Bulletin 1745

SLC Programmable
Controllers
User's Manual
Publication 1745-800 - November, 1987
Also contains the
Self-Teach Manual
Publication 1745-800A -March, 1988
fill ALLEN-BRADLEY
A ROCKWELL INTERNATIONAL COMPANY
User's Manual
40065-236-01(0
Publication 1745-800-November, 1987
Supersedes Publication 1745-800 Dated September, 1985
How to Use This Manual
The User's Manual
Section A - Becoming
Familiar with the
Equipment
Section B - The
Instruction Set,
Programming Techniques
Section C-Installingand
Maintaining the System
The Self-Teach
Manual
The Users Manual contains the necessary information to install,
program, and operate the Bulletin 1745 SLC Programmable Controllers.
The manual has been written with the assumption that the reader has a
basic knowledge of industrial relay control techniques. On this basis,
understanding and applying the controller should be simple and
straightforward.
We have divided the manual into three sections:
Introduces you to the controller components, discusses programming
basics as they apply specifically to SLC controllers, then shows you how to
use the pocket programmer. You will enter a simple program into
memory, in preparation for the next section.
Introduces you to the various instructions, beginning with relay-type
instructions, timers, and counters. It then moves on to the more complex
instructions, some of which combine two or three of the basic instructions.
Keystroke examples are included to help you gain an understanding of
how to apply the instructions to your particular needs. The section ends
with a summary of program editing techniques and on-line data control.
A chapter on using the optional EEPROM module is also included.
Contains the controller specifications and important information on
system layout, installation, and start-up. We have also included a
chapter on maintenance and troubleshooting.
This companion to the Users Manual is designed to
Help the first-time PC user gain an understanding of Bulletin 1745
SLC 100 and SLC 150 Programmable Controllers.
Supplement the programming portion of the Users Manual, providing
additional examples and exercises.
The Self-Teach Manual consists of 16 Question/Exercise (Q/E) units,
corresponding to Chapters 2 thru 17 of the Users Manual. We suggest
that after you read a chapter of the Users Manual, read it a second time,
then refer to the corresponding Question/Exercise Unit in the Self-Teach
Manual, where you will be asked questions, shown examples, and practice
programming.
We believe this to be an efficient technique in gaining an understanding
of Bulletin 1745 SLC Programmable Controllers.
How to Use This Manual ii
Related
Documentation
The following publications will be helpful to you in applying Bulletin
1745 SLC Programmable Controllers.
Publication
Application Considerations for Solid State Controls- SGI-1.1
Describes some important differences between solid state
programmable controller products and hard-wired
electromechanical devices.
Allen-Bradley Programmable Controller
Grounding and Wiring Guidelines ................................ 1770-4.1
Product Data - SLC 100 Processor Unit ....................... 1745-2.1
Product Data - SLC 100 Expansion Units .................... 1745-2.2
Product Data - Pocket Programmer ............................. 1745-2.3
Product Data-EEPROM Memory Module .................. 1745-2.4
Product Data - SLC 150 Processor Unit ....................... 1745-2.5
Product Data - SLC 150 Expansion Unit....................... 1745-2.6
Product Data - SLC 150 High Speed Input Module . 1745-2.7
Product Data-SLC 100/150 Communications Protocol 1745-2.11
Product Data - Personal Computer Interface Kit ... 1745-2.15
Quick Reference Guide ...................................................... 1745-801
Demonstrator Exercises ..................................................... 1745-802
SLC Personal Computer Software User's Manual .. 1745-825
TCAT User's Manual ......................................................... 1745-850
TCAT Demonstrator Exercises ......................................... 1745-852
Chapter Title Page
1 Introduction
Bulletin 1745 SLC Programmable Controllers ................... 1-1
Hard-Wired Control Versus the Bulletin 1745 ............... 1-1
2 Equipment Overview
General ... ....................................................................... 2-1
SLC 150 Processor Unit ..... ............................................. 2-2
SLC 150 Expansion Uhit .... .............................................. 2-4
SLC 150 High Speed Input Module.................................. 2-5
SLC 100 Processor Unit . ........................................... 2-6
SLC 100 Basic Expansion Unit ......................................... 2-8
SLC 100 Relay Output Expansion Unit............................. 2-9
SLC 100 Analog Input Expansion Unit.............................. 2-10
EEPROM Memory Module ............................................... 2-11
Pocket Programmer .......................................................... 2-11
PC Software Interface Converter ...................................... 2-12
Timer Counter Access Terminal (TCAT).............................. 2-12
3 Programming Basics
Ladder Diagram Format..................................................... 3-1
Instructions ....................................................................... 3-1
Instruction Addressing ..................................................... 3-2
Internal Addresses............................................................ 3-3
I/O Addresses .................................................................... 3-4
Instruction Classifications .................................................. 3-6
Logical Continuity .............................................................. 3-7
External I/O Devices .......................................................... 3-8
Processor Operating Cycle ................................................ 3-9
I/O Scan ........................................................................ 3-9
Program Scan ............................................................. 3-9
Typical Scan Times ..................................................... 3-10
Becoming Familiar with the Equipment A-2
Chapter Title Page
4 Using the Pocket Programmer
The Pocket Programmer ................................................... 4-1
Keyboard ..................................................................... 4-1
Display........................................................................... 4-2
Modes of Operation .......................................................... 4-3
Practice Setup .................................................................. 4-4
New Processors ............................................................ 4-6
Using an Access Code (Password) ..................................... 4-7
Mode Selection ................................................................. 4-7
Entering a Simple Program ................................................ 4-8
Display Symbols.................................................................. 4-9
Error Codes-SLC 100andSLC 150 ..................................... 4-10
Error Codes-SLC 150 ....................................................... 4-11
Contents The Instruction Set,
Programming Techniques
Chapter Title Page
5 Relay Type Instructions
General .............................................................................. 5-1
Examine ON, Examine OFF, Output Energize ................... 5-2
Equivalent User Programs ................................................. 5-3
Unconditional Output Energize.......................................... 5-4
Branch Instructions ........................................................... 5-4
The Nested Branch ....................................................... 5-5
Output Latch, Output Unlatch ........................................... 5-6
Hold-In Rungs-Operating Differences Series A vs B .. 5-7
6 Timer Instructions
RTOand RTF Timer Characteristics ................................. 6-1
AC, PR, and RAC Values ............................................. 6-1
Status and Overflow Bits ........................................... 6-2
Reset Instruction .......................................................... 6-2
Typical Timer Operation .............................................. 6-3
Retentive Timer On-Delay (RTO) ....................................... 6-4
Retentive Timer Off-Delay (RTF) ....................................... 6-5
Timing Beyond 999.9 Seconds ........................................... 6-6
Timer Keystroke Example ................................................ 6-7
Programming an RTF Timer.......................................... 6-8
7 Counter Instructions
CTU and CTD Counter Characteristics ............................... 7-1
AC, PR, and RAC Values ............................................... 7-1
Setting a Counter ......................................................... 7-2
Status and Overflow/Underflow Bits............................ 7-2
Reset Instruction .......................................................... 7-2
Typical Up Counter Operation ..................................... 7-3
Up Counter (CTU) .............................................................. 7-4
Keystroke Example ............................................................ 7-5
Up-Down Counter............................................................ 7-6
Counting Beyond 9999 ...................................................... 7-7
B-2 The Instruction Set, Programming Techniques
Chapter Title Page
8 Timers with Long or Fine Time Base
General ............................................................................. 8-1
Long Time Base Instruction ............................................... 8-2
Fine Time Base Instruction ................................................ 8-3
Procedure for Using the Fine Time Base Instruction 8-4
9 MCR and ZCL Instructions
MCR and ZCL Instruction Characteristics ....................... 9-1
ZCL Zones Using the Same Outputs ......................... 9-3
Nesting ZCL Zones .................................................... 9-4
MCR and ZCL Instructions VS a Master Control Relay 9-5
10 Sequencer Instructions
SQO and SQI Sequencer Instructions ............................. 10-1
Time-or Event-Driven ................................................ 10-1
Status and Completion Bits ....................................... 10-2
Reset Instruction ....................................................... 10-2
Sequencer Data ......................................................... 10-3
Monitoring and Changing Data ................................. 10-3
Power Down .............................................................. 10-3
Basic Operation - Sequencer Output .............................. 10-4
Basic Operation-Sequencer Input.................................... 10-5
Sequencer Data ............................................................... 10-6
Filling in the Sequencer Data Form.................................. 10-8
Sequencer Output (SQO) ............................................... 10-10
Sequencer Input (SQI) ................................................... 10-11
Programming Sequencer Instructions .......................... 10-12
11 Special Sequencer Instruction Techniques
Cascading SQO Instructions ............................................ 11-1
Cascading SQI Instructions .............................................. 11-3
Reversing Sequencer Step Operation.............................. 11-4
Sequencer Input Driving a Sequencer Output ............... 11-6
SQI Monitoring an SQO ................................................... 11-6
Sequencer Jump Operation .......................................... 11-10
B-3
Chapter Title Page
12 High Speed Input Programming
The High Speed input (HSi) Module ................................ 12-1
The HSI Counter Instruction ............................................ 12-2
Basic Operation ............................................................... 12-2
Special Application Considerations ................................. 12-4
Application Example-Two Step Cut Off Operation . 12-6
Application Example - Multiple Step Position Control 12-7
13 Shift Register Instruction
General ............................................................................ 13-1
Programming the Shift Register Instruction ................... 13-1
Event-Driven Shift Registers ........................................... 13-2
Time-Driven Shift Registers ............................................. 13-3
Cascading Shift Registers ................................................. 13-4
Circulating Shift Register ................................................. 13-5
Example: Using Shift Register Outputs ........................... 13-6
14 Special Internal Instructions
General ........................................................................... 14-1
Auto-Man Switch - Address 876 ..................................... 14-1
Program lnitialization-Address868 .................................. 14-2
Non-Retentive Latch .................................................. 14-2
Non-Retentive Timers ................................................ 14-3
Initializing an Up-Down Counter ............................... 14-4
Initializing a Latch Instruction .................................... 14-4
TCAT Power-Up - Address 867 ........................................ 14-5
Breakpoint Instruction - Address 100.............................. 14-5
Programmable EEPROM Auto-Load -SLC 150 Only . 14-7
Battery Status-SLC 150 Only ............................................ 14-7
Triac Zero-Cross Turn-On-SLC 150 Only .......................... 14-8
B-4 The Instruction Set, Programming Techniques
Chapter Title Page
15 Program Editing
General ........................................................................... 15-1
Cursor Control ................................................................. 15-2
Keystroke Example - Cursor Control ............................... 15-3
Search Function................................................................ 15-4
Keystroke Example-Search Function .............................. 15-5
Insert and Remove Functions ......................................... 15-6
Changing Instructions in the Program Mode .................. 15-9
Protecting PR Value of Timers, Counters, Sequencers 15-9
Deleting an Entire Program ............................................. 15-9
Program Editing Techniques ......................................... 15-10
16 On-Line Data Control
General ........................................................................... 16-1
Force Function ................................................................ 16-1
TRUE-FALSE Status Indicator .......................................... 16-2
Changing and Monitoring Techniques ............................ 16-4
17 Using the EEPROM Memory Module
The EEPROM Memory Module ....................................... 17-1
EEPROM Program Identification .................................... 17-1
Installing the EEPROM .................................................... 17-2
Storing and Loading Procedures ..................................... 17-2
Storing a Program in the Memory Module .............. 17-3
Loading the EEPROM into the Processor RAM ... 17-3
Auto-Load Procedure ................................................. 17-4
Programmable Auto-Load-SLC 150 Processor Unit . 17-4
Editing EEPROM Programs ............................................. 17-5
Changes not Saved in EEPROM (Error Code E52)_____ 17-5
Contents Installing and
Maintaining the System
Chapter Title Page
18 Specifications
General Specifications-
SLC 100 Processor Unit .............................................. 18-1
SLC 100 Expansion Units............................................. 18-2
Input Specifications -
SLC 100 Processor and Basic Expansion Units . . . . 18-3
SLC 100 Analog Input Expansion Unit......................... 18-4
Output Specifications -
SLC 100 Processor and Expansion Units .................... 18-5
General Specifications -
SLC 150 Processor Unit .............................................. 18-6
SLC 150 Expansion Unit .............................................. 18-7
Input Specifications -
SLC 150 Processor and Expansion Units .................... 18-8
Output Specifications -
SLC 150 Processorand Expansion Units ..................... 18-9
General Specifications-
SLC 150 High Speed Input Module............................18-11
Pocket Programmer ..................................................18-12
EEPROM Memory Module ........................................18-12
Instruction Execution Times and Word Usage -
SLC 100 ......... .......................................................... 18-13
SLC 150 ..................................................................... 18-14
Auto-Baud Recognition-SLC 150 .................................... 18-14
19 System Layout Recommendations
General ... ...................................................................... 19-1
Enclosure Considerations ............................................... 19-1
Component Spacing ...................................................... 19-2
Excessive Heat ................................................................. 19-3
Wiring Layout .................................................................. 19-3
Grounding ........................................................................ 19-3
Master Control Relay ....................................................... 19-4
Common Power Source ................................................... 19-6
Isolation Transformer ...................................................... 19-6
Special Considerations .................................................... 19-7
Excessive Line Voltage Variations .............................. 19-7
Excessive Noise .......................................................... 19-7
Output Contact Protection ........................................ 19-9
Installing and Maintaining the System C-3
Chapter Title Page
22 Maintenance and Troubleshooting
General ............................................................................. 22-1
Safety Considerations ....................................................... 22-1
Preventive Maintenance .................................................. 22-1
Spare Parts ...................................................................... 22-2
Terminal Block Removal - SLC 150 Processor
and Expansion Units................................................... 22-3
Troubleshooting .............................................................. 22-3
Power Supply ............................................................. 22-4
Processor Restart Switch ........................................... 22-5
Power Supply Fuse Replacement............................... 22-5
Processor Fault Detection ......................................... 22-7
RAM Memory Battery Backup .................................. 22-10
I/O Hardware ............................................................. 22-12
Pocket Programmer .................................................. 22-15
Diagnostic Test-Programmer, Mode 9 ...................... 22-15
Communication Problems (Error Codes 10 thru 25) 22-15
Expansion Unit Problem (Error Code 26) .................. 22-16
EEPROM Module Problem (Error Codes 51 and 52) 22-16
I Index
c
C-2 Installing and Maintaining the System
Chapter Title Page
20 Installation Procedure
General ........................................................................... 20-1
Mounting the SLC 100 Processor, Expansion Units .. 20-1
Mounting the SLC 150 Processor, Expansion Units .. 20-2
Mounting the SLC 150 HSI Module ................................ 20-3
Connection Cables .......................................................... 20-4
Wiring I/O Devices and Incoming Power ....................... 20-6
Line Wiring Connections-SLC 100 ................................... 20-6
Digital Input Wiring Connections-SLC 100 ...................... 20-7
Analog Input wiring Connections .................................... 20-8
Output Wiring Connections-SLC 100 ............................ 20-10
Line Wiring Connections-SLC 150 ................................. 20-11
Input Wiring Connections-SLC 150 ............................... 20-12
Output Wiring Connections-SLC 150 ............................ 20-13
Wiring Connections-SLC 150 HSI Module ..................... 20-16
21 Start-Up
General ........................................................................... 21-1
inspecting the Installation (A) ......................................... 21-1
Disconnecting Motion-Causing Devices (B)..................... 21-2
Testing Inputs (C) ............................................................ 21-2
Testing Outputs (D) ......................................................... 21-4
Entering and Testing Your Program (E) ..................... 21-5
Motion Checkout (F) ....................................................... 21-6
Dry Run (G) ...................................................................... 21-7
A
Becoming Familiar
with the Equipment
Chapter
Introduction
Equipment Overview
lPtOffi4$l^ng:BkSics--r
Chapter
Hard-Wired Control
Versus the Bulletin 1745
Introduction
These are microprocessor-based programmable controllers. They make
up a technologically advanced control system having the inherent
flexibility and advantages characteristic of other programmable
controllers-but with an important difference: Simplicity. They were
designed with the first-time user in mind.
You will find these controllers easy to program, operate, and maintain,
allowing you to take full advantage of their capabilities in the shortest
possible time.
A comparison of a hard-wired relay logic system and a system using the
SLC Programmable Controller will show the similarities which make
the Bulletin 1745 controller so easy to apply.
The following figure shows a hard wired relay control logic system. For
purposes of comparison, it is divided into sections, consisting of:
Input Devices, which include devices operated manually (push
buttons) and devices operated automatically (limit switches) by the
machine or process being controlled.
Relay Control Logic, consisting of relays, timers, etc. interconnected
to energize or de-energize output devices in response to the status of the
input devices, and in accordance with the logic designed into the circuit.
Output Devices, consisting of motor starters, solenoids, etc. which
control the machine or process.
A similar control system, using the Bulletin 1745 controller is shown
below. The only difference in this figure is that the relay control logic
section is replaced by the SLC Programmable Controller.
In place of hard-wired relay circuitry, the SLC Programmable
Controller uses programmed instructions,with relay-type symbology.
With the Bulletin 1745, you are still employing familiar relay logic
methods-but in a new way, which provides a great deal more flexibility.
Genera/ The diagrams above list the various SLC Programmable Controller
components. Diagram A indicates the components you can use with the
SLC 150 Processor Unit. Programming and monitoring devices, shown
at the left, include the pocket programmer, PC software interface
converter, and timer counter access terminal (TCAT). These devices
plug into the communication port of the processor.
I/O expansion units, shown at the right, are connected by cable to the
processor unit. They can be used in various combinations to obtain the
I/O configuration you require. If your application involves high speed
counting, you can also add high speed input modules.
The EEPROM memory module, shown in the center, plugs directly into
the processor unit.
Diagram B indicates the components you can use with the SLC 100
Processor Unit. These are the same components used with the SLC 150,
with one exception. The SLC 150 high speed input module can be used
with the SLC 150 processor unit only.
Important features are pointed out on the following pages:
__________________________________Page __________________________________ Page
SLC 150 Processor Unit 2-2 SLC 100 Analog Input Expansion Unit 2-10
SLC 150 I/O Expansion Unit 2-4 EEPROM Memory Module 2-11
SLC 150 High Speed Input Module 2-5 Pocket Programmer 2-11
SLC 100 Processor Unit 2-6 PC Software Interface Converter 2-12
SLC 100 Basic Expansion Unit 2-8 Timer Counter Access Terminal 2-12
SLC 100 Relay Output Expansion Unit 2-9
Chapter
2 2-2
Equipment Overview
(10) Communication
port.
(5) input power
fuse.
(1a) Incoming line
wiring terminals.
(l b) Wiring terminals
for 20 inputs.
(12) Battery
compartment.
(3) Color patch.
(11) Expansion
unit connection.
(6) Input status
indicators.
(4) Diagnostic
indicators.
(9>EEPROM memory
module compartment.
(8) Auto/Manual
switch.
(2) Wiring terminals
for 12 outputs.
(7) Output status
indicators.
SLC 150 Processor Unit The following features are pointed out in the illustration above.
1. a) Incoming line wiring terminals, b) Wiring terminals for 20 inputs.
Self-lifting pressure plates allow for easy wire insertion and secure
connections. Terminals accept two #14 AWG wires. The hinged
cover (shown in the open position) has write-on areas for
identification of external circuits. The terminal block is removable
for easy processor unit replacement.
2. Wiring terminals for 12 outputs. The removable terminal block has
the same construction as the line-input terminal block. Hinged cover
(shown in the open position) has write-on areas.
3. Color patch. Red, black, blue, green, purple, or yellow. Identifies the 6
processor unit versions. See General Specifications, Chapter 18.
4. Five red LED diagnostic indicators:
DC POWER - Indicates that the processor unit is energized and DC
power is being supplied.
PC RUN - Indicates the processor unit is in the Run mode.
CPU FAULT - Indicates the processor has detected an error in the
CPU, expansion units, or memory. Outputs are turned off and
operation is automatically stopped.
BATTERY LOW - An optional battery provides back-up power for
the CMOS RAM memory. This LED alerts you when the battery
voltage level has fallen below a threshold level.
FORCED I/O - Indicates that one or more input or output addresses
have been forced to an ON or OFF state.
Chapter
SLC150 Processor Unit
(continued)
Equipment Overview
2-3
5. Input power fuse compartment. If line terminal voltage is present but
the DC POWER LED is not lit, the fuse may be blown. Refer to
Chapter 22 for fuse replacement procedure.
6. Input status indicators. Twenty red LEDs, identified with address
numbers 1 thru 10 and 101 thru 110, corresponding to numbers below
the input wiring terminals. When an input circuit is energized, the
corresponding status indicator will be lit.
7. Output status indicators. Twelve red LEDs, identified with address
numbers 11 thru 16 and 111 thru 116, corresponding to numbers
above the output wiring terminals. When a programmed output
instruction is TRUE, the corresponding output status indicator will
be lit, and the corresponding output circuit will be energized.
8. Auto/Manual switch. This switch controls restarting of the processor
unit after a power loss, brown-out, or correction of a CPU fault.
Auto - On power-up, the processor runs thru its normal diagnostic
tests and then automatically enters the Run mode (if it was in the
Run mode at the last power-down).
Manual - On power-up, the processor runs thru its diagnostic tests
but will not enter the Run mode. To enter the Run mode, you must
move the switch to the auto position or use the pocket programmer (or
personal computer).
9. E EPROM memory module compartment. The optional memory
module can be plugged into the processor. (Cat. No. is 1745-Ml. SLC
150 processor requires a Series B module or a Series A module having
a 28-pin chip.) The pocket programmer or personal computer
software allows you to store your processor RAM program in the
EEPROM. You can also load a program from the EEPROM into the
processor RAM. In addition, the processor unit has an Auto-Load
feature.
Further details on using the EEPROM module appear in Chapter 17.
We recommend that you install an EEPROM memory
module. This will provide maximum protection against user
program loss or program alteration due to capacitor back-up drain,
battery back-up drain, processor malfunction, or excessive noise.
10. Communication port. The pocket programmer, interface converter,
or TCAT cable is plugged into this socket.
11. Socket for connecting an expansion unit or high speed input module.
Weve included a 20-pin to 10-pin ribbon cable with the processor
unit. Save this cable. You will need it if you want to connect an I/O
expansion unit to the processor unit or if you want to connect both a
high speed input module and an expansion unit.
12. Battery compartment. An optional battery assembly can be
installed in this compartment. This will provide a typical 2-3 year
back-up power for the CMOS RAM memory.
Standard back-up power (1-2 weeks) is provided by a capacitor.
Under certain conditions, battery back-up is preferable. Refer to
General Specifications (Chapter 18) for further information.
Chapter
2 2-4
Equipment Overview
* * (2) Winngtermmals
for 12 outputs. . .
(4) Diagnostic
indicator.

SLC150 Expansion Unit This unit can be connected to an SLC 150 or SLC 100 processor unit.
The following features are pointed out in the illustration above.
1. a) Incoming line wiring terminals, b) Wiring terminals for 20 inputs.
2. Wiring terminals for 12 outputs.
3. Color patch. Identifies the 6 expansion unit versions.
4. Diagnostic indicator: DC POWER - Indicates that the expansion
unit is energized and DC power is being supplied.
5. Input power fuse compartment. If line terminal voltage is present but
the DC POWER LED is not lit, the fuse may be blown. Refer to
Chapter 22 for fuse replacement procedure.
6. Input status indicators. Twenty red LEDs, identified with address
numbers A01 thru A10 and B01 thru BIO, corresponding to numbers
below the input wiring terminals. When an input circuit is energized,
the corresponding status indicator will be lit.
7. Output status indicators. Twelve red LEDs, identified with address
numbers All thru A16 and Bll thru B16, corresponding to numbers
above the output wiring terminals. When a programmed output
instruction is TRUE, the corresponding output status indicator will
be lit, and the corresponding output circuit will be energized.
8. Expansion unit connection. Hinged cover is shown open. The
expansion unit is interconnected with the processor unit and other
expansion units via ribbon cable. See Chapter 20.
Chapter Equipment Overview
2-5
(4) DIP switches
under hinged cover
(2) Interconnect
cable.
(1) Input device
wiring terminals.
(5) LED status
indicators (ACTIVE,
INPUT A. INPUT B).
|3) Expansion
connection on side
of module.
SLC150 High Speed The High Speed Input (HSI) module, illustrated above, is used with the
Input Module SLC 150 processor unit for high speed counting applications. Up to 4
modules can be connected to the processor unit. HSI features:
1. Input device wiring terminals (under hinged cover). Self-lifting
pressure plates allow for easy wire insertion and secure connections.
Terminals accept #14 AWG wires. The hinged cover has write-on
areas for identification of external circuits.
2. Interconnect cable. Plug this 3-inch cable into the expansion socket of
the SLC 150 processor unit.
3. Expansion connection. An I/O expansion unit or another HSI module
can be plugged into a socket on the side of the module. The end plug
in this socket is to be removed only if you add an expansion unit or
HSI module.
4. DIP switches. Hinged cover can be raised for access to DIP switches.
Switches can be set for 24VDC, 12VDC, or 5VDC input circuit
voltage. Switches are also used to select input filter delay time of 4
millisec. or 50 microsec.
5. LED status indicators. ACTIVE is On when HSI counter instruction
is TRUE. INPUT A is On when HSI module receives signal from
input connected to A/COUNT terminals. INPUT B is On when the B
terminals of the HSI receive a signal from an input device or the B
channel of a quadrature type encoder.
2-6
Chapter Equipment Overview
SLC 100 Processor Unit The following features are pointed out in the illustration on Page 2-1.
1. Incoming line wiring terminals. Self-lifting pressure plates allow for
easy wire insertion and secure connections. Terminals accept two
#14 AWG wires. A hinged cover is provided {but not illustrated).
The cover neednt be removed to gain access to the terminals.
2. Wiring terminals for 10 inputs. Same construction as line terminals.
The hinged cover (not illustrated) has write-on areas for
identification of external circuits. Cover is color-coded to identify the
circuit voltage level. The cover neednt be removed to gain access to
the terminals.
3. Wiring terminals for 6 outputs. Same construction as line terminals.
Hinged cover (not illustrated) has write-on areas to identify external
circuits. The cover neednt be removed to gain access to the terminals.
The processor unit has relay (hard contact) output circuits.
4. Five LED diagnostic indicators:
DC POWER (green) - Indicates that the processor unit is energized
and DC power is being supplied.
PC RUN (green) - Indicates the processor unit is in the Run mode.
CPU FAULT (red) - Indicates the processor has detected an error in
either the CPU or memory. Operation is automatically stopped.
BATTERY LOW (red) - A battery provides back-up power for the
CMOS RAM memory. This LED alerts you when the battery voltage
level has fallen below a threshold level.
FORCED I/O (amber) - Indicates that one or more input or output
addresses have been forced to an ON or OFF state.
5. Input power fuse (behind front cover). If line terminal voltage is
present but the DC POWER LED is not lit, the fuse may be blown.
Refer to Chapter 22 for fuse replacement procedure.
6. Input status indicators. Ten red LEDs, identified with address
numbers 1 thru 10, corresponding to numbers 1 thru 10 on the input
device wiring terminals. When an input circuit is energized, the
corresponding status indicator will be lit.
7. Output status indicators. Six red LEDs, identified with address
numbers 11 thru 16, corresponding to numbers 11 thru 16 on the
output contact wiring terminals. When a programmed output
instruction is TRUE, the corresponding output status indicator will
be lit, and the corresponding output contact will close.
8. Auto/Manual switch. This switch controls restarting of the processor
unit after a power loss, brown-out, or correction of a CPU fault.
Auto - On power-up, the processor runs thru its normal diagnostic
tests and then automatically enters the Run mode (if it was in the
Run mode at the last power-down).
Manual - On power-up, the processor runs thru its diagnostic tests
but will not enter the Run mode. To enter the Run mode, you must
move the switch to the auto position or use the pocket programmer (or
personal computer).
Chapter Equipment Overview
2-7
m
Communication
port.
(12) Battery
compartment.
(1) Incoming tine
wiring terminals.
(5) Input power
fuse.
(2) Wiring terminals
for 10 inputs.
C8J Auto/manua!
switch.
(9) EPROM memory
module compartment.
(11) Expansion
unit connection.
(6) Input status
indicators.
(4) Diagnostic
indicators.
(3) Wiring terminals
for 6 outputs.
(7) Output status
indicators.
SLC100 Processor Unit 9. EEPROM memory module compartment. The optional memory
(continued) module can be plugged into the processor. The pocket programmer or
personal computer software allows you to store your processor RAM
program in the EEPROM. You can also load a program from the
EEPROM into the processor RAM. Refer to Chapter 17.
We recommend that you install an EEPROM memory
module. This will provide maximum protection against user
program loss or program alteration due to battery back-up drain,
processor malfunction, or excessive noise.
10. Communication port. The pocket programmer, interface converter,
or TCAT cable is plugged into this socket.
11. Expansion unit connection. The expansion unit cable is plugged in
this socket. SLC 100 and SLC 150 expansion units can be inter
connected to increase the I/O capacity of the controller.
12. Battery compartment. Back-up power for the CMOS RAM is
provided by a replaceable battery assembly, accessible from the
front of the processor unit. The lithium battery provides back-up
power for approx. 2-3 years. Battery replacement: Chapter 22.
2
Equipment Overview
2-8
Chapter
M
(1) Incoming line
wiring terminals.
(5) input power
fuse. (2) Wiring terminals
for 10 inputs.
.(8) Expansion unit
connection.
(6) input status
indicators.
(4) DC Power diagnostic
indicator. (3) Wiring terminals
for 6 outputs.
(7) Output status
indicators.
SLC100 Basic
Expansion Unit
The basic expansion unit can be used with the SLC 100 or SLC 150
processor. The following features are pointed out in the illustration
above.
1. Incoming line wiring terminals. Self-lifting pressure plates allow for
easy wire insertion and secure connections. Terminals accept two
#14 AWG wires. A hinged cover is provided (but not illustrated).
The cover neednt be removed to gain access to the terminals.
2. Wiring terminals for 10 inputs. Same construction as line terminals.
The hinged cover (not illustrated) has write-on areas for identifi
cation of external circuits. Cover is color-coded to identify the circuit
voltage level. The cover neednt be removed to gain access to the
terminals.
3. Wiring terminals for 6 outputs. Same construction as line terminals.
Hinged cover (not illustrated) has write-on areas to identify external
circuits. The cover neednt be removed to gain access to the terminals.
4. Diagnostic indicator: DC POWER (green LED) - Indicates that the
expansion unit is energized and DC power is being supplied.
5. Input power fuse (behind front cover). If line terminal voltage is
present but the DC POWER LED is not lit, the fuse may be blown.
6. Input status indicators. Ten red LEDs, IE thru 10E, correspond to
input device wiring terminals IE thru 10E. When an input circuit is
energized, the corresponding status indicator will be lit.
7. Output status indicators. Six red LEDs, HE thru 16E, correspond to
output contact wiring terminals 1 IE thru 16E. When a programmed
output instruction is TRUE, the corresponding output status
indicator will be lit, and the corresponding output contact will close.
8. Expansion unit connection. The expansion unit is interconnected
with the processor unit and other expansion units via ribbon cable.
See Chapter 20.
Chapter Equipment Overview
2-9
WRITE-ON AREAS
If addresses 111 -116 and
211-216 are allocated,
write "1" after A = and
write "2" after A +1 =.
A =
A +1 =
Relay output expansion unit:
UPPER WIRING TERMINALS
L he J : L u J L
13E
J L
14E
J L
15E
J ; L
16E
j
p 11E -| p 12E -| ; p 13E-j |-'14E -| p 15 p 16E -j
LOWER WIRING TERMINALS
Wiring terminal identification.
SLC100 Relay Output The relay output expansion unit can be connected to the SLC 100 or SLC
Expansion Unit ISO processor unit. It has the same construction features and
dimensions as the basic expansion unit except that the 10 input circuits
are replaced by 6 additional relay (hard contact) output circuits.
Relay output expansion units have wiring terminals for 6 output circuits
on the upper edge of the unit and wiring terminals for 6 more output
circuits on the lower edge of the unit. Write-on areas are provided for
you to identify the first digit of the upper and lower addresses.
The upper group always uses the lower number address block. For
example, if address blocks 2 and 3 apply to a unit, the upper group of
addresses must be 111-116 (address block 2) and the lower group 211-
216 (address block 3). This is illustrated in the diagram above.
2-10
Chapter Equipment Overview
(1) Incoming line
wiring termina Is.
(5) Input power
fuse.
(2) Wiring terminals for
input circuits 1 and 2.
(4) DC Power diagnostic
indicator. (3) Wring terminals for
input circuits 3 and 4.
(9) Expansion unit
connection.
(6) Set point status
indicators.
(7) Set point adjustment
potentiometers.
(8} Protective transparent
cover.
SLC100 Analog Input The analog input unit can be connected to the SLC 100 or SLC 150
Expansion Unit processor unit. The analog unit, illustrated above, has 4 input circuits
and no output circuits. Each input circuit has 2 adjustable set points
which can be individually programmed. The following features are
pointed out.
1. Incoming line wiring terminals. Self-lifting pressure plates allow for
easy wire insertion and secure connections. Terminals accept two
#14 AWG wires. A hinged cover is provided (but not illustrated).
The cover neednt be removed to gain access to the terminals.
2 and 3. Wiring terminals for 4 input circuits. Same construction as line
terminals. The hinged cover (not illustrated) has write-on areas for
identification of external circuits. The cover neednt be removed to
gain access to the terminals.
4. Diagnostic indicator: DC POWER (green LED) - Indicates that the
expansion unit is energized and DC power is being supplied.
5. Input power fuse (behind front cover). If line terminal voltage is
present but the DC POWER LED is not lit, the fuse may be blown.
6. Set point status indicators (red LEDs). The 8 set points (2 per input
circuit) are labeled IE thru 8E. When an input circuit set point is
reached, the corresponding status indicator will be lit.
7. Set point adjustment potentiometers.
8. Protective transparent cover. Hinged to allow access to the
adjustment potentiometers.
9. Expansion unit connection. The expansion unit is interconnected
with the processor unit and other expansion units via ribbon cable.
See Chapter 20.
Chapter Equipment Overview
2- 11
EEPROM MEMORY MODULE
WARNING - DO Nor IMSE.R OR
REVtWE WITH POWER APPLIED
UNEXPECTED OPERA HON
Could pesll.
f'X'Jt-*. ^ v-
EEPROM memory module.
Pocket progra m mer.
EEPROM Memory
Module
This optional device plugs into the SLC 100 or SLC 150 processor
unit. With the EEPROM module, you can:
Save the contents of the processor RAM memory, for storage purposes.
Load the contents of the EEPROM memory into the processor RAM.
As shown in the illustration above, a write-on area is provided for use in
identifying memory contents. You will find detailed information on the
EEPROM module in Chapter 17.
Pocket Programmer The pocket programmer is used to program, edit, and monitor controller
operation. This device, illustrated above, is easily connected to the
communication port of the SLC 100 or SLC 150 processor unit when
needed. You will find detailed information on the pocket programmer in
Chapter 4.
2-12
Chapter Equipment Overview
SLC personal computer interface kit. Includes
software, user's manuals, and interface converter.
PC Software Interface The interface converter, which plugs into the communication port of the
Converter processor unit, is part of the Personal Computer Software package. The
software allows you to use an IBM or IBM-compatible personal computer
in place of the pocket programmer. With the software, you can select
functions equivalent to the operating modes discussed in this manual.
Additional capabilities: off-line programming and program library
development; ladder diagram display and enhancements; data display
and cross reference table generation; program print-out. An RS-232-
C/RS-422 interface converter is required for communication between the
processor and computer.
Refer to the SLC Personal Computer Software Users Manual,
Publication 1745-825, for application and operation information.
Timer Counter Access The TCAT is used with the SLC programmable controllers to access
Terminal (TCAT) programmed timer, counter, and sequencer data. I/O addresses can also
be accessed. This allows production, supervisory, and maintenance
people to monitor this data "on-line.
Refer to the TCAT Users Manual, Publication 1745-850, for application
and operation information.
Chapter
Ladder Diagram Format
Instructions
Programming
Basics
The programming format for SLC controllers is the ladder diagram,
which uses symbology similar to hard-wired relay ladder circuits.
Figure 3.1 shows a relay ladder rung as used in hard-wired relay control
systems and a similar PC ladder rung as used in programming the SLC
controller. With the relay ladder rung, electrical continuity is required
to energize the output, whereas in the PC ladder rung, logical continuity
is required to energize the output.
In the PC ladder rung of Figure 3.1, the individual symbols represent
instructions; the numbers 001, 003, and Oil are the instruction
addresses. When programming the controller, these instructions are
entered one-by-one into the processor memory from the pocket
programmer keyboard. Instructions are stored in the user program
portion of the processor memory.
Some of the instructions entered are used to represent the external input
and output devices connected to the processor unit; other instructions
are "internal, used to establish the exact conditions under which the
processor will energize or de-energize output devices in response to the
status of input devices.
The memory storage unit for instructions is the word, with most
instructions occupying one word of memory storage space.
Figure 3.1
i - i ? * * f J I : *
1
'
LS1 CR4
it
Relay ladder rung consisting of a limit
switch (LS1), a N.O. contact (CR4), and a
coil (CR2). A continuous path is needed
for electrical continuity.
001 003 011
----II---II--j--( )--- :
Similar PC ladder rung. Instruction address
numbers 001,003, and 011 are identified with
LSI, CR4, and CR2 respectively. A continuous
path is needed for logical continuity.
3 2
Chapter Programming Basics
Instruction Addressing To complete the entry of an instruction, you must assign an address
number to it. This number identifies the function of an instruction and
links it to a particular status bit in the data table portion of the memory.
The status bits in the data table can be either ON (logic 1 state) or OFF
(logic 0 state), indicating the TRUE/FALSE status of the instructions
they are associated with.
Figure 3.2 is a simplified representation of the user program and data
table areas of the processor memory.
Figure 3.2
Instructions are stored in
the same order you enter
them. During Operation,
the processor carries out
these instructions in this
same order.
Most instructions occupy
one word of storage
space. 885 words are
available in the SLC TOO,
1200 words in the SLC 150.
The address number you
assign to an instruction
associates it with a
particular status bit.
This bit will be either ON
{logic 1) or OFF (logic 0),
i ndicating whether the
instruction is TRUE or
FALSE.
During operation, the
processor examines this
information and updates
it according to logical
continuity rules.
Simplified representation of the processor memory. The User Program is
the memory area which stores the list of instructions you enter. The
Data Table consists of status bits which indicate the TRUE/FALSE status
of the instructions you enter. Numerical values associated with timer,
counter, and sequencer instructions are also stored in the data table.
Chapter
3
Internal Addresses
Programming Basics
3-3
The table below lists the various internal instructions and the addresses
you will be assigning to them in your user program. The instructions
are discussed in detail in succeeding chapters.
Figure 3.3
Relay Type Instructions
701 thru 863 plus
two addresses of
each I/O address
block (Page 3-5).
701 thru 866 plus
two addresses of
each I/O address
block (Page 3-5).
5
Timer, Counter, Sequencer,
and Reset
901 thru 932
and 951 thru 982
901 thru 932
and 951 thru 982
6,7,
10,11
HSI Counter 901 thru 904
and 951 thru 954
(SQO instructions)
Not applicable 12
Fine Time Base 869 thru 873 869 thru 873 8
Long Time Base 874,875 874,875 8
Breakpoint 100 100 14
Programmable EEPROM
Auto-Load
864 Not applicable 17
Battery Status 865 Not applicable 14
Triac Zero-Cross
Turn-On Enable
866 Not applicable 14
TCAT Power-Up 867 867 14
Program Initialization 868 868 14
Auto/Man Switch 876 876 14
MCR and ZCL Addresses are not required 9
Shift Register Combines Relay Type, ZCL, and
Sequencer instructions
13
Note that these instructions apply to the SLC150 only, although the addresses
apply to instructions used in the SLC 100 ps well (relay type, timer, counter,
sequencer). You must be cautious when Interchanging programs between the
SLC 150 and SLC 100:
CAUTION: Interchanging programs between controllers could cause improper
operation and damage equipment. You must be especially cautious when
interchanging programs between SLC 150 and SLC 100 controllers, because of
differences associated with certain internal addresses and other variations.
Chapter
3 3-4
Programming Basics
I/O Addresses I/O addresses are used in your program to represent the input and
output circuits connected to the processor unit and I/O expansion units.
There are 112 I/O addresses available to you. These are divided into 7
address blocks (10 input addresses and 6 output addresses per block).
The SLC 150 processor unit, having 32 I/O, uses blocks 1 and 2. The SLC
100 processor unit, having 16 I/O, uses block 1.
You can connect various combinations of SLC 150 and SLC 100 I/O
expansion units to your processor unit. Assigning addresses is simple,
once you understand how processor "address blocks are allocated.
Figure 3.4 identifies the address blocks and summarizes the address
block requirements for the various processor and expansion units.
Figure 3.4
The 7 address blocks are identified in
the table to the right. Address block
requirements for the various processor
and expansion units are shown below.
ADDRESS BLOCKS REQUIRED FOR PROCESSOR AND EXPANSION UNITS
Type of Unit I/O
Address
Blocks
Required
Addresses Used
SLC 150 Processor Unit 20/12 2
Block 1 and 2 addresses are used. Inputs: 1-10,101-110.
Outputs: 11-16,111-116.
SLC 150 Expansion Unit 20/12 2 All addresses of 2 consecutive blocks are used.
SLC 150 High Speed Input Module 1/0 None An internal SQO address is associated with the HSI module.
SLC 100 Processor Unit 10/6 1 .. Block 1 addresses are used. Inputs: 1-10. Outputs: 11-16.
SLC 100 Basic Expansion Unit 10/6 1 All addresses of the block are used.
SLC 100 Relay Output Expansion Unit 0/12 2
Output addresses of 2 consecutive blocks are used. Input
addresses of the 2 blocks are bypassed.
SLC' 100 Analog Input Expansion Unit 8/0 ..-. Vi ;. <.
Upper two input addresses (_9, _10) are bypassed. All
output addresses of the block are bypassed.
Address Block
Number
Input
Addresses (10)
Output
Addresses (6)
1 1-10 11-16
1
2 - 101-110 111-116
' 3 ' ' 201-210 211-216
... 4
301-310 311-316
' - .5.' ' 401-410 411-416
6 /./' 501-510 511-516
- 7 - , 601-610 611-616
Connection Examples - The following examples indicate how you
might interconnect expansion units with an SLC 150 processor unit and
an SLC 100 processor unit. Note that example 1 includes an HSI
module.
Blocks1,2 None Blocks3,4 B1ocks5,6 Block 7
EXAMPLE 1 : All input and output addresses of all 7 address blocks are used. The configu
ration provides 1121/0 (70 inputs, 42 outputs). It also provides 1 high speed input circuit.
Chapter
I/O Addresses
(continued)
Programming Basics
3-5
SLC 100 SLC 100 SLC 100 SLC 100 SLC 150
Processor Basic Analog Input Relay Output Expansion
10/6 I/O 10/6 I/O 8/0 I/O 0/12 I/O 20/12 I/O
Block 1 Block 2 Block 3 Blocks 4,5 Blocks 6,7
EXAMPLE 2: All 7 address blocks are used. The configuration provides 84 I/O: 40 discrete
inputs (blocks 1,2,6,7 - addresses 1-10,101-110,501-510,601-610); 8 analog set points
(block 3 - addresses 201 -208); and 36 outputs (blocks 1,2,4,5,6,7 - addresses 11-16,
111-116,311-316,411-416,511-516,611-616).
I/O Terminal Identification - The table below indicates the terminal
identification of the four types of I/O expansion units. The table also
indicates the address blocks, input addresses, and output addresses that
apply if you connect the expansion unit to an SLC 150 processor unit.
:tXUr
rtlittw
i m VV ^i-i.
v
# ^ ^ - i
SLC 150 Inputs: A01-A10 and
B01-B10.
Outputs: A11-A16
and B11-B16.
3 and 4 Terminals: A - 2 and B =* 3. Input
addresses: 201-210 and 301-310.
Output addresses: 211-216 and
311-316.
SLC 100
Basic
Inputs: 1E-1QE.
Outputs: 11E-16E.
3 Input addresses: 201-210.
Output addresses: 211-216.
SLC 100
Relay Output
Upper terminals
(A): 11E-16E.
Lower terminals
(A + 1): 1IE -16E.
3 and 4 Terminals: A - 2 and A +1 = 3.
Upper addresses: 211-216.
Lower addresses: 311 -316.
Input addresses of blocks 3 and 4
are bypassed.
SLC 100
Analog Input
8 set points derived
from the 4 input
circuits: 1E-8E.
3 Set point addresses: 201-208.
Output addresses of block 3 are
bypassed.
Maximum I/O Configuration - The maximum I/O configuration is
112, using all available addresses. If you use SLC 100 relay output or
analog input expansion units, the maximum configuration will be less,
and varies with the particular combination of expansion units used.
Keep in mind that when you've used all 7 address blocks, youve reached
the maximum.
Internal Addresses Associated with I/O Address Blocks - The
table below lists internal relay-type instruction addresses associated
with I/O address blocks. You can use these addresses in your program in
the same way as the relay-type instructions discussed in Chapter 5, but
only if expansion units using the associated address blocks are connected
to the processor unit.
If you are using the SLC 100
processor unit, addresses 17
and 18 (address block 1) can
always be used. If you are
using the SLC 150 processor
unit, addresses 17,18,117,
and 118 (address blocks 1 and
2) can always be used.
Relay-Type Instruction
Addresses
Associated Address
Block Number
17,18 1
117,118 2
217,218 3
317,318 4
417,418 5
517,518 6
617,618 7
Chapter
3
instruction
Classifications
Programming Basics
Instructions are classified as condition instructions and output
instructions. The instruction set is shown in Figure 3.5.
Figure 3.5
Condition Instructions -] [-
Hh
EXAMINE ON
;; ;;;
-.a J
EXAMINE OFF
T BRANCH OPEN
BRANCH CLOSE
Output Instructions -( )-
-i h
-f D-
OUTPUT ENERGIZE
SHIFT REGISTER
latch;
-(SQI)-- SEQUENCER INPUT
-{CTD}- DOWN COUNTER
-(RTF)- RETENTIVE TIMER FF-DELAY
-(RTO)- RETENTIVE TIMER ON-DELAY
-<U)-
ASQOh
-(CTU)-
UNLATCH
SEQUENCER OUTPUT
UP COUNTER
ARSTh RESET
------------ -------------
-(ZCL)- ZONE CONTROL LAST STATE
-(MCR)- MASTER CONTROL RESET
Instruction set of the SLC controller. Symbols are
representations of the pocket programmer keys.
The Shift Register SymboHs-(SR)-. It does not appear on the programmer key.
Chapter
O
Logical
Continuity
Programming Basics
3-7
An example of how condition and output instructions are used is shown
in the ladder diagram of Figure 3.6. The Examine ON and Examine OFF
instructions (conditional) are analogous to relay contacts, while the
Output Energize instruction is analogous to a relay coil. However, this
diagram must be evaluated in terms of logical continuity rather than
electrical continuity.
Figure 3.6
Condition instructions Output Instruction
001
Examine
t
ON
002 ;
XI 1
011
rk t
: * '
\ )
>
; T
Examine
T
Output
OFF . ,
1
Energize
Ladder diagram rung. A continuous path of TRUE condition
instructions is required to make the output Instruction TRU E.
As stated earlier, each instruction is linked to a status bit in the data
table. The bit will be either ON or OFF to indicate the status of the
instruction. Thus, with the Examine ON instruction we are asking the
controller to "examine the status bit for an ON condition. If the status
bit is ON, then the instruction is TRUE; if the bit is OFF, then the
instruction is FALSE.
Similarly, the Examine OFF instruction means "examine the status bit
for an OFF condition. If the status bit is OFF, the instruction is TRUE;
if the bit is ON, the instruction is FALSE.
The Output Energize instruction asks the controller to "set the status bit
of the addressed Output Energize instruction to ON when rung
conditions are TRUE. Thus, in Figure 3.6, when both the Examine ON
instruction and the Examine OFF instruction are TRUE, the status bit
of the Output Energize instruction will be set to ON.
In terms of continuity: When there is a continuous path of TRUE
conditional instructions in a rung, logical continuity exists; accordingly,
the output instruction is TRUE and its status bit will be set ON. If any
conditional instruction in the continuity path goes FALSE, logical
continuity is lost; the output instruction is then FALSE and its status
bit will be set to OFF.
3-8
Chapter Programming Basics
External The user program always includes instructions to represent external
I/O Devices devices connected to the processor and expansion units. The processor
examines the status of these external devices indirectly.
Thus, in Figure 3.7a, the limit switch contact connected to input
terminal 3 causes a voltage to be present at the terminal when the
switch is closed, and removes this voltage when the switch is opened.
The processor senses these voltage levels, and sets the status bit of the
instruction representing the limit switch to ON for the closed condition
and OFF for the open condition.
If an Examine ON instruction is used to represent the limit switch
contact, the open condition makes the instruction logically FALSE, and
the closed condition makes it logically TRUE.
If an Examine OFF instruction is used to represent the limit switch
contact, the open condition makes the instruction logically TRUE, and
the closed condition makes it logically FALSE. Figure 3.7b summarizes
both the Examine ON and Examine OFF cases.
Figure 3.7b also summarizes the Output Energize instruction as it
applies to an external I/O address. In this case, if the status bit of the
instruction is ON, the corresponding output contact (Figure 3.7a) closes,
energizing the external device. If logical continuity of the rung is lost,
the status bit is changed to OFF; the output contact opens, de
energizing the external device.
Figure 3.7
External input devices are wired to processor
unit terminals 1 to 10, corresponding to
instruction addresses 001 to01Q.
LS2 H-
l J
r ) ---1
Supply Voltage -
COM 1 2 3 4 5 COMj 6 7 8 9 10 jcOM
diLj&j&j&j&iiu'
11 11 12 12 IB 13 14 14 15 15 16 16 is controlled by
processor.
Output contacts
(internal).
Open/dosed status
*- Supply Voltage
External output devices are wired
to processor unit terminals 11 to
16, corresponding to instruction
addressesQII to016.
3.7a - External input and output device connections for the SLC
100 processor unit. Input wiring terminals 1 -10 correspond to
addresses 001 -010. Output wiring terminals 11 -16 correspond
toaddresses011-016.
External
Input
Device
Input
Terminal
Hh
Examine ON
Instruction
f t
Examine OFF
Instruction
OFF
FALSE
Status Bit OFF
TRUE
Status Bit OFF
CLOSED
ON
TRUE
Status Bit ON
FALSE
Status Bit ON
---- ( )--------
Output Energize
Instruction
Output
Contacts
External
Output
Device
Status Bit ON
TRUE Rung Conditions
CLOSED
ENERGIZED
Status Bit OFF
FALSE Rung Conditions
OPEN -0-
NOT ENERGIZED
3.7b- Examine ON, Examine OFF, and Output
Energize instructions, as they relate to external
input and output devices.
Chapter
3
Programming Basics
3-9
Processor
Operating Cycle
During each operating cycle, the processor examines the status of input
devices, executes the user program, and changes outputs accordingly.
For a typical 500 word program, the SLC 150 controller repeats this
cycle about 500 times each second; with the SLC 100, the cycle is
repeated about 67 times each second.
A single operating cycle or scan is shown in Figure 3.8. Note that the
cycle is divided into two parts - the I/O scan and the program scan.
I/O Scan In the I/O scan, data associated with external outputs is transferred
from the data table to the output terminals. (This data was up-dated
during the preceding program scan.) In addition, input terminals are
examined, and the associated status bits are changed accordingly.
Program Scan The updated status of the input devices is applied to the user program
during this part of the cycle. The processor executes the entire list of
instructions in the same order they were entered. Status bits are
updated according to logical continuity rules as the program scan moves
from instruction to instruction thru successive ladder rungs. (If you use
an instruction with a unique address more than once in your program,
the solution of the rung in which the instruction last appears takes
precedence. An example appears in Chapter 9, Page 9-3.)
The I/O scan and program scan are separate, independent functions.
Thus, any status changes occurring in external input devices during the
program scan are not accounted for until the next I/O scan. Similarly,
data changes associated with external outputs are not transferred to the
outputs until the next I/O scan. Exception: If you are using the high
speed input module (SLC 150 only), the operating cycle is interrupted to
allow the processor unit to count high speed input signals and
immediately set processor unit outputs associated with SQO instructions
901-904. This is illustrated below.
Figure 3.8
3.8a. Operating cycle of the processor.
3.8b. Operating cycle when using the HSI module. The SLC
150 processor interrupts the operating cycle to count high
speed input signals and immediately set appropriate outputs.
3-10
Chapter Programming Basks
Typical Scan Times The table below lists typical scan times for the SLC 150 and SLC 100
Programmable Controllers. Approximate execution times for the
individual instructions appear on Pages 18-13 and 18-14.
Note: Scan time can vary significantly depending on program content,
program length, and expansion units connected. Also, with the SLC
150, scan time increases if you are using high speed input modules.
Scan times in excess of 100 milliseconds will be detected by the processor
and cause system shutdown. You can measure your scan time using the
techniques described on Page 8-4.
SLC 150 2.5 milliseconds 0.3 milliseconds plus 0.25
milliseconds for each
2 milliseconds
expansiommit address block.
SLC1Q0 15 milliseconds 1.5 milliseconds plus
0.27 milliseconds for each
12.4 milliseconds
expansion unit address Mock.
Chapter
The Pocket Programmer
Keyboard
Using the Pocket
Programmer
Instructions are entered into the processor memory with the pocket
programmer. Becoming familiar with the features and basic operation
of this device will prepare you for the specific programming procedures
discussed in later chapters.
The pocket programmer keyboard is shown below. Upper case functions
(FRC OFF, FRC ON, A, B, C, etc) are obtained by pressing the SHIFT
key, then the desired function key.
Figure 4.1
FRC OFF
0
FRC ON
t T
A
2
8
" > 3 '
C ;
4
0
5
EVENT
8
MODE
PRT
UNPRT
REMOVE INSERT
SEARCH
-(SQO)-
riCTU)-
-(SQD-
ACTDh
AZClh
-<MCR)-
RUNG
-i L)-
T
-( u )-
T
HRXfh
HRTOF
TIME
9
LAST
NEXT
SHIFT
CANCEL
CMD
-lb
MRST)-
A h
ENTER
Pocket programmer keyboard.
Abbreviations and Symbols
FRC OFF Force OFF " > -RTF)- Retentive Timer Off-Delay
FRC ON Force ON -RTO}- Retentive Timer On-Delay
PRT Protect CANCEL
Cancel Command
UNPRT Not Protect
CMD
-isoob Sequencer Output
-R5T)- Reset
ASQih Sequencer Input
.: - :
Branch Open
-{CTU)- Up Counter
Branch Close
Acm- Down Counter
Hb
Azcih Zone Control Last State
Examine ON
AMCRh Master Control Reset
; ; w. ; Examine OFF

*
r
r
Latch
Unlatch ;\: Ah ;
Output Energize
Shift Register (use shift key)
Chapter
4
Using the Pocket Programmer
4-2
Display The display window of the programmer is shown in Figure 4.2. The
LEDs in the upper portion illuminate when instructions are entered,
edited or monitored. Addresses, data, prompt messages, and other
information is presented on the 7-segment displays located below the
LEDs.
Figure 4.2
In this typical display, the cursor is located at an Examine OFF
instruction, address 008. It is the first instruction in rung 3 of the
program, and its current status is TRUE :
1. Illuminated LED indicates the cursor position, that is, the instruction being
entered, edited dr monitored. In this case, the Examine OFF LED is illuminated.
2. Four-character digital display shows instruction addresses and other
information. The symbol at the left indicates that the cursored instruction is at
the beginning of the rung. The number 8 at the right indicates the instruction
1 address, 008.
3. TRUE/FALSE status indicator. It is illuminated, indicating that the Examine OFF
instruction is TRUE. This indicator functions only in the Run or Test mode.
4. Three-character digital display shows rung, mode, or error code number. In this
case, the display indicates that we are in rung 3 of the program.
After you enter a program, you can move thru it from one instruction to another by
pressing the NEXT and LAST keys.
Chapter Using the Pocket Programmer
4-3
Modes of Operation The pocket programmer is used to select the various modes of operation.
A list of these modes appears on the back of the programmer. A detailed
explanation is given below.
Figure 4.3
\
1
CLEAR MEMORY : Selecting this mode erases the contents of
the on-board RAM memory. Upon completion, the
programmer automatically switches to mode 2, Program.
?
H L:Er
'
2
; /
PROGRAM: Used to enter a new program or up-date an
existing one in the RAM memory. ,
p
r
g
3
RUN: in this mode, the processor scans and executes the user
program. Input devices are monitored and output devices are
energized accordingly. In this mode, the programmer can be
used to monitor the user program,forcel/O, andchange
timer/counter preset and accumulated values. Sequencer
preset values can also be changed.
run .
4
i
TEST-SINGLE SCAN: This mode causesthe processor to
complete a single scan of the user program each time the
ENTER key is pressed. No outputs will be energized. Timer and
; time-driven sequencer accumulated values will be incremented
by 0.1 on each scan if rung conditions are correct. The
programmer can be used to monitor the user program,force
I/O, and change counter/timer/sequencer values.
55 c n
5
TEST-CONTINUOUS SCAN: Causesthe processor to operate
from the user program without energizing any outputs^ The
programmer can be used to monitor the user program, force
I/O, and change counter/timer/sequencer values.
E 5 c n

STORE USERRROGRAM IN EEPRM MODULE: Allows you to
save a program, that is, store a program contained in the on
board RAM memory in an EEPROM memory module.
S R U E
' 7
; LOAD USER PROGRAM FROM EEPROM MODULE: This mode
allows you to read a program into memory, that is, load a
program contained in an EEPROM module into the on-board
RAM memory. You can then remove the EEPROM module or
leave it in place. The processor operates from the RAM only.
r E R d
: 8 '
; ENTER/CHANGE ACCESS CODE: This mode allows you to enter
or change an access code or password. PR 5 5
DIAGNOSTIC TEST-PROGRAMMER: A sequence of self
checking diagnostic tests. Refer to Page 22-1S (Maintenance
and Troubleshooting) for details.
d IRp
t' - ,
4-4
Chapter Using the Pocket Programmer
Practice Setup SLC lOO and ISO Demonstrator Units (Catalog Nos. 1745-DEMOl,
-DEM03) provide a convenient means for practicing the keystroke
examples, monitoring techniques, and editing techniques shown in this
manual. If you do not have access to a demonstrator, you can use
another of the practice setups shown below.
Figure 4.4
SLC 1 SO processor unit with the pocket programmer plugged in.
Connect a power cordto the processor as indicated in Figure 4.5.
a r.T'ru*; wi
l
SLC 100demonstrator unit.
Hir, ^ - Vi
SLC 100 processor unit with the pocicet programmer plugged in.
Connect a power cord to the processor as indicated in Figure 4.5.
Chapter
Practice Setup
(continued)
Using the Pocket Programmer
4-5
The figure below shows the procedures for connecting an SLC 100
processor unit or an SLC 150 processor unit to a 115VAC power source.
Figure 4.5
SLC 100 Processor Un it Connections
Green / ,
V-: : : TO 11 5VAC
White Grounded :
j C r Source ;
Black
CHASSIS . 230VAC : 115V ACs 115/230
GND ' NEUT NEUT - VAC
Wiring Terminals of SLC 100
SLC 150 Processor Unit Connections
Green
Tonsure
Whlte
Grounded.
Source;; ;
Black
(2
\> 0
b
0
b Q
0
5 Q
0
5 C5
CHASSIS
GNO
NOT
USED
NOT
USED COM COM
230V AC 11SVAC 115/230 NOT
NEUT NEUT VAC USED COM COM
Wiring Terminals of SLC 150
Connection Procedure -115VAC
1. Plug the programmer cable into the processor unit (see Figure 4.4). Cable
connector is keyed to guard against improper insertion. Make sure the
spring latch is engaged to secure the cable.
2. Far 115VAC power connection, we suggest you use a flexible power cord ;
equipped with a 3-prong plug. Connect the wires as shown above.;
CAUTION: Incorrect wire connections can cause damage to the
processor unit power supply. Oo not jumper 115VAC NEUT and.
230VAC NEUT together. Do not jumper unused 115VAC NEUT or
unused 23QVAC NEUT to the CHASSIS GND terminal.
3. Plug the cord into a grounded 115 VAC outlet. If the outlet is not >
. .controlled by a nearby switch, power can be applied and removed by
plugging and unplugging the power cord.
WARNING: Contact with the source voltage can cause serious injury.
Do not apply power until the wiring is completed and checked.
0 0
4-6
Chapter Using the Pocket Programmer
Practice Setup
(continued)
New Processors
When you apply power to the processor unit, the DC ON indicator should
light, indicating that DC voltage is being supplied to the internal logic
circuitry.
When you turn the pocket programmer switch on, the programmer
display will show "SLC-100 and automatically go thru a series of
diagnostic checks; it then displays the operating mode it was left in
when last used. (If the programmer displays an error, follow the
procedure described in "New Processors at the bottom of this page.)
To be certain that you are beginning with the processor memory cleared,
enter the Clear Memory mode. To do this, press
r
>
1
ENTER
1____ 1
1 1
\____ / v_____ J
The display will show
5 u r E P
It is asking whether you are SURE you want to clear the memory.
Press the ENTER key again. The display will briefly show
d n E
indicating the memory is cleared. It will then show
00 5 End if you are using an SLC 100 processor or I p D End
if you are using an SLC 150 processor. This indicates that you are at the
end of the program and there are 885 (or 1200) words remaining in
memory. Since the memory capacity is 885 (or 1200) words, this also
tells you that the program length is zero words.
Note that the LED labeled PROG is lit. This indicates you are in the
Program mode.
If the controller is protected with an access code: When you turn
the pocket programmer switch on, the programmer will go thru the
diagnostic checks, then display
_ _ _ PR5
Enter the code and press ENTER. The processor will then enter the
mode it was left in when last used.
If this is the first time the processor unit is being used since it left the
factory, the programmer will detect a series of errors in memory. Clear
each error by pressing the CANCEL CMD key after the error is
displayed.
After you clear the errors, you must clear the processor memory. Press
MODE, 1, ENTER, ENTER. This clears the memory and places the
processor in the Program mode.
Chapter Using the Pocket Programmer
4-7
Using an Access Code
(Password)
Mode Selection
You can restrict access to the processor memory by entering a 3-digit
access code or "password. To do this, enter mode 8 (Enter/Change
Access Code) by pressing MODE, 8, ENTER. Then enter any 3-digit
number from 001 to 999 except 356, 712, or 940. Finally, press ENTER.
The access code is now stored in the user program.
Each time you use the pocket programmer (any pocket programmer),
you will be prompted for the access code with the display "PAS; you
must enter the correct code and press ENTER before the processor will
enter the mode it was left in when last used.
The access code will also protect the contents of an EEPROM memory
module. If an access code has been stored in an EEPROM, you will be
required to enter the code before the processor will execute this program
(Chapter 17).
If you want to change your code, enter your code as you normally would,
then re-enter mode 8 and press the new code and ENTER when
prompted for a code.
If you no longer want the processor to be protected by a code, re-enter
mode 8 and press 0, ENTER when prompted for a code.
An access code can be overriden. To do this, press 9, 4, 0, ENTER,
INSERT when prompted for a code. Important: The processor will no
longer be protected by the access code. It must be re-entered.
Operating modes are described in detail on Page 4-3. You can select a
particular mode as follows:
1. Press the MODE key. The programmer will display the symbol and
number of the current mode, for example
P
r n
9 E
2. Press the numerical key corresponding to the particular mode you
want. Your mode will be shown on the display.
Alternately, you can press the NEXT or LAST key repeatedly until
your mode appears on the display.
3. Press the ENTER key. If you selected mode 2, 3, 4, 5, or 9, you are
now in that mode.
If you selected mode 1, press ENTER a second time.
Entering modes 6 and 7 are discussed in detail in Chapter 17.
Entering mode 8 is discussed in the paragraph above, "Using an
Access Code (Password).
Note: When you enter the Run mode (3), outputs in your program are
enabled. When you change from the Run mode to any other mode,
outputs will be disabled.
4-8
Chapter m Using the Pocket Programmer
Entering a Simple The ladder diagram of your program is your "road map in entering and
Program reviewing your program. It is important to check the diagram for
accuracy before you enter it into memory. Number the rungs.
A simple 3-rung ladder diagram is shown below. External I/O addresses
001 and 002 are assigned to the conditional instructions (Examine ON,
Examine OFF) in each of the three rungs. External I/O addresses Oil,
012, and 013 are assigned to the three Output Energize instructions.
The step-by-step programming procedure indicates which keys you
should press, and what you should observe in the programmer display
window after pressing the keys. Note that the PROG LED is
illuminated continuously while you are in the Program mode.
Figure 4.6
Keystroke ExampU-Entering a simpl
: ^
;
Rung 1 <
1
Rung 2
Rung 3 o
e program: ;,
001 002 oil
HITir----------- ( >-
001 002 012
HLII------------ ( y-
001 002 013
HIII------------- ( >-|
-H-
---- f
When you press the Examine ON key, the corresponding LED illuminates. The
dashes are prompting you for an address. The " 1" indicates you are in rung 1.
...
1
-H- __ 1 i
Address 001 is entered by pressing key 1. You do not enter the leading zeros
of an address .. ,
! -M" -I/[- ' ' ' ^ 1
The Examine OFF key is pressed. Dashes are prompting you for an address.
2 > ;
iiua
:
i '
The address has been entered. If you enter an incorrect address, you can
delete itby pressing CANCEL CI\^D and then enter the correct address.
H h
-< )- |
The Output Energize key is pressed. Dashes are prompting you for an address.
: / 1 r 1 ; i V
:r:
V/ V... The address has been entered. This is the final instruction of rung 1.
ENTER aae End
/ The rung is entered into memory by pressing the ENTER key. The display
indicates that 882 words remain in memory.
Keys for
Rungs 2,3
S1E End
j Rungs 2 and 3 of the program are very similar to rung 1. Enter these rungs. At
the end of rung 3 the display should indicate 876 words remain in memory.
NEXT
and
LAST
keys
-][-
h 1 3
NEXT and LAST keys: You can review yourprogram with the NEXT and LAST
keys. Each time you press the NEXT or LAST key, the cursor moves to the
following or previous instruction in the program, indicating its address and
the rung number.
The first instruction of each rung is indicated by the rung Start symbol: j-
When you reach the first instruction of rung 3, the display at the left appears,
Chapter Using the Pocket Programmer
4-9
Display Symbols To guide you thru programming and monitoring procedures, various
abbreviations and symbols appear in the Address-Data and Rung Err-
Mode display areas of the pocket programmer. These abbreviations and
symbols are explained in Figure 4.7.
Figure 4.7
R Accumulated (AC) value, sequencers P R 5 5 Mode 6, Enter/Change Access Code
Rc Accumulated (AC) value, timers/counters Pr ->
s
Preset (PR) value, timers and counters
bn d Branch close P
r D
3 Mode 2, Program
b r Branch open
-
Shift right register
brP Breakpoint instruction r Rung
E Time-driven (Clock), sequencers r R c Reset Accumulated (RAC) value
L
U 1
1
_
JSelect time- or event-driven, sequencers r E - Remove
C L E r Mode 1, Clear Memory
L
L
L
U L
Remove force
C 5 c n Mode 5, Test-Continuous Scan rE r Remove rung
d Step data, sequencers rE P Remove faulty branch error
d IR3 Mode 9, Diagnostic Test * Programmer r E R d Mode 7, Load Program from E EPROM
d n E Done processing run Mode 3, Run
E Event-driven, sequencers, or Error
r u n g
Rung
- E L - Enter logic element 5 R U E Mode 6, Store Program in EEPROM
End End . E L E - I D D Start-up display
F Forced I/O 5 r c h Search
F R I L Failed internal test or password 55 c n Mode 4, Test-Single Scan
Fr.n
Firmware revision number 5bP Prompt for step number
3
r
P Group number, sequencers 5 u r E P : Sure you want to continue?
in r Insert rung USE Mask data, sequencers
m Insert EEL Zone Control Last State
L
Shift left register

Shift key in effect


Rcr Master Control Reset K Start of rung
nF Not found
Promptfordata
P Preset (PR) value, sequencers
4-10
Chapter Using the Pocket Programmer
Error Codes -SLC100 The error code numbers which may appear on the programmer display
and SLC 150 are defined in Figure 4.8. This information also appears on the back of
the pocket programmer.
Internal processor errors (codes 1-9) are those occurring in the processor
circuitry or the memory. When any of these errors occur, the "CPU
Fault LED on the processor unit will light, and all outputs will be
disabled.
Error codes 10-59 identify communication, expansion unit, EEPROM,
and programmer hardware problems (code 27 applies to SLC 150 only).
Programming errors (codes 60-67) are user errors indicating that you
have used an invalid procedure, entered incorrect or incomplete data,
etc. In most cases, the errors are easily understood and remedied;
occasionally, it may be necessary to review the proper keystroke
sequence for the particular programming operation you are attempting.
The procedure for correcting programming errors is to 1) read the error
description, 2) press the CANCEL CMD key, which returns the display
to the point it was at before the error was made, then 3) take corrective
action as determined by the nature of the error.
Figure 4.8
INTERNAL PROCESSOR ERRORS
1 thru 4 ; Processor hardware problem
5 thru 8 Processor memory problem
9 Processor scan time problem
10 thru 25
26
27
51
52
53 thru 59
Communication problem
Expansion unit problem
SLC 150 only. See Figure 4.9
EEPROM module problem
CAUTION - Program changes not saved in EEPROM module
Programmer hardware problem
PROGRAMMING ERRORS
60
61
62
63
64
65
66
67
Incomplete rung (no output instruction)
Invalid address for instruction
User memory exceeded
Instruction cannot be forced
Branch error (short circuit)
Branch error (incomplete branch)
Invalid access code
Rung too large
Chapter Using the Pocket Programmer
4-11
Error Codes -SLC150 Error codes 27-1, 27-2, and 27-5 are detected by the SLC 150 processor
only. If any of these error conditions occur, the pocket programmer will
initially display error code 27. You must then press the CANCEL CMD
key to display the -1, -2, or -5 suffix.
Figure 4.9
Chapter
Programming techniques
Relay- Type Instructions ;
Timer Instructions-----------
Counter Instructions
Timers with Long or Fine Time Base
J; -f. ^
#
- ^
v
MCff and ZCL4nstiuctiom-----------------
Sequencer Instructions
Special Sequencer Instruction Techniques
High Speed Input Programming
Shift Register Instruction
Special Internal Instructions
Program Editing
On-Line Data Control
Using the EEPRM Memory Module
Chapter Relay Type
Instructions
General Relay type instructions include Examine ON, Examine OFF, and
Output Energize instructions, already discussed in Chapters 3 and 4.
This chapter goes into further detail and also introduces you to the
Latch and Unlatch instructions (retentive output) and the Branch Open
and Branch Close instructions.
The figure below summarizes relay type instructions.
001
HI
Examine ON
001
016
Examine OFF Output Energize
: 016
-UH
Lateh
016
( U )
Unlatch
Numbers 001 ahd1)1afevethe symbols are instruction addresses.
An explanation ah^ listih^Of internal and external addresses you
can assign to these instructions appears on Pages 3-3 to 3-5.
H / I]: ;. \
Branch Open
. T
Branch Close
These i nstructions are used to program parallel paths of
conditional instructions within a rung. Addresses are not used.
Thp:symbbls U" indicate Branch Open and Branch Close on
the^proprarnmerJcey^ and ^C software display.
5-2
Chapter Relay Type Instructions
Examine ON,
Examine OFF,
Output Energize
These instructions were already explained (Pages 3-6, 3-7). A user
program applying them is shown in Figure 5.1. This figure shows a
hard-wired circuit and a user program which provides the same results.
Programmed instructions with addresses 733 and 734 are internal.
They do not represent external I/O devices. On the other hand,
instructions 001, 002, Oil, 012, and 013 represent limit switches LSI,
LS2, and pilot lights PLI, PL2, PL3.
You will note similarities between the hard-wired circuit and the user
program. Thus, when relay coil CRl in the hard-wired circuit is
energized, its normally open and normally closed contacts in rungs 3, 4,
and 5 operate, or change state. Similarly, when Output Energize
instruction 733 in the user program goes TRUE, its associated Examine
ON and Examine OFF instructions in rungs 3, 4, and 5 change their
TRUE/FALSE state.
In comparing the diagrams, you will also discover an apparent
contradiction. That is, normally open limit switch LSI and normally
closed limit switch LS2 are both represented in the program by an
Examine ON instruction. This makes sense when you consider that
rungs 1 and 2 must accomplish the same thing: The rung must be TRUE
when the external limit switch is closed, and FALSE when the limit
switch is open. Using an Examine ON instruction to represent the limit
switch satisfies these requirements. The N.O./N.C. mechanical action of
the switch is not a consideration.
Figure 5.1
Rung 1
Rung 2
Rung 3
Rung 4
Rung 5
Hard-wired circuit
Rung 1
Rung 2
Rung 3
Rung 4
Rung 5
001 733
733 734 oil
HHi--------------- ( >
733 734
on
AfcHI---------- < )
733 734
013
HHI---------- ( )
User program
limit switches LSI, LS2, and
pilot lights PL1, P12, and PL3
are represented in the user
* program by instructions 001,
002,011,012, and 013
* respectively. Note that both
the N.O. limit switch LSI and
the$IX. limit switch 1S2 are
v represented by Examine ON
instructions (001,002).
Chapter Relay Type Instructions
5-3
Equivalent User The function of the hard-wired circuit in Figure 5.1 can be achieved with
Programs another, simpler program-the 3-rung ladder diagram in Figure 5.2.
Again, instructions 001 and 002 represent limit switches LSI and LS2;
instructions Oil, 012, and 013 represent pilot lights PLI, PL2, and PL3.
The ladder diagram of Figure 5.2 does not use internal instructions to
represent hard-wired relays CR1 and CR2. Instead, instruction
addresses 001 and 002 are used repeatedly to obtain the logical
continuity equivalent to the electrical continuity of rungs 3, 4, and 5 of
the hard-wired circuit.
Figure 5.2
Hardwired circuit (from Figure 5.1)
001 002
,__I I___NJ
011
Rung l, *
I rk v /
1
<K.,
: Rung 2 <
001 002
, HI I I
012
t VI,
*
rK I I A r *
001 002
__I I____I I
013
f \______;
^ ;.
> i nUTly *5 '
i 11
\ r
*' Equivalent 3-rung user program.
(Compare this with the user
program in Figure 5.1.)
5-4
Chapter Relay Type Instructions
Unconditional
Output Energize
It is possible to enter a rung consisting of an Output Energize
instruction only. Since the rung lacks a condition instruction, the
output will be continuously TRUE. Although the unconditional Output
Energize has a few specialized applications, it is generally an
undesirable programming procedure which you should be careful to
avoid.
Branch Instructions These are used to create parallel paths of condition instructions,
allowing more than one set of conditions (OR logic) to establish
continuity in a rung. Figure 5.3 illustrates a branching condition. The
rung will be TRUE if either instruction 001 or instruction 002 is TRUE.
To program branch instructions with the pocket programmer:
1) Press the Branch Open key before entering the first instruction of
each parallel path.
2) Press the Branch Close key after entering the last instruction of the
last branch.
The ladder diagram of Figure 5.3 illustrates the use of branch
instructions. To program this rung, press the following keys:
- ----- \ A 1
'------
T
- j
Hh
1 T
f~"' 1
-___ ^
Hh
2 T
1---- 1
J
^ h ENTER
Figure 5.3
H
001
002
015
< M
y Two parallel paths
* for logic continuity
(OR logic).
Chapter
The Nested Branch
Relay Type Instructions
5-5
A nested branch (branch within a branch) cannot be programmed, but
you can program an equivalent branching condition. This is shown in
the figure below.
Figure 5.4
- Rung B, equivalent to rung A, can be programmed.
5-6
Chapter Relay Type Instructions
Output Latch, These retentive instructions are used as a pair at the same address.
Output Unlatch
When a rung containing an Output Latch instruction goes TRUE, the
Output Latch status bit is set to ON. The bit can only be turned OFF by
an Output Unlatch instruction located in a separate rung. This is
summarized in Figure 5.5.
The Latch/Unlatch instruction status is retained when you change from
the Run mode to another mode. Thus, in the example of Figure 5.5, if
you change from the Run mode to any other mode while status bit 015 is
ON, the external output device will be de-energized, but the status bit
will remain ON; when you return to the Run mode, the output device
will again be energized.
The Latch/Unlatch instruction status is also retained on power loss,
since the processor memory is provided with battery back-up.
Operation after CPU Faults: Latch instructions are reset to their
initial conditions after a CPU fault is detected (error codes 1 thru 9, 26,
and 51).
Figure 5.5
Output
Terminals
Latch Rung
HIII-----
Unlatch Rung
Programmed Rungs
09 Latch rung is TRUE; Status bit 015 is ON; Output device
is energized. ^
E Latch rung goes FALSE; Status bit 015 remains
ON; Output devicpremainVehergizeGl.
H3 Unlatch runggoes TRUE; Status bit OtSgoesOFF;
Output device is deenergized ,
0 Unlatch runggoesFLSE; Status bit T5 remains OFF;
Output device remains de-energized. ;
00 Latch runggoes TRUE; Statu s bit 015 goes ON ; Output
device is energized.
Timing Diagram
Chapter
Hold-In Rungs
- Operating Differences
Series A vs Series B
Relay Type Instructions
5-7
Figure 5.6 shows a typical hold-in rung, analogous to the familiar
electromechanical start-stop hold-in circuit. All versions of SLC 100 and
SLC 150 processor units will function as described. However, there are
two conditions under which there are operating differences. This is
pointed out in the table.
Figure 5.6
Oil
( )
A typical hold-in rung.
AH processor units:
When Examine ON instruction 001 goes
TRUE, output instruction 011 goes TRUE.
When instruction 001 subsequently
goes FALSE, output 011 remains TRUE,
being "held-in" by Examine ON
instruction 011.
Output 011 will go FALSE when Examine
OFF instruction 002 goes FALSE.
Event
Status of Non-Retentive Outputs in Hold-In Rungs
Series A SLC 150
Seres B SLC 150
and Series A,B,C SLC 100
Power is cycled from
Off to On.
Outputs return to
their last state.
Outputs are Off.
Processor is switched
from the Run mode
to any other oper
ating mode, then
switched back to the
Run mode.
Outputs return to their
last state. However, if
theRrogram mode was
entered and a program
change was made,
51

outputs will be Off.
Outputs are Off.
Chapter
RTO and RTF Timer
Characteristics
AC, PR, and RAC Values
Timer
Instructions
Timer instructions include the Retentive Timer On-Delay -(RTO)- and
the Retentive Timer Off-Delay -(RTF)-. Both require the use of the
Reset instruction -(RST)-. Timer instructions are represented by the
following symbols:
901
(RTO)------
PR 400.0
901
PR 400.0
Address: 901-932. Time base: 0.1 second. Range: 000.1 to 999.9 seconds.
Timers with long or fine time base: Special instructions can be used
for time delays beyond 999,9 seconds and for timers with greater
resolution than 0.1 second. Refer to Chapter 8.
6
I
The timer instruction functions as an internal "clock, counting
0.1-second intervals. The number of intervals counted is called the
Accumulated value (AC). Counting takes place under these
TRUE/FALSE rung conditions:
RTO Timer Rung Conditions
TRUE FALSE TRUE
Timer is
counting.
Counting
stops.
AC value
retained.
Counting
resumes.
AC value represents the cumulative
time during which rung is TRUE.
RTF Timer Rung Conditions
FALSE TRUE FALSE
Timer is
counting.
Counting
stops.
AC value
retained.
Counting
resumes.
AC value represents the cumulative
time during which rung is FALSE.
The clock figure below represents the AC value. The time delay is set by
programming a Preset value (PR). In this case, the PR value is set at
400.0 seconds.
The figure also shows a Reset Accumulated value (RAC) at 0000. This is
automatically set when you program the reset instruction. In most
cases, RAC is left at 0000, but you can change it to any value up to 9999.
If you program an RAC value, the time delay will equal PR minus RAC.
You will find that the programmer display does not show a decimal point
for RAC values. Thus, if you program PR to 30.8 and RAC to 105, the
time delay will be 30.8 minus 10.5 = 20.3 seconds.
RAC
6-2
Chapter Timer Instructions
Status and Overflow Bits The timer status bit has the same address as the timer instruction:
901 901
Hh Hh
The RTO status bit is set ON when the AC value reaches the PR value.
Examine ON instructions at the status bit address go TRUE; Examine
OFF instructions go FALSE.
The RTF status bit is set ON instantaneously when the RTF instruction
goes TRUE, and is set OFF when the AC value reaches the PR value.
Examine ON instructions at the status bit address go FALSE; Examine
OFF instructions go TRUE.
The overflow bit is given the timer address plus 50. (901 + 50 = 951):
The overflow bit is set to ON when the AC value "overflows from 999.9
to 0000. Examine ON instructions at the overflow bit address go TRUE;
Examine OFF instructions go FALSE. RTO and RTF status bits are not
affected when the AC value overflows.
951 951
Hh Hh
RAC 0000
When the RST instruction goes TRUE, status bits and overflow bits are
set to OFF, and the AC value is reset to the RAC value. The RST
instruction must go FALSE again before the timer can resume counting.
Chapter
Typical Timer Operation
Timer Instructions
6 3
The table below indicates how the status and overflow bits of timers
change state as the AC value increments from 1) the reset state
(AC = RAC), 2) up to and past the PR value, 3) beyond a value of 999.9
(overflow), and 4) back to the reset state.
Status Bit
901
Hh
1. Timer
Reset
AC * RAC
2. RTO Rung TRUE
or RTF Rung FALSE.
AC Value Increments
3. AC Value
Overflows Beyond
999.9
4. RST
Rung TRUE.
Timer Reset
RAC RAC RAC RAC RAC
Overflow Bit
951
Hh
0 0 00 0
(Examine ON
Instructions)
PR
AC<PR
PR
AC<PR
PR
AC > PR
PR
AC<PR
PR
AC > PR
PR
AC<PR
RTO Status Bit OFF OFF ON ON ON OFF
RTF Status Bit
OFF ON OFF OFF OFF OFF
Overflow Bits
OFF OFF OFF ON ON OFF
Power Down: The timer status is retentive. When you apply power
after a power-down, the AC value and ON/OFF states of status and
overflow bits will be the same as before the power-down. The status is
also retained when going from the Run mode to another mode.
Operation after CPU Faults: Timer instructions and associated
status bits and data values are reset to their initial conditions after a
CPU fault is detected (error codes 1 thru 9, 26, and 51).
Monitoring and Changing Data: PR and AC values can be monitored
and changed in the Run and Test modes. The PR value can be protected
from changes in the Run and Test modes by using the UNPRT/PRT key.
Refer to Page 15-9.
Chapter
6
Timer instructions
6-4
Retentive Timer As pointed out on Page 6-1, the AC value of the RTO timer increments
On-Delay (RTO) when the RTO rung is TRUE. This is illustrated in the figure below,
which shows an RTO timer ladder diagram and timing diagram.
For illustrative purposes, both Examine ON and Examine OFF
instructions are used at the timer status bit address, 901. These
instructions are used to energize output 015 and de-energize output 016
when the AC value reaches the programmed PR value.
The timing diagram illustrates the retentive nature of the timer, in
effect, the timer measures the cumulative periods during which the
timer rung (1) is TRUE. The AC value will continue to increment
during TRUE rung periods as long as the reset rung (4) remains FALSE.
On the count after 999.9, an overflow bit (not used here) is set ON and
the AC value continues to increment from 0000.
After the timer is reset and rung 1 goes TRUE again, the timing period
will begin at AC RAC. In most applications, the RAC value would be
0000. We chose to show a non-zero value for illustrative purposes.
Figure 6.1
.TRUE
Rung 1
Rung 2
Rung 3
Rung 4
001 901
4 I--------------------<
R
TO)-----
RTO Timer /%r
X
xx.x
Instruction
901 015
-<
1
Status Bit
Address 016
-44------------------------( y
Reset
instruction^ 901
-I I---------- --------- (RST)-------
RACyyyy
Ladder Diagram
Timing Diagram
Letters A to F at the bottom of the timing diagram
indicate the following events:
Examine OFF instruction 901 goes FALSE, making rung
3FALSE. The AC value continues to increment.
A. Rung 1 goes TRUE. The AC value increments,
beginning at AC = RAC. Examine ON instruction901
in rung 2 is FALSE. Examine OFF instruction 901 in
rung 3 is TRUE.
8. Rung 1 goes FALSE. The AC value stops incrementing,
but the existing value is retained.
C. Rung 1 goes TRUE. The AC value continues to
increment from the point it left off.
D. TheAC value has reached the PR value. Examine ON
instruction 901 goes TRUE, making rung 2 TRUE.
E. Rung 1 goes FALSE. The AC value stops incrementing,
but the existing value is retained. Rung2remains
TRUE. Rung 3 remains FALSE.
F. Rung 4 goesTRUE. The AC value is reset to the
programmed RAC value. Examine ON instruction 901
goes FALSE, making rung 2 FALSE. Examine OFF
instruction 901 goes TRUE, making rung 3 TRUE.
While the RST instruction is TRUE, the timer is
disabled. Timing can resume when rung 4 goes FALSE
again.
6
Timer Instructions Chapter
6-5
Retentive Timer The essential difference between the RTO and RTF timers is that with
Off-Delay (RTF) the RTF timer, the AC value increments when the timer rung goes
FALSE rather than TRUE.
Figure 6.2 shows an RTF timer ladder diagram and the corresponding
timing diagram. For illustrative purposes, both Examine ON and
Examine OFF instructions are used at the timer status bit address, 901.
These instructions are used to de-energize output 015 and energize
output 016 when the AC value reaches the programmed PR value.
Here again, the timing diagram illustrates the retentive nature of the
timer. After rung 1 makes a TRUE-FALSE transition, the timer
measures the cumulative periods during which rung 1 is FALSE. The
AC value will continue to increment during FALSE rung periods as long
as the reset rung (4) remains FALSE. On the count after 999.9, an
overflow bit (not used here) is set ON and the AC value continues to
increment from 0000.
Figure 6.2
F. The AC value has reached the PR value. Examine ON
instruction 901 goes FALSE, making rung 2 FALSE.
Examirie-OFF instruction $01goes TRUE, making rung
3 TRUE. The AC value continues to increment. ^
Letters A to G at the bottom of the timing diagram
indicate the following events:
A. The timer is reset, with AC = RAC. Rung 1 is FALSE.
Examine ON instruction 901 in rung 2 is FALSE.
Examine OFF instruction 901 in rung 3 is TRUE.
B. Rung 1 goes TRUE. Instantaneously, Examine ON
instruction 901 goes TRUE and Examine OFF
instruction 901 goes FALSE, making rung 2 TRUE and
, rung 3 FALSE. - . ; \ '
C. Rung 1 goes FALSE. The AC value begins to increment.
D. Rung 1 goes TRUE. The AC value stops incrementing
but the existing value is retained.
G. Rung 4 goes TRUE. The AC value is reset to the RAC
valiue. Jcte thaithisisthe me situation as O^ent A,
; with the Examine ON instruction 901 FALSE and the
Examine OF| instruction 9&1 TRUE. , *
While thetRST iristrdction is- TRVJE, the tinier is
disabled. After the RST instruction goes FALSE and
rung 1 niakesa TRUE to FALSE transition, the timing
period will begin at AC = RAC.
E. Rung 1 goes F ALSE. The AC value continues to
increment from the point it left off.
6
Timer Instructions
6-6
Chapter
Timing Beyond 999.9 Special instructions at addresses 874 and 875 have time bases of 0.5 and
Seconds 1.0 seconds, allowing you to program the equivalent of an RTO timer
with time delays beyond 999.9 seconds. This is discussed in Chapter 8.
You can also use the instructions discussed in this chapter to obtain time
delays beyond 999.9 seconds. An example is shown below, where the
overflow bit of one RTO timer initiates a second RTO timer to produce
an output at 1400 seconds.
Timer 901 in rung 1 is used for the first part of the timing period and
timer 902 in rung 2 is used for the last part. The Examine ON
instruction 001 of rung 1 is repeated in rung 2, so that if timing is
interrupted during the last part of the timing period, the AC value will
stop incrementing, preventing an output in rung 3.
Figure 6.3
Rung 1
001
r ' I |
v 901
I
IRTO)-------
PR 0000
Rung 2 '
001 951
902
1
1 1 1 I
\ RTO)
PR 400.0
Ritnn ^ i
902
r
I | ^
015
l V ,,
(vUfiy j '
V ) "
Rung 4 j
002
. I I
901
1
1 I
-A. RST)--- "
RAC 0000
Rung 5
;
" 002 ; : :
r
, i I ;
902
f ['TTY. - . . . . I
1 1 -.
RAC 0000
Ladder Diagram
Letters A to Eat the bottom of the timing diagram
indicate the following events;:
A. Examine ON instructions 001 in rungs land 2 go TRUE:
Rung 1 goes TRUE. AC value of timer 901-increments
from 0000.. - * -
B. AC value of timer 901 overflows beyond 999.9, setting
the overflow bit (address^SI) pN
r
; Examme ON
instruction 951 In rung 2 goes TRUE, matting rung 2
. TRUE. AC value of timer 902 increments from 0000.
1000 seconds have elapsed. ~
C. AC value of timer 902 reaches programmed PR value
TRUE
of 400.0, setting the status bit (address 902) ON.
Examine ON instruction 902 in rung 3 goes TRUE,
making rung 3 TRUE.
Total time elapsed: 1000 + 400 = 1400 seconds.
D. Instructions 001 in rungs 1 and 2 go FALSE, making
rungs 1 and2 FALSE. Rung3 remains TRUE.
E. Reset rungs 4 and 5 go TRUE. Examine ON instructions
902 and 9S1 go FALSE. AC values are reset to 0000.
While the RST instructions are TRUE, the timer is
disabled. Timing can resume when rungs 4 and 5 go
FALSE again.
Chapter
Timer Keystroke
Example
Timer instructions
6-7
Program this basic RTO timer. After youve programmed it, you may
want to use the NEXT and LAST keys to review your work.
Figure 6.4
Keystroke Example - RTO Instruction
AA1
Rung 1
RAC 10
; IE- A ;
Prompt for an address.
1 ;
-3 [-;
Uv-i
: :: :
I
Address 001 is entered.
-(RTO)- -(RTO)- ' : -, I
:
Prompt for an address.
9, 0, 1 -(RTO)- go I: ; i Address 901 s entered.
ENTER -(RTO)- ; Pr V
Prompt for a preset (PR) value.
3,0,0,0 -(RTO)- 300. 0 Pr PR value of 300.0 seconds is entered.
ENTER BB3 End :
This completes rung 1.
-It- ;-iv
Prompt for an address.
9, 0, 1 -IE- go i e
Address 901 is entered.
H )- -( )- ; 2
Prom pt for an address.
1,1 -( )- __ I I ^
Address 011 Is entered
ENTER OBI End
This completes rung 2. -
- I E- -3I-
- : 3:
Prompt for an address. A
2 iir
u
L
U
Address 002 is entered.
SHIFT -] E-
3,
The SHIFT key must be pressed before
you press the -(RST)- key. The dot to
the right of the rung number indi
cates you have pressed the SHIFT key.
-<RST)- -(RST)- ; 3 -
Prompt for an address.
9,0,1 -(RST)- go i g
Address 901 is entered.
ENTER -(RST)- _____0 rflc
The display indicates that the RAC
value is set to zero You can override
this by entering an RAC value.
1,0 -(RST)-
__ 0 r Rc
The RAC value s specified as 10 For
timers, the actual RAC value is 0.1
of the value displayed (in this case
it is 1 0, not 10) The time delay
(PR-RAC) is set at 300.0-1.0 = 299 0
seconds.
ENTER BI B End
End of program.
Chapterj
6
Timer instructions
6-8
Programming an RTF Timer Figure 6.4 can be easily converted to an RTF timer keystroke example.
Just change the RTO instruction in the ladder diagram to an RTF
instruction. Then, instead of pressing the -(RTO)- key in rung 1, press
the SHIFT key and the -(RTF)- key.
Chapter
CTU and CTD Counter
Characteristics
AC, PR, and RAC
Values
Counter
Instructions
Counter instructions include the Up Counter-(CTU)- and the Down
Counter -(CTD)-. Both are retentive, requiring the use of the Reset
instruction-(RST)-. Counter instructions are represented by the
following symbols:
901 901
(CTU)--------- (CTD)-----------------
PR 1000 PR 1000
Address: 901-932. Internal. Range: 1 to 9999 counts.
Counter instructions count successive FALSE-to-TRUE transitions of
the rung containing the counter instruction. After each count, the rung
must return to FALSE before another count can take place.
The existing count is called the Accumulated value (AC). For up
counters, the AC value increases by 1 for each FALSE-TRUE transition.
For down counters, the AC value decreases by 1 for each FALSE-TRUE
transition.
Up-down counters have both an up counter rung and a down counter
rung. Accordingly, the AC value both increases and decreases,
responding to FALSE-TRUE transitions in both rungs.
The clock figure below represents the AC value. An output can be
obtained at a particular count by programming a Preset value (PR). In
this case, the PR value is set at 1000.
The figure also shows a Reset Accumulated value (RAC) at 0000. This is
automatically set when you program the reset instruction. You can
either leave it at 0000, or change it to any value up to 9999.
RAC
7-2
Chapter Counter instructions
Setting a Counter
Status and
Overflow!Underflow Bits
Reset Instruction
Up counters can be reset to begin counting at AC RAC and produce an
output at AC = PR. To obtain an output at 1000 counts, just set the PR
value to 1000. Or, since RAC can be programmed to any value, you
might set the PR value at 1500 and the RAC value at 0500, etc.
Up-down counters add and subtract counts, starting at AC = RAC, and
produce an output at AC = PR. Thus, if you set RAC at 500 and PR at
1500, an output will be produced whenever the up counts exceed the
down counts by 1000.
The counter status bit has the same address as the counter instruction:
901 901

I \~ Hr
-
The status bit is set ON when the AC value reaches the PR value.
Examine ON instructions at the status bit address go TRUE; Examine
OFF instructions go FALSE.
Overflow and underflow bits are assigned the counter address plus 50.
(901 + 50 = 951):
951 951
I \
The overflow bit is set ON when the AC value "overflows from a count
of 9999 to 0000. The underflow bit is set ON when the AC value "under
flows from 0000 to 9999. Examine ON instructions at the overflow/
underflow bit address go TRUE; Examine OFF instructions go FALSE.
CTU status bits are not affected when the AC value overflows. CTD
status bits will be set ON if the AC value underflows making AC > PR.
The reset (RST) instruction is given the same address as the counter
instruction:
RAC 0000
When the RST instruction goes TRUE, the status, overflow, and under
flow bits are reset to OFF, and the AC value is reset to the RAC value.
The RST instruction must go FALSE again before counting can resume.
Chapter Counter Instructions
7-3
Typical Up Counter
Operation
The table below indicates how the status and overflow bits of counters
change state as the AC value increments from 1) the reset state
(AC = RAC), 2) up to and past the PR value, 3) beyond a value of 9999
(overflow), and 4) back to the reset state.
Power Down: The counter status is retentive. When you apply power
after a power-down, the AC value and the ON/OFF states of status and
overflow/underflow bits will be the same as before power-down. The
status is also retained when going from the Run mode to another mode.
Operation after CPU Faults: Counter instructions and associated
status bits and data values are reset to their initial conditions after a
CPU fault is detected (error codes 1 thru 9, 26, and 51).
Monitoring and Changing Data: PR and AC values can be monitored
and changed in the Run and Test modes. The PR value can be protected
from changes in the Run and Test modes by using the UNPRT/PRT key.
Refer to Page 15-9.
7-4
Chapter Counter Instructions
Up Counter (CTU) As pointed out on Page 7-1, the AC value of the CTU counter increases
by one for each FALSE-to-TRUE transition occurring in the CTU
counter rung. This is illustrated in Figure 7.1, which shows a CTU
counter ladder diagram and the corresponding timing diagram.
For illustrative purposes, both Examine ON and Examine OFF
instructions are used at the counter status bit address, 901. These
instructions are used to energize output 015 and de-energize output 016
when the AC value reaches the PR value.
Figure 7.1
Letters A to E at the bottom of the timing diagram indicate
the following events:
A* The AC value equals the RAC value. Rung 1 is FALSE. ;
Examine ON instruction901 in rung 2 is FALSE.
Examine OFFinrtructign9dl in rudg 3 is TRUE-
IB. Rung 1 goes from FALSE to TRUE, causing the AC value
to increase by one. The rung then returns to FALSE.
This cycle repeats again and again, wfth the AC value
increasing by one count for each FALSE-TRUE
transition. . -
i C. The AC value has reached the programmed PR value.
Examine ON instruction 901 goes TRUE, making rung 2
TRUE:; {Examine OFF instruction901 goes FALSE,
making rung 3 FALSE.
D. The AC value continues to increase for each FALSE-
TRUE transition of rung 1. Rung 2 remains TRUE. Rung
3 remains FALSE.
E. Rung 4 goes TRUE. The AC value is reset to the
programmed RAC vale. Examine ON instruction 901
goes FALSE, making rung 2 FALSE. Examine OFF
instruction 901 goes TRUE, making rung 3 TRUE.
If the counter is not reset as done in event E, the AC value
continues to increase for FALSE-TRUE counter rung
transitions. On the count after 9999, an overflow bit is set
ON and the AC value continues to increment from 0000.
VVhtle the RST instruction iS TRUE, the counter is
disabled. Counting can resume when rung 4 goes
FALSE again;
Chapter
Keystroke Example
Counter Instructions
7-5
Program this basic CTU counter. The programming steps are quite
similar to those of the RTO timer example of Figure 6.4.
Figure 7.2
Keystroke Example - CTU lnstructic
. : ;; U
001
.. 9oi
R
Un
9 ^ [ l ; . . ' " : ' (CTU) .
1
' -V; v
:
; ; V': * . : . pr 3000
:
. / ~ ~ 901 ; on
; .
5
Rung 2 <-------1|---------- ( , }h
oo2
;
; 901
Rung 3 ---- 1 |--------- (RST)---
RAG 10
5
>n
staw BSM mm
Promp
1
-H- __ I I
Address 001 is entered.
-(CTU)- -(CTU)- , ______ |
: Prompt for an address.
9, 0, 1 -(CTU)- i 90 I l
I
; Address 901,isentered.
ENTER -(CTU)- ______ Pr
Prompt for a preset.(PR) value.
3,0,0,0 -(CTU)- 3BQQ P r PR value of 3000 is entered.
ENTER BB3 End
This completes rung 1.
-][- E Prompt for an address.
9 0, 1 30 l E
Address 901 is entered.
-( h ~( >- E:
Prompt for an address.
1,1 -( )- _ M E
Address 011 is entered. ~
ENTER BB l End
This completes rung 2.
-][- -] [-
3
Prompt for an address. ^
2 -It-
__ E 3 Address 002 is entered. '
SHIFT
.
-_E 3.
The SHIFT key must be pressed before
you press the-(RST)~:key: The dot to ;
the right of the rung numberihdi--1.
cates you have pressed the SHIFT key.
-(RST)- -(RST)- 3
Prompt for an address.
9,0,1 -(RST)- : 30 l 3 I
Address901 isenteredi !
ENTER -(RST)- ____0 r fl c
The display indicates that the RAC
value is.set-to zero. You can override
this by entering an RAC vaiue.
1,0 -(RST)-
_ _ 10 r R c
The RAC value of 10 is entered. The
count (PR - RAC) is 3000 -10 = 2990.
ENTER BIB End
End of program.
Chapter Counter Instructions
7 6
Up-Down Counter This counter includes a CTU instruction and a CTD instruction which
share the same address (including status and overflow/underflow
addresses). AC, PR, and RAC values are also shared. This is illustrated
in Figure 7.3, which shows an up-down counter programmed to produce
two outputs:
The first output is energized when the AC value reaches 9000, then de
energized when the AC value overflows beyond 9999. In terms of counts,
this output is energized only when the net count (up counts minus down
counts) is within the range of 3000 to 3999.
The second output is energized when the AC value overflows beyond
9999, that is, when the net count is 4000 or more.
We are assuming that the AC value does not underflow below 0000.
Figure 7.3
Rung 1
Rung 2
Rung 3
Rung 4
Rung 5
Timing Diagram
D. Rung 1 is up counting, and the AC value has reached the
PR value of 9000. Examine
0N
instruction 901 goes TRUE,
making rung 3 TRUE. The net count is 3000 again.
E. The AC value overflows beyond 9999, setting the
overflow bit (address 951) ON. Examine ON instruction
^51 in rung 4 goes TRUE, making rung 4 TRUE. Examine
OFF instruction 951 in rung3 goes FALSE, making rung 3
FALSE. The net count is 4000.
F. Rung 5 goes TRU E. The AC value is reset to the
programmed RAC value of 6000. Status bit and overflow
bit are reset to OFF. Rung 4 goes FALSE.
While the RST instruction is TRUE, the counter is
disabled: Counting can resume when rung 5 goes
FALSE again.
Letters A to F at the bottom of the timing diagram indicate
the following events:
A. CTU counter in rung 1 begins a series of up counts,
beginning at AC = RAC = 6000. Examine ON instruction
901 in rung3t$ FALSE. Examine OFF instruction 951 in
rung 3 is TRUE. Examine ON instruction 951 in rung 4 is
FALSE.
B. The AC value has reached the programmed PR value of
9000, setting the status bit (address 901 ) ON. Examine ,
ON instruction 901 in rung 3 goes TRUE, making rung3
TRUE. The net count is 3000.
C. CTD counter in rung 2 is down counting. The AC value is
now less than the PR value of 9000. Examine ON instruc
tion 901 in rung 3 goes FALSE, making rung 3 FALSE. The
net count has dropped below 3000.
Up Counts Up Counts
001
002
901
951
951
-^Hr
003
901
(CTU)----
PR 9000
901
-(CTD)
PR 9000
015
016
( H
901
(R ST)
RAC 6000
Ladder Diagram
AC a RAG
B CD E F
Chapter Counter Instructions
7-7
Counting
Beyond 9999
When it is necessary to count beyond 9999, one way of accomplishing it
is by programming the counter shown in Figure 7.4.
The overflow bit of counter 901 initiates a single count in counter 902 at
a count of 10,000. Status bits of both counters are programmed in series
to produce an output when an additional 3000 counts are made by
counter 901.
Figure 7.4
001 901
Rung 1
Rung 2
Rung 3
Rung 4
Rung 5
Rung 6
RAC 0000
Ladder Diagram
4 l--------------------------- (CTU>
PR 3000
951 902
H H--------------- (CTU)
PR 0001
951
I I .....................
901
I !
901 902
it t !
/ '
RAC 0000
015
Il II
002
I |
901
! I
002
- \RSTJ
RAC 0000
902
{RST) '
Letters A to E at the bottom of the timing diagram indicate *
the following events:
A. Counter 901 begins a series of counts, beginning at *
AC = RAC=0000. instructions 951 in rungs 2 and 3 are *
FALSE. Examine ON instructions 901 and 902 in rung 4
are FALSE.
B. The AC value has readied counter 901 PR value of 3000.
Examine ON instruction 901 in rung 4 goes TRUE ^but^.* ^
rung 4 remains FALSE.
C. The AC value of counter 901 overflows beyond 9999, *
setting the overflow bit (address 951) ON. This causes ^
the following:
Examine ON instruction 951 in rung 3 goes TRUE, *
^esettingcounter901. Examine ON instruction,9Qt in *
rung 4 goes FALSE; Examine ON instruction 951 in rung 3
goes FALSE; Counter 901 continues to count from 0000.
* Simultaneously, Examine ON instruction 951 in rung 2 has
gone TRUE, then FALSE, causing the AC value of counter
902 to go from 0000to the PR value of 0001. Examine ON
instruction 902 in rung 4 goes TRUE. 10,000 counts have
occurred.
D. The AC value of counter 901 has again reached the PR
* value of 3000. Examine ON instruction 901 in rung4 goes
TRUE, making rung 4 TRUE. 13,000 counts have occurred,
s E. Rungs 5 and 6 go TRUE. The AC values of both counters
* are reset to the RAO value* Status bits and overflow bits
are reset to OFF. Rung 4 goes FALSE.
r* While the RST instructions are TRUE, the counter is
disabled. Counting can resume when rungs 5 and 6 go
FALSE again.
Chapter Timers with Long or
Fine Time Base
General Timers using the long time base and fine time base instructions have the
following applications:
Long time base instructions
Time basesof 0.5 sec and 1.0 sec. These instructions allow you to
program counter-type timers with long time delays, up to 9999
seconds.
With SLC 150 processor unit Catalog Nos. 1745-LP151 and 1745-
LP152, the 1.0 sec time base is derived from the AC line frequency,
useful in "real time clock applications.
Fine time base instructions
Choice of 4 time bases plus the scan rate time base. Allows you to
program timers with greater resolution than the 0.1 sec provided by
the standard timers.
Long time base and fine time base timers use a standard up counter
instruction with a special examine instruction representing the time
base. This provides the equivalence of an RTO timer. An example
appears in Figure 8.1.
Figure 8.1
8 8-2
Chapter Timers with Long or Fine Time Base
Long Time
Base Instruction
Long time base instructions can be used with SLC 100 and SLC 150
processor units at addresses 874 and 875. This is summarized below.
Figure 8.2
Long Time Base Instructions -All SLC 100 Processors
Internal Address Time Increment in seconds
874 0.5 sec. Based on microprocessor clock
875 1.0 sec. Based on microprocessor dock
Long Time Base Instructions - SLC 150 Processor
Processor Unit
Internal
Address
Time Increment in seconds
All AC and DC versions 874 0.5 sec. Based on microprocessor clock
OC versions; Catalog Nos.
1745-LP153, -LP154
875 1.0 sec. Based on microprocessor clock ;
AC versions,Catalog Nos.
1745-LP151, -LP152:
875 1.0 sec. Based on AC line frequency
Not: You do not have to measure your scan time in applying these instructions.
The timer in Figure 8.3 illustrates how the long time base instruction
can be used. When instruction 006 in rung 1 is TRUE, Examine ON
instruction 875 pulses ON and OFF, incrementing the AC value of
counter 901. This provides the equivalence of an RTO timer.
Instruction 875 has a time base of 1.0 second. If an AC powered SLC 150
processor is used, timing will be synchronized with the AC line
frequency.
Figure 8.3
This instruction
initiates timing
Rung 1
\
006
Rung 3
875
901
007
Long time base instruction.
Time increment of
1.0 second.
901
-(ciuH:
PR 0060
013
901
-<RST) *
RAC 0000
long time basetimer.
Preset (PR) of 60
provides a 60 sec
: time delay -
(60 x 1.0 sec).
Chapter
Fine Time
Base instruction
Timers with Long or Fine Time Base
8-3
The fine time base instruction allows you to program timers with
greater resolution than the 0.1 sec provided by the standard timers.
The special internal addresses and corresponding time increments
(resolution) are indicated in Figure 8.4 (upper table). To use these
addresses, you must first measure the scan time of your program, then
refer to the lower table of Figure 8.4 and choose an address compatible
with your application needs and the measured scan time.
For proper operation, do not use an address number lower (shorter time
increment) than the lowest specified for your particular scan time.
Exception: You can always use address 869, which pulses ON and OFF
in time with your scan. This provides a time increment equal to twice
your scan time. But keep in mind that the scan time of a particular
program can vary, and the time increment using address 869 will vary
accordingly.
Caution: If you are using the Zero-Cross Turn-On instruction in
your program, your scan time will be 8.3 msec (or some multiple of 8.3
msec) at 60 Hz, and 10 msec (or some multiple of 10 msec) at 50 Hz.
This will be a deciding factor when applying the instructions listed in
Figure 8.4.
Figure 8.4
Internal Addresses and Corresponding Time
Increments (Resolution)
internal
Address
Tim Increment in Milliseconds
SLC 100 SLC 150
869 Scan rate Scan rate
870 10 10
871 20 20
872 40 50
873 80 100
Acceptable Addresses i
for your Measured Scan Time
Measured Scan
Time in Milliseconds
; Acceptable
Addresses
SLC 100 SLC 150
Less than 5.0
5.0 to 9.9
10.0 to 19.9
20.0 to 39.9
Less than 5.
5.0 to 9.9
10.0 to 29.9
30.0 to 49.9
870.871.872,873
871,872.873
872,873
873
Any value
lessfHaiHpO
Any value
ls$ than 100
869
8
8-4
Chapter Timers with Long or Fine Time Base
Procedure for Using the Add the required fine time base timers to your program. An example
Fine Time Base Instruction appears in Figure 8.5 below. Since you do not as yet know the scan time
of your program, use any of the special internal addresses, and leave the
counter PR value at 0000.
Figure 8.5
Scan Time Measurement:
1. Add the following two rungs to the end of your program:
Figure 8.6
869
931
Rung 1
------------- (CTU)
\ - ' PR 0500
931
932
Rung 2
----------------
-- ----------- {rto)
PR 0000
Rungsfor scan time measurement.
Chapter
Procedure for Using the
Fine Time Base Instruction
(continued)
Timers with Long or Fine Time Base
8-5
2. Enter the Test-Continuous Scan mode (5), then immediately turn off
the programmer (measurement will be more accurate if the
programmer is off).
3. RTO 932 will measure the time it takes to perform 1000 scans. For a
typical SLC 100 program, this would be 15 seconds (15 milliseconds x
1000); for the SLC 150, it would be 4 seconds (4 milliseconds x 1000).
Leave the programmer off long enough to assure that scan time
measurement is complete (2 minutes would be a safe off time). Now
turn the programmer back on and monitor the AC value of the RTO
instruction at address 932.
4. Take note of the final AC value displayed. Subtract 1.0 millisecond
from this value (0.5 millisecond is added to your program by the scan
time measurement rungs and another 0.5 millisecond is added
because of Test mode sub-routines). The resultant is the scan time of
your program, measured in milliseconds.
Note: Your scan time will vary. Some conditions which increase scan
time:
The pocket programmer is turned On.
The TCAT is connected.
Input pulses to an HSI module are being counted (SLC 150 only).
User program instructions are currently being executed.
We recommend that you take several scan time measurements, under
various conditions. This will give you an understanding of scan time
variance for your application. When you repeat the scan time
measurement, you must first reset counter 931 and timer 932 to zero.
5. Delete the scan time measurement rungs (Figure 8.6).
You can now change the address of the fine time base instruction to an
address compatible with Figure 8.4 (lower table) on Page 8-3.
Now set the PR value of the up counter. The time delay in milliseconds
will be the PR value multiplied by the time increment specified for the
special internal address you selected. In the example of Figure 8.5,
address 870 and a PR value of 5 are used, providing a time delay of 50
milliseconds (5 x 10 milliseconds). If you select address 869, the time
delay in milliseconds will be your PR value times twice your measured
scan rate.
Chapter
MCR and ZCL
Instruction
Characteristics
MCR and ZCL
Instructions
The following are special relay-type instructions.
Master Control Reset -(MCR)- (No address required) .
Zone Control Last State -(ZCL)- (No address required).
Figure 9.1a illustrates MCR and ZCL zones. Note that a zone begins
with a start rung and ends with an end rung. The MCR and ZCL
instructions are outputs in these rungs, and do not require an address.
The start rung contains the condition instructions which control the
zone. The end rung contains the MCR or ZCL instruction only. Any
number of rungs can be programmed between the start and end rungs.
When the start rung is TRUE, output instructions in the zone function
normally. When the start rung goes FALSE, non-retentive outputs
within an MCR zone are de-energized; non-retentive outputs in a ZCL
zone remain in their last state. The effect on non-retentive and
retentive instructions is summarized in Figure 9.1a.
Multiple MCR and ZCL zones can be programmed. With the SLC 150,
ZCL zones can be nested (Page 9-4). MCR zones should not be nested.
Figure 9.1a
HIIH
HI ---------
H
H
Hhlh
Hh
Hh
Hh
Ah
{MCR)-------" Start rung,
< )-
-< y
1
When MCR start
rung is FALSE,
non-retentive
outputs are de
energized.
(MCR)---- ~ Uncond tionai
end rung.
-(zee) Start rung.
-i H-
< y
-< h-
-(zci)" -
When ZCL start
rung is FALSE, all
outputs remain
in their last
state.
Unconditional
end rung.
* Instruction
MCR Zone Start
Rung FALSE
ZCL Zone Start
Rung FALSE
Non-Retentive
Outputs
Oe-energized
Remain in
last state
Latch/Unlatch , Remain in last state
Counters,
RTO Timers
AC value stops incrementing, value
retained. Status, overflow, and
underflow bits remain in last state.
RTF Timers*
AC value
increments :
AC value stops
incrementing,
value retained.
Status, overflow,
and underflow bits
remain in last
state.
Sequencers
AC value stops incrementing, value
retained. Step number retained. Bit
addresses remain in lest state.
Reset Remains in last state
Shift Register
Outputs
disabled.
Outputs remain
in last state.
Shifting
disabled. ;
Shifting disabled.
* CAUTION Since the RTF timer runs inside of a FALSE
MCR zone, its accumulator, status, and overflow bits
could change state while an MCR zone is FALSE. This
could affect other outputs in your program.
Chapter
9
IMCRandZCL Instructions
9-2
MCR and ZCL instruction
Characteristics
(continued)
Figure 9. lb lists additional operating characteristics of non-retentive
outputs inside a ZCL zone.
Figure 9.1b
Thetable below applies for either of the following conditions:
1. ZCL zone is FALSE. Non-retentive outputs inside ZCL zone are
being held in last state.
2; ZCL zone is either TRUE or FALSE. Non-retentive output instruction
inside ZCLzone isbeing held ON by a hold-in rung.
Event
Status of Outputs Within ZCL Zone, ^
SLC100 Series A, B,C
and SLC150 Series A
SLC 150
Series B
* Power is cycled from
Off to On.
Outputs return to
their last state.
Outputs
turned Off.
Processor is switched
from the Run mode to
any other operating
mode, then switched
back to the Run mode.
Outputs return to their last
state. However, if the
* Program mode was entered ^
and a^programchange was
made, outputs wilt be Off.
Outputs
turned Off. j
Chapter
9
MCR and ZCL Instructions
ZCL Zones Using the
Same Outputs
9 3
You may use two or more ZCL zones in your program. Multiple ZCL
zones allow you to use the same output instruction several times in your
program without experiencing contention between them. Figure 9.2
shows how this works.
If zone control were not included in Figure 9.2, the output instruction
that appears last in the program would govern the state of the external
output; using multiple zones avoids this. To avoid contention between
the output instructions, only one ZCL zone should be TRUE at a time.
Figure 9.2
Zone
A
Zone
B
Control of Output 011
TRUE FALSE
Output 011 is controlled by instruction 002 in
zone A. Zone B is bypassed in the program scan
and therefore has n effect.
FALSE FALSE
When zone A goes FALSE; output 011 remains in
its last state. Both zones are hwbypassed in
the program scan. ; '
FALSE TRUE
When zone B goes TRUE, output 011 is now
controlled by instruction 004 in zone 8; Zone A is
FALSE and has no effect.
TRUE TRUE
In this case, output 011 is controlled by instruc
tion 004 in Zone 8. This is because zne B is
scanned after zone A and therefore takes
precedence.
9
MCR and ZCL Instructions
9-4
Chapter
Nesting ZCL Zones SLC 100: You cannot nest ZCL zones (place one zone within another)
with the SLC 100 processor unit. It will produce undesired results.
SLC 150: Up to eight ZCL zones can be nested together. Figure 9.3
illustrates three nested zones. Note that each zone has a conditional
start rung and an unconditional end rung. ZCL zone A controls outputs
in programs A, B, and C. Zone B controls outputs in programs B and C.
Zone C controls outputs in program C.
An outer zone must be TRUE in order for internal zones to control their
outputs. If an outer zone is FALSE, all outputs within internal zones are
held in their last state, regardless of the rung conditions of the internal
zones.
Error code 27-5: If ZCL zones are nested deeper than eight zones, or if
each start rung is not accompanied by an end rung, a processor fault will
occur and error code 27-5 will be displayed on the pocket programmer.
This prompts you to correct the condition.
Figure 9.3
Program
A
Program
B
Zone
; : . "
NestedZones.Possiblewiththe SLC 150 only.
Chapter
MCR andZCL Instructions
vs a Master Control Relay
MCR and ZCL Instructions
9-5
In some respects, the function of MCR and ZCL instructions is similar to
a hard-wired master control relay of a relay system, which can be wired
to control the overall function of several operations, based on certain
necessary conditions. An important distinction must be made, however:
The master control relay is a safety device, providing Emergency Stop
capability to the controller operator; with MCR and ZCL instructions,
this is not the case.
We strongly recommend that you install a hard-wired master control
relay to provide emergency I/O power shut-down. Refer to Pages 19-4
and 19-5 for wiring details.
Chapter Sequencer
Instructions
SQO and SQI
Sequencer
Characteristics
Sequencer instructions include the Sequencer Output -(SQO)- and the
Sequencer Input -(SQI)-. Both are retentive, requiring the use of the
Reset instruction. You will find that sequencer instructions will be
easier to understand if you first become familiar with timer and counter
instructions.
Sequencer instructions are represented by the following symbols:
901 901
(SQO)------ ---- (SQI)-----
Address: 901-932 (internal). 100 steps maximum.
High Speed Input Module Applications (SLC 150 only): Sequencer
Output instructions at addresses 901, 902, 903, and 904 are used in
programming high speed input modules. Refer to Chapter 12 for
programming details.
If you are not using high speed input modules, addresses 901,902, 903,
and 904 can be used for standard timer, counter, and sequencer
programming.
Time- Or Event-Driven Sequencers can be time-driven or event-driven. Operation involves an
Accumulated value (AC) and a Preset value (PR).
Time-driven sequencers count 0.1-second intervals while the sequencer
rung is TRUE. When the AC value reaches the PR value, the sequencer
advances to the next step and the AC value increments from 0000 again.
After the final step, the sequencer continues with step 0.
Event-driven sequencers count FALSE-TRUE transitions of the
sequencer rung. When the AC value reaches the PR value, the
sequencer advances to the next step and the AC value increments from
0000 again. After the final step, the sequencer continues with step 0.
The Sequencer Output (SQO) instruction sets the ON/OFF status of up
to 8 bit addresses for each step. This group of bit addresses can be
selected as either 6 external output addresses plus 2 internal addresses,
or as 8 internal addresses.
The Sequencer Input (SQI) instruction examines the ON/OFF status of
up to 8 bit addresses for each step, setting an input-satisfied status bit
ON when the status of the bit addresses matches programmed data. The
group of bit addresses can be selected as either external input addresses
or internal addresses.
10-2
Chapter Sequencer Instructions
StdtUS and The SQI sequencer input-satisfied status bit and the SQO sequencer step
Completion Bits completion bit use the sequencer instruction address:
901 901
HI Hr
The SQI input-satisfied status bit is set ON when the ON/OFF status of
the bit addresses matches the programmed data for the current step.
The SQO step completion bit is set ON for a single program scan
(approx. 15 msec) each time the SQO instruction completes a step.
Examine ON instructions at the bit address go TRUE; Examine OFF
instructions go FALSE.
The SQO step completion bit is discussed further with shift registers, in
Chapter 13.
The SQO cycle completion bit is assigned the sequencer address plus 50.
(901 + 50 = 951):
951 951
Hh HU
The SQO cycle completion bit is set ON when the sequencer completes
its final step. Examine ON instructions at the bit address go TRUE;
Examine OFF.instructions go FALSE.
Reset Instruction The reset (RST) instruction is given the same address as the sequencer
instruction:
RAC 0000
When the RST instruction goes TRUE, the SQO cycle completion bit is
reset to OFF, and the sequencer is reset to the step number
corresponding to the RAC value. Outputs for the step are controlled as
programmed.
The RST instruction must go FALSE again before sequencer operation
can resume.
Chapter
Sequencer Data
Monitoring and
Changing Data
Power Down
Sequencer Instructions
10-3
In programming the ON/OFF status of bit addresses for sequencer steps,
ls and 0s are used, where 1 = ON and 0 = OFF. To simplify
programming, a 2-digit code is used to represent the status of the bit
addresses for a particular step.
Group numbers define which addresses are involved in the sequencer
data. Masking data (using the 2-digit code) indicates which of these
addresses apply to the sequencer and which do not.
Additional details on sequencer data appear on Page 10-6.
The PR value, AC value, and current step number can be monitored in
the Run and Test modes. The PR value of any step can be changed in the
Run or Test modes. Use the PRT/UNPRT key to protect the PR value
from being changed.
The sequencer status is retentive. When you apply power after a power
down, the current step number, AC value, and the completion bit status
will be the same as before power was removed. The status of the input-
satisfied bit will also be the same, provided the status of the external
inputs remain the same.
The sequencer status is also retained when going from the Run mode to
another mode.
Operation after CPU Faults: Sequencer instructions and associated
status bits and data values are reset to their initial conditions after a
CPU fault is detected (error codes 1 thru 9, 26, and 51).
10-4
Chapter Sequencer Instructions
Basic Operation -
Sequencer Output
The SQO instruction can control the ON/OFF status of up to 8 bit
addresses for up to 100 steps. It can be time-driven or event-driven.
With time-driven sequencers, each step functions similar to timer
instructions, involving an AC value and a programmed PR value (dwell
time). In the same way, the event-driven sequencer functions similar to
the counter instruction.
Time-Driven SQO:
Step
Bit Addresses
(Data Entry: ON = 1, OFF = 0)
Dwell Time
(PR Value)
A B C D E
0 OFF OFF OFF OFF OFF 5 seconds
1 OFF ON OFF ON OFF 20 seconds
2 ON ON ON ON OFF 60 seconds
3 ON OFF OFF ON ON 10 seconds
Beginning at step 0: With rung conditions FALSE, the SQO instruction
is waiting on step 0. Bit addresses A thru E are OFF in accordance with
data for step 0. When the SQO instruction goes TRUE, step 0 is
initiated; bit addresses A thru E remain OFF for a dwell time of 5
seconds (assuming SQO remains TRUE). Then step 1 begins; bit
addresses B and D go ON. After 20 seconds, step 2 begins; bit addresses
A and C go ON. After 60 seconds, step 3 begins; bit addresses B and C
go OFF, E goes ON. After 10 seconds, a completion bit is set ON and the
cycle repeats with step 0.
Event-Driven SQO:
Step
Bit Addresses
(Data Entry: ON = 1, OFF = 0)
FALSE-TRUE
Transitions
(PR Value)
A B C D E
0 OFF OFF OFF OFF OFF 1
1 OFF ON OFF ON OFF 1
2 ON ON ON ON OFF 1
3 ON OFF OFF ON ON 1
I
The PR value is set at 1 for each step (the typical case). Beginning with
step 0, bit addresses A thru E are OFF. After a FALSE-TRUE
transition of the SQO instruction occurs, step 1 is in effect; bit addresses
B and D go ON. After a 2nd transition, step 2 is in effect; A and C go
ON. After a 3rd transition, step 3 is in effect; B and C go OFF, E goes
ON. After a 4th transition, a completion bit is set ON and the cycle
repeats with step 0.
Chapter
10
Basic Operation -
Sequencer Input
Sequencer Instructions
10-5
The SQI instruction differs from the SQO instruction in that it examines
up to 8 bit addresses and sets an input-satisfied status bit ON when the
ON/OFF status of these bit addresses matches the programmed data for
a particular step. The SQI sequencer can be either time-driven or event-
driven.
Time-Driven SQI:
Step
Bit Addresses
(Data Entry: ON = l', OFF = 0)
Dwell Time
(PR Value)
Input-Satisfied
Status Bit
A B C D E
0 OFF OFF OFF OFF OFF 120 seconds Each step: This
bit is ON only
if inputs match
programmed
data.
1 OFF ON OFF ON OFF 60 seconds
2 ON ON ON ON OFF 60 seconds
3 ON OFF OFF ON ON 120 seconds
This sequencer moves from step to step in the same way as the time-
driven SQO sequencer.
During the time that a particular step of the SQI instruction is in effect,
the input-satisfied status bit will be set ON only when the status of bit
addresses A thru E matches the programmed data for that step.
Event-Driven SQI:
Step
Bit Addresses
(Data Entry: ON = 1,OFF = 0)
FALSE-TRUE
Transitions
(PR Value)
Input-Satisfied
Status 8 it
A B C D E
0 OFF OFF OFF OFF OFF 1 Each step: This
bit is ON only
if inputs match
programmed
data.
1 OFF ON OFF ON OFF 1
2 ON ON ON ON OFF 1
3 ON OFF OFF ON ON 1
This sequencer moves from step to step in the same way as the event-
driven SQO sequencer.
During the time that a particular step of the SQI instruction is in effect,
the input-satisfied status bit will be set ON only when the status of bit
addresses A thru E matches the programmed data for that step.
Chapter
10 106
Sequencer Instructions
Sequencer Data Sequencer data includes:
Sequencer classification: SQIorSQO; instruction address;
time- or event-driven.
Group number and corresponding 8 bit addresses.
Mask data, indicating which of the 8 bit addresses will be used.
Step data, indicating the ON/OFF status of the
bit addresses for each step.
Program codes for the mask and step data.
Preset values for each step.
We recommend that you use the Sequencer Instruction Data Form to
document this data. This form (included at the end of this manual)
allows you to document sequencer data in an orderly, systematic way,
reducing the chances for programming errors.
A sample data form is shown below.
CLASSIFICATION:
~{SQlh
-iSQOh
ADDRESS:
TIME DRIVEN
EVENT DRIVEN
GROUP NUMBER:
BIT ADDRESS DATA
PROGRAM
CODE
PRESET
VALUES
Bit Addresses-*
Mask Data
B A
Data
8
Data
A
Step Data -* 0
1 1 1
1 f 1
1
1 1 1
1 1 1
2
1 1 1
1 1 i
3
1 1 1
1 1 1
Special Note for SIC Personal Computer Software Users
You will find that sequencer data and the sequencer data
form differ slightly from the data and form discussed in this
manual.
The sequencer data form as it applies to the SLC personal
computer software is shown below. The data you must fHI
in from the tables on the following page are:
Group number
Hex mask
Hex data
Example: In the form below. Group 0 has been specified,
automatically entering VO addresses Oil thru 018 in the
form. Hex Mask 3F has been specified, automatically
entering binary mask 0011 1111 in the form. Hex Data 1B
has been specified for stepO, automatically entering binary
data 0001 1011 in the form.
For "Special Sequencer Instructions", using group numbers
38 thru 69, the software calls for Decimal Data instead of
Hex Data. The decimal data required are step numbers, as
explained inChapter 11.
Hex mask and
Hex data :
I/O Address :
.Hex Mask :
f
Mask:
ji tiex ivis
<C^8 inary i
018 017
0 0
016
3
1
015 014
Time Driven
013 012 011
F
1 1 1
TIME '
sqo#i ;
901 t
-(SQO>- y
GRP 00
m
t
! STE^ Hex ! Binary * I Preset
|> # ; Data 1 t Data
i:
{ Value
! 00 1 1B ! 0 0 0 1 10 1 1 j 0010
1
f
v- 1
f 1 1
End Of Sequencer
- [v: i. >.: ; '
" .* *
Group number
j
10
Sequencer Instructions Chapter
10-7
Sequencer Data
(continued)
Group numbers and program codes are used in filling out the table.
They are listed below.
Figure 10.1
Group Numbers
. External Output Bit Addresses and Internal Bit Addresses
(SQO Sequencers)
Bit
Addresses:
Group
Number
Bit
Addresses
Group
Number"
011-016 (output)
017-018(internal)
0
411-416 (output)
417-418 (internal)
4
111-116 (output)
117-118 (internal)
1
511-516 (output)
517-518 (internal)
5
211-216 (output)
217-218(internai)
: St 1-616.(output)*.
61-7-618 (internal)
H
311-316 (output)
317-318(internal)
3
5
, *. Internal Bit Addresser
* (SQO or SQI Sequencers) * *
>***? *
Group Bit Group
Addresses Number Addresses Number
701-708
; -r "
789-796 27
709-716 17 797-804 28
717-724 18 805-812 29
725-732 19 813-820 30
733-740 20 821-828 31
741-748 21 829-836 32
749-756 22 837-844 33
757-764 23 845-852 34
765-772 24 853-860 35
773-780 25 861-868 36*
781-788 26 869-876 37*
*NOTE: Bit addresses 864thru 876 apply to
special instructions, explained in the
following chapters:
Addresses 869-875: Chapter 8.
Addresses 864-868,876: Chapter 14.
? # External lnput
Bit Addresses
<" (SQI Sequencers)
Bit
:
Group
Addresses Number
001-008 7
101-108 8
201-208 9
301-308 10
401-408 11
501-508 12
601-608 13
009-010
109-110
209-210
14
309-310
409-410 15
509-510
609-610
NOTE: The first two hit.
addresses are not
used for Group 14:
Program Codes
(use Hex Mask and Hex Data
codes for personal computer
softvvaredataform)
Bit Address
Data
Program
Code
0000 0
0001 1-.
0010 2
0011 ;
0100 ^ 4
0101
:i
' 5
: oho 1 6
f
. 0111 7
1000 8
1001. ; : 9
1010 - . A
1011 : B
:
1100
1101 -
1110
1111 '
C
D
E
F
Example - For data 0001 1111
enter code 1 for Data 8, and
code F for Data A.
Thus: 0001 1111
. ; 1 F
Hex Mask and Hex Data Codes
(for personal computer software data form)
Binary
Value
Hex
* Value
0000 0 ""
:
0001 1
:
0010 2
0011 3
0100 ' * - 4 : ' :
0101 5
0110 6 -
0111 7 ; ; ; ;
1000 8
1001 9
1010 A :
1011 B
1100
1101
1110
1111

D
:
;
: e : ; : -
: ; . . F . .
Note that the data .in the "Binary Value" arid
"Hex Value" columns s equivalent to the data
inthe/'8it AddressOata"-and 'Program-Code"
columns in the "Program Codes" table above.
10-8
Chapter Sequencer Instructions
Filling in the To illustrate how the form is used, well enter data for the following
Sequencer Ddtd Form time-driven SQO sequencer (same sequencer as discussed on Page 10-4).
Time-Driven SQO:
Step
Sit Addresses
(Data Entry: ON = 1, OFF = 0)
Dwell Time
(PR Value)
A B C D E
0 OFF OFF OFF OFF OFF 5 seconds
1 OFF ON OFF ON OFF 20 seconds
2 ON ON ON ON OFF 60 seconds
3 ON OFF OFF ON ON 10 seconds
Follow these 3 steps (an explanation follows each data form figure):
Step 1 : a) Enter sequencer classification, b) Enter group number, bit addresses.
(SQ!) ra TIME DRIVEN .
CLASSIFICATION: ^ ijsQO)- ADDRESS: _901 Q EVENT DRIVEN
GR0UP
NUMBER: j0_
BIT ADDRESS DATA
PROGRAM
CODE
PRESET
VALUES
Bit Addresses
Mask Data-*
B A
Data
B
Data
A
018 017 016 015 014 013 012 011
Step Data -* 0
1 ! P"
1 1 1
1
1 I 1
1 t 1
2
1 I 1
1 I 1
3
1 t 1
Step 1: a) Enter the sequencer classification. Weve indicated SQO,
address 901, and time-driven in the heading of the data form.
b) Enter the group number and corresponding 8 bit addresses.
Determine the sequencer group number from Figure 10.1, Page 10-7.
Weve selected group number "0, corresponding to bit addresses
011-018. Addresses Oil thru 016 apply to the external outputs of the
processor unit; addresses 017 and 018 apply to internal relay-type
instructions.
List these 8 bit addresses in reuerse order, beginning with the highest
number in the far left column under B.
Chapter
10
Sequencer Instructions
10-9
Step 2 : a) Enter mask data, b) Enter step data.
-SQD-
CLASSIFICAT10N:
I -(SQO)-
ADDRESS: 901
[X] TIME DRIVEN
EVENT DRIVEN
GROUP NUMBER: 0
BIT ADDRESS DATA
PROGRAM
CODE
PRESET
VALUES
Bit Addresses -*
Mask Data-*
B A
Data
B
Data
A
018 017 016 015 014 013 012 011
0 1 0 0 1 1 1 1
----Step Data * 0 0 0 0 0 0
1 1 t
1 0 1 0 1 0
1 i t
1 1 !
2 1 1 1 1 0
1 1 1
1 1 1
3 1 0 0 1 1
1 1 1
1 1 1
Step 2: a) Enter mask data. Enter a 1 in the form under the addresses
to be controlled by the sequencer. Enter a 0 under those excluded. Our
sequencer has 5 outputs; weve excluded addresses 015, 016, and 018
from sequencer control. These addresses can be used elsewhere in your
program.
Note that the sequencer is controlling 4 external output addresses (Oil
thru 014) and 1 internal address (017).
b) Enter step data. 1 corresponds to an ON condition and 0 corresponds
to an OFF condition. Thus, for each step, the ON and OFF states of A, B,
C, D, and E correspond to the ls and 0s entered under addresses 017,
014, 013, 012, and Oil in the data form.
Step 3 : a) Enter program entry codes for mask and step data, b) Enter preset values.
CLASSIFICATION:
-(SQ0-
M -iSQOh
ADDRESS: 901
[x] TIME DRIVEN
EVENT DRIVEN
GROUP/NUMBER: 0
BIT ADDRESS DATA
PROGRAM /
CODE ' \
PRESET
VALUES
Bit Addresses*
Mask Data*
B A
Data
B
Data
A
018 017 016 015 014 013 012 011
0 1 0 0 1 1 1 1 4 F
Step Data -* 0 0 0 0 0 0 0 0 ! 5. I 0
1 0 1 0 1 0 0 A I 2 i 0. I 0
2 1 1 1 1 0 4 E ! 6 \ 0. \ 0
3 1 0 0 1 1 4 3
!
1
! 0 !
0
r
Masked addresses are 0 for coding.
J
Step 3: a) Enter program codes for mask and step data. The
program code is shown in Figure 10.1, Page 10-7. Applying this code to
mask data 0100 under B, weve entered 4 under "Data B in the form.
Similarly, mask data 1111 under "Data A is identified by code F.
Note: For step data, masked addresses are considered as 0s. Thus, for
step 3 under B, the step data is considered to be 0100. Code 4 is entered.
b) Enter Preset values. Weve specified the PR values to the tenth of a
second, just as with timers.
10-10
Chapter Sequencer instructions
Sequencer Output Figure 10.2 shows a ladder diagram and a completed data form for an
(SQO) SQO instruction. This is a 10-step, time-driven sequencer controlling 4
external output addresses (012, 014, 015, 016) and 1 internal address
(017). Operation is explained below the data form.
Figure 10.2
Rung 1
Rung 2
Rung 3
Rung 4
001
002
Sequencer
Instruction
Step Completion
901 Bit Address
Cycle Completion
951
Bit Address
Reset
Instruction
901
Hsqo)
701
HY
702
901
Krst)
RAC 2
Ladder Diagram
CLASSIFICATION:
Q -tSQIJ-
m -(SQO)-
ADDRESS: 901
M TIME driven
EVENT DRIVEN
GROUP NUMBER: 0
BIT ADDRESS DATA
PROGRAM
CODE
PRESET
VALUES
Bit Addresses
Mask Data-*
B A
Data
B
Data
A 018 017 016 , 015 Q14 013 012 011
0 1 1 . . 1 1 0 1 0 7 A
Step Data 0 , 1 0 1 0 0 1 5 2
! 1 5. ! 0
, . 1 , 1 0 1 ;
! ,
: 0 5 : '8
! :s,:i 0
.2 0
: .y
o- - 0 ' 0 . 2 0
: 1 IMS
i
3-
1
o
:
V .
0 0 5 0
! i 1- : o
- 4
0 0 0 ; 0 1 1 '
: : : ; o ' A
: I h I o
5 0 1 0 ; '.1;
.
1
:
:
; 0 5 8
; !
6 0 1
:
1 0 ; 0 ; ;
, o
6 0 ! ! o ! 5
, . ,
7 1 0 0 ; : I; ;
;
;
: 'T; *
0 4 i I 0. I 5
8 0 i 1 ; "1 0 - 3 : 8 I I l l s
9 o 1 - 1 - 1
:
r 3 A
! ! 3 . ; 0
<8 Masked address. Used as0 for coding purposes.
Operation begins with rung 1 FALSE and the SQO Rung3demonstrates how the cycle completion bit
instruction on step 0. External output addresses 12 and 15 functions. The first time the sequencer recycles from the
are ON, and internal bit address 17 is ON. Now rung 1 goes final (9th) step to step 0, the cycle completion bit is set ON,
TRUE. As long as the rung is TRUE, the sequencer advances causing the Examine ON instruction in rung 3 to go TRUE,
from one step to the next each time the PR value of the Th Cycle completion bit remains ON until the sequencer is
current step is reached. At the beginning of each step, bit reset.
addresses 012, Q14, 015, 016, and 017 are set ON or OFF as
indicated by the 1 's and 0's in the data form. (Addresses
011, 013, and 018 are not used.)
Rung 2 demonstrates how the step completion bit
functions. Each time a step is completed, this bit is set to
ON for a single program scan, during which time the
Examine ON instruction in rung 2 will be TRUE. This bit is
used in shift register applications.
Rung 4 conta ins the reset instruction. When this rung goes
TRU E, the sequencer is reset to step 2, corresponding to the
programmed RAC value. Also, i be cycle completion bit is
reset to OFF.
While the RST instruction is TRUE, the sequencer is held on
its RAC step with the corresponding outputs controlled as
programmed. Operation can resume when rung 4 goes
FALSE again.
Chapter Sequencer Instructions
10-11
Sequencer Input (SQI) Figure 10.3 shows a ladder diagram and a completed data form for an
SQI instruction. This 10-step, event-driven sequencer examines 7
external input addresses, 002-008. Bit address 001 is not used.
Operation is explained below the data form.
Figure 10.3
FALSE-TRUE transitions of rung 1 move the sequencer from
one step to the next. In this case, a single FALSE-TRUE
transition advances the sequencer, since all PR values are
set at1. . /
The ON/OFF states of the external inputs determine
whether the input-satisfied status bit will be ON or OFF.
That is, when the ON/OFF states of the external inputs ;
match the data programmed for the current step, the input-
satisfied status bit will be ON; when the external inputs do
not match the data programmed for the current step, the
status bit will be OFF.
Rungs 2 and 3 are output rungs; containing examine
instructions at the input-satisfied status bit address. When
the status bit is ON, rung 2 is TRUE and rung 3 is FALSE;
when th Status bit is OFF; rung 2 isFLSE and rung 3 is
" TRUE. - -
:
i ; ' ; ; ;
:
'
Rung 4 contains the reset instruction. When this rung goes
. TRUE, the sequencer is reset to step 0 (corresponds to RAC
value}.'." :
:
7 ^
' While the RST instruction is TRUE, the sequencer is held on
its RAC step and the SQI will continue to examine inputs.
Operation can resume when rung 4 goes FALSE again.
70-72
Chapter Sequencer Instructions
Programming The keystroke example below shows you how to program rung 1 of the
Sequencer sequencer appearing on Page 10-10. This example illustrates how to
instructions P
r
g
ram
time- or event-driven operation, the group number, mask data,
step data, and PR values. For practice, you may want to program all ten
sequencer steps and all four rungs of the sequencer ladder diagram.
Figure 10.4
Keystroke Example - Sequencer Instruction. j 901
Rung 1 \-------- 1 -------------------------------(SQC
CLASSIFICATION: ADDRESS: _901 g ^DRIVEN GROUP NUMBER: _0_
BIT ADDRESS DATA
PROGRAM
CODE
PRESET
VALUES
Bit Addresses
Mask Data >
B A
Data
B
Data
A
018 017 016 015 014 013 012 011
0 1 1 1 1 0 1 0 7 A
Step Data * 0 . 1 0 1 0 1 5 2 ! I s. ; o
1 1 0 1 1 0 5 8 ! . ! 5. ! o
2 0 1 0 0 0 2 0 ! I 2. ! 5
(Complete ladder diagram and data form appear on Page 10-10.)
Press
these keys
.This LEQ .
will be Ut
(inaddr ^
iti on to
PROG) ;
Display will show
Address -J Rung/rr
-Data-' ' Mode .
. BBS . : EnJ '
' ' Arbitrarify Wdsiart
aaswords,^'
- I t - i i !
Examine ON instruction, address 001 is entered.
SHIFT,
-<SQO)-
-<SQO)-
i
Display is prompting for address of the SQO instruction.
9*0,1,
ENTER
-SQO)-
L
U I
L
J
I
Address 901 is entered. Display showsC-E, prompting you to specify
time-driven or event-driven.
SHIFT, TIME,
ENTER
-(SQO)- __ 9
r
P
We have specified time-driven (we could also have pressed C instead of
TIME). Display is prompting you for the group number.
0, ENTER -<SQO)-
__ U5E
Group 0 is entered. Display shows USE, prompting you for mask data.
7, SHIFT, A,
ENTER
-<SQO>- d 0
Mask data 7, A is entered from the data form. Display is prompting you for
step data of step 0.
5,2,
ENTER
-(SQO)-
______ F
Step data 5,2 is entered from the data form. Display is prompting for step
0 PR value. Note: With event-driven sequencers, a PR value of 1 is entered
automatically (you can change this).
5,0,
ENTER
-(SQO)-
___ dl
PR value of 5.0 is entered from the data form. Display is prompting you for
step data of step 1.
Keys for steps
1-9,
ENTER
PROG
BE5 End
The display will continue prompting for step data and PR values. When
entering the PR value of step 9, press ENTER a second time. This ends the
data entry; the display at the left will appear.
Chapter Special Sequencer
Instruction Techniques
Cascading SQO SQO instructions can be cascaded in order to control more than 8
Instructions bit addresses. An example is shown in Figure 11.1a. Rung 1 is a
dummy sequencer. Rung 2 resets all sequencer instructions in the
program. It is important that this reset rung follows the dummy
sequencer rung so that the cascaded sequencers are reset properly.
Rungs 3 and 4 are cascaded sequencers controlling 16 bit addresses.
With cascaded SQO instructions, bit addresses controlled by the 2nd,
3rd, and subsequent sequencers are set in the same I/O scan; bit
addresses controlled by the 1st sequencer are set one scan later. This is
the reason weve made the rung 1 sequencer a dummy. It controls no bit
addresses. It serves only to synchronize the setting of bit addresses of the
sequencers in rungs 3 and 4.
Sequencers in rungs 1,3, and 4 have the same address and are operated
by the same rung conditions. They are event-driven (could also be time-
driven), and have the same presets and number of steps. The sequencer
in rung 3 controls Group 0 outputs; the sequencer in rung 4 controls
Group 1 outputs; the sequencer in rung 1 has Mask data of 00, so that it
controls no outputs at all. Data forms are shown in Figure 11.1b on the
next page.
Figure 11.1a
Dummy SQO 901. Controls no
outputs. It serves only to
synchronize subsequent
sequencers.
RSI 901 resets SQO
instructions to step 0.
SQO 901 can be programmed
to control one set of outputs,
Group 0 for example.
SQO 901 can be programmed
again to control another set of
outputs, Group 1 for example.
Cascading sequencers. See Figure 11. 1 bfor data forms.
11-2
Chapter Special Sequencer Instruction Techniques
Cascading SQO The data forms below apply to the cascaded sequencers in Figure
Instructions 11.1 a on the previous page.
(continued)
Figure 11.1b
CLASSIFICATION: ADDRESS: _901_ ""n/dRWEN GROUP NUMBER: _0_
Rung 1
Dummy
Sequencer
Same data
as rung 3
except Mask
is 00
BIT ADDRESS DATA
/. , ;=: :v = v-
PROGRAM
CODE
PRESET
VALUES
Bit Addresses-
Mask Data-
t1 "" - A, J
Data
B
Data
A
018 I 017 016 015 014 013 012 011
0 , 0 o ; , o .. , 0 .. 0 0 0 0 0
Step Data - 0 , 1 t
t
1 , 0 1 0 0 0 1 D 1
1 1 1 .
1 i 1
1
. i , , 1 0 0 - , 1 , 0 1 : . 0 1 0 2 A
1

1
1
1 1 1
1
1 : 1 : 0 o 0 - 1 V 0 0 C 4
1 1 1
1
I - 1 1
1
-
:
^ - - 3 0 0 0 v i . 0 0 0 1 1 1
1
'
1
1
I 1 1
1
Rung 3
Sequencer
CLASSIFICATION:
-SQI)-
xi-isao)-
ADDRESS: 901
TIME DRIVEN
EE EVENT DRIVEN
GROUP NUMBER: 0
BIT ADDRESS DATA
PROGRAM
CODE
PRESET
VALUES
Bit Addresses
Mask Data-
' B , a ;.
Data
B
Data
A 018 017 016 015 014 013 012 011
1 .. 1
:
: 1 , 1 1 1
;
1 1 F F
Step Data- 0 '-1
1
0
. i . . . ,
0 0 0 1 D 1
! ! 1
- ' V . ; - ' 1 0 o , 1 , 0 : 1 , 0 1 0 2 ' A
! ! 1
; 1. ' : 1 0 0 o ; 1 0 0 C ; 4 '
! _j __ : 1
: : I : : ; : . 3 " 0 * o 0 1 0 ; o: ; o ; ; 1 ;
r
1 " 1
! ! i t
Rung 4
Sequencer
CLASSIFICATION:
Q -(SQI>-
0 ASQOh
AOORESS: 901
TIME DRIVEN
0 EVENT DRIVEN
GROUP NUMBER: 1
BIT ADDRESS DATA
PROGRAM
CODE
PRESET
VALUES
Bit Addresses--
Mask Datas-
" ;. : b ; ' ;.! , ; ; A *.. ;.
Data
B
Data
A 118 >117 .' 116 115 114 113 112 111
: 1 .* ", 1 I * 1 ' ! 1 i x .; : : 1 . 1 F F
Step Data - 0 "1: " :i
B
0 ' ::r : v: ; . \ ] ; o .. ; o C C
i t -
1
1
' 1
:
1 ; .' o .; : o 0 0 0 0 8 8
i t 1
r

I i 1
2 0 , 1 : 0 . 0 ' 1 1 1 0 1 4 D
i : !
3 1 , 0 1 o .; 0 1 0 0 A .: 4
! ; !
1
Note for SLC Personal Computer Software Users
The data form you are using prompts you for Hex Mask and Hex Data.
This corresponds to the Program Code used in the forms above. A
comparison of the sequencer data form you are using and the form
shown above appears on Page 10-6.
Chapter Special Sequencer Instruction Techniques
11-3
Cascading SQI
instructions
SQI instructions can be cascaded in order to examine more than eight
input addresses. The example below shows how this is done. (Note that
a dummy sequencer is not required as with SQO instructions.)
Figure 11.2
Rung 1
Rung 2
Rung 3
Rung 4
Rung 5
001
001
901 902
HIII-
002
901
{SQI)'
902
{SQI)
011
-i )
901
{rst) '
RAC 0
902
{RST)'
RAC 0
Input addresses 001 thru 008 are
examined by SQI 901. Addresses 009
and 010 are examined by SQI 902. Input
conditions must be satisfied for both
sequencers in order to energize
instruction 011 in rung 3.
Both sequencers must have the same
number of steps. In this example,
examine instruction 002 resets both
sequencers to step 0.
CLASSIFICATION:
m -(SQi)
~{sQoy
ADDRESS: 901
TIME DRIVEN
0 EVENT DRIVEN
GROUP NUMBER: 7
BIT ADDRESS DATA
PROGRAM
CODE
PRESET
VALUES
Bit Addresses
Mask Data>
B A
Data
B
Data
A
008 007 006 005 004 003 002 001
1 1 1 1 1 . 1 1 1 f F
Step Data - 0 0 0 0 1 0 0 0 1 1 ' 1
! ! ! 1
1 0 0 1 0 0 0 1 0 2 2
! ! !
1
2 0 1 0 0 0 1 0 0 4 4 I \ 1
3 1 0 0 0 1 0 0 0 8 8
! ! ! 1
4 0 0 0 0 0 0 0 0 0 0
! ! ! 1
Sequencer data form for rung 1
CLASSIFICATION:
0 ASQih
-<SQO>~
ADDRESS: 902
TIME DRIVEN
0 EVENT driven
GROUP NUMBER: 14
BIT ADDRESS DATA
PROGRAM
CODE
PRESET
VALUES
Bit Addresses
Mask Data>
B A
Data
B
Data
A
210 209 110 109 010 009 =-
0 0 0 0 1 1 0 o 0 C
Step Data -* 0 0 0 0 0 0 0 0 0 0 0 1 !........ |i
1 0 0 0 0 0 0 0 0 0 0 ! ! ! 1
2 0 0 0 0 0 0 0 0 0 0 1 ! 1
3 0 0 0 0 0 0 0 0 0 0
! I !
1
4 0 0 0 0 1 1 0 0 0 c
! ! !
1
Sequencer data form for rung 2
11-4
Chapter Special Sequencer Instruction Techniques
Reversing Sequencer The reversing sequencer operation allows you to operate a sequencer in
Step Operation a forward or reverse step order. An example is shown in Figure 11.3.
Rung 1 is the forward operating sequencer. Rung 3, having identical
rung conditions, implements reverse operation of the sequencer; note
that this rung is within a ZCL zone.
Operation: When rung 1 is TRUE and rung 2 is FALSE, the sequencer
operates in a forward step order (rung 3 is TRUE, but inoperative).
When rung 2 goes TRUE, rung 3 becomes operative and the sequencer
reverses the step order, beginning with the step in effect at the time.
When rung 2 goes FALSE again, the sequencer operates in a forward
step order again.
The data forms for rungs 1 and 3 are included in the figure. Data for
rung 1 is entered using the program codes listed in Figure 10.1, Page
10-7. Enter rung 3 according to the following special procedure:
1. If you like, you can enter rung 3 by copying rung 1, then modifying
the data. The SQO instruction address is 901, and it is time-driven.
2. Select a special group number from the table below. The number
must correspond to the address number of the sequencer. In this case
number 38 applies.
Address
Group
No.
Address
Group
No.
Address
Group
No.
Address
Group
NO.
901 38 909 46 917 54 925 62
902 39 910 47 918 55 926 63
903 40 911 48 919 56 927 64
904 41 912 49 920 57 928 65
905 42 913 50 921 58 929 66
906 43 914 51 922 59 930 67
907 44 915 52 923 60 931 68
908 45 916 53 924 61 932 69
3. You must specify FF for mask data. This is required when you use
any of special group numbers 38-69.
4. Enter the special step data for reverse step order, as directed below
the rung 3 data form.
5. Preset values for both sequencers must be the same, in this case a
value of 1.0.
Program Editing Note: When you program a reversing sequencer you must select a
special group number from the table above. The step data you program is a decimal
notation for the reversing step order, as opposed to the coded step data for a
regular group number. If you edit a sequencer and change a group number from a
special group number to a regular group number or vice versa, you must also edit
the step data. Failure to do this could result in unexpected sequencer operation.
Chapter Special Sequencer Instruction Techniques
11-5
Figure 11.3
/Same rung
conditions
CLASSIFICATION:
-tSQIH
[xj-iSQO)-
ADDRESS: 901
[U TIME DRIVEN
EVENT DRIVEN
CROUP NUMBER: 0
BIT ADDRESS DATA i ^ *
PROGRAM
CODE
, PRESET
VALUES
Bit Addresses-*
Mask Data -*
B ; tv
Data
8
Data .j
A 018 Dir: 016 015 014 013 ; 012 011
1 . 1 1 ' 1 '
:
V
:.
" 1 ; 1 1 F F > -
Step Data .-* 0 0
:
0 ; o 0 i 0 0 0 - 0 0 - ,0
1 1
1
- 1 0
1 0 V 0 0 0 - 1 - 0 * - 1 = 0 ; o - : a :
! ! 1 ! o
2 0 0 1 0 ' 0 0 0 ' 3 : o - -
I ! 1. I o
3 1 ;
; o
1 0 0 0 0 >
> o
: a 0 >
; - i o
4 0 1 0
: : : 0 ; 1 o ' 1
: 5
5
- 1 ! 0
5 o 0 0
:
T
: o : 0
; o :
i \ j v 1 ! 1 ! o
6 0 : o 1 0 0
: 0 : . 1 ; ;
. 0 . r 2 ; 2
1 l 1 - 1 o
7 0 1 0 o 0 1 , o f 0 4 - 4 -
I < 1 ' n
1 1 1 - 1 o
8 0 0 ' 1 0
. ,
t
,
- 0
:
0 0
: ,2 ,
8
1 1
i
1
n
1 .1
1
-
0
9 1 0 0 - o * 0 ; 0
*
, o * 4 8 1
1 1
1
1
n
1 1
1
1 o
Sequencer data form for rung!
CLASSIFICATION- = ^ ,
wl
ia
R
ES^ ^ ^
CLASSIFICATION. ^
ADDRE5S
' g EVENT DRIVEN
GROUP NUMBER: 38
- ........ .
;
; BIT ADDRESS DATA ; ;
PROGRAM
CODE
PRESET
VALUES
Bit Addresses-*
Mask Data -*
B A
Data -
.. Z
B
;
Data
a .
: : f : : ;f. ..:
s tep Data-* 0 : 0 ;
H
8
. ,
1 1
1
1
U
f 1 : : o :: ::i ! 1 1 o
SIC Personal Computer
Software Users:
When you are prompted for
"Dec Data", enter the step
data as done here-08,09, 1
00,01,02,and soon.
, " / ; 2 ; : o : : o ; hi P
/ 3
;
o :. . . : ;; 1 ; ;
i : hlo
/ , 4
fg
. ; : i ? ; 1 hlo
/ ^
;;;
: o ; 3 ;; ;
i hlo
/ h - 6 : o : ; 4 ;
: : t ! 1 ! 0
/ 7 0 : 5
: l x I o
> j ! . . 8 0 6
I ' 1
n

1 1
1
1 0
0
: , 7 , ,
i ; t
n

1 1 ' 1 0
Sequencer data form for rung 3
Rules for step data: StepO: Enter second last step number (8 in this case.)
Step 1: Enter last step number (9 n this case.) ' : './/
Steps 2 and higher: Enter step number minus 2 (2 minus 2 = 0, 3 minus 2 = 1, etc.)
5
, Reversing sequencer *
11-6
Chapter Special Sequencer Instruction Techniques
Sequencer
Input Driving a
Sequencer Output
The input-satisfied status bit of an SQI instruction can be used to
advance an SQO step number. Figure 11.4 shows how this is done.
The SQI and SQO instructions are assigned addresses 901 and 902.
Both instructions are event-driven with a preset of 1 for each step. The
input-satisfied status bit of the SQI instruction is used in rung 2 to
advance the SQO step number. The SQO step completion bit is then
used to advance the SQI step number.
In step 0, status bits corresponding to bit addresses Oil thru 018 are
OFF, as specified in the SQO data table. Referring to step 0 of the SQI
data table, note that when bit address 005 is ON and bit addresses 006,
007, and 008 are OFF, the programmed data for step 0 is matched,
causing the input-satisfied status bit to go ON. This advances both the
SQI and SQO instructions to step 1, causing outputs 012 and 014 to go
ON. Operation continues from step to step in this manner.
Figure 11.4
SQI driving an SQO
Rung 1
Rung 2
901
<SQI)"
902
{ S Q O )
001
Rung 3 ------ 1 [
001
Rung 4 "||-
901
<RST)'
RAC0
902
<RST)
RAC0
CLASSIFICATION:
0 {SQI)
ASQOh
ADDRESS: 901
TIME DRIVEN
(x| EVENT DRIVEN
GROUP NUMBER: 7
BIT ADDRESS DATA
PROGRAM
CODE
PRESET
VALUES
Bit Addresses
Mask Data-*
B
:
' A
Data
B
Data
A 008 007 006 005 004 003 002
1 1 1 1 0 0 0 0 F 0
Step Data -* 0 o 0 0 1 0 0 0 1 0
r r 1
1 t 1
1
0 0 1 0 0 0 0 2 0
! ! ! 1
2 0 1 - 0 0 0 0 0 4 0
! i ! 1
.3- , 1 :
o 0 0 0 0 0 0 8 0
1 ti,
1 t 1
1
Masked addresses are 0 for coding.
CLASSIFICATION:
CHSQI-
0 -isQoy-
ADDRESS: 902
TIME DRIVEN
ff EVENT DRIVEN
GROUP NUMBER: 0
BIT ADDRESS DATA
PROGRAM
CODE
PRESET
VALUES
Bit Addresses
Mask Data -*
B A
Data
B
Data
A 018 017 016 015 014 013 012 Oil
r ' t 1 ; .r .
, -
; r ; 1 1 ' F - F
Step Data -+ 0 0 0 0 0 ! 0 0 0 0 0 0 ; ; ! 1
. r 0 0 0 0 . T 0 1 o 0 A
! ! 1 1
2 : 0 0 1 . 1
:
; ;.1' .. 1 1 0 3 E
! ! !
1
3 1 : . 1 0 0 0 1 1 C 3 ! ! 1
Chapter Special Sequencer Instruction Techniques
11-7
SQI Monitoring Example 1 - SQI monitoring an SQO step. This is shown in Figure
an SQO 11.5. The SQI instruction in rung 3 is monitoring the SQO instruction
in rung 2. When the SQO instruction reaches step 12, the input-
satisfied status bit of the SQI instruction (rung 1) is set to ON,
energizing output 011.
Figure 11.5
Note : Rung order is selected so that Output 011 is energized
in the same I/O scan that sequencer 901 bit addresses are set.
Rung 1
Rung 2
.Rung 3
902
SQI input-satisfied
status bit
001
011
901
<SQO)---
Group number: 38
data: 12 '9Q2
; (sQi)-
SQI monitoring an SQO step
Program the SQO instruction as you ordinarily would. Program the SQI
instruction according to the following special procedure:
1. Assign it an address between 901 and 932.
2. When prompted for time- or event-driven operation, select either one;
operation will be the same regardless of your choice.
3. Select a group number from the table below. It must correspond to the
address of the SQO instruction you are monitoring. For Figure 11.5,
SQO 901 is monitored, requiring group number 38. You must
program the mask data as FF (for any of group numbers 38-69).
Address
Group
No.
Address
Group
No.
Address
Group
No.
Address
Group
No.
901 38 909 46 917 54 925 62
902 39 910 47 918 55 926 63
903 40 911 48 919 56 927 64
904 41 912 49 920 57 928 65
905 42 913 50 921 58 929 66
906 43 914 51 922 59 930 67
907 44 915 52 923 60 931 68
908 45 916 53 924 61 932 69
4. The programmer will now prompt for step data. Enter the step
number as data (12 for example). Any preset value can be entered.
SLC Personal Computer Software Users: You will be prompted
for "Dec Data. Enter the step number (12 for example).
This completes the SQI instruction entry.
Program Editing Note: When you program a sequencer input instruction to
monitor another sequencer instruction, you must select a special group number
from the table above. The step data you program is the step number you want
to monitor as opposed to the coded step data for a regular group number. If
you edit a sequencer and change a group number from a special group number
to a regular group number or vice versa, you must also edit the step data.
Failure to do this could result in unexpected sequencer operation.
11-8
Chapter Special Sequencer Instruction Techniques
SQI Monitoring Example 2- SQI monitoring an SQO for "greater than {>) step.
3/1 SQO Figure 11-6, SQI 902 is monitoring SQO 901. SQI 902 status bit
(continued
1
) 952 (902 4- 50) is set ON when the SQO step number is greater than (>)
5. The status bit remains ON until SQI 902 is reset.
F i g u r e 1 1 . 6
Note: Rung order is selected so that output011 isenergized
in the same I/O scan that sequencer 901 bit addresses are set.
SQI monitoring an SQO for "greater than" (>) step
Program the SQO instruction as you ordinarily would. Program the SQI
instruction according to the special procedure described in Example 1.
Chapter Special Sequencer Instruction Techniques
11-9
SQI Monitoring
an SQO
(continued)
Example 3 - SQI monitoring an SQO for step number range. In
Figure 11.7, SQI 915 and SQI 916 are monitoring SQO 910 for a range of
steps. Instruction 012 in rung 1 will be ON when the SQO 910 step is
greater than 10 and less than or equal to 15. Reset instructions are used
to set SQI status bits 965 and 966 back to their initial states.
Figure 11.7
Note: Rung order is selected so that output 012 is energized
in the same I/O scan that sequencer 910 bit addresses are set.
Rung 1 "|
Rung 2
Rung 3
Rung 4
Rung 5
Rung 6
965 966
4b
005
SQI 915 and
SQI916
status bits
012
910
~{SQO) "
Group number: 47
Step data: 10 915
-(SQI)-----
Group number: 47
Step data: 15 gie
---------------------------- (SQI)--------- 1
006
006
915
-(rst) "
RAC 0
916
(rst) "
RAC 0
SQI monitoring an SQO for step number range
Program the SQO instruction as you ordinarily would. Program the SQI
instructions according to the special procedure described in Example 1.
7 7-70
Chaptet Special Sequencer Instruction Techniques
Sequencer Jump
Operation
The jump operation allows you to either execute all steps of a sequencer
instruction or to skip certain steps (jump). The sequencer input
monitoring technique (Page 11-7, example 1) is used in the jump
operation.
In Figure 11.8, SQI902 is monitoring stepS of SQO 901. If instruction
002 (rung 3) is TRUE and SQO 901 is on step 5, SQO 901 will be reset to
step 15 by the RST 901 instruction. In effect, steps 5 thru 14 are
skipped. On the other hand, if instruction 002 is FALSE when step 4 is
completed, SQO 901 will continue with steps 5 thru 20.
Figure 11.8
Group number: 38
Step data: 5
SQO 901 Step
1
2
3
4
5
6
- - 7
8
9
10
11
12
13
_*.14
15
16
17
18
19
20
If instruction 002 (rung
3) is TRUE when step 4
is completed, steps 5
thru 14 of SQO 901 are
skipped.
SLC Personal Computer Software Users:
When you are prompted for "pec Data",
enter the step number, 05.
Program Editing Note: When you program a sequencer input instruction to monitor another
sequencer instruction, you must selects special group number from the table on Page 11 -7. The step
datayou program is the step number you want to monitor as opposed to the coded step data for a
regular group number. If you edit a sequencer and change a group number from a special group
number to a regular group number or vice versa, you must also edit the step data. Failure to do this
could result in unexpected sequencer operation. ;;;
Sequencer jump operation
Chapter High Speed Input
Programming
An HSI module (right) connected to an SIC 150 processor unit.
(The HSI module is for use with the SLC 150 processor only).
The High Speed
Input (HSI) Module
The High Speed Input module facilitates the counting of rapid pulses
produced by external input devices such as a solid state sensor or an
encoder. Counting is accomplished in your program by a special event-
driven SQO instruction. We will refer to this as an HSI counter
instruction.
Your SLC 150 controller is designed to accommodate up to four HSI
modules. Addresses for the corresponding four HSI counter instructions
are 901, 902, 903, and 904. The figure below indicates how the addresses
must be assigned.
Address Address Address Address
901 902 903 904
The physical location of the HSI module determines what address you
must assign to it. The HSI connected directly to the processor must be
assigned address 901, the HSI connected to the 1st HSI must be assigned
address 902, etc. Unused addresses can be used for standard
timer/counter/sequencer programming.
Chapter
12
High Speed Input Programming
12-2
The HSI The HSI counter is distinguished by an event-driven SQO instruction
Counter Instruction immediately preceded by an Examine OFF instruction with the same
address. Additional examine instructions can be used in the rung to
enable or disable the counting process. This is illustrated below.
Figure 12.2
The HSI Counter Instruction
001
/
Examine instructions here can
be used in the rung to enable/
disable the counting process.
901 w1
901 |
+b(sqo>-4
V
This pair of adjacent instructions
distinguish the HSI counter. The
SQO is event-driven.
Operation is similar to event-driven sequencers discussed in Chapter 10.
When instruction 001 in Figure 12.2 is TRUE, HSI counter 901 is
enabled. Pulses fed into the HSI 901 module increase the AC value of
SQO 901. When the AC value reaches the programmed PR value, the
HSI counter advances to the next step, setting outputs according to
programmed data.
Maximum Pulse Rate (Frequency) - If the maximum pulse rate is
exceeded, Examine OFF instruction 901 (Figure 12.2) will go FALSE,
disabling the HSI counter. The maximum pulse rate is 5 KHz when you
are using one HSI module. If you use 2, 3, or 4 HSI modules, the
maximum pulse rate is less. This is explained in the table below.
No. of Maximum pul The sum of the
modules rate for a single pulse rates for Example
connected module all modules
1
:
5 KHz If you use 2 HSI modules, neither
: 2 4 KHz " Cannot exceed one can have a pulse rate greater
, 3
:
; * 3 KHz U- 5 KHz than 4 KHz, and the sum of the
; 4 *' - 2 khz "U ..:: pulse rates cannot exceed 5 KHz.
Basic Operation Figure 12.3 shows two HSI counters. Note that each counter is
characterized by an event-driven SQO instruction preceded by an
Examine OFF instruction with the same address.
Cycle Completion Bit (Rung 2): HSI counter 901 includes a cycle
completion bit (901 + 50). Instruction 951 in rung 2 will go TRUE for
one program scan when SQO 901 completes its last step.
Chapter High Speed Input Programming
12-3
Basic Operation Normal Reset (Rung 3): HSI counter 901 is reset normally. When
(continued) instruction 002 goes TRUE, counting is disabled. SQO 901 is reset to
step 0, applying step 0 outputs. SQO 901 remains at step 0 until rung 3
goes FALSE.
Single Shot Reset (Rungs 5 and 6): HSI counter 902 uses a single shot
reset, which resets the counter to a specific step without losing any high
speed input counts. The single shot is initiated by the step completion
bit of an SQO instruction. Thus, when rung 5 goes TRUE, instruction
910 in rung 6 goes TRUE for one program scan. This momentarily sets
rung 6 TRUE, resetting SQO 902 to step 0, where the counter resumes
operation. Any high speed input pulses occurring during reset are
applied to the AC value of step 0.
You must program a 4-digit RAC value for a single shot reset. The first
two digits must be 99; the second two digits specify the step number you
want the counter reset to.
Exceeding the Maximum Pulse Rate: If the maximum pulse rate is
exceeded, Examine OFF instructions 901 and 902 (rungs 1 and 4) will go
FALSE, disabling the counting process. The counters are held in their
last states, with respective outputs applied. Instructions 901 and 902
remain FALSE until the over-speed condition is corrected and the
counters are reset.
Caution: Exceeding the maximum pulse rate will disable the HSI
counter and hold outputs to the last state. Appropriate emergency
stop switches should be used in your application to guard against
unexpected machine operation.
Figure 12.3
Chapter
12 12-4
High Speed Input Programming
Special Application Cascading: You cannot cascade sequencers used in HSI counters. Your
Considerations HSI
coun
t
er
is limited to 8 bit addresses, 6 of which can be external
outputs.
External Outputs: To obtain the fastest possible operation of your HSI
counter, use the external outputs located on the processor unit. These
outputs, corresponding to SQO sequencer group numbers 0 and 1, are
updated immediately, ahead of the I/O scan. See Figure 12.4.
You can also use external outputs located on expansion units. These are
updated during the normal I/O scan.
Figure 12.4
HSI counter outputs addressed to
an expansion unit are updated
Scan Time: As the frequency of your HSI counter increases, your scan
time also increases. Programming preset values of lwill further
increase your scan time.
A scan time in excess of 100 milliseconds will be detected by the
processor unit and cause system shutdown (error code 9). You should
verify your scan time at the maximum HSI input rate for your
application, to assure proper operation of your system. Refer to Page 8-4
for instructions on measuring scan time.
Chapter High Speed Input Programming
C 12-5
Special Application
Considerations
(continued)
Test Single Scan Mode: When the SLC 150 processor unit is placed in
the Test-Single Scan mode and the HSI counter start rung is TRUE, the
HSI will count in real time and the accumulator will increment as it
would in the Run mode.
Disconnecting the HSI Module: The HSI module should not be
connected or disconnected when power is applied to the SLC 150
processor unit.
WARNING: Improper operation and damage to equipment or
personnel could occur if the HSI module is connected or
disconnected when power is applied to the SLC 150 processor unit.
Expansion Socket End Plug: The HSI module has an expansion
socket for the purpose of adding another HSI module or expansion unit
to your system. The HSI module is shipped with an end plug inserted in
this expansion socket. Do not remove this plug unless you are adding
another HSI module or an expansion unit to your system. Removing the
plug will cause a CPU fault, shutting down the processor in the Run
mode.
12 6
Chapter High Speed Input Programming
Application Example -
Two Step
Cut Off Operation
A high speed cut-off operation measures metal strips by counting pre
formed bumps as the metal strip is fed into the cut-off area. The bumps
pass a solid state sensor at the rate of 1000 bumps per second. Every
2000 bumps, the strip is cut. The counting process then resumes.
In the program below, an HSI counter is used to perform the counting
and cut-off operation. SQO 901 outputs at addresses Oil and 012 control
the feed motor and the cut-off saw motor. The counter is enabled only
when the cut-off saw is in the home position.
In step 0, the feed motor is energized, which feeds the metal strip. As the
strip is fed, the bumps are counted by the HSI counter. When 2000
counts are reached, SQO 901 advances to step 1. This lowers the cut-off
saw which cuts the strip and returns to the home position.
When the cut-off saw returns to its home position a limit switch at
address 001 is closed, initiating a single shot reset that resets the
process back to step 0. This single shot reset allows the feeding process
to resume and high speed input signals to be counted immediately. The
preset of 9999 for step 1 has been arbitrarily chosen and allows for over
feeding of the metal strip. The preset for step 1 could be set to any four
digit number except zero since the process is reset when the saw returns
home.
Figure 12.5
Home
Bumps are sensed by solid
state sensor, providing input
to HSI module
r
1
ttttiM
Stt'P _____________
Feed
+
Saw motion
Rung 1
Rung 2
Rung 3
001
910
901
{SQO)
HSI counter
instruction
Event
910
{SQO)'
901
Event-Driven
Group No.: 0
Mask Data: 0
Step 0 Data: 0
Step 0 Preset: 1
{rst)
1
RAC 9900
CLASSIFICATION:
-SQIH
-isQoH
ADDRESS: 901
TIME DRIVEN
M EVENT DRIVEN
GROUP NUMBER: 0
BIT ADDRESS DATA
PROGRAM
CODE
PRESET
VALUES
Bit Addresses-*
Mask Data -*
B A
Data
B
Data
A 018 017 016 015 014 013 012 011
0 0 0 0 0 0 1 : 1 0 3
Step Data -* 0 0 1 o ; 1 2 S 0 ! o ! o
1 1 0 0 2 9 ! 9 ! 9 ! 9
I____L
Masked addresses
t
Output address 011 controls feed
Output address 012 controls saw motion
Chapter High Speed Input Programming
12-7
Application Example -
Multiple Step
Position Control
Drill position and hole depth are controlled by counting high speed input
pulses from an encoder mounted on a feed motor. The feed motor turns a
lead screw which moves the drill forward and backward. As the feed
motor rotates, encoder pulses are fed into the HSI module at a rate of
5000 pulses per second.
Step 0 is the home position, with all outputs off. The preset of 9999 for
step 0 is arbitrarily chosen and allows for encoder movement without
advancing the sequencer step number. A push button at address 001
initiates the process by performing a single shot reset which moves the
process to step 1 where the feed motor is energized. Encoder pulses are
then counted by the HSI counter. After 9000 counts, the drill motor is
turned on. After another 2000 pulses, the drill bit reaches its proper
depth and the sequencer advances to step 3. Step 3 reverses the feed
motor, retracting the drill. After 2000 pulses the drill motor is turned
off. The drill continues to retract to its original position.
When the cycle is complete, the process returns to step 0 which is the
home position with all outputs off.
Figure 12.6
Feed
uviivn
Retract
Drill
Motor
Part
CLASSIFICATION:
HSQO-
m hsqo)-
Rung 1
Rung 2
Rung 3
ADDRESS: 901
001
910
-(sQo
910
901
-(RST)"
RAC 9901
901 901
Ak(sqo)
Event
Event-Driven
Group No.: 0
Mask Data: 0
Step0Data: 0
Step 0 Preset: 1
TIME DRIVEN
[xl EVENT DRIVEN
GROUP NUMBER: 0
BIT ADDRESS DATA
PROGRAM
CODE
PRESET
VALUES
Bit Addresses-*
Mask Data-*
B A
Data
B
Data
A
018 0 1 7 016 015 014 013 012 011
0 0 0 0 0 1 1 1 0 . 7
Step Data - * 0 0 0 0 0 0 0 0 0 0 0 9
!
9
! !
9
!
9
1 0 0 0 0 0 0 1 0 1 9
!
0
! ! o !
0
2 0 0 0 0 0 1 0 1 0 5 2
1
0
1

1
U
! !
9
!
0
3 0 0 0 0 0 1 1 0 0 6 2
o ! 0 i
0
4 0 0 0 0 0 0 1 0 0 2 9
J L U
0
J____ I
0 Masked addresses
t
Output address 011 controls
feed motor - forward
Output address 012 controls feed motor-reverse
Output address 013 controls drill motor
Chapter Shift Register
Instruction
General With the shift register instruction, status data enters an 8-bit register
and is automatically shifted thru the register from one bit address to the
next on a time- or event-driven basis. A typical application is with
conveyors, to monitor and control the flow of the individual parts. In
general, it can be used in the control of machines or processes where
parts are continually shifted from one position to the next.
You can program a shift register to shift status data either right or left.
In operation, the shift register instruction is executed each program
scan, and uses a ZCL zone to control the shifting process. A sequencer
instruction is used to control the shift rate. The unlatch instruction can
be used to set status bits from ON to OFF.
The shift register instruction is retentive. The ON/OFF status and the
position of data is retained if power to the processor unit is removed or if
the processor unit is switched from the Run mode to another mode.
Programming the Shift
Register Instruction
Acceptable addresses for shift registers are shown below. A shift right
register is assigned the address of its most significant bit. A shift left
register is assigned the address of its least significant bit.
Valid addresses include external output addresses and internal
addresses. Internal addresses can be used within your program or used
to obtain outputs, as required.
Figure 13.1
most significant bit
T
least significant bit
18 17 16 15 14 13 12
!1
8-bit register
18,118,218,318,418, 518,618,708,
716,724,732,740,748,756,764,772,
780,788,796,804,812,820,828,836,
844,852,860.
11,111,211,311,411,511,611,701,
709,717,725,733.741,749,757,765,
773.781,789,797,805,813,821,829,
837,845,853,861.
The shift register instruction is represented by the symbol -(SR)-. To
program this instruction, press SHIFT, -( )-, then the appropriate
numeric keys for the address (selected from the table above).
Display symbol for a shift right register: r
Display symbol for a shift left register: L
Display example: When the cursor is on a shift right
register instruction, address 018, rung 3, the output
energize LED will be lit and the display will show: r
Display example: When the cursor is on a shift left
register instruction, address Oil, rung 4, the output
energize LED will be lit and the display will show: L
IB 3
I I H
13-2
Chapter Shift Register Instruction
Event-Driven Shift Figure 13,2 is a ladder diagram of an event-driven shift right register.
Registers indicated in the figure. Rungs 2-3-4 consist of a shift right register
within a ZCL zone.
Each time instruction 001 in rung 1 goes from FALSE to TRUE, step 0 of
the sequencer is completed (AC PR) and the ZCL zone is TRUE for one
program scan. If instruction 002 is TRUE during this scan, rung 3 is
TRUE, and a 1 is shifted into the most significant bit address (18) of the
register; if instruction 002 is FALSE, a 0 is shifted into the register.
Simultaneously, all other status data in the register is shifted right to
the next address, with status data of bit 11 being shifted out of the
register:
Most Significant
bit address
I
18 17 16 15 14 13 12 11
1 orO
Status data shifts on each FALSE to TRU E transition of SQO
Figure 13.2
Event-Driven
Group No.: 0
Mask Data: 0
Step 0 Data: Any
Step 0 Preset: 1
Event-driven shift right register
Figure 13.2 could be changed to an event-driven shift left register
simply by assigning address 11 instead of 18 to the shift register
instruction in rung 3. Operation would be similar, with status data
shifted into the least significant bit address, and status data of bit 18
shifted out of the register:
Least Significant
bit address
i
18 17 16 15 14 13 12 11
Status data shifts on each FALSE to TRUE transition of SQO
1 orO
Chapter Shift Register Instruction
13-3
Time-Driven Shift
Registers
Figure 13.3 is a ladder diagram of a time-driven shift right register.
Note the similarity to the event-driven shift register of Figure 13.2.
Rung 1 is a 1-step, time-driven sequencer. Programmed data is
indicated in the figure; set the PR value to the desired shift rate. Rungs
2-3-4 consist of a shift right register within a ZCL zone.
Step 0 of the sequencer is completed each time the AC value reaches the
PR value. The ZCL zone is then TRUE for one program scan. If
instruction 001 is TRUE during this scan, rung 3 is TRUE, and a 1 is
shifted into the most significant bit address (18) of the register; if
instruction 001 is FALSE, a 0 is shifted into the register.
Simultaneously, all other status data in the register is shifted right to
the next address, with status data of bit 11 being shifted out of the
register:
Most Significant
bit address
I
1 or (
18 17 16 15 14 13 12 11
F 4- -
Clock rate = SQO Preset
Figure 13.3
Time-Driven
Group No.: 0
Mask Data: 0
Step 0 Data: Any
Step 0 Preset:
Shift clock rate
Time-driven shift right register
Figure 13.3 could be changed to a time-driven shift left register simply
by assigning address 11 instead of 18 to the shift register instruction in
rung 3. Operation would be similar, with status data shifted into the
least significant bit address, and status data of bit 18 shifted out of the
register:
Least Significant
bit address
i
18 17 16 15 14 13 12 11
1 or 0
Clock rate = SQO Preset
13-4
Chapter Shift Register instruction
Cascading You can cascade shift register instructions in order to shift more than 8
Shift Registers bits of data. In the 16-bit shift left register of Figure 13.4, status data is
entered into shift register 701. Bit 708 of this register shifts data into
register 709:
716 715 714 713 712 711 710 709 708 707 706 705 704 703 702 701
Status data shifts on each FALSE to TRU E transition of SQO
Important: The rung containing the shift register into which data is
entered must follow the rung containing the second shift register. Thus,
shift register 701 (rung 4) follows shift register 709 (rung 3).
Figure 13.4
Rung 1
Rung 2
Rung 3
Rung 4
Rung 5
001
901
708
002
901 ,
-{SQO)
-izci)----
709
(SR)
701
-($R) "
-{ZCL)-----
Event-Driven
Group No.: 0
Mask Data: 0
Step 0 Data: Any
Step 0 Preset: 1
A 16-bit event-driven shift left register
Chapter
Circulating Shift
Register
Shift Register Instruction
13-5
Figure 13.5 is an example of a circulating time-driven shift left register.
Status data is entered by instruction 001 (rung 3) and shifted left from
bit address 701 to bit address 708; bit address 708 is used in rung 3 to
shift the status data back into bit address 701, and the cycle is repeated:
708 707 706 705 704 703 702 701
Clock rate = SQO Preset
Figure 13.5
Time-Driven
Group No.: 0
Mask Data: 0
Step 0 Data: Any
Step 0 Preset:
Shift clock rate
* Data circulated from bit address 708 to bit address
701 would b overridden by data shifted into bit
address 701 by Examine ON instruction 001.
An 8-bit Circulating shift register
13-6
Chapter Shift Register Instruction
Example: Using Shift Rungs 6 thru 9 in Figure 13.6 show how you can use the various bit
Register Outputs addresses within the shift register to produce external outputs. Note
that these rungs are placed outside the ZCL zone.
Status data is entered by instruction 002 in rung 3. The Ts entered into
the circulating register can be changed to 0s with instruction 003 in
rung 5, which unlatches bit address 701.
Outputs at these bit addresses
(Rungs 6, 7, 8, 9 in Fig 11)
1
708 707
; ;
706 705 704
T
703 702 701
- N- -
Status data shifts on each FALSE to TRUE transition of SQO
Figure 13.6
Event-Driven
Group No.: 0
(Vtask Data: 0
StepO Data: Any
Step 0 Preset: 1
Circulating shift left register using outputs for
bit addresses 703,705,706, and 708
Chapter Special Internal
Instructions
Genera/ This chapter explains how to use the following special internal
instructions:
P^St^esS'
* - *'4-4-*-^'' sassiffii
876 Auto/Man switch. This address bit is ON when the Auto/Man
switch of the processor unit is in the Auto position.
868 Program initialization instruction. Used with timers, counters,
and latch instructions to set initial conditions on power-up.
SLC100
and
SLC15Q
867 TCAT power-up. Used with the Timer Counter Access Terminal
to display a selected timer/counter/sequencer address on
power-up.
100 Breakpoint instruction. Used fof debugging and trouble
shooting. When a rung containing this instruction is TRUE, the
processor will automatically halt its program scan, switch from
the Run to the Test-Single Scan mode, and turn all outputs off.
SLC150
only
864 Programmable EEPROM auto-load. Used to automatically load
the EEPROM program in the processor RAM when the
processor detects a memory checksum error (capacitor or
battery back-up drain, or processor malfunction).
865 Battery status. This bit is ON when the battery voltage is
normal The bit is set OFF when battery voltage drops below a
certain threshold. If a battery is not used, the bit remains ON.
866 Triac zero-cross turn-on. Output instruction, used to
synchronize triac outputs with the AC line.
Auto-Man Switch
-Address 876
This instruction allows you to examine the status of the Auto/Man
switch of the processor:
876 876
Hh
TRUE when the switch
is in the Auto position
FALSE when the switch
is in the Auto position
Chapter
14
14-2
Spedai internal instructions
Program Initialization This is an internal examine instruction you can use to initialize your
- Address 868 program to a known state on power-up. It can be used to initialize
timers, counters, sequencers, and latch instructions.
The bit address of the instruction is 868. This bit is set ON for the first
and only the first program scan under either of the following conditions:
1. Power is switched on to the processor unit in the Run or Test modes.
2. The programmer is used to place the processor unit in the Run or Test
modes.
The following examples show you how to use the program initialization
instruction to program non-retentive timers and a non-retentive latch.
You will also be shown how to initialize an up-down counter and a latch
instruction. Always use instruction 868 in the first rung of your
program so that program initialization will occur properly.
Non-Retentive Latch A ladder diagram for a non-retentive latch instruction is shown in
Figure 14.1. On power-up, instruction 868 in rung 1 will go TRUE for
the first scan, so that instruction 701 will be unlatched initially.
Examine ON instruction 001 in rung 1 is used to unlatch instruction 701
during program execution.
Figure 14.1
Rung 1
Rung 2
001
868
701
-iu
002
701
701
011
Rung 3
Chapter
14
Non-Retentive Timers
Spedai Internai instructions
14-3
Figure 14.2 shows a non-retentive RTO timer. On power-up, instruction
868 in rung 1 will be TRUE for the first scan, so that the timer will be
reset initially. Note that rung 1 also contains an Examine OFF
instruction having the same address (001) as the Examine ON
instruction in rung 2. This Examine OFF instruction resets the timer
when rung 2 goes FALSE.
The figure also illustrates a non-retentive RTF timer. In this case, an
Examine ON instruction (001) is used in the reset rung (1). Rung order
is important with the non-retentive RTF timer. The RST rung must
precede the RTF rung.
Figure 14.2
Chapter
14
Special Internal Instructions
14-4
Initializing an Up-Down
Counter
Initializing a Latch
Instruction
The figure below shows how you can initialize an up-down counter. On
power-up, instruction 868 in rung 1 will go TRUE for the first scan,
resetting the counter to 5, which is between the upper limit of 10 and the
lower limit of 0.
Figure 14.3
Rung 1
Rung 2
Rung 3
Rung 4
Rung S
001
860
002
003
901
I
9S1
951
-^Hr
901
(RST) ' '
RAC 0005
901
-(cru)
PR 0010
901
-(ctd)
PR 0010
011
012
The figure below shows how you can initialize a latch instruction. On
power-up, instruction 868 in rung 1 will go TRUE for the first scan,
latching output Oil.
Figure 14.4
Rung 1
Rung 2
Chapter
TCAT Power-Up
-Address 867
Breakpoint Instruction
-Address 100
Spedai internal Instructions
14-5
If you are using a TCAT (Timer Counter Access Terminal), you can use
this Examine OFF instruction to automatically display any
timer/counter/sequencer address you choose on power-up (instead of
scanning the timer/counter/sequencer addresses). An example is shown
below.
Figure 14.5
On power-up, TCAT goes directly
to rung containing instruction 867
PROGRAMMING NOTE - Instruction 867 should be an Examine OFF,
programmed in series with the rung containing the instruction you want
displayed on power-up. (You can program instruction 867 anywhere in the
rung, to the left of the timer/counter/sequencer instruction.)
This is an output instruction at address 100. You can use it to pin-point
suspected problem areas in your program during debugging and
troubleshooting procedures.
When the rung containing the breakpoint output instruction is TRUE,
the processor will halt the program scan, automatically switch from the
Run mode to the Test-Single Scan mode, and turn all outputs OFF.
Use the breakpoint instruction as follows:
1. Decide on what point in your program you should insert the
breakpoint instruction. This should be directly after the part of your
ladder program that you suspect is not operating correctly.
2. Program the breakpoint rung. The conditions that make the
breakpoint output instruction TRUE should be the conditions that
you suspect would cause your program to malfunction. An example is
shown on Page 14-6.
3. Place the processor in the Run mode and test your program. If the
processor halts and outputs are disabled, the breakpoint output rung
is TRUE.
4. Connect the pocket programmer. It will automatically identify the
breakpoint rung number. (If you are using the SLC Personal
Computer Software, it will display a message telling you that a
breakpoint -(BPT)- has occurred at a specific rung number.)
5. Correct the program malfunction and delete the breakpoint rung.
A breakpoint output rung can be programmed as many times as you
need it in your program.
Important: Do not use the breakpoint output instruction for emergency
stop situations. We strongly recommend that you use a hard-wired
master control relay to provide emergency I/O power shutdown.
14-6
Chapter Special Internal Instructions
Breakpoint Instruction An example of how you might use the breakpoint instruction:
-Address 100
(continued) Operation B: Refer to the program below. When a series of five
external inputs (represented in the program by instructions 001 thru
005) are closed, output instruction Oil is energized, causing assembly
operation B to be performed. When assembly B is completed, instruction
006 goes FALSE, de-energizing output Oil. The external inputs are
then opened and the next operation in the assembly process is initiated.
Operation
Enable Conditions Complete Operation B
The Problem: Occasionally, operation B is not performed because one
of the external inputs does not remain closed for the duration of the
assembly process. Determining which of the five external inputs is at
fault is a difficult and time-consuming troubleshooting procedure.
The Solution: Breakpoint rungs 2 thru 6 are inserted into the user
program:
Rung
Rung
Rung
Rung
Rung
Rung
During operation B, rung 1 will be TRUE and the breakpoint rungs will
be FALSE. If an external input opens before assembly operation B is
completed, one of the breakpoint rungs will go TRUE. This will cause
the processor to switch from the Run mode to the Test Single Scan mode,
disabling all outputs. The pocket programmer will identify the
breakpoint rung number, revealing which external input is causing the
problem.
If operation B is completed without a problem, program execution
continues as normal.
Chapter
Programmable
EEPROM Auto-Load
-SLC150 Only
Battery Status
-SLC150 Only
Special Internal Instructions
14-7
With the SLC 150 processor unit, you can use address 864 in your
program to automatically load the EEPROM program in the processor
RAM when the processor detects a memory checksum error. Such errors
are detected if memory data is altered or lost due to capacitor back-up
drain, battery back-up drain, or processor malfunction. It works like
this:
1. Enter the following unconditional rung as Rung 1 of your program:
Rung 1
2. Store the program in the EEPROM. This is your "back-up program.
3. If a memory problem occurs and the processor unit detects a memory
error (codes 5 thru 8), recycle power. The EEPROM program will be
automatically loaded in the processor RAM, clearing the error.
Refer to Chapter 17 for further information on the Auto-Load Procedure.
Important: Keep in mind that when the auto-load occurs, the I/O table
data is cleared. All retentive instructions (latches, timers, counters,
sequencers) will be reset to their initial states.
If you are using the battery back-up option with the SLC 150, you can
use the status bit at address 865 to energize a "Battery Low indicator
when the battery voltage falls below a certain threshold. This threshold
voltage level will support the processor memory for approximately 2
weeks.
The figure below indicates how you might use this battery status
instruction. Battery low indication is provided only when power is
applied to the processor unit.
Figure 14.6
Battery status bit
Use an external output address to
indicate a "Battery Low" condition.
Arbitrarily, we are using address 011.
Rung is FALSE when battery voltage is normal. Rung goes
TRUE when battery voltage drops below a certain threshold.
14-8
Chapter Special internal instructions
TriacZero-Cross Turn-On This is an output energize instruction at address 866. It is used to
-SLC150 Only synchronize triac outputs with the AC line to help minimize noise
generated when switching loads. To achieve zero-cross turn-on, you
must use a common power source for the processor unit power supply
and the output circuits.
The figure below indicates how to use the triac zero-cross turn-on
instruction. NOTE: When this instruction is in effect, your program
scan will be synchronized with the AC line zero-cross. This means that
your scan time will be 8.3 msec (or some multiple of 8.3 msec) at 60 Hz,
and 10 msec (or some multiple of 10 msec) at 50 Hz.
Caution: Make certain that the scan time resulting from using the
zero-cross turn-on instruction will not adversely affect your program
execution. This is especially important if you are using any of the
fine time base instructions discussed in Chapter 8.
Figure 14.7
Arbitrary conditional Zero-Cross Turn-On
instruction
\ /
[ XXX
H'-------------------
866 ~ I
< H
Zero-cross turn-on is in effect when this rung is made TRUE.
The rung can be placed anywhere in your program.
Alternate method: Zero-cross turn-on is in effect at all times.
Chapter Program
Editing
General In the following paragraphs, you will learn how to edit your program
using the NEXT and LAST keys (cursor control), the SEARCH key, and
the REMOVE and INSERT keys. The following keystroke examples do
not cover all of the editing techniques. Refer to Pages 15-10,15-11, and
15-12 for a comprehensive list.
Program Editing with the TCAT and PC Software: Editing
techniques possible with the TCAT (Timer Counter Access Terminal)
and the SLC Personal Computer Software are described in the
respective Users Manuals, Publications 1745-850 and 1745-825.
15
15-2
Chapter Program Editing
Cursor Control The programmer indicates the cursor location by the particular instruc
tion LED lit, the address number, and the rung number. The cursor
location is moved by pressing the NEXT key or the LAST key.
Each time you press the NEXT key, the cursor moves to the following
instruction, that is, one instruction to the right. Each time you press the
LAST key, the cursor moves to the preceding instruction, one
instruction to the left. You can use this method to move from instruction
to instruction thru the rungs of your program.
When the cursor is positioned on a timer, counter or sequencer
instruction, pressing the NEXT key displays the data associated with
that instruction (PR value, AC value, and other data), in the order in
which it was entered.
You can move the cursor to the start of the next rung by pressing RUNG,
NEXT, or to the start of the preceding rung by pressing RUNG, LAST.
The keystroke example of Figure 15.1 (following page) illustrates use of
the NEXT and LAST keys.
Chapter
Keystroke Example
-Cursor Control
Program Editing
15-3
Cursor control was explained on Page 15-2. The keystroke example
below will show you how to use the NEXT and LAST keys to move the
cursor thru the program and access data.
Figure 15.1..................... ......................................... .......... ........... .
Keystroke Example - Program the ladder diagram below.
Rung 1
Rung 2
Rung 3
001 002 003
HIHkIh
011
004 005
Ak-Hh
006
901
~(rto)'
PR 50.0
901
~<RST)------
RAC 0000
Ladder Diagram
f | ; J v * i ' l l J S if^
* w #** * it^r i
l ! ! W i l h' # * ' * * M l! * * * it . i*
tifiif s Mt pmiM llltiffS I i , * *
LAST
7 times
-][- 3 1
You have located the cursor on the
Examine ON instruction in rung 1.
NEXT
2 times
-]/[ h H 2
The cursor is ndw on the Examine OFF .
instruction in rung 2. The start rung *
symbol shown at the left in the
display indicates this is the first
instruction in the rung.
RUNG,
NEXT
-][- h 5 3
You have moved the cursor to the
first instruction in rung 3.
RUNG,
LAST
-1/h
h H 2
the cursor has returned to the first
instruction in rung 2.
NEXT
2 times
-(RTO)- 3D 1 2
You have moved the cursor to the
RTO instruction in rung 2.
NEXT (RTO)- 5.D P r -
The display is showing the PR value
you entered earlier.
!
NEXT
-] h 1- E 3
The cursor has moved to the next
instruction in your program.
LAST -(RTO)-
;
3D 1
The cursor has moved back to the
RTO instruction. Notice that you did- /
not return to the PR value. You must :
use the NEXT key to access data.
Program editing techniques are summarized on Pages 15-10,15-11,15-12.
15-4
Chapter Program Editing
Search Function The search function can be used to locate:
1. A specific instruction.
2. A specific rung number.
3. The start or end of a program.
4. The start or end of a rung.
5. A specific sequencer step.
When searching for a specific instruction, the search begins at the cursor
location; you can choose the start of the program, or any other point in
the program. When the instruction is found, press SEARCH, ENTER to
find the next occurrence of the instruction.
To move the cursor to a specific rung, you press SEARCH, RUNG, then
the rung number. Specifying rung number 1 will locate the cursor at the
beginning of the program; rung number 999 will locate the cursor at the
end of the program.
To move to the start of a rung, press SEARCH, LAST. To move to the
end of the rung, press SEARCH, NEXT.
To move to a specific sequencer step, locate the cursor on any sequencer
data, then press SEARCH, the step number, ENTER.
The keystroke example of Figure 15.2 illustrates the use of the SEARCH
key.
Chapter
Keystroke Example
-Search Function
Program Editing
15-5
The search function was explained on Page 15-4. The keystroke
example below will show you how to use the SEARCH key to find a
specific instruction, the start of the program, and the end of the
program.
Figure 15.2
Keystroke Exampie - Program the ladder diagram below.
Rung 1
Rung 2
ogi 002
011
003
004 003
HI----------
012
< )--------
Ladder Diagram
r # - ' # ' f i r i i ^^ -|f l-J -^Jl
0/0 W va 'a* i i si m- .-.iS m
& t^^ : '' ^ .* ^^ : . * 4m % ?jh f?
:
^'W5l 0 -- -m'm.
:
i! is1 $ ^ W^/g: - a i ? /fi fpP
SEARCH
r : . ^ i .
5 r c h '
You are in asearch operation.
-]/[-
An Examine OFF instruction is
specified. Dashesare prompting
you for an address.
3 -l/[-
__3
Address 003 is entered.
ENTER -]/[- :
. . . . . .
3
\ I
Search begins at cursor location.
The rung number is displayed when
the instruction is found.
SEARCH,
ENTER
-]/[-
: ; 3 2
Pressing SEARCH, ENTER will locate
the next occurrence of the specified
instruction.
SEARCH
5 r c h
You have initiated a new search
operation.
RUNG, 1 __ i
You are searching for rung 1, the
start of your program.
ENTER
-] i- : h I I
Search iscompteted. Thecursor is
on the first instruction of rung 1.
SEARCH,
RUNG,
9,9,9
3 3 3 ;
To find the end of the program, you
enter a rung number which is
certain to exceed the number of
rungs in your program. 999 is a good
choice.
ENTER
015 End
The cursor is at the end of your
program.
Program editing techniques are summarized on Pages 15-10,15-11,15-12.
15-6
Chapter Program Editing
Insert end Remove While in the Program mode, you can insert and remove instructions,
Functions branches, rungs, or sequencer steps by using the INSERT and REMOVE
keys. The keys also allow you to copy a rung and insert it anywhere in
your program. These editing techniques are summarized on Pages 15-11
and 15-12.
The keystroke examples of Figures 15.3,15.4, and 15.5 illustrate how to
insert and remove instructions, branches, and rungs.
Figure 15.3
Keystroke Example - Program the ladder diagram below.The
keystroke example vyill show you howto insert and remove an
instruction.
Insert an Examine OFF
instruction, address 002
001
Rung 1
015
< y
Ladder Diagram
LAST -( j- :
15 !
The cursor is positioned on the
instruction following the point
where the new instruction is to be.
INSERT
m
Display is prompting you to insert an
instruction.
-] /[- -l/[-
... i.
Prompt for an address.
"
:
2 ;
1
Address 002 is entered.
ENTER -( )-
15 i
The instruction has been entered.
The cursor has moved to the next
instruction.
LAST -]/[- 1
Cursor is positioned on the newly
entered instruction. Now we'll
remove it.
REMOVE -l/[-
rE
Display indicatesthe remove
function.
ENTER A )- 15 1
The instruction has been removed:
The cursor has moved to the next
instruction.
LAST -] i~ H 1 I
The cursor has moved to the first
instruction in the rung, verifying the
removal of the Examine OFF
instruction.
Program editing techniques are summarized on Pages 15-10,15-11,15-12.
Chapter Program Editing
15-7
Figure 15.4
Keystroke Example - Program these rungs. The keystroke exf
remove branches.
1 n
1
M
2
,
01
V I
R
ung 1
Rung 1 i------------- 1 || |----------------------- ( )
f t
I 003 !
1
--------- 1 |-------- . Insert, then
remove
inSj
Example 1
Example 1:
imple will show you how to insert and
I 001 002 011 |
L____l l__ l l__________-_____ t \____I
r
ini
i
ert ' *
---------- 1 ,-----------
003 004
HIIH
y 005 4
Example 2
1
y
[
t
0
1IS
lljpg
I
BMPfl
LAST 3times -1-
h 1 1
We must first insert a branch open instruction preceding instruction 001.
Cursor s on instruction 001.
INSERT, T T bra I Display indicates in. Insert, then bro, branch open.
ENTER -] [-
1 1 Branch open instruction entered. Cursor moves to next instruction.
NEXT, NEXT -( )-
11 !
Cursor is nowon the instruction following the point where the new
branch will be inserted.
INSERT,
T
T bra 1
The branch open instruction is entered. We can now enter instruction
003. Note: Any number of examine instructions could be entered
without pressing ENTER after each one.
-l E-,3 -1 h
__3 1 Examine ON, address003 has been entered.
T
J
bnd 1
To complete the branch, we've pressed the branch close key. Display
bnd indicates branch end.
ENTER
-( )-
1 i 1 Cursor has moved to the instruction following the branch close.
LAST, LAST
-H-
3 1
Cursor is on the examine instruction in the branch we just entered. We
will now remove this branch.
REMOVE,
ENTER
J bnd i
The examine instruction is removed. Cursor is on the branch close. This
instruction and the 2 branch open instructions in the program must be
removed. We can do this very simply, with 2 keystrokes.
MODE J
rE P EEH
First, we attempt to move off the rung. The display indicates a branch
error E64 (short circuit). It is asking whether we want to remove it.
ENTER
pr
D
g g
Next, we press ENTER, which removes the branch instructions. We could
also have removed the 3 branch instructions individually.
I Example 2:
lil
j i |BB8
LAST, LAST T
bnd 1
In this case, the instruction beginning the new branch (003) is already
preceded by a branch open instruction. Begin by moving the cursor to
the instruction following the point where the branch will be inserted.
INSERT, T T bra 1 Display indicates branch open. We can now enter instruction 005.
-H-,5 - h
__5 i
Examine ON, address 005 has been entered.
ENTER T
bnd 1
New branch is entered. Cursor moves to the next instruction.
15-8
Chapter Program Editing
Insert and Remove
Functions
(continued)
Figure 15.5
Keystroke Example - Program the ladder diagram below. The
keystroke example will show you how to insert and remove a
rung.
001 002
Rung 1 ------1 ------------- (
005
013
Rung 2
003 004
....Tk-------- * b
Ladder Diagram
012
LAST ( )"
IE ; : E;
:
You can move the cursor to any in
struction in the rung which follows
the location where you will insert
the new rung. The cursor is located
on the output instruction in rung 2.
INSERT,
RUNG
i n r
The display is prompting you to
insert a rung.
-1 K5 : l- "
i!L
T
I
r
u
Examine ON instruction is inserted.
This will be rung 2, as indicated.
H )-. 1.3 -( )-
iL
U
r
u
The output instruction is entered.
NEXT -)/{-
t
L
U
L
U
Cursor has moved to the first
instruction in rung 3. This was
formerly rung 2.
LAST ; -(
T
U
m
Cursor is back to the output
instruction of the newly entered
rung. We'H remove this rung.
REMOVE,
RUNG
-( )-
rE r
Display is prompting you to remove
a rung.
ENTER
H 3 E
Rung is removed. Cursor has
moved to the following rung,
which is now rung 2 again.
Program editing techniques are summarized on Pages 15-10,15-11,15-12.
Chapter Program Editing ^ ^
Changing Instructions
in the Program Mode
With the CANCEL CMD key, you can easily change an instruction,
address, or data while the cursor is still located on the instruction.
You can also change an instruction, address, or data after a rung or
program is completed. Just locate the cursor on the instruction to be
changed, then enter a new instruction, address, and data. Refer to the
program editing summary on Pages 15-11 and 15-12.
Protecting the PR Value
of Timers, Counters,
and Sequencers
The PRT key allows you to protect the PR value. This prevents anyone
from changing the PR value while the processor is in the Run or Test
modes. In the case of timers and counters, neither the PR value nor the
AC value can be changed while the processor is in the Run or Test
modes.
You can change a PR value in the Program mode even if it is protected.
But if you change a protected PR value, you must protect it again after
changing it. Refer to the program editing techniques on Page 15-12.
Deleting an Entire Selecting mode 1, Clear Memory, allows you to delete your entire
Program program. Refer to the program editing summary on Page 15-11.
Chapter
15
Program Editing
15- W
Program Editing
Techniques
You can use the following procedures to move about your program
while you are in the Program, Run or Test modes.
Move to the following instruction. NEXT
Handy when you want to move to a nearby instruction or
review your program instruction-by-instruction.
Move to the previous instruction. LAST
Move to the following rung. RUNG, NEXT
If the cursor is on a branch or condition instruction, you
wi)l move to the start of the next rung. If the cursor son
the output, you will move to the output of the next rung.
Move to the previous rung. RUNG, LAST
if the cursor is on a branch or condition instruction, you
will move to the start of the last rung. If the cursor is on
the output, you will move to the output of the last rung.
Move to the start of the rung. SEARCH, LAST This saves time when the rung is complex, where you
would otherwise have to press LAST or NEXT many times
to go thru the instructions and/or data.
Move to the end of the rung. SEARCH,NEXT
Move to a specific rung,
number 5 for example. Two
methods can be used.
RUNG, 5, ENTER
If the cursor son a branch or condition instruction, you
will move to the start of rung 5. If the cursor son the
output, you will move to the output of rung 5,
SEARCH, RUNG,
5, ENTER
You will move to the start of rung 5.
Move to the start of the program.
SEARCH, RUNG,
1, ENTER
You will move to the start of rung 1.
Move to the end of the program.
SEARCH, RUNG,
9,9,9, ENTER
You will move to the end statement after the last rung.
Move to a specific instruction,
-] [-, 001 for example.
SEARCH,-] [-,1,
ENTER
Search begins at cursor location. If the instruction is not
found in the program, n F is displayed.
Move to next occurrence of the
specific instruction.
SEARCH,ENTER |
i
If the instruction occurs only once in the program, the
display of the first occurrence reappears.
Chapter Program Editing
15-11
Program Editing You can use the following procedures to add, delete, or change
TechnigUGS instructions and rungs while you are in the Program mode.
(continued)
Correct an error while
entering an instruction,
;
address, or data.
You can correct errors as long T
as the Cursor position has not
been moved (pressing ENTER,
NEXT, LAST, or another instruc- -
tion key moves the cursor).
cAtoi cMo :
: (as often as
; ; required)
Each time you press the key, a
f
previous keystroke is "wiped ;
out". An instruction and its
address can be canceled and
changed in this way.
Insertan instruction in a
completed rung.
Example: -] [-, 008
Locate the cursor on the ' ' "
instruction foI(ovying the point...
where you want to add the ;
new instruction to the rung.
INSERT,-] [-.
; .;< ; 8, ENTER
* Cursor moves to the instruction
following the new instruction.
Delete art examine
instruction.
Locate the cursor on the ;!
instruction to be deleted. ;
REMOVI*
, < ENTER / ;;
Cursor moves to the instruction
f which followed the deleted !
instruction.
1
! .
Change an instruction
or its address in a ;
completed rung. Example:
-(RTO)- 901 to -( )-, 012
Locate the cursor on the
instruction to be changed.
)-, 1,2,
ENTER
We have changed the
;

instruction and its address
Cursor moves to the following
instruction.
Another example:
-] [- 002 to-J [-, 702
Locate the cursor on the .
instruction to be changed-
-] I-, 7,0,2,
ENTER
We have changed the address
only.
Insert or remove a branch. ; Refertothekeystroke example of Figure 15.4 on Page 15-7.
Inserta rung. Example:
003 016
-1 M )- .
Locate the cursor on any
instruction in the rung which ,
follows the point where you
want to. ehter the opw rung.
INSERT, RUNG,
1,6, NEXT
Rung is inserted. Cursor has
mdvdtothehextTuhg: Rung
;

numbers have been - ?
putomatiCAlty changed.
Add a rung to the end of
the program.
Locate the cursor on the End
display. :
-] E-3,-( K
1,6, ENTER
We have entered the example
rung at the end of the program.
Delete a rung.
Locate the cursor on any
instruction in the rung you
, want to delete. /;
:
REMOVE,
RUNG, ENTER
Rung is removed. Cursor has
moved to the following rung.
Copy a rung. Example:
Insert a copy of rung 2
after rung 5.
Locate the cursor on any
instruction in rung 2.
REMOVE,
RUNG, INSERT,
6, ENTER
Rung 2 is repeated and placed
after rung5rThefolfowihg
rungsare re-numbered
accordingly.
Delete your
entire program.
(Select Clear Memory,
" mode 1.)
We will assume you are entered
in the Program, Run, or Test
mode. Cursor can be on any
instruction in the program.
:
;
MODE, 1,
ENTER
Thieipromptmessage Sure?,
g i vesy o u t heopp o rtu n ityto
, change your mind. You would
press CANCE L OVID to avoid
" clearing ydurprogfarp."
ENTER
You haveautomatically enterd
the Program mode. 885 words
(SLC100) or 1200 words (SLC
150) of m emory are avail able
.' to you / . ,,..
: ;
;
15-12
Chapter Program Editing
Program Editing
Techniques
(continued)
Use the following procedures to change or protect timer/counter data
while you are in the Program mode. The table also lists procedures for
changing, protecting, adding and deleting sequencer data.
Change the PR value of a
timer or counter. Example:
change timer PR to 20.0.
Locate the cursor on the
PR value.
2,0,0,
ENTER
Value is changed to 20.0 sec.
Cursor has moved to the next in
struction. NOTE: If PR value was
protected, you must protect it
again after changing the value.
Protect the PR val ue of a
timer or counter (this also
protects AC value).
Locate the cursor on the
PR value.
SHIFT,
PRT
Cursor moves to next instruc
tion. The PRT LED will be lit
while cursor is on the PR value
(Program, Run, Test modes) and
the AC value (Run, Test modes).
Remove protection
from the PR value.
Locate the cursor on the
PR value.
UNPRT
PR and AC values have returned
to the unprotected state.
Change the RAC value of
the RST instruction.
Example: change RAC to 9.
Locate the cursor on the
RAC value.
9, ENTER
Value is changed. Cursor has
moved to the next instruction.
. l.i i.f i '
* ixi'IP-
iv'M
ri-L"
wsmmk
Access data in a
specific step. Example:
access data in step 5.
Cursor can be located on
sequencer group, mask, step,
or PR data.
SEARCH,
5, ENTER
Cursor has moved to the step
data of step 5.
Change group number,
mask data, step
data, or PR values.
Example: change step
data for step 5 to 5,7.
Locate the cursor on step 5.
Display shows current data and
d 5.
5,7,
ENTER
Value is changed to 5, 7. Cursor
has moved to PR value of step 5.
Other data is changed in this
same way. Just locate cursor on
data, enter new data, and press
ENTER.
Protect the PR val ue of a
sequencer step.
Locate the cursor on the
PR value of the step.
SHIFT,
PRT
Cursor moves to next instruc
tion. PRT LED will be lit while
cursor is on protected PR value
(Program, Run, Test modes).
Remove protection
from the PR value.
Locate the cursor on the
PR value of the step.
UNPRT
The PR value has returned to the
unprotected state.
Add a step after the final
step. Example: step data
of 7,3; PR of
1.0 second.
Locate the cursor on the PR
data for the final step.
INSERT, NEXT,
7,3, ENTER, 1,0,
ENTER, ENTER
New step is added. You can add
as many steps as you want
before pressing the final ENTER.
Insert a step somewhere
before the final step.
Locate cursor on the PR data of
the step following the point
where you will insert a step.
INSERT, 7,3,
ENTER, 1,0,
ENTER
We have added the same data as
in the example above. Cursor
has moved to the next step.
Delete a step.
Locate cursor on the step data
or PR value of the step to be
deleted.
REMOVE,
ENTER
Step is removed. Following
steps are re-numbered.
Chapter
Generai
Force Function
On-Line
Data Control
With the controller in the Run or Test mode, you can monitor, control,
and change your program. This is referred to as On-Line Data Control.
It includes:
Forcing external I/O addresses.
Monitoring timer, counter, and sequencer data.
Changing PR, AC, and RAC values.
WARNING: Before you force external I/O or change data,
investigate the effects on machine operation to avoid possible
personal injury and equipment damage.
On-Line Data Control with the TCAT and PC Software: On-line
data control techniques possible with the TCAT (Timer Counter Access
Terminal) and the SLC Personal Computer Software are described in
the respective Users Manuals, Publications 1745-850 and 1745-825.
This function (FRC ON and FRC OFF keys) can be used in the Run and
Test modes to force an external I/O address to an ON or OFF state
regardless of its actual status. This function is very helpful in start-up
and troubleshooting procedures.
Forcing an input address: When you force an input address, you are
forcing the status bit of the instruction at the I/O address to an ON or
OFF state. The program scan records this, and the program is executed
with this forced status regardless of the actual ON/OFF status of the
input device. This is illustrated in Figure 16.1.
Figure 16.1
Address 03 is forced ON
\
003
1
i j - ; ,:.r
015
" ' i - V-____ !
; V I
Bit forced
ON
TRUE
015
I I ::
016
( \______
! I
{ r
TRUE
TRUE
Input Device
O-
Input Terminals (SLC 100)
/
Address 003
Output Device
Address 015
Address 016
Output Terminals
(SLC 100)
Forcing an input address. The program is
executed as if the input device were actually ON.
16 16-2
Chapter On-Line Data Control
Force Function Forcing an output address: In this case, we are forcing only the
(continued) output terminal to an ON or OFF state. The status bit of the output
instruction at the address is not affected. Refer to Figure 16.2.
A forced I/O address will be retained in memory when any of the
following occurs: 1) A power outage; 2) The mode is changed from Run;
3) The pocket programmer is disconnected. A forced I/O address will not
be retained if you enter the Program mode and make a change, or if a
processor fault is detected.
Figure 16.3 on the following page shows the keystrokes used for forcing
I/O addresses.
Forcing sequencer I /O bit addresses: These programmed I/O
addresses cannot be accessed in the user program, but they can be forced
ON or OFF.
Example: To force sequencer output bit address 016 ON, press INSERT,
-( )-, 1, 6, ENTER, SHIFT, FRC ON. To remove the force, press
REMOVE, -( )-, 1, 6, SHIFT, FRC ON, ENTER. To remove all forces in
the program, press REMOVE, ENTER.
Fi gure 16. 2
Address 015 is forced ON
003
, II
015
_____( \______
11 V I
FALSE Bremains
OFF
015
I t
016
/ A
II
\ r
FALSE FALSE
Input Terminals (SLC100)
Output Device
Forced-ON terminal
(SLC 100)
Forcing an output address. The output device associated with the
forced output address is turned ON. The status bit is not affected.
TRUE-FALSE With the controller in the Run or Test mode, you can monitor the
Status Indicator TRUE/FALSE status of an instruction. The ON LED of the programmer
is lit when the cursored instruction is TRUE, and not lit when the
instruction is FALSE. Remember that when you force an output
address, only the output terminal is forced; the output instruction is not
affected, and therefore the ON LED remains off.
Figure 16.3 indicates how the ON LED functions.
Chapter On-Line Data Control
16-3
Figure 16.3
Keystroke Example - Forcing instruction addresses. Program the ladder
diagram at the right. Read the following information before going thru
the keystroke example. Note that the ON LED and the force function are
effective in the Run and Test modes only.
ON LED: Indicates whether the cursored instruction ts TRUE or FALSE. The
LED is lit when the instruction is TRUE and not lit when it is FALSE. The LED
is not lit when an output terminal is forced.
FORCE LED: This LED is continuously lit whenever one or more instructions
in the program are forced ON or OFF.
FORCE ON function key: Pressing this key will force the status bit address
of the cursored instruction to the ON state (except for output addresses). If
the status bit was already ON, it will be held ON until the force is removed.
FORCE OFF function key: Pressing this key will force the status bit address
of the cursored instruction to the OFF state. If the status bit was already
OFF, it will be held OFF until the force is removed.
Rung 1
Rung 2
Rung 3
001 002 on
ITT:----(
001 002
012
-4kHi<
001 002
013
Ladder Diagram
:.LT
1 J. .v. j
MODE, 3,
ENTER
BIB End
You are in the Run mode. The PROG LED is no longer lit.
LAST
8 times
-]/K
ON
E 1
You have moved thru your program to the Examine OFF instruction in rung 1.
The ON LED is lit, indicating the instruction is TRUE (status bit OFF).
SHIFT,
FRC ON
-/K
FORCE
F E 1
Status bit address 002 has been forced ON. The letter F in the display indicates
the address has been forced (either ON or OFF). The ON LED is not lit,
indicating the instruction is FALSE. The FORCE LED is lit, and will stay lit as
long as one or more instructions in the program have been forced ON or OFF.
NEXT
3 times
~] h
ON,
FORCE
F E E
Cursor is located on the Examine ON instruction in rung 2. The letter F in the
display indicates bit address 002 has been forced. We did this in the previous
step. The ON LED is lit, indicating the instruction is TRUE (status bit ON).
NEXT
-( )-,
ON,
FORCE
IE E
Cursor is located on the output instruction in rung 2. The ON LED is lit,
indicating that the instruction is TRUE. By forcing status bit address 002 ON,
we have made both condition instructions in rung 2 TRUE, making the rung
TRUE, Notice that the letter F does not appear in the display. This is because
we have not applied the force function to status bitaddress012.
NEXT,
SHIFT,
FRC ON
-1 h,
ON,
FORCE
F 1 3
We have moved the cursor to the Examine ON instruction 001 in rung 3 and
have forced bit address 001 ON. Now both bit addresses 001 and 002 are
forced ON. (Rung 2 is now FALSE. Rung 3 is now TRUE).
NEXT
-] K
ON,
FORCE
F S 3
Cursor is on the Examine ON instruction 002, rung 3. The next two steps show
you howto remove a force from a particular bit address (002 in this case).
REMOVE
-3 h 1
ON,
FORCE
rE F 3
Display indicates "remove force".
SHIFT,
FRC ON
-1 h
FORCE
E 3
The Force ON is removed from ail instructions at status bit address 002. Status
bit address 001 is still forced ON, therefore the FORCE LED remains lit.
REMOVE,
ENTER
-] h
E 3
To remove forces from all forced addresses, press REMOVE, ENTER as we've
done here. Cursor does not have to be on a forced instruction.
16-4
Chapter On-Line Data Control
Changing and You can use the following procedures to change or monitor PR, AC, and
Monitoring RAC values of timers and counters while you are in the Run or Test
Techniques
mode
The figure also lists procedures for changing and monitoring sequencer
PR and RAC values.
Figure 16.4
'nx
Change the PR va! ue (i f
unprotected). Example:
change PR to 200.
Locate the cursor on the
PR value. (IfthePRT LED
is lit, value cannot be i
changed.)
2,0,0,
ENTER
Value is changed. Cursor remains on the
PR value. Press NEXT or LAST to move it.
Monitor and change
an AC value.
' Assume this is a
timer. Change the AC value
to 10.0.
Locate the cursor on the
AC value.
1,0,0,
ENTER
The AC value is changed to 10.0 seconds.
If the AC value is incrementing, it will
continueto increment from 10.0.
NOTE: If the PR value is protected, the
PRT LED will be lit and you will not be
ableto change the AC:value.
Change th RAC value.
Example: change RAC tor 5.
Locate the cursor on the
RAC value.
5, ENTER
Value is changed. Cursor remains on the
RAC value. ' A
TTw'TTi TiTTTiIE t-
i-fryv-SrA-yrTTr ' .vu : V<rrrtTTT T j i .3. 1 thT ? ,
Monitor step data, PR
values, or AC values.
Locate the cursor on the
mask data {U S E):
NEXT
Current step number and corresponding
step data is displayed. If the sequencer is
operating, the step number anddata will
be incrementing.
NEXT
Current step number and corresponding
PR value is displayed, if the sequencer is
operating, the PR value and step number
will be incrementing.
NEXT
Current step number and corresponding
AC value is displayed. If the sequencer is
operating, the AC value and step number
will be incrementing.
Change the PR val ue
(unprotected) of a
specific step.
Example: change PR value
of step 5 to 25.
Locate the cursor on the
PR value. Ifthesequen-
cer is operating, the PR
value and step number
will be incrementing.
INSERT Display prompts for step number, S t P.
5. ENTER Current PR value of step 5 is displayed-
2, 5, ENTER
New PR value of 25 is entered. If the
sequencer is operating, the PR value and
step number will be incrementing.
Change the RAC value.
Example: change RAC to 2.
Locate the cursor on the
RAC value.
2, ENTER
Value is changed. Cursor remains on the
RAC value.
Chapter Using the EEPROM
Memory Module
SLC ISO processor unit
The EEPROM The EEPROM is a non-volatile memory in convenient modular form, for
Memory Module use with SLC lOO and SLC 150 Programmable Controllers.
A Series B module or a Series A module having a 28-pin chip must be
used with the SLC 150 processor unit. The majority of Series A modules
sold in the past meet the 28-pin chip requirement.
EEPROM Program Since EEPROM modules can be inserted in any SLC 100 or SLC 150
Identification processor unit, it is important that you identify each EEPROM with the
particular program it contains and the controller or controllers it is to be
used with.
Caution: Interchanging programs between controllers could cause
improper operation and equipment damage. You must be especially
cautious when interchanging programs between SLC 150 and SLC 100
controllers, because of differences associated with certain internal
addresses and other variations.
17
17 17-2
Chapter Using the EEPROM Memory Module
Installing the
EEPROM
The procedure for installing the EEPROM in the processor unit is shown
in the figure below.
EEPROM MEMORY MODULE
WARNING - DO NOT INSERT OR
REMOVE WITH POWER APRtED.
UNEXPECTED OPERATION
COULD RESULT.
Write-on area.
Memory module socket.
SLC 150 processor unit. EEPROM
socket cover on SLC 100 processor
unit is similarly located.
Caution:. Always turn off power to the processor before you
insert or remove the EEPROM. This guards against possible
damage to the EEPROM and also avoids undesired CPU faults.
INSTALLATION PROCEDURE:
1. Turn off power to the processor unit.
2. To insert the memory module, remove the cover from the front of the
processor unit. Save the cover for use later.
3. Align the memory module socket with the receptacle inside the
processor unit. Push carefully to seat the module.
4. Restore power to the processor.
Storing and Loading The following paragraphs explain how to use the pocket programmer to
Procedures store a processor RAM program in the EEPROM and to load an
EEPROM program in the processor RAM. ff you are using the personal
computer software, refer to the SLC Personal Computer Software Users
Manual (Pub. 1745-825) for further information on these procedures.
Chapter
Storing a Program in the
Memory Module
Loading the EEPROM into
the Processor RAM
Using the EEPROM Memory Module
17-3
The following steps show you how to use the pocket programmer to store
(save) the contents of the processor RAM in the EEPROM memory
module. If you are using an access code, it will be stored in the
EEPROM. Well assume that the memory module is not plugged in.
1. Connect the programmer. Press MODE, 6, ENTER. Display will
show SurE ?
Note: You could press ENTER a second time, altho it isnt necessary.
Error code E51 will appear; you can ignore the error code and perform
step 2.
2. Disconnect power from the processor. Insert the memory module.
Restore power.
3. Press ENTER, ENTER. After a brief time, the display will
momentarily show donE. Any program previously stored in the
memory module will be erased.
4. You can now disconnect power and remove the memory module
(replace cover), or you can leave the module in place. The processor
operates from the RAM only.
Caution: It is important to enter mode 6 before installing the
memory module. Reason: If the processor were in the Run mode
when you disconnect power, insert the memory module, and restore
power (step 2), your program could be automatically erased and
replaced with the contents of the memory module. Refer to auto
load procedure on the following page.
The following steps show you how to use the pocket programmer to load
(read) the contents of the EEPROM memory module into the processor
RAM. If you know that the processor is in the Run mode, you may be
able to use the auto-load procedure described on the following page. If
the processor is in some other mode, follow these steps:
1. Disconnect power from the processor. Insert the memory module.
Restore power.
2. Connect the programmer. Press MODE, 7, ENTER, ENTER. (If an
access code is stored in the EEPROM, you will be requested to enter
the code after you press ENTER the second time.)
3. Duplication of the EEPROM contents in the RAM occurs almost
instantaneously. The previous program in the RAM is automatically
erased.
4. You can now disconnect power and remove the memory module
(replace cover), or you can leave the module in place. The processor
operates from the RAM only.
17-4
Chapter Using the EEPROM Memory Module
Auto-Load Procedure If you are using an SLC 100 processor unit: The auto-load procedure
will load the contents of an EEPROM into the processor RAM without
the use of the programmer. The only exception: If the EEPROM has an
access code, you must use the programmer. (It doesnt matter whether
the processor has the same code as the EEPROM, a different code, or no
code.)
Follow these steps:
1. The processor must be in the Run mode initially.
2. If the processor is energized, disconnect power. Insert the EEPROM.
Caution: To avoid automatically entering the Run mode when you
restore power, set the Auto/Man switch to Man at this time.
3. Restore power. The EEPROM contents is automatically duplicated in
the RAM. The previous program in the RAM is automatically erased.
4. When you are prepared to enter the Run mode, set the Auto/Man
switch to Auto.
If you are using an SLC 150 processor unit: In this case, you can
enter an access code in the processor RAM to protect the stored program
against unauthorized EEPROM loading. The table below indicates the
conditions under which the auto-load procedure will and will not
function. If the auto-load is functional, follow steps 1 - 4 in the
paragraph above.
Has access code Has no access code or access
code does not match code in
processor
No. You must use
programmer.
Has access code Hassame access code Yes
as the processor
Has no access code May or may not have access Yes
code
Programmable
Auto-Load-SLC 150
Processor Unit
With the SLC 150 processor unit, you can use address 864 in your
program to automatically load the EEPROM program in the processor
RAM when the processor detects a memory checksum error. Such errors
are detected if memory data is altered or lost due to capacitor back-up
drain, battery back-up drain, or processor malfunction. It works like
this:
1. Enter the following unconditional rung as Rung 1 of your program:
864 I
< H
Rung 1
Chapter Using the EEPROM Memory Module
17-5
Programmable
Autoload -SLC 150
Processor Unit
(continued)
2. Enter the rest of your program and store the program in the
EEPROM. This is your "back-up program.
3. If a memory problem occurs and the processor unit detects a
memory error (codes 5 thru 8), recycle power. The EEPROM program
will be automatically loaded in the processor RAM, clearing the error.
An error 6 message will be displayed by your pocket programmer or
computer following an auto-load error. This error message can be
cleared by using the Cancel key on the pocket programmer or re
entering the Run/Mon/Test mode via SLC personal computer
software.
Important: Keep in mind that when the auto-load occurs, the I/O table
data is cleared. All retentive instructions (latches, timers, counters,
sequencers) will be reset to their initial states.
Editing EEPROM
Programs
You cannot edit the EEPROM program directly. You must first load the
program into the processor RAM, if it is not already in the RAM. You
then edit the RAM program and store the edited program in the
EEPROM.
For example, suppose an EEPROM is installed, and its contents are
loaded in the RAM. You can change the program in the EEPROM as
follows:
1. The RAM program is a duplicate of the EEPROM program; edit the
RAM program.
2. Press MODE, 6, ENTER, ENTER.
3. The edited program is now in the EEPROM (and in the RAM).
Changes not Saved Error code E52 tells you that the processor RAM program does not
if) EEPROM match the EEPROM program. If an EEPROM is installed in the
(Error Code E52) processor unit,this error will appear after you edit your program and
attempt to enter the Run or Test modes. This reminds you that you
should load the edited program in the EEPROM before going into the
Run mode.
Error code E52 can be overridden by pressing ENTER again. Note:
Error code E52 is not displayed when on-line data changes are made to
the processor RAM.
Installing and
Maintaining the System
Chapter
Specifications
Installation Procedure
Start-Up
Index
Chapter Specifications
General Specifications -SLC100 Processor Unit
Voltage Ranges {Incoming Power,lnput Circuits, Output Circuits):
Catalog
Number
Voltage Ranges
(Incoming Power
Connections)
External I/O Circuits
input
Output
(Hard Contact)
1 745-LP101
85-132/170-265 VAC
50/60 Hz
85-132 VAC
50/60 Hz
, 10-2 50V AC/
(

10-125VDC :
1745-LP102
85-132/170-265 VAC
50/60 Hz
170-265 VAC
50/60 Hz
1745-LP103
85-132/170-265 VAC
50/60 Hz
10-30V
AC/DC
: 1 745-IP104
18-30VDC
10-30 V
' AC/DC ;
Full wave rectified
AC voltage 18V RMS
20%, 30V peak .
Input Terminal Cover
Color Code
Volts Color
85-132 VAC
50/60 Hz
Red
170-265 VAC
50/60 Hz
Black
10-30V
AC/DC
Blue
Maximum Power Requirement:
1745-LP101, -LP102, -LP103: 20VA. 1745-LP104: 15VA.
Input Power Fuse Protection:
1745-LP101, -LP102,-LP103: 315mA/250V. 1745-LP104: 1.6A/250V.
Fuse Types: SAN-O: SOCSD4. Bussman: MDL, or GDC (miniature).
Hold-Up Time: The processor can sustain operation for approx. 300 milli
seconds in the event of power interruption or removal. It takes approx.
85 milliseconds for the processor to reach full power from an initial
power on condition.
Specifications applying to all Catalog Numbers
Memory Type: CMOS RAM with battery back
up. Provision for optional EEPROM module
(Cat. No. 1745-M1).
Battery Back-Up: Lithium battery, non
rechargeable, 2-3 year life.
User Memory Size: 885 words maximum.
(Most instructions require 1 word.)
Typical Scan Time: 15 msec (depends on
program length).
I/O Capacity: 161/0 (10 inputs, 6 outputs).
Expandable to 112 I/O.
Input specifications: Page 18-3.
Output specifications: Page 18-5.
Internal Relay-Type Instructions: 181 max,
regular or atched.
Timers/Counters/Sequencers: 32 max, any
combination. Retentive.
Time Base: 0.1 sec. Fine time bases to 0.01 sec
can be selected.
Timer Range: 0.1 to 999.9 seconds.
Counter Capacity: 9999 counts.
Sequencer Capacity: 8 bits x 100 steps.
Shift Register: 8-bit groups.
Noise Immunity: NEMA Standard ICS 2-230.
Vibration: DIN Rail Mounting: 0.006 inch peak
to peak displacement, 1 Og peak (max)
acceleration, 1 Hr/axis. Screw Fastener
Mounting: 0.015 inch peak to peak
displacement, 2.5g peak(max) acceleration,
1 Hr/axis.
Ambient Temperature Rating: 0 to 60 C
(operating). - 40to 85 C (storage).
Humidity Rating: 5 to 95% (without
condensation).
Wiring: #14 - #24 AWG stranded. 3/64"
insulation (max).
18-2
Chapter Specifications
General Specifications General specifications for the basic, relay output, and analog input
-SLC 100 Expansion expansion units are shown below.
Units
Voltage Ranges (Incoming Power, Input Circuits, Output Circuits):
Maximum Power Requirement:
1745-E101, -El02, -El 03, -E105, -E106: 12VA
1745-E104, -E107: 9VA.
Input Power Fuse Protection:
1745-E101,-E102, -E103: 315mA/250V.
1745-E 104: 1.6A/250V.
1745-E 105: 160mA/250V.
1745-E 106: 200mA/250V.
1745-E 107: 1A/250V.
Fuse Types: SAN-O: SOCSD4.
Bussman: MDL, or GDCI (miniature).
I/O Capacity:
1745-E 101,-E102,-E103,-E104:
16 I/O (10 inputs, 6 outputs).
1745-E105: 12 I/O (0 inputs, 12 outputs).
1745-E 106, -E107: 4 analog input circuits,
with 2 adjustable set points per input.
Input specifications: Pages 18-3 and 18-4.
Output specifications: Page 18-5.
Specif ications applying to all Catalog Numbers
Noise Immunity: NEMA Standard ICS 2-230.
Vibration:
DIN Rail Mounting: 0.006 inch peak to peak
displacement, 1.0g peak (max) acceleration,
1 Hr/axis. Screw Fastener Mounting: 0.015
inch peak to peak displacement, 2.5g
peak(max) acceleration, 1 Hr/axis.
Ambient Temperature Rating:
0 to 60 C (operating).
-40 to 85 C (storage).
Humidity Rating:
5 to 95% (without condensation).
Wiring: #14- #24 AWG stranded.
3/64" insulation (max).
Input Terminal Cover
Color Code
Volts Color
85-132 VAC
50/60 Hz
Red
170-265 VAC
50/60 Hz
Slack
10-30V
AC/DC
Blue
Catalog Number
Voltage Ranges
External I/O
(Incoming Power
Connections)
Input Circuits
Output Circuits -
Hard Contact
1745-E101
85-132/170-265 VAC
50/60 Hz
85-132 VAC
50/60 Hz
1745-E 102
85-132/170-265 VAC
50/60 Hz
170-265 VAC
50/60 Hz
1745-E 103
85-132/170-265 VAC
50/60 Hz
10-30V AC/DC . 1Q-250VAC/10-125 VDC
18-30 VDC
1745-E104
Full wave rectified
AC voltage
18 volts RMS 20%,
30 volts peak
10-30V AC/DC
1745-E 105
85-132/170-265 VAC
50/60 Hz
N/A
1745-E106
85-132/170-265 VAC
50/60 Hz :
Analog Inputs
18-30 VDC
N/A
1745-El 07
Full wave rectified
AC voltage
18 volts RMS 20%,
30 volts peak
0-10 VDC or
0-20 mA
Chapter Specifications
18-3
Input Specifications
-SLC100 Processor and
Basic Expansion Units
Input specifications are shown below. The 2 mA OFF state leakage
current specification allows direct interface to solid state sensing
devices.
Note that the 2 mA OFF state leakage current for 24VAC circuits
applies to inputs 1 and 2 only. When required, you can also achieve a 2
mA OFF state leakage current for inputs 3 thru 10, as indicated in the
specifications.
All input circuits include optical isolation as well as filtering and surge
suppression to guard against damage by transients from external input
devices.
ON State Voltage Range and Frequency:
1745-LP101,-E101 : 85-132 VAC, 50/60 Hz.
1745-LP102, -E102: 170-265 VAC, 50/60 Hz.
1745-LP103, -LP104, -E103, -E104: 10-30V, AC/DC
Maximum OFF State Voltage:
1745-LP101, -E101: 35V.
1745-LP102, -E102: 50V.
1745-LP103, LP104;-E103,-E104: 5V.
Maximum OFF State Leakage Current:
1745-LP101, -LP102, -E101, -E102: 2 mA.
1745-LP103, -LPI04, -E103, -E104: 2mA, inputs 1 and 2 only.
To achieve a 2 mA OFF state leakage current for inputs 3
thru 10, connecta 5.6KQ, 1/2 watt (min) resistor from the
input terminal to the common terminal.
Nominal Input Current:
1745-LP101, -LP102, E101, -E102: 8 mA.
1745-LP103, -LP104, -E103, -E104: Inputs 1 and 2-
8 mA at 12V, 18 mA at 24V. Inputs 3 thru 10- 6 mA at 12V,
14 mA at 24V.
Specifications applying to all Catalog Numbers:
Input Filter Time Delay:
; 10-25msec. - ~
Electrical-Optical Isolation:
A I SOCkvolts between input voltage and control logic.
Chapter
18 18-4
Specifications
Input Specifications
-SLC100 Analog
Input Expansion
Unit
Input specifications for the analog input expansion unit are shown
below.
Voltage Inputs
Minimum Isolation Between Input and Control Logic:
1500 volts.
Input Type: Differential.
Input Impedance:
+ V to ( - ): > 1000 K ohms.
, + Vor(-)to COM: > 500 K ohms.
Tri p Point Repeatabi lity over Ti me and Temperature :
25-35C: 0.25% offulhscale or 25mi!livolts (typical).
1.00% of full scale or 100millivolts (worst case).
0-60C: 0.50% of full scale or 50 millivolts (typical).
1.50% of full scale or 150 millivolts (worst case).
Hysteresis: 10 millivolts.
Maximum Operating Range:
+ Vto(-): Oto + 10volts.
+ V or (-) to COM: -35 to +35 volts.
Minimum Circuit Protection Range:
+ V to ( -), + V or (-) to COM: 50.0 volts.
Maximum Input Response Time:
3.5 milliseconds.
Current Inputs
?
Minimum Isolation Between Input and Control Logic:
:? 1500 volts. ; ;
Input Ty^e:: Differentiat.
Input Impedance:
Trip Point ftepeatability over Time and Temperature:
25-35C: 0.50% of full scale or 0.10mA (typical).
1.75% of full scale or 0.35mA (worst case).
0-60C: 1.00% of full scale or 0.20mA (typical).
2.75% of full scale or 0.55mA (worst case).
Hysteresis: 4Q microamps.
Maximum Operating Range:
+ Ito(~): 0 to 20 mA.
+1 or (- ) to COM: -35 to + 35 volts.
Miriirnutm Circuit Protection Range:
; ; 40mA. -
+ l or (-) to COM: 50.0 volts.
Maximum Input Response Time:
' 3.5 mill (seconds;
Chapter Specifications
18-5
Output Specifications
-SLC100 Processor
and Expansion Units
Output specifications for all versions of the processor unit and the basic
and relay output expansion units are shown below.
Internal output circuitry includes surge suppression to guard against
possible damage by transients from external output devices. We
recommend that you also use some type of contact protection when
switching inductive load devices. Refer to Page 19-9.
Voltage Range and Ffquency *
:
;
io-l5 vACfso/eoHz), 10-125 vdc.
Contact Ratings:
Maximum ;
Volts
;
; *
Amperes
Amperes
Continuous
Voltamperes
Make Break Make Break
240VAC :
: X 20 V AC
. 7.5A 0.75A
1.5A
:
2.5A : 1800VA ; 180 VA
: 125VDC i 0.22A ;; 1 0A ; : 28VA
i 24VDC ; - .-C2&C.; / ; ; * 2.5A ; ; 28VA .i . .
;
:
Contact Resistance: 20 m (typical).
; Electrical Isolation: 2000 volts. -
OFF State Leakage Current: 2 mA (AC voltage only).
Internai! RCfNetwork Values: R= 120 ohms, C = 0.022 microfarad.
18-6
Chapter Specifications
General Specifications - SLC150 Processor Unit
Voltage Ranges (Incoming Power, Input Circuits, Output Circuits):
Catalog
Number
Voltage Ranges
(Incoming Power
Connections)
External I/O
Input Circuits - 20 Output Circuits - 12 Color Patch*
1745-LP151
85-132/170-265 VAC
50/60 Hz
85-132 VAC 50/60Hz
Current Sinking
10 Triac - 85-265 VAC 50/60 Hz
2 Hard Contact-10-250VAC/10-125VDC
Red
1745-LP152
85-132/170-265 VAC
50/60 Hz
170-265 VAC 50/60Hz
Current Sinking
10 Triac - 85-265 VAC 50/60 Hz
2 Hard Contact- 10-250VAC/10-125VDC
Black
1745-LP153
85-132/170-265 VAC
50/60 Hz
10-30 VDC
Current Sinking
12 Hard Contact- 10-250VAC/10-125VDC Blue
1745-LP154 18-30 VDC
10-30 VDC
Current Sinking
10 PNP Transistor - 10-50 VDC
2 Hard Contact- 10-250VAC/10-125VDC
Green
1745-LP156
85-132/170-265 VAC
50/60 Hz
10-30 VDC
Current Sourcing
12 Hard Contact- 10-250VAC/10-125VDC Purple
1745-LP157 18-30 VDC
10-30 VDC
Current Sourcing
10 NPN Transistor-10-50 VDC
2 Hard Contact- 10-250VAC/10-125VDC
Yellow
* Color patch appears in the upper right corner of the unit, above the cluster of LED status indicators.
Maximum Power Requirement:
1745-LP151,-LP152, -LP153, -LP156: 25VA.
1745-LP154, -LP157: 15VA.
Input Power Fuse Protection:
1745-LP151, -LP152, -LP153: 315mA/250V.
1745-LP154: 1.6A/250V.
Fuse Types: SAN-O: SOCSD4.
Bussman: MDL, or GDC (miniature).
Hold-Up Time:
The processor can sustai n operati on for a
minimum of 25 milliseconds in the event of a
power interruption.
I/O Capacity:
20inputsand 12outputs. See table above.
Input specifications: Page 18-8.
Output specifications: Pages 18-9 and 18-10.
Memory Type: CMOS RAM.
Standard Capacitor Back-up: Provides memory
back-up for 2 weeks at 30C and 1 week at
60C. No maintenance required.
Note: If the processor unit is operated in
temperatures above 50C for extended
periods of time, capacitor life cannot be
guaranteed beyond 2 years. For these
applications, we recommend that you install
the Lithium battery for memory back-up.
Optional Battery Back-up: Catalog No. 1745-B1.
Lithium battery, non-rechargeable. 2 to 3
year life. Actual life may vary, depending on
controller environmental conditions,
installation: Page 22-11.
User Memory Size: 1200 words max.
Most instructions require 1 word.
Typical Scan Time:
4 msec (1000 word program).
Internal Relay Type Instructions:
177 max. (regular or latched).
Timers, Counters, Sequencers:
32 max, any combination, retentive.
Time Base: 0.1sec. Fine time basesdown to
0.01 second can be selected.
Timer Range:
0.1 to 999.9 seconds.
Sequencer Capacity:
8 bits x 100 steps.
Shift Register:
8 bit groups.
Noise Immunity:
NEMA Standard ICS 2-230.
Vibration:
0.015 inch peak to peak displacement, 2.5g
peak(max) acceleration, 1 Hr/axis.
Ambient Temperature Rating:
0 to 60 C (operating).
- 40 to 85 C (storage).
Humidity Rating:
5 to 95% (without condensation).
Wiring: #14- #24 AWG stranded.
3/64" insulation (max).
Chapter
18
Specifications
18-7
General Specif cations - SLC150 Expansion Unit
Voltage Ranges (Incoming Power, Input Circuits, Output Circuits):
Catalog
Number
Voltage Ranges
{Incoming Power
Connections)
External I/O
Input Circuits - 20
Output Circuits-12 Color Patch*
1745-E151
85-132/170-265 VAC
" 50/60 Hz
85-132 VAC 50/60HZ
Current Sinking
! 10 Triac- 85-265 VAC 50/60 Hz
2 Hard Contact - 10-250VAG10-125VDC
Red
1745-E 152
85-132/170-265 VAC
50/60 Hz
170-265 VAC 50/60Hz
Current Sinking
10 Triac - 85-265 VAC 50/60 Hz
2 Hard Contact - 10-250VA010-125VDC
Slack
1745-El 53
85-132/170-265 VAC
50/60 Hz
10-30VDC
Current Sinking
12 Hard Contact - 10-250VAC/10-125VDC Blue
1745-El 54 18-30VDC
10-30 VDC
Current Sinking
10 PNP Transistor-10-50 VDC
2 Hard Contact- 10-250VAC/10-125VDC
Green
1745-El 56
85-132/170-265 VAC
50/60 Hz
10-30 VDC
, Current Sourcing
12 Hard Contact - 10-250VAC/10-125VDC Purple
1745-El 57 18-30VDC
10-30 VDC
Current Sourcing j
10 NPN Transistor-10-50 VDC
2 Hard Contact- 10-250VAC/10-125VDC
Yellow
* Color patch appears in the upper right corner of the unit, above theciuster of LED status indicators.
Specifications applying to all Catalog Numbers
Noise Immunity: NEMA Standard ICS 2-230.
Vibration:
0.015 inch peak to peak displacement, 2.5g
peak(max) acceleration, 1 Hr/axis.
Ambient Temperature Rating:
0 to 60 C (operating).
- 40 to 85 C (storage).
Humidity Rating:
5 to 95% (without condensation).
Wiring: #14-#24AWG stranded.
3/64" insulation (max).
Maximum Power Requirement:
1745-E151, -E152, -E153, -E156: 15 VA.
1745-E154, -E157: 9 VA.
Input Power Fuse Protection:
1745-E 151, -E152, -E153: 315mA/250V.
1745-E 154: 1.6A/250V.
Fuse Types: SAN-O: SOC SD4.
Bussman: MDL, or GDC (miniature).
I/O Capacity:
20 inputs and 12 outputs. See table above.
Input specifications: Page 18-8. ; ;
Output specifications: Pages 18-9 and 18-10.
18-8
Chapter Specifications
Input Specifications
-SLC150 Processor
and Expansion Units
Input specifications are shown below. All input circuits include optical
isolation as well as filtering to guard against high voltage transients
from external input devices.
ON State Voltage Range and Frequency:
1745-LP151, -E151: 85-132 VAC, 47-63 Hz.
1745-LP152, -E152: 170-265 VAC, 47-63 Hz.
1745-LP153,-LP154,-LP156,-LP157,
-El 53, -E154, -E156, -E157: 10-30VDC.
Maximum OFF State Voltage:
1745-LP151, -E151: 30V.
1745-LP152,-E152: 50V.
1 745-LP1 53, -LP154, -LP156, -LP157,
-El53,-El54,-El56,-E157: 4V
Maximum OFF State Leakage Current:
1745-LP151, -LP152, -El51, -El 52: 2 mA.
1745-LP153,-LP154,-LP156,-LP157,
-E 153,-E154,-E156, -E157: 1mA.
Nominal Input Current:
1745-LP151, -LP152, - E151, -E152: 8 mA.
1745-LP153,-LP154, -LP156,-LP157,
-El 53, -El 54, -E 156, -E157: 4mA at 12VDC,
8mA at 24VDC.
Input Filter Time ON Delay:
1745-LP 151, -LP152, -E151, -E152: 3 to 13msec.
1745-LP153,-LP154,-LP156,-LP157,
-E153, -E 154, -E 156, -E157: 4 to 8 msec.
Input Filter Time OFF Delay:
1745-LP151, -LP152,-E151, -E152: 9 to 18 msec.
1745-LP153, -LP154, -LP156, -LP157,
-E153,-E154,-E156,-E157: 4 to 8 msec.
Electrical-Optical Isolation:
1500 volts between input voltage and control logic.
Applies to all catalog numbers.
Chapter
Output Specifications
- SLC150 Processor and
Expansion Units
Specifications
18-9
TRIAC OUTPUTS, 1745-LP151, -LP152, -E151, -E152
(Hard contact relay outputs: Page 18-10)
Output Voltage Range: 85-265 VAC.
Continuous Output Current per Circuit:
" 1A at 30C, linearly derated to 0.5A at 60C.
Continuous Output Current per Chassis:
: 10A at 30C, linearly derated to 5A at 60C.
I Surge Current:
; 10A for 25 msec. Repeat once each second at 30X or once
each 2 seconds at 60C.
Minimum Load Current: 10 mA.
Maxirpum OFF State Leakage Current: 2 mA.
OFF to ON Response Time (non-zero cross): 0.1 msec (max).
:
Zero-Cross Turn-on Timing Accuracy: 500' microseconds.
7
* ^aturation Vltge Drop: 1.5 volts at 1.0A.
Electrical-Optical Isolation:
; 1500 volts between output voltage and control logic.
Recommended Output Fusing: San-O: SOCST4-3A,
Bussman: MSL-2A, or equivalent.
TRANSISTOR OUTPUTS, 1745-LP154, -LP157, -E154, -E157
(Hard contact relay outputs: Page 18-10)
Output Voltage Range: 10-50 VDC.
Continuous Output Current per Circuit:
: ; 1A at 30
q
C, linearly derated to 0.5A at 60C.
Continuous Output Current per Chassis:
: ;
:
10A at 30C. 5Aat 60C.
Surge Current:
3A for 20 msec. Repeat once each second at 30C, or once
each 2 seconds at 60C.
Minimum Load Current: 1.0 mA.
Maximum OFF State Leakage Current: 0.1 mA.
OFF to ON Response Time: 100 microseconds.
Maximum ON State Voltage Drop:
1.5 volts at 1.0A. 0.8 volts at 0.5A.
Electrical-Optical Isolation:
1500 volts between output voltage and control logic.
Recommended Output Fusing: San-O: SOC ST4-2A,
MSL^Z^wquivalent
TS- TO
Chapter Specifications
Output Specifications
-SIC 150 Processor
and Expansion Units
(continued)
Specifications for hard contact relay outputs are shown below. We
recommend that you use some type of surge suppression when switching
inductive load devices with hard contact outputs. Refer to Page 19-9.
HARD CONTACT RELAY OUTPUTS
Wiring Terminals, Internal Arc Suppression:
Catalog
Number
Hard Contact Relay Outputs
1745-t.P151
1745-l.P152
1745-LP154
1745-LP157
Units have 2 hard contact relay outputs, at
terminals 11 and 111. These outputs do not
have internal arc suppression circuitry.
1745-LP153
1745-LP156
Units have 12 hard contact relay outputs. Relay
outputs at terminals 12 thru 16 and 112 thru
116 have internal arc suppression circuitry.
Relay outputs at terminals 11 and 111 do not
have internal arc suppression circuitry.
1745-E151
1745-E152
1745-E154
1745-E157
Units have 2 hard contact relay outputs, at
terminals A11 and 611. These outputs do not
have internal arc suppression circuitry.
1745-E153
1745-E156
Units have 12 hard contact relay outputs. Relay
outputs at terminals A12 thru A16 and B12 thru
S16 have internal arc suppression circuitry.
Relay outputs at terminals A11 and Bi t do not
have internal arc suppression circuitry.
Voltage Range and Frequency:
10-250 VAC (50/60 Hz), 10-125 VDC
Contact Ratings:
Maximum
Volts
: Amperes
Amperes
Continuous
Voltamperes
Make Break Make Break
240VAC!
120VAC
7.5 A
ISA
0.75A
1.5A
2.5A 1800VA 180 VA
125VDC ; 0.22A 1 0A 28VA
24VDC *
:
: 12A 2.5 A 28VA
Contact Resistance: 20 mfi (typical).
Electrical Isolation:
2000 volts between output contacts and control logic.
OFF State Leakage Current:
Processor unit outputs at terminals 11 and 111 (all catalog
numbers); Also expansion unit outputs at terminals A11
and B11 (all catalog numbers): No leakage current.
Processor unit outputs at terminals 12 thru 16 and 112
thru 116 of 1745-LP153, -LP156; Also expansion unit
outputs at terminals A12 thru A16 and B12 thru B16 of
1745-E153, -E156: 2mA (AC voltage only). To limit
leakage current, use a loading resistor across the load as
shown on Page 20-15.
18-10
Chapter
18
Specifications
Output Specifications
-SLC150 Processor
and Expansion Units
(continued)
Specifications for hard contact relay outputs are shown below. We
recommend that you use some type of surge suppression when switching
inductive load devices with hard contact outputs. Refer to Page 19-9.
HARD CONTACT RELAY OUTPUTS
Wiring Terminals, Internal Arc Suppression:
Catalog
Number ;
Hard Contact Relay Outputs
1745-LP151
1745-LP152
1745-LP154
1745-LP157
Units have 2 hard contact relay outputs, at
terminals 11 and 111. These outputs do not
have internal arc suppression circuitry.
1745-LP153
1745-LP156
Units have 12 hard contact relay outputs. Relay
outputs at terminals 12 thru 16 and 112 thru
116 have internal arc suppression circuitry.
Relay outputs at terminals 11 and 111 do not
have internal arc suppression circuitry.
1745-E151
1745-E152
1745-El 54
1745-E157
Units have 2 hard contact relay outputs, at
terminals A11and B11. These outputs do not
have internal arc suppression circuitry.
1745-E153
1745-E156
Units have 12 hard contact relay outputs. Relay
outputs at terminals A12 thru A16 and B12 thru
B16 have internal arc suppression circuitry.
Relay outputs at terminals A11 and B11 do not
have internal arc suppression circuitry.
Voltage Range and Frequency:
10-250 VAC (50/60 Hz), 10-125VDC
Contact Ratings:
Maximum
Volts
Amperes
Amperes
Continuous
Voltamperes
Make Break Make Break
240VAC
120VAC
, 7.5A ;
15A
0.75A
1.5A
2.5A 1800VA 180 VA
125VDC ; : o . 2 2 A ; ; ; 1 0 A 28VA
; 24VDC : . 1 . 2 A
:
: : 2.5A 28VA
Contact Resistance: 20 ma (typical).
Electrical Isolation:
2000 volts between output contacts and control logic.
OFF State Leakage Current:
Processor unit outputs at terminals 11 and 111 (all catalog
numbers); Also expansion unit outputs at terminals A11
and B11 (all catalog numbers): No leakage current.
Processor unit outputs at terminals 12 thru 16 and 112
thru 116 of 1745-LP153, -LP156; Also expansion unit
outputs at terminals A12 thru A16 and 812 thru 816 of
1745-E153, -E156: 2mA (AC voltage only). To Iimit
leakage current, use a loading resistor across the load as
shown on Page 20-15.
Chapter Specifications
18-11
Specif cations - SLC 150
High Speed Input
Module
ON State Voltage Range:
5VDC 2-7VDC
12VDC 5-15V DC
24 V DC 10-30VDC
Maximum OFF State Voltage:
5VDC 0.8VDC
12VDC 2VDC
24VDC 4VDC
Maximum OFF State Leakage Current:
1 mA (all voltage levels)
Nominal Input Current:
5VDC 25mA
12VDC 17mA
24VDC 15mA
Maximum Turn ON and OFF Time:
Filter not selected - 50 microseconds 25%
Filter selected -4 milliseconds 25%
Electrical-Optical Isolation:
1500 volts between input voltage and control logic.
Noise Immunity:
NEMA Standard ICS 2-230
Vibration:
0.015 inch peak to peak displacement, 2.5g peak (max)
acceleration, 1Hr/axis
Ambient Temperature Rating:
0C to 60C (operating). -40C to 85C (storage)
Humidity Rating:
5 to 95% (without condensation)
Wiring:
#14to #24AWG stranded. 3/64" insulation (max)
18-12
Chapter Specifications
Specifications -
Pocket Programmer catalog no. 1745-PT1
Display:
Light emitting diodes (LEDs) and 7-segment
LED readouts.
Keyboard:
Thirty momentary push keys with tactile feedback.
Interconnect Cble:
Six-foot (1.8 m) cable. Mates with processor unit.
Operating Power:
Supplied by processor unit.
Ambient Temperature Rating:
0 to 50 C (operating).
-40 to 85 C (storage).
Overall Dimensions (Approx.):
7x3x1 inches (178x76x25 mm).
Specifications -
EEPROM Memory catalog No. ms-Mi
Module Memory Type:
;Electrically-Erasable Programmable
Read-Only Memory (EEPROM).
Memory Size:
1200 words maxi mu m. M ost i nstr u cti o n s
require 1 word.
Ambient Temperature Range:
0 to 60 C (operating).
-40 to 85 C (storage).
Chapter
Instruction
Execution Times
and Word Usage
-SLC100
Specifications
18-13
Approximate instruction execution times in microseconds:
4 [- -]/[-
Examine ON, Examine OFF 25
-( )-
Output Energize 30
4D-, 4U)- Latch, Unlatch 32
-(RTO)- Retentive Timer On-Delay 208
; -(RTF)- Retentive Timer Off-Delay 208
-(CTU)- Up Counter 196
-(CTD)- Down Counter 156
-(ZCL)- Zone Control Last State 37
-(MCR)- Master Control Reset 34
T
Branch Open 30
=r Branch Close 32
-(RST)- Reset 156
-(SQO)- : Sequencer Output, time-driven 370
-(SQO- Sequencer Output, event-driven 362
-(SQD- Sequencer Input, time-driven 390
(SQf)- Sequencer Input, event-driven 378
-(SR)- : Shift Register 24
The I/O Scan execution time is approximately 1500
microseconds, plus 270 microseconds for each expansion unit.
Note: Execution times are approximate. You can measure
your total program scan time by programming the rungs
shown in Figure 8.6, Page 8-4.
Instruction Word Usage: The instructions above require one
word of memory, except for the Reset and all versions of the
Sequencer; These require
-(RST)-: 2 words.
-(SQO)-, (SQf): 7 + 3(number of steps) words
: : : ; ;
11 !
: : : : : 2 " ..
18-14
Chapter Specifications
Instruction
Execution Times Approximate instruction execution times in microseconds:
and Word Usage
-SLC 150 -\\r-Vh
-(LK-(U)-
-(RTO)-
-(RTF)-
-(CTU)-
HCTDh
-(ZCL)-
-(MCR)-
T
3 "
-(RST)-
-(SQO)-
-(SQO)-
~{SQI)~
-(SQD-
-iSR)-
Examine ON, Examine OFF 2
Output Energize 3
Latch, Unlatch 1
Retentive Timer On-Delay 50
Retentive Timer Off-Del ay 50
Up Counter 43
Down Counter 43
Zone Control Last State 2
Master Control Reset
3 + 3 x (no. of rungs in zone)
Branch Open 0
Branch Close 0
Reset 50
Sequencer Output, time-driven 113
Sequencer Output, event-driven 113
Sequencer Input, time-driven 113
Sequencer Input, event-driven 113
Shift Register 5
The I/O Scan execution time is approximately 300 microseconds,
plus 250 microseconds for each expansion unit.
Note: Execution times are approximate. You can measure your
total program scan time by programming the rungs shown in
Figure 8.6, Page 8-4.
Instruction Word Usage: The instructions above require one
word of memory, except for the Reset and all versions of the
Sequencer. These require
-(RST)-: 2 words.
~(SQO)~, (SQi): 7 + 3(number of steps) words
2
AutOBaud The SLC 150 processor unit automatically adjusts its communication
Recognition - SLC150 baud rate to allow communication with external devices such as
computers and modems. Acceptable baud rates are 300,1200,2400,
9600 and 19,200.
This auto-baud feature is effective in any mode except the Run mode. If
the SLC 150 is in the Run mode and you want to communicate at a
different baud rate, remove power from the processor unit or enter any
other operating mode. Then connect the external device you want to
communicate with. If you remove power from the processor unit in the
Run mode, the Auto/Man switch must be set to the Man position in order
for the baud rate to be adjusted on power-up. Once power is applied, you
can return the switch to the Auto position.
Chapter
General
Enclosure
Considerations
System Layout
Recommendations
To help you install the controller as safely and securely as possible, we
have set up a few specific recommendations and guidelines for you to
follow. They are the result of product testing and Alien-Brad leys
extensive experience with solid state industrial controls.
For general installation guidelines, also refer to article 70E of the
National Fire Protection Association (NFPA). Article 70E describes
electrical safety requirements for employee workplaces.
Figure 19.1 shows some of the components that make up a typical
installation.
Figure 19.1
environment that will shield your controller from electrical noise
and airborne contaminants.
2. Disconnect, to remove power from the system.
3. Fused isolation transformer or a constant voltage transformer, as
your application dictates.
4. Master control rlay/emergency stop circuit.
5. Terminal blocks or wiring ducts.
6. Suppression devices for limiting EMI generation.
The enclosure protects the equipment from atmospheric contamination.
Standards established by the National Electrical Manufacturers
Association (NEMA) define enclosure types, based on the degree of
protection an enclosure will provide. Select a NEMA rated enclosure
that is suitable for your application and environment.
The enclosure must be equipped with a disconnect device.
Chapter
19 19-2
System Layout Recommendations
Component Spacing The figure below shows acceptable layouts. Follow the recommended
minimum spacing to allow for convection cooling within the enclosure.
Cooling air in the enclosure must be kept within a range of 0 to 60C.
Note that SLC 100 and SLC 150 expansion units can be interconnected
with either an SLC 100 or an SLC 150 processor unit. High speed input
modules can be used with the SLC 150 processor unit only.
Figure 19.2
Chapter System Layout Recommendations
19-3
Excessive Heat For most applications, normal convection cooling will keep the
controller components within the specified operating range. Proper
spacing of components within the enclosure is usually sufficient for heat
dissipation.
Additional cooling provisions might be necessary when high ambient
temperatures are encountered.
In some applications, a substantial amount of heat is produced by other
equipment inside or outside the enclosure. In this case, blower fans may
be placed inside the enclosure to assist in air circulation and to reduce
"hot spots near the controller. Do not bring in unfiltered outside air. It
may introduce harmful contaminants or dirt that could cause improper
operation or damage to components. In extreme cases, air conditioning
may be required to protect against heat build-up within the enclosure.
Wiring Layout Careful wire routing within the enclosure helps to cut down electrical
noise between I/O lines. Follow these rules for routing your wires:
1. Route incoming power to the processor and expansion units by a
separate path from wiring to I/O devices. Do not run signal wiring
and power wiring in the same conduit! Where paths must cross, their
intersection should be perpendicular.
2. If wiring ducts are used, allow at least 2 inches between I/O wiring
ducts and the processor or expansion unit. If terminal strips are used
for I/O wiring, allow at least 2 inches between the terminal strips and
the processor or expansion unit.
3. Segregate I/O wiring by signal type. Bundle wiring with similar
electrical characteristics together.
Wiring with different signal characteristics should be routed into the
enclosure by separate paths whenever possible.
Grounding In solid state control systems, grounding helps limit the effects of noise
due to electromagnetic induction (EMI). The grounding path for the
controller and its enclosure is provided by the equipment grounding
conductor.
WARNING: The SLC controller, other control devices, and the
enclosure must be properly grounded. All applicable codes and
ordinances must be observed when wiring the controller system.
Ground connections should run from the CHASSIS GND terminal on
each processor and expansion unit to the ground bus. Ground wires can
be daisy-chained between units to minimize the number of ground wire
connections. Exact connections will differ between applications. An
authoritative source on grounding requirements for most installations is
the National Electrical Code.
Chapter
19 19-4
Grounding
(continued)
Master Control Relay
System Layout Recommendations
In addition to the grounding required for the controller and its
enclosure, you must also provide proper grounding for all controlled
devices in your application. Care must be taken to provide each device
with an acceptable grounding path.
A hard-wired master control relay (supplied by you) provides a
convenient means for emergency controller shutdown. Since the master
control relay allows the placement of several Emergency Stop switches
in different locations, its installation is important from a safety
standpoint. Overtravel limit switches or mushroom-head push buttons
are wired in series so that when any of them opens, the master control
relay is de-energized. This will remove power from the machine. Never
alter these circuits to defeat their function, since serious injury or
machine damage could result.
If you are using a DC power supply, interrupt the DC side rather than
the AC side to avoid the additional delay of power supply turn-on and
turn-off. As shown in Figure 19.3 on the following page, the DC power
supply should receive its power directly from the fused secondary of the
transformer. Power to the DC input and output circuits must be
connected through a set of master control relay contacts.
The main power disconnect switch should be located where operators
and maintenance personnel have quick and easy access to it. If a
disconnect switch is to be mounted inside the controller enclosure, the
switch operating handle should be on the outside of the enclosure, so
that power can be disconnected without opening the enclosure.
Wiring the master control relay into a grounded system is shown in
Figure 19.3. Whenever any of the Emergency Stop switches are opened,
power to input and output devices is removed.
When the master control relay is used to remove power from the
external I/O circuits, power continues to be provided to the controllers
power supply so that diagnostic indicators on the processor can still be
observed.
NOTE - The master control relay is not a substitute for a disconnect to
the controller. It is intended for any situation where the operator must
quickly de-energize I/O devices only. When inspecting or installing
terminal connections, replacing output fuses, or working on equipment
within the enclosure, the disconnect must be used to shut off power to
the rest of the system.
Chapter System Layout Recommendations
19-5
Master Control Relay The master control relay must not be controlled by the SLC controller.
(continued) The operator must be provided with the additional safety of a direct
connection between an emergency stop switch and the master control
relay.
WARNING: Do not program Emergency Stop switches in the
controller program. Any Emergency Stop switch should turn off all
machine power by turning off the master control relay.
Observe all applicable local codes concerning the placement and
labeling of Emergency Stop switches.
Figure 19.3
Expansion Units. See Chapter 20. Expansion Units. See Chapter 20.
Refer to Chapter 20 for details on line wiring connections and I/O wiring connections to SLC components.
Chapter
19-6
Common Power Source
Isolation Transformer
System Layout Recommendations
We strongly recommend that the processor unit and all expansion units
interconnected with it have the same power source as the input and
output devices. This inhibits electrical interference.
The processor unit power supply monitors the incoming voltage. When
it detects low line voltage, the monitor signals the processor to stop
receiving input data. At the same time, the controller will turn all
outputs OFF and the CPU FAULT LED will be lit.
In addition to monitoring incoming voltage at its power terminals, the
processor unit detects the absence of power to any expansion unit it is
interconnected with. If power to an expansion unit is lost (or not yet
applied), the CPU fault LED will be lit and all controller outputs will be
turned off.
This fault detection makes it necessary that you apply power to the
expansion units before you apply power to the processor unit, to avoid an
unwanted CPU fault. Of course, applying power in sequence is
unnecessary if the processor and expansion units have a common power
source.
You may want to use an isolation transformer in the AC line to the
controller. See Figure 19.3 (Page 19-5). This type of transformer
provides isolation from your power distribution system and is often used
as a "step down transformer to reduce line voltage. Any transformer
used with the controller must have a sufficient power rating for its load.
This power rating is generally expressed in volt-amperes (VA).
To supply the worst-case power to the controller power supply, an
isolation transformer should have a rating of approximately 3 times the
maximum power requirement of the processor and expansion units.
This allows ample power to be delivered to the power supply throughout
the AC cycle. This also allows sufficient power for most types of input
devices connected to the controller. If output devices are connected
through the transformer as in Figure 19.3, their maximum VA
requirements must be added to determine correct transformer size.
Chapter
Special Considerations
Excessive Line Voltage
Variations
Excessive Noise
System Layout Recommendations
19-7
The recommendations given previously will provide favorable operating
conditions for most controller installations. Your application may
involve one or more of the following adverse conditions. Additional
measures can he taken to minimize the effect of these conditions.
The best solution to excessive line voltage variation is to correct any
feeder problems in your distribution system. Where this does not solve
the line variation problem, or in certain critical applications, a constant
voltage transformer can be used. If a constant voltage transformer is
required, it must be connected to the controller power supply and all
input devices connected to the SLC controller. Output devices should be
connected on the same power line, but their connection along the power
line is normally made before the constant voltage transformer. A
constant voltage transformer must have a sufficient power rating for its
load.
When the SLC controller is operating in a "noise-polluted industrial
environment, special consideration should be given to possible electrical
interference.
The effect of electrical interference is reduced by the following:
SLC controller design features.
Proper mounting of controller within an enclosure.
Proper equipment grounding.
Proper routing of wiring.
NOTE - To increase the operating noise margin, we recommend that
you provide suppression for noise generating devices.
19-8
Chapter System Layout Recommendations
Excessive Noise Potential noise generators include inductive loads, such as relays,
(continued) solenoids, and motor starters when operated by "hard contacts like
push buttons or selector switches. Suppression may be necessary when
such loads are connected as output devices or when connected to the
same supply line that powers the controller. Figure 19.4 lists Allen-
Bradley load devices and recommended suppressors. Figure 19.5 shows
how suppressors are used.
If an SLC 150 triac output (1745-LP151, -LP152, -E151, -E152) is
connected with a hard contact to control an inductive load, we
recommend that you use varistors to suppress noise. Do not use
suppressors having RC networks, since damage to triacs could occur.
Allen-Bradley AC surge suppressors which are not recommended for use
with triacs include Catalog Nos. 599-K04, 599-KA04,199-FSMA1, 199-
FSMA2,1401-N10, and 700-N24.
Applications such as high frequency welding equipment and large AC
motors generate excessively high levels of noise pollution. In these
applications, all possible sources of noise should be suppressed. Best
results are achieved when the noise suppressing networks are connected
as closely as possible to the noise generating device.
Figure 19.4
Bulletin 509 Motor Starter 120 VAC 599-K04
Bulletin 509 Motor Starter 240 VAC 599-KA04
Bulletin 100 Contactor 120VAC 199-FSMA1
Bulletin 100 Contactor 240 VAC 199-FSMA2
Bulletin 709 Motor Starter 120 VAC 1401-N10
Bulletin 700 Type R, RM Relays AC coil None required
Bulletin 700 Type R Relay 12VDC 700-N22
Bulletin 700 Type RM Relay 12VDC 700-N28
Bulletin 700 Type R Relay 24 VDC 700-N10
Bulletin 700 Type RM Relay 24VDC 700-N13
Bulletin 700 Type R Relay 48 VDC 700-N16
Bulletin 700 Type RM Relay 48 VDC 70Q-N17
Bulletin 700 Type R Relay 115-125 VDC 700-N11
Bulletin 700 Type RM Relay 115-125 VDC 700-N14
Bulletin 700 Type R Relay 230-250 VDC 700-N12
Bulletin 700 Type RM Relay 230-250 VDC 700-N15
Bulletin 700
Type N, P, or PK Relay
150V max, AC or DC
Miscellaneous
700-N24
electromagnetic devices
limited to 95 sealed VA
Chapter System Layout Recommendations
19-9
Output Contact Protection Inductive output devices such as motor starters and solenoids may
require the use of some type of surge suppression to protect the
controller output contacts. Examples are shown in Figure 19.6.
These surge suppression circuits are connected directly across the
output device. The effect is to reduce arcing of the output contacts
(arcing can be caused by the high transient voltage which occurs when
switching off an inductive device). Suitable surge suppression methods
for inductive AC output devices include a varistor, an RC network, and
an Allen-Bradley surge suppressor (see Figure 19.4). These components
must be appropriately rated to suppress the switching transient
characteristic of the particular inductive device.
For inductive DC output devices, a diode is suitable. A 1N4004 diode is
acceptable for most applications. A surge suppressor can also be used, as
indicated in Figure 19.4.
We recommend that you locate the suppression device as close as
possible to the output device.
Figure 19.5
Surge Suppression for Inductive AC Output Devices
Surge Suppression for Inductive DC Output Devices
* A surge suppressor
can also be used
Contact protection methods for inductive AC and DC output devices. A list of Allen-Bradley suppressors appears in Figure 19.4.
20
Installation
Procedure
Chapter
General The following paragraphs will show you how to
1. Mount the processor, expansion units, and high speed input module.
2. install connection cables.
3. Wire input devices, output devices, and incoming power.
IMPORTANT: Before you begin, plan your system layout according to
the guidelines in Chapter 19, System Layout Recommendations.
1 2
Mounting the SLC
100 Processor and
Expansion Units
1. Screw mounting: The processor unit can be mounted directly to the
back panel of your enclosure using four #10 screws. Hole locations
are shown in the dimension drawing below.
2. DIN rail mounting: The processor unit can be mounted in your
enclosure on a 35 mm by 7.5 mm DIN mounting rail (Catalog No.
199-1DR). Two DIN rail fasteners are provided on the processor unit.
The DIN rail can be screwed, bolted, or welded to the enclosure back
panel. Install the processor unit by hanging the unit on the top edge
of the DIN rail, then pressing the unit toward the rail until it snaps
into place. To remove the processor unit, pry open the fasteners.
20-2
Chapter Installation Procedure
Mounting the SLC Dimensions are shown below. Take note of the important mounting
150 Processor and recommendations. If you are using a high speed input module with the
Expansion Units processor unit, allow panel space to the right of the processor unit. Refer
to Page 19-2 for layout recommendations.
IMPORTANT: SLC 150 processor and expansion units utilize the
mounting back panel as a heat sink for dissipating excess heat during
operation. It is important that you mount the unit on a smooth metal
back panel to provide good thermal conductivity. Back panel
temperature specification: 60C maximum. :
Mounting on a sub panel - In high ambient temperatures (60C),
sub panels not exposed to air outside the enclosure could heat up
beyond 6CPC. In these situations, the sub panel temperature can be
reduced by removing other heat generating equipment from the :
enclosure or by providing fans or air conditioning for cooling.
Chapter KjfTjl Installation Procedure
20-3
Mounting the SLC
150 High Speed Input
Module
Mount directly to the back panel of your enclosure using four #10
screws. The module must be mounted directly to the right of the
150 processor unit or directly to the right of another high speed input
module. Refer to Page 19-2 for layout recommendations.
2.36" 3.0
20-4
Chapter [Installation Procedure
Connection Cables Two cables are used for interconnecting processor and expansion units:
Interconnect cable 1745-C2 is a 10-pin to 10-pin cable supplied with each
expansion unit. Interconnect cable 1745-C3 is a 20-pin to 10-pin cable
supplied with the SLC 150 processor unit. Both cables are 18.5 inches
(47 cm) long. See the figure below for cable connector details.
Important: Do not use cables longer than those provided. Longer cables
could affect the integrity of data communications between the processor
and expansion units, possibly causing unsafe operation.
1745-C3 interconnect cable
supplied with SLC 150 processor unit
1745-C2 interconnect cable
supplied with expansion units
20-pin connector on one end
10-pin connector on
the other end
Black key. Mates with
^ keyslot on expansion unit.
Black key. Mates with keyslot on
processor unit (SLC 1 SO only) or
high speed input module socket.
End views
10-pin connector on
each end of cable.
Black key. Mates with
keyslot on expansion unit.
Keyslot. Mates with white
key on expansion unit.
Chapter
20
Installation Procedure
20-5
Connection Cables
(continued)
The figure below explains how to install the interconnect cables.
A-Connecting expansion units to an SLC 150 processor unit
SLC150 processor unit or SLC ISO expansion units
high speed input module
B - Connecting expansion units to an SLC 100 processor unit
Connecting an expansion unit
to an SLC 150 processor unit:
Use cable 1745-C3, supplied with the
SLC ISO processor unit.
1. Open the access doors.
2. Refer to illustration A. Align the 20-
pin cable connector with the socket
on the processor unit. Push gently;
tabs will lock tlie connector in place.
3. Align the 10-pin connector with the
expansion unit socket having the
keyslot. Push gently; tabs will lock
theconnector in place.
4: Close the access doors.
Connecting an expansion unit
to a high speed input module:
Same as above, but remove the plug
from the high speed input module
socket.
Connecting an expansion unit
to an SLC 100 processor unit:
Us Cable 1745-C2, supplied with the
expansion unit.
1. Open the access doors.
2. Refer to illustration B. Align the
cable connector having the keyslot
with the socket on the processor
unit. Push gently; tabs will lock the
connector in place. !
3. Align the connector having the
; black key with the expansion unit
socket having the keyslot. Push
gently; tabs will Ipck the connector
in place.
4. Close the access doors.
Connecting one expansion unit
to another:
Use cable 1745-C2, supplied with the
expansion unit.
1. Open the access doors.
2. Refer to illustrations A and B. On
the expansion unit already connect
ed to another unit: Align the cable
connector having the keyslot with
the socket. Push gently; tabs will
lock the connector in place.
3. On the other expansion unit: Align
the connector having the black key
with the socket having the keyslot.
Push gently; tabs willlock the
connector in place.
4. Close the access doors.
To remove cable: Move tabs on socket outward; connector will pop out.
20-6
Chapter Installation Procedure
Wiring I/O Devices General wiring recommendations:
and Incoming Power
Use acceptable wire gauge: The I/O wiring terminals are designed
to accept up to two #14 AWG stranded wires.
Label wires: All wiring to I/O devices, power sources, and ground
should be appropriately labeled. Tape, shrink-tubing, or other
dependable means can be used for labeling purposes. In addition to
labeling, insulation color may be used to identify wiring based on
signal characteristics. For example, DC I/O wiring may be blue; AC
I/O wiring may be red.
Bundle wires: Wiring for each I/O device should be bundled
together. If you use ducts, allow at least 2 inches between wiring
bundles and ducts so there is sufficient room to wire the devices.
Power and ground wires, of appropriate gauge, may be used as
jumpers from one I/O terminal to the next, if the I/O terminals are the
same voltage.
Identify terminals: Terminal coverplates have a write-on area for
each terminal. Use this area to identify your I/O devices.
CAUTION: Calculate the maximum possible current in each
power and common wire. Observe all local electrical codes
dictating the maximum current allowable for each wire size.
Current above the maximum ratings may cause wiring to
overheat which may damage equipment.
Before you install and wire the I/O devices, disconnect power from the
controller and any other source to the I/O devices. Remove the
protective terminal coverplates.
Line Wiring Connections Make line connections to the processor and expansion units as follows:
-SLC100
CAUTION: Incorrect wire connections can cause damage to the
processor unit power supply. Do not jumper 115VAC NEUT and
230VAC NEUT together. Do not jumper unused 115VAC NEUT
or unused 230VAC NEUT to the CHASSIS GND terminal.
To L
Ground
Bus
0 T
115VAC
li
<5. 0 Cb
CHASSIS
GND
230VAC
NEUT
1TSVAC
NEUT
tT 5/2 30
VAC
To LO Hi
Ground
Bus
*- 230VAC
<5-, 050
m
CHASSIS
GND
230VAC
NEUT
115V AC
NEUT
115 230
VAC
Wiring Terminals Wiring Terminals
Note: An N.E.C. Class II
y
0
power supply is
Ground required for UL listing.
Wiring Terminals
Catalog Nos. 1745-LP101,-LP102,-LP103,-E101,-E102,-E103, -E105.-E106 Catalog Nos. 1745-LP104, -E104,-E107
Chapter Installation Procedure
20-7
Discrete Input
Wiring Connections
-SLC 100
SLC 100 input circuitry is current sinking. Circuitry includes optical
isolation and surge suppression to guard against damage by
transients from user input devices.
A direct interface to solid state sensing devices and SLC 100 controller
output circuits is possible because of the 2 mA OFF state leakage
current specification, indicated below. Note that the 2 mA value applies
only to inputs 1 and 2 in some units. You can achieve a 2 mA current
value for inputs 3 thru 10 by adding a resistor, as indicated.
Catalog Number
Maximum OFF
State Leakage
Current
Processor
Unit
Expansion
Unit
1745-LP101
1745-LP102
1745-E101
1745-El 02
2 mA, all
inputs
1745-LP1Q3
1745-LP1Q4
1745-E103
1745-El 04
2 mA, inputs 1
and 2 only
To achieve a 2 mA OFF state
leakage current for inputs 3
thru 10, connect a resistor
from the input terminal to
the COM terminal as shown
in the wiring diagram.
Input terminal coverplates are color coded: 115 VAC - red,
230VAC - black, 24VDC - blue. Wire input devices as shown below.
Input wiring terminal numbers in the diagrams (1 thru 10) apply to processor units; Terminals of
20-8
Chapter Installation Procedure
Analog Input Wiring connections for the analog input expansion unit are shown
Wiring Connections below. These connection diagrams use a single analog input circuit,
providing one or two programmable set points. If you require more than
two set points per input circuit, use the connection diagrams on the next
page.
Analog input circuit number 1 is used, as in
connection diagrams 1end 2. Set pointsf 1E and 2
T apply. Arbitrarily, address block 3, addresses 201-
208 is assigned. Examine ON instructions 201 and
202 are programmed for setpoints 1E and2E.
The /'applied vOifage" is V for connection diagram
i, br V1-V2 fpr diagrain 2. When this voltage
increases to set point 1E, instruction 201 goes TRUE.
Vtfhen the vdltage increases to set point 2 E,
instruction 202 goes TRUE. When the voltage drops
J below these set point levels (note hysteresis), the
respective instructions go FALSE.
APPLICATION NOTES
1. + V must be Or 10 volts greater tha n(-).
2. * V and (- > must be kept within 35 volts of
;
> com. :
3. All COM terminals of the expansion unit are
connected together internally.
4. Ail SH termmals are connected together
internally, and are connected to chassis
ground. / / ;;
;i
5. Important wiring recommendations will be
found in Publication 1770-4.1, "Program
mable Controller Grounding and Wiring
Guidelines".
6 Adjustment:'Use a screwdriver with a blade
width of 0.1 inch or less. Procedure:
a) Apply the desired set point voltage or
current to the input-circuit. Measure the
voltage or current, or simulate the condition
* for which the set point is to be adjusted.
b) Turn the adjustment potentiometer until
the corresponding LED indicator lights. CW
increases th setting. There are 18 turns
between minimum and maximum setting.
c) Verify the setting during controller Start
Up procedures.
Connected interrally to chassis ground
; *.' . . . . + V1 I+I1 |-{1)| SH [COM
/ n \ -
1 SI_1
V
HXE
Floating *
1. Voltage source, single ended connection.
Connected internally to chassis ground
Current
+ V1 I + I1 - (1) 1 SH com]
Source
-L
n>o<n;
\ ; ;
:
-
- \ \
:

~L_
Floating
3. Current source. Terminal +V connected
to terminal +1. COM not used.
CAUTION: If an open circuitsexists at the-
source end of the input circuit, the input
could oscillate around the set point, ~
adversely affecting user program operation. ' ^
Chapter installation Procedure
20-9
Analog Input In these connection diagrams, two analog input circuits of the expansion
Wiring ConnGCtionS unit are interconnected, providing four programmable set points (IE,
(continued) 2E, 3E, and 4E in this case).
20-10
Chapter Installation Procedure
Output Wiring
Connections
-SLC100
Wiring connections for output devices are shown below. Note that the
diagram shows the internally-connected output contacts and parallel RC
networks. The RC networks guard against possible damage by
transients from external output devices.
External connections are shown for outputs 11,15, and 16. Weve added
a suppressor in parallel with two of the external devices for the purpose
of contact protection. Contact protection is discussed on Page 19-9.
In cases where you need to limit the effects of leakage current, add a
resistor in parallel with the load as indicated in the diagram.
Since the output contacts are isolated from each other, each output
circuit can be wired independently, with its own ground return. You can
apply a different voltage in each output circuit, as your application
might require. Power or ground wires can be jumpered between sets of
terminals if desired.
You should provide appropriate fusing to protect the output devices and
wiring from short circuits and overload conditions.
12 12
I Ml 1 - -- - - 1 -) Il
To limit the effects of
leakage current, use a
loading resistor across
the load as shown at
the right.
L
t
115V AC
____ 11 mo
;
Resistor
: 115VAC: 15Kohm, 2 watt
230VAC: 15K ohm, 5 watt
Chapter
B
Installation Procedure
20-11
Line Wiring Make line connections to the processor and expansion units as follows.
Connections - SLC 150
To
Ground
Bus
115VAC
Lo Hi
0 0 000
00000
CHASSIS
GND
NOT
USED
NOT
USED
230V AC 115VAC 115/230 NOT
NEUT NEUT VAC USED
CHASSIS NOT not
GND used : r USED
- \
230V AC
NEUT
115VAC 115/230 NOT i: * : . -,
.0 NEUT j I vac : ; USED
* :. - V
Catalog Nos. 1745-LP151, -LP152, -LP153, -LP156, -E151, -El52, -El 53,-El 56
To
Ground
Bus
0 0
24VDC
Note: An N.EC. Class II ;
power supply is J ,
required for UL listing.
0 0
00
CHASSIS NOT NOT ^ i
GND USED USED
NOT 24VOC + 24 NOT
;
USEO NEUT VDC ; USED
Catalog Nos. 1745-LP154. -LP157, -El 54, -El 57
CAUTION: Incorrect wire connections can cause damage to the
processor unit power supply. Do not jumper 115V AC NEUT and
230VAC NEUT together. Do notjumper unused 115 VAC NEUT
or unused 230VAC NEUT to the CHASSIS GND terminal.
20-12
Chapter Installation Procedure
input Wiring Connections -SLC150
1745-LP151, -LP152, -E151, -E152 Current sinking input circuitry
input Wiring Terminals
of 1745-LP151,-LP152
COM COM
LI (Hi) L2 (Lo)
AC Voltage
LS1
PB2
COM COM 101 102 103 | 104 105 106 107 108
10
109
COM
110 COM
In nut Wirino Terminals I
C0M
I
C
H H 1
A

3
I
A04
l
A05
l
A06
l H H H A1o|cQM
of 1745-E151,-E152
COM COM B01 B02 B031 B04 B05| B06 807 B08 B09 B10 COM
Six COM terminals are connected together internally
1745-LP153, -LP154, -E153, -E154 Current sinking input circuitry DC + DC-
Input Wiring Terminals
of 1745-LP153, -LP154
of 1745-E153, -E154 "
PB2
I
*-------- DC Voltage
: -, .
LSI
r-O^O....................
sono sia
/ X (PNP)
/ X. Switch
xe
| COM | COM^
1
I
2
I
3
I
4 | 5 | 6 | 7 | 8 | 9 10
T
>CQm| ;
I com] com) 101 | 102 103 | 104 | 105 | 108 | 107 | 108 | 109 i io | com|
|cOM|cOm| A0l| A021 A03| AQ4| A05| A0e| A07j A0s| A09| fi 401 COM |
COM} COM) BOI) B02j B03| B041 BOS | B061 B071 B08| 809 B101
Six COM terminals are connected together internally
1745-LP 156, -LP157, E156, -E157 Current sourcing input circuitry
Input Wiring Terminals
of 1745-LP156,-LP157
Input Wiring Terminals
of 1745-E 156, -E157 '
DC + DC-
4 ---------- DC Voltage--------------
Solid State > r \
(NPN) Switch / X
PB2
IS1
L<
Xs|
: ; ' ^
| VDCf VDC j 1 1 '
2
I 3 I 4 | 5 | 6 | 7 |*8 | 9 | 10 VDC|,
| VDC| VDC 101 | 102 | 103 | 104 | 105 | 106 | 107 | 108 j;109 |
J
1101 VDC
VDC| VDC| A01 A021 A031 A041 A0s| A06| A07| A08 A09 A10| VDC
-
| VDC| VDC| B01 B02 | B031 B041 B051 BOG | B071 BOB ; B091 B101 VDC
Six VDC terminals are connected together internally
Chapter m Installation Procedure ^ ^
Output Wiring
Connections
-SLC150
Wiring connections are shown on Pages 20-14 and 20-15. Note that each
processor and expansion unit has two isolated groups of outputs plus two
additional isolated hard contact relay outputs.
Triac Outputs: Triac outputs include optical isolation as well as MOV
protection to guard against possible damage by transients from external
outputs. Triac output firing can be synchronized with the AC line to
accomplish zero-cross turn-on and minimize noise generated when
switching loads. This is accomplished by making instruction -{866)-
TRUE in the user program. If this feature is used, your scan time will be
8.3 msec (or some multiple) at 60 Hz and 10 msec (or some multiple) at
50 Hz. A common power source must be used for the processor unit
power supply and output circuits to achieve zero-cross turn on.
Since triacs turn off at AC line zero cross, it is not necessary to use
external surge suppression when switching inductive loads. However, if
hard contacts are connected with triacs to switch an inductive load, we
recommend using varistors for external surge suppression. Do not use
suppressors having RC networks, since damage to triacs could occur.
Refer to Pages 19-8,19-9 for further discussion on surge suppression.
Hard Contact Relay Outputs: Outputs at terminals 12-16 and
112-116 (A12-A16and B12-B16) include arc suppression circuitry (RC
networks) which protects contacts when switching inductive loads. We
recommend that you also connect external surge suppression to protect
the contacts from high transient voltage which occurs when an inductive
device is switched off.
Hard contact relay outputs at terminals 11 and 111 (All and Bll) do not
include internal arc suppression. Contact protection/surge suppression:
See Pages 19-8,19-9.
Transistor Outputs: Catalog Numbers 1745-LP154and 1745-El54
have current sourcing (PNP) transistor outputs. Catalog Numbers
1745-LP157 and 1745-E157 have current sinking (NPN) transisitor
outputs.
We recommend that you connect external surge suppression to protect
transistors from the high transient voltage which occurs when an
inductive device is turned off. An IN4004 diode is acceptable for most
applications. Refer to Pages 19-8,19-9 for further discussion on surge
suppression.
Fusing: You should provide appropriate fusing to protect output
devices and wiring from short circuits and overload conditions. Refer to
Chapter 18, Page 18-9 for recommended fusing.
20-14
Chapter Installation Procedure
Output Wiring
Connections -SZ.C 150
(continued)
Wiring connections for catalog numbers 1745-LP151, -LP152, -LP154,
-E151, -E152, -E154 are shown below.
1745-LP151, -LP152, -E151, -E152 Wiring terminal numbers in the diagram (11 thru 16 and 111 thru
116) apply to 1745-LP151, -LP152* Terminal numbers of 1745-E151,-E152are A11 thru A16and B11 thru B16.
1745-LP154, -E154 Current sourcing (PNP) transistor outputs. Output wiring terminal numbers in the
diagram (11 thru 16 and 111 thru 116) apply to 1745-LP154. Terminal numbers of 1745-6154 are A11 thru
A16and B11 thru 816.
Chapter tnstaltation Procedure
20-15
Output Wiring Wiring connections for catalog numbers 1745-LP153, -LP156, -LP157,
Connections -SLC 150 -E153,-E156,-E157 are shown below.
(continued)
1745-LP153, -LPT56
f
-ET 53, -El 56.' Output wiring terminal numbers in the diagram (11 thru 16
and i 11 thru 116) apply to 1745-LP153, -LP156. Terminal numbers of 1745-E153, -E156 are A11 thru A16
and 611 thru B16. '
s
;-
-Hard contact relay outputs
No arc suppression
Hard contact relay outputs - Group 1 *
VACA/DC is shared
Output /
Wiring
Terminals
Solenoid
Suppressor
DC Voltage-----
DC( + ) DC(-)
Hard contact relay outputs - Group 2*
VCA/PC is shared
r- . l , s 1 r .... 1 r . \ r 1
r -11 -]
Vv
VI
HC
X
12 ;
",
1
3
' 14 15 16
Not
Used
r
1
" i
i
l
l
iC
>C
1 1 2 , 1 1 3 .:i1 4 1 1 5 116
Not.
Used
Suppressor
115VAC ----
L1 (Hi) L2 (Lo) : - U (Hi) i-2 (Lo)
r
Group 1 and 2 hard contact relay
outputs have built-in arc suppression
(R = 120 ohms, C = 0.022 microfarad).
To limit the effects of leakage
current, use a loading resistor across
the load as shown at the right.
Resistor
120VAC: 15K ohm, 2 watt
240VAC: 15K ohm, 5 watt
L2 (Lo)
1745-LP157, -E157 Current sinking (NPN) transistor outputs. Output wiring terminal numbers in the
diagram (11 thru 16 and 111 thru 116) apply to 1745-LP157. Terminal numbers of 1745-E 157 are All thru
A16 and B11 thru B16.
Transistor outputs-Group 1
u
. . . Transistor outputs - Group 2
Hard contact VDC and COM are shared , _ * VDCand COM are shared
relay output
relay output
:.;b;
; i ; :4 i 1 1
\ :T : it- ~t.
"1
+ VDC
1 .?
12 : 13 14 15 16
COM
1
r"i
+ VDC
2 '
;
112 113 114 115 116
COM
; ;; 2
Output /
Wiring ;
Terminals
Solenoid
--------1 .......1 ------
: Suppressor
;
48VDC
DC :
( + )
DC
-)
20-16
Chapter Installation Procedure
Wiring Connections
-SLC150 High Speed
Input Module
Typical connection diagrams are shown below and on the following page.
DIP switches must be set for the input voltage range, input filter
selection, and the encoder/count function. This is explained below.
DIP switches are located under the
module cover, as shown at the
right.
The tables below explain the DIP
switch settings. The maximum
input pulse rate is also listed.
Input
input
Voltage
Switch
Settings
: A
24VDC
12 VDC
5VDC
1 OFF, 2 OFF
1 ON, 2 OFF
T OFF, 2 ON
B
24 VDC
12 VDC
5VDC
3 OFF, 4 OFF
3 ON. 4 OFF
3 OFF, 4 ON
Input
Filter
; Selection
Switch
Settings
'A
4 millisec.
50 microsec.
6 ON
6 OFF
B
4 millisec.
50 microsec.
7 ON
7 OFF
Function
Switch
Settings
Count;
:
" J /
Select this function
to count high speed
input signals received
at terminal A/COUNT
8 ON
Encoder
Select this function
to interfaceto ;
quadrature type
encoder
8 OFF
Il : Maximuin Plse Rate
Note: If maximum or total
frequencies are exceeded, status
bit 9011-904 will be set ON
Number of HSI
Modules
Connected
T 2 3 4
Highest Single
Frequency
(KHz)
5 4 3 2
Highest Total
Frequency
(KHz)
5 . 5, 5 5
HIGH SPEED INPUT MODULE
f i
Lift here to gain access
to the DIP switches.
8
7
6
5
4
3
2
1
ON
DIP switches. The top switch is
number 8 and the bottom switch
is number 1. Switch number Sis
not used.
Move the switch to the right for
the ON position.
To CHASSIS GND
terminal on
!

processor unit
5,12; or
24 VDC
Solid state
sensor or hard
contact input
device
---- / \
I I
--- V -/..
/
Shielded
twisted pair,
Belden or
equivalent
CHASSIS GND
+
A/COUNT
HSI Module Terminals
Connectipns for a solid state sensor or hard ^contact input device
(Count application)
Chapter Installation Procedure
20-17
Wiring Connections
-SLC150 Highspeed
Input Module
(continued)
The following wiring diagrams apply to single-ended and differential
encoder applications. Note: The purpose of the B terminal of the HSI
module is to indicate a direction change for input pulses. This function
is not recognized by SLC 150 Series A processor units. In the diagrams
below, the B channel of a quadrature type encoder is connected to the B
terminals to help increase immunity to noise and shaft jitter.
5 VDC
Differential wiring connections for a Bulletin 845Nencoder
Chapter Start-Up
General Start-up involves the following procedures, to be carried out in sequence:
A. Inspect the installation before power is connected.
B. Disconnect motors and other devices which cause machine motion.
C. Test inputs.
D. Test outputs.
E. Enter and verify your program.
F. Test the system with motors and other motion-causing devices
reconnected.
G. Go thru a dry run of the application.
The purpose of these procedures is to isolate such problems as wiring
mistakes, equipment malfunction, and programming errors in a
systematic, controlled manner.
We urge you to go thru these procedures very carefully. This will help
avoid possible personal injury and equipment damage.
Do not attempt system start-up until you are thoroughly familiar with
the controller components and programming/editing techniques
discussed in earlier chapters. You must also be thoroughly familiar
with the particular application.
Note: For general recommendations concerning installation safety
requirements and safety related work practices, refer to NFPA 70E,
Electrical Safety Requirements for Employee Workplaces.
SLC PERSONAL COMPUTER SOFTWARE USERS: This chapter is written with the
assumption that you will be using a pocket programmer in the start-up procedures.
If you are using the SLC Persona! Computer Software, you will find that the multi
rung display and monitoring capabilities are valuable tools. However, the SLC
Personal Computer Software does not allow you to use the FORCE function as we
recommend in this chapter.
Inspecting the You can often prevent serious problems in later test procedures by first
Installation (A) making a thorough physical inspection. We recommend that you:
1. Make sure that the controller and all other devices in the system are
securely mounted.
2. Check all wiring, including: connections from the main disconnect to
the controller input; the master control relay/emergency stop circuit;
input device circuits; output device circuits; expansion cables.
Make certain that all wiring connections are correct and that there
are no missing wires. Check the tightness of all terminals to make
certain wires are secure.
3. Measure the incoming line voltage to be certain that it corresponds to
controller requirements and that it falls within the specified voltage
range. See specifications for input voltage ranges.
Chapter
21-2
y
Disconnecting Motion-
Causing Devices (B)
Testing Inputs (C)
Start-Up
In the following test procedures, the controller will be energized. As a
safety precaution, you must make certain that machine motion will not
occur. The preferred way to disconnect a motion-causing device such as
a motor is to disconnect the motor wires at the motor starter or the motor
itself. In this way, you can test the operation of the starter coil,
verifying that your output circuit is wired correctly and functioning.
Similarly, the preferred way to disconnect a solenoid is to disengage the
valve, leaving the coil connected.
In some instances, you may not be able to disconnect a device the
preferred way. In this case, it will be necessary to open the output
circuit at some convenient point.
For circuit testing purposes, it is best to open the circuit at a point as
close as possible to the motion-causing device. For example, your output
might be a relay coil which in turn energizes a motor starter; if it is
impractical to disconnect the motor wires, the next best thing to do is to
open the circuit at a point between the motor starter and the relay
contact.
WARNING: Machine motion during system checkout can be
hazardous to personnel. During the following checkout procedures
C, D, and E, you must disconnect all devices which, when energized,
might cause machine motion.
When you are certain that machine motion can not occur with the
controller energized, you can begin testing inputs. Follow these steps:
1. Energize the controller.
2. Connect the pocket programmer and enter the Clear Memory mode
(mode 1). Press ENTER when the display prompts you with SurE ? A
clear memory is necessary for this test.
3. The controller will enter the Program mode automatically when the
memory is cleared.
Enter the test rung shown below. The Examine ON instruction
should be assigned the address corresponding to the first input you
will test. The Output instruction should be assigned an internal
address, 701, to avoid involving output circuits at this time.
Address of
input device
being tested
i
XXX
Input test rung
4. Place the controller in the Test-Continuous Scan mode (5). Cursor to
the Examine ON instruction in the test rung with the programmer.
Chapter
Testing Inputs (C)
(continued)
Start-Up
21-3
5. Manually close and open the addressed input device. Use a wooden
stick for this purpose, as recommended below.
WARNING: Never reach into a machine to actuate a switch,
since unintentional machine motion can occur. Use a wooden
stick or some other non-conductive device to guard against
personal injury and electrical shock.
Observe the ON LED indicator on the pocket programmer and status
LED on the processor or expansion unit. The LEDs should be ON (lit)
when the input device is closed, and OFF when the input device is
open. Say for example the first input device you wanted to test was an
Examine ON instruction at address 001 in rung 1. When input 001 is
ON, the display on the programmer would look like this:
nr -( >- T _3"
m
-(RTO)- -{RTF>- -<CTU)- '(CTD)' -(RST)-

-(U- -tu>- -(SQD- -<SQO)- - -(ZCL)-

-<MCR)- PRT PROG ON FORCE

ADDRESS
RUNG/ERR
i
j;
DATA MODE
Cursor to the output instruction at address 701. It should be ON
when the input device is ON.
If the ON LED and test rung respond properly, testing of the first
input is complete. Repeat this procedure for each input. To save time,
begin at step 3, by entering the Program mode. Remove the Examine
ON instruction of the test rung, and insert a new Examine ON
instruction with the appropriate address.
We recommend that you do not program multiple rungs. This is a
potential source of confusion and errors.
Troubleshooting: Ifa status indicator on the processor or expansion
unit or the ON LED on the programmer fails to go ON when it should,
check the following:
a) The input terminal power source.
b) The input circuit wiring.
c) The input device itself.
d) The expansion unit connection.
if the source of the problem is not found to be in a), b), c), or d), try
connecting to another input terminal. If the problem still exists, the
processor unit or pocket programmer may need replacement. Contact
your local Allen-Bradley representative.
21-4
Chapter \ Start-Up
Testing Outputs (D) After all inputs have been tested and are functioning properly, test the
outputs. Once again, make certain that no machine motion can occur.
Follow these steps:
1. Energize the controller.
2. Connect the pocket programmer and enter the Clear Memory mode
(mode 1). Press ENTER when the display prompts you with SurE ?
3. The controller will enter the Program mode (mode 2) automatically.
Enter the test rung shown below. The Examine ON instruction is
assigned an internal address, 701, to avoid involving external inputs.
The Output instruction should be assigned the address corresponding
to the first output device you will test.
Address of
output device
being tested
i
Output test rung
4. Place the controller in the Run mode (mode 3). Display the test rung
on the pocket programmer.
5. Move the cursor to the output instruction. Force this instruction
address to the ON state, using the Force ON function. The FORCE
LED on the programmer should be lit. Also, the FORCED I/O
indicator on the processor unit should light. If for example your first
output device to be tested were at address Oil in rung 3, the pocket
programmer display should look like this:
Mb -( )- T J

-(RTO)- -{RTFJ- (CTU)- -{CTD)- -(RST-

-<L)- -(u )- -(SQO- -(SQO)- -(ZCL)-

-{MCR- PRT PROG ON FORCE

ADDRESS
RUNG/ERR
' l ( ' j
DATA MODE
Now observe the output terminal status indicator LED and the output
device. The LED should be ON and the output device should be
energized (unless you had to purposely disconnect it).
6
6. Remove the Force ON condition, using the Force OFF function. The
test rung should go FALSE, the output status indicator should go
OFF, and the output device should be de-energized.
Chapter
Testing Outputs (D)
(continued)
Entering and Testing
Your Program (E)
Start-Up
21-5
If the LED status indicators, and output device functioned properly,
testing of the first output is complete. Repeat this procedure for each
output. To save time, begin at step 3, by entering the Program mode,
deleting the test rung, and re-entering it with the appropriate output
address.
We recommend that you do not program multiple rungs. This is a
potential source of confusion and errors.
Troubleshooting: If the output terminal LED status indicator does not
go ON and the output device does not energize, try another output
terminal and check the expansion unit connection. If the problem still
exists, the processor unit or pocket programmer may need replacement.
Contact your local Allen-Bradley representative.
If the output terminal status indicator goes ON but the output device
fails to operate, check:
a) The output terminal power source.
b) The output circuit wiring.
c) The output device itself.
If the source of the problem is not found to be in a), b), or c), the processor
unit or pocket programmer may need replacement. Contact your local
Allen-Bradley representative.
After all inputs and outputs have been tested and are functioning
properly, you can enter your program in the processor RAM memory.
Before entering your program, enter mode 1 and follow the prompting
message to clear the processor RAM memory. The processor will enter
the Program mode automatically when memory is cleared. Enter your
program using the keystroke sequences you have become familiar with
in previous chapters. Careful program entering will reduce the chance
of program related problems.
Program Verification - After the program has been entered, it must
be verified. Each instruction and rung must be closely checked for
errors before the controller is placed into operation. Check your written
program, rung for rung, against the program you have just entered into
the processor RAM. Use the NEXT and LAST keys to step through your
program and check addresses and other information associated with
your instructions. The most common mistakes in program entry are:
Incorrect addressing of instructions.
Omission of an instruction or rung.
Mistaken entry of the same output instruction and address twice in a
program. This will cause the first output instruction to be ignored.
Program Checkout Using the Test-Single Scan Mode - After the
user program has been entered and verified, the Test-Single Scan mode
(mode 4) can be used to verify correct operation of the user program.
This mode allows you to step through the sequence of events that are to
be executed by your program.
21-6
Chapter Start-Up
Entering and Testing
Your Program (E)
(continued)
When the controller is placed in the Test-Single Scan mode, the
processor unit will complete one scan of the user program each time the
ENTER key is pressed. Controller outputs are disabled in this mode,
however execution of the user program can be monitored with the
programmer. Timer and time driven sequencer accumulated values will
be incremented by 0.1 for each scan of the user program if rung
conditions are correct. To check out the user program using the Test-
Single Scan mode follow the steps below.
1. Place the controller in the Test-Single Scan mode using the pocket
programmer.
2. Use the cursor keys to display the output instruction or ladder rung
that you wish to monitor.
3. Simulate the input conditions necessary to execute the first step of the
user program. If it is not practical to manually activate the input
device, use the FORCE function to simulate the proper condition.
4. As you simulate the input conditions that will make rung 1 TRUE,
the status of your input devices changes state but you will not be able
to see this change updated on the programmer until the ENTER key
is pressed. Press the ENTER key and monitor the programmer
display to verify correct operation of the user program.
Say for example your first rung is an Examine ON instruction and an
Output Energize instruction. You could simulate the ON condition
necessary to make the Examine ON instruction TRUE. The ON LED
for the examine instruction would not be lit until you press the
ENTER key. When you turn the input device OFF, the Examine ON
instruction will continue to remain TRUE (ON LED lit), until the
ENTER key is pressed again.
5. Repeat steps 2 thru 4 for each step of your program to verify that the
user program is executed correctly.
Motion Checkout (F) Now that program execution has been verified, checkout of machine
motion can begin. All persons involved with the programming,
installation, layout design, machine or process design and maintenance
should be involved in making decisions for determining the best and
safest way to test the total system.
The following procedures are general in nature. Individual conditions
may warrant their modification. The basic approach is to initiate
testing with the least amount of machine motion. Only some outputs
are allowed to generate machine motion. Then additional machine
motion can be added gradually, thereby allowing any problems to be
. detected more easily under controlled conditions. The following
procedure gives steps for testing machine motion using one output at a
time.
Chapter
Motion Checkout (F)
(continued)
Dry Run (G)
Start-Up
21-7
WARNING: During all phases of motion checkout, station a person
ready to operate an Emergency Stop Switch if necessary. The
Emergency Stop Switch will de-energize the master control relay
and remove power from the machine. This circuit must be hard
wired only; it must not be programmed.
Procedures are as follows:
1. Identify the first output device to be tested and reconnect its wiring.
WARNING: Contact with AC line potential may cause injury to
personnel. When reconnecting wiring, make sure that AC power
disconnect switch is opened.
2. Place the controller in the Run mode and observe the behavior of the
output device. To do this, simulate the input conditions necessary to
energize the output in the program. If it is not practical to manually
activate an input device, use the FORCE function to simulate the
proper input condition.
Repeat steps 1 and 2, testing each output device, one at a time.
After thoroughly checking out the controller system and program,
proceed with a dry run of the application with all output devices
enabled. This dry run will vary with the application. A machine tool
dry run would test the program with all outputs enabled but without
tooling an actual piece part. After the entire system is checked out, and
your dry run has been completed satisfactorily, we recommend that you
load your program into an EEPROM memory module for back-up
program storage. Refer to Page 17-3 for directions on loading the
EEPROM from RAM. This step completes start-up procedures. Your
SLC Programmable Controller is now ready for operation.
Chapter Maintenance and
Troubleshooting
General The SLC controller has been designed to simplify maintenance and
troubleshooting procedures. By observing the diagnostic indicators on
the front of the processor unit, the majority of faults can be located and
corrected. These indicators, along with error codes displayed on the
programmer and PC software screen, help trace the source of the fault to
the users input/output devices, wiring, or the controller.
SLC PERSONAL COMPUTER SOFTWARE USERS: This chapter is written with the
assumption that you will be using a pocket programmer in certain troubleshooting
procedures. You can also use the SLC Personal Computer Software, except in
instances where we suggest using the FORCE function. The SLC Personal Computer
Software does not allow you to use the FORCE function.
Safety
Considerations
Safety considerations are an important element of proper trouble
shooting procedures. Actively thinking about the safety of yourself and
others, as well as the condition of your equipment, is of primary
importance. Several safety areas are discussed below.
Power Supplies: Before working on a power supply, always remove
the AC power source at the main power disconnect switch. When using
more than one power supply, be sure to disconnect all of them.
Replacing Fuses: When replacing a fuse, be sure to remove all power
from the system.
Main Power Disconnect: The main power disconnect switch should be
located where operators and maintenance personnel have quick and
easy access to it. Ideally, the disconnect switch is mounted on the
outside of the enclosure, so that it can be accessed without opening the
enclosure. In addition to disconnecting electrical power, all other
sources of power (pneumatic and hydraulic) should be de-energized
before working on a machine or process controlled by an SLC controller.
Activating Devices When Troubleshooting: When troubleshooting,
never reach into the machine to actuate a device. Unexpected machine
motion could occur. Use a wooden stick. A metal rod is more likely to
damage the machine and could conduct electricity back to you.
Stand Clear of Machine: When troubleshooting any controller
problem, have all personnel remain clear of the machine. The problem
could be intermittent, and sudden unexpected machine motion could
occur. Have someone ready to operate an emergency stop switch in case
it becomes necessary to shut off power to the machine.
Program Alteration: There are several causes of alteration to the user
program, including extreme environmental conditions, Electromagnetic
Interference (EMI), improper grounding, improper wiring connections,
and unauthorized tampering. If you suspect the memory has been
altered, check the program against an approved version such as on an
EEPROM memory module.
22
222
Chapter Maintenance and Troubleshooting
Safety
Considerations
(continued)
Hardware Redundancy: Circuits installed on the machine for safety
reasons, like overtravel limit switches, stop push buttons, and
interlocks, should always be hard-wired directly to the master control
relay. These devices must be wired in series so that when any one device
opens, the master control relay is de-energized thereby removing power
to the machine. Never alter these circuits to defeat their function.
Serious injury or machine damage could result.
Power Distribution: There are some points about power distribution
that you should be aware of. First, the master control relay must be able
to inhibit all machine motion by removing power to the machine I/O
devices when the relay is de-energized.
Second, if you are using a DC power supply, interrupt the load side
rather than the AC line power. This avoids the additional delay of
power supply turn-on and turn-off. The DC power supply should be
powered directly from the fused secondary of the transformer. Power to
the DC input and output circuits is connected through a set of master
control relay contacts.
Periodic Tests of Master Control Relay Circuit: Any part can fail,
including the switches in a master control relay circuit. The failure of
one of these switches would most likely cause an open circuit which
would be a safe power-off failure. However, if one of these switches
shorts out, it no longer provides any safety protection. These switches
should be tested periodically to assure they will stop machine motion
when needed.
Pteven tive The printed circuit boards of the controller must be protected from dirt,
Maintenance oil, moisture and other airborne contaminants. In order to protect these
boards, the controller must be installed in an enclosure suitable for the
environment. The interior of the enclosure should be kept clean and the
enclosure door should be kept closed whenever possible.
Regularly inspect your terminal connections for tightness. Loose
connections may cause improper functioning of the controller or damage
the components of the system.
WARNING: To ensure personal safety and to guard against
damaging equipment, inspect connections with incoming power
OFF.
The National Fire Protection Association (NFPA) gives
recommendations for electrical equipment maintenance. Refer to article
70B of the NFPA for general requirements regarding safety related
work practices.
Chapter
22
Spare Parts
Terminal Block Removal
- SLC150 Processor and
Expansion Units
Maintenance and Troubleshooting
22-3
Stock a full set of spare parts to minimize down-time. We recommend
that at least 10% (minimum of 1) of each SLC controller component be
stocked as spare parts. Recommended spare parts are listed below.
5LC 100 Processor Unit : 1745-LP1Q1, -LP102,
-LP103.-LP14
SLC 100 Basic Expansion Unit 1745-El 01, -E102,
-E103, -E104
SLC 100 Relay Output Expansion Unit 1745-E15
SLC 100 Analog Input Expansion Unit 1745-E106, -El 07
SLC 150 Processor Unit ; , 1745-LP151, -LP152,
-LP153, -LP154,
-LP156, -LP157
SLC 150 Expansion Unit 1745-El 51,-E152,
-E153.-E154,
-El 56, -E157
SLC 150 High Speed Input Module 1745-E155
Pocket Programmer 1745-PT1
EE PROM Memory Module 1745-MI
Processor/Programmer Interconnect Cable 1745-C1
Expansion Unit Interconnect Cable -10 pin to 10 pin 1745-C2
Expansion Unit Interconnect Cable -20 pin to 10 pin 1745-C3
Plastic Parts Kit-SLC 100 ' 1
x
1745-N3
Plastic Parts Kit-SLC 150 1745-N4
Terminal Block tor Power Supply, inputs, and Outputs
- SLC 150 Processor and Expansion Units
1745-N5
Relay Board - SLC 100 Processor Unit 1745-R1
Relay Board - SLC 100 Basic Expansion Unit 1745-R2
Relay Board-SLC 100 Relay Output Expansion Unit 1745-R3
Battery Assembly - SLC 100 and 150 Processor Units 1745-B1
Power Spply Fuses^ISpf package:
j SLC 100/150 AC Processen Units and AC Basic Expansion Units
SLC 100/150 DC Processor Unit and DC Bask Expansion Units
SLC 100 Relay Output Expansion Unit
' SLC10AC Anaioglnput Expansion. Unit
SLC 100 DC Analog Input Expansion Unit
1745-F1
1745-F2
1745-F3
1745-F4
1745-F5
The wiring terminal blocks can be removed to allow replacement of the
processor unit without removing power supply, input, or output wiring.
To remove a terminal block, back out the two screws located at the ends
of the terminal block. Alternate between the two screws, backing out
about five turns at a time. This will help avoid binding.
To replace the terminal block, align the terminal block screws with the
holes on the chassis. Alternate between the two screws, as you did when
removing the terminal block. Press on the center of the terminal block
as you tighten the screws to help guard against an improper seat.
^ ^ ChaptertjtMaintenance and Troubleshooting
Troubleshooting If installation and start-up procedures detailed in Chapters 19, 20, and
21 were followed closely, your SLC controller will give you reliable
service. If a problem should occur, the first step in the troubleshooting
procedure is to identify the problem and its source. Do this by observing
your machine or process and by monitoring the diagnostic indicators on
the controller. By doing this, the source of a problem can generally be
narrowed down to the processor/expansion unit, wiring, or the
input/output devices.
If a problem should occur within the processor/expansion unit, we
recommend that you start troubleshooting the following areas.
Power Supply The power supply is located in the processor/expansion unit. Its purpose
is to convert incoming power to the logic level voltage required by the
processor/expansion unit, programmer and EEPROM module. The DC
POWER green LED indicator on the front of the processor/expansion
unit is ON when the proper logic level voltage is at the output of the
power supply. If the DC POWER indicator is not illuminated when
incoming power is available, the following should be checked to identify
the source of the problem:
1. Incoming power wiring and connections.
2. Power supply fuse. See Pages 22-5 and 22-6 for replacement
procedures.
3. Incoming power voltage level. See following paragraph.
Incoming Voltage Monitor: The power supply monitors the voltage at
the incoming power terminals:
Specified Voltage Allowable Range
115VAC 85-132VAC
230VAC 170-265VAC
24VDC 18-30VDC
If the incoming voltage falls outside the allowable voltage range, the PC
RUN indicator on the processor unit will extinguish and all outputs will
be disabled. Note that the DC POWER indicator might not be
extinguished because the voltage could be sufficient for the power
supply to provide the necessary logic level voltage.
Chapter
22
Maintenance and Troubleshooting
22-5
Processor Restart Switch
Power Supply Fuse
Replacement
The restart switch (MAN/AUTO) on the processor can be used in
conjunction with the incoming voltage monitor feature to aid in
troubleshooting the controller. When the incoming voltage monitor
detects abnormal line voltage, it shuts the processor down. The
processor restart switch (MAN/AUTO) setting determines what happens
when power is restored to acceptable levels. (The processor must have
been in the Run mode when the outage occurred.)
If you place the restart switch in the Manual (MAN) position, the pro
cessor will not automatically enter the Run mode on power-up. Instead,
the processor goes through its normal diagnostic tests, but the outputs
remain disabled. To enter the Run mode, you must move the restart
switch to the Automatic (AUTO) position or use the pocket programmer.
This feature provides you with the additional safety of manually
restarting the controller when you want.
In the AUTO position, upon power-up, the processor goes through its
normal diagnostic tests then automatically enters the Run mode. (The
processor must have been in the Run mode when power was removed.)
Under normal power-up conditions, the DC POWER indicator will
illuminate. If a power supply fuse is blown, the DC POWER indicator
will not illuminate. One of the following conditions could cause a blown
power supply fuse:
Excessive line voltage.
Internal power supply malfunction.
CAUTION: Use only replacement fuses of the type and rating
specified for the unit. Improper fuse selection may result in
equipment damage.
WARNING: Contact with AC line potential may cause injury to
personnel. Remove system power before attempting fuse
replacement.
s
s
's
#
'
22-6
Chapter Maintenance and Troubleshooting
Power Supply Fuse After the conditions causing the malfunction have been corrected, the
Replacement fuse
can
be replaced. It is especially important to check the wiring.
(continued) Replacement procedure:
Replacement Procedure - SLC 100 Units: See Figure 22.1.
1. Disconnect line power to processor/expansion unit.
2. Remove the EEPROM module if you are replacing the processor unit
fuse. Loosen the 2 cover screws. Move the cover aside to expose the
fuse. The cover does not have to be removed.
3. Locate the fuse. Use a miniature fuse puller to grip the fuse and
remove it from its holder. Discard this fuse and replace it with the
recommended replacement fuse.
4. Replace the cover and tighten the screws. Do not over tighten.
6. Restore power. The DC POWER indicator should now be lit.
Replacement Procedure - SLC 150 Units: See Figure 22.1.
1. Disconnect line power to processor/expansion unit.
2. Remove the fuse compartment cover.
3. Remove fuse holder. Push the handle to the left, then pull outward.
4. Remove the fuse from its holder and replace it with a recommended
replacement fuse.
5. Place the fuse holder back into its compartment. Push inward until it
locks into place. You may first have to shift the position of the wires.
6. Replace the fuse compartment cover.
7. Restore power. The DC Power indicator should now illuminate.
Figure 22.1
Chapter
Processor Fault
Detection
Maintenance and Troubleshooting
22-7
The processor continually monitors itselffor any problems that might
cause the controller to improperly execute the user program. A built-in
"watch-dog timer circuit will time out if a processor hardware
malfunction occurs. Errors in memory data are also detected through
built-in diagnostic routines.
If a processor hardware malfunction or a memory data error is detected,
the processor CPU FAULT indicator will light and outputs are disabled.
To clear a processor hardware fault, follow this procedure:
1. Toggle the processor restart switch (MAN/AUTO). If this does not
clear the fault, then:
2. Turn processor power OFF, then ON, If the fault still does not clear:
3. Connect the pocket programmer to display the error code. Processor
error codes, fault descriptions and remedies are listed in Figure 22.2a
and 22.2b.
Figure 22.2a
01 h-Pracessor-hardwareproblem:
malfunction hascaused"watdv.
dog timer to time-out
Contact your A-B representative for
repair or replacement.
02 Processor hardware problem:
unable to write in RAM.
Contact your A-B representative for
repair or replacement.
03 Processor hardware problem:
internai communication error.
Contact your A-B representative for
repair or replacement.
04 Processor hardware problem:
unable to write in RAM.
Contact your A-B representative for
repair or replacement.
05 s Processor memory problem:
incorrect checksum in user
program.
Correct user program or delete
program and re-enter.
06 '* Processor memory problem : parity
error in user program op-code. -
Correct user program or delete
program and re-enter.
07 i Processor*memory problem: preset
onaccumutated valuesout of range
of user program.
Correct user program or delete
program and re-enter.
03 Processor memory problem:
incorrect checksum in I/O table.
Correct user program or delete
program and re-enter.
09 Processor scan time exceeds 100
ms.
Reduce size of user program.
22-8
Chapter
22
Maintenance and Troubleshooting
Processor Fault
Detection
(continued)
Error Codes Detected by the SLC 150 Processor only: Error codes
27-1, 27-2, and 27-5 are detected by the SLC 150 processor only. If
any of these error conditions occur, the pocket programmer will initially
display error code 27. You must then press the CANCEL CMD key to
display the -1,-2, or -5 suffix.
Figure 22.2b
27-1
High speed input
modute problem ;
Check the high speed input module connection.
* Determine whether you are using an insufficient
number of high speed Input modules to support
your program.
* Determine whether two high speed sequencer
instructions have been assigned the same address.
27-2 Zero-cross turn- '
on failure
, Check to make sure that an AC powered unit is
used when address 866 is used. Check the line
frequency. Refer to note below.
If you are using an AC powered unit and the line
frequency is within range listed in note , the
problem is a hardware failure. Contact your local
A-B representative for repair or replacement.
27-5 ZCL programming
error
Determine whether you have programmed more
than 8 nested ZCL zones.
Make certain that each ZCL start rung has a ZCL
. end rung.;
Error Code 27-2: The processor measures the input power frequency
each time you power-up. If the frequency falls outside the ranges of
57-63 Hz or 47-53 Hz, a processor fault may occur. The pocket
programmer will display error 27. When this happens, press the cancel
key; if the number 2 appears, the error is a zero-cross fault. (If you are
using the SLC Personal Computer Software, a message indicating a
Zero-Cross fault appears on the screen.)
Correct the fault as follows:
1. Remove input power to the processor.
2. Correct the input power problem so that the input frequency remains
within a valid range.
3. Apply input power to the processor.
Note: When you perform the corrective action above, retentive outputs
(timers, counters etc.) will remain in their last state when the Run mode
is re-entered. If you want the retentive outputs to be reset to their Off
states on power-up, you must clear the error message before performing
the corrective steps above. Do this by pressing the cancel key until the
message "Run 3 is displayed. (If you are using the SLC Personal
Computer Software, press any key until the main menu is displayed.)
Then correct the fault as indicated above.
Chapter
Processor Fault
Detection
(continued)
22
Maintenance and Troubleshooting
22-9
For your convenience, a processor diagnostic guide is shown in
Figure 22.3.
Figure 22.3
on ; ; ON OFF OFF None; normal status indication in Run
mode.
on :
: : off OFF OFF None; normal status indication when not
in Run mode.
on : OFF
{If con
troller is
in Run
; mode.)
OFF OFF Processor restart switch in MAN position.
OFF OFF - OFF
:
OFF 1. Incoming power absent.
2. Incoming power wiring /connection
problem.
3. Blown power supply fuse. (To replace
fuse, see Pages 22-5,22-6.)
4. Power supply malfunction.
ON OFF ; ;
{If con
troller is
in Run
mode.)
ON : OFF
1. Processor hardware fault {error codes
1 -4). See Figure 22.2a.
2. Processor memory fault {error codes 5 -
9). See Figure 22.2a.
3. Expansion unit problem (error code 26).
See Page 22-16.
4. Incoming power below minimum
voltage level (see Chapter 18,
Specifications).
ON ON
{if con
troller is
in Run
mode.)
OFF : ; on ;
Battery needs to be replaced.
22-10
Chapter Maintenance and Troubleshooting
RAM Memory The SLC 100 processor unit is supplied with battery backup as
Battery Backup Standard. The SLC 150 processor unit is supplied with capacitor back
up as standard, but can be equipped with battery backup as an option.
Figure 22.4 shows the location of the battery compartment in the SLC
100 and SLC 150 processors.
Figure 22.4
Battery compartment,
SLC 100 processor unit.
Battery Handling Precautions
Lithium batteries should be handled and disposed of carefully. Follow the procedures below to
ensure proper battery and controller operation, and to reduce hazards to personnel:
e Onlyusethebatteryforitsintendedapplication.
Do not attempt to charge the battery. An explosion could result, or the cell could overheat
and cause burns to personnel.
Do not open, puncture, crush or otherwise mutilate the battery. The possibility of an
explosion exists and/or toxic, corrosive and flammable'chemicals would be exposed.
Do not incinerate or expose the battery to high temperatures. Do not solder the battery or its
leads. An explosion could occur.
Do not short together the positive and negative leads since the battery could overheat.
Dispose of used batteries immediately. Do not store used batteries longer than 3 months.
Chapter
RAM Memory
Battery Backup
(continued)
Maintenance and Troubleshooting
22-11
Battery Replacement - SLC 100: A lithium battery is housed in a
small compartment on the front of the processor unit. This battery
provides backup power to the processor RAM when external power is
removed. The battery provides backup power for a typical life span of 2-
3 years. Actual battery life span may vary depending on controller
environmental conditions.
The processor BATTERY LOW indicator will be lit when the battery
voltage falls below a threshold voltage. Replace the battery at this time.
You can replace the battery without disconnecting power or disturbing
normal operation of the machinery. Procedure:
1. Remove small compartment door on front of processor.
2. Remove battery from compartment. Unplug lead wires from
processor.
3. Connect new battery making sure that the slot on the
battery lead is correctly aligned with the key of the processor
units socket. Insert battery into compartment.
4. Replace compartment door.
Battery Installation or Replacement-SLC 150: You can install or
replace the battery, Catalog No. 1745-B1, without disconnecting power
or disturbing normal operation of your machinery. Procedure:
1. Remove battery compartment door from the front of the processor
unit.
2. If you are installing a battery in a new processor unit (battery never
installed before), unplug the battery connector and lead wires (red
and white) by inserting your finger into the compartment and pulling
up on the lead wires. If this cannot be done with a finger, you may
wish to use a needle nose pliers to pull out the lead wires.
2a. If you are replacing an old battery, remove the battery assembly
stored in the compartment. To do this, first pull up on the lead wires
and remove them from the compartment. The battery is held in
place by a small retainer clip on the right of the battery. Apply
pressure on the left of the battery with a small screwdriver or other
small tool to push the battery against the clip while pulling the lead
wires up at the same time. This will allow the battery to be pulled
straight out of the compartment. Unplug female from male end of
connector to disconnect old battery.
3. Connect a new battery making sure that the slot on the battery
assembly connector aligns with the key of the processor unit socket.
4. Insert battery into compartment minus side first (white lead wire).
Push the retainer clip to the side with the battery while inserting so
that the battery will fall to the bottom of the compartment and stay in
place with the clip.
5. Place battery connector and lead wires in compartment.
6. Replace compartment door.
22 22-12
Chapter maintenance and Troubleshooting
I/O Hardware When troubleshooting, pay careful attention to these general warnings:
WARNING: Have all personnel remain clear of the controller
equipment when power is applied. The problem may be
intermittent and sudden unexpected machine motion could occur
and result in injury. Have someone ready to operate an emergency
stop switch in case it becomes necessary to shut off power to the
controller equipment. Also see NFPA 70E Part II for additional
guidelines for safety related work practices.
WARNING: Never reach into a machine to actuate a switch since
unexpected machine motion can occur and cause injury. Use a
wooden stick. A metal rod could damage the machine and/or
conduct current to the person holding it.
WARNING: Remove all electrical power at the main power dis
connect switches before checking electrical connections or inputs /
outputs causing machine motion.
If the controller is operating in the Run mode but output devices do not
operate as programmed, most likely the problem is one of the following:
I/O devices.
Wiring between I/O devices and user power.
User power.
Identifying one of the above as a problem can usually be narrowed down
by comparing the actual status of the suspect I/O with controller status
indicators. This comparison technique is similar to procedures given in
Start-Up, Chapter 21.
Each I/O device has two status indicators. One of these indicators is
located on the front of the processor/expansion unit and the other is the
"ON LED on the programmer. These two status LEDs indicate the
logical (TRUE/FALSE) nature of programmed instructions
corresponding to connected I/O devices.
Testing Outputs: If an output device does not energize as expected,
observe the appropriate status indicator on the processor/expansion unit
to see if it is lit.
If the status indicator is lit but the output device does not energize,
check wiring connections between the wiring terminals and output
device. If wiring connections appear correct, use a test light or voltmeter
to check for power at the output wiring terminals. If there is power at
the wiring terminals, check your output device.
If there is no power at the wiring terminals, the processor/expansion
unit output relay may be faulty. Reconnect the output device to a spare
output terminal. If none is available, replace the output relay board.
If the status indicator is not lit, the logical status of the corresponding
programmed instruction is FALSE. Connect the pocket programmer
and monitor each instruction in the programmed rung and observe the
"ON LED status indicator on the programmer. A continuous path of
TRUE condition instructions must exist in order for the status indicator
to be lit and the output device energized. If a continuous path of TRUE
condition instructions does not exist, your problem might involve input
devices.
Chapter
22
I/O Hardware
(continued)
Maintenance and Troubleshooting
22-13
If you want to make sure that your output can be energized before you
start checking your input devices, you can use the Force function to
energize the output. Refer to Page 16-1 for information on using the
Force function. If the Force function energizes your output, your
processor/expansion unit is functioning properly. Move on and test the
input device that energizes the problem output.
A guide for troubleshooting output devices is shown in Figure 22.5.
Figure 22.5
il & p.'#- ^ ^
Energized
(ON)
K: U! : true
1
' ; None. Correct status
indication.
De-energized
(OFF)
OFF FALSE
- "' t p "
None. Correct status
indication.
De-energized
: (OFF)
ON TRUE
1. Wiring to output device
at fault.
2. Output device fault.
3. Processor/expansion unit
output relay fault.
De-energized
(OFF)
OFF
Rung conditions are
TRUE but output
instruction is FALSE.

Programming error. Two
outputs at the same address.
Energized
(ON)
ON
Rung conditions are
FALSE but output
instruction isTRUE.
Programming error. Two
outputs at the same address.
Testing Inputs: If input hardware is suspected as being the source of a
problem, follow the procedures given below to isolate the problem:
1. Using the programmer, place the controller in the TEST - Continuous
Scan mode (mode 5).
2. The input status indicator located on the processor/expansion unit,
illuminates when the input circuit is receiving power; that is, when
the input device is ON. You should compare the actual ON/OFF
status of the suspect input device with its corresponding input status
indicator. To do this, manually turn the input device ON and OFF
and observe the status indicator.
Procedure continues on next page.
22 22-14
Chapter Maintenance and Troubleshooting
I/O Hardware Step 2, Testing Inputs, (continued):
(continued)
WARNING: Do not reach into a machine to actuate a switch by
hand. Unexpected machine motion could cause injury. Stand clear
of the machine and use a wooden stick to operate the switch.
If the input status indicator does not illuminate when the input device
is ON, check the following:
User power to the input device.
Wiring between input device and user power.
The input device.
CAUTION: Remove system power before checking electrical
connections or input devices.
If the input status indicator illuminates, go to step 3.
3. Using the programmer, place the controller in the Run or Test mode
(mode 3, 4 or 5). Compare the programmers ON status indicator with
the actual ON/OFF status of the suspect input device.
If the programmer does not show the correct status indication for the
suspect condition instruction, the input circuitry may not be
supplying the required logic level voltage. In this case, reconnect the
input device to a spare input circuit. If this does not solve the
problem, contact your A-B representative for repair or replacement of
the processor or expansion unit.
A guide for troubleshooting input devices is shown in Figure 22.6.
Figure 22.6
0-=JT^- Closed (ON) ON TRUE @ FALSE None. Correct status indication.
0^0 Open (OFF) * OFF FALSE TRUE None. Correct status indication.
Closed (ON) ON FALSE TRUE M 1. Processor/expansion unit input
circuitry fault.
2. Processor/programmer
communication fault.
Closed (ON) OFF FALSE TRUE ^ 1. Wiring/power to processor/expansion
unit input circuitry f au It.
2. Processor/expansion unit input
; circuitry fault. / .'V
0^0 Open (OFF) OFF TRUE FALSE 1, Programming error. T
2. Processor/programmer
com m dpication fault.
Open (OFF) ON TRUE H FALSE Q J Short circuit ininputdviceof wiring.
Chapter
Pocket Programmer
Diagnostic Test -
Programmer, Mode 9
Communication
Problems (Error
Codes 10 thru 25)
22
Maintenance and Troubleshooting
22-15
The programmer can be used to program, edit, monitor and troubleshoot
the controller.
If no display appears when the programmer is initially energized, check
the following:
DC POWER indicator on the processor unit: If the LED is OFF, power
is not available for the programmer.
Interconnect cable: Check connections at programmer and processor
unit for proper fit.
If everything appears to be correct, replace the interconnect cable. If
this does not solve the problem, contact your A-B representative for
repair or replacement of the pocket programmer.
Error Code 55: If a programmer hardware malfunction is detected,
error code 55 will be displayed by the programmer. If this happens,
contact your A-B representative for repair or replacement of the
programmer.
When mode 9 is selected, the programmer automatically runs through a
series of diagnostic tests including:
1. Firmware revision number (displayed once at start of test).
2. LED indicators: Each LED is individually illuminated.
3. Digital display: Each segment of the digital display is individually
illuminated.
4. LED indicators and digital display combined: All indicators and LED
display segments illuminate.
In addition, the keyboard can be tested to verify that it is working
correctly. When a key is pressed, a unique numeric value is displayed on
the programmer.
You exit the diagnostic mode by pressing CANCEL CMD or by toggling
the ON/OFF switch on the programmer.
Error codes 10 through 25 will be displayed if communication problems
are detected between the programmer and the processor unit. Follow
the procedures given below to locate the problem:
1. Check the interconnect cable to insure it is securely connected at both
the processor and programmer.
2. Recycle power to the programmer.
3. Recycle power to the processor unit.
If the error code still appears, contact your A-B representative for repair
or replacement of the processor/expansion unit and/or pocket
programmer.
22-16
Chapter Maintenance and Troubleshooting
Expansion Unit Problem In the Run and Test modes, the processor unit will continually monitor
(Error Code 26) the expansion units that are connected. If a problem is detected with
any of the expansion units, the processor unit will shut down, all outputs
will be turned OFF, and the CPU FAULT LED indicator will illuminate.
Error code 26 will be displayed by the pocket programmer. If the above
conditions exist, your controller should be checked for the following fault
conditions.
1. Check program addressing and the number of expansion units
connected. If you have addressed an expansion unit that is not
connected, this error condition will occur.
2. Check the expansion unit interconnect cable for damage. Make sure
that all expansion units are properly connected.
3. Check expansion unit power connections and hardware. Make sure
that the DC power LED is lit on each expansion unit connected.
If items 1,2, and 3 above appear to be O.K., and the CPU Fault still
exists, the expansion unit may need to be replaced. Contact your local
Allen-Bradley representative for repair or replacement.
EEPROM Module If error code 51 is displayed by the programmer when programming the
Problem (Error EEPROM module, a malfunction has occurred in either the processor
Codes 51 and 52)
unit or EEPR
OM module. If this happens, try a different EEPROM
module. If the problem persists after replacing the EEPROM module,
contact your A-B representative for repair or replacement of the
processor unit.
Error code 52 appears when the program in the processor units RAM
does not match the program stored in the EEPROM module. The error
code is a cautionary reminder that changes have been made to the
program and the RAM and EEPROM no longer match. You can correct
this error in two ways:
1. Select mode 6, Store Program in EEPROM, and transfer the new
program into the EEPROM. The previous contents on the EEPROM
module will be deleted.
2. Press ENTER a second time to override the error code.
Note: Error code 52 will not appear if on-line data changes are made
while the EEPROM module is installed.
a
Index
Subject Page
A
Accumulated value (AC) ...................................... 6-1,7-1,10-1
Address block ..................................................................... 3-4
Addresses ........................................................................... 3-1
Auto baud recognition ................................................... 18-14
Auto/Manual switch instruction ..................................... 14-1
B
Battery replacement ...................................................... 22-10
Battery status instruction ................................................ 14-7
Bit addresses ....................................................... 3-3,3-5,10-1
Branch close instruction .................................................... 5-4
Branch open instruction ..................................................... 5-4
Breakpoint instruction ..................................................... 14-5
C
Cascading shift registers .................................................. 13-4
Cascading SQI instructions ............................................... 11-3
Cascading SQO instructions ............................................. 11-1
Changing and monitoring techniques .............................. 16-4
Changing the PR value ..................................................... 16-4
Changing the RAC value ................................................... 16-4
Circulating shift register ................................................... 13-5
Clear memory mode .......................................................... 4-3
Componentspacing .......................................................... 19-2
Condition instructions ........................................................ 3-6
Connection cables............................................................. 20-4
Counter keystroke example ............................................... 7-5
Counter overflow/underflow bit ....................................... 7-2
Counter status bit .............................................................. 7-2
Counting beyond 9999 ..................................................... 7-7
CPU fault detection .......................................................... 22-7
Cursor.................................................................................. 4-2
Cursor control .................................................................. 15-2
Cycle completion bit ................................................ 10-2,12-2
D
Diagnostic test-programmer mode ......................... 4-3,22-15
Display symbols .................................................................. 4-9
Down counter (CTD) instruction ....................................... 7-1
E
Editing EEPROM programs .............................................. 17-5
EEPROM auto-load procedure ......................................... 17-4
EEPROM memory module ...................................... 2-11,17-1
EEPROM program identification ..................................... 17-1
1-2
Index
Subject Page
E (continued)
EEPROM programmable auto-load ................................. 17-4
Electrical continuity ......................................................... 3-1
Enter/change access code mode ....................................... 4-3
Entering a simple program ................................................ 4-8
Equivalent user programs .................................................. 5-3
Error codes ................... 4-10, 22-7, 22-8, 22-9, 22-15, 22-16
Event-driven sequencer................................................... 10-1
Event-driven shift register ............................................... 13-2
Examine OFF instruction ........................................... 3-7, 5-2
Examine ON instruction ............................................ 3-7, 5-2
Excessive noise ................................................................ 19-8
External I/O addresses ....................................................... 3-4
External I/O devices ........................................................... 3-8
F
FALSE instruction ............................................................... 3-7
FALSE-TRUE transition .............................................. 7-1,10-1
Fine time base instructions ............................... ... 8-1,8-2
Force function ................................................................. 16-1
Forcing an input address ................................................. 16-1
Forcing an output address ............................................... 16-2
Forcing sequencer I/O bit addresses ............................... 16-2
G
Grounding ........................................................................ 19-3
H
Hard-wired circuit............................................................... 5-2
Hard-wired relay logic system ........................................... 1-1
High speed input (HSI) module ............................... 2-5,12-1
Hold-in rung ....................................................................... 5-7
HSI application examples ...................................... 12-6,12-7
HSI counter instruction ........................................... 12-1,12-2
HSI maximum pulse rate ................................................. 12-2
HSI normal reset .............................................................. 12-3
HSI single shot reset ........................................................ 12-3
I
I/O address block............................................................... 3-4
I/O addresses ..................................................................... 3-4
I/O scan .............................................................................. 3-9
Initializing a latch instruction ........................................... 14-4
Initializing an up counter ................................................. 14-4
Input-satisfied status bit .................................................. 10-2
Insert and remove functions ........................................... 15-6
Installation procedure ..................................................... 20-1
index
1-3
Subject Page
I (continued)
Installing the EEPROM ..................................................... 17-2
Instruction classifications .................................................. 3-6
Instruction execution times .............................. 18-13,18-14
Instruction word usage ........................................ 18-13,18-14
Instructions ...................................................................... 3-1
Internal addresses ............................................................. 3-3
Isolation transformer ....................................................... 19-6
L
Ladder diagram ................................................................. 3-1
Least significant bit ......................................................... 13-1
Loading the EEPROM into the processor RAM ............... 17-3
Logical continuity ... .................................................. 3-1,3-7
Long time base instructions ...................................... 8-1,8-2
M
Maintenance and troubleshooting.................................. 22-1
Master control relay ........................................................ 19-4
MCR instruction ................................................................. 9-1
MCR/ZCL instructions vs master control relay .................. 9-5
Mode selection .................................................................. 4-7
Modes of operation ........................................................... 4-3
Monitoring and changing an AC value ............................. 16-4
Most significant bit .......................................................... 13-1
N
Nested branch ................................................................... 5-5
Nesting ZCL zones......... .................................................... 9-4
Non-retentive latch ......................................................... 14-2
Non-retentive timers ....................................................... 14-3
Normally closed (N.C.) contacts ........................................ 5-2
Normally open (N.O.) contacts........................................... 5-2
O
OFF status bit ..................................................................... 3-7
On-delay timer ................................................................... 6-1
On-line data control ........................................................ 16-1
ON status bit ...................................................................... 3-7
Operating times ............................................................... 3-10
Output contact protection ............................................... 19-9
Output energize instruction ..................................... 3-7, 5-2
Output instructions ............................................................ 3-6
Output latch instruction .................................................... 5-6
Output unlatch instruction ................................................ 5-6
Index
Subject Page
P
Password ........................................................................... 4-7
PC software interface converter ..................................... 2-12
Pocket programmer .......................................................... 4-1
Powersupply fuse replacement ....................................... 22-5
Preset (PR) value ...................................... 6-1, 7-1, 10-1, 10-9
Processor memory ............................................................ 3-1
Processor memory data table ........................................... 3-2
Processor operating cycle ................................................. 3-9
Processor unit . ......................................................... 2-2, 2-6
Program editing .............................................................. 15-1
Program editing techniques........................................... 15-10
Program initialization instruction .................................... 14-2
Program mode ................................................................... 4-3
Program scan ..................................................................... 3-9
Programmable EEPROM auto-load ................................. 14-7
Programmer display .......................................................... 4-2
Programmer keyboard ...................................................... 4-1
Programming sequencer instructions ........................... 10-12
R
Read mode ........................................................................ 4-3
Relay-type instructions ..................................................... 5-1
Reset accumulated value (RAC) .................... 6-1,7-1,7-2,10-2
Reset (RST) instruction .................................... 6-2, 7-2,10-2
Retentive instructions ....................................................... 5-6
Retentive timer off-delay (RTF) ......................................... 6-4
Retentive timer on-delay (RTO) ......................................... 6-4
Reversing sequencer step operation ............................... 11-4
RTF status bit ..................................................................... 6-2
RTF timer .......................................................................... 6-1
RTO status bit .................................................................... 6-2
RTO timer .......................................................................... 6-1
Run mode .......................................................................... 4-3
Rung numbers .......................................................... 4-2,4-8
S
Save mode ......................................................................... 4-3
Scan time ......................................................................... 12-4
Scan time measurement .................................................... 8-5
Search function ................................................................ 15-4
Sequencer data form ....................................................... 10-6
Sequencer group numbers .............................................. 10-7
Sequencer hex data ......................................................... 10-6
Sequencer hex mask......................................................... 10-6
Sequencer input driving a sequencer output................. 11-6
Sequencer input ladderdiagram ................................... 10-11
Sequencer instructions ................................................... 10-1
Index
1-5
Subject Page
5 (continued)
Sequencer jump operation ............................................ 11-10
Sequencer mask data ....................................................... 10-9
Sequencer output ladder diagram ................................. 10-10
Sequencer program codes ............................................... 10-7
Sequencer step data ........................................................ 10-6
Shift left register .............................................................. 13-1
Shift register instruction .................................................. 13-1
Shift right register ............................................................ 13-1
SLC 100 analog input expansion unit................................ 2-10
SLC 100 basic expansion unit ............................................. 2-8
SLC 100 relay output expansion unit ................................. 2-9
SLC 150 expansion unit ...................................................... 2-4
SLC 150 terminal block removal ...................................... 22-3
Spare parts ....................................................................... 22-3
Special internal instructions ............................................ 14-1
Special sequencer group numbers .................................. 11-7
Specifications.................................................................... 18-1
SQI basic operation .......................................................... 10-5
SQI monitoring an SQO .................................................... 11-7
SQI sequencer .................................................................... 9-1
SQO basic operation ........................................................ 10-4
SQO sequencer .................................................................. 9-1
Start-up ............................................................................ 21-1
Status bit ............................................................................ 3-2
Step completion bit ......................................................... 10-2
Storing a program in the memory module ...................... 17-3
T
TCAT power-up instruction .............................................. 14-5
Test continuous scan mode ............................................... 4-3
Test single scan mode ........................................................ 4-3
Time-driven sequencer .................................................... 10-1
Time-driven shift register ................................................. 13-2
Timer counter access terminal (TCAT) ............................. 2-12
Timer instructions .............................................................. 6-1
Timer keystroke example ................................................... 6-7
Timer operation ................................................................. 6-3
Timer overflow bit ............................................................. 6-2
Timing beyond 999.9 seconds ............................................ 6-6
Triac zero-cross turn-on instruction ................................ 14-8
Troubleshooting I/O hardware ...................................... 22-12
Troubleshooting safety considerations ........................... 22-1
TRUE-FALSE status indicator ............................................ 16-2
TRUE instruction ................................................................ 3-7
1-6
Index
Subject Page
u
Unconditional output energize.......................................... 5-4
Up counter (CTU) instruction ................................... 7-1,7-4
Up counter operation ........................................................ 7-3
Up-down counter .............................................................. 7-6
User program .................................................................... 3-1
Using an access code ......................................................... 4-7
Using shift register outputs ............................................. 13-6
W
Wiring connections ...................................... 20-6 thru 20-17
Wiring layout.................................................................... 19-3
Word .................................................................................. 3-1
Z
ZCL instruction ................................................................... 9-1
ZCL zone .................................................................... 9-4,13-1
ZCL zones using the same outputs .................................... 9-3
SEQUENCER INSTRUCTION DATA FORM
'i
/
SEQUENCER n (SQI)
CLASSIFICATION:
a
-(SQO)-
ADDRESS:
TIME DRIVEN
EVENT DRIVEN
GROUP NUMBER:
BIT ADDRESS DATA
PROGRAM
CODE
PRESET
VALUES
Bit Addresses->
Mask Data -
E A
Data
B
Data
A
Step Data 0
i 1
1 1
1
1 1
1 1
1 1.... -................. _i
2
1 1
1 1
3
1 1
1 1
4
1 [
1 1
1
5
1 1
1 1
6
i i
! 1
7
1 '1 -------------
1 1
1 1
8
1 1
1 1
.........- 1 1
9
1 1
1 1
10
1 "t
1 t
1 .1
11
1 1
1 1
1 1
12
1 1
1 1
13
1 [
1 t
1 1
14
1 1
1 1
i *
15
1 1
1 1
16
1 i
1 )
17
1 E
1 1
1 ______ i
18
1 1
; 1
19
1 1
1 1
20
* 1
) 1
1 1
ALLEN-BRADLEY
WIBiyA ROCKWELL INTERNATIONAL COMPANY
Industrial Control Group
Milwaukee, Wisconsin 53204
Publication 1745*800 - November, 1987
Supersedes Publication 1745-800 Dated September, 1985 40065-236-01(0
fl ALLENBRABLEY
'TIIHU'r A ROCKWELL INTERNATIONAL COMPANY
Self-Teach
Manual
Bulletin 1745
SLC
Programmable Controllers
40065-237-01 (D)
Publication 1745-800A - March, 1988
Supersedes Publication 1745-800A Dated November, 1987
Tabe
of Contents
Unit Title Page
1 How to Use This Manual
A Companion to the User's Manual................................... 1-1
A 1-2-3 Procedure ............................................................. 1-1
2 Equipment Overview
Key Terms and Concepts ................................................. 2-1
Question Group 2A ......................................................... 2-1
3 Programming Basics
Key Terms and Concepts ........... ..................................... 3-1
Matching Exercise ........................................................... 3-2
Question Group 3A ............................................................ 3-3
Question Group 3B ............................................................ 3-4
Question Group 3C ............................................................ 3-5
Question Group 3D ............................................................ 3-6
Question Group 3E ............................................................. 3-7
4 Using the Pocket Programmer
Key Terms and Concepts ................................................. 4-1
Question Group 4A .................................................... 4-2
Examine the Programmer .... ............................................. 4-3
Question Group 4B . ..................................................... 4-3
Question Group 4C ...................................................... 4-5
Question Group 4D ...................................................... 4-6
5 Relay- Type Instructions
Key Terms and Concepts ................................................. 5-1
Question Group 5A ............................................................ 5-1
Question Group 5B ............................................................ 5-2
Question Group 5C ............................................................ 5-2
Question Group 5D ........................................................... 5-3
2
Table of Contents
Unit Title Page
6 Timer Instructions
Key Terms and Concepts ................................................... 6-1
Question Group 6A ............................................................ 6-1
Question Group 6B ............................................................ 6-2
Question Group 6C............................................................. 6-4
Question Group 6D ............................................................ 6-6
7 Counter Instructions
Key Terms and Concepts ................................................ 7-1
Question Group 7A ............................................................ 7-1
Question Group 7B ............................................................ 7-3
Question Group 7C ............................................................ 7-4
Question Group 7D ............................................................ 7-5
8 Timers with Long or Fine Time Base
Key Terms and Concepts ................................................ 8-1
Question Group 8A ........................... ............................ 8-1
Question Group 8B ......................................................... 8-2
9 MCR and ZCL Instructions
Key Terms and Concepts ................................................ 9-1
Question Group 9A ............................................................ 9-1
Question Group 9B ............................................................ 9-2
Question Group 9C............................................................. 9-3
Question Group 9D ............................................................ 9-4
10 Sequencer Instructions
Key Terms and Concepts ................................................ 10-1
Question Group 10A ....................................................... 10-1
Question Group 10B ........................................................ 10-3
Question Group 10C......................................................... 10-4
Question Group 10D ........................................................ 10-6
Question Group 10E ........................................................ 10-6
Table of Contents
3
Unit Title Page
11 Special Sequencer Instruction Techniques
Key Terms and Concepts ................................................ 11-1
Question Group 11A ....................................................... 11-1
Question Group 11B......................................................... 11-2
Question Group 11C......................................................... 11-4
Question Group 11D ........................................................ 11-5
Question Group 11E ........................................................ 11-5
12 High Speed Input Programming
Key Terms and Concepts ................................................. 12-1
Question Group 12A ....................................................... 12-1
Question Group 12B......................................................... 12-2
Question Group 12C......................................................... 12-3
13 Shift Register Instruction
Key Terms and Concepts ................................................. 13-1
Question Group 13A ....................................................... 13-1
Question Group 13B......................................................... 13-2
Question Group 13C......................................................... 13-3
14 Special Internal Instructions
Key Terms and Concepts ................................................. 14-1
Question Group 14A ........................................................ 14-1
Question Group 14B......................................................... 14-2
Question Group 14C......................................................... 14-3
15 Program Editing
Key Terms and Concepts ................................................. 15-1
Question Group 15A ........................................................ 15-1
Question Group 15B......................................................... 15-3
4
Table of Contents
Unit Title Page
16 On-Line Data Control
Key Terms and Concepts ................................................. 16-1
Question Group 16A ........................................................ 16-1
Exercises .......................................................................... 16-2
17 Using the EEPROM Memory Module
Key Terms and Concepts .............................................. 17-1
Question Group 17A ..................................................... 17-1
18 Answers
Unit 2 ............................................................................... 18-1
Unit 3 ............................................................................... 18-1
Unit 4 ............................................................................... 18-5
Units ............................................................................. 18-6
Unit 6 ............................................................................... 18-7
Unit 7 ............................................................................... 18-9
Unit 8 ............................................................................. 18-10
Unit 9 ............................................................................. 18-11
Unit 10............................................................................ 18-12
Unit 11 ........................................................................... 18-14
Unit 12 ........................................................................... 18-15
Unit 13........................................................................... 18-17
Unit 14............................................................................ 18-17
Unit 15............................................................................ 18-18
Unit 16............................................................................ 18-22
Unit 17............................................................................ 18-23
Unit
A Companion to the
User's Manual
A 1-2-3 Procedure
How to Use
This Manual
The Self-Teach Manual is designed for use with the SLC Programmable
Controller Users Manual, Publication 1745-800.
This manual consists of Question/Exercise Units corresponding to
Chapters 2 thru 17 of the Users Manual. Question/Exercise Units
include questions, a summary of key terms and concepts, and in some
cases additional programming details, examples, and exercises.
We suggest you use the following procedure. You will need a simple
controller set-up or a factory demonstrator to practice programming.
1. Read Chapter 2 of the U sers Manual twice, then refer to Question-
Exercise Unit 2 of this manual.
2. Read the "Key Terms and Concepts in the Question-Exercise unit.
Make sure you understand them. Review the referenced Users
Manual pages if necessary.
3. Answer the questions, then check your answers with those in Unit
18. If you have answered any questions incorrectly, go back and
review the text material associated with these questions.
Repeat steps 1,2, and 3 for succeeding chapters (read the chapters in
numerical sequence).
Set your own pace.
Q-E Unit Equipment
Overview
Key Terms and
Concepts
You should become thoroughly familiar with the following terms and
concepts. Re-read the referenced pages if necessary.
SLC150 Processor Unit 2-2
Pocket Programmer 2-11
High Speed Input Module 2-5
SLC 100 Processor Unit 2-6
Expansion Unit 2-4,2-8,2-9,2-10
EEPROM Memory Module 2-11
PC Software Interface Converter 2-12
Timer Counter Access Terminal 2-12
Question Group 2A 1.
Answers in Unit 18
2.
3.
4.
5.
6.
7.
8.
9.
The pocket programmer must remain connected to an SLC processor
unit in order to run your program. True or false?
The EEPROM memory module must be inserted in order to operate
an SLC controller. True or false?
An SLC processor unit user program is retained when processor
power is removed. True or false?
Which of the following statements are true?
a. The pocket programmer plugs directly into the processor unit.
b. The pocket programmer can communicate directly with the
processor unit with no cable connections at distances up to 6 feet.
c. The pocket programmer must be wired to the processor unit by
means of a 3-wire power cord.
d. The 6 ft. interconnect cable that is connected to the pocket
programmer plugs in to the processor unit when needed.
The EEPROM memory module is used to:
a. Store the contents of the processor RAM.
b. Load the contents of EEPROM memory to the processor RAM.
c. Provide back-up storage for your program.
d. All of the above.
e. None of the above.
The SLC 150 uses its back panel as a heat sink. True or false?
The incoming power terminals on SLC processor units have self
lifting pressure plates for easy wire insertion and secure
connections. True or false?
There are 10 input circuits on the SLC 100, and 20 inputs on the SLC
150 processor unit. True or false?
There are 6 output circuits on the SLC 150 processor unit. True or
false?
10. SLC 100 and SLC 150 processor and expansion units can be mixed
and matched to suit your application. True or false?
11. Each I/O circuit on the processor and expansion unit is associated
with an external I/O address. True or false?
Q-E Unit ^PMEquipment Overview
Question Group 2A
(continued)
Answers in Unit 18
12. A snap-on cover protects the EE PROM port when the E EPROM
module is not in use. True or false?
13. There are 21 LED diagnostic indicators on the processor unit that
aid in monitoring and troubleshooting the SLC 100 Programmable
Controller. True or false?
14. I/O terminal circuitry interfaces the logic level voltage of the
processor with the voltage levels of external input and output
devices. True or false?
15. Input terminal circuitry senses whether external input devices are
ON or OFF and relays this information to the processor unit. True
or false?
16. Output terminal circuitry controls the ON/OFF status of external
output devices, based on commands received from the processor unit.
True or false?
17. SLC 100 processor units have 10 LED status indicators that
correspond to the 10 input circuits. An LED is lit when the
corresponding input circuit is energized. True or false?
18. SLC 150 processor units have 6 LED status indicators that
correspond to the 6 output circuits. An LED is lit when the
corresponding output instruction is TRUE. True or false?
19. SLC 100 basic expansion units have 10 LED status indicators that
correspond to the 10 input circuits and cannot be used with the SLC
150 controllers. True or false?
20. SLC 100 basic expansion units have 6 LED status indicators that
correspond to the 6 output circuits. An LED is lit when the
corresponding output instruction is TRUE. True or false?
21. SLC I/O wiring terminals have self-lifting pressure plates for easy
wire insertion and secure connections. True or false?
22. SLC 100 input terminal covers are color-coded for easy
identification. True or false?
23. The pocket programmer is your means of communicating with the
processor unit. True or false?
24. The EEPROM memory module is an optional device that can be used
to store the contents of the processor RAM. True or false?
25. You can load the contents of the EEPROM memory module to the
processor RAM memory. True or false?
26. The EEPROM module has a write-on area for use in identifying its
contents. True or false?
27. The EEPROM memory module requires a special mounting plate
that will hold up to four memory modules and a reserve battery.
True or false?
28. The relay output expansion unit has no inputs. True or false?
29. There are 12 hard contact output circuits in the relay output
expansion unit. True or false?
Q-E Unit
Question Group 2A
(continued)
Answers in Unit 18
Equipment Overview
2-3
30. SLC personal computer software can also be used for programming
SLC processor units. True or false?
31. Expansion units are available with AC, DC, triac and transistor
outputs. True or false?
32. High speed input modules can be used only with the SLC 150
processor. True or false?
33. Relay expansion units have wiring terminals for 12 output circuits
and can be used with either the SLC 100 or SLC 150. True or false?
34. The TCAT is used to access programmed timer data only. True or
false?
35. The analog input expansion unit allows connection of up to 8 analog
input signals. True or false?
Q-E Unit Programming
Basics
Key Terms and You should become thoroughly familiar with the following terms and
Concepts concepts. Re-read the referenced pages if necessary.
Relay Ladder Rung 3-1 Output Instructions 3-6
PC Ladder Rung 3-1 Instruction Set 3-6
Processor Memory 3-2 Examine ON 3-7
User Program 3-2 Examine OFF 3-7
Instructions 3-1 Electrical Continuity 3-7
Word 3-1 Logical Continuity 3-7
Data Table 3-2 Output Energize 3-7
Addresses 3-2 TRUE 3-7
Status Bits 3-2 FALSE 3-7
ON (logic 1), OFF (logic 0) States 3-2 External I/O Devices 3-8
TRUE/FALSE Status (Instructions) 3-2 Operating Cycle 3-9
External I/O Addresses 3-4 I/O Scan 3-9
Internal Addresses 3-3 Program Scan 3-9
Condition Instructions 3-6
SYMBOLOGY
HI- -( h
3-2
Q-E Unit
Matching Exercise
Answers in Unit 18
Programming Basics
Each of the following terms can replace one of the callout letters in the
figures below. Fill in the correct letter for each term.
1. Processor Memory _
2. Address_______
3. User Program___
4. Instruction______
5. Data Table _____
6. Relay Ladder Rung _
7. Status Bit_______
8. Word______
9. PC Ladder Rung_
T1 CR4 CR3
Q-EUnit
Question Group 3A
Answers in Unit 18
Programming Basics
3-3
1. Instructions are either:
a) TRUE or FALSE. b) ON or OFF.
2. Status bits are either:
a) TRUE or FALSE. b) ON or OFF.
3. Status bits tell us exactly where an instruction is located in the user
program. True or false?
4. All SLC 150 programs are compatible with the SLC 100. True or
false?
5. The address number of an instruction tells us:
a) Whether the instruction is internal or external.
b) Whether the instruction represents an input or an output device.
c) a and b
6. An address number of 016 indicates that the address is associated
with an internal instruction. True or false?
7. How many external addresses are available for programming?
a) 32 b) 112 c) 885
8. The memory storage unit for instructions is called:
a) the BYTE, b) the word. c) the bit.
9. The data table portion of memory stores the list of instructions you
enter. True or false?
10. The instruction address links the instruction to a particular status
bit in the data table portion of the memory. True or false?
11. Relay-type instructions are used internally and externally. True or
false?
12. Address 868 has a function called_____________ instruction.
13. When developing an SLC program, you may use as many address
blocks as you like, so long as you do not exceed 112 addresses. True
or false?
14. When using the HSI, the operating cycle is interrupted to allow
processor to count high speed input signals. True or false?
15. Triac zero cross turn on can be programmed in the SLC 150 by using
address 864 in the user program. True or False?
3-4
Q-E Unit Programming Basics
Question Group 3B 1. Instructions are classified into two groups, input instructions and
Answers in Unit 18 output instructions. True or false?
2. The branching instructions are classified in the output instruction
group. True or false?
3. Examine ON and Examine OFF instructions are classified as
instructions. Choose one of the following.
a. input, b. output, c. condition, d. unconditional.
4. The Examine ON instruction means "examine the status bit for an
ON condition. True or false?
5. With the Output Energize instruction, the status bit of the
addressed Output Energize instruction is set ON when the
conditional instructions in that rung are TRUE. If there are no
conditional instructions, the status bit is always ON. True or false?
6. Logical continuity exists in a rung if:
a. The Examine ON instructions in the rung are TRUE.
b. The Examine OFF instructions in the rung are FALSE.
c. A continuous path of TRUE conditional instructions exists.
d. Only one conditional instruction in the rung is FALSE.
7. If an Examine ON instruction is used to represent a limit switch
contact, a closed condition for the limit switch makes this
instruction logically TRUE. True or false?
8. The controller operating cycle is divided into two parts, the I/O scan
and the program scan. True or false?
9. If an external input device changes state during the program scan,
which of the following is true?
a. The change of state will be recognized immediately during that
program scan.
b. The change of state will be recognized during the next I/O scan.
c. The user program scan will be reset to 0.
d. The program scan will start over again.
10. For a typical 500 word program, the SLC 100 repeats its processor
operating cycle 67 times each second. How many times does the SLC
150 controller repeat its cycle in one second:
a. 200 b. 300 c. 400 d. 500 e. None of these.
11. If you are using a high speed input module, the SLC 150 operating
cycle is interrupted to allow the processor unit to count high speed
input signals and immediately set processor unit outputs. True or
false?
12. The SLC 150 I/O scan is 300 microseconds plus 250 for each
expansion unit address block used. How long is the I/O scan for the
SLC100?
a. 1.5 msec plus .27 ms for each expansion unit.
b. 1.5 sec plus .27 sec for each expansion unit.
c. 6090 microseconds plus 500 microseconds for each expansion
unit.
d. none of these.
13. The typical SLC 100 operating cycle is 15 msec, whereas the typical
SLC 150 operating cycle is only 2.5 msec. True or false?
Q-EUnit
Question Group 3C
Answers in Unit 18
Programming Basics
3-5
In the figure of the SLC 100 processor unit I/O terminals below, a limit
switch is wired to an input terminal and a starter coil is wired to an
output terminal. Programmed instructions associated with these
devices are shown in the ladder rung. Answer the following questions.
[com I
Supply Voltage
1 2 * 3 4 [com] 6 I 7 I 8 I 9 I 10
, External input devices are,
wird to processor uftit
terminals 1 to 10, corres
ponding to instruction
addressesOOi to 010.
rlh Hh Hh Hh rih HH ' output contacts {internal).
1 ,, l..,,,.!,, I , i . I | I . 1 . I , I ,, 1,1 Open/dosed status is
controlled by processor. 1111 n 112 12 13 141141 15 I S 16 116
: SupptyVoltage
\
External output devices are wired!
to processor unit terminals 11 to - *
r
16, correspondingto instruction
addresses 011 to 016.
m 733
-Ib^Nc
Associated
with LSI
< y

Associated
with M
1. What is the 3-digit address number of the instruction associated
with N.O. limit switch LSI?
2. Which of the two classifications does this instruction belong to?
3. What is the name of the instruction?
4. Assume that the controller is energized and operating (Run mode),
and the limit switch is in the closed position. Will this instruction be
TRUE or FALSE?
5. Will the corresponding status bit be ON or OFF?
6. What is the 3-digit address number of the instruction associated
with coil M?
7. Which of the two classifications does this instruction belong to?
8. What is the name of the instruction?
9. What rung conditions are necessary to make this instruction TRUE?
10. When this instruction is TRUE, will the associated status bit be ON
or OFF?
11. The instruction at address 733 is associated with an external I/O
device True or false?
12. What is the name of the instruction?
3-6
Q-E Unit Programming Basks
Question Group 3C 1 3 . When this instruction is TRUE, will the corresponding status bit be
(continued) ON or OFF?
Answers in Unit 18 14. When the rung is TRUE, the status bits associated with each of the
instructions will be ON. True or false?
15. If a N.C. limit switch were substituted for LSI, the instruction
representing it would have to be changed to an Examine OFF
instruction in order to energize coil M for the closed position of the
switch. True or false?
16. Suppose you had one expansion unit connected to your processor
unit. If the limit switch and coil were connected to corresponding
terminals on the expansion unit, what addresses would you assign to
these instructions?
Question Group 3D
Answers in Unit 18
In the figure below, a simple programmed rung is shown. Answer the
following questions.
1. In what part of the operating cycle does the status bit of instruction
001 change from OFF to ON or vice versa?
2. In what part of the operating cycle does the status bit of instruction
Oil change from OFF to ON or vice versa?
3. The output contact will go ON or OFF during the program scan.
True or false?
4. The time period beginning when the input terminal representing
instruction 001 goes ON and ending when the output terminal
associated with instruction Oil goes ON is
a) Fixed, at approximately 25 milliseconds.
b) Variable, but never longer than one operating cycle.
c) Variable, depending on the location of this rung in the program.
d) Variable, depending on what point in the operating cycle the
processor happens to be at when the input terminal goes ON.
e) Variable, depending on program length (how many instructions
in the program) and content (the various types of instructions in
the program).
Which of the above statements are true?
Q-EUnit Programming Basics
3-7
Question Group 3E Assign address and determine the number of address blocks required for
Answers in Unit 18 the SLC system below.
SLC 150
Processor
SLC 100 Basic
Expansion
Relay
Output
..'r*,
Unit : ; Expansion
' ;
: - '
Unit
Address Blocks
Used:
Analog
Input
Expansion
Unit
Q-E Unit Using the Pocket
Programmer
Key Terms and
Concepts
You should become thoroughly familiar with the following terms and
concepts. Re-read the referenced pages if necessary.
Pocket Programmer 4-1
Keyboard 4-1
LED Indicators 4-2
Address/Data Area 4-2
Display 4-2
Rung/Error/Mode Area 4-2
Modes of Operation 4-3
Access Code (Password) 4-7
Mode Selection 4-7
Display Symbols 4-9
Error Codes 4-10, 4- 11
Internal Processor Errors 4-10
Programming Errors 4-10, 4- 11
SYMBOLOGY
nT -<>- T JT
B m El
-<RTO>- -(RTF)- <CTUb -{CTD>- -(RST)-
m m m
-<L>- -(U)- -(SQI) -(SQO) <zc L)
m m m M
-{IV1CR}- PRT PROG ON FORCE
I 1
ADDRESS
RUNG/ERR
h
FTFTr
*4 U
FTr
4
lLo O'-.-oL-l o
*L
-ol
S
V DATA____________________________ MODE J
FRC OFF
0
D
5
MODE
PRT
UNPRT
A
2
F
7
REMOVE
SEARCH
-<SQO>-
-{CTU}-
-(SQO-
-iCTDb
B
3
EVENT
8
INSERT
-<ZCL>-
-(MCR>-
NEXT
RUNG
ilh
T
-<U>-
T
-iRTfh
-(RTO)-
"-----------
SHIFT
CANCEL
CMD
-II-
----------- >
-(RST)-
-( v-
ENTER
4 2
0-E Unit Using the Pocket Programmer
Question Group 4A
Answers in Unit 18
1. The pocket programmer is only used to enter your program True or
false?
2. The pocket programmer has 30 keys, many with upper case
functions. True or false?
3. The pocket programmer has an ON/OFF switch located just below
the display. True or false?
4. The pocket programmer display consists of two separate areas. The
upper display consists of 20 square LEDs. An LED will be lit when
you press the corresponding key on the keyboard. The lower display
area consists of seven-segment LEDs which display various data and
messages True or false?
o. To select an upper case function on the keyboard, which key must be
pressed first
0
a RUNG. b. SEARCH c. SHIFT, d. MODE. e. NEXT.
6. The pocket programmer can be password-protected to prevent
unauthorized access to the user program. True or false?
7. What mode of operation must you enter to change or enter a
password?
a. Mode 2. b. Mode 4. c. Mode 6. d. Mode 8. e. Mode 10.
8. Error codes must be converted to binary code before they can he
interpreted. True or false
9
9. When any error code from 01 thru 08 appears on the display:
a. An internal processor error has occurred.
b. The processor CPU FAULT LED will light.
c. All outputs will be disabled.
d. All of the above.
e. None of the above.
10. The processor unit will function in only two modes, Programming
and Run. True or false
9
11. There is a table fixed to the back of the pocket programmer with
information on error codes, modes of operation and instruction
addressing. True or false?
12. If you enter mode 9 on the pocket programmer the display will read
ERROR 40. True or false?
13 If you enter mode 9, the pocket programmer will perform a
diagnostic test on itself. True or false?
14 In order to clear the processor RAM memory you must enter mode 1.
True or false?
15. Error codes 60 - 66 are user errors that indicate:
a. Invalid procedure (s)
b. Incorrect data
c. Incomplete data
d. All of the above
16. Error Code 27 is detected only by an SLC 150 Processor. True or
false?
Q-E Unit
Question Group 4 A
(continued)
Answers in Unit 18
Examine the
Programmer
Question Group 4B
Answers in Unit 18
Using the Pocket Programmer
4-3
17. The keyboard is used to encer your program information, and the
display shows you this information and data as you enter it.
True or false?
1. Examine the pocket programmer keyboard and press one of t he
keys. As you press down on the key you can feel the key give under
the pressure of your finger. As you let up on the key, it will return to
its original position. This tactile feedback feature helps make it
easy to program the SLC Programmable Controller. You can feel
the key and know that the information is entered.
2. Turn the pocket programmer over so that you can see the table that
is fixed to the back side. This table can be very useful whenever you
are using the pocket programmer. Mode numbers and descriptions,
acceptable addresses for programming various instructions, and
error code descriptions are featured on this table. Refer to this table
when you need information on any of these items.
3. Above the information table at the top of the programmer is the
interconnect cable. The cable should remain connected to the
programmer at all times. When you no longer need the programmer
to communicate with the processor, disconnect the cable at the
processor unit and leave the cable connected to the programmer.
1. SLC Programmable Controllers operate from a 5 VDC power source
and should not be connected to 120 VAC power. True or false?
2. The pocket programmer operates from a lithium power battery and
can communicate with the processor unit with no cable connection at
a distance of up to 6 ft. True or false?
3. When power is applied to the processor unit, the DC POWER LED
should light. True or false
9
4. When power is first applied to the pocket programmer, it will
automatically go thru a series of diagnostic checks. True or false?
5. The interconnect cable is equipped with spring latches that secure
the cable to the programmer and processor unit. True or false?
4-4
Q-E Unit Using the Pocket Programmer
Question Group 4B
(continued)
Answers in Unit 18
6. When connecting a three wire power cable to an SLC processor,
connect the black wire to the terminal marked CHASSIS GND.
True or false?
7. The interconnect cable should remain attached to the programmer
at all times. When not needed, disconnect the programmer at the
processor unit and leave the cable connected to the programmer.
True or false?
8. To avoid accidental memory loss, the pocket programmer will ask
you to verify that you want to clear memory when you enter mode 1
What prompting message does the display show you when you enter
mode 1?
9 When the processor memory has been cleared on the SLC 100, there
are 885 words of memory available for programming. True or false?
10. A typical rung has one or more condition instructions and end with a
single output instruction. True or false
9
11. If you enter the wrong address for an instruction, you can change it
by pressing the CANCEL CMI) key until the incorrect information
is deleted. The correct address can then be entered. True or false?
12. It is possible to have two output instructions in the same rung. True
or false
9
13. The output instruction completes the ladder rung. After entering
the output instruction and its address, pressing the ENTER key will
enter the rung in memory. True or false?
14. Ladder rungs are numbered as they are entered in memory. While
you are entering the rung, the display tells you what rung number
you are entering True or false?
15. The upper case functions are all color-coded blue for easy
identification. True or false
9
16. When you press an instruction key, the corresponding instruction
LED will be lit in the upper part of the display. In the lower display
area, three underlines (------ ) appear under the address line, which
are actually prompting you for an address for the instruction you
have just entered. True or false?
17. The instruction address is entered with the numeric keys that are
located in the 2 top rows on the keyboard. True or false?
18. Ifyou wanted to assign address 001 to an instruction, you need not
enter the leading zeros of the address. Pressing numeric key 1 is all
you must do to enter this address. True or false?
19. The SLC 150 can be programmed with the same pocket programmer
used to program the SLC 100. True or false?
Q-E Unit
Question Group 4C
Answers i n U n i t 1 8
Using the Pocket Programmer
4-5
Program the rungs below and answer the questions that follow. liefer to
the keystroke sequence in Figure 4.7 of the Users Manual if you need
help entering this sample program. Make sure that you have cleared
the processor memory before you begin to program these rungs.
Rung 1
Rung 2
00' 002 003 34 005 701
( >
001 002 003 004 005 702
IHHHHIk<>
Rung 3
006 007 901 902 903 703
4HHNHIII( >
1. After you have entered this program into an SLC 150 processor unit,
there are________ words of memory available.
a. 1182 b. 1200 c. 867 d. None of these.
2. It is possible to examine an input address more than once in your
program. True or false?
3. It is possible to examine an output address for an ON or OFF
condition. True or false?
4. Enter the Run mode and cursor to the Examine ON instruction at
address 003 in rung 1 using the NEXT and LAST keys. Is the ON
LED in the display lit?
5. Cursor right to the Examine OFF instruction at address 004 with
the NEXT key. Is the ON LED in the display lit?
6. If you have no external I/O devices connected, you cannot turn any
inputs ON or OFF. Without using the Force function, all Examine
ON instructions should be FALSE and Examine OFF instructions
should be TRUE. True or false?
7. Using the NEXT key, cursor thru this program until the display
reads
1182 End
Press the LAST key once and observe the display. Which square
LEDs on the display are lit?
8. Press the LAST key three times. Which square LEDs on the display
are lit?
9. Why is the ON LED lit
9
4 - 6
Q-E Unit Using the Pocket Programmer
Question Group 4D Matching exercise -Match the SLC 150 error codes with their
Answers in Unit 18 appropriate description.
Error Code
27-2 ZCL programming error
27-5 Zero cross turn on failure
27-1 HS1 module problem
Q-E Unit Relay-Type
Instructions
Key Terms and
Concepts
You should become thoroughly familiar with the following terms and
concepts. Re-read the referenced pages if necessary'.
Hard-Wired Circuit 5-2
Examine ON 5-2
Examine OFF 5-2
Output Energize 5-2
Branch Instructions 5-4
Nested Branch 5-5
Output Latch 5-6
Output Unlatch 5-6
SYMBOLOGY
HI-
1
-< >-
-U>-
T
-<u>-
T
Question Grouf 1. In a relay ladder rung, output devices are represented by relay coils
A vers ;n Urn! ' or pilot lights. In a PC ladder rung, these output devices are
represented by which instruction?
a. Examine ON.
b. Examine OFF.
c. Output Energize.
d. Branch Close.
2. Relay-type instructions are used for external I/O points only. True
or faise?
3. An Examine ON instruction examines a status bit for an ON
condition. The instruction is TRUE when the status bit is ON. True
or false?
4. Since the Examine ON instruction examines for an ON condition, it
can be used to represent a normally open or a normally closed set of
contacts if you want to know when your input device is ON. True or
false?
5. Since the Examine OFF instruction examines for an OFF condition,
it can be used to represent a normally open or a normally closed set
of contacts if you want to know when your device is OFF. True or
false?
6. It is possible to program a rung consisting only of an Output
Energize instruction. True or false?
5-2
Q-E Unit Relay-Type Instructions
Question Group 5A
(continued)
Answers in Unit 18
7. The instruction in question 6 will always be TRUE and the output
will always be energized when in the Run mode. True or false?
8. The unconditional output energize instruction is generally an
undesirable programming procedure. True or false?
9. If you have a normally open limit switch and you want a pilot light
to go ON when the limit switch is open, programming a rung using
an Output Energize instruction to represent the pilot light and an
Examine OFF instruction to represent the limit switch could
accomplish this. True or false?
10 A separate branch close instruction (T~ ) must be used for every-
rung of the parallel branch that you wish to close. True or false?
Question Group SB Study the rung below and answer the questions that follow.
Answers in Unit 18
Rung 1
001
in
002 CC3
________ IL_ -11________
ois
1. If the examine instruction at address 001 is TRUE, output 015 will
also be TRUE. True or false?
2. If the examine instruction at address 002 is TRUE, output 015 will
also be TRUE. True or false?
3. If the examine instructions at addresses 002 and 003 are TRUE,
output 015 will also be TRUE. True or false?
4. If the examine instructions at addresses 001 and 003 are TRUE,
output 015 will also be TRUE. True or false?
5. If the examine instructions at addresses 001 and 002 are TRUE,
output 015 will also be TRUE. True or false?
6 If the examine instructions at addresses 001, 002 and 003 are all
TRUE, the output at address 015 will be OFF (de-energized). True
or false?
Question Groups C l. Which of the rungs in the following figure use the proper branching
Answers in Unit 18 procedure for the Bulletin 1745 programming format? Enter the
correct rung on the pocket programmer. If you need help, the correct
key sequence for this problem is in the answer section.
Q-E Unit
Question Group 5C
(continued)
Question Group 50
Answers in Unit 18
Relay-Type Instructions
5-3
A C
B D
Study the rungs below and answer the questions that follow. Refer to
Page 5-4 if you need help.
Rung 1
Rung 2
001
II
015
II
V
L
002 004 015
_________ l
I I I I v
w
1. When input 001 is ON, output 015 is ON. True or false?
2. When input 001 makes a transition from TRUK to FALSE,output
015 remains ON True or false?
3. When input 002 is ON. output 015 will unlatch and turn OFF. True
or false?
4. When input 001 is ON output 015 is latched ON. Output 015 will
unlatch only when inputs 002 and 004 are ON. True or false?
5. If output 015 is latched ON and power is removed, it will return to
ON when power is restored. True or false?
6. If the Examine ON instructions at addresses 001,002 and 004 are all
TRUE, the output at address 015 will be OFF {de energized). True
or false?
Q- Unit
Key Terms and
Concepts
Question Group 6A
Answers in Unit 18
Timer
Instructions
You should become thoroughly familiar with the following terms and
concepts. Re-read the referenced pages if necessary.
Accumulated Value (AC) 6-1 Overflow Bit 6-2
Preset Value (PR) 6-1 Reset (RST) 6-2
Reset Value (RAC) 6-1 Timer Operation 6-3
Timing Range 6-1 Retentive Timer On-Delay (RTO) 6-4
Status Bit 6-2 Retentive Timer Off-Delay (RTF) 6-5
Timing Beyond 999.9 Seconds 6-6
SYMBOLOGY
-<RTF>-
-<RTO)-
-(RST)-
L*
1 The RTO and RTF instructions both require a reset instruction.
True or false?
2 Address assignments for timers must be from 901 thru 932. True or
false?
3 The timer instruction counts 0.01 second time intervals. True or
false?
4. The number of intervals counted while the timer is t iming is called
the accumulated value. True or false?
5. Because of the retentive nature of these timers, their AC value is
retained when power is lost and when switching from the Run mode.
True or false
9
6. For RTO instructions, the timer starts timing when rung conditions
are TRUE. When the rung conditions are FALSE, the timer stops
timing but the AC value is retained so that timing is resumed from
that point when rung conditions are TRUE again. True or false?
7. An RTF timer starts timing when rung conditions change from
TRUE to FALSE. The AC value represents the cumulative time
that the rung has been FALSE. True or false?
8. The time delay for timer instructions is actually the AC value minus
the PR value. True or false?
6-2
Q-E Unit Timer Instructions
Question Group 6A 9. A PR value of 500 with an RAC value of 0 represents a time delay of:
(continued)
Answers in Unit 18
a
. 500 seconds.
b. 5 minutes.
c. 5 hours.
d 50 seconds,
e. none of the above.
10. Once a PR value has been set, it cannot be changed True or false?
11. In order to change a PR value in the run mode, the PR value must be
protected. True or false?
12. AC values cannot be changed. True or false
9
13. The timing range for timer instructions is from 0.1 to 999.9 seconds.
True or false?
14. Timer status bits can be assigned addresses from 951 thru 982. True
or false?
15. Timer overflow status bits must be assigned an address that equals
the timer address plus 50. True or false?
16. The overflow status bit is set ON when the AC value''overflows
from a count of 9999 to 0000. Examine ON instructions at the
overflow address are then TRUE. True or false?
17. The RESET (RST) instruction is given an address that is the same
as the timer address. True or false?
18. When the reset instruction is TRUE, status bits and overflow bits
return to their initial state and the AC value is reset to the
programmed RAC value. True or false?
Question Group 6B
Answers in Unit 18
Study the rungs below and answer the questions that follow. You may
want to program these rungs and observe what happens on the pocket
programmer.
Rung 5
Q-E Unit
6
Timer Instructions
Question Group 6B
(continued)
Answers in Unit 18
6-3
1. When input 001 is first turned ON, which of the following is correct?
a. Rung 2 is TRUE.
b. Rung 3 is TRUE.
c. Rung 4 is TRUE.
d. Rung 5 is TRUE.
e. None of the above.
2. When the AC value of timer 901 reaches 015.0 and rung 1 remains
TRUE, which other rungs are TRUE?
a. 2. b. 3. c. 4. d. 2.4. e. 3,4.
3. Rung 4 will be TRUE as soon as the AC value exceeds the PR value.
True or false?
4. When rung 5 is TRUE, what will the AC value be reset to?
a. 015.0. b. 901. c. 0. d. AC value minus 50. c. None of these.
5. Address 951 is the address of:
a. The examine instruction in rung 4.
b. The overflow status bit of timer 901
c. Both of the above.
d. None of the above.
6. Suppose that rung 1 is TRUE for ten seconds and then power is lost.
What will the AC value of counter 901 be when power is restored?
a. 110.0. b. 010.0. c. 001.0. d. 100.0. e. 000.1.
7. When will rung number 2 be TRUE?
a. As soon as rung 1 is TRUE.
b. When timer 901 has an AC value of 015.0 or more.
c. Until timer 901 has an AC value of 015.0.
d. While the RST instruction is TRUE.
e. None of the above.
8. If the RTO instruction in rung 1 had an address of 925, what would
the address of the Examine ON instruction in rung 4 have to be to
examine the overflow status bit of timer 925?
a. 901. b. 951. c. 925. d. 975. e. None of these.
9. When the AC value of timer 901 exceeds 9999, what output will be
energized
9
a. 901. b. Oil. c. 012. d. 013. e. None of these.
10. What initiates the timing function for timer 901?
a Examine ON at address 001 is TRUE.
b. Examine ON at address 002 is TRUE.
c. Examine ON at address 951 is TRUE.
d. All of the above.
e. None of the above.
11. What is the address of the examine instruction that will reset timer
901?
a. 001. b. 901. c. 951. d. 002 e. None of these.
SA
Q-E Unit Timer Instructions
Question Group 6C Study the rungs below and answer the questions that follow. Youmay
Answers in Unit 18 want to program these rungs and observe what happens on the pocket
programmer.
1. When rung 1 goes TRUE, input 001 must be ON. Trueorfalse?
2. When rung 1 goes TRUE, timer 901 will start timing. True or false?
3. Rung 2 will be TRUE when:
a Rung 3 is TRUE,
b Rung 3 is FALSE.
c. Input 002 is ON.
d. Input 002 is OFF.
e. None of the above.
4. Rung 4 will be TRUE as soon as the AC value exceeds the PR value.
True or false?
5. Rung 3 is TRUE:
a. When the AC value equals or exceeds 0300.
b Until the AC value equals or exceeds 0300
c. When rung 2 is TRUE.
d. Upon power-up only.
e. None of the above.
6. For an RTF timer, the AC value represents the cumulative time that
the RTF rung has been FALSE. True or false?
7. If your accumulator value is up to 0250 and power to your system is
lost, what will your accumulator value be when power is restored?
a. 0000. b. 0300. c. 9999. d. 0250. e. None of these.
Q-E Unit
6
Timer Instructions
Question Group 6C
(continued)
Answers in Unit 18
6-5
8. When will output 012 be energized?
a. Never.
b. Always.
c. When rung 3 is TRUK.
d. When rung 1 is FALSE.
e. None of the above.
9. When will output 013 be energized?
a. Never.
b. Always.
c. When timer 901 AC value exceeds 9999.
d. When input 002 is ON
e. Until timer 901 AC value exceeds 9999
10. When will output 014 be energized?
a. When timer 901 AC value exceeds 9999.
b. When input 002 is ON.
c. Until timer 901 AC value exceeds 9999.
d. bandc.
11. It is possible for status bit 901 and status bit 951 to be ON at the
same time. True or false?
12. When your AC value is at 500, status bit 901 will be OFF. True or
false?
13. Suppose the AC value equals or exceeds the PR value and status bit
901 has gone OFF. If the reset instruction goes TRUE:
a. The AC value will be reset to the RAC value.
b. Status bit 901 will remain OFF.
c. Status bit 901 will be reset to ON.
d. Overflow status bit 951 will reset to OFF (if it has been set ON).
e. a, b, and d above.
14. If RTF 901 is reset, status bit 901 will go ON after rung 1 makes a
TRUE to FALSE transition. True or false?
6-6
Q-E Unit Timer Instructions
QUGStion Croup 6D Study the rungs below and answer the questions that follow. You
Answers in Unit 18 may want to program these rungs and observe what happens on the
pocket programmer.
Rung 1
Rung 2
Rung 3
Rung 4
Rung 5
001
0 0 1 9 5 1
HIII-
901
-{ RTO y
PR 000.0
902
RT
y
PR 8S0.0
902
||
011
II
002
||
901
II
RAC 0000
002
||
902
RAC 0000
1. After-1 [- 001 goes TRUE, how much time must elapse before
output 011 is energized?
a. 850 seconds,
b 999 9 seconds,
c. 1850 seconds,
d 1000 seconds,
e. None of the above.
2. Which rung(s) must be TRUE in order for output 011 to be
energized?
a. 1. b. 1,2. c. 1,2,4. d. 3. e. None of these.
3. When input 002 is ON, what will happen?
a. Timer 901 will be reset.
b. Timer 902 will be reset.
c. Rung 4 will be TRUE.
d. Rung 5 will be TRUE.
e. All of the above.
4. After what time period will timer 902 start timing?
a. Input 001 and status bit 901 must be ON. 850 seconds have
elapsed.
b. Input 001 and status bit 951 mu^t be ON. 1000 seconds have
elapsed.
c. Input 002 must be ON.
d. All of the above.
e. None of the above
5. Timer 901 starts timing when the rung conditions for rung l are
FALSE. True or false?
Q-E Unit
Key Terms and
Concepts
Question Group 7A
Answers in Unit 18
Counter
Instructions
You should become thoroughly familiar with the following terms and
concepts. Re-read the referenced pages/figures if necessary.
Preset Value (PR) 7-1 Underflow Bit 7-2
Reset Value (RAC) 7-1 Reset Instruction 7-2
Accumulated Value (AC) 7-1 FALSE-TRUE Transition Fig. 7.1
Status Bit 7-2 Up Counter-(CTU)- 7-4
Overflow Bit 7-2 Up-Down Counter 7-6
SYMBOLOGY
-<Rsn-
-fCTU)-
^^
-(CTD)-
J
1. CTU counters start counting when rung conditions are TRUE.
True or false?
2. CTU counters count FALSE to TRUE transitions of the rung
containing the CTU instruction. True or false?
3. A CTU counters AC value increases by 1 count for each FALSE to
TRUE transition of the CTU rung. True or false?
4. If a CTU counter rung is FALSE and then goes TRUE, its AC value
will increase by 1. When the rung goe9 FALSE again, the AC value
will increase by 1 again. True or false?
5. CTD counters start counting when rung conditions are TRUE.
True or false?
6. CTD counters count FALSE to TRUE transitions of the rung
containing the CTD instruction. True or false?
7. A CTD counters AC value will decrease by 1 for each FALSE to
TRUE transition of the CTD rung. True or false?
8. The counter status bit is set ON when the AC value reaches the PR
value. True or false?
7-2
Q-EUnit Counter Instructions
Question Group 7A 9. The counter status bit has an address that is:
(continued) a. The same as the counter instruction.
Answers in Unit 18 b. The counter address plus 50.
c. The counter address minus 50.
d. Automatically assigned when the instruction is entered
e. None of the above.
10. The counter overflow status bit has an address that is:
a. The same as the counter instruction.
b. The counter address plus 50.
c. The counter address minus 50.
d. Automatically assigned when the instruction is entered.
e. None of the above.
11. The counter overflow status bit is set OX when:
a. The AC value equals or exceeds the PR value.
b. The AC value exceeds 9999
c. The AC value exceeds the PR value minus the RAC value
d. All of the above.
e. None of the above.
12. The counter underflow bit is set OX when:
a. The AC value exceeds 9999
b. The AC value goes below 0000.
c. The AC value is less than the PR value.
d. The AC value equals the PR value minus the RAC value.
13. The reset instruction is given the same address as the counter
instruction. True or false?
14. When the reset instruction is TRUE, status, overflow and underflow
bits are reset to OFF. True or false?
15. When the reset instruction is TRUE, the AC value is reset to the PR
value. True or false?
16 In the Run mode, when the cursor is positioned on the reset
instruction and rung conditions are TRUE, the OX LED in the
programmer display will be lit. True or false?
17. PR and AC values can be monitored and changed only in the
Program mode. True or false?
18. Your PR values can be protected from changes in the Run and Test
modes by using the PRT/UNPRT key. True or false?
Q-E Unit
Question Group 7B
Answers in Unit 18
Counter Instructions
7-3
Study the rungs below and answer the questions that follow. You may
want to program these rungs and observe what happens.
1. The address for the CTU instruction in rung 1 is an acceptable
address for a counter instruction. True or false?
2. If you wanted to examine the overflow status bit of the counter in
rung 1. what address would you assign to the examine instruction?
a. 901. b. 951. c. 952. d. 978. e. None of these.
3. When would output Oil be energized?
a. Until the AC value equals the PR value.
b. When the AC value equals or exceeds the PR value.
c. Only when the AC value exceeds 9999
d. Only when the AC value goes below 0000.
e. None of the above.
4. When would output 012 be energized?
a. Until the AC value equals the PR value.
b. When the AC value equals or exceeds the PR value.
c. Only when the AC value exceeds 9999.
d. Only when the AC value goes below 0000.
e. None of the above.
5. Suppose your AC value is at 0048 and you lose AC line power to the
controller When power is restored to your controller, what will your
AC value be?
a. 0000. b. 0048. c. 0049. d. 0050. e. None of these
6. Rung 4 goes TRUE and while it is TRUE rung 1 goes thru 5 PAUSE
to TRUE transitions. After that, rungs 1 and 4 go FALSE at the
same time. What is the AC value of counter 928 at this time
9
a. 0005. b. 0004. c. 0000. d. 0001. e. None of these
7. Suppose you were running a production line and you were using a
counter to keep track of the number of parts produced. If you wanted
to subtract the number of rejected parts, so your counter would count
onlv good parts, you could program an up/down counter True or
false?
7-4
Q-EUnit Counter Instructions
Question Group 7C Study the rungs below and answer the questions that follow. You may
Answers in Unit 18 want to program these rungs and observe what happens on the pocket
programmer.
Rung 1
Rung 2
Rung 3
Rung 4
11
502
0
951
PR 0015
PR 0015
011
-< >-
012
< >
Rung 5
003
Hh
RAC 0000
1. What i3 the address of the examine instruction that will cause the
counter to increment?
a. 001. b. 002. c. 901. d. 951. e. 003.
2. What is the address of the examine instruction that will cause the
counter to decrement?
a. 001. b. 002. c. 901. d. 951. e. 003.
3. What is the address of the examine instruction that will preset the
counter to a count of zero when TRUE?
a. 001. b. 002. c. 901. d. 951. e. 003.
4. When would output 011 be energized?
a. When the up counter reaches a count of 0015.
b. When the down counter goes below 0000.
c. When status bit 901 is ON.
d. All of the above.
e. None of the above.
5. When would output 012 be energized
9
a. When the up counter exceeds a count of9999.
b. When the down counter goes below 0000.
c. When status bit951isON.
d. All of the above.
e. None of the above.
6. When input 003 is ON, which counter(s) would be reset?
a. CTU901. b. CTD901. c. Both. d. Noneofthese.
Q-E Unit
Question Group 7C
(continued)
Answers in Unit 18
Question Group 7D
Answers in Unit 18
Counter Instructions
7 5
7. Suppose rung 5 is TRUE and counters are reset. Inputs 001 and 002
are both actuated 5 times. What will the AC value of CTU 901 be?
a. 0015. b. 0005. c. 0000. d. 0010. c. None of these.
8. What will the AC value of CTD 901 be in question 7?
a. 0015. b 0005. c. 0000. d. 0010. e. None of these.
9 From that point input 001 is actuated 9 times. What will the new
AC value of CTU 901 be?
a. 0001. b. 0019. c. 0009. d. 0011. e. None of these.
10. The AC value of CTU 901 will always be the same as CTD 901
during normal operation. True or false?
11. While the reset instruction is TRUE, both counters are disabled and
the inputs 001 and 002 will not enable the counters. True or false?
Study the rungs below and answer the questions that follow.
Rung 1
Rung 2
Rung 3
Rung 4
Rung 5
Rung 6
II--------
----------- (
P
951
/
\
?
951
---- II--------------(
001
901
002
- 1H
002
902
RAC 0000
011
~<
901
"<
RST
>-
RAC 0000
RAC 0000
1 It is possible to energize an output after a count of something greater
than 9999 by cascading counters together. True or false?
2
2. When does counter 902 start counting?
a When the AC value of CTU 901 reaches 3000.
b. When the AC value of CTU 901 reaches 6000
c. When the AC value of CTU 901 exceeds 9999.
d. When the AC value of CTU 901 reaches 0001.
c Noncoftheabove.
7-6
0-E Unit Counter Instructions
Question Group 7D
3. When will output 011 be energized?
(continued)
a. When the AC value of CTU 901 reaches 6000.
Answers in Unit 18 b. When CTU 901 is reset.
c. When CTU 902's AC value equals or exceeds 0001 and CTU
901s AC value equals or exceeds 6000.
d. Then CTU 901's AC value exceeds 9999 and CTU 902s AC value
equals or exceeds 0001.
e. None of the above.
4. When output 011 is energized, how many counts have occurred?
a. 13,000. b. 10,000. c. 0001. d. 16.000. e. None of these.
5. The AC value of counter 901 must reach 6,000 twice before output
011 will be energized, True or false?
6. If you wanted output 011 to go ON after a count of 10,500, what
would you change the PR value of counter 901 to
9
a. 9999. b. 0500. c. 0501. d. 0001. e. None of these.
Q-E Unit Timers with Long or
Fine Time Base
Key Terms and
Concepts
You should become thoroughly familiar with the following terms and
concepts. Re-read the referenced pages if necessary.
Long Time Base Instructions 8-2 Scan Time Measurement 8-4
Fine Time Base Instructions 8-3
SYMBOLOGY
869 870 871
HI------ II------- IH
872 873 874
HI-------II-------Ih-
875
HI
Question Group 8A
Answer? in Unit 18
1. Fine Time Base instructions are bits that pulse ON and OFF at
intervals of 10 milliseconds to one second. True or false?
2. If the scan time of your program is less than 10 milliseconds but
more than 5 milliseconds, you could select a fine time base of 10
milliseconds using address 870. True or false?
3. The only way to determine the scan time of your program is to write
down all the instructions you use in your program and add up the
instruction execution times. True or false?
4. The pulse rate of the fine time base instruction at address 869 is the
same as your measured scan time. True or false?
5. You can only use address 869 if your measured scan rate is less than
5.0 milliseconds. True or false?
6. By using a fine time base instruction with a counter instruction, you
could program a time delay that is less than the 0.1 sec. provided by
standard timers. True or false?
7. The rungs that you add to your program to measure scan time
should be deleted from your program when you are ready to run.
True or false?
8. Long time base instructions can be used with the SLC 100 and SLC
150 processors at addresses 875 and 874. True or false?
9. The long time base instruction allows you to program timers with
greater resolution than the .1 second provided by the standard
timers. True or false?
10. Fine time base instructions allow you to choose only one of four time
bases. True or false?
11. 0.5 and 1.0 second time bases allow you to program timers with time
delays up to 9999 seconds. True or false?
12. The SLC 150 1.0 second long time base is based on the processor scan
cycle allowing you to program real time clock applications. True or
false?
8-2
Q-E Unit Timers with Long or Fine Time Base
Question Group 8B Study the SLC 100 program below and answer the questions that follow.
Answers in Unit 18 You may want to program these rungs and observe what happens on the
pocket programmer.
Rung 1
Rung 2
001 872
901
901
(CTU)------
PR 0003
011
Rung 3
901
(rst)~
RAC 0000
1. When input 001 is ON, rung 1 will be TRUE once every 40
milliseconds. True or false?
2. If input 001 stays ON, when will output 011 be energized?
a. Immediately.
b. After 12 seconds
c After 120 milliseconds.
d. Never.
e. None of the above.
3. If you wanted a time delay of 240 milliseconds without changing the
PR value of CTU 901, what address would you assign to the fine base
instruction in rung 1?
a. 870. b. 871 c 873. d. 874. e 875.
MCR and ZCL
Instructions
Q-E Unit
Key Terms and
Concepts
You should become thoroughly familiar with the following terms and
concepts. Re-read the referenced pages if necessary.
Master Control Reset -{MCR}- 9-1 Non-retentive 9-1
Zone Control Last State -{ZCL}- 9-1
Zone 9-1
Start Rung 9-1
End Rung 9-1
Multiple ZCL Zones 9-3
Nesting ZCL Zones 9-4
Master Control Relay 9-5
SYMBOLOGY
-<zcl>-
-<MCR>-
SHIFT
Question Group 9A
Answers in Unit 18
1. The master control reset instruction (MCR) allows you to use one set
of condition instructions to control multiple outputs. True or false?
2. The master control reset instruction (MCR) consists of a start rung
which contains the condition instructions for the zone, and an end
rung which contains no conditional instructions and marks the end
of the zone. True or false?
3. All non-retentive outputs between the MCR start and end rungs are
controlled by the MCR instruction. True or false?
4. Any number of rungs may be programmed between the MCR start
and end rungs providing memory space is available. True or false?
5. When the MCR start rung is TRUE, all non-retentive outputs within
the zone are de-energized. True or false?
6. In an MCR zone when the start rung is FALSE, latch/unlatch
instructions remain in their last state regardless of whether they
were ON or OFF. True or false?
7. A timer or counter in an MCR zone with a FALSE start rung will
have its AC value reset to the RAC value. True or false?
8. A sequencer instruction in an MCR zone with a FALSE start rung
will have its step number retained. AC value stops incrementing
and will be retained. Programmed outputs, completion and input
satisfied bits will remain in their last states. True or false?
9. A reset instruction in an MCR zone with a FALSE start rung will
remain in its last state. Instructions cannot be reset. True or false?
10. An MCR instruction is assigned an address that is between 033 and
099. True or false?
11. When the MCR rung is TRUE and you cursor to the MCR
instruction on the display, the ON LED should be lit. True or false?
9-2
Q-E Unit MCR and ZCL Instructions
Question Group 9B Study the rungs below and answer the questions that follow. You should
Answers in Unit 18 program these rungs and observe how the MCR instruction works.
1. Turn inputs 1 through 5 ON Outputs 11 and 12 will be ON. True or
false?
2. Turn input 5 OFF. Outputs 11 and 12 will be ON. True or false?
3. Turn input 1 OFF. Outputs 11 and 12 will be OFF. True or false?
4. Turn input 1 back ON and input 2 OFF Outputs 11 and 12 will be
OFF. True or false?
5. Inputs 1,2, and 3 are the condition instructions that control the
MCR zone. True or false?
6. When inputs 1, 2, and 3 are ON, the outputs in the MCR zone
operate normally. True or false?
Q-E Unit
Question Group 9C
Answers in Unit 18
MCR andZCL Instructions
9-3
1. The ZCL instruction operates the same as the MCR instruction.
True or false?
2. The ZCL instruction does not require an address. True or false?
3. It is possible to nest ZCL zones with the SLC 100? True or false?
4. The ZCL zone is defined as the rungs between the ZCL start and end
rungs. True or false?
5. When the ZCL start rung isTRL'E, non retentive outputs are de
energized. True or false?
6. When the ZCL start rung is FALSE, timers and counters function
the same as they would in an MCR zone with a FALSE start rung.
True or false?
7 An infinite number of ZCL zones may be nested together when
using an SLC 150? True or false?
8. When the ZCL start rung is FALSE, sequencers function the same
as they would in an MCR zone with a FALSE start rung. True or
false?
9. When the ZCL start rung is FALSE, latch/'unlatch instructions
operate the same as they would in an MCR zone with a FALSE start
rung. True or false?
10. More than one ZCL instruction may be used in your program. True
or false?
11. If two ZCL zones are used with an SLC 100, one zone must end before
another can begin. True or false?
12. A ZCL or MCR instruction may be used instead of hard-wiring a
Master Control Relay for emergency shut-down. True or false?
13. A Master Control Relay provides emergency shut-down capability
for the operator of a machine. This system should be hard-wired to
shut your controller down in the event of an emergency. A ZCL or
MCR instruction cannot provide this degree of protection. True or
false?
14. ZCL zones may not share common outputs. True or false?
9-4
Q-E Unit MCR and ZCL Instructions
Question Group 9D
Answers in Unit 18
Study the rungs below and answer the questions that follow.
Rung
Rung
Rung
Rung
Rung
Rung
Rung
Rung
1. It is possible to have two ZCL zones in a program as long as they
dont overlap. True or false?
2. If input 001 is OFF, outputs in the lower ZCL zone will be held in
their last state. True or false?
3. This program will not work properly because output 012 appears
twice in the program. True or false?
4. If input 001 is OX, what must happen in order for output 012 to be
ON?
a. Rung 6 must be TRUE.
b. Rung 3 must be TRUE.
c. Input 2 must be OFF.
d. Both a and b above.
e. None of the above
5. This program would work identically if MCR instructions were used
in place of the ZCL instructions. True or false?
Q-E Unit Sequencer
Instructions
Key Terms and You should become thoroughly familiar with the following terms and
Concepts concepts Re-read the referenced pages if necessary.
Time-Driven 10-1 Sequencer Output 10-4
Event Driven 10-1 Sequencer Input 10-5
SQI Input-Satisfied Status Bit 10-2 Sequencer Data 10-6
SQO Step Completion Bit 10-2 GroupNumbers 10-7
SQO Cycle Completion Bit 10-2 Sequencer Data Form 10-8
Reset Instruction (RST) 10-2 Mask/Step Data 10-9
SYMBOLOGY
-4sqo>- -<SQI>- TIME EVENT
1 1
-<RST>-
QueStion Group 10A 1. The Sequencer Output instruction (SQO) is retentive and requires a
Answers in Unit 18 reset instruction, however the Sequencer Input instruction (SQI) is non-
retentive and requires no reset instruction. True or false?
2. Sequencer instructions are typically used with machines or
processes involving repeating operating cycles which can be
segmented into step3. True or false?
3. Sequencer instructions must be assigned an address
from_____ thru ______ .
4. Sequencers can have up to
____ steps and can be
______driven or_______driven.
5. When using a time-driven sequencer, what advances the sequencer
to the next step?
a. When the AC value equals 999.
b. When the AC value equals the PR value.
c. When the AC value equals the RAC value.
d. When the input satisfied bit is ON.
e. None of the above.
6. Time-driven sequencers count 1.0 second intervals. True or false?
10-2
Q-E Unit Sequencer Instructions
Question Group 10A 7. Event-driven sequencers count FALSE to TRUE transitions of the
(continued) sequencer rung. True or false?
Answers in Unit 18 8. Event-driven sequencers move to the next step when their AC value
equals the RAC value. True or false?
9. Sequencer output instructions set the ON/OFF status for one group
of bit addresses for each step. True or false?
10. After the final step, the sequencer continues with step 0. True or
false?
11. The sequencer input instruction examines the ON/OFF status of one
group of bit addresses for each step. An input-satisfied status bit is
set ON, when the status of the examined bit addresses matches
programmed data. True or false?
12. The SQI sequencer input-satisfied status bit is assigned an address
that is equal to the SQI instruction plus 50. True or false?
13. The SQO cycle completion bit is assigned the same address as the
sequencer. True or false?
14. The SQO cycle completion bit goes ON when the sequencer
completes its final step. True or false?
15. The reset (RST) instruction is given the same address as the
sequencer. True or false?
16. When the reset instruction goes TRUE, which of the following
statements are true?
a. The SQI input-satisfied status bit is reset to OFF.
b. The completion bit is reset to OFF.
c. Sequencer instruction is reset to the programmed RAC step value.
d. All of the above.
e. None of the above.
17. The RST instruction must go FALSE before the sequencer can
resume operation. True or false?
18. When programming sequencer data for the bit addresses to be
controlled, a two-digit code is used to represent the ON/OFF status
for each step. Instead of entering eight l's or 0s only 2 digits are
entered for each step. True or false?
19 If AC power is lostduring sequencer operation and then restored,
the sequencer will start over from step 0. True or false?
20 Sequencer status will be retained when switching from one mode to
another. True or false?
21. Sequencer output instructions at addresses 901,902, 903, 904 are
used in programming high speed input modules. True or false?
22. SQI and SQO instructions can be time or event driven. True or
false?
23. The SQI instruction is no different than the SQO instruction. True
or false?
Q-E Unit Sequencer Instructions
10-3
Question Group 10B 1. Sequencer Programming Example.
Answers in Unit 18 Use the Sequencer Instruction Data Form to document an SQO time-
driven sequencer at address 901. You want to control outputs at bit
addresses 011 through 016 for a simple 4-step sequence
Step 0 has no bits ON for 5 seconds.
Step 1 has only bit 016 ON for 15 seconds.
Step 2 has bits Oil, 012, 013, and 014 ON for 30 seconds.
Step 3 has bits 013, 014,015, and 016 ON for 1 minute.
Try not to look at the answer until you have completed the form.
Use this form as a work sheet:
(I <SQJ> TIME DRIVEN
CLASSIFICATION: ADDRESS:--------- ^
EV
ENT DRIVEN
GR0UP NUMBER
=
BIT ADDRESS DATA
PROGRAM
CODE
PRESET
VALUES
Bit Addresses
Mask Data-*-
B A
Data
B
Data
A
Step Data -+ 0
___1__1__1__
1
1 1 1
1 t 1
2
1 1 1

3
1 1 !
1 1 1
Use this form for your Final answer:
CLASSIFICATION: ADDRESS:
TIME DRIVEN
EVENT DRIVEN
GROUP NUMBER:
BIT ADDRESS DATA
PROGRAM
CODE
PRESET
VALUES
Btt Addresses *
Mask Data-*
B A
Data
B
Data
A
Step Data 0
1 1 1
___1__1__1__
1
1 1 1
___1__1__1__
2
1 1 1
1
3
1 1 1
10-4
Q-E Unit Sequencer Instructions
Question Group TOC Study the rungs below and the sequencer data form that follows. This
Answers in Unit 18 information will help you answer the questions in group IOC.
Rung 1
RAC oocc
CLASSIFICATION: ^ ADORESS: 905_ GROUP NUMBER: _0
BIT ADDRESS DATA
PROGRAM
CODE
PRESET
VALUES
Bit Addresses -*
Mask Data-*
B A
Data
B
Data
A 018 017 0 1 6 015 0 1 A 013 0 1 2 0 1 1
0 0 1 ! 1 1 1 1 3 F
Step Data-* 0 0 0 0 0 0 0 0 1 0 1 i ! 0 } 1
1 0 0 0 0 0 0 1 1 0 3
i I o ! 1
2 0 0 0 0 0 1 1 1 0 7
0 I 1
3 0 0 0 0 1 1 1 1 0 F
! o ! i
0 0 0 1 1 1 1 1 1 F ! o. 1 i
5 0 0 1 1 1 1 1 1 3 F ! o . j i
6 0 0 0 0 0 0 0 0 0 0 ! o ! 1
7 0 0 1 1 1 1 1 1 3 F ! o ; i
8 0 0 0 0 0 0 0 0 0 0 ! ! o ! i
9 0 0 1 1 1 1 1 1 3 F
! ; o ; t
1. How many bit addresses are controlled by this sequencer?
a. 4. b. 6. c. 8. d. 10. e. 12.
2. What is the mask data program code for this sequencer?
a. 3F. b FE. c. OF. d. CE. e 01.
3. Assuming normal operation, when input 005 is turned ON', the
sequencer will perform the steps as you have programmed. When
input 005 is turned OFF, the sequencer will stop at the step it was
currently on and resume from that step when input 005 is turned
OX again. True or false?
Q-E Unit
10
Question Group IOC
(continued)
Answers in Unit 18
Sequencer Instructions
10-5
4. Suppose input 005 were turned OFF at step 3 in the Run mode.
Inputs Oil through 014 would be energized. True or false?
5. If you wanted to control only outputs 011,012,013, and 014, what
would the program entry code for your mask data be?
a. C3. b. OF. c. 2B. d. B2. e. None of these.
6. What is the preset value for each step?
a. lOsec. b. 0.1 sec. c. l.Osec d lOOsec. e. Noneofthese.
7. When will rung 2 be TRUE?
a. For 1.0 second after each step
b. For 10 seconds after each step.
c. For one program scan after each step is completed.
d. All of the above.
e. None of the above.
8. For whatstep(s) of the sequence will all outputs be ON?
a. 1. b. 5. c. 8. d. 7. e. 9.
9. For what step(s) of the sequence will all outputs be OFF?
a. 1. b. 6. c 8. d. 9. e. 16.
10. FR values can be changed in the Run and Test modes. True or false?
11. The sequencer RAC value should always be set to 0. True or false?
12. The reset instruction will always reset the sequencer to step 0 of the
sequence. True or false?
13. When will bit address 703 be ON?
14. When input 001 is ON, the sequencer will be reset to step 0 and the
completion bit will be reset to OFF. True or false?
15. While rung 4 is TRUE, the sequencer will be held on step 0. True or
false?
16. If a bit address of the group controlled by your sequencer is masked,
it may be used elsewhere in your program. True or false?
10-6
Q-E Unit Sequencer Instructions
Question Group 10D
Answers in Unit 18
1. If you wish to energize an output only after a certain set of input
conditions have been satisfied, a sequencer input instruction (SQI)
can be used. True or false?
2. A typical application for a sequencer input instruction might be a
packaging application where certain limit switches must be tripped
before the conveyor can cycle to its next position. True or false?
3. How many bit addresses can the SQI instruction examine?
a. 1. b. 2. c. 4. d. 6. e. 8.
4. What happens when all input conditions for a given step are
satisfied?
a. The sequencer advances to the next step.
b. The sequencer is reset to step 1.
c. The input satisfied bit is set ON.
d. All flags are reset to 0.
e. None of the above.
Question Group 10E Study the rungs below and the sequencer data form that follows. This
Answers in Unit 18 information will help you answer the questions for group E.
CLASSIFICATION: | ADDRESS: JS3_ ^ EVENT^ORIVEN OUR NUMBER -2-
BIT ADDRESS DATA
PROGRAM
CODE
PRESET
VALUES
Bit Addresses
Mask Data
B A
0at3
3
Data
A oos 007 006 005 004 003 002 001
0 1 1 1 1 I 0 7 c
Step Data 0 0 0 1 1 1 0 0 0 3 8
11 1
1
. 1 1 1
1
1 0 0 0 0 0 1 1 0 0 6
I 1 A
1 1 1
2 0 0 0 1 1 0 0 0 1 8
I -I
I I 1
3 0 1 1 0 0 0 0 0 6 0
1 1 1 ?
4 0 1 1 1 1 1 1 0 7 E
!
1 1 1
Q-E Unit
Question Group 10E
(continued)
Answers in Unit 18
Sequencer Instructions
10-7
1. How many bit addresses arc examined by this sequencer?
a. 2. b. 4. c. 6. d. 8. e. None of these.
2. What is the bit address group number controlled by this sequencer?
a. 1. b. 3. c. 5. d. 7. e. 9.
3. When will the input-satisfied bit be ON for step number 0?
a. When inputs 3 and 8 are ON.
b. When inputs 4,5, and 6 are ON.
c. When rung 1 makes a FALSE -TRUE transition.
d. When the sequencer advances to step 2.
e. None of the above.
4. When will output 014 be energized?
a. Always.
b. Never.
c. When the AC value exceeds 9999.
d. Until the input satisfied conditions for a particular step are met.
e. For the first second of each step.
5. The SQI sequencer will advance to the next step whenever the
FALSE to TRUE transitions of the SQI rung match the programmed
preset value. True or false?
6. If input conditions have not been met but the SQI rung goes thru a
FALSE to TRUE transition, the sequencer will advance to the next
step if the preset value for that step is 1. True or false
9
7. The reset instruction can be used to reset the sequencer to any step.
True or false?
8. The reset instruction will reset the sequencer to the programmed
RAC step, reset the input-satisfied bit to 0, and reset the completion
bit to 0. True or false?
9. When will the sequencer advance to step 4?
a. When rung 1 goes thru one FALSE to TRUE transition at step 3.
b When rung 1 goes thru two FALSE to TRUE transitions at step 3
c. When the input-satisfied bit for step 3 goes ON.
d. When rung 4 is TRUE
c. None of the above.
10. What conditions must be met for the input-satisfied bit to be ON for
step 4?
a Inputs corresponding to program entry code 7E must be ON.
b Inputs 2 through 7 must be ON.
c. All inputs controlled by this sequencer must be ON.
d. All of the above.
e. None of t he above.
Q-E Unit Special Sequencer
Instruction Techniques
Key Terms and You should become thoroughly familiar with the following terms and
Concepts concepts. Re-read the referenced pages if necessary.
Cascading Sequencers 11-1 SQI Monitoring an SQO 11-7
Reversing 11-4 Sequencer Jump Operation 11-10
SQI Driving an SQO 11-6
SYMBOLOGY

-(SQO)- (SQD- (RST). TIME EVENT


Question Group 11A l. SQI instructions can be cascaded in order to monitor more than
Answers in Unit 18 8 input addresses. True or false?
2. SQO instructions can be cascaded in order to control a sequence of
operations that energizes outputs in more than one group. True or
false?
3. A reversing sequencer operation allows you to operate a sequencer
in forward or reverse step order. True or false?
4. The reversing sequencer operation requires a ZCL zone to control
reverse operation. True or false?
5. To program a reversing sequencer you must assign a special group
number to the reversing SQO instruction. True or false?
6. If you had a sequencer at address 921, and you wanted to make it a
reversing sequencer, what group number would you assign to the
reversing sequencer instruction? ______________
7. For a reversing sequencer operation, the preset values for both
sequencers must be the same. True or false?
8. It is possible to program an SQO instruction that will energize
outputs in response to the conditions satisfied in an SQI instruction.
True or false?
9. With the SLC 100 you cant use an SQI instruction to monitor an
SQO instruction. True or false?
10. If you don't want to use all the steps of a programmed SQO
instruction, you can program a sequencer jump to skip the steps you
dont want to use. True or false?
11. An SQI status bit can be used to advance an SQO to its next step.
True or false?
12. The jump operation allows you to skip certain steps of your program
if the proper conditions are met. True or false?
11-2
Q-E Unit Special Sequencer Instruction Techniques
Question Group 11B
Answers in Unit 18
Study the rungs below and the sequencer data forms that follow. These
will help you answer the questions for group 11B
Rung 1
Rung 2
Rung 3
Rung 4
001
11
901
1 I
002
ISQOJ
901
001
\RbTJ
RAC0
901
001
ISQO;
901
1 1
Q-E Unit Special Sequencer Instruction Techniques
11-3
Question Group 11B
( c o n t in u e d )
A n s w e rs i n U n i t 1 8
Rung 1
CLASSIFICATION:
(SQl>
0 -<SQO>-
ADDRESS: 901
TIME DRIVEN
S EVENT DRIVEN
GROUP NUMBER: 0
BIT ADDRESS DATA
PROGRAM
CODE
PRESET
VALUES
Bit Addresses-*
Mask Data-*
B A
Data
B
Data
A 018 017 016 015 014 013 012 011
0 0 0 0 0 0 0 0 0 0
Step Data * 0 1 1 0 1 0 0 0 1 0 1
i j l
1 0 0 1 0 1 0 1 0 2 A
r: y.
2 1 1 0 0 0 1 0 0 C 4
1 1
HT
1 1 1
1
3 0 0 0 1 0 0 0 1 1 1
1 1 1 .
1 1 1
1
Rung 3
Rung 4
CLASSIFICATION: ADDRESS: _901_ | GROUP NUMBER: _0
BIT ADDRESS DATA
PROGRAM
CODE
PRESET
VALUES
Bit Addresses-*
Mask Data -*
B A
Data
B
Data
A
018 017 016 015 014 013 012 oil
1 1 1 1 1 1 1 1 F F
Step Data -* 0 1 1 0 1 0 0 0 1 D 1
: ; : <
1 0 0 1 0 1 0 1 0 2 A
I 1.
1 1
2 1 1 0 0 0 1 0 0 C 4
i l l ,
1 1 1
1
3 0 0 0 1 0 0 0 1 1 1
i l 1 .
1 1 1
1
-<SQI>- . TIME DRIVEN
CLASSIFICATION: ADDRESS: _901_ _ r w c w r qrivEN
GR0UP NUM8ER:
-3-
BIT ADDRESS DATA
PROGRAM
CODE
PRESET
VALUES
Bit Addresses -*
Mask Data-*
8 A
Data
B
Data
A
118 117 116 115 114 113 112 111
1 1 1 1 1 1 1 1 F F
Step Data -* 0 1 1 0 0 1 1 0 0 C C
! I ! 1
1 1 0 0 0 1 0 0 0 8 8 ! ! : 1
2 0 1 0 0 1 1 0 1 4 D ; ! ; 1
3 1 0 1 0 0 1 0 0 A 4
! ! ! 1
1. Rung 1 is used to synchronize the bit addresses of the sequencers
in rungs 3 and 4. True or false?
2. Rung 2 will reset the SQO instructions to step 0 True or false?
3. The data in rungs 3 and 4 are very rarely the same when using
cascaded SQO instructions. True or false?
4. The sequencers in rungs 1,3 and 4 are time driven. True or false
9
5. The sequencer in rung 4 controls Group 2 outputs. True or false?
6. The mask data of a Dummy rung is always Hexadecimal FF in the
program code. True or false?
11-4
Q-E Unit Special Sequencer Instruction Techniques
Question Group 11C Study the rungs below and fill out the sequencer data form for SQO 905
Answers in Unit 18 in rung 3. You want to program a reversing sequencer so select the right
group number, program code, and preset values. The correct answer is
located in the answer section. Try not to look at the answer until you
have completed the blank form below.
CLASSIFICATION:

(El
{SQI>
-<SQO}-
ADDRESS: 905
0 TIME DRIVEN
EVENT DRIVEN
GROUP NUMBER: _0
BIT ADDRESS DATA
PROGRAM
CODE
PRESET
VALUES
Bit Addresses
Mask Data-
B A
Data
8
Data
A
018 017 016 015 0*4 013 012 011
0 0 1 1 1 t 1 1 3 F
Step Data - 0 0 0 0 0 0 0 0 0 0 0
T4 5
1 0 0 0 0 0 0 0 1 0 1
TT r
! 1
u
- 1
5
2 0 0 0 0 0 0 1 0 0 2
!!
5
3 0 0 0 0 0 1 0 0 0 4
T T o . ! 5
4 0 0 0 0 1 0 0 0 0 8

n
1
1 1 V. 1 5
5 0 0 0 1 0 0 0 0 1 0
' I
0
'
5
6 0 0 1 0 0 0 0 0 2 0
1 1 O 1
5
CLASSIFICATION:
C (SQI>
-(sooy-
ADDRESS:
TIME DRIVEN
EVENT DRIVEN
GROUP NUMBER:
BIT AOORESS DATA
PROGRAM
CODE
PRESET
VALUES
Bit Addresses -*
Mask Data -
B A
Doto
B
Doto
A
Step Data - 0
1 1 1
1
1 1 I
1 1 1
2
1 1 1
3
1 1 r
1 1 1
Q
1 1 i
-!
1

5
f 1 1
1 1 1
6
1 1 1
1 1 1
Q-E Unit
Question Group 11D
Answers in Unit 78
Question Group 11E
Answers in Unit 18
Special Sequencer Instruction Techniques
11-5
1. Suppose that you are controlling a long sequence of events with an
SQO sequencer. You would like to know when the sequencer is on
the last step of the sequence. You could program an SQI sequencer
to monitor the SQO instruction for the last step. True or false?
2. If you want to monitor step 5 of an SQO instruction at address 925,
you could program an SQI sequencer, select group number
________ , and enter_______ for the step number.
3 If you wish to know when a sequence of events has reached or past a
certain step in your application, you could program a
a An SQI monitoring an SQO
b An SQI instruction using a > (greater than) status bit
c. An SQO instruction using a < (less than) status bit
d. a and b
e. a and c
4. If you wanted to know when your application had completed step 25
but not yet started step 30, you could program two SQI instructions
to monitor an SQO instruction. The SQI instructions would have
step data of:
a 25. 29
b. 24,28
c. 25,30
d. 26,30
e. 26,28
1. Suppose that you are controlling a bottling operation for a soft drink
line. You bottle Brand A three days a week and Brand B 2 two days
a week. Both processes are controlled by an SQO instruction. Brand
A requires 15 steps of the sequencer operation but when you bottle
Brand B, you can skip steps 5 through 9 of the sequencer operation
Given the ladder diagram below, fill in the missing information to
complete the sequencer jump operation.
Q- F Unit
Key Terms and
Concepts
Question Group 12A
Answers in Unit 18
High Speed
Input Programming
You should become thoroughly familiar with the following terms and
concepts. Re-read the referenced pages if necessary.
HSI Counter Instructions 12-2 Cascading 12-4
Maximum Pulse Rate 12-2 Scan Time 12-4
Normal Reset 12-3 Socket End Plug 12-5
Single Shot Reset 12-3
1. High speed counting is accomplished in your program by a(n)
a. time driven SQO instruction.
b. special event driven SQI instruction.
c. special event driven SQO instruction.
d. time driven SQO instruction.
e. HSI instruction
2. The controller is designed to handle up to______I1SI module(s).
a. 8
b. 6
c. 4
d. 12
e. 1
3. The corresponding HSI counter instruction addresses are
a. 601-608.
b. 601-604.
c. 901-908.
d. 901-904.
e. 951-954.
4. You must program a 4-digit RAC value for a single shot reset. The
first two digits must be 99 What do the other two di gits represent?
a. The instruction number.
b. The counter location.
c. The step number you want the sequencer set to.
d. The SSR number.
c. They have no significance.
5. What is the maximum pulse rate of one HSI module?
a. 5MHz
b. 5KHz
c. 2KHz
d. lOKHz
6 What happens when the maximum pulse rate is exceeded?
a. Instruction 601 goes FALSE,
b The HSI counter is disabled.
c. Instruction 901 goes FALSE.
d. Both a and b.
e. Both c and b.
12-2
Q-E Unit High Speed Input Programming
Question Group 12A 7. What happens when you remove the end plug, which is inserted in
(continued) the expansion socket, while the processor is in the Run mode?
Answers in Unit 18
a. A CPU fault will occur and the processor will always shut down.
b. The processor may shut down.
c. Nothing if you have a lithium battery back-up.
d. The program will be temporarily suspended.
8. Is it possible to cascade sequencers used in HSI counters?
a. Yes.
b. No.
c. Maybe.
d. Only on the SLC 100.
e. I don't know.
Question Group 12B 1. HSI counter instructions are very similar to some sequencer
Answers in Unit 18 instructions described earlier. True or False?
2. To obtain the fastest possible output control when using your HSI
counter, use the external outputs located on the expansion unit.
True or false?
3. As the frequency of your HSI counter increases, your scan time also
increases. Therefore, programming preset values of 1 will decrease
your scan rate. True or false?
4. If the processor is placed in the Test-Single Scan mode and the HSI
counter start rung is TRUE, will the HSI countin real time and
increment the accumulator as it would in the Run mode? Yes or no?
5. The HSI module should not be connected or disconnected when
power is applied to the processor unit. True or false
9
6. If you use two or more HSI modules the maximum pulse rate, for
each module, is less than if you were using only one module. True or
false?
7. The single shot reset is used to reset the counter to a specified step
without losing any high speed input counts. True or false?
Q-E Unit
Question Group 12C
Answers in Unit 18
High Speed Input Programming
12-3
An SLC 150 and HSI module is being used to count cans in a high
speed packaging application. The cans pass a solid state sensor at a rate
of 200 cans per second. The solid state sensor is connected to an HSI
module. After 24 cans are fed into a case, the conveyor belt is stopped.
The full case is removed and replaced with an empty one. The conveyor
then carries the next 24 cans into the empty case This process may be
summarized in 2 steps.
Step/operation 0 - Conveyor ON, fill case
Step/operation 1 - Conveyor OFF, eject case
The conveyor is controlled by SLC 150 output address 111.
The eject solenoid is controlled by SLC 150 output address 112.
A limit switch at address 001 senses when an empty case is in position.
The empty case, once in position, will reset the process to step 0 and
enable the conveyor. Hint: Use a single shot reset so the HSI module
does not miss counting any cans.
Complete the ladder diagram and sequencer data table to perform the
application in 12C.
12-4
0-E Unit High Speed Input Programming
Question Group 12C
(continued)
Answers in Unit 18
CLASSIFICATION:
(SQI>
-<SQO>-
ADDRESS:
TIME DRIVEN
EVENT ORIVEN
GROUP NUMBER:
BIT ADDRESS DATA
PROGRAM
CODE
PRESET
VALUES
Bit Addresses
Mask Data>
B A
Data
B
Data
A
Step Data 0
1 P"
1 1
!
1
1 1 1
! 1
1
2
1 1 i

i i I
1 i i
Type:
Use this form for your final answer:
nswer.
CLASSIFICATION:^^ AOOAiSS:_ Q EVENT^DFMVEN NUMBER:------
BIT ADDRESS DATA
PROGRAM
COOE
PRESET
VALUES
Bit Addresses
Mask Data
B A
Data
B
Data
A
Step Data- 0
i 1
1
i i i
2
i i i
1
1
1
_________
3
i 1 i
i i i
Type:
Q-E Unit
Key Terms and
Concepts
Question Group 13A
Answers in Unit 78
Shift Register
Instruction
You should become thoroughly familiar with the following terms and
concepts. Re-read the referenced pages if necessary.
Status Data 13-1
8-bit Register 13-1
Shift Right 13-1
Shift Left 13-1
Most Significant Bit 13-1
Least Significant Bit 13-1
Event-Driven 13-2
Time-Driven 13-3
Cascading 13-4
Circulating 13-5
SYMBOLOGY
SHIFT
< y TIME EVENT
1. Shift registers can be used to control machines or processes where
parts are continually shifted from from one position to the next.
True or false?
2. Address assignments are not important for shift register
instructions. True or false?
3. When programming a shift register, a ZCL zone is used to control
the shifting process and a sequencer instruction is used to control
the shift rate. True or false?
4 5 6 7
4. If you were programming a shift register instruction and you wanted
to shift data through the outputs of expansion unit number 2 from
least significant bit to most significant bit, what address would you
assign to the shift register instruction?
a. 211. b. 218. c. 111. d. 118. e. None of the above.
5. If you needed a shift left register for the application in question 4,
what address would you assign to the shift register instruction?
a. 211. b. 218. c. 111. d. 118. e. None of the above.
6. You can program a shift register instruction to shift ls or 0s
through the register. True or false?
7. You can program shift register instructions to be either time or
event-driven. True or false?
13 2
Q-E Unit Shift Register Instruction
Question CifOUp 13A 8. An event driven shift register instruction shifts status data (cither a
(continued) 1 or a 0) on each FALSE-to-TRUE transition of the sequencer
Answers in Unit 18 instruction that drives it. True or false?
9. A time-driven shift register instruction shifts status data at a
clocked rate that equals the preset value you have programmed for
the SQO instruction when rung conditions are TRUE True or false?
10. What is the most significant bit address in group number 5?______
a. I IB. b. 111. c. 518. d. 511. e. None of the above.
Question Group 'i3 Study the rungs below and answer the questions that follow. You may
Answers in Unit 18 want to program these rungs and observe what happens on the pocket
programmer.
Rung
Rung
Rung
Rung
Rung
Event- Dri ven
Group No. : Any
Mask Dat a: 0
Step 0 Data: Any
Step 0 Preset: 1
1 When input 002 is ON, a 1 is shifted into the 011 register every time
rung 1 goes through a FALSE-to-TRUE transition. True or false
7
2. If input 002 is OFF, a 0 is shifted into the register every time rung 1
goes through a FALSE-to-TRUE transition True or false
7
3. In rung 4. the shift register instruction is assigned the least
significant bit address in output group number 0. If data is
continually shifted through the register, what address will data be
shifted to after address 018?
a. 019. b 011. c. 118. d lit e. None of the above.
4. When data leaves address 118, it is shifted back to address 011.
True or false?
5. The order of rungs 3 and 4 is not critical to the shift register
operation. True or false
7
Q- F Unit
13
Question Group 13C
Answers in Unit 18
Shift Register Instruction
13-3
1. You can program a shift register instruction to shift data in a
circulating manner so that data leaving the most significant bit
address is shifted back into the least significant bit address or vice
versa. True or false
9
2. If you wanted to produce an external output when a certain bit in an
internal shift register is ON, you could program a rung with an
Examine ON instruction corresponding to the address of the shift
register bit address. You could then assign an external output
address to an Output Energize instruction. When the bit address in
the shift register goes ON, the Examine ON instruction will be
TRUE, causing the output to be energized. True or false?
3. If you program an internal shift register instruction, you can only
shift data left. True or false?
Q-E Unit Special Internal
Instructions
Key Terms and
Concepts
You should become thoroughly familiar with the following terms and
concepts. Re-read the referenced pages if necessary.
Auto/Man Switch Instruction 14-1
Program Initialization Instruction 14-2
TCAT Power-up Instruction 14-5
Breakpoint Instruction 14-5
Programmable EEPROM Auto-Load 14-7
Battery Status Instruction 14-7
Triac Zero-Cross Turn-On 14-8
Question Group 14A l. The program initialization instruction is a bit that pulses ON and
Answers in Unit 18 OFF in accordance with the processor I/O scan. True or false?
2. The program initialization instruction has two hard wired terminals
on the processor so you can wire input devices directly. True or
false?
3. The program initialization instruction is a bit in memory that is set
ON for the first program scan under certain conditions. True or
false?
4. If you use the pocket programmer to place the processor unit in the
Run or Test modes, the program initialization instruction will go ON
for the first program scan and then turn OFF. True or false?
5. You can use bit address 868 to program non- retentive timers,
counters and non-retentive latch instructions. True or false?
6. The program initialization instruction is an internal examine
instruction that you can use to initialize your program to a known
state on power-up. True or false?
7. Breakpoint instructions can be programmed on both the SLC 150
and SLC 100. True or False?
8. Address 864 can be programmed in the SLC 150 to allow the
EEPROM memory module to clear processor faults caused by
memory errors. True or False?
9. The status of bit address 865 can be examined for battery status.
True or False?
10. A breakpoint output instruction should be used in place of a hard
wired E-Stop. True or False?
11. Triac zero-cross turn ON instructions are used to minimize noise
generated when switching loads. True or False?
12. To enable triac zero-cross turn ON, status bit address 866 must be
set ON with:
a. an unconditional rung.
b. a conditional rung.
c. neither a or b.
d. either a orb.
J 4-2
Q-E Unit Special Internai Instructions
Question Group 14A
(continued)
Answers in Unit 18
13. Although special functionality of addresses 864,865 and 866 arc
unique only to the SLC 150, these addresses are simple Relay type
instructions in the SLC 100. True or false?
14. Address 865 is used for the programmable EEPROM auto-load
feature. True or false?
Q ues tion Group 148 Study the rungs below and answer the questions that follow. You may
Answers in Unit 18 want to program these rungs and observe what happens on the pocket
programmer.
1. When power is first applied, the reset instruction in rung 1 is TRUE.
True or false?
2. When input 001 is ON, timer 901 starts timing. When will status bit
901 be ON?
a. As soon as input 001 is ON.
b. After input 001 goes OFF.
c. When rung 1 is TRUE.
d. After 30 seconds,
e After 300 seconds.
3. What happens when rung 2 goes FALSE?
a. Timer 901 stops timing.
b. Timer 901 is reset,
c Input 001 is OFF.
d. All of the above
e. None of the above.
4. Timer 901 starts timing when input 001 is ON The accumulator
reaches a value of 025.0 and power is lost When power is restored,
what will the AC value be?
025.0 b 010.0. c. 000 0 d. 999.9 e. None of these.
Q-EUnit
14
Special Internal Instructions
14-3
Question Group 14B
(continued)
Answers in Unit 18
5. Timer 901 starts timing when input 001 is ON. The accumulator
reaches a value of 025.0 and input 001 is turned OFF. When input
001 is turned ON again, what will the AC value be?
a. 026.0. b. 010.0. c. 000.0. d. 999.9. c. None of these.
6. Since the AC value is reset to 0 when power is lost and restored, this
type of timing example is classified as a(n)_____________ timer.
Question Group 14C
Answers in Unit 18
Study the rungs below and answer the questions that follow.
Rung 1
001
901
-(rst)
RAC 0005
Rung 2
Rung 3
Rung A
Rung 5
002
901
(CTU)
PR 0010
901
-(ctd)
PR 0010
011
1. What is the address of the examine instruction that will cause the
counter to increment?
a. 001. b. 002. c. 901. d. 951. e. 003.
2. If power is lost and then restored, the AC values of the counters will
be:
a. The same as they were before power was lost.
b. Equal to the programmed preset values.
c. Reset to 5.
d. Reset to 0000.
e. None of the above.
3. What is the address of the examine instruction used to reset the
counters during program execution?
a. 003. b. 901. c. 001. d. 002. e. 868.
14-4
Q-E Unit Special Internal Instructions
Question Group 14C 4. Output address Oil will be turned ON when:
(continued)
Answers m Unit 18 a. The AC value is greater than or equal to 10.
b. The AC value is less than or equal to 10.
c. The AC value is less than 0.
d. The AC value is greater than 9999.
e. None of the above.
5. Output address 012 will be turned ON when
a. The AC value is greater than or equal to 10.
b. The AC value is less than or equal to 10.
c. The AC value underflows below 0.
d. The AC value is greater than 9999.
c. None of the above.
6. If the AC value is 2, and input 003 makes three FALSE to TRUE
transitions, then input 002 makes three FALSE to TRUE
transitions, which of the following will be TRUE?
a. The AC value would be 2.
b. Output 012 would be ON.
c. Underflow bit 951 would be OFF.
d. aandc.
e. aandb.
Q-E Unit Program Editing
Key Terms and
Concepts
You should become thoroughly familiar with the following terms and
concepts. Re-read the referenced pages if necessary.
Cursor Control 15-2 Clear Memory Mode 15-9
Search Function 15-4 Protecting PR Values 15-9
Remove/Insert Functions 15-6
Cancel Command 15-9
Changing Instructions In the
Program Mode 15-9
SYMBOLOGY
RUNG
-----------
NEXT LAST INSERT
SEARCH
CANCEL
CMD
REMOVE
PRT
UNPRT
Question Group 15A
Answers in Unit 18
1. The RUNG, NEXT and LAST keys allow you to move through your
program and stop at any instruction you wish to see on the display
True or false?
2. Since the pocket programmer can display only one instruction at a
time, the cursor keys are necessary to help you move through your
program for editing or troubleshooting purposes. True or false?
3. The cursor functions in which of the following modes of operation?
a. Run.
b. Test.
c. Load EEPROM Module.
d. Program.
e. Clear Memory.
4. When you are cursored on the first instruction of a rung, the display
will indicate this by displaying the symbol l~ in front of the
address information. True or false?
5. While in that rung, if you cursor right (NEXT), the instruction to the
immediate right of the first instruction will be displayed. True or
false?
6. If you are cursored on the output instruction in the last rung of your
program and you press the NEXT key, the pocket programmer will
display:
5B5 End
Although your program may vary in length, this message is
intended to tell you that you are at the end of your program and you
have so many words of memory remaining. True or false?
15-2
Q-E Unit Program Editing
Question Group 15A 7. If you are cursored on the output instruction in the last rung of your
(continued) program and you press RUNG, LAST, you will move to the first
Answers in Unit 18 instruction in the first rung. True or false?
8. If you cursor to a sequencer instruction, the instruction LED will
light and its address and rung number will be displayed. By using
the NEXT key , you can step through the instruction and access
other data associated with that instruction. True or false?
9. If you have a long program, the SEARCH function will help you save
time finding a specific instruction. The SEARCH function can also
help you find the start or end of rungs or the start or end of your
program. True or false?
10. If you are cursored to a point in the middle of your program and are
searching for a specific instruction, the search will wrap around and
search your whole program until the instruction is found. True or
false?
11. To locate the start of your program, the correct keystroke sequence
is: SEARCH. RUNG, 1, ENTER. Trucor false?
12. If you are searching for a specific instruction and the pocket
programmer displays the message
nF
(not found), the instruction you were searching for was not found in
your program. True or false?
13. You can add and delete examine instructions and entire rungs in
your program with the REMOVE and INSERT keys only in the
Program mode. True or false?
14. If you want to add a rung to your program, you must cursor to the
rung that will follow the rung you are about to insert and press
INSERT, RUNG. After this key sequence you can enter the new
rung. True or false?
15. A new rung may only be added in the Program mode. True or false?
16. When you remove or insert an examine instruction, this change is
automatically recorded in RAM memory. True or false?
17. If you cursor to an output instruction in a rung of your program and
remove that output instruction, the conditional instructions will be
automatically removed so that the whole rung is removed.
True or false?
18. By entering mode 1 and following the prompting messages on the
pocket programmer, you can clear the processor RAM memory. True
or false
9
19. Mode 1 can also be used to clear the memory of an EEPROM module.
True or false?
20. Once RAM memory is cleared, the controller automatically enters
the Program mode. Trucor false?
21. Sequencer data can onlv be changed in the Program mode. True or
false
9
22. Adding or deleting steps of a sequencer instruction can be performed
through an editing function in the Program mode True or false?
Q-E Unit
15
Question Group 15A
(continued)
Answers in Unit 18
Question Group 15B
Answers in Unit 18
Program Editing
15-3
23. When you cursor to a sequencer instruction, each time you press the
NEXT key, one of the values programmed as sequencer data will be
displayed. True or false?
24. If you want to change a sequencer parameter in the Program mode
you must cursor to the sequencer instruction and press the
sequencer key associated with that instruction and then press the
ENTER key. From that point you are able to change any data or
preset value. True or false?
25. Changes that you make to sequencer data are entered into a
temporary storage register. When you have finished editing the
sequencer, you must press ENTER to register the last change you
have made. These changes will not be permanently recorded in
RAM memory until the ENTER key is pressed again. True or false?
Program the following rung3 and complete the program editing
exercises that follow.
1. After you have entered this program, stay in the Program mode. An
additional rung must be entered in this program that will follow
rung 4. The rung you want to insert will examine status bit 951 for
an ON condition and energize output address 016 when rung
conditions are TRUE. See Figure 15.5 if you need help inserting the
new rung.
After you have entered this rung, cursor through your program, and
verify that the rung you have just entered has been inserted between
rungs 4 and 5 of your original program. Your edited program will
now contain 7 rungs. Check your final program with the answer for
Question / Exercise 1, group B, in the answer section. Verify that
the rung you have just entered is now rung 5.
15-4 15
Program Editing
Question Group 15B
(continued)
Answers in Unit 18
2. For this exercise you will remove an examine instruction from rung
2. You must remove the instruction that examines address 005 for
an ON condition. Refer to Figure 15 3 if you need help removing this
examine instruction. Check the new configuration of rung 2 in the
answer section and make sure that it matches your edited rung.
3. The Examine ON instruction that you removed in exercise 2 should
now be placed in rung 1. Insert this examine instruction between
the Examine ON at address 001 and the Examine ON at address
002. If you need help inserting this instruction, refer to Figure 15.3.
Check the answer section for the correctly edited rung and compare
this with the rung you have just edited.
4. Add a branch to the new rung 1 so that the ladder diagram looks like
this:
Rung 1
001 002 005
011
____ / \______
l )
733
Refer to Figure 15.4 if you need help inserting this branch. You will
find the correct keystroke sequence for adding this branch in the
answer section.
5. Remove the branch you have just entered. If you attempt to leave
the rung before you have removed all of the branch instructions, the
programmer will display an error message
rE P EEH
This message is telling you that you have created a short circuit. At
this point you can either insert a new instruction or, press ENTER,
and the branch instructions will be automatically removed.
6. For this editing exercise, you will remove the rung that you have
inserted in exercise 1. Refer bo Figure 15.5 if you need help
removing this rung Note that when you remove the output
instruction from the rung, the conditional instructions associated
with that rung are not automatically removed.
When you remove the ouLput instruction, the programmer will
prompt you with
-EL-
You must either add another output instruction or remove all the
remaining conditional instructions in that rung. The correct
keystroke sequence for removing this rung is located in the answer
section Verify that there are only 6 rungs left in the modified
program
7 Before you move on to the questions and exercises in Q-E Unit 16,
you must clear the processor RAM memory. Enter mode 1 and
follow the prompting messages on the pocket programmer. If you
need help, follow the keystroke example in the table on Page 15-8.
After the memory is cleared, you will have 885 words of memory
available for your next exercise.
Q-E Unit On-Line
Data Control
Key Terms and
Concepts
You should become thoroughly familiar with the following terms and
concepts. Re-read the referenced pages if necessary.
On-Line Data Control 16-1 TRUE-FALSE Status Indicator 16-2
Forcing I/O Addresses 16-1 Monitoring Data 16-4
FRC ON, FRC OFF 16-1
SYMBOLOGY
1 2 3 4 5 6 7 8 9 10
FRC ON FRC OFF
REMOVE INSERT
Question Group 16A
Answers in Unit 18
1. When the processor is in the Run mode, the pocket programmer can
be used to change certain instructions in your program. True or
false?
2. If left unprotected, timer and counter data can be changed in the
Run mode with the pocket programmer. True or false?
3. Sequencer data may also be changed in the Run mode. True or false?
4. Timer, counter, and sequencer data may only be monitored in the
Run mode. True or false?
5. By using the Force function, you can force an external I/O address
into an ON or OFF state in the Run mode. True or false?
6. When you force an input device to an ON or OFF state, you are
forcing the status bit at the I/O address and not the input terminal.
True or false?
7. When you force an output device to an ON or OFF state, you are
forcing the status bit at the I/O address and not the output terminal.
True or false?
8. If you are monitoring an Examine ON instruction with the pocket
programmer and that instruction is forced ON,
a. The FORCE LED will be lit.
b. The ON LED will be lit.
c. The FORCED I/O LED on the processor will be lit.
d. An "F will appear next to the displayed instruction.
e. All of the above.
9. The only way to remove a FRC ON function is with a FRC OFF
function. True or false?
10. When an input is forced into an ON or OFF condition, the FORCED
I/O indicator on the processor unit will be lit. True or false?
16-2
Q-E Unit On-Line Data Control
Question Group 16A ll. When an input is forced ON, the program is executed as if the input
(continued) device were actually ON. True or false?
Answers in Unit 18
12. A forced I/O address will not be retained if you enter the Program
mode and make a change or if a processor fault is detected. True or
false?
13. It is possible to remove all forces within your program without
removing each forced instruction individually. True or false?
14. Forced I/O addresses may be removed individually by cursoring to
the forced instruction and pressing REMOVE, ENTER. True or
false?
15. The pocket programmer allows you to view timer, counter, and
sequencer data in the Run and Test modes. True or false?
16. To view data associated with timer or counter instructions you must
cursor to the instruction you wish to view. Once you are positioned
on that instruction, pressing the NEXT key will display the PR
value. Pressing the NEXT key again will display the AC value.
Pressing the NEXT key one more time will display the PR value
again. True or false?
17. If you are monitoring the AC value and you press the LAST key, the
PR value will be displayed. True or false?
18. Timer and counter PR and AC values can only be changed in the
Program mode True or false
9
19. If a PR value is protected, it cannot be unprotected in the Run mode.
True or false?
Exercises Program the following rungs and complete the exercises that follow.
When programming the timer instruction, leave the PR value
unprotected.
Q-E Unit On-Line Data Control
16-3
Exercises
(continued)
1. Enter the Run mode and turn input 001 ON. Cursor to the timer
instruction in rung 1 and observe the AC value as it increments.
Refer to Figure 16.4 if you need help monitoring this timer data. As
you cursor to the timer instruction, pressing the NEXT key will
display the PR value. Pressing NEXT again will display the AC
value.
2. While in the Run mode, change the PR value of RTO 901 to 0100 If
you need help changing this PR value, refer to Figure 16.4.
3. The reset instruction should be changed to make the RAC value
equal to 10 instead of 0. Refer to Figure 16.4 if you need help
changing the RAC value.
4. Enter the Run mode and turn input 001 ON. Cursor to the RTO
instruction and monitor the AC value as it increments. Next, cursor
to the Examine On instruction at address 001 in that rung. Force
input 001 to an OFF condition. If you need help implementing the
FRC OFF condition, refer to Figure 16.3.
When you have forced input 001 OFF, cursor to the RTO instruction
and monitor the AC value. Verify that turning input 001 OFF and
ON has no effect on the rung conditions. Remove the FRC OFF
condition and verify that the rung will now function normally.
5. Cursor to the Examine ON instruction at address 003 in rung 5.
Force input 003 to an ON condition. If you need help implementing
the FRC ON function, refer to Figure 16.3.
After you have forced input 003 ON, turn input device 003 ON and
OFF and verify that the reset instruction remains TRUE even
though the condition instruction that will enable the reset
instruction is FALSE.
Cursor to rung 1 and try to enable the RTO instruction by turning
input 001 ON. Verify that the timer AC value is reset to the RAC
value and will not increment even though the rung conditions are
TRUE.
Remove all forces in this program before you move on to the next
exercise.
6.
Q- Unit
Key Terms and
Concepts
Question Group 17A
Answers in Unit 18
Using the EEPROM
Memory Module
You should become thoroughly familiar with the following terms and
concepts, Re-read the referenced pages if necessary.
EEPROM 17-1 Load (Read) 17-3
Non-volatile 17-1 Auto-Load 17-4
Store (Save) 17-2 Editing EEPROM Programs 17-5
SYMBOLOGY
MODE
E
6
F
7
ENTER
1. The EEPROM memory module uses the same battery the processor
uses to retain memory contents True or false?
2. The EEPROM memory module has a memory capacity of 1200
words, so both SLC 100 and SLC 150 programs can be duplicated in
the EEPROM module. True or false?
3. Before the EEPROM can be inserted into the processor module, AC
line power to the processor must be removed. This helps to guard
against possible damage to the EEPROM or unwanted CPU faults.
True or false?
4. The EEPROM module must be used in conjunction with the pocket
programmer or SLC computer software in order to load programs
into the processor RAM. True or false?
5. The EEPROM is housed in a small plastic case with a large white
write-on area to help you identify EEPROM contents. True or false?
6. To save or store the contents of the processor RAM in the EEPROM,
you must use mode 6 (Save). True or false
1 2 3 4 5 6 7 8 9
7. When you enter mode 6, prompti ng messages that appear on the
pocket programmer display will guide you through the saving
process. True or false?
8. In order to avoid accidental memory loss, the programmer will
prompt you with the message SurE ? when you enter mode 6. True
or false?
9 If a program is in the EEPROM module and you want to load a now
program, you must erase the old program in the EEPROM module
by entering mode 10 True or false?
10 If you clear memory (mode 1), and then enter mode 6 and go through
the saving process, the contents of the empty RAM will be duplicated
in the EEPROM module, leaving the EEPROM blank True or false?
11 The programmable EEPROM auto load instruction (864) can be
used with the SLC 100 or SLC 150. True or false
9
17-2
Q-E Unit Using the EE PROM Memory Module
Question Group 17A 12. The programmable EE PROM auto-load instruction can be used to
clear a memory error and reload your user program into the
processor RAM memory. True or false?
(continued)
Answers in Unit 18
13. If you want to load the contents of the EEPROM into the processor
RAM you could enter mode 7 (Read). True or false?
14. When the EEPROM contents are loaded to RAM memory, a program
already in the processor RAM will be automatically erased. True or
false?
15. When you enter mode 7. prompting messages on the pocket
programmer will guide you through the copying process. True or
false?
16. The auto-load procedure is a time saving convenience in applications
where the same program is to be used in a number of processors or
when quick program change-overs are necessary True or false?
17. The program in the processor RAM will be er ased when you follow
the auto-load procedure. True or false
7
18. The auto-load procedure is disabled if an access code is stored in the
EEPROM. True or false?
19. The EEPROM modules are interchangeable with SLC 100 and SEC
150 programmable controllers. True or false?
20. SLC 100 programs can be easily run on the SLC 150 programmable
controller. True or false?
21. All SLC 150 programs are compatible with SLC 100 controllers.
True or false?
Unit
Q-E Unit 2
Q-E Unit 3
Answers
Group 2A:
1. False. 2. False. 3. True. 4. (d). 5. (d).
6. True. 7. True. 8 True. 9 False. 10. True.
11. True. 12. True. 13. True. 14. True. 15. True.
16. True. 17. True. 18. False. 19. False. 20. True.
21. True. 22. True. 23. True. 24. True. 25. True.
26 True
27. False. A mounting plate is not needed for the
EEPROM module. The EEPROM needs no battery.
28. True 29. True. 30. True 31. True. 32. True.
33 True 34. False. 35. False
Matching Exercise:
1. I. 2. G. 3 C 4. B 5. F.
6. H. 7. D. 8. E. 9. A.
Group 3A:________________________________________
1. (a). 2. (b).
3. False. Status bits will be ON or OFF, telling you whether the
instruction is TRUE or FALSE.
4. False.
5. (c).
6 False. Addresses 701 thru 867 are for internal relay-type
instructions.
7
7. (b). 8. (b) 9. False. 10 True. 11. True.
12. Program initialization. 13. False 14. True 15. True.
18-2
Unit Answers
Q-EUnit3 Group 3B:___________________________________________
(continued)
1. False. Instructions are classified as conditional and output
instructions.
2. False. Branching instructions are classified as conditional.
3. (c). 4. True. 5. True. 6. (c). 7. True.
3. True. 9. (b). 10. (e) 11. True. 12. (A)
13. True
Group 3C:_____________________________________________
I. 003. 2. Conditional. 3. Examine ON. 4. TRUE.
5. ON. 6. Oil. 7. Output. 8. Output Energize.
9 A continuous path of TRUE condition instructions must exist. In
this case, instructions 003 and 733 must be TRUE.
10. ON.
II. False External I/O terminals have address numbers from 001 to
016, 101 to 116, 201 to216,and 301 to316.
12. Examine OFF. 13. OFF.
14. False. When the rung is TRUE, Examine ON instruction 003 is
TRUE and its status bit is ON ; Examine OFF instruction 733 is
TRUE and its status bit is OFF ; Output Energize instruction 011 is
TRUE and its status bit is ON.
15. False. If the closed position of the switch is to energize coil M, the
switch must be represented by an Examine ON instruction. This is
true whether the switch is N O or N.C
16. Address 103 for LSI. Address 111 for coil M.
Unit Answers
18-3
Q-E Unit 3 Group 3D:_________________________________________________
(continued)
1. I/O scan.
2. l^rogram scan.
3. False. Output contact will go ON or OFF during I/O scan.
4. a) False. The time period is variable, as explained in d) and e).
b) False. Time period can be longer than one cycle, as explained in
d).
c) False. After the input terminal goes ON (any point in the
operating cycle), its corresponding status bit will not be set ON until
the next I/O scan, no matter where the rung is located in the program.
Similarly, the output terminal will not be set ON until the following
I/O scan, no matter where the rung is located in the. program.
d) True. If the input terminal goes ON early in the program scan, it
will take longer to reach the next I/O scan than if the input terminal
went ON late in the program scan.
Shortest time period: The input terminal goes ON just at the
beginning of the I/O scan. The output terminal goes ON one
operating cycle later
Longest time period: The input terminal goes ON just at the
beginning of the program scan The status bit of instruction 001
does not go ON until the I/O scan is reached, one operating cycle
later. The output terminal does not go ON until a second operating
cycle has passed.
Note: We are neglecting I/O scan length here, since it is very short
compared to the total operating cycle length.
e) True. Obviously, the more instructions in the program, the
longer the program scan This means that after the input terminal
goes ON, it takes longer to get to the I/O scan (when the status bit of
instruction 001 goes ON), and it takes longer to get to the next I/O
scan (when the output terminal goes ON).
Program content also has an effect on program scan length, since
some instructions take a longer time to execute than others.
18
Answers
18-4
Unit
Q-EUnit3 Group 3K:
(continued)
Address Blocks
Used
Address Blocks
Total [
Used l
Input Addresses
1 - 10
201 - 210
_ -
501 - 508
101 - no
_ - _ _ -
H
- 16
111 - M6
311 - 316
4M - 416
Output Addresses
Unit
Q-E Unit 4
Answers
18-5
Group 4 A:____________________________________________
1. False. The pocket programmer can also be used for monitoring your
program and troubleshooting.
2. True. 3. True. 4. True.
5. (c). 6. True. 7. (d).
8. False. There is a table fixed to the back of the pocket programmer
with a description of the error codes.
9. (d).
10. False. The processor will function in all modes of operation.
11. True.
12. False. If you enter mode 9, the programmer will initiate a diagnostic
test.
13. True. 14. True. 15. (d). 16. True. 17. True.
Group 4B;____________________________________________
1. False. The SLC 100 controller power supply will convert your
incoming line power to the 5 VDC required.
2. False. The pocket programmer receives power from the processor
unit by means of the interconnect cable.
3. True. 4. True. 5 True.
6. False. Connect the green wire to the terminal marked CHASSIS
GRD
7. True. 8 SurE? 9. True 10. True. 11. True.
12. False Only one output instruction per rung
13. True. 14. True. 15. True. 16. True
17. True 18 True. 19. True
18-6
Unit Answers
Q-EUnit4 Group 4C:_____________________________
(continued)
1. (a). 2. True. 3. True. 4. No.
6. True. 7 The Output Energize TED.
8. The Examine OFF LED and the ON LED.
9. The Examine OFF instruction is TRUE.
Group 4D:________________________
27-5 ZCL, Programming error.
27-2 Zero cross turn on failure
27-1 HS1 module problem
5. Yes.
r
Q-E Unit 5 Group 5A:________________________________________________
1. (0.
2. False. Relay type instructions are used internally also.
3. True. 4. True. 5. True. 6. True.
7. True. 8. True. 9. True. 10. False.
Group 5B:____________________________________________
1. True.
2. False. A continuous path of TRUE condition instructions does not
exist. Input 001 OR inputs 002 and. 003 must be ON for output 015
to be energized.
3. True. 4. True 5. True.
6 False. Continuous path of TRUE instructions does exist.
18
Answers Unit
18- 7
Q-EUnit5 Group 5C:
(continued)
1 (c). The keystroke sequence is as follows:
T
HP
1
HP
2
i------i

T
HP
3
HP
2
T
HP
4 T
-< >-
1 5
ENTER
Groiup 51):
1. True. 2. True 3. Fais. 4. True. 5. True. 6. True.
Q-E Unit 6 Group 6A:_______________________________________________
1 True. 2. True. 3. False. Timers count 0.1 second intervals.
4. True. 5. True. 6 True 7. True.
8. False. The time delay is actually the PR value minus the RAC
value.
9. (d). 500x0.1 = 50 seconds.
10. False PR values can easily be changed in the Run or Program
mode.
11. False.
12. False AC values can be changed as easily as PR values.
13 True.
14. False. The address assignments from 951 to 982 are reserved for
overflow status bits.
15. True. 16. True. 17. True. 18 True
18
Answers
18-8
Unit
Q-EUnit6 Group 6B:__________________________________________________
(continued)
1. (b). The status bit does not go ON until the AC value reaches the PR
value.
2 (a). 3. False. 4. (c). 5. (c). 6. (b).
7. (b). 8. id). 925 + 50 = 975
9. (d). The Exami ne ON instruction at address 951 examines the
overflow status bit of timer 901 for an ON condition.
10. (a). 11. (d).
Group 6C:_____________________________________________
1. True.
2. False. RTF timers start timing when their rung conditions change
from TRUE to FALSE.
3. (b).
4. False. Rung 4 will be TRUE when the AC value exceeds 9999.
5. (a). 6. True. 7. (d). RTF timer status is retentive
8. (c). 9. (c). 10. (d). 11. False.
12. True. Status bit 901 will be OFF when the AC value reaches 300.
13. (e). 14. True.
Group 6D:___________________________________________
1. (cl. RTO 901 overflows from 999.9 to 1,000. RTO 902 times to an
AC value of 850.0. (1000 + 850 =1850 seconds.)
2. (d). Rungs 1 and 2 (or input-| [-001) must be TRUE for 1,850
seconds before output 011 will be energized. After l ,850 seconds,
output Oil will remain ON even if rungs 1 and 2 go FALSE. The
only way to turn output 011 OFF is to reset.
3. (e). 4. (b)
5 False Timing starts when rung conditions are TRUE.
Unit
Q-E Unit 7
Answers
18-9
Group 7A:
1. False. 2. True. 3. True.
4. False. AC value will increment when the rung makes the next
transition to TRUE.
5. False. 6. True. 7. True. 8. True. 9. (a).
10. (b). 11. (b). 12. (b). 13. True. 14. True
15. False. When the reset instruction is TRUE, the AC value is reset to
the RAC value.
16. True.
17. False. Counter parameters can also be changed in the Run mode.
18. True.
Group 7B:_____________________________________________
1. True. The address range for counters is from 901 thru 932.
2. (d). 928 + 50 = 978 3. (b). 4. (a).
5. (b). Counter instructions are retentive.
6 (c). The counter is inactive while the reset instruction is TRUE.
7 True. An up-counter could be programmed to keep track of all parts
made, and a down-counter could be programmed at the same address
to subtract the bad parts from the total count.
18-10
Unit Answers
Q-EUnit7 Group 7C:_________________________________________________
(continued)
I. (a). 2. (b). 3. (e). 4 (d). 5. (d).
6. (c). 7. (c).
8. (c). CTU has incremented 5 times but CTO has decremented 5
times, leaving the AC value at 0000.
9. (c).
10. True. Counters have the same address, therefore the same AC
value.
II. True.
Group 71):____________________________________________
1. True. 2. (c).
3. (c). Both of these conditions must be mol. Counter 902 will not Start
counting until counter 901 has overflowed. When 901 overflows, the
Examine instruction in rung 3 will reset counter 901 and it must
reach the preset value again before the status bit is set ON again.
4. (d). 5. True. 6. (b).
Q-EUnit8 Group 8A:_________________________________________________
1. True.
2. False. You should select a time increment of 20, 40, or 80
milliseconds.
3. False Although this method will work, adding the timing rungs to
your program is faster and more accurate.
4. True.
5. False You can always use address 869, since it is associated with
your scan rate.
6 True 7. True. 8. True 9. False 10. False 11. True
12. False.
Group 8B:
1 True. 2. (c). 3. (c).
Unit Answers
18-11
Q-E Unit 9 Group 9A:________________________________________________
1. True. 2. True. 3. True. 4. True.
5. False. When the MCR start rung is FALSE, all non retentive
outputs within the zone are de-energized
6. True.
7. False. A timer or counter functioning in an MCR zone with a
FALSE start rung will have its status, underflow, and overflow bits
held in their last state The AC value will stop incrementing, hut
that value will be retained.
8. True. 9 True
10. False An MCR instruction is assigned no address at all.
11. False The ON LED does not indicate when \ICR or ZCL
instructions are TRUE or FALSE.
Group 9B:_____________________________________________
1. True 2. True.
3. True. MCR start rung is now FALSE. All non-retentive outputs
within the zone are de-energized. Outputs 011 and 012 are de
energized even though the condition instructions for their rungs are
TRUE. These outputs arc being controlled by the MCR zone.
4. True. All three conditional instructions in the MCR start rung must
be TRUE for outputs in the zone to function normally.
5. True. 6. True.
Group 9C:_____________________________________________
1 False. 2. True. 3 False 4 True.
5. False. When the ZCL start rung is TRUE, all outputs within the
zone function normally.
6 True. 7 False. 8. True 9. True. 10. True. 11. True.
12. False A hard-wired Master Control Relay must be used.
13 True. 14. False
18-12
Unit Answers
Q-E Unit 9 Group 9D:________________________________________________
(continued)
1. True. The two zones may not overlap. Overlapping zones may cause
unexpected operation.
2. False
3. False. The ZCL zone allows you to select which rung conditions you
want to control output 012. If input 001 is ON, rung 3 controls
output 012. If input 001 is OFF, rung 6 controls output 012.
4. (b).
5 False. The program would operate differently with MCR
instructions. The lower MCR zone (rungs 5, 6, and 7) would always
control output 012. Also, under the MCR zone, any outputs which
were ON at the time the MCR took effect would be de-energized. In
a ZCL zone, these outputs would remain in their last state.
Q-E Unit 10 Group 10A:________________________________________________
1. False. Both instructions are retentive.
2. True. 3. 901 thru 932.
4. Sequencers can have up to 100 steps and they can be time-driven or
event-driven.
5. (b). 6. False. Time-driven sequencers count 0.1 second
intervals.
7. True.
8. False. Event-driven sequencers move to the next step when their
AC value matches their PR value.
9. True. 10. True. 11. True.
12. False. The SQI sequencer input-satisfied status bit has the same
address as the SQI sequencer instruction.
13. False. The cycle completion bit is assigned the sequencer address
plus 50.
Unit Answers
18-13
Q-E Unit 10 Group 10A:____________________________________________
(continued)
14. True. 15. True. 16. (d). 17 True. 18. True.
19. False. Sequencer data is retentive The sequencer will resume
operation from the point where it left off.
20. True. 21. True. 22. False 23. False
Group 10B:________________________________________
CLASSIFICATION:
-<SQIh
0 -<SQOh
0 TIME DRIVEN
ADDRESS: _901_ g ,r
VENT DR|VEN
GROUP NUMBER: _0
BIT ADDRESS DATA
PROGRAM
CODE
PRESET
VALUES
Bit Addresses -*
Mask Data -
B A
Data
3
Data
A
18 17 16 15 14 13 12 11
0 0 1 1 1 1 1 1 ) P
Step Data -+ 0 0 0 0 0 0 0 0 0 0 0
! !
5
!
0
i 0 0 1 0 0 0 0 0 2 0 i : 5 o
2 0 0 0 0 1 1 1 1 0 F 1 3 ; o 0
3 0 0 1 1 1 1 0 0 3 C
1
6
!
0
1
0
Group 10C:
1. Cb). Mask data is3F. Bit addresses Oil thru 016 arc controlled by
this sequencer.
2. (a). 3. True. 4. True. 5. (b). 6. (b).
7. (c). 8. (b),(d),and(e). 9. (bland(c).
10. True. 11. False.
12. False. The reset instruction will reset the sequencer to the
programmed RAC step value.
13. Bit address 703 will be ON for one program scan each time SQO
completes a step.
14. True. 15. True. 16. True.
18-14
Unit Answers
QE Unit 10 Group 101):________________________________________________
(continued)
1. True. 2. True. 3. (e). 4. (c).
Group 10E:____________________________________________
1. (c). Inputs 001 and 008 are not examined by this sequencer
2. (d). 3. (b). 4. (d). 5 True.
6. True. The input-satisfied status bit will not go ON' for that step.
7. True. 8. True.
9. (b). The preset value for step 4 is 2 and so two FALSE-to-TRUE
transitions of the rung must occur before the sequencer will advance
to the next step.
10. (d).
Q-EUnit11 Group 11A:
1 True. 2. True. 3. True. 4. True. 5. True. 6. 58.
7 True. 8. True 9. False 10. True. 11. True. 12. True
Group 1 IB:
1. True. 2 True. 3. False. 4. False. 5. False. 6 False.
Group 11C:
CLASSIFICATION: ADDRESS: _SSi. GROUP NUMBER: _
8IT ADDRESS DATA
PROGRAM
CODE
PRESET
VALUES
Bit Addresses-*
1

Mask Data -*
8 A
Data
8
Data
A
r F
Step Data -> 0 0 5
! ! o S
1 0 6
! l o i s
2 0 0 1 l o i s
3 0 1 ! 0 ! 5
4
0 2 ! 0 1 5
5 0 3 0 ! 5
6 0 4
0 ! 5
Unit
Q-E Unit 11
(continued)
Q-E Unit 12
Answers
18-15
Group IIP:___________________________________________
1. True. 2. Group number 62 and step number 5. 3. (d) 4. (a)
Group 11E:_________________________________________
Group 12A:______________________________________
1. (c). 2. (c). 3. (d). 4. (c).
5. (b). 6. <e). 7. (a). 8. (b).
Group 12B:______________________________________
1 True.
2 False. You should use the external outputs on the processor.
3. False. 4. Yes. 5. True.
6. True. Refer to the Maximum Pulse Rate table on page 12-2.
7. True.
18-16
Unit Answers
Q-E Unit 12 Group 12C:
(continued)
CLASSIFICATION: ADDRESS: _901_ | EVENT^OrvEN OUP NUMBER: _L
BIT ADDRESS DATA
PROGRAM
CODE
PRESET
VALUES
Bit Addresses
Mask Data-
B A
Data
B
Dota
A 118 117 116 115 114 113 112 in
o <? 9 0 o o
1 1 0 3
Step Data 0
o 0 0 0 0 9 9 1
0 1
0 ! o ! 2 : 4
1
n n n 0 n n 1 0 0 2 9 ! 9 ! 9 ! 9
2
1 1 1
1 1 1
3
1 1
1 1 1
Type: HSISequencer
Use this form for your final answer:
nswer.
CLASSIFICATION:
-<SQI>-
0 -(SQO)-
AODRESS: 910
TIME DRIVEN
EVENT DRIVEN
GROUP NUMBER: 0
BIT ADDRESS DATA
PROGRAM
CODE
PRESET
VALUES
Bit Addresses->
Mask Data
B A
Data
B
Data
A 018 017 016 01S 014 013 012 on
0 0 0 0 0 0 0 0 0 0
Step Data 0
D. 0 0 0 0 0
9 Q
0 0
0 ; 0 \0 ;
l
1 1 1
1 1
2
1 1 1
1 1 1
3
i 1 1
1 r 1
Type: Single Shot Reset Sequencer
Unit
0-f Unit 13
Q-E Unit 14
Answers
18-17
Group 13A:
1. True. 2. False. 3. True. 4. (a). 5. (b).
6. True. 7. True. 8. True. 9. True. 10. (c).
Group 13B:
1. True. 2. True. 3. (d). 4. False. 5. False
Group 13C:
1. True. 2. True. 3. False.
Group 14A:
1. False. 2. False. 3. True.
7. True. 8. True. 9. True.
13. True 14. False (864)
4. True.
10. False.
5. True. 6. True.
11. True. 12. (d).
Group 14B:
1. True. Address 868 is the program initialization hit. This bit will be
ON during the first program scan for power-up
2. (d). 3. (d).
4. (c). RTO timer status is retentive, but the program initialization bit
is always ON for the first program scan on power-up. When this bit
is ON, the Examine ON instruction at address 868 in rung 3 will be
TRUE, enabling the reset instruction that resets the timer to 0.
5. (c). Since the AC value has not reached the PR value, status bit 901
has not been set ON. When input 001 is turned OFF, Examine OFF
instruction 001 in rung 3 will reset timer 901 to the RAC value.
6. Non-retentive
18-18
Unit Answers
Q-EUnit 14
(continued)
Group 14C:
1. (b).
2. (c). The counter status is retentive. However, the Examine ON
instruction at address 868 is the program initialization instruction,
which is TRUE for the first program scan and will reset the counters
automatically upon power-up.
3. (c). 4. (a). 5. (c) and (d).
6. (e). Even though the current AC value of 0002 does not indicate an
underflow condition, output 012 was turned ON when the AC value
undcrflowcd to 9999 (0002 minus 0003). Once set ON, overflow/
underflow bits can only be turned OPE with the reset instruction..
1. True. 2. True. 3. (a), (b), and (d).
4. True. 5. True. 6. True.
7. False. The cursor will move to the output instruction in the rung
directly above the last rung of your program.
8. True. 9. True. 10. True. 11. True. 12. True.
13. True. 14. True. 15. True. 16. True.
17. False. All conditional instructions must also be removed.
18. True.
19. False. Mode 1 has no effect on the EEPROM memory module.
20. True.
21. True. However sequencer presets can be changed in the Run. Test,
or Program modes.
Q-E Unit 15 Group 15A:
22. True. 23. True.
Unit Answers
18-19
Q-E Unit 15 Group 15A:_______________________________________________
(continued)
24. False. Cursor to the value you want to change, enter the new value
and press ENTER.
25. False. Changes are immediately entered into RAM memory.
Group 15B:___________________________________________
1. See diagram below.
Rung 7
18-20
Unit Answers
Q-E Unit 15 Group 15B:_______________
(continued)
2 and 3. See diagrams below.
Questi on 2:
Questi on 3:
Rung 7
Unit
Q-E Unit 15
(continued)
Answers
18-21
Group 15B:
4. Correct keystroke sequence for adding the branch: Cursor to
Examine ON instruction at address 001 in rung 1 and press
INSERT
T
INSERT
T
ENTER
ENTER NEXT NEXT NEXT
6. See diagram below.
C01 005 002
Rung 1
Rung 2
Rung 6
RACOCOO
Correct keystroke sequence for removing the rung in exercise 6: Cursor
to any instruction in rung 5 and press
ENTER
_______
REMOVE RUNG
The entire rung will be removed from memory.
18-22
Unit Answers
Q-E Unit 16 Group 16A:
1. True. Timer and counter parameters can be changed in the Run
mode.
2. True.
3. False. Sequencer data may only be changed in the Program mode.
Sequencer Preset values may be changed in the Run mode.
4. False. Data may also be monitored in the Test modes.
5. True. 6. True.
7. False. The status bit is not affected. Only the output terminal is
forced.
8. (e).
9. False. The FRC OFF function will force the instruction to an OFF
condition. To remove the FRC ON condition you must cursor to the
forced instruction and press REMOVE, SHIFT, FRC ON.
10. True. 11. True. 12. True.
13. True. To remove all forces in your program you must press
REMOVE, ENTER.
14. False. This will remove all forces in your program. To remove a
forced ON instruction, cursor to that instruction and press
REMOVE, SHIFT, FRC ON. To remove a forced OFF instruction,
cursor to that instruction and press REMOVE, SHIFT, FRC OFF.
15. True.
16. False. Pressing the NEXT key one more time will take you to the
next rung.
17. True.
18. False. Timer and counter PR and AC values can be changed in the
Run mode also.
19. True However you can switch to the Program mode and unprotect.
Unit
Q-E Unit 17
Answers
18-23
Group 17A:____________________________________________
1. False. The EEPROM requires no battery to retain memory
contents.
2. True. 3. True.
4. False. The Auto-load procedure can be used. See Page 16-3 of the
User's Manual for details.
5. True. 6. True. 7. True. 3 True.
9. False. The old program will be automatically erased when you load
a new program.
10 True. 11. False, only SLC 150 12. True. 13. True.
14. True. 15. True. 16 True.
17. True.
18. True
19. True.
20 True. However caution should be used when using addresses that
have unique functions with the SLC 150.
21 False. SLC 150 special instruction addresses and HSI counter
instructions are not compatible with the SLC 100.
(Sh ALLEN-BRADLEY
T:t!UT A ROCKWELL INTERNATIONAL COMPANY
Industrial Control Group
Milwaukee. Wisconsin 53204
Publication 1745-800A - March, 1988