OPERATION MANUAL

THREE-PHASE MULTI TARIFF-DEMANDMETER
ACTIVE
ELECTRONIC ELECTRICITY METER


MODEL : VEM-T5100DB0
MODEL : VEM-T5100DB2




















2
CONTENTS


GENERAL INFORMATION AND WARNINGS ...3
TYPE CODE TABLE............3
GENERAL FEATURES...................................... .....4
TABLE OF PRODUCT SPECIFICATIONS............ 5
FUNCTIONS..........5
INSTALLATION INSTRUCTIONS.........6
CONNECTION DIAGRAMS............7
RS485 CONNECTION INFORMATION.............7
DISPLAY SYMBOLS.......8
DISPLAY INFORMATION..9
SUB-MENU INFORMATION.......................10-11
SECOND SUB-MENU INFORMATION..............13-15
ERROR WARNING DISPLAYS.........14
COMPANY AND TECHNICAL SERVICE INFORMATION...15





































GENERAL INFORMATION AND WARNINGS
3

This manual provides information regarding the specifications, installation and operation of the VIKO BRAND,
VEM-T series Electronic Electricity Meters.
PLEASE READ THIS MANUAL CAREFULLY BEFORE ATTEMPTING TO INSTALL OR
OPERATE THE METER!
THE INSTALLATION OF THE METER MUST BE PERFORMED BY QUALIFIED PERSONNEL,
IN ACCORDANCE WITH THE METERS OPERATIONAL INFORMATION.
POWER LINES MUST BE DISCONNECTED DURING THE INSTALLATION AND
DISASSEMBLY OF THE METER.
COMING INTO CONTACT WITH PARTS THAT ARE CHARGED WITH VOLTAGES POSE
LETHAL RISK.
THE METER MUST BE OPERATED IN ENVIRONMENTS HAVING TEMPERATURES
BETWEEN THE VALUES SPECIFIED WITHIN THIS MANUAL.
THE EXTERIOR SURFACE OF THE METER SHOLD NOT BE CLEANED USING ABRASIVE
MATERIALS.
THE CALIBRATION AND PROGRAMMING OF THE METER IS CARRIED OUT DURING THE
PRODUCTION PHASE AND EACH METER IS OFFERED AFTER CONDUCTING QUALITY
CONTROLS. THERE ARE NO MAINTENANCE OR PROGRAMMING ACTIVITIES THAT MAY
BE CONDUCTED BY THE USERS.
This manual is the property of Viko, and it may not be copied, reproduced, or lent to third parties.
All information contained herein is current information at the time of printing. VIKO reserves the right to make
changes without prior notification.

Scope of the Guarantee
Our meters are guaranteed against production flaws for a period of five (5) years. The damages that may arise
due to installation and operation of the meters that are not in accordance with the information stated in this
manual are excluded from the scope of the guarantee.
Servicing or maintenance may only be performed by VIKOs authorized technical service personnel or other
persons or organizations that are authorized by VIKO. The damages that may arise due to the servicing or
maintenance performed by unauthorized persons renders the guarantee void.

VIKO BRAND, VEM-T series Electronic Electricity Meters are designed and produced in accordance with the
most current international standards applicable in Turkey. The meters are designed to provide precise readings,
with the help of high-tech components for flawless operation over long periods of time in accordance with the
most current international standards to provide ease of use while possessing physical qualities that are able to
satisfy site requirements.
The meter satisfies the following standards:
TS EN 50470-1
TS EN 50470-3
TS EN 62054-21
TS EN 62056-21













METER TYPE CODE TABLE
4
PRODUCT
CODE
TYPE OF
MEASUREMENT CURRENT TYPE OF CONNECTION
MEASUREMENT
CLASS
COMMUNICATION
OUTPUT TYPE
VEM
-
X XXXXX X X X X
VIKO ENERGY
METERING M = MONOPHASE 1080 D = DIRECT CONNECTION A = CLASS A 0= NOT
NULL
CHARACTER
NORMAL
T = THREEPHASE 10100
C = WITH CURRENT
TRANSFORMER B = CLASS B 1= RS232
P= WITH
ADVANCE
PAYMENT
C = COMBI x5
V = WITH CURRENT/VOLTAGE
TRANSFORMER C = CLASS C 2= RS485
1060 3= PLC
5(80)
5(100)



General Features
Active energy measurement
Active demand measurement
Has a timer and calendar that may operate during power outages.
Automatic daylight saving adjustments in accordance with the EU norms in force
Technical hardware that allows for canceling the application of daylight savings or makes it possible to
alter the times.
Storage of the data belonging to the previous year.
8 time zones and 4 tariffs, the tariffs may be altered without having to remove the meter from where it is
placed.
Communication through an optical port
Large LCD display for ease of reading
Availability of information from the optical port and LCD display even if there is a power outage.
Ability to view the electric terminal cover and top covers (open/closed) positions on the LCD display
Critical battery level warning
Timer error warning
60 day demand profile
Ability to set the index information displayed on the LCD display in 5 integers and 3 decimals, 6
integers and 2 decimals or 7 integers and 1 decimal.
Displaying of the active operational direction for all phases on the LCD display
Phase sequence error warnings
Demand definition and displaying of warnings in the event of exceeding demand

THE FOLLLOWING INFORMATION ARE DISPLAYED IN THE SUB-MENU THAT CAN BE
ACCESSED BY PRESSING AND HOLDING DOWN THE METER READING BUTTON.
Displaying of the index information of the previous month on the LCD display
Displaying of the voltage levels for each phase on the LCD display
Displaying of the voltage levels between phases on the LCD display
Displaying of the current values for each phase on the LCD display
Displaying of the power factor values for each phase on the LCD display
Displaying of the network frequency for each phase on the LCD display
Displaying of the power values for each phase on the LCD display
Displaying of the total power passing through the meter on the LCD display




TABLE OF PRODUCT SPECIFICATIONS
5
MODEL
T5100DB2
T5100DB0
T10100DB2
T10100DB0

TYPE OF
CONNECTION
THREEPHASE,
3 PHASE
4 WIRES
THREEPHASE,
3 PHASE
4 WIRES

CURRENT CIRCUIT
POWER CONSUMPTION
< 2 W 10 VA
OPERATING VOLTAGE 230/400 V 230/400 V
VOLTAGE CIRCUIT
POWER CONSUMPTION
<4VA
MINIMUM CURRENT
FOR CORRECT
MEASUREMENT
0.25 A 0.5 A
TIMER BATTERY
VOLTAGE
3.6 V
CURRENT FOR
STARTING
MEASUREMENT
0.02 A 0.04 A
READING BATTERY
VOLTAGE
3.6 V
REFERENCE
CURRENT
5 A 10 A BATTERY CAPACITY 1.2 Ah
MAXIMUM CURRENT 100A 100A BATTERY LIFE 10 YEARS
CONSTANT 1000 imp/kWh 1000 imp/kWh TIMER PRECISION <0,5 Sec./DAY
CLASS OF ERROR B B NUMBER OF TARIFFS 4 Energy tariffs
FREQUENCY 50 Hz 50 Hz
NUMBER OF
TIMEZONES
8 time zones
ISOLATION CLASS IP54 IP54 DISPLAY LCD life 10 years
RELATIVE RATE OF
HUMIDITY
95% 95% DIMENSIONS
TEMPERATURE
RANGE
-40 C / +70 C -40 C / +70 C WEIGHT
CLASS OF EMC E2 E2
CLASS OF
ENVIRONMENT
M1 M1







6



HOLDING PART : They are used during the installation of the meter. The position of the part of the meter
can be adjusted vertically with the help of the adjustment screws found on the back of the meter.

LCD DISPLAY : It displays the information gathered by the meter.

OPTICAL PORT : It is a communication unit that enables communication between the meter and a hand
held terminal or computer for the programming of permitted parameters or for the reading of the information
gathered by the meter.

READING BUTTON : It is the button that successively updates the informaton gathered by the meter on the
LCD display. If the meter button is not pressed, the display information will be updated automatically every 5
seconds and displayed on the screen. The automatic screen will start to operate 30 seconds after a reading has
been conducted using the button.

TOP COVER SEAL: It is a seal affixed after the production, quality control and calibration procedures of the
meter have been conducted. Due to the fact that legal action may be taken against unauthorized persons
that tamper with these seals, the seals shall not be removed or damaged.

TERMINAL COVER SEAL: It is an area where the distribution company must affix their seals in order to
prevent unauthorized access to the electric terminal block where the meter connections are made. Due to the
fact that legal action may be taken against persons that have not been authorized by the distribution
company but tamper with the electric terminal seals, the seals shall not be removed or damaged

TERMINAL COVER : It is the part which covers the area where the meters connections are made. In the
event that the covers are opened, the information at the time of opening of the covers are recorded in the
devices memory. After installation, power is supplied after the covers have been closed. There is a part
underneath that may be broken off for the cables to be inserted.

























Figure 1 Figure 2
7



INSTALLATION OF THE METER AND ITS SEALS

The meter is installed by the help of the installation part located on the top of the device and the three
installation holes found on either bottom side of the device. The dimensions of the device are shown in
figure 1, and the installation holes are shown in figure 2.
The VEM-T series electronic electricity meters are protected against unauthorized use with the help of a
total of 3 seals of which 2 are calibration seals and 1 is an electric terminal cover seal.


INSTALLATION INSTRUCTIONS

1- Install the meter using the installation holes as shown in figure 2.
2- Make the phase and neutral connections in accordance with the connection diagram.
(While the connections are being made, make sure that the tips of the cables are properly stripped,
that the connection screws in the electric terminal are tightened in a way that does not damage the
conductor, and that no faulty connections are made.)
3- Before applying voltage, make sure that the electric terminal cover and the electric terminal cover
button are closed.
4- Apply voltage and current. In the event that the directions of the current and voltage connections are
made in reverse, the phase that has been connected in reverse will be displayed on the screen as phase
P. In the event that the phase sequence has been connected in reverse, the R-S-T symbols flash on the
meter display. When this happens, control the meters connections after you have disconnected the
power. In the event that the meter is properly connected and the three phases are energized, the R-S-T
symbols will light up constantly. In the event that the current polarities are properly connected a + P
symbol will be displayed on all phases.




CONNECTION DIAGRAM OF A THREE-PHASE METER












RS 485 CONNECTI ON









8



VEM-T10100DB2 MODEL: The RS485 outputs are supplied as standard components in our VEM-T5100DB2
Three-phase meters. It is possible to obtain a read-out from the meters thanks to these outputs. It is possible to
access numerous meters by connecting these outputs in parallel. The protocol structure for communicating with
the meters is as follows: Communicating structure is in accordance with the TS EN 62056-21 standard.

Communication established!

Baud Rate 300
--> /?00012835![CRLF]
<-- /VIK5<1>VEM-M1080DB2
--> [ACK]051
--> [ACK]051

Baud Rate 9600
--> [SOH]R2[STX]0.0.0()[ETX]P
<-- [STX]0.0.0(00012835)[ETX]?
--> [SOH]B0[STX]0.0.0()[ETX]P
--> [SOH]B0[STX]0.0.0()[ETX]P

Communication shut down!


DI SPLAY SYMBOLS










Timer error warning


Lights up when information related to date is displayed on the LCD screen.

Lights up when information related to time is displayed on the LCD screen.


Battery warning



The section where OBIS codes of the information displayed on the meter screen is shown.


The numerator where the information contained in the meter is displayed.


The section that indicates which tariff information belongs to the tariffs


Indicates the tariff that the meter keeps records in.

The symbols indicating the direction of the current passing through the meter. When the
symbol +P is displayed on screen, it means that the connections of the meter have been
properly made. When the symbol +P is displayed on screen, it means that the meters current
9
connections have been made in reverse.

It is displayed on the screen in the event that voltage is applied on the phase connections, it lights up
constantly when the connections have been made properly, and it flashes when there is an error in the
phase sequence.


Indicates that the information displayed on the screen is related to demand.


Indicates the measurement units of the information displayed.


Terminal cover opening warning.


Top cover opening warning.

Displayed when information regarding reactive consumption is displayed on screen.


DI SPLAY I NFORMATI ON

DATE




TIME





TOTAL ACTIVE ENERGY




TARIFF 1
ACTIVE ENERGY



TARIFF 2
ACTIVE ENERGY




TARIFF 3
ACTIVE ENERGY


10
TARIFF 4
ACTIVE ENERGY



CURRENT PERIOD (MONTH) ACTIVE ENERGY
P-MAX VALUE




DATE OF INFORMATION OF
ACTIVE ENERGY P
MAX




TIME OF INFORMATION OF
ACTIVE ENERGY P
MAX



Can be read in sequence by pressing the display information reading button. The automatic screen that operates 30 seconds after the
display button is pressed, indicates the information on screen at 5 second intervals.


SUB-MENU INFORMATION
The sub-menu can be accessed by pressing and holding down the meter reading button for 3 seconds. The latest
demand reset information for the meter is displayed in the sub-menu. To exit the sub-menu, the reading button
must be pressed and held down for 3 seconds. If the meter is left in the sub-menu, it will return to the main
menu automatically after 30 seconds.




SERIAL NUMBER



PREVIOUS PERIOD TOTAL
ACTIVE ENERGY




PREVIOUS PERIOD TARIFF 1 TOTAL
ACTIVE ENERGY



PREVIOUS PERIOD TARIFF 2 TOTAL
ACTIVE ENERGY



PREVIOUS PERIOD TARIFF 3 TOTAL
ACTIVE ENERGY
11




PREVIOUS PERIOD TARIFF 4 TOTAL
ACTIVE ENERGY




PREVIOUS PERIOD (MONTH) ACTIVE ENERGY
P-MAX VALUE



PREVIOUS PERIOD
DATE OF INFORMATION OF
ACTIVE ENERGY P
MAX




PREVIOUS PERIOD
TIME OF INFORMATION OF
ACTIVE ENERGY P
MAX





DATE OF THE OPENING
TERMINAL COVER





TIME OF THE OPENING
TERMINAL COVER




NUMBER OF TIMES TERMINAL
COVER HAS BEEN OPENED












12



2. SUB-MENU INFORMATION (OPERATIONAL INFORMATION)
The following information may be accessed in the meters 2nd sub-menu. To display the menu on the screen,
the reading button must be pressed and held down for 6 seconds. The first sub-menu is displayed 3 seconds
after the menu button is pressed, and if the button is kept held down for 6 seconds, the second sub-menu is
displayed. The menu button must be pressed for a long period of time to exit the sub-menu in question. If the
meter is left in the second sub-menu, it will return to the main menu automatically after 30 seconds.


R PHASE VOLTAGE VALUE





S PHASE VOLTAGE VALUE





T PHASE VOLTAGE VALUE




VOLTAGE VALUE BETWEEN R-S PHASES




VOLTAGE VALUE BETWEEN R-T PHASES





VOLTAGE VALUE BETWEEN S-T PHASES




R PHASE CURRENT





S PHASE CURRENT




13

T PHASE CURRENT




R PHASE ACTIVE POWER





S PHASE ACTIVE POWER





T PHASE ACTIVE POWER




R PHASE REACTIVE POWER





S PHASE REACTIVE POWER





T PHASE REACTIVE POWER




R PHASE APPARENT POWER




S PHASE APPARENT POWER






T PHASE APPARENT POWER


14






R PHASE COS VALUE





S PHASE COS VALUE




T PHASE COS VALUE




R PHASE FREQUENCY




S PHASE FREQUENCY




T PHASE FREQUENCY





ERROR WARNING DISPLAYS



Terminal cover opening warning.


The meter is designed to detect and record instances when the cover used for covering the terminal section that
the connections are made is opened. For the meter not to keep records of any opening of the covers during the
initial installation of the meter, the cover opening records are not kept until the meter records indexes. However,
a warning flashes to indicate the opening of the electric terminal covers. If the index that is required for
keeping record has not passed through the meter, the warning on the screen disappears after the covers are
closed. In order for records to be kept after the meter is installed, the terminal covers must be closed, and the
necessary index must be passed through the meter. If the recording of the opening of covers is activated, the
meter, records the date and time of the first opening of the covers in each month and counts, records, and stores
the number of times they have been opened during the month. This information may be accessed in the meters
15
sub-menus. During the passage to the next month, it stores the current information in its memory as the
previous months information and resets the information for the next month. It keeps recording the openings of
the covers in the next month as described above. If a month passes with the cover of the device open, it records
the date of the passing of the month as the initial opening of the covers, but indicates the number of openings as
0.
It is possible to delete the electric terminal cover opening warning through conducting optical readings from the
meter. Optical readings only delete the warning on the device display, the stored memory regarding the
openings are not erased. .




Top cover opening warning:



The device is designed to detect, record and store the date and time of the opening of the cover that covers the
section where the measurement section is located. The top cover should not be tampered with, as the opening
of the top cover which has been sealed will be regarded as attempting illegal use. When the cover is opened, a
flashing warning for the opening of the top cover will be displayed on the screen. The date and time of the
opening of the top cover will be recorded and stored in memory. Only the first opening of the covers will be
recorded, and subsequent openings will be ignored. It is only possible to reset the warning for the opening of
the top cover by authorized personnel in the factory environment.


Battery warning:




Appears on the screen when the battery supplying power to the meters timer is at a critical level. Due to the
fact that the battery is place underneath the top cover, it must be replaced by authorized service personnel.
Contact our technical service in the event that a warning is displayed.



Timer error warning:



Appears on the screen when there is an error associated with the timer. In this case, the meters tariff function is
disabled and it records the whole index as a T1 tariff. Please contact our technical service in the event that a
timer error warning is displayed.












16


COMPANY DETAILS

COMPANY TITLE: VIKO Elektrik ve Elektronik Endustrisi San.ve Tic. A.S.

ADDRESS: Abdurrahmangazi Mah. Ebubekir Cad. No:44
34887 Sancaktepe-Samandira / Istanbul

Tel : 0 216 564 55 55
Fax: 0 216 564 55 05
Web: www.vikosayac.com

TECHNICAL SERVICE ADDRESS

Abdurrahmangazi Mah. Ebubekir Cad. No:44
34887 Sancaktepe-Samandira / Istanbul

Tel : 0 216 564 55 55
Fax: 0 216 564 55 66

You might also like