,

C
h
a
n
g
w
o
n

C
i
t
y
,

G
y
e
o
n
g
n
a
m
,
6
4
1
-
7
1
3
,

K
o
r
e
a
C
H
A
S
S
I
S

C
O
D
E
:

T
Q
C
e
i
l
i
n
g

C
a
s
s
e
t
t
e

4
-
w
a
y
A
R
N
U
1
5
G
T
Q
*
2
A
R
N
U
1
8
G
T
Q
*
2
N
a
m
e

1

L
i
q
u
i
d

p
i
p
e

c
o
n
n
e
c
t
i
o
n

U
n
i
t

s
i
z
e
(
1
5
k
,

1
8
k
)
:

6
.
3
5

2

G
a
s

p
i
p
e

c
o
n
n
e
c
t
i
o
n

U
n
i
t

s
i
z
e
(
1
5
k
,

1
8
k
)
:

1
2
.
7

3

D
r
a
i
n

p
i
p
e

c
o
n
n
e
c
t
i
o
n


4

P
o
w
e
r

s
u
p
p
l
y

c
o
n
n
e
c
t
i
o
n


5

A
i
r

d
i
s
c
h
a
r
g
e

g
r
i
l
l


6

A
i
r

s
u
c
t
i
o
n

g
r
i
l
l

N
u
m
b
e
r
D
e
s
c
r
i
p
i
t
i
o
n
N
o
t
e
1
.

U
n
i
t

s
h
o
u
l
d

b
e

i
n
s
t
a
l
l
e
d

i
n

c
o
m
p
l
i
a
n
c
e

w
i
t
h

t
h
e

i
n
s
t
a
l
l
a
t
i
o
n

m
a
n
u
a
l





i
n

t
h
e

p
r
o
d
u
c
t

b
o
x
.
2
.

U
n
i
t

s
h
a
l
l

b
e

g
r
o
u
n
d
e
d

i
n

a
c
c
o
r
d
a
n
c
e

w
i
t
h

t
h
e

l
o
c
a
l

r
e
g
u
l
a
t
i
o
n
s

o
r





a
p
p
l
i
c
a
b
l
e

n
a
t
i
o
n
a
l

c
o
d
e
s
.
(
u
n
i
t

:

m
m
)
5
7
0
5 7 0
5
1
7
6
8
1 7 4
5 1 7
4
6
1
5 2 3
3
0
1
9
1
4
2
.
5
1
6
5
6
3
9 5 . 5
7 94 8
1 2 5 5 9 . 5
5
7
0
7 6
9 4
2 5 6
2
4
3
1
B
r
a
n
c
h

D
u
c
t

C
o
n
n
e
c
t
i
o
n
R
3
5
7 0 0
2 2 . 5
3
8
0
(
A
i
r

o
u
t
l
e
t

h
o
l
e
)
4
7
3
7
0
0
3 7 6 ( I n l e t G r i l l e )
4
R
2
0
56
B

A
R
R
O
W

V
I
E
W
A

A
R
R
O
W

V
I
E
W
B
A
V
P
2
5
(

3
2
)

C
E
I
L
I
N
G

O
P
E
N
I
N
G
5
0
0
m
m

o
r

m
o
r
e
*
5
0
0
m
m

o
r

m
o
r
e
*


R
E
Q
U
I
R
E
D

S
P
A
C
E
5
0
0
m
m

o
r

m
o
r
e
*
5
0
0
m
m

o
r

m
o
r
e
*
- 27 -
Copyright2010LGElectronics.Inc.Allrightreserved.
Onlyfortrainingandservicepurposes
LGEInternalUseOnly
1. Functions ....................................................................................28
2. Operation Details........................................................................29
3. Dimensions .................................................................................31
Ceiling Mounted Cassette Type (4Way) (2)
- 28 -
Copyright2010LGElectronics.Inc.Allrightreserved.
Onlyfortrainingandservicepurposes
LGEInternalUseOnly
1. Functions
Indoor Unit
Operation ON/OFF by Remote controller
Sensing the Room Temperature
Room temperature control
Starting Current Control
Indoor Fan Speed Control
Soft Dry Operation Mode
Airflow Direction Control
Deice (defrost) control (Heating)
Auto Restart
Hot-start Control (Heating)
The indoor fan does not rotate until the evaporator pip-
ingtemperaturewillbereachedat25C(76F).
Compact and light design
To install a unit is very convenient because of smaller
sizethantextile.
Low noise
Themostadvancedlow-noisedesign.
Theadoptionofturbofanandroundtypeheatexchang-
ergivethequietestoperation.
Long life filter
Longlifewrinkle(type)andwashableandanti-bacteria
filterisadopted.
High head Drain pump
Built-indrainpumpautomaticallydrainswater.
Astandarddrain-headheightofupto700mm
(27-9/16inch)ispossible.
High-Ceiling corresponding Function
Accordingtotheheightofceiling,theRPMofindoorfan
motorisselectedtoincreaseairreachingdistance.
Central Control(Optional)
Swirl Swing Control
Itisoperatingindividuallyortotallybycentralcontrolfunction.
Itisoperatingswirlswing
Roomtemperaturesensor.(Thermistor)
MaintainstheroomtemperatureinaccordancewiththeSettingTemperature.
Indoorfanisdelayedfor5secondsatthestarting.
Jet,High,Med,Low,Lolow
Intermittentoperationoffanatlowspeed.
Thelouvercanbesetatswingupanddownautomatically.
Althoughtheair-conditioneristurnedoffbyapowerfailure,itisrestartedauto-
maticallypreviousoperationmodeafterpowersupply.
Boththeindoorandoutdoorfanstopsduringdefrosting.
Hotstartafterdefrostends.
Functions
- 29 -
Copyright2010LGElectronics.Inc.Allrightreserved.
Onlyfortrainingandservicepurposes
LGEInternalUseOnly
2. Operation Detail
n Auto Swing Control
Thisfunctionistoswingthelouverupanddownautomatically.
n Soft-Dry Operation
Theindoorfanspeedisautomaticallysettothelow,sotheshiftoftheindoorfanspeedisimpossiblebecauseof
alreadybeingsettothebestspeedforDryOperationbymicrocontrollercontrol.
n Cooling Mode Operation
WhenselectingtheCooling( )ModeOperation,theunitwilloperateaccordingtothesettingbytheremotecon-
trollerandtheoperationdiagramisasfollowing
(1) The function of main control
Operation Detail
Thermal ON Thermal OFF
IndoorUnitmode ST+0.5 ST-0.5
2TH(Remo.+Indoor)
Tobeselectedhighertemperature Tobeselectedhighertemperature
contrastIndoorUnitandRemo. contrastIndoorUnitandRemo.
Remo.Mode ST+0.5 ST-0.5
IntakeAirTemperature
Thermo.ON
(SETTEMPERATURE
+0.5C(33F))
Thermo.OFF
(SETTEMPERATURE
Morethan Morethan
-0.5C(33F))
3minutes 3minutes
Selected Selected Selected
Speed Speed Speed
INDOORFAN LowLow
- 30 -
Copyright2010LGElectronics.Inc.Allrightreserved.
Onlyfortrainingandservicepurposes
LGEInternalUseOnly
n Heating Mode Operation
Theunitwilloperateaccordingtothesettingbytheremotecontrollerandtheoperationdiagramisshownasfollowing.
n Hot-start Control
Theindoorfandoesnorotateuntiltheevaporatorpipingtemperaturewillbereachedto25C(76F).
Theoperationdiagramisasfollowing.
35C(94F)
30C(86F)
27C(80F)
25C(76F)
22C(72F)
Pipe
temperature
OFF
Indoor fan
speed
LO
LOW
LOW
SELECTED
FAN
LOW LOLOW
COMP ON
Operation Detail
Thermal

OFF

ON
OFF ON
ON
ON Outdoor fan
Indoor fan
4 Way ON
Room
Temperature
Thermal Off
Thermal On
Indoor pipe
Temperature
33C(92F)
25C(76F)
20C(68F)
36C(96F)
Minimum
3min
Setting
fan
speed
Setting
fan
speed
Setting
fan
speed
Stop Low Stop Stop Low Low Low Low
ThermalON ThermalOFF
IndoorUnitmode ST+2 ST+4
2TH Tobeselectedlowertemperature Tobeselectedlowertemperature
(Remo.+Indoor) contrastIndoorUnitandRemo. contrastIndoorUnitandRemo.
Remo.mode ST+0 ST+2
- 31 -
Copyright2010LGElectronics.Inc.Allrightreserved.
Onlyfortrainingandservicepurposes
LGEInternalUseOnly
3. Dimensions
Dimensions
7
6
,

S
e
o
n
g
s
a
n
-
d
o
n
g
,

C
h
a
n
g
w
o
n

C
i
t
y
,

G
y
e
o
n
g
n
a
m
,
6
4
1
-
7
1
3
,

K
o
r
e
a
C
H
A
S
S
I
S

C
O
D
E
:

T
P
C
e
i
l
i
n
g

C
a
s
s
e
t
t
e

4
-
w
a
y
A
R
N
U
2
1
G
T
P
*
2
A
R
N
U
2
4
G
T
P
*
2
A
R
N
U
2
8
G
T
P
*
2
N
o
t
e
1
.

U
n
i
t

s
h
o
u
l
d

b
e

i
n
s
t
a
l
l
e
d

i
n

c
o
m
p
l
i
a
n
c
e

w
i
t
h

t
h
e

i
n
s
t
a
l
l
a
t
i
o
n

m
a
n
u
a
l





i
n

t
h
e

p
r
o
d
u
c
t

b
o
x
.
2
.

U
n
i
t

s
h
a
l
l

b
e

g
r
o
u
n
d
e
d

i
n

a
c
c
o
r
d
a
n
c
e

w
i
t
h

t
h
e

l
o
c
a
l

r
e
g
u
l
a
t
i
o
n
s

o
r





a
p
p
l
i
c
a
b
l
e

n
a
t
i
o
n
a
l

c
o
d
e
s
.
6 8 4
8 4 0
6 7 1
7
8
7
7
8
7
8
4
0
N
a
m
e

1

L
i
q
u
i
d

p
i
p
e

c
o
n
n
e
c
t
i
o
n

U
n
i
t

s
i
z
e
(
2
4
k
,

2
8
k
)
:

9
.
5
2

2

G
a
s

p
i
p
e

c
o
n
n
e
c
t
i
o
n

U
n
i
t

s
i
z
e
(
2
4
k
,

2
8
k
)
:

1
5
.
8
8


3

D
r
a
i
n

p
i
p
e

c
o
n
n
e
c
t
i
o
n


4

P
o
w
e
r

s
u
p
p
l
y

c
o
n
n
e
c
t
i
o
n


5

A
i
r

d
i
s
c
h
a
r
g
e

g
r
i
l
l



6

A
i
r

s
u
c
t
i
o
n

g
r
i
l
l

N
u
m
b
e
r
D
e
s
c
r
i
p
i
t
i
o
n
(
u
n
i
t

:

m
m
)
2 0 4
8
0
4
1 5 4
9 9
8 2
6 0
8
4
0
6
0
3
5
0
1
6
5
8
0
5
3
.
5
1
0
8
2 0 4
4 06 5
43
1
2
B
r
a
n
c
h

D
u
c
t

C
o
n
n
e
c
t
i
o
n
7 94 1 . 5
9 5 0
2 5
6 1 4 ( I n l e t G r i l l e )
5
0
0
(
A
i
r

o
u
t
l
e
t

H
o
l
e
)
4
-
R
2
0
7
3
7
9
5
0
56
4
7
5
4 2 0
4 2 0
3 9 3
8
7
0
-
9
2
0
(
C
E
IL
IN
G
O
P
E
N
IN
G
S
P
A
C
E
)
7
8
6
(
S
U
S
P
E
N
S
IO
N
P
O
S
IT
IO
N
)
3 0 0
O R L E S S
6 8 2 ( S U S P E N S I O N P O S I T I O N )
6 6 9 ( S U S P E N S I O N P O S I T I O N )
8 7 0 - 9 2 0 ( C E I L I N G O P E N I N G S P A C E )
C
e
i
l
i
n
g

o
p
e
n
i
n
g
B
A
O
U
T
D
O
O
R
A
IR
IN
T
A
K
E
(
D
IR
E
C
T
C
O
N
N
E
C
T
IO
N
)
B
R
A
N
C
H
D
U
C
T
C
O
N
N
E
C
T
IO
N
B
R
A
N
C
H
D
U
C
T
C
O
N
N
E
C
T
IO
N
1
3
-

3
, 3
H
o
le
1
3
-
3
, 3
H
o
le

7
0
7
1
3
5
0
1
6
5
7 9
5 0 5 0 3 2
9
2
9
2
9
2
9
2
5
0
1
6
5
1
0
3
1
7 1 2 6
6 2
3
5
B

A
R
R
O
W

V
I
E
W
A

A
R
R
O
W

V
I
E
W
V
P
2
5
(

3
2
)

5
0
0
m
m
o
r
m
o
r
e
*
5
0
0
m
m
o
r
m
o
r
e
*


R
E
Q
U
I
R
E
D

S
P
A
C
E
5
0
0
m
m
o
r
m
o
r
e
*
5
0
0
m
m
o
r
m
o
r
e
*
- 32 -
Copyright2010LGElectronics.Inc.Allrightreserved.
Onlyfortrainingandservicepurposes
LGEInternalUseOnly
Dimensions
8
4
0
2 4 6
1 9 5
3
5
0
1 0 05 2
1
6
5
7
6
,

S
e
o
n
g
s
a
n
-
d
o
n
g
,

C
h
a
n
g
w
o
n

C
i
t
y
,

G
y
e
o
n
g
n
a
m
,
6
4
1
-
7
1
3
,

K
o
r
e
a
C
H
A
S
S
I
S

C
O
D
E
:

T
N
C
e
i
l
i
n
g

C
a
s
s
e
t
t
e

4
-
w
a
y
A
R
N
U
3
6
G
T
N
*
2
N
o
t
e
1
.

U
n
i
t

s
h
o
u
l
d

b
e

i
n
s
t
a
l
l
e
d

i
n

c
o
m
p
l
i
a
n
c
e

w
i
t
h

t
h
e

i
n
s
t
a
l
l
a
t
i
o
n

m
a
n
u
a
l





i
n

t
h
e

p
r
o
d
u
c
t

b
o
x
.
2
.

U
n
i
t

s
h
a
l
l

b
e

g
r
o
u
n
d
e
d

i
n

a
c
c
o
r
d
a
n
c
e

w
i
t
h

t
h
e

l
o
c
a
l

r
e
g
u
l
a
t
i
o
n
s

o
r





a
p
p
l
i
c
a
b
l
e

n
a
t
i
o
n
a
l

c
o
d
e
s
.
N
a
m
e

1

L
i
q
u
i
d

p
i
p
e

c
o
n
n
e
c
t
i
o
n

U
n
i
t

s
i
z
e
(
3
6
k
)
:

9
.
5
2

2

G
a
s

p
i
p
e

c
o
n
n
e
c
t
i
o
n

U
n
i
t

s
i
z
e
(
3
6
k
)
:

1
5
.
8
8


3

D
r
a
i
n

p
i
p
e

c
o
n
n
e
c
t
i
o
n


4

P
o
w
e
r

s
u
p
p
l
y

c
o
n
n
e
c
t
i
o
n


5

A
i
r

d
i
s
c
h
a
r
g
e

g
r
i
l
l



6

A
i
r

s
u
c
t
i
o
n

g
r
i
l
l

N
u
m
b
e
r
D
e
s
c
r
i
p
i
t
i
o
n
(
u
n
i
t

:

m
m
)
43
1
2
B
r
a
n
c
h

D
u
c
t

C
o
n
n
e
c
t
i
o
n
1 0 7
7 8
1 0 3
1 4 1
2 4 6
4 0
1
1
0
6
0
8
4
0
8
0
5
3
.5
9 5 0
2 5
6 1 4 ( I n l e t G r i l l e )
5
0
0
(
A
i
r

o
u
t
l
e
t

H
o
l
e
)
4
-
R
2
0
7
3
7
9
5
0
56
4
7
5
4 2 0
4 2 0
3 9 3
8
7
0
-
9
2
0
(
C
E
IL
IN
G
O
P
E
N
IN
G
S
P
A
C
E
)
7
8
6
(
S
U
S
P
E
N
S
IO
N
P
O
S
IT
IO
N
)
3 0 0
O R L E S S
6 8 2 ( S U S P E N S I O N P O S I T I O N )
6 6 9 ( S U S P E N S I O N P O S I T I O N )
8 7 0 - 9 2 0 ( C E I L I N G O P E N I N G S P A C E )
C
e
i
l
i
n
g

o
p
e
n
i
n
g
B
A
O
U
T
D
O
O
R
A
IR
IN
T
A
K
E
(
D
IR
E
C
T
C
O
N
N
E
C
T
IO
N
)
B
R
A
N
C
H
D
U
C
T
C
O
N
N
E
C
T
IO
N
B
R
A
N
C
H
D
U
C
T
C
O
N
N
E
C
T
IO
N
1
3
-

3
, 3
H
o
le
1
3
-

3
, 3
H
o
le

7
0
1 0 0
6 0 6 0
4 3
9
2
9
2
9
2
9
2
3
5
0
1
6
5
1
6
5
1
0
7 1 4 4
8 0
7
1
3
1
3
5
B

A
R
R
O
W

V
I
E
W
A

A
R
R
O
W

V
I
E
W
V
P
2
5
(

3
2
)

5
0
0
m
m

o
r

m
o
r
e
*
5
0
0
m
m

o
r

m
o
r
e
*


R
E
Q
U
I
R
E
D

S
P
A
C
E
5
0
0
m
m

o
r

m
o
r
e
*
5
0
0
m
m

o
r

m
o
r
e
*
- 33 -
Copyright2010LGElectronics.Inc.Allrightreserved.
Onlyfortrainingandservicepurposes
LGEInternalUseOnly
Dimensions
7
6
,

S
e
o
n
g
s
a
n
-
d
o
n
g
,

C
h
a
n
g
w
o
n

C
i
t
y
,

G
y
e
o
n
g
n
a
m
,
6
4
1
-
7
1
3
,

K
o
r
e
a
C
H
A
S
S
I
S

C
O
D
E
:

T
M
C
e
i
l
i
n
g

C
a
s
s
e
t
t
e

4
-
w
a
y
A
R
N
U
4
2
G
T
M
*
2
A
R
N
U
4
8
G
T
M
*
2
N
o
t
e
1
.

U
n
i
t

s
h
o
u
l
d

b
e

i
n
s
t
a
l
l
e
d

i
n

c
o
m
p
l
i
a
n
c
e

w
i
t
h

t
h
e

i
n
s
t
a
l
l
a
t
i
o
n

m
a
n
u
a
l





i
n

t
h
e

p
r
o
d
u
c
t

b
o
x
.
2
.

U
n
i
t

s
h
a
l
l

b
e

g
r
o
u
n
d
e
d

i
n

a
c
c
o
r
d
a
n
c
e

w
i
t
h

t
h
e

l
o
c
a
l

r
e
g
u
l
a
t
i
o
n
s

o
r





a
p
p
l
i
c
a
b
l
e

n
a
t
i
o
n
a
l

c
o
d
e
s
.
N
a
m
e

1

L
i
q
u
i
d

p
i
p
e

c
o
n
n
e
c
t
i
o
n

U
n
i
t

s
i
z
e
(
4
2
k
,

4
8
k
)
:

9
.
5
2

2

G
a
s

p
i
p
e

c
o
n
n
e
c
t
i
o
n

U
n
i
t

s
i
z
e
(
4
2
k
,

4
8
k
)
:

1
5
.
8
8


3

D
r
a
i
n

p
i
p
e

c
o
n
n
e
c
t
i
o
n


4

P
o
w
e
r

s
u
p
p
l
y

c
o
n
n
e
c
t
i
o
n


5

A
i
r

d
i
s
c
h
a
r
g
e

g
r
i
l
l



6

A
i
r

s
u
c
t
i
o
n

g
r
i
l
l

N
u
m
b
e
r
D
e
s
c
r
i
p
i
t
i
o
n
(
u
n
i
t

:

m
m
)
43
1
2
8
4
0
2 8 8
2 3 7
B
r
a
n
c
h

D
u
c
t

C
o
n
n
e
c
t
i
o
n
3
5
0
5
3
.5
1 0 08 4
1
6
5
9 5 0
2 5
6 1 4 ( I n l e t G r i l l e )
5
0
0
(
A
i
r

o
u
t
l
e
t

H
o
l
e
)
4
-
R
2
0
7
3
7
9
5
0
56
O
U
T
D
O
O
R
A
IR
IN
T
A
K
E
(
D
IR
E
C
T
C
O
N
N
E
C
T
IO
N
)
1
3
-

3
, 3
H
o
le

7
0
7 1 7 5
1 1 0
7
1
3
1
3
5
B

A
R
R
O
W

V
I
E
W
B
R
A
N
C
H
D
U
C
T
C
O
N
N
E
C
T
IO
N
B
R
A
N
C
H
D
U
C
T
C
O
N
N
E
C
T
IO
N
1
3
-
3
, 3
H
o
le
6 0 6 0 7 6
1 3 6
9
2
9
2
9
2
9
2
3
5
0
1
6
5
1
6
5
1
0
1 0 0
A

A
R
R
O
W

V
I
E
W
4
7
5
4 2 0
4 2 0
3 9 3
8
7
0
-
9
2
0
(
C
E
IL
IN
G
O
P
E
N
IN
G
S
P
A
C
E
)
7
8
6
(
S
U
S
P
E
N
S
IO
N
P
O
S
IT
IO
N
)
3 0 0
O R L E S S
6 8 2 ( S U S P E N S I O N P O S I T I O N )
6 6 9 ( S U S P E N S I O N P O S I T I O N )
8 7 0 - 9 2 0 ( C E I L I N G O P E N I N G S P A C E )
C
e
i
l
i
n
g

o
p
e
n
i
n
g
B
A
V
P
2
5
(

3
2
)

5
0
0
m
m

o
r

m
o
r
e
*
5
0
0
m
m

o
r

m
o
r
e
*


R
E
Q
U
I
R
E
D

S
P
A
C
E
5
0
0
m
m

o
r

m
o
r
e
*
5
0
0
m
m

o
r

m
o
r
e
*
- 34 -
Copyright2010LGElectronics.Inc.Allrightreserved.
Onlyfortrainingandservicepurposes
LGEInternalUseOnly
1. Functions ....................................................................................35
2. Operation Details........................................................................36
3. Dimensions .................................................................................43
Art Cool Type(Mirror)
- 35 -
Copyright2010LGElectronics.Inc.Allrightreserved.
Onlyfortrainingandservicepurposes
LGEInternalUseOnly
Functions
1. Functions
Roomtemperaturesensor.(THERMISTOR)
MaintainstheroomtemperatureinaccordancewiththeSettingTemp.
Indoorfanisdelayedfor5secatthestarting.
High,Med,Low,CHAOS
Intermittentoperationoffanatlowspeed.
Thefanisswitchedtolow(Cooling),med(Heating)speed.
Theunitwillbestoppedafter1,2,3,4,5,6,7hours.
Thefanisswitchedtointermittentorirregularoperation
Thefanspeedisautomaticallyswitchedfromhightolowspeed.
Thelouvercanbesetatthedesiredpositionorswing
upanddownautomatically.
Indoor Unit
Operation ON/OFF by Remote controller
Sensing the Room Temperature
Room temperature control
Starting Current Control
Indoor Fan Speed Control
Operation indication Lamps (LED)
Soft Dry Operation Mode
Boththeindoorandoutdoorfanstopsdur-
ingdefrosting.
Theindoorfandoesnotrotateuntilthe
evaporatorpipetemperaturewillbereached
at28C(82F).
Sleep Mode Auto Control
Natural Air Control by CHAOS Logic
Airflow Direction Control
Defrost(Deice) control (Heating)
Hot-start Control (Heating)
SignalReceptor
Receivesthesignalsfromtheremotecontrol.(Signalreceivingsound:twoshortbeepsoronelongbeep.)
OperationIndicationLamps
On/Off :Lightsupduringthesystemoperation.
SleepMode :LightsupduringSleepModeAutooperation.
Timer :LightsupduringTimeroperation.
DefrostMode :LightsupduringDefrostModeorHotStartoperation.
- 36 -
Copyright2010LGElectronics.Inc.Allrightreserved.
Onlyfortrainingandservicepurposes
LGEInternalUseOnly
Operation Details
2. Operation Details
DISPLAY
1) High quality LCD remote controller supplied
Operation Indicator
Onwhileinapplianceoperation,offwhileinappliancepause
Timer Indicator
Onwhileintimermode(on/off)andinsleeptimermode,offwhentimermodeiscompletedorcanceled
Defrost Indicator
Offexceptwhenhotstartduringheatingmodeoperationorwhileindefrostcontrol.
Plasma Indicator
Onwhileinplasmamode,offwhileplasmamodeiscanceled.
Auto restart Indicator
Onwhileautorestartmode,offwhileautorestartmodeiscanceled.
Auto restart
Incasethepowercomesonagainafterapowerfailure,AutoRestartingOperationisthefunctiontooperate
proceduresautomaticallytothepreviousoperatingconditions.
Ifyourwanttousethisoperation,presstheAutoRestartButton.
Power(Forced Operation)
Operationstarts,whenthisbuttonispressedandstopswhenyoupressthebuttonagain.
n Cooling Mode Operation
When the intake air temperature reaches 0.5C(33F) below the setting temp, the compressor and the outdoor
fanstop.
Whenitreaches0.5C(33F) abovethesettingtemp,theystarttooperateagain.
CompressorONTemp=>SettingTemp+0.5C(33F)
CompressorOFFTemp=>SettingTemp-0.5C(33F)
Whileincompressorrunning,operatingwiththeairflowspeedsetbytheremotecontroller.Whileincompres-
sornotrunning,operatingwiththelowairflowspeedregardlessofthesetting.
n HealthyDehumidificationMode
Whenthedehumidificationoperationinputbytheremotecontrollerisreceived,theintakeairtemperatureis
detectedandthesettingtempisautomaticallysetaccordingtotheintakeairtemperature.
26C(78F)IntakeAirTemp =>25C(76F)
24C(76F)IntakeAirTemp<26C(78F)=>IntakeAirTemp-1C(34F)
18C(64F)IntakeAirTemp<24C(76F)=>IntakeAirTemp-0.5C(33F)
IntakeAirTemp<18C(64F) =>18C(64F)
Whileincompressoroff,theindoorfanrepeatslowairflowspeedandpause.
Whiletheintakeairtempisbetweencompressorontemp.andcompressorofftemp.,10-mindehumidification
operationand4-mincompressoroffrepeat
CompressorONTemp.=>SettingTemp+0.5C(33F)
CompressorOFFTemp.=>SettingTemp-0.5C(33F)
In10-mindehumidificationoperation,theindoorfanoperateswiththelowairflowspeed.
n HeatingModeOperation
Function of Controls
- 37 -
Copyright2010LGElectronics.Inc.Allrightreserved.
Onlyfortrainingandservicepurposes
LGEInternalUseOnly
Operation Details
WhentheintakeairTemp.reachesCompressorOFFTemp.,thecompressoristurnedoff.
WhentheintakeairTemp.reachesCompressorONTemp.,thecompressoristurnedon.
ThemoONTemp.=>SettingTemp.+2C(36F)
ThemoOFFTemp.=>SettingTemp.+4C(39F)
Whileincompressoron,whenabove38C(100F),itoperateswithsettingairflowspeed(whileinsleepmode,
withthemediumairflowspeed).
Whileincompressoroff,theindoorfanisoffwhentheindoorpipetempisbelow33C(92F),whenabove
35C(94F),itoperateswiththelowairflowspeed.
Whileindefrostcontrol,bothoftheindoorandoutdoorfansareturnedoff.
n Defrost Control
Whileinheatingmodeoperationinordertoprotectoutdoorunitfromfreezing,reversedtocoolingcycleto
defrostoftheoutdoorunit.
n Fuzzy Operation (Outdoor unit C/O Model)
AccordingtothetemperaturesetbyFuzzyrule,whentheintakeairtempis0.5C(33F)ormorebelowthe
settingtemp,thecompressoristurnedoff.When0.5C(33F)ormoreabovethesettingtemp,thecompres-
soristurnedon.
CompressorONTemp=>SettingTemp+0.5C(33F)
CompressorOFFTemp=>SettingTemp+0.5C(33F)
AtthebeginningofFuzzymodeoperation,thesettingtemperatureisautomaticallyselectedaccordingtothe
intakeairtempatthattime.
26C(78F)IntakeAirTemp =>25C(76F)
24C(76F)IntakeAirTemp<26C(78F)=>IntakeAirTemp+1C(34F)
22C(72F)IntakeAirTemp<24C(76F)=>IntakeAirTemp+0.5C(33F)
18C(64F)IntakeAirTemp<22C(72F)=>IntakeAirTemp
IntakeAirTemp<18C(64F) =>18C(64F)
WhentheFuzzykey(TemperatureControlkey)isinputaftertheinitialsettingtemperatureisselected,the
Fuzzykeyvalueandtheintakeairtemperatureatthattimearecomparedtoselectthesettingtemperature
automaticallyaccordingtotheFuzzyrule.
WhileinFuzzyoperation,theairflowspeedoftheindoorfanisautomaticallyselectedaccordingtothetemper-
ature
n Fuzzy Operation (Outdoor unit H/P Model)
Whenanyofoperationmodeisnotselectedlikethemomentofthepoweronorwhen3hrshaspassedsince
theoperationoff,theoperationmodeisselected.
Whendeterminingtheoperationmode,thecompressor,theoutdoorfan,andthe4wayvalveareoffandonly
theindoorfanisoperatedfor15seconds.Thenanoperationmodeisselectedaccordingtotheintakeair
tempatthatmomentasfollows.
24C(76F)InatakeAirTemp=>FuzzyOperationforCooling
21C(70F)InatakeAirTemp<24C(76F)=>FuzzyOperationforDehumidification
InatakeAirTemp<21C(70F)=>FuzzyOperationforHeating
Ifanyoftheoperationmodesamongcooling/dehumidification/heatingmodeoperationsiscarriedoutfor10
secorlongerbeforeFuzzyoperation,themodebeforeFuzzyoperationisoperated.
- 38 -
Copyright2010LGElectronics.Inc.Allrightreserved.
Onlyfortrainingandservicepurposes
LGEInternalUseOnly
Operation Details
1) Fuzzy Operation for Cooling
AccordingtothesettingtemperatureselectedbyFuzzyrule,whentheintakeairtempis0.5C(33F)ormore
belowthesettingtemp,thecompressoristurnedoff.When0.5C(33F)ormoreabovethesettingtemp,the
compressoristurnedon.
CompressorONTemp.=>SettingTemp+0.5C(33F)
CompressorOFFTemp.=>SettingTemp+0.5C(33F)
AtthebeginningofFuzzymodeoperation,thesettingtemperatureisautomaticallyselectedaccordingtothe
intakeairtempatthattime.
26C(78F)IntakeAirTemp =>25C(76F)
24C(76F)IntakeAirTemp<26C(78F)=>IntakeAirTemp+1C(34F)
22C(72F)IntakeAirTemp<24C(76F)=>IntakeAirTemp+0.5C(33F)
18C(64F)IntakeAirTemp<22C(72F)=>IntakeAirTemp
IntakeAirTemp<18C(64F) =>18C(64F)
WhentheFuzzykey(TemperatureControlkey)isinputaftertheinitialsettingtemperatureisselected,the
Fuzzykeyvalueandtheintakeairtemperatureatthattimearecomparedtoselectthesettingtemperature
automaticallyaccordingtotheFuzzyrule.
WhileinFuzzyoperation,theairflowspeedoftheindoorfanisautomaticallyselectedaccordingtothetemperature.
2) Fuzzy Operation for Dehumidification
AccordingtothesettingtemperatureselectedbyFuzzyrule,whentheintakeairtempis0.5C(33F)ormore
belowthesettingtemp,thecompressoristurnedoff.When0.5C(33F)ormoreabovethesettingtemp,the
compressoristurnedon.
CompressorONTemp.=>SettingTemp+0.5C(33F)
CompressorOFFTemp.=>SettingTemp+0.5C(33F)
AtthebeginningofFuzzymodeoperation,thesettingtemperatureisautomaticallyselectedaccordingtothe
intakeairtempatthattime.
26C(78F)IntakeAirTemp =>25C(76F)
24C(76F)IntakeAirTemp<26C(78F)=>IntakeAirTemp+1C(34F)
22C(72F)IntakeAirTemp<24C(76F)=>IntakeAirTemp+0.5C(33F)
18C(64F)IntakeAirTemp<22C(72F)=>IntakeAirTemp
IntakeAirTemp<18C(64F) =>18C(64F)
WhentheFuzzykey(TemperatureControlkey)isinputaftertheinitialsettingtemperatureisselected,the
Fuzzykeyvalueandtheintakeairtemperatureatthattimearecomparedtoselectthesettingtemperature
automaticallyaccordingtotheFuzzyrule.
WhileinFuzzyoperation,theairflowspeedoftheindoorfanrepeatsthelowairflowspeedorpauseasin
dehumidificationoperation.
- 39 -
Copyright2010LGElectronics.Inc.Allrightreserved.
Onlyfortrainingandservicepurposes
LGEInternalUseOnly
Operation Details
3) Fuzzy Operation for Heating
AccordingtothesettingtemperatureselectedbyFuzzyrule,whentheintakeairtempis3C(37F)ormore
abovethesettingtemp,thecompressoristurnedoff.Whenbelowthesettingtemp,thecompressoris
turnedon.
CompressorONTemp=>SettingTemp+2C(36F)
CompressorOFFTemp=>SettingTemp+4C(39F)
AtthebeginningofFuzzymodeoperation,thesettingtemperatureisautomaticallyselectedaccordingto
theintakeairtempatthattime.
20C(68F)IntakeAirTemp=>IntakeAirTemp+0.5C(33F)
IntakeAirTemp<20C(68F)=>20C(68F)
WhentheFuzzykey(TemperatureControlkey)isinputaftertheinitialsettingtemperatureisselected,the
Fuzzykeyvalueandtheintakeairtemperatureatthattimearecomparedtoselectthesettingtemperature
automaticallyaccordingtotheFuzzyrule.
WhileinFuzzyoperation,theairflowspeedoftheindoorfanissettothehighorthemediumaccordingto
theintakeairtemperatureandthesettingtemperature.
n Airflow Speed Selection
Theairflowspeedoftheindoorfanissettohigh,medium,low,orchaosbytheinputoftheairflowspeed
selectionkeyontheremotecontroller.
n On-Timer Operation
Whenthesettimeisreachedafterthetimeisinputbytheremotecontroller,theappliancestartstooperate.
ThetimerLEDisonwhentheon-timerisinput.Itisoffwhenthetimesetbythetimerisreached.
Iftheapplianceisoperatingatthetimesetbythetimer,theoperationcontinues.
n Off-Timer Operation
Whenthesettimeisreachedafterthetimeisinputbytheremotecontroller,theappliancestopsoperating.
ThetimerLEDisonwhentheoff-timerisinput.Itisoffwhenthetimesetbythetimerisreached.
Iftheapplianceisonpauseatthetimesetbythetimer,thepausecontinues.
- 40 -
Copyright2010LGElectronics.Inc.Allrightreserved.
Onlyfortrainingandservicepurposes
LGEInternalUseOnly
Operation Details
n Off-Timer <=> On-Timer Operation
Whenthesettimeisreachedaftertheon/offtimeisinputbytheremotecontroller,theon/off-timeroperation
iscarriedoutaccordingtothesettime.
n Sleep Timer Operation
When the sleep time is reached after <1,2,3,4,5,6,7,0(cancel) hr> is input by the remote controller while in
applianceoperation,theoperationoftheappliancestops.
Whiletheapplianceisonpause,thesleeptimermodecannotbeinput.
While in cooling mode operation, 30 min later since the start of the sleep timer, the setting temperature
increasesby1C(34F)Afteranother30minelapse,itincreasesby1C(34)again.
Whenthesleeptimermodeisinputwhileincoolingcyclemode,theairflowspeedoftheindoorfanissetto
thelow.
Whenthesleeptimermodeisinputwhileinheatingcyclemode,theairflowspeedoftheindoorfanissetto
themedium.
n Chaos Swing Mode
BytheChaosSwingkeyinput,thevaneautomaticallyoperateswiththeChaosSwingortheyarefixedtothe
desireddirection.
n Chaos Natural Wind Mode
WhentheChaosNaturalWindmodeisselectedandthenoperated,thehigh,medium,orlowspeedoftheair-
flowmodeisoperatedfor2~15secrandomlybytheChaosSimulation.
n Jet Cool Mode Operation (Outdoor unit C/O Model)
IftheJetCoolkeyisinputatanyoperationmodewhileinapplianceoperation,theJetCoolmodeoperates.
IntheJetCoolmode,theindoorfanisoperatedatsuper-highspeedfor30minatcoolingmodeoperation.
IntheJetCoolmodeoperation,theroomtemperatureiscontrolledtothesettingtemperature,18C(64F).
WhenthesleeptimermodeisinputwhileintheJetCoolmodeoperation,theJetCoolmodehasthepriority.
WhentheJetCoolkeyisinput,theupper/lowervanesareresettothoseoftheinitialcoolingmodeandthen
operatedinorderthattheairoutflowcouldreachfurther.
n Jet Cool Mode Operation (Outdoor unit H/P Model)
While in heating mode or Fuzzy operation, the Jet Cool key cannot be input. When it is input while in the
othermodeoperation(cooling,dehumidification,ventilation),theJetCoolmodeisoperated.
IntheJetCoolmode,theindoorfanisoperatedatsuper-highspeedfor30minatcoolingmodeoperation.
IntheJetCoolmodeoperation,theroomtemperatureiscontrolledtothesettingtemperature,18C(64F).
WhenthesleeptimermodeisinputwhileintheJetCoolmodeoperation,theJetCoolmodehasthepriority.
WhentheJetCoolkeyisinput,theupper/lowervanesareresettothoseoftheinitialcoolingmodeandthen
operatedinorderthattheairoutflowcouldreachfurther.
n Auto Restarting Operation
When the power is restored after a sudden power failure while in appliance operation, the mode before the
powerfailureiskeptonthememoryandtheapplianceautomaticallyoperatesinthemodeonthememory.
OperationModethatiskeptonthememory
- 41 -
Copyright2010LGElectronics.Inc.Allrightreserved.
Onlyfortrainingandservicepurposes
LGEInternalUseOnly
Operation Details
-StateofOperationON/OFF
-OperationMode/SettingTemp/SelectedAirflowSpeed
-SleepTimerMode/RemainingTimeofSleepTimer(unitofhour)
n Forced Operation (Outdoor unit C/O Model)
Tooperatetheappliancebyforceincasethattheremotecontrollerislost,theforcedoperationbuttonison
themainunitoftheappliancetooperatetheapplianceinthestandardconditions.
Presstheforcedoperationbutton,theforcedoperationiscarriedout.
Presstheforcedoperationbuttononceagaintostopoperation.
Theforcedoperationiscarriedoutincoolingmodewiththesettingtemperature22C(72F)andthehigh
speedofairflow.
n Forced Operation (Outdoor unit H/P Model)
Tooperatetheappliancebyforceincasethattheremotecontrollerislost,theforcedoperationselection
switchisonthemainunitoftheappliancetooperatetheapplianceinthestandardconditions.
Presstheforcedoperationbutton,theforcedoperationiscarriedout.
Presstheforcedoperationbuttononceagaintostopoperation.
Intheforcedoperationmode,theindoorfanisoperatedatlowspeedforaround15secandthentheoperation
conditionissetaccordingtotheintakeairtemperatureasfollows.
24C(76F)IntakeAirTemp=>CoolingModeOperation,22C(72F),HighSpeed
21C(70F)IntakeAirTemp<24C(76F)=>DehumidificationOperation,23C(74F),HighSpeed
IntakeAirTemp<21C(70F)=>HeatingModeOperation,24C(76F),HighSpeed
n Test Operation Control
Tochecktheconditionoftheinstallationwheninstallingtheappliance,theapplianceisoperatedatcooling
mode,highspeedofairflow,compressor-onfor18minwithoutcontrollingtheroomtemperature.
Aftersupplyingpowertothemainbody,keeppressingtheforcedoperationbuttonforabout3seconds.
Whileintestoperation,akeycanbeinputbytheremotecontroller.
Whenakey(operationstart/stop,operationmodeselection,airflowspeedselection,temperaturecontrol,Jet
Cool)isinputbytheremotecontroller,thetestoperationiscanceledandtheapplianceisoperatedaccording
tothesettingbytheremotecontroller.
n Protection of the evaporator pipe from frosting
In the temperrature of the indoor pipe is below 0C(32F) after 7 minutes from starting the compressor, the
compressorandoutdoorfanarestopped,and3minutesdelayofoperatingofthecompressor,whenthetem-
peratureoftheindoorpipeisover7C(45F),thecompressorandtheoutdoorfanarereoperated.
Outdoorfanmotorstopswhenindoorpipetemperatureisblow3C(37F)andrestartsatthepipetemperature
above 6C(43F) or after 90 seconds, if the pipe temperature does not rise to 6C(43F), outdoor fan motor
runscontinuouslyatevenbelow3C(37F).
- 42 -
Copyright2010LGElectronics.Inc.Allrightreserved.
Onlyfortrainingandservicepurposes
LGEInternalUseOnly
Operation Details
n Buzzer Sounding Operation
Whentheappliance-operationkeyisinputbytheremotecontroller,theshortbeep-beep-sounds.
Whentheappliance-pausekeyisinputbytheremotecontroller,thelongbeepsounds.
n Air Cleaner Operation
WhenanaircleanerfunctionisselectedduringAirConditioneroperation
-Plasmaaircleanerfunctionwillbeoperatedwhileinanyoperationmodewithselectingthefunction.
-Thefunctionistobestoppedwhileitisoperatingwithselectingthefunction.
Whenanaircleanerfunctionisselectedduringoperationoff
-Thefunctionwillbeonlyoperated.
Wheninletgrilleofairconditionerisopenedduringplasmaoperation,HighVoltageGenerator(H.V.B)istobe
stopped.Wheninletgrilleofairconditionerisclosedduringplasmaoperation,HighVoltageGenerator(H.V.B)
willbeoperatedagain.
- 43 -
Copyright2010LGElectronics.Inc.Allrightreserved.
Onlyfortrainingandservicepurposes
LGEInternalUseOnly
Dimensions
3. Dimensions
7
6
,

S
e
o
n
g
s
a
n
-
d
o
n
g
,

C
h
a
n
g
w
o
n

C
i
t
y
,

G
y
e
o
n
g
n
a
m
,
6
4
1
-
7
1
3
,

K
o
r
e
a
w
w
w
.
l
g
e
a
i
r
c
o
n
.
c
o
m
C
H
A
S
S
I
S

C
O
D
E
:

S
E
A
R
T

C
O
O
L

M
i
r
r
o
r
A
R
N
U
0
7
3
S
E
*
2
A
R
N
U
0
9
3
S
E
*
2
A
R
N
U
1
2
3
S
E
*
2
A
R
N
U
1
5
3
S
E
*
2
W
M
o
d
e
l
A
R
N
U
0
7
3
S
E
*
2
A
R
N
U
0
9
3
S
E
*
2
A
R
N
U
1
2
3
S
E
*
2
A
R
N
U
1
5
3
S
E
*
2
H
D
9
1
5
(
3
6
)
2
8
2
(
1
1
-
1
/
8
)
1
6
9
(
5
-
5
/
8
)
N
o
t
e
1
.

U
n
i
t

s
h
o
u
l
d

b
e

i
n
s
t
a
l
l
e
d

i
n

c
o
m
p
l
i
a
n
c
e

w
i
t
h

t
h
e

i
n
s
t
a
l
l
a
t
i
o
n

m
a
n
u
a
l





i
n

t
h
e

p
r
o
d
u
c
t

b
o
x
.
2
.

U
n
i
t

s
h
a
l
l

b
e

g
r
o
u
n
d
e
d

i
n

a
c
c
o
r
d
a
n
c
e

w
i
t
h

t
h
e

l
o
c
a
l

r
e
g
u
l
a
t
i
o
n
s

o
r





a
p
p
l
i
c
a
b
l
e

n
a
t
i
o
n
a
l

c
o
d
e
s
.
[
U
n
i
t

:

m
m
(
i
n
c
h
)
]
[
U
n
i
t

:

m
m
(
i
n
c
h
)
]
9
1
5
(
3
6
)
2 8 2 ( 1 1 - 1 / 8 )
2 8 2 ( 1 1 - 1 / 8 )
1
6
9
(
5
-
5
/
8
)
5
6
7
(
2
2
-
3
/
8
)
5
1
(
2
-
1
/
1
6
)
5 3 ( 2 - 1 / 1 6 )
1 6 5 ( 6 - 1 / 2 )
H
W
D
L
G

E
l
e
c
t
r
o
n
i
c
s

U
S
A
,

H
V
A
C

D
i
v
i
s
i
o
n
1
0
0
0

S
y
l
v
a
n

A
v
e
n
u
e
,

E
n
g
l
e
w
o
o
d

C
l
i
f
f
s
,

N
J

0
7
6
3
2
w
w
w
.
l
g
u
s
a
.
c
o
m

/

w
w
w
.
l
g
h
v
a
c
.
c
o
m
1
2
N
a
m
e



1
A
i
r

d
i
s
c
h
a
r
g
e

g
r
i
l
l




2
A
i
r

s
u
c
t
i
o
n

g
r
i
l
l

N
u
m
b
e
r
D
e
s
c
r
i
p
i
t
i
o
n
2 6 5 ( 1 0 - 1 / 2 )
- 44 -
Copyright2010LGElectronics.Inc.Allrightreserved.
Onlyfortrainingandservicepurposes
LGEInternalUseOnly
Dimensions
D
i
s
p
l
a
y

&

s
i
g
n
a
l

r
e
c
e
i
v
e
r
P
a
r
t

N
a
m
e
F
r
o
n
t

p
a
n
e
l
A
i
r

s
u
c
t
i
o
n

g
r
i
l
l
e
I
n
s
t
a
l
l
a
t
i
o
n

p
l
a
t
e
K
n
o
c
k
o
u
t

h
o
l
e
5



N
o
.
24 3 1
R
e
m
a
r
k
N
o
t
e
1
.

U
n
i
t

s
h
o
u
l
d

b
e

i
n
s
t
a
l
l
e
d

i
n

c
o
m
p
l
i
a
n
c
e

w
i
t
h

t
h
e

i
n
s
t
a
l
l
a
t
i
o
n

m
a
n
u
a
l





i
n

t
h
e

p
r
o
d
u
c
t

b
o
x
.
2
.

U
n
i
t

s
h
a
l
l

b
e

g
r
o
u
n
d
e
d

i
n

a
c
c
o
r
d
a
n
c
e

w
i
t
h

t
h
e

l
o
c
a
l

r
e
g
u
l
a
t
i
o
n
s

o
r





a
p
p
l
i
c
a
b
l
e

n
a
t
i
o
n
a
l

c
o
d
e
s
.
31
2
4
2 9 9
4 8
9 3
2 8 1
1
2
2
2
0
0
1
1
0
7
8
0
4
1 0
6 3
5
3
5
8
7
2
7
6
,

S
e
o
n
g
s
a
n
-
d
o
n
g
,

C
h
a
n
g
w
o
n

C
i
t
y
,

G
y
e
o
n
g
n
a
m
,
6
4
1
-
7
1
3
,

K
o
r
e
a
C
H
A
S
S
I
S

C
O
D
E
:

S
8
A
R
T

C
O
O
L

M
i
r
r
o
r
A
R
N
U
1
8
G
S
8
*
2
A
R
N
U
2
4
G
S
8
*
2
(
u
n
i
t

:

m
m
)
- 45 -
Copyright2010LGElectronics.Inc.Allrightreserved.
Onlyfortrainingandservicepurposes
LGEInternalUseOnly
1. Functions ....................................................................................46
2. Operation Details........................................................................47
3. Dimensions .................................................................................54
ArtCoolGallery
- 46 -
Copyright2010LGElectronics.Inc.Allrightreserved.
Onlyfortrainingandservicepurposes
LGEInternalUseOnly
Functions
1. Functions
Roomtemperaturesensor.(THERMISTOR)
MaintainstheroomtemperatureinaccordancewiththeSettingTemp.
Indoorfanisdelayedfor5secatthestarting.
High,Med,Low,CHAOS
Intermittentoperationoffanatlowspeed.
Thefanisswitchedtolow(Cooling),med(Heating)speed.
Theunitwillbestoppedafter1,2,3,4,5,6,7hours.
Thefanisswitchedtointermittentorirregularoperation
Thefanspeedisautomaticallyswitchedfromhightolowspeed.
Thelouvercanbesetatthedesiredpositionorswing
upanddownautomatically.
Indoor Unit
Operation ON/OFF by Remote controller
Sensing the Room Temperature
Room temperature control
Starting Current Control
Indoor Fan Speed Control
Operation indication Lamps (LED)
Soft Dry Operation Mode
Boththeindoorandoutdoorfanstopsdur-
ingdefrosting.
Theindoorfandoesnotrotateuntilthe
evaporatorpipetemperaturewillbereached
at28C(82F).
Sleep Mode Auto Control
Natural Air Control by CHAOS Logic
Airflow Direction Control
Defrost(Deice) control (Heating)
Hot-start Control (Heating)
SignalReceptor
Receivesthesignalsfromtheremotecontrol.(Signalreceivingsound:twoshortbeepsoronelongbeep.)
OperationIndicationLamps
On/Off :Lightsupduringthesystemoperation.
SleepMode :LightsupduringSleepModeAutooperation.
Timer :LightsupduringTimeroperation.
DefrostMode :LightsupduringDefrostModeorHotStartoperation.
- 47 -
Copyright2010LGElectronics.Inc.Allrightreserved.
Onlyfortrainingandservicepurposes
LGEInternalUseOnly
Operation Details
2. Operation Details
DISPLAY
1) High quality LCD remote controller supplied
Operation Indicator
Onwhileinapplianceoperation,offwhileinappliancepause
Timer Indicator
Onwhileintimermode(on/off)andinsleeptimermode,offwhentimermodeiscompletedorcanceled
Defrost Indicator
Offexceptwhenhotstartduringheatingmodeoperationorwhileindefrostcontrol.
Plasma Indicator
Onwhileinplasmamode,offwhileplasmamodeiscanceled.
Auto restart Indicator
Onwhileautorestartmode,offwhileautorestartmodeiscanceled.
Auto restart
Incasethepowercomesonagainafterapowerfailure,AutoRestartingOperationisthefunctiontooperate
proceduresautomaticallytothepreviousoperatingconditions.
Ifyourwanttousethisoperation,presstheAutoRestartButton.
Power(Forced Operation)
Operationstarts,whenthisbuttonispressedandstopswhenyoupressthebuttonagain.
n Cooling Mode Operation
When the intake air temperature reaches 0.5C(33F) below the setting temp, the compressor and the outdoor
fanstop.
Whenitreaches0.5C(33F) abovethesettingtemp,theystarttooperateagain.
CompressorONTemp=>SettingTemp+0.5C(33F)
CompressorOFFTemp=>SettingTemp-0.5C(33F)
Whileincompressorrunning,operatingwiththeairflowspeedsetbytheremotecontroller.Whileincompres-
sornotrunning,operatingwiththelowairflowspeedregardlessofthesetting.
Function of Controls
- 48 -
Copyright2010LGElectronics.Inc.Allrightreserved.
Onlyfortrainingandservicepurposes
LGEInternalUseOnly
Operation Details
n HealthyDehumidificationMode
Whenthedehumidificationoperationinputbytheremotecontrollerisreceived,theintakeairtemperatureis
detectedandthesettingtempisautomaticallysetaccordingtotheintakeairtemperature.
26C(78F)IntakeAirTemp=>25C
24C(76F)IntakeAirTemp<26C(78F)=>IntakeAirTemp-1C
18C(64F)IntakeAirTemp<24C(76F)=>IntakeAirTemp-0.5C(33F)
IntakeAirTemp<18C(64F)=>18C(64F)
Whileincompressoroff,theindoorfanrepeatslowairflowspeedandpause.
Whiletheintakeairtempisbetweencompressorontemp.andcompressorofftemp.,10-mindehumidification
operationand4-mincompressoroffrepeat
CompressorONTemp.=>SettingTemp+0.5C(33F)
CompressorOFFTemp.=>SettingTemp-0.5C(33F)
In10-mindehumidificationoperation,theindoorfanoperateswiththelowairflowspeed.
n HeatingModeOperation
WhentheintakeairTemp.reachesCompressorOFFTemp.,thecompressoristurnedoff.
WhentheintakeairTemp.reachesCompressorONTemp.,thecompressoristurnedon.
ThemoONTemp.=>SettingTemp.+2C(36F)
ThemoOFFTemp.=>SettingTemp.+4C(39F)
Whileincompressoron,whenabove38C(100F),itoperateswithsettingairflowspeed(whileinsleepmode,
withthemediumairflowspeed).
Whileincompressoroff,theindoorfanisoffwhentheindoorpipetempisbelow33C(92F),whenabove
35C(94F),itoperateswiththelowairflowspeed.
Whileindefrostcontrol,bothoftheindoorandoutdoorfansareturnedoff.
n Defrost Control
Whileinheatingmodeoperationinordertoprotectoutdoorunitfromfreezing,reversedtocoolingcycleto
defrostoftheoutdoorunit.
n Fuzzy Operation (Outdoor unit C/O Model)
According to the temperature set by Fuzzy rule, when the intake air temp is 0.5C(33F) or more below the
settingtemp,thecompressoristurnedoff.When0.5C(33F)ormoreabovethesettingtemp,thecompres-
soristurnedon.
CompressorONTemp=>SettingTemp+0.5C(33F)
CompressorOFFTemp=>SettingTemp+0.5C(33F)
AtthebeginningofFuzzymodeoperation,thesettingtemperatureisautomaticallyselectedaccordingtothe
intakeairtempatthattime.
26C(78F)IntakeAirTemp=>25C(76F)
24C(76F)IntakeAirTemp<26C(78F)=>IntakeAirTemp+1C(34F)
22C(72F)IntakeAirTemp<24C(76F)=>IntakeAirTemp+0.5C(33F)
18C(64F)IntakeAirTemp<22C(72F)=>IntakeAirTemp
IntakeAirTemp<18C(64F)=>18C(64F)
When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, the
Fuzzy key value and the intake air temperature at that time are compared to select the setting temperature
automaticallyaccordingtotheFuzzyrule.
WhileinFuzzyoperation,theairflowspeedoftheindoorfanisautomaticallyselectedaccordingtothetemper-
- 49 -
Copyright2010LGElectronics.Inc.Allrightreserved.
Onlyfortrainingandservicepurposes
LGEInternalUseOnly
Operation Details
ature
n Fuzzy Operation (Outdoor unit H/P Model)
Whenanyofoperationmodeisnotselectedlikethemomentofthepoweronorwhen3hrshaspassedsince
theoperationoff,theoperationmodeisselected.
Whendeterminingtheoperationmode,thecompressor,theoutdoorfan,andthe4wayvalveareoffandonly
the indoor fan is operated for 15 seconds. Then an operation mode is selected according to the intake air
tempatthatmomentasfollows.
24C(76F)InatakeAirTemp=>FuzzyOperationforCooling
21C(70F)InatakeAirTemp<24C(76F)=>FuzzyOperationforDehumidification
InatakeAirTemp<21C(70F)=>FuzzyOperationforHeating
Ifanyoftheoperationmodesamongcooling/dehumidification/heatingmodeoperationsiscarriedoutfor10
secorlongerbeforeFuzzyoperation,themodebeforeFuzzyoperationisoperated.
1) Fuzzy Operation for Cooling
AccordingtothesettingtemperatureselectedbyFuzzyrule,whentheintakeairtempis0.5C(33F)ormore
belowthesettingtemp,thecompressoristurnedoff.When0.5C(33F)ormoreabovethesettingtemp,the
compressoristurnedon.
CompressorONTemp=>SettingTemp+0.5C(33F)
CompressorOFFTemp=>SettingTemp+0.5C(33F)
AtthebeginningofFuzzymodeoperation,thesettingtemperatureisautomaticallyselectedaccordingtothe
intakeairtempatthattime.
26C(78F)IntakeAirTemp=>25C(76F)
24C(76F)IntakeAirTemp<26C(78F)=>IntakeAirTemp+1C(34F)
22C(72F)IntakeAirTemp<24C(76F)=>IntakeAirTemp+0.5C(33F)
18C(64F)IntakeAirTemp<22C(72F)=>IntakeAirTemp
IntakeAirTemp<18C(64F)=>18C(64F)
When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, the
Fuzzy key value and the intake air temperature at that time are compared to select the setting temperature
automaticallyaccordingtotheFuzzyrule.
WhileinFuzzyoperation,theairflowspeedoftheindoorfanisautomaticallyselectedaccordingtothetemperature.
2) Fuzzy Operation for Dehumidification
AccordingtothesettingtemperatureselectedbyFuzzyrule,whentheintakeairtempis0.5Cormorebelow
thesettingtemp,thecompressoristurnedoff.When0.5C(33F)ormoreabovethesettingtemp,thecom-
pressoristurnedon.
CompressorONTemp=>SettingTemp+0.5C(33F)
CompressorOFFTemp=>SettingTemp+0.5C(33F)
- 50 -
Copyright2010LGElectronics.Inc.Allrightreserved.
Onlyfortrainingandservicepurposes
LGEInternalUseOnly
Operation Details
At the beginning of Fuzzy mode operation, the setting temperature is automatically selected according to
theintakeairtempatthattime.
26C(78F)IntakeAirTemp=>25C(76F)
24C(76F)IntakeAirTemp<26C(78F)=>IntakeAirTemp+1C(34F)
22C(72F)IntakeAirTemp<24C(76F)=>IntakeAirTemp+0.5C(33F)
18C(64F)IntakeAirTemp<22C(72F)=>IntakeAirTemp
IntakeAirTemp<18C(64F)=>18C(64F)
WhentheFuzzykey(TemperatureControlkey)isinputaftertheinitialsettingtemperatureisselected,the
Fuzzykeyvalueandtheintakeairtemperatureatthattimearecomparedtoselectthesettingtemperature
automaticallyaccordingtotheFuzzyrule.
WhileinFuzzyoperation,theairflowspeedoftheindoorfanrepeatsthelowairflowspeedorpauseasin
dehumidificationoperation.
3) Fuzzy Operation for Heating
AccordingtothesettingtemperatureselectedbyFuzzyrule,whentheintakeairtempis3C(37F)ormore
above the setting temp, the compressor is turned off. When below the setting temp, the compressor is
turnedon.
CompressorONTemp=>SettingTemp+2C(36F)
CompressorOFFTemp=>SettingTemp+4C(39F)
At the beginning of Fuzzy mode operation, the setting temperature is automatically selected according to
theintakeairtempatthattime.
20C(68F)IntakeAirTemp=>IntakeAirTemp+0.5C(33F)
IntakeAirTemp<20C(68F)=>20C(68F)
WhentheFuzzykey(TemperatureControlkey)isinputaftertheinitialsettingtemperatureisselected,the
Fuzzykeyvalueandtheintakeairtemperatureatthattimearecomparedtoselectthesettingtemperature
automaticallyaccordingtotheFuzzyrule.
WhileinFuzzyoperation,theairflowspeedoftheindoorfanissettothehighorthemediumaccordingto
theintakeairtemperatureandthesettingtemperature.
n Airflow Speed Selection
Theairflowspeedoftheindoorfanissettohigh,medium,low,orchaosbytheinputoftheairflowspeed
selectionkeyontheremotecontroller.
n On-Timer Operation
Whenthesettimeisreachedafterthetimeisinputbytheremotecontroller,theappliancestartstooperate.
ThetimerLEDisonwhentheon-timerisinput.Itisoffwhenthetimesetbythetimerisreached.
Iftheapplianceisoperatingatthetimesetbythetimer,theoperationcontinues.
n Off-Timer Operation
Whenthesettimeisreachedafterthetimeisinputbytheremotecontroller,theappliancestopsoperating.
ThetimerLEDisonwhentheoff-timerisinput.Itisoffwhenthetimesetbythetimerisreached.
Iftheapplianceisonpauseatthetimesetbythetimer,thepausecontinues.
- 51 -
Copyright2010LGElectronics.Inc.Allrightreserved.
Onlyfortrainingandservicepurposes
LGEInternalUseOnly
Operation Details
n Off-Timer <=> On-Timer Operation
Whenthesettimeisreachedaftertheon/offtimeisinputbytheremotecontroller,theon/off-timeroperation
iscarriedoutaccordingtothesettime.
n Sleep Timer Operation
When the sleep time is reached after <1,2,3,4,5,6,7,0(cancel) hr> is input by the remote controller while in
applianceoperation,theoperationoftheappliancestops.
Whiletheapplianceisonpause,thesleeptimermodecannotbeinput.
While in cooling mode operation, 30 min later since the start of the sleep timer, the setting temperature
increasesby1C(34F)Afteranother30minelapse,itincreasesby1C(34F)again.
Whenthesleeptimermodeisinputwhileincoolingcyclemode,theairflowspeedoftheindoorfanissetto
thelow.
Whenthesleeptimermodeisinputwhileinheatingcyclemode,theairflowspeedoftheindoorfanissetto
themedium.
n Chaos Swing Mode
BytheChaosSwingkeyinput,thevaneautomaticallyoperateswiththeChaosSwingortheyarefixedtothe
desireddirection.
n Chaos Natural Wind Mode
WhentheChaosNaturalWindmodeisselectedandthenoperated,thehigh,medium,orlowspeedoftheair-
flowmodeisoperatedfor2~15secrandomlybytheChaosSimulation.
n Jet Cool Mode Operation (Outdoor unit C/O Model)
IftheJetCoolkeyisinputatanyoperationmodewhileinapplianceoperation,theJetCoolmodeoperates.
IntheJetCoolmode,theindoorfanisoperatedatsuper-highspeedfor30minatcoolingmodeoperation.
IntheJetCoolmodeoperation,theroomtemperatureiscontrolledtothesettingtemperature,18C(64F)
WhenthesleeptimermodeisinputwhileintheJetCoolmodeoperation,theJetCoolmodehasthepriority.
WhentheJetCoolkeyisinput,theupper/lowervanesareresettothoseoftheinitialcoolingmodeandthen
operatedinorderthattheairoutflowcouldreachfurther.
n Jet Cool Mode Operation (Outdoor unit H/P Model)
While in heating mode or Fuzzy operation, the Jet Cool key cannot be input. When it is input while in the
othermodeoperation(cooling,dehumidification,ventilation),theJetCoolmodeisoperated.
IntheJetCoolmode,theindoorfanisoperatedatsuper-highspeedfor30minatcoolingmodeoperation.
IntheJetCoolmodeoperation,theroomtemperatureiscontrolledtothesettingtemperature,18C(64F)
WhenthesleeptimermodeisinputwhileintheJetCoolmodeoperation,theJetCoolmodehasthepriority.
WhentheJetCoolkeyisinput,theupper/lowervanesareresettothoseoftheinitialcoolingmodeandthen
operatedinorderthattheairoutflowcouldreachfurther.
n Auto Restarting Operation
When the power is restored after a sudden power failure while in appliance operation, the mode before the
powerfailureiskeptonthememoryandtheapplianceautomaticallyoperatesinthemodeonthememory.
OperationModethatiskeptonthememory
- 52 -
Copyright2010LGElectronics.Inc.Allrightreserved.
Onlyfortrainingandservicepurposes
LGEInternalUseOnly
Operation Details
-StateofOperationON/OFF
-OperationMode/SettingTemp/SelectedAirflowSpeed
-SleepTimerMode/RemainingTimeofSleepTimer(unitofhour)
n Forced Operation (Outdoor unit C/O Model)
Tooperatetheappliancebyforceincasethattheremotecontrollerislost,theforcedoperationbuttonison
themainunitoftheappliancetooperatetheapplianceinthestandardconditions.
Presstheforcedoperationbutton,theforcedoperationiscarriedout.
Presstheforcedoperationbuttononceagaintostopoperation.
Theforcedoperationiscarriedoutincoolingmodewiththesettingtemperature22C(72F)andthehigh
speedofairflow.
n Forced Operation (Outdoor unit H/P Model)
Tooperatetheappliancebyforceincasethattheremotecontrollerislost,theforcedoperationselection
switchisonthemainunitoftheappliancetooperatetheapplianceinthestandardconditions.
Presstheforcedoperationbutton,theforcedoperationiscarriedout.
Presstheforcedoperationbuttononceagaintostopoperation.
Intheforcedoperationmode,theindoorfanisoperatedatlowspeedforaround15secandthentheoperation
conditionissetaccordingtotheintakeairtemperatureasfollows.
24C(76F)IntakeAirTemp=>CoolingModeOperation,22C(72F),HighSpeed
21C(70F)IntakeAirTemp<24C(76F)=>DehumidificationOperation,23C(74F),HighSpeed
IntakeAirTemp<21C(70F)=>HeatingModeOperation,24C(76F),HighSpeed
n Test Operation Control
Tochecktheconditionoftheinstallationwheninstallingtheappliance,theapplianceisoperatedatcooling
mode,highspeedofairflow,compressor-onfor18minwithoutcontrollingtheroomtemperature.
Aftersupplyingpowertothemainbody,keeppressingtheforcedoperationbuttonforabout3seconds.
Whileintestoperation,akeycanbeinputbytheremotecontroller.
Whenakey(operationstart/stop,operationmodeselection,airflowspeedselection,temperaturecontrol,Jet
Cool)isinputbytheremotecontroller,thetestoperationiscanceledandtheapplianceisoperatedaccording
tothesettingbytheremotecontroller.
n Protection of the evaporator pipe from frosting
In the temperrature of the indoor pipe is below 0C(32F) after 7 minutes from starting the compressor, the
compressorandoutdoorfanarestopped,and3minutesdelayofoperatingofthecompressor,whenthetem-
peratureoftheindoorpipeisover7C(45F),thecompressorandtheoutdoorfanarereoperated.
Outdoorfanmotorstopswhenindoorpipetemperatureisblow3C(37F)andrestartsatthepipetemperature
above6Corafter90seconds,ifthepipetemperaturedoesnotriseto6C(43F),outdoorfanmotorrunscon-
tinuouslyatevenbelow3C(37F).
- 53 -
Copyright2010LGElectronics.Inc.Allrightreserved.
Onlyfortrainingandservicepurposes
LGEInternalUseOnly
Operation Details
n Buzzer Sounding Operation
Whentheappliance-operationkeyisinputbytheremotecontroller,theshortbeep-beep-sounds.
Whentheappliance-pausekeyisinputbytheremotecontroller,thelongbeepsounds.
n Air Cleaner Operation
WhenanaircleanerfunctionisselectedduringAirConditioneroperation
-Plasmaaircleanerfunctionwillbeoperatedwhileinanyoperationmodewithselectingthefunction.
-Thefunctionistobestoppedwhileitisoperatingwithselectingthefunction.
Whenanaircleanerfunctionisselectedduringoperationoff
-Thefunctionwillbeonlyoperated.
Wheninletgrilleofairconditionerisopenedduringplasmaoperation,HighVoltageGenerator(H.V.B)istobe
stopped.Wheninletgrilleofairconditionerisclosedduringplasmaoperation,HighVoltageGenerator(H.V.B)
willbeoperatedagain.
- 54 -
Copyright2010LGElectronics.Inc.Allrightreserved.
Onlyfortrainingandservicepurposes
LGEInternalUseOnly
Dimensions
3. Dimensions
7
6
,

S
e
o
n
g
s
a
n
-
d
o
n
g
,

C
h
a
n
g
w
o
n

C
i
t
y
,

G
y
e
o
n
g
n
a
m
,
6
4
1
-
7
1
3
,

K
o
r
e
a
w
w
w
.
l
g
e
a
i
r
c
o
n
.
c
o
m
C
H
A
S
S
I
S

C
O
D
E
:

S
F
A
R
T

C
O
O
L

G
a
l
l
e
r
y
A
R
N
U
0
7
3
S
F
*
2
A
R
N
U
0
9
3
S
F
*
2
A
R
N
U
1
2
3
S
F
*
2
W
M
o
d
e
l
A
R
N
U
0
7
3
S
F
*
2
A
R
N
U
0
9
3
S
F
*
2
A
R
N
U
1
2
3
S
F
*
2
H
D
6
0
0
(
2
3
-
5
/
8
)
6
0
0
(
2
3
-
5
/
8
)
1
4
6
(
5
-
1
1
/
1
6
)
N
o
t
e
1
.

U
n
i
t

s
h
o
u
l
d

b
e

i
n
s
t
a
l
l
e
d

i
n

c
o
m
p
l
i
a
n
c
e

w
i
t
h

t
h
e

i
n
s
t
a
l
l
a
t
i
o
n

m
a
n
u
a
l





i
n

t
h
e

p
r
o
d
u
c
t

b
o
x
.
2
.

U
n
i
t

s
h
a
l
l

b
e

g
r
o
u
n
d
e
d

i
n

a
c
c
o
r
d
a
n
c
e

w
i
t
h

t
h
e

l
o
c
a
l

r
e
g
u
l
a
t
i
o
n
s

o
r





a
p
p
l
i
c
a
b
l
e

n
a
t
i
o
n
a
l

c
o
d
e
s
.
[
U
n
i
t

:

m
m
(
i
n
c
h
)
]
[
U
n
i
t

:

m
m
(
i
n
c
h
)
]
L
G

E
l
e
c
t
r
o
n
i
c
s

U
S
A
,

H
V
A
C

D
i
v
i
s
i
o
n
1
0
0
0

S
y
l
v
a
n

A
v
e
n
u
e
,

E
n
g
l
e
w
o
o
d

C
l
i
f
f
s
,

N
J

0
7
6
3
2
w
w
w
.
l
g
u
s
a
.
c
o
m

/

w
w
w
.
l
g
h
v
a
c
.
c
o
m
N
a
m
e



1
A
i
r

d
i
s
c
h
a
r
g
e

g
r
i
l
l




2
A
i
r

s
u
c
t
i
o
n

g
r
i
l
l

N
u
m
b
e
r
D
e
s
c
r
i
p
i
t
i
o
n
P
i
p
e

H
o
l
e
F
i
x

H
o
l
e
H
a
n
g
e
r

H
o
l
e
H
W
D
1
2
1
1
5
0
0
(
1
9
-
5
/
8
)
5 2 5 ( 2 0 - 5 / 8 )
- 55 -
Copyright2010LGElectronics.Inc.Allrightreserved.
Onlyfortrainingandservicepurposes
LGEInternalUseOnly
1. Funtions ......................................................................................56
2. Operation Details........................................................................57
3. Dimensions .................................................................................60
Ceiling Concealed Duct Type (Low static)
- 56 -
Copyright2010LGElectronics.Inc.Allrightreserved.
Onlyfortrainingandservicepurposes
LGEInternalUseOnly
1. Funtions
Indoor Unit
Operation ON/OFF by Remote controller
Sensing the Room Temperature
Room temperature control
Starting Current Control
Indoor Fan Speed Control
Soft Dry Operation Mode
Deice (defrost) control (Heating)
Auto Restart
Hot-start Control (Heating)
Theindoorfandoesnotrotateuntiltheevaporatorpiping
temperaturereaches25C(76F).
High head height Drain pump
Astandarddrain-headheightofupto700mm(27-9/16inch)
ispossible.
Central Control(Optional)
Itisoperatingindividuallyortotallybycentralcontrolfunction.
Roomtemperaturesensor.(Thermistor)
MaintainstheroomtemperatureinaccordancewiththeSettingTemperature.
Indoorfanisdelayedfor5secondsatthestarting.
High,Med,Low
Intermittentoperationoffanatlowspeed.
Althoughtheair-conditioneristurnedoffbyapowerfailure,itisrestartedauto-
maticallypreviousoperationmodeafterpowersupply.
Boththeindoorandoutdoorfanstopsduringdefrosting.
Hotstartafterdefrostends.
Functions
- 57 -
Copyright2010LGElectronics.Inc.Allrightreserved.
Onlyfortrainingandservicepurposes
LGEInternalUseOnly
2. Operation Details
n Soft-Dry Operation
Theindoorfanspeedisautomaticallysettothelow,sotheshiftoftheindoorfanspeedisimpossiblebecauseof
alreadybeingsettothebestspeedforDryOperationbymicrocontrollercontrol.
n Cooling Mode Operation
WhenselectingtheCooling()ModeOperation,theunitwilloperateaccordingtothesettingbytheremotecontroller
andtheoperationdiagramisasfollowing.
IntakeAirTemperature
Thermo.ON
(SETTEMPERATURE
+0.5C(33F))
Thermo.OFF
(SETTEMPERATURE
Morethan Morethan
-0.5C(33F))
3minutes 3minutes
Selecting Selecting Selecting
fanspeed fanspeed fanspeed
COMPRESSOR ON OFF ON OFF ON
INDOORFAN LowLow
(1) The function of main control
Operation Details
Thermal ON Thermal OFF
IndoorUnitmode ST+0.5 ST-0.5
2TH(Remo.+Indoor)
Tobeselectedhighertemperature Tobeselectedhighertemperature
contrastIndoorUnitandRemo. contrastIndoorUnitandRemo.
Remo.Mode ST+0.5 ST-0.5
- 58 -
Copyright2010LGElectronics.Inc.Allrightreserved.
Onlyfortrainingandservicepurposes
LGEInternalUseOnly
Operation Details
n Heating Mode Operation
Theunitwilloperateaccordingtothesettingbytheremotecontrollerandtheoperationdiagramisshownasfollowing.
Thermal
Outdoor fan
Indoor fan
4way valve
Setting Temperature
(Thermal ON)
Setting Temperature
+3C(37F)
(Thermal OFF)
Indoor unit
Heat-Exchanger
temperature
T
LT
T
ST
1min
Minimum
3min
1min
3min
Setting
fan
spped
Setting
fan
spped
Setting
fan
spped
40C(104F)
T
On
T
Off
ON
ON
ON
ON
Low Low Low Low Low Off Off Off
ON
OFF
OFF
Low fan during 10sec
A
A
B
C
B
Intake Air Temperature
Compressor-off interval : - While the indoor Heat-Exchanger temperature is higher than 40C(104F), fan operates
at low speed, when it becomes lower than 40C(104F) fan stops.
- For eluminating latent heat-loss, fan operates at low speed for 10 seconds periodically.
- To be operated "Low" except initial Hotstart operation
C
Chassis
HotstartOn T
On
HotstartOff T
Off
Lowtemperature T
LT
SettingTemperature T
ST
HighStatic LowStatic Convertible
BH BG BR
19C(66F) 19C(66F) 19C(66F) 19C(66F) 19C(66F) 19C(66F) 19C(66F) 26C(78F) 26C(78F)
22C(72F) 22C(72F) 22C(72F) 22C(72F) 22C(72F) 22C(72F) 22C(72F) 27C(80F) 27C(80F)
25C(76F) 25C(76F) 25C(76F) 25C(76F) 25C(76F) 25C(76F) 25C(76F) 28C(82F) 28C(82F)
27C(80F) 27C(80F) 27C(80F) 27C(80F) 27C(80F) 27C(80F) 27C(80F) 30C(86F) 30C(86F)
B1 B2 CE CF VE VJ
- 59 -
Copyright2010LGElectronics.Inc.Allrightreserved.
Onlyfortrainingandservicepurposes
LGEInternalUseOnly
n Hot-Start Control
TheindoorfandoesnotrotateuntiltheindoorunitHex-Exchangertemperaturereaches30C(86F).
Theoperationdiagramisasfollowing.
Operation Details
ON
ON
Off Off Low Low
1 min
Hotstart On
Hotstart Off
Indoor unit
Heat-Exchanger
temperature
Setting fan
speed
Setting fan
speed
Thermal
Outdoor fan
Indoor fan
4way Valve ON
1 min
InitialHotstartOnstate
PowerOff On
OperationOff On
Coolingoperation Heatingoperation
Defrostoperation
- 60 -
Copyright2010LGElectronics.Inc.Allrightreserved.
Onlyfortrainingandservicepurposes
LGEInternalUseOnly
3. Dimensions
Dimensions
7
6
,

S
e
o
n
g
s
a
n
-
d
o
n
g
,

C
h
a
n
g
w
o
n

C
i
t
y
,

G
y
e
o
n
g
n
a
m
,
6
4
1
-
7
1
3
,

K
o
r
e
a
w
w
w
.
l
g
e
a
i
r
c
o
n
.
c
o
m
C
H
A
S
S
I
S

C
O
D
E
:

B
1
/
B
2
C
e
i
l
i
n
g

C
o
n
c
e
a
l
e
d

D
u
c
t

(
L
o
w

S
t
a
t
i
c
)
A
R
N
U
0
7
3
B
1
G
2

A
R
N
U
0
9
3
B
1
G
2
A
R
N
U
1
2
3
B
1
G
2
A
R
N
U
1
5
3
B
1
G
2
A
R
N
U
1
8
3
B
2
G
2
A
R
N
U
2
4
3
B
2
G
2
N
o
t
e
1
.

U
n
i
t

s
h
o
u
l
d

b
e

i
n
s
t
a
l
l
e
d

i
n

c
o
m
p
l
i
a
n
c
e

w
i
t
h

t
h
e

i
n
s
t
a
l
l
a
t
i
o
n

m
a
n
u
a
l





i
n

t
h
e

p
r
o
d
u
c
t

b
o
x
.
2
.

U
n
i
t

s
h
a
l
l

b
e

g
r
o
u
n
d
e
d

i
n

a
c
c
o
r
d
a
n
c
e

w
i
t
h

t
h
e

l
o
c
a
l

r
e
g
u
l
a
t
i
o
n
s

o
r





a
p
p
l
i
c
a
b
l
e

n
a
t
i
o
n
a
l

c
o
d
e
s
.
N
a
m
e
1
L
i
q
u
i
d

p
i
p
e

c
o
n
n
e
c
t
i
o
n
2
G
a
s

p
i
p
e

c
o
n
n
e
c
t
i
o
n

3
D
r
a
i
n

p
i
p
e

c
o
n
n
e
c
t
i
o
n

4
P
o
w
e
r

s
u
p
p
l
y

c
o
n
n
e
c
t
i
o
n

5
A
i
r

d
i
s
c
h
a
r
g
e

6
A
i
r

s
u
c
t
i
o
n
N
u
m
b
e
r
D
e
s
c
r
i
p
i
t
i
o
n
[
U
n
i
t

:

m
m
(
i
n
c
h
)
]
U
n
i
t

s
i
z
e
(
7
k
,
9
k
,
1
2
k
,
1
8
k
)
:

6
.
3
5
(
1
/
4
)
U
n
i
t

s
i
z
e
(
2
4
k
)
:

9
.
5
2
(
3
/
8
)
U
n
i
t

s
i
z
e
(
7
k
,
9
k
,
1
2
k
,
1
8
k
)
:

1
2
.
7
(
1
/
2
)
U
n
i
t

s
i
z
e
(
2
4
k
)
:

1
5
.
8
8
(
5
/
8
)
A
3 8 3 ( 1 5 - 1 / 1 6 )
5 7 5 ( 2 2 - 5 / 8 )
1 6 1 ( 6 - 5 / 1 6 )
1 4 ( 1 / 2 )
1 5 4 ( 6 )
1 9 0 ( 7 - 7 / 1 6 )
1 8 ( 3 / 4 )
1
8
(
3
/
4
)
B
C
1
3
(
1
/
2
)
D
8
2
0
(
3
2
-
5
/
1
6
)
A
B
C
D
A
R
N
U
0
7
3
B
1
G
2

A
R
N
U
0
9
3
B
1
G
2
A
R
N
U
1
2
3
B
1
G
2
A
R
N
U
1
5
3
B
1
G
2
A
R
N
U
1
8
3
B
2
G
2
A
R
N
U
2
4
3
B
2
G
2
7
2
8
(
2
8
-
1
1
/
1
6
)
8
5
6
(
3
3
-
1
1
/
1
6
)
7
9
4
(
3
1
-
5
/
1
6
)
1
1
0
0
(
4
3
-
5
/
1
6
)
1
0
0
8
(
3
9
-
1
1
/
1
6
)
1
1
3
1
(
4
4
-
9
/
1
6
)
1
0
7
2
(
4
2
-
3
/
1
6
)
[
U
n
i
t

:

m
m
(
i
n
c
h
)
]
L
G

E
l
e
c
t
r
o
n
i
c
s

U
S
A
,

H
V
A
C

D
i
v
i
s
i
o
n
1
0
0
0

S
y
l
v
a
n

A
v
e
n
u
e
,

E
n
g
l
e
w
o
o
d

C
l
i
f
f
s
,

N
J

0
7
6
3
2
w
w
w
.
l
g
u
s
a
.
c
o
m

/

w
w
w
.
l
g
h
v
a
c
.
c
o
m
2
1
1
9
0
(
7
-
7
/
1
6
)
6
5
(2
-1
/2
)
6
0
(2
-3
/8
)
2 7 7 ( 1 0 - 7 / 8 )
2 1 6 ( 8 - 1 / 2 )
2 4 ( 1 1 / 1 2 )
1
3
4
2
5
6
- 61 -
Copyright2010LGElectronics.Inc.Allrightreserved.
Onlyfortrainingandservicepurposes
LGEInternalUseOnly
1. Funtions ......................................................................................62
2. Operation Details........................................................................63
3. Dimensions .................................................................................66
Ceiling Concealed Duct Type (Built in)
- 62 -
Copyright2010LGElectronics.Inc.Allrightreserved.
Onlyfortrainingandservicepurposes
LGEInternalUseOnly
1. Funtions
Indoor Unit
Operation ON/OFF by Remote controller
Sensing the Room Temperature
Room temperature control
Starting Current Control
Indoor Fan Speed Control
Soft Dry Operation Mode
Deice (defrost) control (Heating)
Auto Restart
Hot-start Control (Heating)
Theindoorfandoesnotrotateuntiltheevaporatorpiping
temperaturereaches25C(76F).
High head height Drain pump
Astandarddrain-headheightofupto700mm(27-9/16inch)
ispossible.
Central Control(Optional)
Itisoperatingindividuallyortotallybycentralcontrolfunction.
Roomtemperaturesensor.(Thermistor)
MaintainstheroomtemperatureinaccordancewiththeSettingTemperature.
Indoorfanisdelayedfor5secondsatthestarting.
High,Med,Low
Intermittentoperationoffanatlowspeed.
Althoughtheair-conditioneristurnedoffbyapowerfailure,itisrestartedauto-
maticallypreviousoperationmodeafterpowersupply.
Boththeindoorandoutdoorfanstopsduringdefrosting.
Hotstartafterdefrostends.
Functions
- 63 -
Copyright2010LGElectronics.Inc.Allrightreserved.
Onlyfortrainingandservicepurposes
LGEInternalUseOnly
2. Operation Details
n Soft-Dry Operation
Theindoorfanspeedisautomaticallysettothelow,sotheshiftoftheindoorfanspeedisimpossiblebecauseof
alreadybeingsettothebestspeedforDryOperationbymicrocontrollercontrol.
n Cooling Mode Operation
WhenselectingtheCooling()ModeOperation,theunitwilloperateaccordingtothesettingbytheremotecontroller
andtheoperationdiagramisasfollowing.
(1) The function of main control
Operation Details
Thermal ON Thermal OFF
IndoorUnitmode ST+0.5 ST-0.5
2TH(Remo.+Indoor)
Tobeselectedhighertemperature Tobeselectedhighertemperature
contrastIndoorUnitandRemo. contrastIndoorUnitandRemo.
Remo.Mode ST+0.5 ST-0.5
IntakeAirTemperature
Thermo.ON
(SETTEMPERATURE
+0.5C(33F))
Thermo.OFF
(SETTEMPERATURE
Morethan Morethan
-0.5C(33F))
3minutes 3minutes
Selecting Selecting Selecting
fanspeed fanspeed fanspeed
COMPRESSOR ON OFF ON OFF ON
INDOORFAN LowLow
- 64 -
Copyright2010LGElectronics.Inc.Allrightreserved.
Onlyfortrainingandservicepurposes
LGEInternalUseOnly
Operation Details
n Heating Mode Operation
Theunitwilloperateaccordingtothesettingbytheremotecontrollerandtheoperationdiagramisshownasfollowing.
Thermal
Outdoor fan
Indoor fan
4way valve
Setting Temperature
(Thermal ON)
Setting Temperature
+3C(37F)
(Thermal OFF)
Indoor unit
Heat-Exchanger
temperature
T
LT
T
ST
1min
Minimum
3min
1min
3min
Setting
fan
spped
Setting
fan
spped
Setting
fan
spped
40C(104F)
T
On
T
Off
ON
ON
ON
ON
Low Low Low Low Low Off Off Off
ON
OFF
OFF
Low fan during 10sec
A
A
B
C
B
Intake Air Temperature
Compressor-off interval : - While the indoor Heat-Exchanger temperature is higher than 40C(104F), fan operates
at low speed, when it becomes lower than 40C(104F) fan stops.
- For eluminating latent heat-loss, fan operates at low speed for 10 seconds periodically.
- To be operated "Low" except initial Hotstart operation
C
Chassis
HotstartOn T
On
HotstartOff T
Off
Lowtemperature T
LT
SettingTemperature T
ST
HighStatic LowStatic Convertible
BH BG BR
19C(66F) 19C(66F) 19C(66F) 19C(66F) 19C(66F) 19C(66F) 19C(66F) 26C(78F) 26C(78F)
22C(72F) 22C(72F) 22C(72F) 22C(72F) 22C(72F) 22C(72F) 22C(72F) 27C(80F) 27C(80F)
25C(76F) 25C(76F) 25C(76F) 25C(76F) 25C(76F) 25C(76F) 25C(76F) 28C(82F) 28C(82F)
27C(80F) 27C(80F) 27C(80F) 27C(80F) 27C(80F) 27C(80F) 27C(80F) 30C(86F) 30C(86F)
B1 B2 CE CF VE VJ
- 65 -
Copyright2010LGElectronics.Inc.Allrightreserved.
Onlyfortrainingandservicepurposes
LGEInternalUseOnly
n Hot-Start Control
TheindoorfandoesnotrotateuntiltheindoorunitHex-Exchangertemperaturereaches30C(86F).
Theoperationdiagramisasfollowing.
Operation Details
ON
ON
Off Off Low Low
1 min
Hotstart On
Hotstart Off
Indoor unit
Heat-Exchanger
temperature
Setting fan
speed
Setting fan
speed
Thermal
Outdoor fan
Indoor fan
4way Valve ON
1 min
InitialHotstartOnstate
PowerOff On
OperationOff On
Coolingoperation Heatingoperation
Defrostoperation
- 66 -
Copyright2010LGElectronics.Inc.Allrightreserved.
Onlyfortrainingandservicepurposes
LGEInternalUseOnly
3. Dimensions
Dimensions
7
6
,

S
e
o
n
g
s
a
n
-
d
o
n
g
,

C
h
a
n
g
w
o
n

C
i
t
y
,

G
y
e
o
n
g
n
a
m
,
6
4
1
-
7
1
3
,

K
o
r
e
a
w
w
w
.
l
g
e
a
i
r
c
o
n
.
c
o
m
C
H
A
S
S
I
S

C
O
D
E
:

B
3
/
B
4
C
e
i
l
i
n
g

C
o
n
c
e
a
l
e
d

D
u
c
t

(
B
u
i
l
t

i
n
)
A
R
N
U
0
7
3
B
3
G
2
+
P
B
S
G
B
3
0
(
A
c
c
e
s
s
o
r
y
)
,

P
B
S
C
3
0
(
A
c
c
e
s
s
o
r
y
)
A
R
N
U
0
9
3
B
3
G
2
+
P
B
S
G
B
3
0
(
A
c
c
e
s
s
o
r
y
)
,

P
B
S
C
3
0
(
A
c
c
e
s
s
o
r
y
)
A
R
N
U
1
2
3
B
3
G
2
+
P
B
S
G
B
3
0
(
A
c
c
e
s
s
o
r
y
)
,

P
B
S
C
3
0
(
A
c
c
e
s
s
o
r
y
)
A
R
N
U
1
5
3
B
3
G
2
+
P
B
S
G
B
3
0
(
A
c
c
e
s
s
o
r
y
)
,

P
B
S
C
3
0
(
A
c
c
e
s
s
o
r
y
)
A
R
N
U
1
8
3
B
4
G
2
+
P
B
S
G
B
4
0
(
A
c
c
e
s
s
o
r
y
)
,

P
B
S
C
4
0
(
A
c
c
e
s
s
o
r
y
)
A
R
N
U
2
4
3
B
4
G
2
+
P
B
S
G
B
4
0
(
A
c
c
e
s
s
o
r
y
)
,

P
B
S
C
4
0
(
A
c
c
e
s
s
o
r
y
)
N
o
t
e
1
.

U
n
i
t

s
h
o
u
l
d

b
e

i
n
s
t
a
l
l
e
d

i
n

c
o
m
p
l
i
a
n
c
e

w
i
t
h

t
h
e

i
n
s
t
a
l
l
a
t
i
o
n

m
a
n
u
a
l





i
n

t
h
e

p
r
o
d
u
c
t

b
o
x
.
2
.

U
n
i
t

s
h
a
l
l

b
e

g
r
o
u
n
d
e
d

i
n

a
c
c
o
r
d
a
n
c
e

w
i
t
h

t
h
e

l
o
c
a
l

r
e
g
u
l
a
t
i
o
n
s

o
r





a
p
p
l
i
c
a
b
l
e

n
a
t
i
o
n
a
l

c
o
d
e
s
.
W
i
t
h

S
u
c
t
i
o
n

G
r
i
l
l
e
W
i
t
h

S
u
c
t
i
o
n

G
r
i
l
l
e

&

S
u
c
t
i
o
n

C
a
n
v
a
s
A
_
1
A
_
2
C
_
2
B _ 2
A
_
3
B
_
3
C _ 3
B
t
u
/
h
A
_
1
7
,
9
,
1
2
k
8
2
0
(
3
2
-
5
/
1
6
)
1
8
,
2
4
k
1
1
0
0
(
4
3
-
5
/
1
6
)
A
_
2
B
_
2
C
_
2
P
B
S
G
B
3
0
9
1
0
(
3
5
-
1
3
/
1
6
)
3
5
9
(
1
4
-
1
/
8
)
5
6
(
2
-
3
/
1
6
)
P
B
S
G
B
4
0
1
1
8
8
(
4
6
-
1
3
/
1
6
)
3
5
9
(
1
4
-
1
/
8
)
5
6
(
2
-
3
/
1
6
)
2 5 0 ( 9 - 1 3 / 1 6 )
1 9 0 ( 7 - 7 / 1 6 )
6 1 8 ( 2 4 - 5 / 1 6 )
3 8 8 ( 1 5 - 1 / 4 )
1 9 0 ( 7 - 7 / 1 6 )
5 0 0 ( 1 9 - 1 1 / 1 6 ) ( M a x )
5 7 5 ( 2 2 - 5 / 8 )
3 8 8 ( 1 5 - 1 / 4 )
A
_
3
B
_
3
C
_
3


P
B
S
C
3
0
8
2
1
(
3
2
-
5
/
1
6
)
2
7
4
(
1
0
-
1
1
/
1
6
)
4
2
~
2
5
0
(
1
-
9
/
1
6
~
9
-
1
3
/
1
6
)


P
B
S
C
4
0
1
1
0
0
(
4
3
-
5
/
1
6
)
2
7
4
(
1
0
-
1
1
/
1
6
)
4
2
~
2
5
0
(
1
-
9
/
1
6
~
9
-
1
3
/
1
6
)
L
G

E
l
e
c
t
r
o
n
i
c
s

U
S
A
,

H
V
A
C

D
i
v
i
s
i
o
n
1
0
0
0

S
y
l
v
a
n

A
v
e
n
u
e
,

E
n
g
l
e
w
o
o
d

C
l
i
f
f
s
,

N
J

0
7
6
3
2
w
w
w
.
l
g
u
s
a
.
c
o
m

/

w
w
w
.
l
g
h
v
a
c
.
c
o
m
1
9
0
(
7
-
7
/
1
6
)
6
5
(2
-1
/2
)
6
0
(2
-3
/8
)
2 7 7 ( 1 0 - 7 / 8 )
2 1 6 ( 8 - 1 / 2 )2 4 ( 1 1 / 1 2 )
N
a
m
e
1
L
i
q
u
i
d

p
i
p
e

c
o
n
n
e
c
t
i
o
n
2
G
a
s

p
i
p
e

c
o
n
n
e
c
t
i
o
n

3
D
r
a
i
n

p
i
p
e

c
o
n
n
e
c
t
i
o
n

4
P
o
w
e
r

s
u
p
p
l
y

c
o
n
n
e
c
t
i
o
n

5
A
i
r

d
i
s
c
h
a
r
g
e


6
A
i
r

s
u
c
t
i
o
n
N
u
m
b
e
r
D
e
s
c
r
i
p
i
t
i
o
n
U
n
i
t

s
i
z
e
(
7
k
,
9
k
,
1
2
k
,
1
8
k
)
:

6
.
3
5
(
1
/
4
)
U
n
i
t

s
i
z
e
(
2
4
k
)
:

9
.
5
2
(
3
/
8
)
U
n
i
t

s
i
z
e
(
7
k
,
9
k
,
1
2
k
,
1
8
k
)
:

1
2
.
7
(
1
/
2
)
U
n
i
t

s
i
z
e
(
2
4
k
)
:

1
5
.
8
8
(
5
/
8
)
6
5
4
13
2
[
U
n
i
t

:

m
m
(
i
n
c
h
)
]
B
3
/
B
4
W
i
t
h

S
u
c
t
i
o
n

G
r
i
l
l
e
&

S
u
c
t
i
o
n

C
a
n
v
a
s

W
i
t
h

S
u
c
t
i
o
n

G
r
i
l
l
e

- 67 -
Copyright2010LGElectronics.Inc.Allrightreserved.
Onlyfortrainingandservicepurposes
LGEInternalUseOnly
1. Funtions ......................................................................................68
2. Operation Details........................................................................69
3. Dimensions .................................................................................72
Ceiling Concealed Duct Type (High Static)
- 68 -
Copyright2010LGElectronics.Inc.Allrightreserved.
Onlyfortrainingandservicepurposes
LGEInternalUseOnly
Funtion
1. Funtions
Indoor Unit
Operation ON/OFF by Remote controller
Sensing the Room Temperature
Room temperature control
Starting Current Control
Indoor Fan Speed Control
Soft Dry Operation Mode
Deice (defrost) control (Heating)
Auto Restart
Hot-start Control (Heating)
Theindoorfandoesnotrotateuntiltheevaporatorpiping
temperaturereaches25C(76F)
High head height Drain pump
Astandarddrain-headheightofupto700mm(27-9/16inch)
ispossible.
Central Control(Optional)
Itisoperatingindividuallyortotallybycentralcontrolfunction.
Roomtemperaturesensor.(Thermistor)
MaintainstheroomtemperatureinaccordancewiththeSettingTemperature.
Indoorfanisdelayedfor5secondsatthestarting.
High,Med,Low
Intermittentoperationoffanatlowspeed.
Althoughtheair-conditioneristurnedoffbyapowerfailure,itisrestartedauto-
maticallypreviousoperationmodeafterpowersupply.
Boththeindoorandoutdoorfanstopsduringdefrosting.
Hotstartafterdefrostends.
- 69 -
Copyright2010LGElectronics.Inc.Allrightreserved.
Onlyfortrainingandservicepurposes
LGEInternalUseOnly
Operation Details
2. Operation Details
n Soft-Dry Operation
Theindoorfanspeedisautomaticallysettothelow,sotheshiftoftheindoorfanspeedisimpossiblebecauseof
alreadybeingsettothebestspeedforDryOperationbymicrocontrollercontrol.
n Cooling Mode Operation
WhenselectingtheCooling()ModeOperation,theunitwilloperateaccordingtothesettingbytheremotecontroller
andtheoperationdiagramisasfollowing.
(1) The function of main control
IntakeAirTemperature
Thermo.ON
(SETTEMPERATURE
+0.5C(33F))
Thermo.OFF
(SETTEMPERATURE
Morethan Morethan
-0.5C(33F))
3minutes 3minutes
Selecting Selecting Selecting
fanspeed fanspeed fanspeed
COMPRESSOR ON OFF ON OFF ON
INDOORFAN LowLow
- 70 -
Copyright2010LGElectronics.Inc.Allrightreserved.
Onlyfortrainingandservicepurposes
LGEInternalUseOnly
Operation Details
n Heating Mode Operation
Theunitwilloperateaccordingtothesettingbytheremotecontrollerandtheoperationdiagramisshownasfollowing.
Thermal
Outdoor fan
Indoor fan
4way valve
Setting Temperature
(Thermal ON)
Setting Temperature
+3C(37F)
(Thermal OFF)
Indoor unit
Heat-Exchanger
temperature
T
LT
T
ST
1min
Minimum
3min
1min
3min
Setting
fan
spped
Setting
fan
spped
Setting
fan
spped
40C(104F)
T
On
T
Off
ON
ON
ON
ON
Low Low Low Low Low Off Off Off
ON
OFF
OFF
Low fan during 10sec
A
A
B
C
B
Intake Air Temperature
Compressor-off interval : - While the indoor Heat-Exchanger temperature is higher than 40C(104F), fan operates
at low speed, when it becomes lower than 40C(104F) fan stops.
- For eluminating latent heat-loss, fan operates at low speed for 10 seconds periodically.
- To be operated "Low" except initial Hotstart operation
C
Chassis
HotstartOn T
On
HotstartOff T
Off
Lowtemperature T
LT
SettingTemperature T
ST
HighStatic LowStatic Convertible
BH BG BR
19C(66F) 19C(66F) 19C(66F) 19C(66F) 19C(66F) 19C(66F) 19C(66F) 26C(78F) 26C(78F)
22C(72F) 22C(72F) 22C(72F) 22C(72F) 22C(72F) 22C(72F) 22C(72F) 27C(80F) 27C(80F)
25C(76F) 25C(76F) 25C(76F) 25C(76F) 25C(76F) 25C(76F) 25C(76F) 28C(82F) 28C(82F)
27C(80F) 27C(80F) 27C(80F) 27C(80F) 27C(80F) 27C(80F) 27C(80F) 30C(86F) 30C(86F)
B1 B2 CE CF VE VJ
- 71 -
Copyright2010LGElectronics.Inc.Allrightreserved.
Onlyfortrainingandservicepurposes
LGEInternalUseOnly
Operation Details
n Hot-Start Control
TheindoorfandoesnotrotateuntiltheindoorunitHex-Exchangertemperaturereaches30C(86F).
Theoperationdiagramisasfollowing.
ON
ON
Off Off Low Low
1 min
Hotstart On
Hotstart Off
Indoor unit
Heat-Exchanger
temperature
Setting fan
speed
Setting fan
speed
Thermal
Outdoor fan
Indoor fan
4way Valve ON
1 min
InitialHotstartOnstate
PowerOff On
OperationOff On
Coolingoperation Heatingoperation
Defrostoperation
- 72 -
Copyright2010LGElectronics.Inc.Allrightreserved.
Onlyfortrainingandservicepurposes
LGEInternalUseOnly
Dimensions
3. Dimensions
7
6
,

S
e
o
n
g
s
a
n
-
d
o
n
g
,

C
h
a
n
g
w
o
n

C
i
t
y
,

G
y
e
o
n
g
n
a
m
,
L
G

E
l
e
c
t
r
o
n
i
c
s

U
S
A
,

H
V
A
C

D
i
v
i
s
i
o
n
1
0
0
0

S
y
l
v
a
n

A
v
e
n
u
e
,

E
n
g
l
e
w
o
o
d

C
l
i
f
f
s
,

N
J

0
7
6
3
2
w
w
w
.
l
g
u
s
a
.
c
o
m

/

w
w
w
.
l
g
h
v
a
c
.
c
o
m
6
4
1
-
7
1
3
,

K
o
r
e
a
w
w
w
.
l
g
e
a
i
r
c
o
n
.
c
o
m
C
H
A
S
S
I
S

C
O
D
E
:

B
H
C
e
i
l
i
n
g

C
o
n
c
e
a
l
e
d

D
u
c
t

(
H
i
g
h

S
t
a
t
i
c
)
A
R
N
U
0
7
3
B
H
A
2
A
R
N
U
0
9
3
B
H
A
2
A
R
N
U
1
2
3
B
H
A
2
A
R
N
U
1
5
3
B
H
A
2
A
R
N
U
1
8
3
B
H
A
2
A
R
N
U
2
4
3
B
H
A
2
N
o
t
e
1
.

U
n
i
t

s
h
o
u
l
d

b
e

i
n
s
t
a
l
l
e
d

i
n

c
o
m
p
l
i
a
n
c
e

w
i
t
h

t
h
e

i
n
s
t
a
l
l
a
t
i
o
n

m
a
n
u
a
l





i
n

t
h
e

p
r
o
d
u
c
t

b
o
x
.
2
.

U
n
i
t

s
h
a
l
l

b
e

g
r
o
u
n
d
e
d

i
n

a
c
c
o
r
d
a
n
c
e

w
i
t
h

t
h
e

l
o
c
a
l

r
e
g
u
l
a
t
i
o
n
s

o
r





a
p
p
l
i
c
a
b
l
e

n
a
t
i
o
n
a
l

c
o
d
e
s
.
N
a
m
e

1

L
i
q
u
i
d

p
i
p
e

c
o
n
n
e
c
t
i
o
n

2

G
a
s

p
i
p
e

c
o
n
n
e
c
t
i
o
n


3

D
r
a
i
n

p
i
p
e

c
o
n
n
e
c
t
i
o
n


4

P
o
w
e
r

s
u
p
p
l
y

c
o
n
n
e
c
t
i
o
n


5

A
i
r

d
i
s
c
h
a
r
g
e


6

A
i
r

s
u
c
t
i
o
n
N
u
m
b
e
r
D
e
s
c
r
i
p
i
t
i
o
n
[
U
n
i
t

:

m
m
(
i
n
c
h
)
]
U
n
i
t

s
i
z
e
(
7
k
,
9
k
,
1
2
k
,
1
8
k
)
:

6
.
3
5
(
1
/
4
)
U
n
i
t

s
i
z
e
(
2
4
k
)
:

9
.
5
2
(
3
/
8
)
U
n
i
t

s
i
z
e
(
7
k
,
9
k
,
1
2
k
,
1
8
k
)
:

1
2
.
7
(
1
/
2
)
U
n
i
t

s
i
z
e
(
2
4
k
)
:

1
5
.
8
8
(
5
/
8
)
4 8 ( 1 - 7 / 8 )
5 2 ( 2 - 1 / 1 6 )
1 6 5 ( 6 - 7 / 1 3 )
1 2 3 ( 4 - 1 3 / 1 6 )
1 4 0 ( 5 - 9 / 1 6 )
1
0
1
(
3
-
1
5
/
1
6
)
3
1
(
1
-
3
/
1
3
)
5
1
(
2
-
1
/
1
6
)
2
9
(
1
-
1
/
8
)
7
0
(
2
-
3
/
4
)
1 0 0 ( 3 - 1 5 / 1 6 )
2
6
0
(
1
0
-
1
/
4
)
8
7
(
3
-
7
/
1
6
)
7
5
0
(
2
9
-
1
/
2
)
3
0
(
1
-
3
/
1
6
)
4
7
(
1
-
7
/
8
)
4 5 0 ( 1 7 - 1 1 / 1 6 )
5 0 ( 1 - 1 5 / 1 6 )
3 5 5 ( 1 4 )
9
3
2
(
3
6
-
1
1
/
1
6
)
1 3 3 ( 5 - 1 / 4 )
3 5 5 ( 1 4 )
4 5 0 ( 1 7 - 1 1 / 1 6 )
4 5 0 ( 1 7 - 1 1 / 1 6 )
2 6 0 ( 1 0 - 1 / 4 )
1 5 8 ( 6 - 1 / 4 )
7 5 ( 2 - 1 5 / 1 6 )
4
7
(
1
-
7
/
8
) 4
9
(
1
5
/
1
6
)
2
4
(
1
5
/
1
6
)
2
1
(
7
/
8
)
8
8
2
(
3
4
-
3
/
4
)
6
5
(
2
-
9
/
1
6
)
1
0
8
(
4
-
3
/
1
3
)
6
4
(
2
-
1
/
2
)
2
4
3
(
9
-
9
/
1
6
)
2
1
2
(
8
-
3
/
8
)
2
4
3
(
9
-
9
/
1
6
)
1
1
9
(
4
-
1
1
/
1
6
)
1 0 6
( 4 - 1 / 8 )
1 2 7 ( 5 )
1
1
5
(
4
-
1
/
2
)
7
4
5
(
2
9
-
3
/
8
)
2 0 ( 3 / 4 )1 7 5 ( 6 - 7 / 8 )
3
2
5
1
4
6
1
1
4
(
4
-
1
/
2
)
2 2 4 ( 8 - 7 / 8 )
6
0
( 2
- 3
/ 8
)
R
3
7
.5
8
8
2
(
3
4
-
3
/
4
)
- 73 -
Copyright2010LGElectronics.Inc.Allrightreserved.
Onlyfortrainingandservicepurposes
LGEInternalUseOnly
Dimensions
7
6
,

S
e
o
n
g
s
a
n
-
d
o
n
g
,

C
h
a
n
g
w
o
n

C
i
t
y
,

G
y
e
o
n
g
n
a
m
,
6
4
1
-
7
1
3
,

K
o
r
e
a
w
w
w
.
l
g
e
a
i
r
c
o
n
.
c
o
m
C
H
A
S
S
I
S

C
O
D
E
:

B
G
C
e
i
l
i
n
g

C
o
n
c
e
a
l
e
d

D
u
c
t

(
H
i
g
h

S
t
a
t
i
c
)
A
R
N
U
2
8
3
B
G
A
2

A
R
N
U
3
6
3
B
G
A
2
A
R
N
U
4
2
3
B
G
A
2
N
o
t
e
1
.

U
n
i
t

s
h
o
u
l
d

b
e

i
n
s
t
a
l
l
e
d

i
n

c
o
m
p
l
i
a
n
c
e

w
i
t
h

t
h
e

i
n
s
t
a
l
l
a
t
i
o
n

m
a
n
u
a
l





i
n

t
h
e

p
r
o
d
u
c
t

b
o
x
.
2
.

U
n
i
t

s
h
a
l
l

b
e

g
r
o
u
n
d
e
d

i
n

a
c
c
o
r
d
a
n
c
e

w
i
t
h

t
h
e

l
o
c
a
l

r
e
g
u
l
a
t
i
o
n
s

o
r





a
p
p
l
i
c
a
b
l
e

n
a
t
i
o
n
a
l

c
o
d
e
s
.
2
6
1
(
1
0
-
1
/
4
)
3
2
(
1
-
3
/
1
3
)
5
1
(
2
-
1
/
1
6
)
1
0
2
(
4
)
8
3
0
(
3
2
-
1
1
/
1
6
)
2
9
(
1
-
3
/
8
)
7
5
(
2
-
1
5
/
1
6
)
8 7 ( 3 - 7 / 1 6 )
1
,
2
3
0
(
4
8
-
7
/
1
6
)
1
,
1
8
2
(
4
6
-
1
/
2
)
2
3
(
1
5
/
1
6
)
4
9
(
1
5
/
1
6
)
1
,
1
8
2
(
4
6
-
5
/
8
)
1 5 8 ( 6 - 1 / 4 )1 1 3 ( 4 - 7 / 1 6 )
2 9 8 ( 1 1 - 1 1 / 1 6 )
1 8 6 ( 7 - 5 / 1 6 )
2
3
2
(
1
-
1
/
4
)
2
4
3
(
9
-
9
/
1
6
)
2
4
3
(
9
-
9
/
1
6
)
2
3
2
(
1
-
1
/
4
)
2
3
2
(
1
-
1
/
4
)
1 6 5 ( 6 - 7 / 1 3 )
5 3 ( 2 - 1 / 1 6 ) 4 7 ( 1 - 7 / 8 )
1 4 0 ( 5 - 9 / 1 6 )
1 2 2 ( 4 - 1 3 / 1 6 )
1 0 0 ( 3 - 1 5 / 1 6 )
8
7
(
3
-
7
/
1
6
)
4 5 0 ( 1 7 - 1 1 / 1 6 )
4 5 0 ( 1 7 - 1 1 / 1 6 )
5 0 ( 1 - 1 5 / 1 6 )
3 5 5 ( 1 4 )
1
0
8
(
4
-
3
/
1
3
)
L
G

E
l
e
c
t
r
o
n
i
c
s

U
S
A
,

H
V
A
C

D
i
v
i
s
i
o
n
1
0
0
0

S
y
l
v
a
n

A
v
e
n
u
e
,

E
n
g
l
e
w
o
o
d

C
l
i
f
f
s
,

N
J

0
7
6
3
2
w
w
w
.
l
g
u
s
a
.
c
o
m

/

w
w
w
.
l
g
h
v
a
c
.
c
o
m
1
1
5
(
4
-
1
/
2
)
1
,
0
4
3
(
4
1
)
2 0 ( 3 / 4 )
2 2 0 ( 8 - 5 / 8 )
N
a
m
e

1

L
i
q
u
i
d

p
i
p
e

c
o
n
n
e
c
t
i
o
n

U
n
i
t

s
i
z
e
(
2
8
k
,
3
6
k
,
4
2
k
)
:

9
.
5
2
(
3
/
8
)

2

G
a
s

p
i
p
e

c
o
n
n
e
c
t
i
o
n

U
n
i
t

s
i
z
e
(
2
8
k
,
3
6
k
,
4
2
k
)
:

1
5
.
8
8
(
5
/
8
)


3

D
r
a
i
n

p
i
p
e

c
o
n
n
e
c
t
i
o
n


4

P
o
w
e
r

s
u
p
p
l
y

c
o
n
n
e
c
t
i
o
n


5

A
i
r

d
i
s
c
h
a
r
g
e


6

A
i
r

s
u
c
t
i
o
n

N
u
m
b
e
r
D
e
s
c
r
i
p
i
t
i
o
n
[
U
n
i
t

:

m
m
(
i
n
c
h
)
]
3
2
5
1
4
6
1
5
2
(
5
-
7
/
8
)
2 2 4 ( 8 - 7 / 8 )
6
0
( 2
- 3
/ 8
)

1
0
0
- 74 -
Copyright2010LGElectronics.Inc.Allrightreserved.
Onlyfortrainingandservicepurposes
LGEInternalUseOnly
Dimensions
7
6
,

S
e
o
n
g
s
a
n
-
d
o
n
g
,

C
h
a
n
g
w
o
n

C
i
t
y
,

G
y
e
o
n
g
n
a
m
,
6
4
1
-
7
1
3
,

K
o
r
e
a
w
w
w
.
l
g
e
a
i
r
c
o
n
.
c
o
m
C
H
A
S
S
I
S

C
O
D
E
:

B
R
C
e
i
l
i
n
g

C
o
n
c
e
a
l
e
d

D
u
c
t

(
H
i
g
h

S
t
a
t
i
c
)
A
R
N
U
4
8
3
B
R
A
2
N
o
t
e
1
.

U
n
i
t

s
h
o
u
l
d

b
e

i
n
s
t
a
l
l
e
d

i
n

c
o
m
p
l
i
a
n
c
e

w
i
t
h

t
h
e

i
n
s
t
a
l
l
a
t
i
o
n

m
a
n
u
a
l





i
n

t
h
e

p
r
o
d
u
c
t

b
o
x
.
2
.

U
n
i
t

s
h
a
l
l

b
e

g
r
o
u
n
d
e
d

i
n

a
c
c
o
r
d
a
n
c
e

w
i
t
h

t
h
e

l
o
c
a
l

r
e
g
u
l
a
t
i
o
n
s

o
r





a
p
p
l
i
c
a
b
l
e

n
a
t
i
o
n
a
l

c
o
d
e
s
.
N
a
m
e

1

L
i
q
u
i
d

p
i
p
e

c
o
n
n
e
c
t
i
o
n

U
n
i
t

s
i
z
e
(
4
8
k
)
:

9
.
5
2
(
3
/
8
)

2

G
a
s

p
i
p
e

c
o
n
n
e
c
t
i
o
n

U
n
i
t

s
i
z
e
(
4
8
k
)
:

1
5
.
8
8
(
5
/
8
)


3

D
r
a
i
n

p
i
p
e

c
o
n
n
e
c
t
i
o
n


4

P
o
w
e
r

s
u
p
p
l
y

c
o
n
n
e
c
t
i
o
n


5

A
i
r

d
i
s
c
h
a
r
g
e


6

A
i
r

s
u
c
t
i
o
n

N
u
m
b
e
r
D
e
s
c
r
i
p
i
t
i
o
n
[
U
n
i
t

:

m
m
(
i
n
c
h
)
]
2 2 1 ( 8 - 3 / 4 )
1 2 3 ( 4 - 1 3 / 1 6 )
7 2 ( 2 - 1 3 / 1 6 )
2
6
(
1
)
8
3
(
3
-
1
/
4
)
1
0
1
(
3
-
1
5
/
1
6
)
9 0 ( 3 - 9 / 1 6 )
1
3
5
(
5
-
5
/1
6
)
1 2 2 ( 4 - 1 3 / 1 6 )
1 4 4 ( 5 - 1 1 / 1 6 )
2
6
0
(
1
0
-
1
/
4
)
1
9
0
(
7
-
7
/
1
6
)
1
1
5
(
4
-
9
/
1
6
)
1
,
2
8
4
(
5
0
-
9
/
1
6
)
1
,
2
3
0
(
4
8
-
7
/
1
6
)
4 7 7 ( 1 8 - 3 / 4 )5 6 ( 2 - 3 / 1 6 )
5 9 0 ( 2 3 - 3 / 1 6 )
5 9 0 ( 2 3 - 3 / 1 6 )
1
1
8
(
4
-
5
/
8
)
1
,
0
0
4
(
3
9
-
9
/
1
6
)
1
1
4
(
4
-
7
/
1
6
)
1
,
2
3
0
(
4
8
-
7
/
1
6
)
5
0
(
1
-
1
5
/
1
6
)
3 2 ( 1 - 3 / 1 3 )
1 6 8 ( 6 - 5 / 8 )
1 8 5 ( 7 - 1 / 4 )
2
4
1
(
9
-
1
/
2
)
2
4
1
(
9
-
1
/
2
)
2
7
9
(
1
1
)
2
7
9
(
1
1
)
3 8 0 ( 1 5 )
1 4 0 ( 5 - 9 / 1 6 )
2
1
5
(
8
-
1
/
2
)
L
G

E
l
e
c
t
r
o
n
i
c
s

U
S
A
,

H
V
A
C

D
i
v
i
s
i
o
n
1
0
0
0

S
y
l
v
a
n

A
v
e
n
u
e
,

E
n
g
l
e
w
o
o
d

C
l
i
f
f
s
,

N
J

0
7
6
3
2
w
w
w
.
l
g
u
s
a
.
c
o
m

/

w
w
w
.
l
g
h
v
a
c
.
c
o
m
1
2
0
(
4
-
3
/
4
)
1
,
0
9
2
(
4
3
)
2 5 ( 1 )
3 0 3 ( 1 2 )
3
2
1
5
6
4
1
9
8
(
7
-
3
/
4
)
3 1 2 ( 1 2 - 1 / 4 )
6
0
( 2
- 3
/ 8
)
R
6
0
- 75 -
Copyright2010LGElectronics.Inc.Allrightreserved.
Onlyfortrainingandservicepurposes
LGEInternalUseOnly
Dimensions
7
6
,

S
e
o
n
g
s
a
n
-
d
o
n
g
,

C
h
a
n
g
w
o
n

C
i
t
y
,

G
y
e
o
n
g
n
a
m
,
6
4
1
-
7
1
3
,

K
o
r
e
a
w
w
w
.
l
g
e
a
i
r
c
o
n
.
c
o
m
C
H
A
S
S
I
S

C
O
D
E
:

B
8
C
e
i
l
i
n
g

C
o
n
c
e
a
l
e
d

D
u
c
t

(
H
i
g
h

S
t
a
t
i
c
)
U
R
N
U
7
6
3
B
8
A
2
U
R
N
U
9
6
3
B
8
A
2
N
o
t
e
1
.

U
n
i
t

s
h
o
u
l
d

b
e

i
n
s
t
a
l
l
e
d

i
n

c
o
m
p
l
i
a
n
c
e

w
i
t
h

t
h
e

i
n
s
t
a
l
l
a
t
i
o
n

m
a
n
u
a
l





i
n

t
h
e

p
r
o
d
u
c
t

b
o
x
.
2
.

U
n
i
t

s
h
a
l
l

b
e

g
r
o
u
n
d
e
d

i
n

a
c
c
o
r
d
a
n
c
e

w
i
t
h

t
h
e

l
o
c
a
l

r
e
g
u
l
a
t
i
o
n
s

o
r





a
p
p
l
i
c
a
b
l
e

n
a
t
i
o
n
a
l

c
o
d
e
s
.

1

L
i
q
u
i
d

p
i
p
e

c
o
n
n
e
c
t
i
o
n

2

G
a
s

p
i
p
e

c
o
n
n
e
c
t
i
o
n


3

D
r
a
i
n

p
i
p
e

c
o
n
n
e
c
t
i
o
n


4

P
o
w
e
r

s
u
p
p
l
y

c
o
n
n
e
c
t
i
o
n


5

A
i
r

d
i
s
c
h
a
r
g
e


6

A
i
r

s
u
c
t
i
o
n
D
e
s
c
r
i
p
i
t
i
o
n
[
U
n
i
t

:

m
m
(
i
n
c
h
)
]
U
n
i
t

s
i
z
e
(
7
6
k
,
9
6
k
)
:

9
.
5
2
(
3
/
8
)
U
n
i
t

s
i
z
e
(
7
6
k
)
:

1
9
.
0
5
(
3
/
4
)
U
n
i
t

s
i
z
e
(
9
6
k
)
:

2
2
.
2
(
7
/
8
)
1
,
5
6
2
(
6
1
-
7
/
1
3
)
1
,
6
2
2
(
6
3
-
1
1
/
1
3
)
6 8 8 ( 2 7 )
6 8 8 ( 2 7 )
5 6 0 ( 2 2 )6 4 ( 2 - 7 / 1 3 )
3 0 ( 1 - 3 / 1 6 )

1
,
2
2
0
(
4
8
)
3
2
9
(
1
2
-
1
5
/
1
6
)
3
2
0
(
1
2
-
5
/
8
)
3
2
9
(
1
2
-
1
5
/
1
6
)
3 1 8 ( 1 2 - 7 / 1 3 )
2
9
3
(
1
1
-
7
/
1
3
)
4 6 0 ( 1 8 - 1 / 1 3 )
4
6
0
(
1
8
-
1
/
1
3
)
2 9 0 ( 1 1 - 7 / 1 6 )1 6 1
( 6 - 3 / 8 )
7
0
(
2
-
3
/
4
)
1
2
0
(
4
-
3
/
4
)
9
9
(
3
-
7
/
8
)
1
4
0
(
5
-
9
/
1
6
)
4 4 0 ( 1 7 - 3 / 8 ) 2 0 ( 3 / 4 )
1
,
3
9
6
(
5
4
-
1
5
/
1
6
)
1
1
5
(
4
-
9
/
1
6
)
L
G

E
l
e
c
t
r
o
n
i
c
s

U
S
A
,

H
V
A
C

D
i
v
i
s
i
o
n
1
0
0
0

S
y
l
v
a
n

A
v
e
n
u
e
,

E
n
g
l
e
w
o
o
d

C
l
i
f
f
s
,

N
J

0
7
6
3
2
w
w
w
.
l
g
u
s
a
.
c
o
m

/

w
w
w
.
l
g
h
v
a
c
.
c
o
m
3
2
1
4
6
5
1
,
5
6
2
(
6
1
-
1
/
2
)
6 4 ( 2 - 1 / 2 )
7 0 ( 2 - 3 / 4 )
6 0 ( 2 - 3 / 8 )
1 2 2 ( 4 - 7 / 8 )
3
5
8
(
1
4
)
1
0
9
(4
-1
/4
)
6
8
(2
-5
/8
)
1
8
(3
/4
)
5
8
(2
-1
/4
)
N
a
m
e
N
u
m
b
e
r
- 76 -
Copyright2010LGElectronics.Inc.Allrightreserved.
Onlyfortrainingandservicepurposes
LGEInternalUseOnly
1. Functions ....................................................................................77
2. Operation Details........................................................................78
3. Dimensions .................................................................................85
Wall Mountedd Type
- 77 -
Copyright2010LGElectronics.Inc.Allrightreserved.
Onlyfortrainingandservicepurposes
LGEInternalUseOnly
Functions
1. Functions
Roomtemperaturesensor.(THERMISTOR)
MaintainstheroomtemperatureinaccordancewiththeSettingtemperature
Indoorfanisdelayedfor5secatthestarting.
High,Med,Low,CHAOS
Intermittentoperationoffanatlowspeed.
Thefanisswitchedtolow(Cooling),med(Heating)speed.
Theunitwillbestoppedafter1,2,3,4,5,6,7hours.
Thefanisswitchedtointermittentorirregularoperation
Thefanspeedisautomaticallyswitchedfromhightolowspeed.
Thelouvercanbesetatthedesiredpositionorswing
upanddownautomatically.
Indoor Unit
Operation ON/OFF by Remote controller
Sensing the Room Temperature
Room temperature control
Starting Current Control
Indoor Fan Speed Control
Operation indication Lamps (LED)
SignalReceptor
Receivesthesignalsfromtheremotecontrol.(Signalreceivingsound:twoshortbeepsoronelongbeep.)
OperationIndicationLamps
On/Off :Lightsupduringthesystemoperation.
SleepMode :LightsupduringSleepModeAutooperation.
Timer :LightsupduringTimeroperation.
DefrostMode :LightsupduringDefrostModeorHotStartoperation.
Temperature :Indicatethesettingtemperature.
Soft Dry Operation Mode
Boththeindoorandoutdoorfanstopsdur-
ingdefrosting.
Theindoorfandoesnotrotateuntilthe
evaporatorpipetemperaturewillbereached
at28C(82F).
Sleep Mode Auto Control
Natural Air Control by CHAOS Logic
Airflow Direction Control
Defrost(Deice) control (Heating)
Hot-start Control (Heating)
- 78 -
Copyright2010LGElectronics.Inc.Allrightreserved.
Onlyfortrainingandservicepurposes
LGEInternalUseOnly
Operation Details
2. Operation Details
DISPLAY
(1) High quality LCD remote controller supplied
Operation Indicator
Onwhileinapplianceoperation,offwhileinappliancepause
Timer(on/off) and Sleep timer Indicator
Onwhileintimermode(on/off)andinsleeptimermode,offwhentimermodeiscompletedorcanceled
Defrost Indicator
Offexceptwhenhotstartduringheatingmodeoperationorwhileindefrostcontrol.
Plasma Indicator
Onwhileinplasmamode,offwhileplasmamodeiscanceled.
Auto restart
Incasethepowercomesonagainafterapowerfailure,AutoRestartingOperationisthefunctiontooperate
proceduresautomaticallytothepreviousoperatingconditions.
Ifyourwanttousethisoperation,presstheAutoRestartButton.
Power(Forced Operation)
Operationstarts,whenthisbuttonispressedandstopswhenyoupressthebuttonagain.
n Cooling Mode Operation
Whentheintakeairtemperaturereaches0.5C(33F)belowthesettingtemp,thecompressorandtheoutdoor
fanstop.
Whenitreaches0.5C(33F) abovethesettingtemp,theystarttooperateagain.
CompressorONTemp=>SettingTemp+0.5C(33F)
CompressorOFFTemp=>SettingTemp-0.5C(33F)
While in compressor running, operating with the airflow speed set by the remote controller. While in com-
pressornotrunning,operatingwiththelowairflowspeedregardlessofthesetting.
Function of Controls
- 79 -
Copyright2010LGElectronics.Inc.Allrightreserved.
Onlyfortrainingandservicepurposes
LGEInternalUseOnly
Operation Details
n Healthy Dehumidification Mode
Whenthedehumidificationoperationinputbytheremotecontrollerisreceived,theintakeairtemperatureis
detectedandthesettingtempisautomaticallysetaccordingtotheintakeairtemperature.
26C(78F)IntakeAirTemp=>25C(76F)
24C(76F)IntakeAirTemp<26C(78F)=>IntakeAirTemp-1C(34F)
18C(64F)IntakeAirTemp<24C(76F)=>IntakeAirTemp-0.5C(33F)
IntakeAirTemp<18C(64F)=>18C(64F)
Whileincompressoroff,theindoorfanrepeatslowairflowspeedandpause.
Whiletheintakeairtempisbetweencompressorontemp.andcompressorofftemp.,10-mindehumidification
operationand4-mincompressoroffrepeat
CompressorONTemp.=>SettingTemp+0.5C(33F)
CompressorOFFTemp.=>SettingTemp-0.5C(33F)
In10-mindehumidificationoperation,theindoorfanoperateswiththelowairflowspeed.
n Heating Mode Operation
Whentheintakeairtempreaches+3Cabovethesettingtemp,thecompressoristurnedoff.Whenbelowthe
settingtemp,thecompressoristurnedon.
ThermoONTemp.=>SettingTemp.+2C(36F)
ThermoOFFTemp.=>SettingTemp.+4C(39F)
Whileincompressoron,whenabove38C(100F),itoperateswithorsettingairflowspeed(whileinsleep
mode,withthemediumairflowspeed).
Whileincompressoroff,theindoorfanisoffwhentheindoorpipetempisbelow33C(92F),whenabove
35C(94F),itoperateswiththelowairflowspeed.
Whileindefrostcontrol,bothoftheindoorandoutdoorfansareturnedoff.
n Defrost Control
Whileinheatingmodeoperationinordertoprotectoutdoorunitfromfreezing,reversedtocoolingcycleto
defrosttheoutdoorunit.
n Fuzzy Operation (Outdoor unit C/O Model)
AccordingtothetemperaturesetbyFuzzyrule,whentheintakeairtempis0.5C(33F) ormorebelowtheset-
tingtemp,thecompressoristurnedoff.When0.5C(33F)ormoreabovethesettingtemp,thecompressoris
turnedon.
CompressorONTemp=>SettingTemp+0.5C(33F)
CompressorOFFTemp=>SettingTemp+0.5C(33F)
AtthebeginningofFuzzymodeoperation,thesettingtemperatureisautomaticallyselectedaccordingtothe
intakeairtempatthattime.
- 80 -
Copyright2010LGElectronics.Inc.Allrightreserved.
Onlyfortrainingandservicepurposes
LGEInternalUseOnly
Operation Details
26C(78F)IntakeAirTemp=>25C(76F)
24C(76F)IntakeAirTemp<26C(78F)=>IntakeAirTemp+1C(34F)
22C(72F)IntakeAirTemp<24C(76F)=>IntakeAirTemp+0.5C(33F)
18C(64F)IntakeAirTemp<22C(72F)=>IntakeAirTemp
IntakeAirTemp<18C(64F)=>18C(64F)
When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, the
Fuzzy key value and the intake air temperature at that time are compared to select the setting temperature
automaticallyaccordingtotheFuzzyrule.
WhileinFuzzyoperation,theairflowspeedoftheindoorfanisautomaticallyselectedaccordingtothetemper-
ature
n Fuzzy Operation (Outdoor unit H/P Model)
Whenanyofoperationmodeisnotselectedlikethemomentofthepoweronorwhen3hrshaspassedsince
theoperationoff,theoperationmodeisselected.
Whendeterminingtheoperationmode,thecompressor,theoutdoorfan,andthe4wayvalveareoffandonly
the indoor fan is operated for 15 seconds. Then an operation mode is selected according to the intake air
tempatthatmomentasfollows.
24C(76F)InatakeAirTemp=>FuzzyOperationforCooling
21C(70F)InatakeAirTemp<24C(76F)=>FuzzyOperationforDehumidification
InatakeAirTemp<21C(70F)=>FuzzyOperationforHeating
Ifanyoftheoperationmodesamongcooling/dehumidification/heatingmodeoperationsiscarriedoutfor10
secorlongerbeforeFuzzyoperation,themodebeforeFuzzyoperationisoperated.
1) Fuzzy Operation for Cooling
AccordingtothesettingtemperatureselectedbyFuzzyrule,whentheintakeairtempis0.5C(33F) ormore
belowthesettingtemp,thecompressoristurnedoff.When0.5C(33F) ormoreabovethesettingtemp,the
compressoristurnedon.
CompressorONTemp=>SettingTemp+0.5C(33F)
CompressorOFFTemp=>SettingTemp+0.5C(33F)
AtthebeginningofFuzzymodeoperation,thesettingtemperatureisautomaticallyselectedaccordingtothe
intakeairtempatthattime.
26C(78F)IntakeAirTemp=>25C(76F)
24C(76F)IntakeAirTemp<26C(78F)=>IntakeAirTemp+1C(34F)
22C(72F)IntakeAirTemp<24C(76F)=>IntakeAirTemp+0.5C(33F)
18C(64F)IntakeAirTemp<22C(72F)=>IntakeAirTemp
IntakeAirTemp<18C(64F)=>18C(64F)
When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, the
Fuzzy key value and the intake air temperature at that time are compared to select the setting temperature
automaticallyaccordingtotheFuzzyrule.
WhileinFuzzyoperation,theairflowspeedoftheindoorfanisautomaticallyselectedaccordingtothetemperature.
2) Fuzzy Operation for Dehumidification
AccordingtothesettingtemperatureselectedbyFuzzyrule,whentheintakeairtempis0.5C(33F) ormore
belowthesettingtemp,thecompressoristurnedoff.When0.5C(33F) ormoreabovethesettingtemp,the
compressoristurnedon.
CompressorONTemp=>SettingTemp+0.5C(33F)
CompressorOFFTemp=>SettingTemp+0.5C(33F)
- 81 -
Copyright2010LGElectronics.Inc.Allrightreserved.
Onlyfortrainingandservicepurposes
LGEInternalUseOnly
Operation Details
AtthebeginningofFuzzymodeoperation,thesettingtemperatureisautomaticallyselectedaccordingtothe
intakeairtempatthattime.
26C(78F)IntakeAirTemp=>25C(76F)
24C(76F)IntakeAirTemp<26C(78F)=>IntakeAirTemp+1C(34F)
22C(72F)IntakeAirTemp<24C(76F)=>IntakeAirTemp+0.5C(33F)
18C(64F)IntakeAirTemp<22C(72F)=>IntakeAirTemp
IntakeAirTemp<18C(64F)=>18C(64F)
When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, the
Fuzzy key value and the intake air temperature at that time are compared to select the setting temperature
automaticallyaccordingtotheFuzzyrule.
While in Fuzzy operation, the airflow speed of the indoor fan repeats the low airflow speed or pause as in
dehumidificationoperation.
3) Fuzzy Operation for Heating
According to the setting temperature selected by Fuzzy rule, when the intake air temp is 3C(37F) or more
abovethesettingtemp,thecompressoristurnedoff.Whenbelowthesettingtemp,thecompressoristurned
on.
CompressorONTemp=>SettingTemp.+2C(36F)
CompressorOFFTemp=>SettingTemp.+4C(39F)
AtthebeginningofFuzzymodeoperation,thesettingtemperatureisautomaticallyselectedaccordingtothe
intakeairtempatthattime.
20C(68F)IntakeAirTemp=>IntakeAirTemp+0.5C(33F)
IntakeAirTemp<20C(68F)=>20C(68F)
When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, the
Fuzzy key value and the intake air temperature at that time are compared to select the setting temperature
automaticallyaccordingtotheFuzzyrule.
WhileinFuzzyoperation,theairflowspeedoftheindoorfanissettothehighorthemediumaccordingtothe
intakeairtemperatureandthesettingtemperature.
n Airflow Speed Selection
The airflow speed of the indoor fan is set to high, medium, low, or chaos by the input of the airflow speed
selectionkeyontheremotecontroller.
n On-Timer Operation
Whenthesettimeisreachedafterthetimeisinputbytheremotecontroller,theappliancestartstooperate.
ThetimerLEDisonwhentheon-timerisinput.Itisoffwhenthetimesetbythetimerisreached.
Iftheapplianceisoperatingatthetimesetbythetimer,theoperationcontinues.
n Off-Timer Operation
Whenthesettimeisreachedafterthetimeisinputbytheremotecontroller,theappliancestopsoperating.
ThetimerLEDisonwhentheoff-timerisinput.Itisoffwhenthetimesetbythetimerisreached.
Iftheapplianceisonpauseatthetimesetbythetimer,thepausecontinues.
- 82 -
Copyright2010LGElectronics.Inc.Allrightreserved.
Onlyfortrainingandservicepurposes
LGEInternalUseOnly
Operation Details
n Off-Timer <=> On-Timer Operation
Whenthesettimeisreachedaftertheon/offtimeisinputbytheremotecontroller,theon/off-timeroperationis
carriedoutaccordingtothesettime.
n Sleep Timer Operation
When the sleep time is reached after <1,2,3,4,5,6,7,0(cancel) hr> is input by the remote controller while in
applianceoperation,theoperationoftheappliancestops.
Whiletheapplianceisonpause,thesleeptimermodecannotbeinput.
While in cooling mode operation, 30 min later since the start of the sleep timer, the setting temperature
increasesby1C(34F)Afteranother30minelapse,itincreasesby1C(34F)again.
Whenthesleeptimermodeisinputwhileincoolingcyclemode,theairflowspeedoftheindoorfanissetto
thelow.
Whenthesleeptimermodeisinputwhileinheatingcyclemode,theairflowspeedoftheindoorfanissetto
themedium.
n Chaos Swing Mode
BytheChaosSwingkeyinput,thevaneautomaticallyoperateswiththeChaosSwingortheyarefixedtothe
desireddirection.
n Chaos Natural Wind Mode
WhentheChaosNaturalWindmodeisselectedandthenoperated,thehigh,medium,orlowspeedoftheair-
flowmodeisoperatedfor2~15secrandomlybytheChaosSimulation.
n Jet Cool Mode Operation (Outdoor unit C/O Model)
IftheJetCoolkeyisinputatanyoperationmodewhileinapplianceoperation,theJetCoolmodeoperates.
IntheJetCoolmode,theindoorfanisoperatedatsuper-highspeedfor30minatcoolingmodeoperation.
IntheJetCoolmodeoperation,theroomtemperatureiscontrolledtothesettingtemperature,18C(64F)
WhenthesleeptimermodeisinputwhileintheJetCoolmodeoperation,theJetCoolmodehasthepriority.
DuringtheJETCOOLfunctionatanymoment,theA/Cstartstoblowthecoolairwithsidelouversclosedat
extremelyhighspeedfor30minutessettingtheroomtemp.automaticallyto18C.
n Jet Cool Mode Operation (Outdoor unit H/P Model)
WhileinheatingmodeorFuzzyoperation,theJetCoolkeycannotbeinput.Whenitisinputwhileintheother
modeoperation(cooling,dehumidification,ventilation),theJetCoolmodeisoperated.
IntheJetCoolmode,theindoorfanisoperatedatsuper-highspeedfor30minatcoolingmodeoperation.
IntheJetCoolmodeoperation,theroomtemperatureiscontrolledtothesettingtemperature,18C(64F)
WhenthesleeptimermodeisinputwhileintheJetCoolmodeoperation,theJetCoolmodehasthepriority.
DuringtheJETHEATfunctionatanymoment,theA/Cstartstoblowthehotairwithsidelouversclosedat
extremelyhighspeedfor60minutessettingtheroomtemp.automaticallyto30C(86F).
n Auto Restarting Operation
When the power is restored after a sudden power failure while in appliance operation, the mode before the
powerfailureiskeptonthememoryandtheapplianceautomaticallyoperatesinthemodeonthememory.
OperationModethatiskeptonthememory
-StateofOperationON/OFF
- 83 -
Copyright2010LGElectronics.Inc.Allrightreserved.
Onlyfortrainingandservicepurposes
LGEInternalUseOnly
Operation Details
-OperationMode/SettingTemp/SelectedAirflowSpeed
-SleepTimerMode/RemainingTimeofSleepTimer(unitofhour)
n Forced Operation
Operationprocedureswhentheremotecontrolcan'tbeused.
Theoperationwillbestartedifthepowerbuttonispressed.
Ifyouwanttostopoperation,re-pressthebutton.
Whileinforcedoperation,thekeyinputbytheremotecontrolhasnoeffectandthebuzzersounds10timesto
indicatetheforcedoperation.
n Test operation
DuringtheTESTOPERATION,theunitoperatesincoolingmodeathighspeedfan,regardlessofroomtem-
peratureandresetsin181minutes.
Duringtestoperation,ifremotecontrollersignalisreceived,theunitoperatesasremotecontrollersets.
Ifyouwanttousethisoperation,PressandholdON/OFFbutton3~5seconds,thenthebuzzersound1"beep".
Ifyouwanttostoptheoperation,re-pressthebutton.
n Protection of the evaporator pipe from frosting
Iftheindoorpipetempisbelow0C(32F)in7min.afterthecompressoroperateswithoutanypausewhilein
coolingcycleoperationmode,thecompressorandtheoutdoorfanareturnedoffinordertoprotecttheindoor
evaporatorpipefromfrosting.
Whentheindoorpipetempis7C(45F)orhigherafter3min.pauseofthecompressor,thecompressorand
theoutdoorfanisturnedonaccordingtotheconditionoftheroomtemperature.
n Buzzer Sounding Operation
Whentheappliance-operationkeyisinputbytheremotecontrol,theshort"beep-beep-"sounds.
Whentheappliance-pausekeyisinputbytheremotecontrol,thelong"beep"sounds.
When a key is input by the remote control while the slide switch on the main unit of the appliance is on the
forcedoperationposition,theerrorsound"beep-beep-beep-beep-beep-"ismade10timestoindicatethatthe
remotecontrolsignalcannotbereceived.
Heat pump Model
Cooling Model
Room Temp. 24C(76F) 21C(70F) Room Temp. < 24C(76F) Room Temp. < 21C(70F)
Operatingmode Cooling Cooling HealthyDehumidification Heating
IndoorFanSpeed High High High High
SettingTemperature 22C(72F) 22CC(72F) 23C(74F) 24C(76F)
- 84 -
Copyright2010LGElectronics.Inc.Allrightreserved.
Onlyfortrainingandservicepurposes
LGEInternalUseOnly
Operation Details
n Air Cleaner Operation
WhenanaircleanerfunctionisselectedduringAirConditioneroperation
-Plasmaaircleanerfunctionwillbeoperatedwhileinanyoperationmodewithselectingthefunction.
-Thefunctionistobestoppedwhileitisoperatingwithselectingthefunction.
Whenanaircleanerfunctionisselectedduringoperationoff
-Thefunctionwillbeonlyoperated.
Wheninletgrilleofairconditionerisopenedduringplasmaoperation,HighVoltageGenerator(H.V.B)istobe
stopped.Wheninletgrilleofairconditionerisclosedduringplasmaoperation,HighVoltageGenerator(H.V.B)
willbeoperatedagain.
- 85 -
Copyright2010LGElectronics.Inc.Allrightreserved.
Onlyfortrainingandservicepurposes
LGEInternalUseOnly
Dimensions
3. Dimensions
L
o
w
e
r

t
h
a
n

2
.
3
m

M
o
r
e

t
h
a
n

2
0
0

m
m
H
i
g
h
e
r

t
h
a
n

e
y
e
-
l
e
v
e
l
M
o
r
e

t
h
a
n

1
0
0

m
m
M
o
r
e

t
h
a
n

1
0
0

m
m
7
6
,

S
e
o
n
g
s
a
n
-
d
o
n
g
,

C
h
a
n
g
w
o
n

C
i
t
y
,

G
y
e
o
n
g
n
a
m
,
6
4
1
-
7
1
3
,

K
o
r
e
a
C
H
A
S
S
I
S

C
O
D
E
:

S
E
P
I
P
E

A
N
D

D
R
A
I
N

D
I
M
E
N
S
I
O
N
P
I
P
I
N
G
/
W
I
R
I
N
G
D
I
R
E
C
T
I
O
N
P
I
P
I
N
G
/
W
I
R
I
N
G

D
I
R
E
C
T
I
O
N
W
a
l
l

M
o
u
n
t
e
d
A
R
N
U
0
7
G
S
E
*
2
A
R
N
U
0
9
G
S
E
*
2
A
R
N
U
1
2
G
S
E
*
2
A
R
N
U
1
5
G
S
E
*
2
W
M
o
d
e
l
A
R
N
U
0
7
G
S
E
*
2
A
R
N
U
0
9
G
S
E
*
2
A
R
N
U
1
2
G
S
E
*
2
A
R
N
U
1
5
G
S
E
*
2
H
D
8
9
5

2
8
2
1
6
5
N
o
t
e
1
.

U
n
i
t

s
h
o
u
l
d

b
e

i
n
s
t
a
l
l
e
d

i
n

c
o
m
p
l
i
a
n
c
e

w
i
t
h

t
h
e

i
n
s
t
a
l
l
a
t
i
o
n

m
a
n
u
a
l





i
n

t
h
e

p
r
o
d
u
c
t

b
o
x
.
2
.

U
n
i
t

s
h
a
l
l

b
e

g
r
o
u
n
d
e
d

i
n

a
c
c
o
r
d
a
n
c
e

w
i
t
h

t
h
e

l
o
c
a
l

r
e
g
u
l
a
t
i
o
n
s

o
r





a
p
p
l
i
c
a
b
l
e

n
a
t
i
o
n
a
l

c
o
d
e
s
.
(
u
n
i
t

:

m
m
)
5
6
7
2 6 5
N
a
m
e
12345678
F
r
o
n
t

p
a
n
e
l
A
i
r

d
i
s
c
h
a
r
g
e
A
i
r

s
u
c
t
i
o
n
L
i
q
u
i
d

p
i
p
e
G
a
s

p
i
p
e
D
r
a
i
n

p
i
p
e
R
i
g
h
t

s
i
d
e

p
i
p
i
n
g
/
w
i
r
i
n
g

c
o
n
n
e
c
t
i
o
n
L
e
f
t

s
i
d
e

p
i
p
i
n
g
/
w
i
r
i
n
g

c
o
n
n
e
c
t
i
o
n

6
.
3
5

F
l
a
r
e

c
o
n
n
e
c
t
i
o
n

1
2
.
7

F
l
a
r
e

c
o
n
n
e
c
t
i
o
n
E
x
t
e
r
n
a
l

d
i
a
.

1
7
N
u
m
b
e
r


R
e
q
u
i
r
e
d

s
p
a
c
e
(
u
n
i
t
:
m
m
)
D
e
s
c
r
i
p
i
t
i
o
n
(
u
n
i
t

:

m
m
)
P
I
P
I
N
G

D
I
R
E
C
T
I
O
N
- 86 -
Copyright2010LGElectronics.Inc.Allrightreserved.
Onlyfortrainingandservicepurposes
LGEInternalUseOnly
Dimensions
7
6
,

S
e
o
n
g
s
a
n
-
d
o
n
g
,

C
h
a
n
g
w
o
n

C
i
t
y
,

G
y
e
o
n
g
n
a
m
,
6
4
1
-
7
1
3
,

K
o
r
e
a
C
H
A
S
S
I
S

C
O
D
E
:

S
5
W
a
l
l

M
o
u
n
t
e
d
A
R
N
U
1
8
G
S
5
*
2
A
R
N
U
2
4
G
S
5
*
2
W
M
o
d
e
l
A
R
N
U
1
8
G
S
5
*
2
A
R
N
U
2
4
G
S
5
*
2
H
D
1
0
9
0

3
0
0
1
7
8
N
o
t
e
1
.

U
n
i
t

s
h
o
u
l
d

b
e

i
n
s
t
a
l
l
e
d

i
n

c
o
m
p
l
i
a
n
c
e

w
i
t
h

t
h
e

i
n
s
t
a
l
l
a
t
i
o
n

m
a
n
u
a
l





i
n

t
h
e

p
r
o
d
u
c
t

b
o
x
.
2
.

U
n
i
t

s
h
a
l
l

b
e

g
r
o
u
n
d
e
d

i
n

a
c
c
o
r
d
a
n
c
e

w
i
t
h

t
h
e

l
o
c
a
l

r
e
g
u
l
a
t
i
o
n
s

o
r





a
p
p
l
i
c
a
b
l
e

n
a
t
i
o
n
a
l

c
o
d
e
s
.
(
u
n
i
t

:

m
m
)
2 8 1
8
0
4
F
r
o
n
t

p
a
n
e
l
A
i
r

d
i
s
c
h
a
r
g
e
A
i
r

s
u
c
t
i
o
n
L
i
q
u
i
d

p
i
p
e
G
a
s

p
i
p
e
D
r
a
i
n

p
i
p
e
R
i
g
h
t

s
i
d
e

p
i
p
i
n
g
/
w
i
r
i
n
g

c
o
n
n
e
c
t
i
o
n
L
e
f
t

s
i
d
e

p
i
p
i
n
g
/
w
i
r
i
n
g

c
o
n
n
e
c
t
i
o
n

6
.
3
5

F
l
a
r
e

c
o
n
n
e
c
t
i
o
n

1
2
.
7

F
l
a
r
e

c
o
n
n
e
c
t
i
o
n
E
x
t
e
r
n
a
l

d
i
a
.

1
7
P
I
P
E

A
N
D

D
R
A
I
N

D
I
M
E
N
S
I
O
N
P
I
P
I
N
G
/
W
I
R
I
N
G
D
I
R
E
C
T
I
O
N
P
I
P
I
N
G
/
W
I
R
I
N
G

D
I
R
E
C
T
I
O
N
P
I
P
I
N
G

D
I
R
E
C
T
I
O
N
L
o
w
e
r

t
h
a
n

2
.
3
m

M
o
r
e

t
h
a
n

2
0
0

m
m
H
i
g
h
e
r

t
h
a
n

e
y
e
-
l
e
v
e
l
M
o
r
e

t
h
a
n

1
0
0

m
m
M
o
r
e

t
h
a
n

1
0
0

m
m
N
a
m
e
12345678
N
u
m
b
e
r


R
e
q
u
i
r
e
d

s
p
a
c
e
(
u
n
i
t
:
m
m
)
D
e
s
c
r
i
p
i
t
i
o
n
(
u
n
i
t

:

m
m
)
- 87 -
Copyright2010LGElectronics.Inc.Allrightreserved.
Onlyfortrainingandservicepurposes
LGEInternalUseOnly
1. Funtions ......................................................................................88
2. Operation Details........................................................................89
3. Dimensions .................................................................................92
Ceiling & Floor
Ceiling Suspended
- 88 -
Copyright2010LGElectronics.Inc.Allrightreserved.
Onlyfortrainingandservicepurposes
LGEInternalUseOnly
1. Function
Indoor Unit
Operation ON/OFF by Remote controller
Sensing the Room Temperature
Room temperature control
Starting Current Control
Indoor Fan Speed Control
Soft Dry Operation Mode
Deice (defrost) control (Heating)
Auto Restart
Hot-start Control (Heating)
Theindoorfandoesnotrotateuntiltheevaporatorpiping
temperaturereaches25C(76F).
High head height Drain pump
Astandarddrain-headheightofupto700mm(27-9/16inch)
ispossible.
Central Control(Optional)
Itisoperatingindividuallyortotallybycentralcontrolfunction.
Roomtemperaturesensor.(Thermistor)
MaintainstheroomtemperatureinaccordancewiththeSettingTemperature.
Indoorfanisdelayedfor5secondsatthestarting.
High,Med,Low
Intermittentoperationoffanatlowspeed.
Althoughtheair-conditioneristurnedoffbyapowerfailure,itisrestartedauto-
maticallypreviousoperationmodeafterpowersupply.
Boththeindoorandoutdoorfanstopsduringdefrosting.
Hotstartafterdefrostends.
Function
- 89 -
Copyright2010LGElectronics.Inc.Allrightreserved.
Onlyfortrainingandservicepurposes
LGEInternalUseOnly
2. Operation Details
Operation Details
n Soft-Dry Operation
Theindoorfanspeedisautomaticallysettothelow,sotheshiftoftheindoorfanspeedisimpossiblebecauseof
alreadybeingsettothebestspeedforDryOperationbymicrocontrollercontrol.
n Cooling Mode Operation
WhenselectingtheCooling()ModeOperation,theunitwilloperateaccordingtothesettingbytheremotecontroller
andtheoperationdiagramisasfollowing.
(1) The function of main control
Thermal ON Thermal OFF
IndoorUnitmode ST+0.5 ST-0.5
2TH(Remo.+Indoor)
Tobeselectedhighertemperature Tobeselectedhighertemperature
contrastIndoorUnitandRemo. contrastIndoorUnitandRemo.
Remo.Mode ST+0.5 ST-0.5
IntakeAirTemperature
Thermo.ON
(SETTEMPERATURE
+0.5C(33F))
Thermo.OFF
(SETTEMPERATURE
Morethan Morethan
-0.5C(33F))
3minutes 3minutes
Selecting Selecting Selecting
fanspeed fanspeed fanspeed
COMPRESSOR ON OFF ON OFF ON
INDOORFAN LowLow
- 90 -
Copyright2010LGElectronics.Inc.Allrightreserved.
Onlyfortrainingandservicepurposes
LGEInternalUseOnly
Operation Details
n Heating Mode Operation
Theunitwilloperateaccordingtothesettingbytheremotecontrollerandtheoperationdiagramisshownasfollowing.
Thermal
Outdoor fan
Indoor fan
4way valve
Setting Temperature
(Thermal ON)
Setting Temperature
+3C(37F)
(Thermal OFF)
Indoor unit
Heat-Exchanger
temperature
T
LT
T
ST
1min
Minimum
3min
1min
3min
Setting
fan
spped
Setting
fan
spped
Setting
fan
spped
40C(104F)
T
On
T
Off
ON
ON
ON
ON
Low Low Low Low Low Off Off Off
ON
OFF
OFF
Low fan during 10sec
A
A
B
C
B
Intake Air Temperature
Compressor-off interval : - While the indoor Heat-Exchanger temperature is higher than 40C(104F), fan operates
at low speed, when it becomes lower than 40C(104F) fan stops.
- For eluminating latent heat-loss, fan operates at low speed for 10 seconds periodically.
- To be operated "Low" except initial Hotstart operation
C
Chassis
HotstartOn T
On
HotstartOff T
Off
Lowtemperature T
LT
SettingTemperature T
ST
HighStatic LowStatic Convertible
BH BG BR
19C(66F) 19C(66F) 19C(66F) 19C(66F) 19C(66F) 19C(66F) 19C(66F) 26C(78F) 26C(78F)
22C(72F) 22C(72F) 22C(72F) 22C(72F) 22C(72F) 22C(72F) 22C(72F) 27C(80F) 27C(80F)
25C(76F) 25C(76F) 25C(76F) 25C(76F) 25C(76F) 25C(76F) 25C(76F) 28C(82F) 28C(82F)
27C(80F) 27C(80F) 27C(80F) 27C(80F) 27C(80F) 27C(80F) 27C(80F) 30C(86F) 30C(86F)
B1 B2 CE CF VE VJ
- 91 -
Copyright2010LGElectronics.Inc.Allrightreserved.
Onlyfortrainingandservicepurposes
LGEInternalUseOnly
Operation Details
n Hot-Start Control
TheindoorfandoesnotrotateuntiltheindoorunitHex-Exchangertemperaturereaches30C(86F).
Theoperationdiagramisasfollowing.
ON
ON
Off Off Low Low
1 min
Hotstart On
Hotstart Off
Indoor unit
Heat-Exchanger
temperature
Setting fan
speed
Setting fan
speed
Thermal
Outdoor fan
Indoor fan
4way Valve ON
1 min
InitialHotstartOnstate
PowerOff On
OperationOff On
Coolingoperation Heatingoperation
Defrostoperation
- 92 -
Copyright2010LGElectronics.Inc.Allrightreserved.
Onlyfortrainingandservicepurposes
LGEInternalUseOnly
3. Dimensions
Dimensions
7
6
,

S
e
o
n
g
s
a
n
-
d
o
n
g
,

C
h
a
n
g
w
o
n

C
i
t
y
,

G
y
e
o
n
g
n
a
m
,
6
4
1
-
7
1
3
,

K
o
r
e
a
C
H
A
S
S
I
S

C
O
D
E
:

V
E
C
e
i
l
i
n
g

&

F
l
o
o
r
A
R
N
U
0
9
G
V
E
A
2
A
R
N
U
1
2
G
V
E
A
2
N
o
t
e
1
.

U
n
i
t

s
h
o
u
l
d

b
e

i
n
s
t
a
l
l
e
d

i
n

c
o
m
p
l
i
a
n
c
e

w
i
t
h

t
h
e

i
n
s
t
a
l
l
a
t
i
o
n

m
a
n
u
a
l





i
n

t
h
e

p
r
o
d
u
c
t

b
o
x
.
2
.

U
n
i
t

s
h
a
l
l

b
e

g
r
o
u
n
d
e
d

i
n

a
c
c
o
r
d
a
n
c
e

w
i
t
h

t
h
e

l
o
c
a
l

r
e
g
u
l
a
t
i
o
n
s

o
r





a
p
p
l
i
c
a
b
l
e

n
a
t
i
o
n
a
l

c
o
d
e
s
.
W
M
o
d
e
l
A
R
N
U
0
9
G
V
E
A
2
A
R
N
U
1
2
G
V
E
A
2
H
D
9
0
0
4
9
0
2
0
0
(
u
n
i
t

:

m
m
)
5
8
7
2 7 3


R
e
q
u
i
r
e
d

s
p
a
c
e
(
u
n
i
t
:
m
m
)
N
a
m
e
123456789
1
0
L
i
q
u
i
d

p
i
p
e
G
a
s

p
i
p
e
S
u
c
t
i
o
n

g
i
l
l
e
D
i
s
c
h
a
r
g
e

g
r
i
l
l
e
S
u
s
p
e
n
s
i
o
n

b
r
a
c
k
e
t
R
i
g
h
t

s
i
d
e

d
r
a
i
n

h
o
s
e

h
o
l
e
L
e
f
t

s
i
d
e

d
r
a
i
n

h
o
s
e

h
o
l
e
W
i
r
i
n
g

c
o
n
n
e
c
t
i
o
n
P
i
p
i
n
g

c
o
n
n
e
c
t
i
o
n
S
i
g
n
a
l

r
e
c
e
i
v
e
r

&

O
p
e
r
a
t
i
o
n

i
n
d
i
c
a
t
o
r

6
.
3
5

F
l
a
r
e

c
o
n
n
e
c
t
i
o
n

1
2
.
7

F
l
a
r
e

c
o
n
n
e
c
t
i
o
n
N
u
m
b
e
r
D
e
s
c
r
i
p
i
t
i
o
n
(
u
n
i
t

:

m
m
)
S
l
i
t

h
o
l
e
S
l
i
t

h
o
l
e
M
o
r
e

t
h
a
n

2
0
0
m
m
M
o
r
e

t
h
a
n

5
0
m
m
M
o
r
e

t
h
a
n

2
0
0
m
m
M
o
r
e

t
h
a
n

2
0
0
m
m
M
o
r
e

t
h
a
n

5
0
m
m
M
o
r
e

t
h
a
n

2
0
0
m
m
- 93 -
Copyright2010LGElectronics.Inc.Allrightreserved.
Onlyfortrainingandservicepurposes
LGEInternalUseOnly
Dimensions
7
6
,

S
e
o
n
g
s
a
n
-
d
o
n
g
,

C
h
a
n
g
w
o
n

C
i
t
y
,

G
y
e
o
n
g
n
a
m
,
6
4
1
-
7
1
3
,

K
o
r
e
a
C
H
A
S
S
I
S

C
O
D
E
:

V
J
C
e
i
l
i
n
g

S
u
s
p
e
n
d
e
d
A
R
N
U
1
8
G
V
J
A
2
A
R
N
U
2
4
G
V
J
A
2
N
o
t
e
1
.

U
n
i
t

s
h
o
u
l
d

b
e

i
n
s
t
a
l
l
e
d

i
n

c
o
m
p
l
i
a
n
c
e

w
i
t
h

t
h
e

i
n
s
t
a
l
l
a
t
i
o
n

m
a
n
u
a
l





i
n

t
h
e

p
r
o
d
u
c
t

b
o
x
.
2
.

U
n
i
t

s
h
a
l
l

b
e

g
r
o
u
n
d
e
d

i
n

a
c
c
o
r
d
a
n
c
e

w
i
t
h

t
h
e

l
o
c
a
l

r
e
g
u
l
a
t
i
o
n
s

o
r





a
p
p
l
i
c
a
b
l
e

n
a
t
i
o
n
a
l

c
o
d
e
s
.
W
M
o
d
e
l
A
R
N
U
1
8
G
V
J
A
2
A
R
N
U
2
4
G
V
J
A
2
H
D
9
5
0
6
5
0
2
2
0
(
u
n
i
t

:

m
m
)


R
e
q
u
i
r
e
d

s
p
a
c
e
(
u
n
i
t
:
m
m
)
N
a
m
e
123456789
1
0
1
1
L
i
q
u
i
d

p
i
p
e
G
a
s

p
i
p
e
S
u
c
t
i
o
n

g
i
l
l
e
D
i
s
c
h
a
r
g
e

g
r
i
l
l
e
S
u
s
p
e
n
s
i
o
n

b
r
a
c
k
e
t
R
i
g
h
t

s
i
d
e

d
r
a
i
n

h
o
s
e

h
o
l
e
L
e
f
t

s
i
d
e

d
r
a
i
n

h
o
s
e

h
o
l
e
W
i
r
i
n
g

c
o
n
n
e
c
t
i
o
n
P
i
p
i
n
g

c
o
n
n
e
c
t
i
o
n
R
i
g
h
t

s
i
d
e

d
r
a
i
n

p
i
p
e

c
o
n
n
e
c
t
i
o
n
L
e
f
t

s
i
d
e

d
r
a
i
n

p
i
p
e

c
o
n
n
e
c
t
i
o
n

6
.
3
5

F
l
a
r
e

c
o
n
n
e
c
t
i
o
n

1
2
.
7

F
l
a
r
e

c
o
n
n
e
c
t
i
o
n
N
u
m
b
e
r
D
e
s
c
r
i
p
i
t
i
o
n
(
u
n
i
t

:

m
m
)
S
l
i
t

h
o
l
e
S
l
i
t

h
o
l
e
S
l
i
t

h
o
l
e
S
l
i
t

h
o
l
e
M
o
r
e

t
h
a
n

7
0
0
m
m
M
o
r
e

t
h
a
n

3
0
0
m
m
M
o
r
e

t
h
a
n

7
0
0

m
- 94 -
Copyright2010LGElectronics.Inc.Allrightreserved.
Onlyfortrainingandservicepurposes
LGEInternalUseOnly
1. Function ......................................................................................95
2. Operation Details........................................................................96
3. Dimensions .................................................................................99
Floor Standing Type
- 95 -
Copyright2010LGElectronics.Inc.Allrightreserved.
Onlyfortrainingandservicepurposes
LGEInternalUseOnly
1. Function
Indoor Unit
Operation ON/OFF by Remote controller
Sensing the Room Temperature
Room temperature control
Starting Current Control
Indoor Fan Speed Control
Soft Dry Operation Mode
Deice (defrost) control (Heating)
Auto Restart
Hot-start Control (Heating)
Theindoorfandoesnotrotateuntiltheevaporatorpiping
temperaturereaches25C(76F).
High head height Drain pump
Astandarddrain-headheightofupto700mm(27-9/16inch)
ispossible.
Central Control(Optional)
Itisoperatingindividuallyortotallybycentralcontrolfunction.
Roomtemperaturesensor.(Thermistor)
MaintainstheroomtemperatureinaccordancewiththeSettingTemperature.
Indoorfanisdelayedfor5secondsatthestarting.
High,Med,Low
Intermittentoperationoffanatlowspeed.
Althoughtheair-conditioneristurnedoffbyapowerfailure,itisrestartedauto-
maticallypreviousoperationmodeafterpowersupply.
Boththeindoorandoutdoorfanstopsduringdefrosting.
Hotstartafterdefrostends.
Function
- 96 -
Copyright2010LGElectronics.Inc.Allrightreserved.
Onlyfortrainingandservicepurposes
LGEInternalUseOnly
Operation Details
2. Operation Details
n Soft-Dry Operation
Theindoorfanspeedisautomaticallysettothelow,sotheshiftoftheindoorfanspeedisimpossiblebecauseof
alreadybeingsettothebestspeedforDryOperationbymicrocontrollercontrol.
n Cooling Mode Operation
WhenselectingtheCooling()ModeOperation,theunitwilloperateaccordingtothesettingbytheremotecontroller
andtheoperationdiagramisasfollowing.
(1) The function of main control
Thermal ON Thermal OFF
IndoorUnitmode ST+0.5 ST-0.5
2TH(Remo.+Indoor)
Tobeselectedhighertemperature Tobeselectedhighertemperature
contrastIndoorUnitandRemo. contrastIndoorUnitandRemo.
Remo.Mode ST+0.5 ST-0.5
IntakeAirTemperature
Thermo.ON
(SETTEMPERATURE
+0.5C(33F))
Thermo.OFF
(SETTEMPERATURE
Morethan Morethan
-0.5C(33F))
3minutes 3minutes
Selecting Selecting Selecting
fanspeed fanspeed fanspeed
COMPRESSOR ON OFF ON OFF ON
INDOORFAN LowLow
- 97 -
Copyright2010LGElectronics.Inc.Allrightreserved.
Onlyfortrainingandservicepurposes
LGEInternalUseOnly
Operation Details
n Heating Mode Operation
Theunitwilloperateaccordingtothesettingbytheremotecontrollerandtheoperationdiagramisshownasfollowing.
Thermal
Outdoor fan
Indoor fan
4way valve
Setting Temperature
(Thermal ON)
Setting Temperature
+3C(37F)
(Thermal OFF)
Indoor unit
Heat-Exchanger
temperature
T
LT
T
ST
1min
Minimum
3min
1min
3min
Setting
fan
spped
Setting
fan
spped
Setting
fan
spped
40C(104F)
T
On
T
Off
ON
ON
ON
ON
Low Low Low Low Low Off Off Off
ON
OFF
OFF
Low fan during 10sec
A
A
B
C
B
Intake Air Temperature
Compressor-off interval : - While the indoor Heat-Exchanger temperature is higher than 40C(104F), fan operates
at low speed, when it becomes lower than 40C(104F) fan stops.
- For eluminating latent heat-loss, fan operates at low speed for 10 seconds periodically.
- To be operated "Low" except initial Hotstart operation
C
Chassis
HotstartOn T
On
HotstartOff T
Off
Lowtemperature T
LT
SettingTemperature T
ST
HighStatic LowStatic Convertible
BH BG BR
19C(66F) 19C(66F) 19C(66F) 19C(66F) 19C(66F) 19C(66F) 19C(66F) 26C(78F) 26C(78F)
22C(72F) 22C(72F) 22C(72F) 22C(72F) 22C(72F) 22C(72F) 22C(72F) 27C(80F) 27C(80F)
25C(76F) 25C(76F) 25C(76F) 25C(76F) 25C(76F) 25C(76F) 25C(76F) 28C(82F) 28C(82F)
27C(80F) 27C(80F) 27C(80F) 27C(80F) 27C(80F) 27C(80F) 27C(80F) 30C(86F) 30C(86F)
B1 B2 CE CF VE VJ
- 98 -
Copyright2010LGElectronics.Inc.Allrightreserved.
Onlyfortrainingandservicepurposes
LGEInternalUseOnly
Operation Details
n Hot-Start Control
TheindoorfandoesnotrotateuntiltheindoorunitHex-Exchangertemperaturereaches30C(86F).
Theoperationdiagramisasfollowing.
ON
ON
Off Off Low Low
1 min
Hotstart On
Hotstart Off
Indoor unit
Heat-Exchanger
temperature
Setting fan
speed
Setting fan
speed
Thermal
Outdoor fan
Indoor fan
4way Valve ON
1 min
InitialHotstartOnstate
PowerOff On
OperationOff On
Coolingoperation Heatingoperation
Defrostoperation
- 99 -
Copyright2010LGElectronics.Inc.Allrightreserved.
Onlyfortrainingandservicepurposes
LGEInternalUseOnly
Dimensions
3. Dimensions
7
6
,

S
e
o
n
g
s
a
n
-
d
o
n
g
,

C
h
a
n
g
w
o
n

C
i
t
y
,

G
y
e
o
n
g
n
a
m
,
6
4
1
-
7
1
3
,

K
o
r
e
a
w
w
w
.
l
g
e
a
i
r
c
o
n
.
c
o
m
C
H
A
S
S
I
S

C
O
D
E
:

C
E
F
l
o
o
r

S
t
a
n
d
i
n
g
A
R
N
U
0
7
3
C
E
A
2
A
R
N
U
0
9
3
C
E
A
2
A
R
N
U
1
2
3
C
E
A
2
A
R
N
U
1
5
3
C
E
A
2
A
R
N
U
0
7
3
C
E
U
2
A
R
N
U
0
9
3
C
E
U
2
A
R
N
U
1
2
3
C
E
U
2
A
R
N
U
1
5
3
C
E
U
2
N
o
t
e
1
.

U
n
i
t

s
h
o
u
l
d

b
e

i
n
s
t
a
l
l
e
d

i
n

c
o
m
p
l
i
a
n
c
e

w
i
t
h

t
h
e

i
n
s
t
a
l
l
a
t
i
o
n

m
a
n
u
a
l





i
n

t
h
e

p
r
o
d
u
c
t

b
o
x
.
2
.

U
n
i
t

s
h
a
l
l

b
e

g
r
o
u
n
d
e
d

i
n

a
c
c
o
r
d
a
n
c
e

w
i
t
h

t
h
e

l
o
c
a
l

r
e
g
u
l
a
t
i
o
n
s

o
r





a
p
p
l
i
c
a
b
l
e

n
a
t
i
o
n
a
l

c
o
d
e
s
.
<
W
i
t
h

C
a
s
e
>
<
W
i
t
h
o
u
t

C
a
s
e
>
1
0
6
7
(
4
2
)
1
0
6
7
(
4
2
)
1
4
8
.
3
(
5
-
1
3
/
1
6
)
1
4
8
.
3
(
5
-
1
3
/
1
6
)
4 9 ( 1 5 / 1 6 )
7 0 ( 2 - 3 / 4 )
6 3 5 ( 2 5 )
2
0
3
(
7
-
1
5
/
1
6
)
9
7
8
(
3
8
-
1
/
2
)
7
9
4
(
3
1
-
5
/
1
6
)
6 3 9 ( 3 1 - 1 / 4 )
1
3
(
1
/
2
)
2 0 . 4 ( 3 / 4 )
6 . 2 8
( 1 / 4 )
1
9
0
(
7
-
7
/
1
6
)
1
6
1
(
6
-
5
/
1
6
)
1
4
(
1
/
2
)
W
M
o
d
e
l
A
R
N
U
0
7
3
C
E
A
2
A
R
N
U
0
9
3
C
E
A
2
A
R
N
U
1
2
3
C
E
A
2
A
R
N
U
1
5
3
C
E
A
2
H
D
1
0
6
7
(
4
2
)
6
3
5
(
2
5
)
2
0
3
(
7
-
1
5
/
1
6
)
A
R
N
U
0
7
3
C
E
U
2
A
R
N
U
0
9
3
C
E
U
2
A
R
N
U
1
2
3
C
E
U
2
A
R
N
U
1
5
3
C
E
U
2
9
7
8
(
3
8
-
1
/
2
)
6
3
9
(
3
1
-
1
/
4
)
1
9
0
(
7
-
7
/
1
6
)
[
U
n
i
t

:

m
m
(
i
n
c
h
)
]
[
U
n
i
t

:

m
m
(
i
n
c
h
)
]
L
G

E
l
e
c
t
r
o
n
i
c
s

U
S
A
,

H
V
A
C

D
i
v
i
s
i
o
n
1
0
0
0

S
y
l
v
a
n

A
v
e
n
u
e
,

E
n
g
l
e
w
o
o
d

C
l
i
f
f
s
,

N
J

0
7
6
3
2
w
w
w
.
l
g
u
s
a
.
c
o
m

/

w
w
w
.
l
g
h
v
a
c
.
c
o
m
1
2
N
a
m
e



1
A
i
r

d
i
s
c
h
a
r
g
e

g
r
i
l
l




2
A
i
r

s
u
c
t
i
o
n

g
r
i
l
l

N
u
m
b
e
r
D
e
s
c
r
i
p
i
t
i
o
n
- 100 -
Copyright2010LGElectronics.Inc.Allrightreserved.
Onlyfortrainingandservicepurposes
LGEInternalUseOnly
Dimensions
7
6
,

S
e
o
n
g
s
a
n
-
d
o
n
g
,

C
h
a
n
g
w
o
n

C
i
t
y
,

G
y
e
o
n
g
n
a
m
,
6
4
1
-
7
1
3
,

K
o
r
e
a
w
w
w
.
l
g
e
a
i
r
c
o
n
.
c
o
m
C
H
A
S
S
I
S

C
O
D
E
:

C
F
F
l
o
o
r

S
t
a
n
d
i
n
g
A
R
N
U
1
8
3
C
F
A
2
A
R
N
U
2
4
3
C
F
A
2
A
R
N
U
1
8
3
C
F
U
2
A
R
N
U
2
4
3
C
F
U
2
N
o
t
e
1
.

U
n
i
t

s
h
o
u
l
d

b
e

i
n
s
t
a
l
l
e
d

i
n

c
o
m
p
l
i
a
n
c
e

w
i
t
h

t
h
e

i
n
s
t
a
l
l
a
t
i
o
n

m
a
n
u
a
l





i
n

t
h
e

p
r
o
d
u
c
t

b
o
x
.
2
.

U
n
i
t

s
h
a
l
l

b
e

g
r
o
u
n
d
e
d

i
n

a
c
c
o
r
d
a
n
c
e

w
i
t
h

t
h
e

l
o
c
a
l

r
e
g
u
l
a
t
i
o
n
s

o
r





a
p
p
l
i
c
a
b
l
e

n
a
t
i
o
n
a
l

c
o
d
e
s
.
1
2
<
W
i
t
h

C
a
s
e
>
<
W
i
t
h
o
u
t

C
a
s
e
>
2 0 3
( 7 - 1 5 / 1 6 )
1
3
4
5
(
5
2
-
1
5
/
1
6
)
6 3 5 ( 2 5 )
7 0 ( 2 - 3 / 4 )
1
4
8
.
3
(
5
-
1
3
/
1
6
)
1
0
4
8
.
4
(
4
1
-
1
/
4
)
4 9 . 5 ( 1 - 1 5 / 1 6 )
1
4
8
.
3
(
5
-
1
3
/
1
6
)
1
9
0
(
7
-
7
/
1
6
)
1
6
1
(
6
-
5
/
1
6
)
1
4
(
1
/
2
)
1
2
5
6
(
4
9
-
7
/
1
6
1
0
9
8
(
4
3
-
1
/
4
)
1
0
7
2
(
4
2
-
3
/
1
6
)
1
0
9
.
8
(
4
-
5
/
1
6
)
3
0
(
1
-
3
/
1
6
)
8 1 . 4 ( 3 - 3 / 1 6 )
1 4 5
( 5 - 1 1 / 1 6 )
7 0
( 2 - 3 / 4 )
2 1 . 4 ( 1 - 3 / 1 6 )
6 3 9 ( 3 1 - 1 / 4 )
W
M
o
d
e
l
A
R
N
U
1
8
3
C
F
A
2
A
R
N
U
2
4
3
C
F
A
2
H
D
1
3
4
5
(
5
2
-
1
5
/
1
6
)
6
3
5
(
2
5
)
2
0
3
(
7
-
1
5
/
1
6
)
A
R
N
U
1
8
3
C
F
U
2
A
R
N
U
2
4
3
C
F
U
2
1
2
5
6
(
4
9
-
7
/
1
6
)
6
3
9
(
3
1
-
1
/
4
)
1
9
0
(
7
-
7
/
1
6
)
[
U
n
i
t

:

m
m
(
i
n
c
h
)
]
2
0
3
(
7
-
1
5
/
1
6
)
L
G

E
l
e
c
t
r
o
n
i
c
s

U
S
A
,

H
V
A
C

D
i
v
i
s
i
o
n
1
0
0
0

S
y
l
v
a
n

A
v
e
n
u
e
,

E
n
g
l
e
w
o
o
d

C
l
i
f
f
s
,

N
J

0
7
6
3
2
w
w
w
.
l
g
u
s
a
.
c
o
m

/

w
w
w
.
l
g
h
v
a
c
.
c
o
m
N
a
m
e



1
A
i
r

d
i
s
c
h
a
r
g
e

g
r
i
l
l




2
A
i
r

s
u
c
t
i
o
n

g
r
i
l
l

N
u
m
b
e
r
D
e
s
c
r
i
p
i
t
i
o
n
(
u
n
i
t

:

m
m
)
- 101 -
Copyright2010LGElectronics.Inc.Allrightreserved.
Onlyfortrainingandservicepurposes
LGEInternalUseOnly
1. Funtions ....................................................................................102
2. Operation Details......................................................................103
3. Dimensions ...............................................................................107
Vertical Air Handling Unit
- 102 -
Copyright2010LGElectronics.Inc.Allrightreserved.
Onlyfortrainingandservicepurposes
LGEInternalUseOnly
Funtions
1. Funtions
Indoor Unit
Operation ON/OFF by Remote controller
Sensing the Room Temperature
Room temperature control
Starting Current Control
Indoor Fan Speed Control
Soft Dry Operation Mode
Deice (defrost) control (Heating)
Auto Restart
Hot-start Control (Heating)
Theindoorfandoesnotrotateuntiltheevaporatorpiping
temperaturereaches25C(76F)
Central Control(Optional)
Itisoperatingindividuallyortotallybycentralcontrolfunction.
Roomtemperaturesensor.(Thermistor)
MaintainstheroomtemperatureinaccordancewiththeSettingTemperature.
Indoorfanisdelayedfor5secondsatthestarting.
High,Med,Low
Intermittentoperationoffanatlowspeed.
Althoughtheair-conditioneristurnedoffbyapowerfailure,itisrestartedauto-
maticallypreviousoperationmodeafterpowersupply.
Boththeindoorandoutdoorfanstopsduringdefrosting.
Hotstartafterdefrostends.
If the electric heater has been installed, indoor fan continuous
willbe.
- 103 -
Copyright2010LGElectronics.Inc.Allrightreserved.
Onlyfortrainingandservicepurposes
LGEInternalUseOnly
Operation Details
2. Operation Details
n Soft-Dry Operation
Theindoorfanspeedisautomaticallysettothelow,sotheshiftoftheindoorfanspeedisimpossiblebecauseof
alreadybeingsettothebestspeedforDryOperationbymicrocontrollercontrol.
n Cooling Mode Operation
WhenselectingtheCooling()ModeOperation,theunitwilloperateaccordingtothesettingbytheremotecontroller
andtheoperationdiagramisasfollowing.
(1) The function of main control
IntakeAirTemperature
Thermo.ON
(SETTEMPERATURE
+0.5C(33F))
Thermo.OFF
(SETTEMPERATURE
Morethan Morethan
-0.5C(33F))
3minutes 3minutes
Selecting Selecting Selecting
fanspeed fanspeed fanspeed
COMPRESSOR ON OFF ON OFF ON
INDOORFAN LowLow
- 104 -
Copyright2010LGElectronics.Inc.Allrightreserved.
Onlyfortrainingandservicepurposes
LGEInternalUseOnly
Operation Details
n Heating Mode Operation
Theunitwilloperateaccordingtothesettingbytheremotecontrollerandtheoperationdiagramisshownasfollowing.
Thermal
Outdoor fan
Indoor fan
4way valve
Setting Temperature
(Thermal ON)
Setting Temperature
+3C(37F)
(Thermal OFF)
Indoor unit
Heat-Exchanger
temperature
T
LT
T
ST
1min
Minimum
3min
1min
3min
Setting
fan
spped
Setting
fan
spped
Setting
fan
spped
40C(104F)
T
On
T
Off
ON
ON
ON
ON
Low Low Low Low Low Off Off Off
ON
OFF
OFF
Low fan during 10sec
A
A
B
C
B
Intake Air Temperature
Compressor-off interval : - While the indoor Heat-Exchanger temperature is higher than 40C(104F), fan operates
at low speed, when it becomes lower than 40C(104F) fan stops.
- For eluminating latent heat-loss, fan operates at low speed for 10 seconds periodically.
- To be operated "Low" except initial Hotstart operation
C
Chassis
HotstartOn T
On
HotstartOff T
Off
Lowtemperature T
LT
SettingTemperature T
ST
VerticalAirHandlingUnit
NJ NK
19C(66F) 19C(66F)
22C(72F) 22C(72F)
25C(76F) 25C(76F)
27C(80F) 27C(80F)
- 105 -
Copyright2010LGElectronics.Inc.Allrightreserved.
Onlyfortrainingandservicepurposes
LGEInternalUseOnly
Operation Details
n Hot-Start Control
TheindoorfandoesnotrotateuntiltheindoorunitHex-Exchangertemperaturereaches22(71.6).
Theoperationdiagramisasfollowing.
ON
ON
Off Off Low Low
1 min
Hotstart On
Hotstart Off
Indoor unit
Heat-Exchanger
temperature
Setting fan
speed
Setting fan
speed
Thermal
Outdoor fan
Indoor fan
4way Valve ON
1 min
InitialHotstartOnstate
PowerOff On
OperationOff On
Coolingoperation Heatingoperation
Defrostoperation
Chassis
HotstartOn T
On
HotstartOff T
Off
Lowtemperature T
LT
SettingTemperature T
ST
HighStatic LowStatic Convertible
BH BG BR
19C(66F) 19C(66F) 19C(66F) 19C(66F) 19C(66F) 19C(66F) 19C(66F) 26C(78F) 26C(78F)
22C(72F) 22C(72F) 22C(72F) 22C(72F) 22C(72F) 22C(72F) 22C(72F) 27C(80F) 27C(80F)
25C(76F) 25C(76F) 25C(76F) 25C(76F) 25C(76F) 25C(76F) 25C(76F) 28C(82F) 28C(82F)
27C(80F) 27C(80F) 27C(80F) 27C(80F) 27C(80F) 27C(80F) 27C(80F) 30C(86F) 30C(86F)
B1 B2 CE CF VE VJ
- 106 -
Copyright2010LGElectronics.Inc.Allrightreserved.
Onlyfortrainingandservicepurposes
LGEInternalUseOnly
Operation Details
n Heater Operation
TheunitwilloperateaccordingtothesettingtemperatureandtheindoorunitHeat-Exchangertemperature.
Heateroperationdiagramisshownasfollowing.
Heater 2
Heater 1
45 (113)
30 (86)
42 (108)
28 (82)
Indoor unit
Heat-Exchanger
temperature
Setting temperature (A)
A-1 (34)
A-2 (36)
ON
ON
OFF
OFF
ON
ON
Heater ON Heater ON Heater OFF
- 107 -
Copyright2010LGElectronics.Inc.Allrightreserved.
Onlyfortrainingandservicepurposes
LGEInternalUseOnly
Dimensions
3. Dimensions
7
6
,

S
e
o
n
g
s
a
n
-
d
o
n
g
,

C
h
a
n
g
w
o
n

C
i
t
y
,

G
y
e
o
n
g
n
a
m
,
L
G

E
l
e
c
t
r
o
n
i
c
s

U
S
A
,

H
V
A
C

D
i
v
i
s
i
o
n
1
0
0
0

S
y
l
v
a
n

A
v
e
n
u
e
,

E
n
g
l
e
w
o
o
d

C
l
i
f
f
s
,

N
J

0
7
6
3
2
w
w
w
.
l
g
u
s
a
.
c
o
m

/

w
w
w
.
l
g
h
v
a
c
.
c
o
m
6
4
1
-
7
1
3
,

K
o
r
e
a
w
w
w
.
l
g
e
a
i
r
c
o
n
.
c
o
m
C
H
A
S
S
I
S

C
O
D
E
:

N
J
V
e
r
t
i
c
a
l

A
i
r

H
a
n
d
l
i
n
g

U
n
i
t
A
R
N
U
1
8
3
N
J
A
2
A
R
N
U
2
4
3
N
J
A
2
A
R
N
U
3
0
3
N
J
A
2
A
R
N
U
3
6
3
N
J
A
2
N
o
t
e
1
.

U
n
i
t

s
h
o
u
l
d

b
e

i
n
s
t
a
l
l
e
d

i
n

c
o
m
p
l
i
a
n
c
e

w
i
t
h

t
h
e

i
n
s
t
a
l
l
a
t
i
o
n

m
a
n
u
a
l





i
n

t
h
e

p
r
o
d
u
c
t

b
o
x
.
2
.

U
n
i
t

s
h
a
l
l

b
e

g
r
o
u
n
d
e
d

i
n

a
c
c
o
r
d
a
n
c
e

w
i
t
h

t
h
e

l
o
c
a
l

r
e
g
u
l
a
t
i
o
n
s

o
r





a
p
p
l
i
c
a
b
l
e

n
a
t
i
o
n
a
l

c
o
d
e
s
.
N
a
m
e

1

L
i
q
u
i
d

p
i
p
e

c
o
n
n
e
c
t
i
o
n

2

G
a
s

p
i
p
e

c
o
n
n
e
c
t
i
o
n


3

D
r
a
i
n

p
i
p
e

c
o
n
n
e
c
t
i
o
n


4

P
o
w
e
r

s
u
p
p
l
y

c
o
n
n
e
c
t
i
o
n


5

A
i
r

d
i
s
c
h
a
r
g
e


6

A
i
r

s
u
c
t
i
o
n
N
u
m
b
e
r
D
e
s
c
r
i
p
i
t
i
o
n
[
U
n
i
t

:

m
m
(
i
n
c
h
)
]
U
n
i
t

s
i
z
e
(
1
8
k
)
:

6
.
3
5
(
1
/
4
)
U
n
i
t

s
i
z
e
(
2
4
k
,
3
0
k
)
:

9
.
5
2
(
3
/
8
)
U
n
i
t

s
i
z
e
(
1
8
k
)
:

1
2
.
7
(
1
/
2
)
U
n
i
t

s
i
z
e
(
2
4
k
,
3
0
k
)
:

1
5
.
8
8
(
5
/
8
)
5

4
1
(
1
-
5
/
8
)
4
0
3 3 1 ( 1 3 )
4
0
(
1
-
9
/
1
6
)
3
6
4
(
1
4
-
5
/
1
6
)
1
2
3
6
(
4
8
-
5
/
8
)
6
5
(
2
-
9
/
1
6
)
1
1
7
.
5
(
4
-
5
/
8
)
2 5 4 ( 1 0 )
5
4
3
(
2
1
-
3
/
8
)
4 5 7 ( 1 8 )
4 3 2 ( 1 7 )
3
0
8
(
1
2
-
1
/
8
) 4
0
(
1
-
9
/
1
6
)
4
6
(
1
-
1
3
/
1
6
)
1
2
6
3
4
- 108 -
Copyright2010LGElectronics.Inc.Allrightreserved.
Onlyfortrainingandservicepurposes
LGEInternalUseOnly
Dimensions
7
6
,

S
e
o
n
g
s
a
n
-
d
o
n
g
,

C
h
a
n
g
w
o
n

C
i
t
y
,

G
y
e
o
n
g
n
a
m
,
6
4
1
-
7
1
3
,

K
o
r
e
a
w
w
w
.
l
g
e
a
i
r
c
o
n
.
c
o
m
C
H
A
S
S
I
S

C
O
D
E
:

N
K
V
e
r
t
i
c
a
l

A
i
r

H
a
n
d
l
i
n
g

U
n
i
t
A
R
N
U
4
2
3
N
K
A
2
A
R
N
U
4
8
3
N
K
A
2
A
R
N
U
5
4
3
N
K
A
2
N
o
t
e
1
.

U
n
i
t

s
h
o
u
l
d

b
e

i
n
s
t
a
l
l
e
d

i
n

c
o
m
p
l
i
a
n
c
e

w
i
t
h

t
h
e

i
n
s
t
a
l
l
a
t
i
o
n

m
a
n
u
a
l





i
n

t
h
e

p
r
o
d
u
c
t

b
o
x
.
2
.

U
n
i
t

s
h
a
l
l

b
e

g
r
o
u
n
d
e
d

i
n

a
c
c
o
r
d
a
n
c
e

w
i
t
h

t
h
e

l
o
c
a
l

r
e
g
u
l
a
t
i
o
n
s

o
r





a
p
p
l
i
c
a
b
l
e

n
a
t
i
o
n
a
l

c
o
d
e
s
.
L
G

E
l
e
c
t
r
o
n
i
c
s

U
S
A
,

H
V
A
C

D
i
v
i
s
i
o
n
1
0
0
0

S
y
l
v
a
n

A
v
e
n
u
e
,

E
n
g
l
e
w
o
o
d

C
l
i
f
f
s
,

N
J

0
7
6
3
2
w
w
w
.
l
g
u
s
a
.
c
o
m

/

w
w
w
.
l
g
h
v
a
c
.
c
o
m
6 3 5
( 2 5 )
3
0
8
(
1
2
-
1
/
8
)
4
0
(
1
-
9
/
1
6
)
4
1
(
1
-
5
/
8
)
4
0
(
1
-
9
/
1
6
)
4
0
(
1
-
9
/
1
6
)
1
1
8
(
4
-
5
/
8
)
3
6
2
(
1
4
-
1
/
4
)
3
9
(
1
-
9
/
1
6
)
6
5
(
2
-
9
/
1
6
)
1
4
0
0
(
5
5
-
1
/
8
)
1
4
1
8
(
5
5
-
1
3
/
1
6
)
5 0 8
( 2 0 )
4 3 0
( 1 6 - 1 5 / 1 6 )
4
9
(
1
-
1
5
/
1
6
)
5
4
0
(
2
1
-
1
/
4
)
5 5
( 2 - 3 / 1 6 )
5 2
( 2 - 1 / 1 6 )
6 1 0
( 2 4 )
N
a
m
e

1

L
i
q
u
i
d

p
i
p
e

c
o
n
n
e
c
t
i
o
n

U
n
i
t

s
i
z
e
(
2
8
k
,
3
6
k
,
4
2
k
)
:

9
.
5
2
(
3
/
8
)

2

G
a
s

p
i
p
e

c
o
n
n
e
c
t
i
o
n

U
n
i
t

s
i
z
e
(
2
8
k
,
3
6
k
,
4
2
k
)
:

1
5
.
8
8
(
5
/
8
)


3

D
r
a
i
n

p
i
p
e

c
o
n
n
e
c
t
i
o
n


4

P
o
w
e
r

s
u
p
p
l
y

c
o
n
n
e
c
t
i
o
n


5

A
i
r

d
i
s
c
h
a
r
g
e


6

A
i
r

s
u
c
t
i
o
n

N
u
m
b
e
r
D
e
s
c
r
i
p
i
t
i
o
n
[
U
n
i
t

:

m
m
(
i
n
c
h
)
]
4
5
2
3
6
1
- 109 -
Copyright2010LGElectronics.Inc.Allrightreserved.
Onlyfortrainingandservicepurposes
LGEInternalUseOnly
Part 3
Trouble shooting guide
- 110 -
Copyright2010LGElectronics.Inc.Allrightreserved.
Onlyfortrainingandservicepurposes
LGEInternalUseOnly
Self-diagnosis function ...................................................................111
Trouble shooting guide
- 111 -
Copyright2010LGElectronics.Inc.Allrightreserved.
Onlyfortrainingandservicepurposes
LGEInternalUseOnly
Self-diagnosis function
Self-diagnosis function
Self-Diagnosis Function
Error Indicator
Thisfunctionindicatestypesoffailureinself-diagnosisandoccurrenceoffailureforaircondition.
Errormarkisdisplayedondisplaywindowofindoorunitsandwiredremotecontroller,and7-segmentLEDof
outdoorunitcontrolboardasshowninthetable.
Ifmorethantwotroublesoccursimultaneously,lowernumberoferrorcodeisfirstdisplayed.
Aftererroroccurrence,iferrorisreleased,errorLEDisalsoreleasedsimultaneously.
Error Display
1st,2ndLEDof7-segmentindicateserrornumber,3rdLEDindicatesunitnumber.
Ex)211:No.21errorofmasterunit
213:No.21errorofslave2
011 051:No.105errorofmasterunit
Display Title Cause of Error
I
n
d
o
o
r

u
n
i
t

r
e
l
a
t
e
d

e
r
r
o
r
0 1 - Airtemperaturesensorofindoorunit Airtemperaturesensorofindoorunitisopenorshort
0 2 - Inletpipetemperaturesensorofindoorunit Inletpipetemperaturesensorofindoorunitisopenorshort
0 3 -
Transmissionerror:wiredremotecontroller
indoorunit
FailingtoreceivewiredremotecontrollersignalinindoorunitPCB
0 4 - Drainpump Malfunctionofdrainpump
0 5 - Transmissionerror:outdoorunit indoorunit FailingtoreceiveoutdoorunitsignalinindoorunitPCB
0 6 - Outletpipetemperaturesensorofindoorunit Outletpipetemperaturesensorofindoorunitisopenorshort
0 7 - Differentoperationmode Operationmodebetweenindoorunitandoutdoorunitisdifferent
0 9 - SerialNo.
IncasewhentheserialnumbermarkedonEEPROMofIndoorunitis0or
FFFFFF
1 0 - Poorfanmotoroperation
Disconnectingthefanmotorconnector/Failureofindoorfanmotorlock
Airtemperaturesensorofindoorunitisopenorshort
- 112 -
Copyright2010LGElectronics.Inc.Allrightreserved.
Onlyfortrainingandservicepurposes
LGEInternalUseOnly
Self-diagnosis function
**Incasethevalueismorethan100k(open)orlessthan100(short),Erroroccurs
Refer:Resistancevaluemaybechangeaccordingtotemperatureoftempsensor,
Itshowsaccordingtocriteriaofcurrenttemperature(5%margin) Normal
Airtempsensor:10C(50F)=20.7k:25C(76F)=10k:50C(122F)=3.4k
Pipetempsensor:10C(50F)=10k:25C(76F)=5k:50C(122F)=1.8k
n Error diagnosis and countermeasure flow chart
Is sensor properly
connected to PCB?
Is the resistance value
of sensor normal?*
Connect properly to PCB
Change the sensor
Change the PCB
Yes
Yes
No
No
Measure the resistance of outlet pipe temp sensor.
CN_PIPE/OUT: Pipe outlet temp sensor
CN_ROOM: Indoor air temp sensor
CN_PIPE/IN: Pipe inlet temp sensor
Error
No.
Error Type Error Point Main Reasons
01 Indoorunitairsensorerror
Indoorunitsensoris
open/short
1.IndoorunitPCBwrongconnection
2.IndoorunitPCBfailure
3.Sensorproblem(mainreason)
02 Indoorunitpipeinletsensorerror
06 Indoorunitpipeoutletsensorerror
<Standard Indoor Unit>
<Fresh Air Intake Unit>
- 113 -
Copyright2010LGElectronics.Inc.Allrightreserved.
Onlyfortrainingandservicepurposes
LGEInternalUseOnly
*Ifthereisnoremotecontrollertoreplace:Useanotherunitsremotecontrollerdoingwell
**Checkcable:Contactfailureofconnectedportionorextensionofcablearemaincause
Checkanysurroundednoise(checkthedistancewithmainpowercable)
makesafedistancefromthedevicesgenerateelectromagneticwave
***AfterreplacingindoorunitPCB,doAutoAddressing&inputunitsaddressifconnectedtocentralcontroller.
(AlltheindoorunitsconnectedshouldbeturnedonbeforeAutoAddressing
03 Notransmissionbetweencabled
remotecontroller&indoorunit
Error
No.
Error Type Error Point Main Reasons
Theremotecontroller
didnotreceivethesig-
nalfromindoorunit
duringspecifictime
1.Remotecontrollerfault
2.IndoorunitPCBfault
3.Connectorfault,Wrongconnection
4.transmissioncableproblem
n Error diagnosis and countermeasure flow chart
CN-REMO
: Remote controller connection
The PCB can differ from model to model.
Check from the right source.
Checking transmission cable connection status
Does the error happens
again if the remote
controller is replaced?*
Does the error occurred
when the cable of remote
controller is replaced?
Replace cabled remote
controller
Check connection &
transmission cable **
Replace indoor unit PCB ***
Yes
Yes
No
No
Self-diagnosis function
- 114 -
Copyright2010LGElectronics.Inc.Allrightreserved.
Onlyfortrainingandservicepurposes
LGEInternalUseOnly
1. Drain pump/float switch fault
04 Drain pump error
2. Improper drain pipe location, clog-
ging of drain pipe
3. Indoor unit PCB fault
Error
No.
Error Type Error Point Main Reasons
Error diagnosis and countermeasure flow chart
Float switch is open due to
rising of condensate water
level because of drain
pump fault or drain pipe
clogging
Is the drain pan filled
half with condensate
water? (half level of
float switch)*
Is drain pump working?
(Sound/drain noise/
contact etc.)
Replace float switch
Replace Indoor PCB or
reconnect the connector
Yes
Yes
No
No
Is Float switch short
On measuring its
resistance?
No
Yes
Drain pump blocked by
foreign particles?
Yes
In indoor unit PCB
Does the terminal voltage
for drain pump has
208/230V output?**
Replace indoor unit PCB
Replace Drain Pump
Yes
Remove it & clean the pump
No
* If the float goes up higher than a half of float
switch then the circuit is open & the unit is
stopped automatically.
Self-diagnosis function
- 115 -
Copyright2010LGElectronics.Inc.Allrightreserved.
Onlyfortrainingandservicepurposes
LGEInternalUseOnly
*** Indoor PCB drain pump connector
(Check input of 208/230V)
(Marked as CN-DPUMP)
float
A:Point to check rotating
Float switch Housing (CN-FLOAT)
Float switch connector
[***] Standard of drain pipe head height / slope
MAX 450
700mm(27-9/16inch)
Self-diagnosis function
- 116 -
Copyright2010LGElectronics.Inc.Allrightreserved.
Onlyfortrainingandservicepurposes
LGEInternalUseOnly
1.Autoaddressingisnotdone
2.transmissioncableisnotconnected
3.Shortcircuitoftransmissioncable
4.Indoorunittransmissioncircuitfault
05 5.Outdoorunittransmissioncircuitfault
6.Notenoughdistancebetweenpowerandtrans-
missioncable?
Error
No.
Error Type Error Point Main Reasons
Nosignaltransmission
betweenindoor&outdoor
units.
Indoor&Outdoorunit
transmissionerror
Does all the IDUs show
same error code CH05?
Is outdoor PCB LED
blinking?
Yes
Yes
No
Is main circuit breaker off?
No
Check the main power
supply at the ODU
terminal block?
Improper connection of power supply cable
Main power supply problem
Yes
No
Yes
No
Outdoor PCB fault
Replace after checking
Re connect transmission cable
No
Yes
Indoor PCB fault
Replace after checking
* (Note1) Transmission from IDU is normal if voltage
fluctuation(-9V ~ +9V) exists when checking DC voltage
of communication terminal between IDU and ODU
Is total number of indoor
units connected displayed
after auto addressing?
No
END
* If the DC voltage between transmission terminal A, B
of indoor unit is fluctuate within (-9V~+9V) then
transmission from outdoor unit is normal
Check the insulation of inverter
/ constant compressor and replace
if required
Check the capacity of main circuit
breaker and replace if required
If all ok,
Turn on main circuit breaker
Replace outdoor PCB after
checking
Replace TRANS after checking
Replace the PCB of indoor unit
displayed error
Re-connect after check the
transmission cable of indoor
unit displayed error**
Check if the
transmission cable is
properly connected
to indoor / outdoor
terminal block?*
n Error diagnosis and countermeasure flow chart
Self-diagnosis function
- 117 -
Copyright2010LGElectronics.Inc.Allrightreserved.
Onlyfortrainingandservicepurposes
LGEInternalUseOnly
06
RefertoCH02
Error
No.
Error Type Error Point Main Reasons
Indoorunitoutletpipe
temperaturesensoropen
orshort
Indoorunitoutletpipe
temperaturesensor
error
07
1.Indoorunitsareindifferentmode
2.PCBfault
3.cabledremotecontrollerfault
j Checkingch07method
IDUdoesntoperateasOperationmodeis
flickeringatIDUwiredremotecontrollerandIDU
displaywindow.
Error
No.
Error Type Error Point Main Reasons
TheIndoorunitsstarted
laterareoperatedindif-
ferentmodefromearlier
one.
AllIndoorunitsarenot
runninginsamemode
n Error diagnosis and countermeasure flow chart
*Checkmodeselectionsettingofwiredremotecontroller.
**OutdoormainPCBdipswitchno.5(Cooling)orno.6(heating)isinOn,differentmodeoperationerror
mayoccurbecausetheoperationmodeisfixedbydipswitchsetting.
Dip switch Setting
***DissolutionmethodCH07withremotecontroller
1)Errorremovalmethod:TurnoffremotecontrollerbypressingtheOn/Offbuttononthecabledremotecontroller.
Theerrorcodewillberemovedautomaticallyafterfewseconds.
Withcablelessremotecontroller:Turnoffindoorunit,andthenturnonbychangingtheoperation
mode.Theerrorwilldisappear.
Is operation mode of
outdoor & Indoor units
same?
Adjust outdoor main PCB
dip switch setting *
Yes
No
END
Does error code
disappear
after set operation
mode same?**
Replace Indoor PCB***
No
Yes
1 2 3 4 5 6 7
ON
1 2 3 4 5 6 7
ON
1 2 3 4 5 6 7 8 9 10 11 12 13 14
1 2 3 4 5 6 7
ON
1 2 3 4 5 6 7
ON
1 2 3 4 5 6 7 8 9 10 11 12 13 14
Self-diagnosis function
- 118 -
Copyright2010LGElectronics.Inc.Allrightreserved.
Onlyfortrainingandservicepurposes
LGEInternalUseOnly
09
1.Errordevelopedintransmissionbetweenthe
micro-processorandtheEEPROMonthesur-
faceofthePCB.
2.ERRORduetotheEEPROMdamage
Error
No.
Error Type Error Point Main Reasons
IndoorunitEEPROM
error
n Error diagnosis and countermeasure flow chart
****AfterreplacingtheindoorunitPCB,makesuretobedonetodoAutoaddressingandinputtheaddressofcentralcontrol
*****IfODUDryContactfunctionisset,differentmodeoperationerrormaybeoccurredbecausetheoperationmodeisfixed.
-ReplacetheindoorunitPCB,andthenmakesuretoperformAutoaddressingandinputtheaddressofcentralcontrol
Self-diagnosis function
- 119 -
Copyright2010LGElectronics.Inc.Allrightreserved.
Onlyfortrainingandservicepurposes
LGEInternalUseOnly
10
IndoorunitBLDCfanmotor
failure
Error
No.
Error Type Error Point Main Reasons
IndoorBLDCfanmotor
feedbacksignalisabsent
(for50sec.)
1.Motorconnectorconnectionfault
2.IndoorPCBfault
3.Motorfault
n Error diagnosis and countermeasure flow chart
Is connector
connection proper?
Yes
No
Connect properly
Is fan motor
normal?*
Replace indoor unit fan motor
* It is normal when check hall sensor of indoor fan motor as shown below
Yes
No
k
Replace indoor unit PCB **
<Checking connection state of fan motor connector>
1 4 5 6 7
1
5
6
7
4
4
4
4
Each termainl with the tester
Tester
TH chassis
hundreds k hundreds k
hundreds k hundreds k
+ - TD chassis
Normal resistance(10%)
** Replace the indoor unit PCB, and then make sure to do Auto addressing and input the
address of central control
(Notice: The connection of motor connector to PCB should be done under no power
supplying to PCB)
Self-diagnosis function
P/NO : MFL50459505 NOVEMBER, 2010

You might also like